38XTZ 007-024
40ABZ 007, 008, 016, 020 and 024
40ALZ 011 and 014
Split system air-cooled air
conditioners
Carier is participating in
the Eurovent Certification
Programme. Products are
as listed in the Eurovent
Directory of Certified
Products.
40ABZ/ALZ
38XTZ 007 and 008
38XTZ 016 and 024
Installation, Operation and Maintenance Instructions
CONTENTS
START-UP CHECK LIST ................................................................................................................................................................3
PHYSICAL DATA ............................................................................................................................................................................4
ELECTRICAL DATA (3 PHASE, 50 HZ) ...................................................................................................................................... 4
Standard refrigerant line diameters (inches) .......................................................................................................................................4
DIMENSIONS, mm ........................................................................................................................................................................... 5
Service clearance, mm ......................................................................................................................................................................11
Centre of gravity coordinates (mm - approx.) .................................................................................................................................. 12
Weight distribution (kg - approx.) ....................................................................................................................................................13
FAN CURVES (STANDARD) ...................................................................................................................................................... 14
Unit transport, lifting and handling .................................................................................................................................................. 22
UNIT INSTALLATION ................................................................................................................................................................. 22
Repositioning unit air discharge ....................................................................................................................................................... 26
MASTER LINK I ELECTRONIC CONTROL ............................................................................................................................. 29
REFRIGERANT LINE CONNECTIONS ..................................................................................................................................... 31
Connection between units ................................................................................................................................................................. 31
UNIT COMPONENTS ................................................................................................................................................................... 35
Description of unit protection devices ..............................................................................................................................................35
GENERAL MAINTENANCE ....................................................................................................................................................... 36
FINAL RECOMMENDATIONS ................................................................................................................................................... 39
Site address: .......................................................................................................................................................................................................................................
Equipment type and serial No: 38XTZ ...........................................................................................................................................................................................
..............................................................kPaPressure drop (air): ............................................................. kPa
....................................................... PaDischarge air pressure: ...................................................... Pa
Fan motor input:Ph. 1:
Ph. 2:
Ph. 3:
........................................... VoltsFan motor input:Ph. 1: ..........................................Volts
Refrigerant-air heat exchanger (condenser)Copper tubes, aluminium fins
Face aream
Number of rows2333233
FanPropeller
Quantity2212222
Nominal air flowl/s1805163925004445500062396389
Indoor unit 40ABZ/ALZ***007008011***014***016020024
Weightkg135140160236290305325
Refrigerant-air heat exchanger (evaporator)Copper tubes, aluminium fins
Face aream
Number of rows ... fins/m4...3944...3944...4723...3944...3945...4725...551
FanTwo, double-inlet centrifugal
Nominal air flowl/s1416158317772694272229723250
Air filterWashable
Quantity1122333
Width x heightmm612 x 600612 x 600612 x 600740 x 700632 x 615632 x 615632 x 780
*Based on an outdoor air temperature of 35°C db and an indoor air entering temperature of 19°C wb and 27°C db.
** The refrigerant charge is for the complete system (38XTZ and 40ABZ or 40ALZ), but excludes the refrigerant connection lines.
*** Sizes 011 and 014 are 40ALZ models.
Nominal power input*kW8.78.79.529.5212.6612.6617.0117.0119.7019.7026.8226.8233.3033.30
Nominal current drawn*A22.815.625.016.933.222.044.629.051.735.870.446.587.456.0
Maximum power input**kW 9.59.510.610.614.014.018.418.421.821.829.329.334.734.7
Maximum current drawn** A24.917.027.818.536.723.748.331.157.238.676.951.091.158.0
*Based on an outdoor air temperature of 35°C db and an indoor air entering temperature of 19°C wb and 27°C db.
** Based on an outdoor air temperature of 40°C db for sizes 007, 011, 014, 020 and 024 and 44°C db for sizes 008 and 016.
*** 40ALZ models.
Note: The power input of the optional/accessory electric resistance heaters (that can be installed in the unit) is not included.
Table 3 - Operating limits
ZoneAir temperature °C
Dry bulbWet bulb
Indoor
Maximum+35+21
Minimum+19+14
Outdoor
Maximum+40/44*Minimum19**-
Indoor air flow
Maximum+20% of nominal value
Minimum-20% of nominal value
Hot water coil (accessory/option)
Maximum water temperature80°C
*Sizes 007, 011, 014, 020 and 024: 40°C
Sizes 008 and 016: 44°C
** With optional/accessory head pressure control, the unit will operate at
temperatures below 19°C.
Table 4 - Standard refrigerant line diameters (inches)
Air flow: 1416 l/sAir flow: 1416 l/s
Static pressure: 105 PaStatic pressure: 126 Pa
Dry coil
Motor pulley control
(Standard drive)
Power input, kW
14
Air flow
Standard motor pulley drive
1- Closed4- 3 turns open
2- 1 turn open5- 4 turns open
3- 2 turns open6- 4.5 turns open
40ABZ 008
Fig. 11 - Fan curves (standard)
Motor pulley control
(Standard drive)
Dry coil 15.66 r/s
Wet coil 15.66 r/s
Power input
Power input, kW
Available static pressure
Available static pressure
Standard drive data
Motor: 1,104 kW
Pulleys: - Motor: Ø 100; Shaft Ø 24
-Fan: Ø 125; Shaft Ø 20
Standard motor pulley opening: 3.5 turns open
Motor pulley control
(Standard drive)
Air flow
Nominal air flow
Wet coilDry coil
Air flow: 1583 l/sAir flow: 1583 l/s
Static pressure: 105 PaStatic pressure: 125 Pa
Dry coil
Power input, kW
Air flow
Standard motor pulley drive
1- Closed4- 3 turns open
2- 1 turn open5- 4 turns open
3- 2 turns open6- 4.5 turns open
15
40ALZ 011
Fig. 12 - Fan curves (standard)
Motor pulley control
(Standard drive)
Power input
Available static pressure
Motor: 1,472 kW
Pulleys: - Motor: Ø 125; Shaft Ø 24
Standard motor pulley opening: 4 turns open
Standard drive data
-Fan: Ø 150; Shaft Ø 20
Air flow
Wet coilDry coil
Air flow: 1777 l/sAir flow: 1777 l/s
Static pressure: 115 PaStatic pressure: 148 Pa
Dry coil
Motor pulley control
(Standard drive)
Dry coil 17.58 r/s
Wet coil 17.58 r/s
Nominal air flow
Power input, kW
16
Power input, kW
Available static pressure
Air flow
Standard motor pulley drive
1- Closed4- 3 turns open
2- 1 turn open5- 4 turns open
3- 2 turns open
40ALZ 014
Available static pressure
Dry coil 13.91 r/s
Wet coil 13.91 r/s
Fig. 13 - Fan curves (standard)
Motor pulley control
(Standard drive)
Power input
Power input, kW
Standard drive data
Motor: 2,208 kW
Pulleys: - Motor: Ø 100; Shaft Ø 28
-Fan: Ø 150; Shaft Ø 25
Standard motor pulley opening: 2 turns open
Motor pulley control
Air flow
Nominal air flow
Wet coilDry coil
Air flow: 2894 l/sAir flow: 2694 l/s
Static pressure: 115 PaStatic pressure: 114 Pa
Dry coil
(Standard drive)
Power input, kW
Available static pressure
Air flow
Standard motor pulley drive
1- Closed4- 3 turns open
2- 1 turn open5- 4 turns open
3- 2 turns open
17
40ABZ 016
Wet coil 16.5 r/s
Fig. 14 - Fan curves (standard)
Motor pulley control
(Standard drive)
Dry coil 16.5 r/s
Power input
Available static pressure
Motor: 2,944 kW
Pulleys: - Motor: Ø 125; Shaft Ø 28
Standard motor pulley opening: 1.5 turns open
Standard drive data
-Fan: Ø 175; Shaft Ø 25
Power input, kW
Air flow
Nominal air flow
Wet coilDry coil
Air flow: 2722 l/sAir flow: 2722 l/s
Static pressure: 160 PaStatic pressure: 210 Pa
Dry coil
Motor pulley control
(Standard drive)
18
Power input, kW
Available static pressure
Air flow
Standard motor pulley drive
1- Closed4- 3 turns open
2- 1 turn open5- 4 turns open
3- 2 turns open6- 4.5 turns open
40ABZ 020
Fig. 15 - Fan curves (standard)
Motor pulley control
(Standard drive)
Available static pressure
Motor: 4,048 kW
Pulleys: - Motor: Ø 150; Shaft Ø 28
Standard motor pulley opening: 3.5 turns open
Dry coil 18.83 r/s
Standard drive data
-Fan: Ø 175; Shaft Ø 25
Power input
Wet coil 18.83 r/s
Power input, kW
Air flow
Nominal air flow
Wet coilDry coil
Air flow: 2972 l/sAir flow: 2972 l/s
Static pressure: 185 PaStatic pressure: 230 Pa
Available static pressure
Dry coil
Motor pulley control
(Standard drive)
Power input, kW
Air flow
Standard motor pulley drive
1- Closed4- 3 turns open
2- 1 turn open5- 4 turns open
3- 2 turns open6- 4.5 turns open
19
40ABZ 024
Available static pressure
Fig. 16 - Fan curves (standard)
Motor pulley control
(Standard drive)
Dry coil 19.5 r/s
Power input
Wet coil 19.5 r/s
Power input, kW
Available static pressure
Standard drive data
Motor: 4,048 kW
Pulleys: - Motor: Ø 150; Shaft Ø 28
-Fan: Ø 175; Shaft Ø 25
Standard motor pulley opening: 1.5 turns open
Motor pulley control
(Standard drive)
Air flow
Nominal air flow
Wet coilDry coil
Air flow: 3250 l/sAir flow: 3250 l/s
Static pressure: 230 Pa Static pressure: 290 Pa
Dry coil
Power input, kW
20
Air flow
Standard motor pulley drive
1- Closed4- 3 turns open
2- 1 turn open5- 4 turns open
3- 2 turns open6- 4.5 turns open
PRELIMINARY CHECKS
Check equipment received
Carry out an external check to ensure that the units have not
been damaged during transport.
If there are any signs of damage or oil, contact the shipping
company before installing the units. Send the claim documents
directly to the shipping company, stating clearly what has been
damaged. Carrier is not responsible for damage sustained
during shipment, handling and storage.
Check the contents correspond to those listed on the delivery
note. Inform your nearest Carrier office if anything is missing.
To prevent loss or damage, do not remove the original
packaging until the unit has reached the final installation site,
where the installation must be carried out by qualified
personnel.
ATTENTION: Ensure that the unit power supply complies
with the power supply at the installation site.
SAFETY CONSIDERATIONS
Installation and servicing of air conditioning equipment can be
hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install,
start-up or service air conditioning equipment. Untrained
personnel can perform the basic maintenance functions of
cleaning and replacing filters.
-Before performing service or maintenance operations on
the unit, turn off the main power switch to the outdoor
unit 38XTZ. Electrical shock could cause personal injury.
-During unit operation, some of the refrigerant circuit
elements could reach a temperature in excess of 90oC so
only trained or qualified personnel should access areas
protected by access panels.
-The 40ABZ/ALZ units are designed for ducted installation (indoor air discharge). If ducts are not used the
installer must place a protection grille in the discharge.
-Moving, lifting, transporting and positioning the units
must be done with all outside panels installed.
-Move and position the units with care.
-Do not start up the units until all electrical and
refrigerant connections have been made and the system
has been charged with the necessary oil and refrigerant
quantity.
-Ensure that the equipment used to move the units is
appropriate for the unit weight.
-The location or base on which the 38XTZ outdoor units
are installed must be able to support the operating
weight of these units.
The system used to fix or support the 40ABZ/ALZ
indoor units must also be able to support their weight.
-The units are supplied with a dry nitrogen holding
charge which must be removed before making the
refrigerant line connections and charging the units.
-The 38XTZ and 40ABZ/ALZ units should not be
installed in an explosive atmosphere.
-The unit can operate in normal radioelectric atmospheres
in residential, commercial and light industrial
installations.
All other operations should be performed by trained service
personnel.
When working on air conditioning equipment, observe
precautions in the literature, tags and labels attached to the unit
and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves.
Use a quenching cloth for unbrazing operations.
When handling or charging refrigerant, evacuating the
refrigerant circuit, carrying out leak test, etc., ensure that
adequate precautions are taken.
ATTENTION - VERY IMPORTANT
-To prevent electrical shock or equipment damage, make
sure disconnects are open before electrical connections
are made. If this action is not taken, personal injury may
occur.
For other applications check the electromagnetic
radiation around the units. The units are tested in
accordance with applicable standards on electromagnetic
compatibility.
-DO NOT CONNECT R-22 UNITS TO UNITS FOR R407C, E.G. DO NOT CONNECT A 38XT OUTDOOR
UNIT WITH A 40ABZ/ALZ INDOOR UNIT OR A
38XTZ WITH A 40AB/AL.
21
UNIT TRANSPORT, LIFTING AND HANDLING
-Ensure the lifting and transport equipment used is able to
support the unit weight (see Table 1).
-When rigging, use spreaders to prevent damage to the
panels (see Figs. 17, 18 and 19).
40ABZ/ALZ models
-Insert protective material between the lifting cables and
the casing.
38XTZ 011 to 024
Base
See detail
Spreaders
Rigging hook
Protective
material
Spreaders
Fig. 17
38XTZ 007 and 008
-Insert protective material between the lifting cables and
the casing.
Protective
material
Base
Fig. 19
-38XTZ 011 to 024 units have four 17 mm ø holes in all
four corners of the base, where the rigging hooks for the
lifting slings can be inserted (see Figs. 2 to 4).
ATTENTION
-To prevent transport damage, do not unpack the units
until they have reached their final location.
-Never roll or tip the unit more than 5o.
-Do not remove the plastic packing material from the
38XTZ units until they have reached their final location.
This protects the units from dust in the atmosphere.
-The 40ABZ/ALZ units must also be protected by plastic
packing material until they reach their final location.
IMPORTANT: Make sure that all unit panels are fixed in
place before moving. Raise and set down the unit carefully.
UNIT INSTALLATION
38XTZ outdoor units
22
Spreaders
Clearance between units, walls and other objects
These units have been designed for outdoor installation.
IMPORTANT: It is not possible to connect outdoor supply
and return air ducts to the 38XTZ outdoor units.
-The surface on which the units are mounted must be able
to support the unit weight (See Table 1 - Physical Data).
-Leave sufficient clearance around the unit for service and
maintenance (see Fig. 7).
Fig. 18
-Select a location free of dust or foreign matter which may
cause coil clogging.
-Leave sufficient clearance for free air circulation (outdoor
supply and return air).
-For minimum clearances between the units and walls or
roofs, see Fig. 20:
Table 6 - Minimum clearances (mm)
ABCD (*)
5005001000Free (*)
(*) Leave a minimum of 1 m clearance around the unit.
38XTZ 014
38XTZ 007 and 008
Return air
PLAN VIEW
ROOF
Supply
air
FLOOR
RIGHT SIDE VIEW
Supply
air
WALL
Return air
Return air
Supply air
PLAN VIEW
Supply
air
FLOOR
RIGHT SIDE VIEW
WALL
Return air
Fig. 20
Table 5 - Minimum clearances (mm)
ABCDEF (*)
20020050020020005000 (*)
(*) Leave a minimum of 1 m clearance around the unit.
38XTZ 011, 016, 020 and 024
Return air
PLAN VIEW
ROOF
Supply air
Control
FLOOR
box
Access
panel
FRONT VIEW
Return
air
WALL
Fig. 22
Table 7 - Minimum clearances (mm)
ABCD (*)
5001000500Free (*)
(*) Leave a minimum of 1 m clearance around the unit.
-If several units are installed close to each other in the same
area, ensure the minimum clearance between them to
allow free air flow.
38XTZ 007 and 008
Return air
Return air
FLOOR
FRONT VIEW
Return air
Return air
PLAN VIEW
ROOF
Supply air
Control box
Access panel
Fig. 21
Return air
WALL
Return air
Return
air
Supply air
Supply air
PLAN VIEW
VISTA EN PLANTA
Return air
NO
Return air
Fig. 23
Supply air
Supply air
Return air
Return air
Return air
Return air
OK
23
-The clearance between the units must be sufficient to
ensure that the discharge air from one unit does not mix
with the supply air of another unit.
38XTZ 014
Installation on the ground
-38XTZ units can be positioned on the floor of a patio, on
the ground or on a lawn. If installed on the ground or on
the lawn they should be mounted on a 100 mm high
concrete base that is 100 mm larger than the base unit on
all four sides.
Return air
Return air
PLAN VIEW
Fig. 24
-If the air enters through the units on one side only and is
discharged through the top, the clearances can be reduced.
38XTZ 011, 016, 020 and 024
Return air
Return
air
Return air
38XTZ 007 and 008
Concrete base
Fig. 26
38XTZ 011 to 024
Return
air
Return air
Return
air
Return air
PLAN VIEW
Fig. 25
-The air enters through three sides and is discharged
through the top.
Table 8 - Minimum clearances between units (mm)
38XTZABC
007 and 008200500400
014500700500
011, 016, 020 and 024500700500
Concrete base
Fig. 27
-If this type of installation is used, ensure that the units are
not affected by flooding, snow accumulation or leaves.
-Ensure that the units are secured to prevent injuries to
people handling or working on the units.
IMPORTANT: Rainwater is drained through the unit base.
For this reason the units must be elevated above the concrete
base to allow correct drainage.
-Rainwater drainage
38XTZ units incorporate drillholes in the base in order to
correctly drain any condensate or rainwater which may
enter the unit in the fan area. Ensure correct drainage.
24
-It is recommended to use flexible connections which
absorb vibrations, prevent noise inside the ductwork and
allow access to the unit.
Base
Vibration isolators
Fig. 28
-38XTZ 007 and 008 units incorporate two feet in the base
(See Fig. 1 - unit base), with two holes to fix the unit to
the floor (see Figs. 8 and 9, Centre of gravity and Weight
distribution).
Models 38XTZ 011 to 024 incorporate fixing holes in the
base profile to attach the units to the floor (See Figs. 2, 3
and 4 and Figs. 8 and 9, Centre of gravity and Weight
distribution).
-38XTZ 011 to 024 can have several types of vibration
isolator, as shown below:
Unit
Hexagonal nut
Washer
When selecting the installation site, observe the following
points:
-Ensure that the condensate water collected in the drain pan
is correctly evacuated.
-Leave sufficient clearance for installation and maintenance
(see Fig. 7 - Service clearances).
-If the units are not ducted, ensure that the return air is
sufficient for the required air flow.
-See Table 1, Physical Data, for unit weights and ensure
that the installation surface can support the unit weight.
-In accordance with applicable standards and laws the unit
can be suspended from the ceiling or floor-mounted (see
Fig. 30).
ROOF
TECHO
Supply
air
IMP.
AIRE
Vibration isolators
Supply
air
IMP.
AIRE
Flexible mounting
Base
Unit
Flexible mounting
PNL 40 x 40 x 4
Washer
Spring washer
Hexagonal nut
PNU 80 x 45 x 6
Concrete base
100 mm
Fig. 29
IMPORTANT: Units must be installed in accordance with
applicable local, national and European installation and
safety standards and regulations.
40ABZ/ALZ indoor units
These units have been designed for indoor installation, connected
to supply and return air ducts.
Vibration isolators
TECHO
ROOF
Fig. 30
The units leave the factory with the air discharge set to
horizontal. It can be changed to vertical discharge by following
the steps below:
-Change from horizontal (standard) to vertical discharge
with changing the position of the motor. See Figs. 31 and
32, depending on model.
a)Detach the side access panels .
b)Remove the drive belt(s) .
c)Unscrew the fans from the brackets securing them to
the base.
d)Detach the rear panel with the fan outlets and the top
panel .
e)For units 40ABZ 007, 008, 40ALZ 011, 014 change the
motor to the other fan.
f)For units 40ABZ 016, 020, 024 detach the drive base
together with the motor and reposition it on the
opposite side.
g)Remove the fan pulley and reposition it on the other
side.
25
h)Interchange the position of panels and , fastening
them correctly to the unit.
i)Bolt the U-bracket to each fan.
j)Bolt the U-bracket to the angle iron holding the fans
to the base.
k)Replace the drive belt(s) and ensure that the tension is
correct.
l)Replace the access panels .
Repositioning unit air discharge
40ABZ 007, 008/40ALZ 011, 014
Return
air
Return
air
Supply air
Supply
air
Condensate drainage
40ABZ o 40ALZ units are supplied with a condensate drain
pan with two drain pipes (outside diameter 23 mm). These
tubes leave the factory separately wrapped so it is easy to check
them.
The connection to the drain pipe can be vertical (see Fig. 33) or
horizontal (see Fig. 34).
•Vertical drain: Remove the prepunched knockout(s) in the
unit base.
•Horizontal drain: Drainage through holes in the side of the
unit base, to the right- or left-hand side.
Drain pipe
23 mm OD
Hole in unit base
Return
air
Supply
air
Return
air
Legend
1 Side access panel5 U-bracket
2 Rear discharge panel6 Drive belt(s)
3 Top panel7 Roof panel
4 Angle iron to attach fan to base8 Fan pulley
Fig. 31
Repositioning unit air discharge
40ABZ 016, 020, 024
Return
air
Return
air
Supply air
Supply
air
Supply
air
Return
air
Interior
drain pan
Unit base
Field-supplied trap
Drain pipe
23 mm OD
Interior
drain pan
Unit base
Field-supplied trap
75 mm
100 mm
Fig. 33 - Vertical drain
Salida panel
Outlet panel, unit side
lat. unidad
75 mm
100 mm
Return
air
Supply
air
Legend
1 Side access panel
2 Rear discharge panel6 Drive belt(s)
3 Top panel7 Roof panel
4 Angle iron to attach fan to base8 Fan pulley
5 U-bracket9 Base with motor
Return
air
Supply
air
Fig. 32
26
Return
air
Fig. 34 - Horizontal drain
The field-installed trap must be below the drain pan.
The drain pipe must never be higher than the drain pan.
Return
air
Supply
air
NO
YES
Fig. 35
Ductwork
The ductwork dimensions should be determined in accordance
with the air flow to be carried, and the available static pressure
of the unit. The different air flows and power input values for
each unit are shown in the fan performance curves.
When indoor pressure and air flow requirements differ from
nominal ratings, the motor pulley can be adjusted for different
available static pressure values :
1.Move the motor along its track in order to remove the belt
(ver Fig. 37).
2.Loosen the pulley setscrews and rotate as necessary.
3.Tighten the setscrews .
4.Replace the belt(s) in the channel of the pulley.
5.Tighten the belt(s), using the tension screw nut and washer
(see Fig. 38).
6.Check the new fan speeds with a tachometer.
7.After the first operating hours, check the belt tension and
if necessary retighten the belts (see Fig. 38).
Setscrews
Motor support
It is recommended to observe the following considerations:
a)Whatever type of ductwork is used, it should not be made
of materials which are flammable, or which give off toxic
gases in the event of a fire. The internal surfaces should be
smooth, and not contaminate the air which passes through.
b)At the points where the ducts join the unit, it is
recommended to use flexible connections which absorb
vibrations, prevent noise inside the ductwork and allow
access to the unit (see Fig. 36).
c)Bends near the unit outlet should be avoided as much as
possible. If unavoidable, they should be as slight as
possible, and internal deflectors should be used when the
duct has large dimensions.
d)The installation of baffles in the supply air outlet ducts
significantly dampens the noise created by the air flow.
e)The ratio between the duct sides should not exceed 1:3
(rectangular ducts).
Flexible joint
Supply air
Return air
Motor pulley
Motor
Belt
Tensioning screw
Fig. 37
Align the pulleys using a ruler.
1 Fixed flange
2 Setscrews
3 Movable flange
4 Straight-edge must be parallel with belt
5 Motor and fan shafts must be parallel
6 Pulleys
7 Motor and fan shafts must be parallel
Unit
Fig. 36 - Side view
f)Adjust the belts and pulleys to obtain air flows and static
pressures that differ from the nominal values, if required.
The units are factory-set to supply nominal air flow and
nominal static pressure, as shown in Figs. 10 to 16.
Fig. 38
To align fan and motor pulleys:
1.Loosen fan pulley setscrews. Slide fan pulley along the
pulley shaft and align with the motor using a ruler, making
sure that it is parallel to the belt.
2.Tighten the fan pulley setscrews.
To adjust the belt tension, loosen the motor mounting plate
bolts and slide the motor mounting plate until the belt is
tight.
27
3.Belt tension (see Fig. 39)
The minimum belt deflection is 10 mm when the force
shown in Fig. 39 is applied.
Fan pulley
2 kg or 3 kg
Motor
pulley
Fig. 39
ATTENTION: Once the motor pulley opening or closing has
been set, check that the setscrews have been correctly
tightened.
ELECTRICAL CONNECTIONS
WARNING: To prevent electrical shock or equipment
damage, make sure disconnects are open before electrical
connections are made. If this action is not taken, personal
injury may occur.
-Route all cables through the conduits in the 38XTZ units
to the terminals of the main disconnect switch (see unit
wiring diagram).
-Voltage to the unit must be within 2% of the voltage and
10% of the current indicated on the nameplate. Contact
your local power company for correction of an incorrect
line voltage.
-Take special care when making the earth connection. This
is the first cable to be connected, and it must be longer
than the live cables.
-Operation of the unit on improper line voltage constitutes
abuse and is not covered by the Carrier warranty.
IMPORTANT: To ensure the correct unit power supply it is
necessary first to determine the wire section. The unit
electrical data (see Table 2, Electrical Data) and the line
length (maximum admissible voltage loss 5%) must be taken
into consideration.
If the indoor unit includes an electric heater, this must be
taken into consideration when sizing the system power
supply cable (38XTZ-40ABZ/ALZ) and the isolator switch
and fuses.
-Never operate a unit if the voltage imbalance exceeds 2%.
The following formula must be used to determine the
percentage of voltage imbalance.
Voltage imbalance % =
Largest deviation from average voltage
Average voltage
NOTE: The power supply for the units has to be in
accordance with applicable standards and laws, the low
voltage directive, etc.
-Connect the power supply for the complete system
(outdoor unit and indoor unit) via the 38XTZ outdoor unit
(see Fig. 40).
-Consult the wiring diagram supplied with the unit, that
shows all power connections between the 38XTZ outdoor
unit and the 40ABZ/ALZ indoor unit and the general power
supply to the system.
-The connection cables between the units must not be
lighter than the flexible Neoprene-covered cable (type
H05 RN-F), with an appropriate wire section for the
supply to the 40ABZ unit.
-The power of the optional electric heater of the indoor unit
is supplied via the main disconnect switch of the 38XTZ
unit (see Fig. 42).
Example: Nominal supply: 400-3-50
AB = 404 V
BC = 399 V
AC = 394 V
Fig. 41
Average voltage =404 + 399 + 394= 399 = 400 V
3
Determine maximum deviation from average voltage:
AB = 404 - 400 = 4
BC = 400 - 399 = 1
AC = 400 - 394 = 6
Largest deviation is 6 volts. Percentage voltage imbalance is
therefore:
6x 100 = 1.5 %
400
Fig. 40 - General unit power supply
Legend
Q1: Main unit power supply disconnect switch.
Located in the outer panel of the 38XTZ unit.
F1: Field-installed fuses.
28
-The cables marked 1 from the 40ABZ/ALZ indoor units
are run to the 38XTZ outdoor unit control box for
connection to the fan motor, and in the case of the optional
electric heater also cables marked 2.
40ABZ/ALZ
Optional
electric heater
fan motor
-Thermostat connection
Thermostat/unit connection must be via a loom
manufactured in accordance with the wiring diagram
accompanying the unit and the thermostat installation
instruction. Remember that for:
-Models 38XTZ 007 and 008 with 40ABZ 007 and
008 the thermostat is 220 V/1 ph/50 Hz (*).
-Models 38XTZ 011 and 014 with 40ALZ 011 y 014
the thermostat is 24 V with connection to the
programmable or non-programmable versions (*).
-Models 38XTZ 016 to 024 with 40ABZ 016 to 024,
units with Master Link I, the thermostat is 24 V with
connection to the programmable or nonprogrammable versions (*).
(*) NOTE: Refer to the applicable thermostat installation manuals for each model.
MASTER LINK I ELECTRONIC CONTROL
(38XTZ 016-024)
General description
An electronic control system which operates these units is
incorporated in the electrical box. This simplifies and improves
service operations and improves the performance.
Fig. 42
Legend
F3: Thermomagnetic indoor fan switch (included in the control box).
K2: Indoor fan motor contactor (included in the control box).
F4: Indoor fan motor thermal protection (included in the control box).
F1: General fuses of the installation (field-supplied).
Q1: Unit main disconnect switch (included in the 38XTZ panel).
F18:Thermomagnetic switch of the optional electric heater.
K6: Optional electric heater contactor.
R3: Optional crankcase heater.
F6: Thermomagnetic switch of the optional crankcase heater.
M: 40ABZ/ALZ indoor fan motor.
: Connection cables between the 40ABZ/ALZ indoor unit fan motor and the
38XTZ control box.
: Cables from the 40ABZ/ALZ unit of the outdoor unit for the power supply of the
heating coil.
NOTE:
The cables shown by the broken lines are not factory-supplied.
-If the units include options or accessories, such as heating
coils for electric heaters or the compressor crankcase
heater, proceed as follows:
a)Compressor crankcase heater (230 V/1 ph) - this must
be permanently connected, and the power supply
must be separate from the rest of the unit power. It
must be protected by a fuse.
b)Heating coils for electric heater - connect in
accordance with the wiring diagram downstream of
the 38XTZ main disconnect switch. Do not exceed
the power in kW recommended by Carrier. Use
correctly sized main fuses and the new unit power
supply cable section, if the electric heater power input
plus the power input of the indoor fan is higher than
the total power input given in Table 2, Electrical Data.
This new Master Link I electronic control system allows
communication with specific servicing tools, basic or advanced
(PC).
In addition, the information stored in the unit can be used as a
history record, facilitating service operations.
The system is composed of the following elements:
-Basic or main board
-Extension board
-Temperature probe
-Safety transformer
The main board, or basic unit, is factory-configured for each
model. Nevertheless, please find below the components which
the installer or maintenance technician (never the user) can
initialize, together with an illustration of the board.
Red LED
Green LED
DIP-switches
Main electronic board - Master Link I
Fig. 43
29
Extension board (PA1, PA2)
Fig. 44
Remote reset (38XTZ 011, 014)
IMPORTANT: The unit is supplied with a remote electric
reset which does not allow start-up of the compressor until
the protection devices have been activated. During unit startup in cooling as well as after shut-down caused by a trip
protection device, the equipment is reset by placing the
ambient thermostat controls in the position ‘OFF’ .
CAUTION: Once the operations needing the TEST mode
have been finalized the original configuration should be reset.
Never leave the test configuration on for normal operation.
No. 4: Informs the control of the setting to be observed during
defrost (heat pump units only).
DIP-switches
The board incorporates 8 DIP-switches numbered from 1 to 8,
with two positions each (ON/OFF), located as indicated in Fig.
43 (SW1).
No. 1: Do not modify the factory-set position.
No. 2 and 3: Inform the control of characteristics during
defrosts (heat pump units only).
Possible positions in other heat pump models:
-No. 2 ON, No. 3 ON: Indoor fan stopped during defrost
operation (if no other stage is activated).
-No. 2 ON, No. 3 OFF: Indoor fan functioning during
defrost operation.
-No. 2 OFF, No. 3 ON: Supplementary electric heating
stage is activated during defrost.
-No. 2 OFF, No. 3 OFF: Defrost in TEST mode.
Significantly reduces the settings associated with the
defrost.
Remote reset
The RESET operation indicated in the previous sections can be
initiated in two ways:
1.On the remote thermostat, move the thermostat controls to
the OFF and AUTO positions.
2.Disconnect the voltage to the unit.
If the unit incorporates the extension board necessary for
the electric heating and a protection trips, the protection
LED incorporated in the thermostat will flash until the unit
is reset.
Stage sequence switch
The electronic control incorporates a stage sequence switch,
which prevents simultaneous energizing of all compressors and
fans when the unit starts up and does not allow all the
components to stop together when the unit is shutdown.
Possible positions:
ON: 30 minutes
OFF: 60 minutes
These values can be changed using the servicing tools (basic or
advanced).
If a change in position is effected with the unit in operation, the
RESET order must be given so that the control can take into
account the new setting when initiating the subsequent defrost.
If RESET is not ordered, the control will continue the current
defrost at the old setting. The new setting will be used for the
next defrost.
ATTENTION: DIP-switches No. 2, 3 and 4 can only be
varied in heat pump models. For cooling only units, the
position of the DIP-switches does not affect the operation.
No. 5: Informs the control of the behaviour to be adopted when
a protection trips.
Possible positions:
ON: Blocked. After a protection has tripped, even though the
protection itself resets, the unit is blocked until the RESET is
effected from the thermostat.
OFF: Automatic reset. It is not necessary to RESET after a
protection has tripped.
NOTE: The RESET operation must be initiated from the
thermostat.
No. 6: Do not modify the factory-set position.
No. 7: Do not modify the factory-set position.
No. 8: Do not modify the factory-set position.
ATTENTION: The DIP-switches must be handled with
the utmost care so that the electronic board is not damaged.
Tools of the appropriate size for these switches must be used.
The time between start-up or shutdown for each component is
an internal parameter in the electronic control and can only be
changed using the servicing tools, basic or advanced
(accessory).
30
LEDs
There are two LEDs (red and green) on the electronic board
which indicate its status (see Fig. 43).
Intermittent green LED: The board status is correct.
Green LED off: The following steps should be taken:
1.Check whether there is 24 V AC running through the B1
connections on the board (see Fig. 43).
2.If there is, replace the board with a new one.
3.If there is none, look for the fault in the unit electrical
system and repair it.
4.Recheck the B1 connections.
Green LED on: Replace the board.
Red LED off: The status is correct.
Red LED on: Three possibilities:
1.Defective connection between the main board and the
secondary board. Check CO1 (Figs. 43 and 44)
connection. Check the status of the connecting cable.
2.Remote control incorrectly connected.
3.The secondary board jumpers J1 and J2 (Fig. 44) are
incorrectly connected. In order to correct this, use the table
below.
Table 9 - Secondary board jumpers
ModelCorrect connectionBoard
REFRIGERANT LINE CONNECTIONS
Connection between units
The 38XTZ outdoor units must be connected with the 40ABZ/
ALZ indoor units with refrigerant-grade copper pipes for correct
operation.
For each compressor in the 38XTZ outdoor unit a pipe for
refrigerant gas and another pipe for liquid refrigerant must be
installed.
For copper-pipe refrigerant connection lines the following
points must be observed:
-Ensure that the line length is as short as possible.
-The number of bends or elbows must be the minimum
possible.
-Design the lines with the correct diameter for the required
compressor oil suction velocity.
-Route the lines so that they do not obstruct the normal
building use. Avoid exposing them to extreme high or low
temperatures.
-Install them where they cannot be damaged.
-If they are routed outside the building, protect them
against extreme temperatures and damaging environmental
influences.
-Insulate the suction line along its complete length, and the
liquid line when it passes through any support, wall, etc.
A: Cooling only models with 1 compressor + electric heater
in indoor unit.
B: Cooling only models with 2 compressors + electric heater
in indoor unit.
C:Heat pump models with 1 compressor + electric heater in
indoor unit.
D: Heat pump models with 2 compressors + electric heater in
indoor unit.
Intermittent red LED: DIP-switch No. 1 in OFF position (see
Fig. 43).
CAUTION: When the red LED is illuminated intermittently
do not try to start up the unit. To correct this status, DIPswitch No.1 must be in the ON position after having been
RESET.
IMPORTANT: Always use refrigerant-grade deoxidized and
dehydrated copper tubing between the indoor and outdoor
units.
-Carefully protect the copper pipes during transport,
installation and connection, against possible ingression of
water or moisture.
-Also prevent entry of any contaminants or foreign
substances.
-Four operations are very important:
-Pipe cleaning
-Pipe leak tightness
-Correct leak tests
-Correct evacuation
-When pipes are soldered, cut or flared, etc. ensure that no
residue or shavings can enter the pipes. Blow any residue
away from the pipe ends and check them carefully.
Refrigerant piping design
The design and sizing of the pipe diameters depends on the unit
location which can be:
31
-Outdoor unit above the indoor unit.
outdoor unit
Suction line
(gas)
Refrigerant
40ABZ
indoor unit
Liquid pressure
control device*
Fig. 45
NOTE:
*Install when the liquid column height exceeds 10 m.
-Indoor unit above the outdoor unit.
40ABZ
indoor unit
Suction line
(gas)
38XTZ
Liquid line
flow
-The outdoor and indoor units are on the same level (Fig.
47). First make an actual outline diagram of the lines and
an exact calculation of the total equivalent length. If the
diagram shows any level changes to overcome (beams and
other structural elements) the resulting section (ascending
and descending) must be included in the calculations. This
means that for a gas pipe the diameter of the horizontal
sections, the vertical ascending and descending sections
must be calculated separately.
This means that in this type of installation, as in any other,
a section called horizontal can include sections that are not
all horizontal (see Fig. 48).
Gas pipe
Beam
Frame or roof
Beam
Liquid line
Refrigerant
flow
38XTZ
outdoor unit
Fig. 46
-Both units on the same level.
Suction line
(gas)
40ABZ
indoor unit
Liquid line
38XTZ
outdoor unit
Refrigerant
flow
Fig. 47
Depending on the unit installation
-Outdoor unit above the indoor unit (Fig. 45). The suction
line is unfavourable in cooling mode, the suction of the
refrigerant gas corresponds to refrigerant flow direction, and
is ascending.
The liquid line refrigerant flow direction is descending in
cooling mode and is calculated as explained later.
-Outdoor unit below the indoor unit (Fig. 46). The suction
line flow is descending in cooling mode, so that the oil flow
is not so problematic.
The liquid line flow direction is ascending in cooling
mode, and is calculated as explained later.
Fig. 48
- Horizontal sections = A
- Vertical descending sections = B
- Vertical ascending sections = C
The calculation of the suction line, for example, includes
sections “A”, as well as sections “B” and sections “C” so
that the total of the pressure loss is the total of the three
sections.
Pipe diameter calculation procedure
Once the refrigerant piping outline has been exactly defined we
can proceed with the size selection.
Suction line
To size the pipes:
-Make a diagram with the actual outline of the pipes in the
system. Record the dimensions (in metres) of the various
sections and the elements to be included (siphons, elbows,
valves, etc.).
-Calculate the equivalent length of:
Vertical sections: length in metres of the straight section
pipe run plus the equivalent length of the accessories
installed (elbows, siphons, etc.).
Horizontal sections: length in metres of the actual pipe run
plus the equivalent length of the accessories installed
(elbows, etc.).
-The total length is the sum of the equivalent lengths of the
vertical and horizontal sections.
-For the vertical sections distinguish between ascending
vertical refrigerant flow sections and descending flow
sections.
32
-Depending on the installation, the suction line (gas) can
be:
1.The outdoor unit is above the indoor unit. Suction
with ascending refrigerant flow.
2.The outdoor unit is below the indoor unit. Suction
with descending refrigerant flow.
3.Units on the same level. The refrigerant flow
direction does not change, the flow is towards the
compressor.
-The liquid line is affected as explained later, depending on
the unit installation. If the head exceeds 10 m, install a
control valve (see Fig. 45).
-In the first installation case calculate the gas pipe as
ascending.
Selection process:
-Enter the diagram in Fig. 49 horizontally at the model
number given in the legend.
-The model number lines run horizontally and intersect the
various diameter curves (lines going from right to left) and
the various gas velocity curves (lines going from left to
right).
-Select a diameter and a velocity, and record the one shown
in the specified design conditions for the suction line.
-For the intersection point of the model number line with
the selected diameter and velocity run down vertically to
find out the pressure loss in kPa or psi for each 10 m
equivalent length (length in line metres plus accessories).
For other lengths the pressure loss is directly proportional.
In the second case, calculate the suction as ascending.
-The suction line must comply with the following points:
•Maximum admissible pressure loss for the total
length = 20 kPa (3 psi).
•Minimum velocity in ascending sections = 6 m/s.
•Horizontal or descending sections: the velocity can be
between 4 and 6 m/s.
•Maximum line velocity = 15 m/s.
•The horizontal sections must have a 2% slope towards
the compressor.
•In the vertical sections with ascending gas flow, it is
advisable to install siphons every 8 m in height.
Install the first siphon at the base of the ascending
column.
•Select the suction line diameter (Fig. 49).
Liquid line
The liquid line diameter can be selected using the table below.
Table 10 - Liquid line diameter
Total equivalent length
ModelsUp to 10 mFrom 10 to 30 mFrom 30 to 45 m
38XTZ 007 + 40ABZ 007 5/8"5/8"5/8"
38XTZ 008 + 40ABZ 008 5/8"5/8"3/4"
38XTZ 011 + 40ALZ 011 5/8"3/4"3/4"
38XTZ 014 + 40ALZ 014 5/8"3/4"7/8"
38XTZ 016 + 40ABZ 016 5/8"5/8"3/4"
38XTZ 020 + 40ABZ 020 5/8"3/4"3/4"
38XTZ 024 + 40ABZ 024 5/8"3/4"7/8"
Calculate the equivalent lengths of the horizontal and vertical
sections and then add them to the equivalent length of the
installed accessories. Enter Table 10 for the total equivalent
length value to select the piping diameter for the right model.
Liquid line requirements:
-Do not insulate the liquid line, except where it is exposed
to the outside.
-If the liquid refrigerant flow is descending and the column
height exceeds 10 m, a pressure-balancing valve must be
installed in the lower part to equalise the pressures
between this point and the higher liquid column (see Fig.
45).
Pressure loss/10 m equivalent length in m
Legend
1- 38XTZ 007 + 40ABZ 007
2- 38XTZ 008 + 40ABZ 008
- 38XTZ 016 + 40ABZ 016
3- 38XTZ 011 + 40ALZ 011
- 38XTZ 020 + 40ABZ 020
4- 38XTZ 014 + 40ALZ 014
- 38XTZ 024 + 40ABZ 024
Note: See Table 4, page 4 for the standard outlet connection diameters.
Fig. 49 - Suction line diameter
Normal cooling mode.
The manual control valve permits equalisation of the
pressures between the highest and lowest point of the
liquid column. Adjust the valve so that the pressure at the
expansion system inlet is the same as at the highest liquid
column point.
-The pressure loss in the liquid line must not be higher than
34 kPa (5 psi).
-If the refrigerant flow is ascending and the piping height
exceeds 15 m, at least 1 K of liquid subcooling is required
for each 3.6 m in excess of 15 m.
Subcooling can be contained in the liquid and suction lines
(maximum 15 m).
-In long lines it is advisable to install expansion bends.
33
ATTENTION: Before connecting the refrigerant lines
carefully follow the steps below:
-Remove the nitrogen holding charge from the refrigerant
circuits.
-Use silver alloy rod for soldering purposes, and ensure
that this work is done in a nitrogen atmosphere.
-Check the pipes for leaks before welding the joint to the
unit pipes.
-Once these connections have been made, carry out
another leak test.
REFRIGERANT CHARGE
The 38XTZ and 40ABZ units are supplied with an R-407C
holding charge. This must be removed before soldering the
connecting refrigerant lines to the unit. Once the soldering has
been completed, the complete refrigerant circuit must be
evacuated then the correct quantity of R-407C refrigerant for
each system must be charged.
•Any loss of oil from the system during maintenance
must be stopped immediately and the collected oil
must be removed in accordance with applicable
regulations.
d)If, when the unit is run, symptoms of loss of charge (for
example, low pressure switch tripping or abnormally low
cooling capacities) are detected, first conduct a leak test
followed, if necessary, by a gas tightness test using
compressed nitrogen. For the latter all refrigerant must be
removed from the circuit. Transfer the refrigerant to a
storage tank and then clean the circuit as described earlier.
e)Before adding the refrigerant charge proceed as follows:
-Draw a vacuum in the refrigerant circuit until a
pressure of 667 Pa (-755 mm Hg) has been reached
for at least two hours. At a greater distance between
units the period must be longer. The period of time
of the vacuum is important.
-Check that there are no refrigerant leaks.
Continue to charge refrigerant as described below:
WARNING: If any brazing is to be done the refrigerant circuit
must be filled with nitrogen. Combustion of refrigerant R-407C
produces toxic phosgene gas.
To evacuate and charge the unit with refrigerant, use devices
that are suitable and specific for refrigeant R-407C, used in
these units:
-A pump for exclusive use with R-407C or with a nonreturn valve in the R-22 pump.
-Hose connections and pressure gauge jumper for R-407C.
-R-407C cylinder in brown colour. Charging is always by
weight, using scales and a bottle. Only charge liquid
refrigerant.
-Leak detection - it is difficult to detect R-407C refrigerant
leaks.
Refrigerant R-407C consists of a non-azeotropic blend of 23%
of R-32, 25% of R-125 and 52% of R-134a, and is
characterised by the fact that at the time of the change in state
the temperature of the liquid/vapour mixture is not constant. All
checks must be pressure tests, and the appropriate pressure/
temperature ratio table must be used for the interpretation of the
values.
Leak detection is especially important for units charged with
refrigerant R-407C. Depending on whether the leak occurs in
the liquid or the vapour phase, the proportion of the different
components in the mixture remaining in the unit is not the
same.
Total charge = unit charge plus additional charge per metre
suction line and per metre liquid line.
-The refrigerant charge for the 38XTZ and 40ABZ/ALZ
units is given in Table 1 - Physical Data.
For each metre of refrigerant connection line installed,
refrigerant has to be added in accordance with the table below:
Table 12 - Refrigerant charge (g/m)
Diameter1/2"5/8"3/4"7/8"1-1/8"1-3/8"
Liquid line75120180250420645
Suction line1423344781123
OIL RECHARGE
If any oil needs to be added to fill the siphons and above all
when the total line length is high, use the same type and brand
as used in the compressors.
Compressor oil:
Type: 160PZ Maneurop-Danfoss (depends on the compressor
manufacturer).
The following basic guidelines must be observed:
a)Whenever there is a leak the complete refrigerant R-407C
charge that remains in the circuit must be removed.
b)After the leak has been repaired, evacuate the circuit.
c)Take into consideration that:
•All leaks must be repaired immediately by qualified
personnel.
•Refrigerant must never be discharged to the
atmosphere.
•Use a refrigerant reclaim unit.
34
START-UP
UNIT COMPONENTS
Necessary checks/precautions before start-up:
-Confirm that the electrical power source agrees with the
unit nameplate rating.
-Ensure that the power connections between speed and
thermostat have been made and correctly tightened.
-Check that there are no refrigerant leaks in the soldered
refrigerant lines, and that the refrigerant and oil charges
are correct.
-Check the 40ABZ/ALZ drain connection and that the
water is drained correctly.
-Ensure that the unit is level and well-supported.
-Check for proper fan rotation direction
-Check the condition of the ductwork in case damage has
occurred during installation.
-The air filter should be clean and in place.
-All the panels should be fitted and firmly secured with the
corresponding screws.
-Make sure that compressors float freely on the mounting
springs.
WARNING: The compressors are mounted on vibration
isolators. Do not loosen or remove the support mounting
bolts.
IMPORTANT: Actual start-up should only be done under the
supervision of a qualified refrigeration mechanic.
Initial checks
With the unit in operation, ensure that the values shown on the
high and low pressure gauges are within the normal limits. It is
advisable to simulate unit shutdown due to high and low
pressure, in order to make sure that the pressurestats work
properly. To do so, proceed as follows:
-High pressure shutdown: Completely cover the outdoor
air inlet, or disconnect the outdoor fan and motor. The unit
should stop at a pressure of 2844 kPa.
-Low pressure shutdown: Cover the indoor air inlet, or
disconnect the indoor fan and motor. Observe the low
pressure gauge. The unit should stop at a pressure of 265
kPa.
The pressure switches are automatically reset. As this takes
some time, the unit will stop, the pressures will equalise, and
then the unit will be reset and will start up again.
Check that the motor and compressor consumptions are
approximately the same as those shown in the fan performance
curves and in the cooling capacity tables, for the unit operating
conditions (indoor and outdoor temperatures, air flow and static
pressures, based on the speed, etc.).
The 38XTZ and 40ABZ/ALZ units incorporate the following
components:
-Three-phase hermetic reciprocating compressors with
internal thermal protection in the 38XTZ units.
-Refrigerant-to-air heat exchangers (evaporators and
condensers) made of copper tubes and pre-treated, waterresistant aluminium fins.
-All-copper refrigerant circuit. R-407C refrigerant control
in the 40ABZ/ALZ indoor units using thermostatic
expansion valves or throttle valves depending on the
model.
-High and low pressure switch and filter drier (38XTZ).
-Fan high pressure switch (38XTZ 014).
-Soldered copper refrigerant connection lines at the unit
outlets.
-Complete internal wiring. Main on/off disconnect switch
in the 38XTZ outdoor units. These units also include the
complete electrical boxes with compressor and indoor fan
motor contactors, transformers (depending on the model)
and other components. Thermomagnetic disconnect
switches for compressors and fan motors.
-Master Link I electronic control board for sizes 38XTZ
016 to 024.
-Fans:
The 40ABZ/ALZ indoor units have centrifugal fans driven
by three-phase motors with adjustable belt-pulley drives.
The 38XTZ outdoor units have direct-drive propeller fans.
-Thermal and acoustical insulation. Flexible shock
absorbers in all moving components.
-Air filters in the 40ABZ/ALZ indoor units.
-Pre-painted galvanised sheet steel casings.
DESCRIPTION OF UNIT PROTECTION DEVICES
The unit includes the following compressor protection devices:
-Internal compressor protection device for all 38XTZ
units to avoid superheat.
-Short-cycle protection standard for units 38XTZ 007-014.
-Short-cycle protection included on the Master Link I main
electronic board for units 38XTZ 016-024
-Indoor fan motor thermomagnetic switch in the 38XTZ
unit control box.
-Thermomagnetic compressor and indoor fan motor
disconnect switch, in the 38XTZ unit control box.
-High pressurestat: This protects the unit against excessive
condensing pressure.
The high pressurestat has factory-fixed non-adjustable
settings. To check, see section Initial checks.
35
-Fan high pressure switch (38XTZ 014).
-Low pressurestat: This protects the 40ABZ/ALZ units
against excessive low pressure in the evaporator or in the
refrigerant lines.
The low pressurestat has factory fixed non-adjustable
settings. To check, see section Initial checks.
CAUTION: When any of these cuts out, the unit stops and
will not re-start until the contacts have been reclosed after
rectification of the fault.
Table 13 - Pressure switch settings
38XTZ 007, 008, 011, 016, 020 and 024
Cut-outCut-inReset
High pressurestat*2844 kPa*1863 kPaManual
Low pressurestat*265 kPa*363 kPaAutomatic
*Factory-calibrated
38XTZ 014
Cut-outCut-inReset
High pressurestat*2844 kPa*1863 kPa-Manual
Low pressurestat*265 kPa*363 kPaAutomatic
High pressurestat, fan*2354 kPa*1863 kPaAutomatic
*Factory-calibrated
WARNING: Alteration of factory settings other than the
design set-point, without manufacturer's authorisation, may
void the warranty.
Table 14 - Operating limits
ZoneAir temperature °C
Min.Max.
Cooling operation:
Indoor
Maximum+35+21
Minimum+19+14
Outdoor
Maximum+40/44*Minimum19**-
Indoor air flow
Maximum+20% of nominal value
Minimum-20% of nominal value
Hot water coil (accessory/option)
Maximum water temperature80°C
*Sizes 007, 011, 014, 020 and 024: 40°C
Sizes 008 and 016: 44°C
** With optional/accessory head pressure control, the unit will operate at
temperatures below 19°C.
GENERAL MAINTENANCE
ATTENTION: Before starting any servicing or maintenance
operation on the unit, make sure that the power supply has
been disconnected. A current discharge could cause personal
injury.
In order to obtain maximum performance from the unit special
attention should be paid to the following points:
-Electrical connections: The supply voltage should be
within the limits permitted by the compressor and the unit.
Ensure that no faulty contacts exist in the terminal blocks,
contactor boards, etc. Make sure that all the electrical
connections are properly tightened, and that all the
electrical components (contactors, relays, etc) are firmly
secured to the corresponding rails.
Pay special attention to the condition of the connecting
cables between the control elements and the electrical box,
and to that of the unit power supply cable. They should not
be twisted and there should be no slits or notches in the
insulation. Check the starting and running consumptions
are within the limits specified in the corresponding
technical information.
-Drainage: Frequently check that the drain is not obstructed,
and that the condensate pan is clean and level. Ensure that
the condensate drain pan of the 40ABZ/ALZ unit is
perfectly clean and does not contain sludge or other
foreign substances, corrosion, etc. and is level.
-Inlet filter: This should be cleaned periodically. The
frequency depends on the purity of the entering air. The
filter may be cleaned with a household vacuum cleaner, or
by immersing it in water.
-Refrigerant circuit: Ensure that there is no leakage of
refrigerant or oil from the compressor. Check that the high
and low side operating pressures are normal. Make sure
that the coils are not dirty, if necessary clean with water
and air. Straighten bent aluminium fins with a suitable fin
comb. Check for unusual compressor noise.
-Controls: Check the operation of all electric controls, high
and low pressurestats, etc.
-Fans: The fan of the 38XTZ unit must rotate freely. There
must not be any foreign elements in the fans of the
40ABZ/ALZ indoor units. Please check:
a)the condition of the pulleys
b)the condition of the belts
c)the belt tension.
ATTENTION: Operation of the units at temperatures, air
flows, etc. outside the limits indicated in the table above can
cause serious damage to the units and will void the Carrier
warranty.
36
Periodically check the condition of the belts and pulleys and
ensure that they are correctly aligned. Also ensure that the
belt tension is correct. At the first start-up, and after a longer
shut-down period, recheck the belt tension after a few hours
of operation.
2 kg or 3 kg
Legend
1 Pulleys
2 Motor and fan shafts must be parallel
3 Straight-edge must be parallel with belt
Fig. 50
-Lubrication: Both the motors and the fans have factory-
lubricated and sealed bearings, and need no further
lubrication.
The compressor has its own oil supply, including the
amount for the siphons and refrigerant lines. Oil should
not be added unless a leak has occurred. Always use oil of
the same brand and type that was used for the original
charge.
Servicing recommendations
-Before replacing any of the elements in the cooling circuit,
ensure that the entire refrigerant charge is removed from
both the high and low pressure sides of the unit.
-The control elements of the cooling system are highly
sensitive. If they need to be replaced, care should be taken
not to overheat them with blowlamps whilst soldering. A
damp cloth should be wrapped around the component to be
soldered, and the flame directed away from the component
body.
-Silver alloy soldering rods should always be used.
-If the total unit gas charge has to be replaced, the quantity
should correspond to the original unit gas and liquid
charge, plus the required charge for the refrigerant lines.
The unit should be properly evacuated beforehand.
-During unit operation all panels should be in place,
including the electrical box access panel.
-If it is necessary to cut the lines of the refrigerant circuit,
tube cutters should always be used and never tools which
produce burrs. All refrigerant circuit tubing should be of
copper, specially made for refrigeration purposes.
Compressor replacement
NOTE: This operation must be done by a qualified
technician.
When an internal fault occurs, the compressor must be
replaced. This must be done as detailed below:
-Disconnect the unit from the electrical supply.
-Remove the panels.
-Remove the gas from the refrigerant circuit using recovery
equipment to avoid harming the atmosphere.
-Electrically disconnect the compressor.
-Unbraze or unscrew the suction and discharge lines, taking
care not to damage the rest of the components.
-Remove the fastenings from the compressor.
-Replace the compressor, ensuring that it contains
sufficient oil.
-Check if the oil of the defective compressor contains any
acidity from burnt-out windings.
-If the oil contains acid, this will also be present in the
refrigerant circuit. All the acid must be removed from the
refrigerant circuit, otherwise the new compressor will also
be damaged. In order to remove the acid proceed as
follows:
a)Thoroughly clean the refrigerant circuit using dry
nitrogen in the opposite direction to the refrigerant
flow.
Also carefully clean the separate parts of the
refrigerant circuit.
Install anti-acid filters in the liquid line. Solder the
refrigerant lines. Evacuate the lines and charge them
with refrigerant. Operate the unit for some time.
Remove the oil and check the acidity.
If there is still acid present, repeat the steps above
several times, until no acid exists.
b)If you do not want to carry out the procedure
described under (a), introduce an anti-acid substance
into the refrigerant circuit, if the refrigerant line
length is short.
c)It is also possible to install an anti-acid filter in the
suction lines.
d)Analyse the refrigerant circuit acidity several times
and replace the filters several times until no acidity
exists.
e)Remove the filter from the liquid line in the 38XTZ
units. Install a new filter when no acid remains in
the circuit.
-Once the defective compressor has been replaced by a new
one and the oil has been analysed, proceed as follows:
-Braze or screw in the lines.
-Install a new filter in the liquid line of the 38XTZ
units.
-Connect the compressor according to the wiring
diagram.
-Evacuate the compressor.
-Carry out a leak test. Repair any leaks detected.
-Fill the refrigerant charge indicated on the nameplate,
plus the required charge for the refrigerant connection
lines.
37
Table 15 - Options/accessories
38XTZ-40ABZ/ALZOptionAccessory
Heating coils for 40ABZ/ALZ indoor units:
A - electric resistance heatersxx
B - hot-water coilsxx
Thermal-magnetic crankcase heaters for 38XTZ outdoor unitsxx
Low refrigerant pressure switch for 38XTZ outdoor units*x-
Head pressure control for cooling operation at outdoor air temperatures below +19°C (38XTZ)xx
Special drives for higher indoor unit fan static pressure
(40ABZ/ALZ - installed in the units on request)x-
Room thermostat, wired remote control - versions:
A -220 V for sizes 38XTZ 007 and 008 with 40ABZ 007 and 008
(one stage cooling, one stage heating)-x
B -24 V for sizes 38XTZ 011 to 024 with 40ABZ/ALZ 011 to 024
(two stages cooling, three stages heating)
B1 - Programmable, with remote sensor option for return air duct or room air-x
B2 - Non programmable-x
From the Master Link I control, for sizes 38XTZ 016-024/40ABZ 016-024
A - Advanced service tool (via PC software)**-x
B - Interface converter, for control of up to 15 x 15 units via PC software**-x
C - Basic tool**-x
D - Communication board**-x
Accessories are not factory-installed.
Options can be ordered for factory-installation in the units, or they can be installed later.
*To be requested at time of order, installed in the 38XTZ units.
** -With the basic service tool the communication board must also be ordered.
-With the advanced service tool (via PC software) the communication board and the communication interface converter
must also be ordered.
-If an installation includes various units connected to a communication bus, all units on the bus must include the
communication board.
38
FINAL RECOMMENDATIONS
The unit you have purchased has undergone strict quality
control procedures before leaving the factory.
All components, including the control systems and electrical
equipment, etc., are certified by our Quality Control
Department, and tested under the harshest possible operating
conditions in our laboratories. However, after leaving the
factory, it is possible that one or more of these elements may be
damaged due to causes beyond our control. In such an event,
the user should not work on any of the internal components,
or subject the unit to operating conditions which are not
specified in this manual, since serious damage may result and
the guarantee would be invalidated. Repair and maintenance
work should always be left to the installer.
Table 16 - Troubleshooting chart
IMPORTANT: All recommendations concerning unit
installation are intended to be as a guideline. Qualified
technicians or installers must carry out the installation
correctly and in accordance with applicable local, national
and European standards and with the design conditions. They
should also comply with all applicable regulations for air
conditioning and refrigeration installations.
NOTE: The manufacturer does not accept responsibility for
any malfunctions resulting from misuse of the 38XTZ and
40ABZ/ALZ units, or from an incorrect installation and the
damage caused by this.
SymptomsCauseRemedy
Unit does not startNo power supplyConnect power supply
Main switch openClose switch
Low line voltageCheck voltage and remedy the deficiency
A protection has trippedReset
Contactor stuck openReplace contactor
Seized compressorReplace compressor
Unit starts and stops frequentlyDefective compressor contactorReplace contactor
Defective compressorReplace compressor
Refrigerant lossesCheck. Remove the charge. Repair leaks.
Evacuate. Recharge with refrigerant
Unit continuously cuts out atDefective low pressurestatReplace pressurestat
low pressureRefrigerant lossesCheck and add the necessary quantity
Indoor fan does not operateCheck fan motor
Unit continuously cuts out atDefective high pressurestatReplace pressurestat
high pressureRefrigerant lossesCheck and correct
Outdoor fan does not operateCheck fan motor
Abnormal system noisePiping vibrationSupport piping and check drainage
Noisy compressorCheck and change if necessary
Badly fitting panelsInstall correctly
Water lossDefective drainage connectionsCheck and tighten if necessary
Compressor loses oilLeak in systemRepair leak
Green and red Master Link I LEDs onSee pages 29 to 31See pages 29 to 31
39
Order No. 13867-20, 12.02; Supersedes order No. NewPrinted on Totally Chlorine Free Paper.
Manufacturer reserves the right to change any product specifications without notice.Printed in the Netherlands.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.