Final installation checks.................................................................................................................11/12
ATTENTION INSTALLERS AND SERVICE TECHNICIANS!
AIR CONDITIONER WITH R-410A – QUICK REFERENCE GUIDE
•R-410A refrigerant operates at 50%-70% higher pressures than R-22. Be sure that servicing
equipment and replacement components are designed to operate with R-410A.
•R-410A refrigerant cylinders are pink.
• R-410A refrigerant cylinders have a dip tube which allows liquid to flow out with the cylinder in a v ertical
position with the valve at the top .
•R-410A systems should be charged with liquid refrigerant. Use a commercial type metering device
in the manifold hose in order to vaporize the liquid refrigerant before it enters in the unit.
•A vacuum pump is not enough to remove moisture from oil.
•Oils absorb moisture rapidly. Do not expose oil to atmosphere.
•Never open system to atmosphere while it is under vacuum.
•When the system must be opened for service, break vacuum with dry nitrogen.
•Do not vent R-410A into the atmosphere.
•Use only Carrier matching indoor units (Table I).
ENGLISH
Table I
Heat
pump
models
38VYX 110110110
38VYX 130130130
———
———
CassetteSatellitePower
“40KQV”
“40SQV”supply
220
÷240V ~ 50Hz
GB - 1
38VYX110/38VYX130
General information
Precautions for safety
The unit must be installed according to the national plantengineering standards.
• Read this “PRECAUTIONS FOR SAFETY” carefully before
Installation.
• The precautions described below include the important items
regarding safety. Observe them without fail.
• After the installation work, perform a trial operation to check for
any problem.
Follow the Owner’s Manual to explain how to use and maintain the
unit to the customer.
• Turn off the main power supply switch (or breaker) before the unit
maintenance.
• Ask the customer to keep the Installation Manual together with the
Owner’s Manual.
CAUTION:
• This air conditioner adopts the new HFC refrigerant (R410A)
which does not destroy ozone layer.
The characteristics of R410A refrigerant are ; easy to absorb
water, oxidizing membrane or oil, and its pressure is approx. 1.6
times higher than that of refrigerant R22.
Accompanied with the new refrigerant, refrigerating oil has also
been changed.
Therefore, during installation work, be sure that water, dust,
former refrigerant, or refrigerating oil does not enter the
refrigerating cycle.
To prevent charging an incorrect refrigerant and refrigerating oil,
the sizes of connecting sections of charging port of the main unit
and installation tools are charged from those for the conventional
refrigerant. Accordingly the exclusive tools are required for the
new refrigerant (R410A).
• Connect indoor and outdoor units with field-supplied copper pipes
by means of flare connections. Use insulated seamless
refrigeration grade pipe only, (Cu DHP type according to
ISO1337), degreased and deoxidized, suitable for operating
pressures of at least 4200 kPa and for burst pressure of at least
20700 kPa. Under no circumstances must sanitary type copper
pipe be used.
Moreover, do not use the existing piping because there are
problems with pressure-resistance force and impurity in it.
• Check that the impedance of the mains power supply is in
conformance with the unit power input indicated in the
electric data (EN 61000-3-11).
• This unit complies with low-voltage (EEC/73/23) and electromagnetic compatibility (EEC/89/336) directives.
• This appliance must be connected to the main power supply by
means of a switch with a contact separation of at least 3 mm.
The installation fuse (25A D type
the power supply line of this conditioner.
WARNING:
• Ask an authorized dealer or qualified installation professional to
install/maintain the air conditioner. Inappropriate installation may
result in water leakage, electric shock or fire.
• T urn off the main power supply switch or breaker before attempting
any electrical work. Make sure all power switches are off. Failure
to do so may cause electric shock.
• Connect the connecting cable correctly. If the connecting cable is
connected in a wrong way, electric parts may be damaged.
• When moving the air conditioner for the installation into another
place, be very careful not to enter any gaseous matter other than
the specified refrigerant into the refrigeration cycle.
If air or any other gas is mixed in the refrigerant, the gas pressure
in the refrigeration cycle becomes abnormally high and it may
cause pipe burst and injuries on persons.
• Do not modify this unit by removing any of the safety guards or by
by-passing any of the safety interlock switches.
• Exposure of unit to water or other moisture before installation may
cause a short-circuit of electrical parts. Do not store it in a wet
basement or expose to rain or water.
• After unpacking the unit, examine it carefully for possible damage
• Do not install in a place that might increase the vibration of the unit.
• To avoid personal injury (with sharp edges), be careful when
handling parts.
) must be used for
• Perform installation work properly according to the Installation
Manual.
Inappropriate installation may result in water leakage, electric
shock or fire.
• When the air conditioner is installed in a small room, provide
appropriate measures to ensure that the concentration of
refrigerant leakage occurred in the room does not exceed the
critical level.
• Install the air conditioner securely in a location where the base
can sustain the weight adequately.
• Perform the specified installation work to guard against an
earthquake.
If the air conditioner is not installed correctly, accidents may occur
due to the falling unit.
• If refrigerant gas has leaked during the installation work, ventilate
the room immediately.
If the leaked refrigerant gas comes in contact with fire, noxious
gas may generate.
• After the installation work, confirm that refrigerant gas does not
leak. If refrigerant gas leaks into the room and flows near a fire
source, such as a cooking range, noxious gas might generate.
• Electrical work must be performed by a qualified electrician in
accordance with the Installation Manual.
Make sure the air conditioner uses an exclusive power supply. An
insufficient power supply capacity or inappropriate installation may
cause fire.
• Use the specified cables for wiring and connect them firmly to
the terminals.
To prevent external forces applied to the terminals from affecting
the terminals.
• Be sure to provide grounding. Do not connect ground wires to gas
pipes, water pipes, lightning rods or ground wires for telephone
cables.
• Conform to the regulations of the local electric company when
wiring the power supply.
Inappropriate grounding may cause electric shock.
• Do not install the air conditioner in a location subject to a risk of
exposure to a combustible gas.
If a combustible gas leaks, and stays around the unit, a fire may
occur.
Required tools for installation work
- Philips screw driver
- Cutter drill (65 mm)
- Spanner
- Pipe cutter
- Cutter
- Reamer
- Gas leak detector
- Meter
- Thermometer
- Volt-ohm-milliammeter
- Electro circuit tester
- Hexagonal wrench
- Flare tool
- Pipe bender
- Water level
- Metal saw
R410A (Special requirement)
- Manometer for pressure measuring
(Charge hose : R410A special requirement)
- Vacuum pump
(Charge hose : R410A special requirement)
- Torque wrench:
• 1/4 (17 mm) 16 N•m (1,6 kgf•m)
• 3/8 (22 mm) 42 N•m (4,2 kgf•m)
.
• 1/2 (26 mm) 55 N•m (5,5 kgf•m)
• 5/8 (15,9 mm) 120 N•m (12,0 kgf•m)
- Copper pipe gauge adjusting projection margin
- Vacuum pump adapter
GB - 2
38VYX110/38VYX130
Accessory and refrigerant
T able II: Accessory and Installation Parts
Outdoor unitDrain nipple
Installation manual x 1
Refrigerant Piping
• Piping kit used for the conventional refrigerant cannot be used.
• Use copper pipe with 0.8 mm or more thickness for Ø 9,52
mm.
T able III: Length of refrigerant
Length of refrigerant pipe connected
to indoor/outdoor units.
20 m o shorter: for all unitsDo not add refrigerant at installation site
Refrigerant addition
Waterproof rubber cap
• Use copper pipe with 1.0 mm or more thickness for Ø 15,87 mm.
• Flare nut and flare works are also different from those of the
conventional refrigerant.
Take out the flare nut attached to the main unit of the air
conditioner, and use it.
.
ENGLISH
(1)
from 20 m to 50 mAdd 40 g of refrigerant for every meter of pipe beyond 20 m
NOTES: Caution at addition of refrigerant
(1)
When the total length of refrigerant pipe exceeds 20m, add 40g/m. The pipe total maximum length is 50 m. (Max. amount of additional refrigerant is
1200g.). Charge the refrigerant accurately. Overcharge may cause a serious trouble of compressor..
T able IV : Operating limits
Cooling (2)
Heating (2)
Mains power supplyNominal single-phase voltage220÷240V ~ 50Hz
Notes:1. Data referred to the outdoor unit only.
2. According to prEN14511.
d.b. - dry bulb;w.b. - wet bulb
(1)
Maximum conditions
Minimum conditions
Maximum conditions
Minimum conditionsoutdoor temperature –15°C d.b.
Operating voltage limitsmin. 198V – max. 264V
WARNING:
During heat pump operation unit will undergo several defrost cycles to
eliminate ice that might possibly collect on the outdoor unit in very low
ambient temperatures.
In these cycles, fan speed will automatically reduce and cannot be
varied until defrost cycle is completed.
outdoor temperature 43°C
indoor temperature 32°C d.b.; 23°C w.b.
outdoor temperature -5°C
indoor temperature 21°C d.b.; 15°C w.b.
outdoor temperature 24°C d.b.; 18°C w.b.
indoor temperature 27°C d.b.
Selection of installation
Air purge
• For air purge, use a vacuum pump.
• Do not use refrigerant charged in the outdoor unit for air purge.
(The refrigerant for air purge is not contained in the outdoor unit.)
Electrical cabling
• Be sure to fix the power cables and indoor/outdoor connecting
cables with clamps so that they do not contact with the cabinet,
etc.
GB - 3
38VYX110/38VYX130
Selection of installation
Installation Place
• A place which provides a specified space around the outdoor unit.
• A place where the operation noise and discharged air are not
given to your neighbors.
• A place that is not exposed to a strong wind.
• A place that does not block a passage.
• When the outdoor unit is installed in an elevated position, be sure
to secure its feet.
• There must be sufficient space for carrying in the unit.
• A place where the drain water does not make any problem.
• If the unit is installed in areas where heavy snowfalls may occur, it
is necessary to raise its level at least 200 mm above the usual
snow level.
• The support must be suitable for the unit weight.
CAUTION:
• Install the outdoor unit at a place where discharge air is not blocked.
• When an outdoor unit is installed in a place that is always exposed
to a strong wind like a coast or on a high storey of a building,
secure a normal fan operation by using a duct or a wind shield
• When installing the outdoor unit in a place that is constantly
exposed to a strong wind such as the upper stairs or rooftop of a
building, apply the windproof measures referring to the following
examples.
• Install the unit so that its discharge port faces the wall of the
building. Keep a distance 500 mm or more between the unit and
the wall surface.
• Supposing the wind direction during the operation season of the
air conditioner, install the unit so that the discharge port is set at
right angle to the wind direction.
• Installation in the following places may result in some troubles. Do
not install the unit in such places below.
•A place full of machine oil.
•A place full of sulphuric gas.
•A place where high-frequency radio waves are likely to be
generated as from audio equipment, welders, and medical
equipment.
Knockout procedure
• The indoor/outdoor connecting pipes can be connected to 4
directions.
Take off the knockout part of the pipe cover in which pipes or
wires pass through the base plate.
• As shown in the figure, do not remove the pipe cover from the
cabinet so that the knockout hole can be easily punched.
To knock out, punch the 3 connected parts with a screwdriver
and remove the pipe cover by hand.
• After marking the knockout hole, remove the burr and mount
the attached protective bush and guard material for pass-through
part in order to protect pipes and wires.
• After connecting the pipes, be sure to mount the pipe cover.
The pipe cover is easily mounted by cutting off the slit at the
lower part of the cover.
How to remove the front panel
1. Remove screws of the front panel.
2. Pull the front panel downward.
Removing the front panel, the electric parts appear at the front side.
• The power supply cables can be inserted into the pipe holes.
Enlarge the pipe holes if they are too small.
• The power supply cable and the indoor/outdoor connecting cable
must be fixed by means of the strip on the connection fixing
bracket so that they are not in contact with the compressor and
the hot pipes.
To ensure good tensile strength, the electric cables must be
fastened using the cable-holder on the plate.
500
Cover knockout for pipe connection
GB - 4
Rear direction
Pipe cover
Side direction
Down direction
Front direction
Strong wind
Strip
Electric parts box
Fixing plate
Piping hole
Cable-holder for
electric cables
Front panel
Loading...
+ 9 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.