Installation and servicing of air conditioning
equipment can be hazardous due to system pres
sure and electrical components. Only trained
and qualified service personnel should install,
repair or service air conditioning equipment.
Untrained personnel can perform basic main
tenance functions of cleaning coils and cleaning
and replacing filters. All other operations should bci
performed by trained service personnel. When
working on air conditioning equipment, observe
precautions in the literature, tags and labels
attached to the unit and other safety precautions
that may apply.
Follow all safety codes. Wear safety glasses and
work gloves. Use quenching cloth for brazing
operations. Have fire extinguisher available for all
brazing operations.
WARNING; Before performing service or
maioienance oj^erairon^ on system, turn off
m^n power switch to iadoor mut and out
door UJI&. Tui» off accessory heater power
switch if applicable. Eleetrical shock could
cause persoii^ injury.
ik -If MTG
SLOTS(USE ANY
2)
C=3 SPACE REQUIRED FOR SERVICE
^ CONDENSER AIRFLOW
CONCRETE MOUNTING PAD^ISQUARE OR CIRCULAR)
^CONCRETE PAD SHOULD WEIGH |-f TO 2 TIMES WEIGHT OF UNIT
*AII models except 38VH001 are supplied with a 3/4-in to
1-1/8 in suction valve connection adapter (field installed)
for 1-1/8 in suction line (field supplied)
001
0021003
165
20q 205
2- 8
3-2 3-2
1-11
2-5 2-5
5/8 1 3/41 3/41 3/4 I 3/4 | 3/4
-5-1/4
2
004
225
3- 8
2-11
3/8
045005
250
240
3- 8
3- 8
2-11
2-11
INSTALLATION
Step 1 — Check Equipment and Jobsite
UNPACKAGE UNIT — Move to final location.
Slide from carton taking special care not to damage
service valves or grilles.
INSPECT EQUIPMENT — File claim with ship
ping company if damaged or incomplete.
COMPLETE OR CONSIDER SYSTEM RE
QUIREMENTS before installation:
Consult local building codes and National
Electrical Code (NEC) for special installation
requirements.
When installing, allow sufficient space for airflow
clearance, wiring, refrigerant piping and service.
Recommended space minimum requirements are:
overhead — 4 ft, perimeter — 3 ft (Fig. 1). Position
so water from roof or eaves does not pour directly
on unit.
Install on a solid, level mounting pad. Position
tie-down bolts in pad. Any 2 holes in unit base may
be used to fasten unit to pad.
Carrier Cooling System Capacity Optimization may
require field replacement of piston in AccuRater™
(bypass type) refrigerant control supplied on evap
orator. See Table 2. Enter table at cooling system
Outdoor Air Design Temperature closest to that of
locality. Find AccuRater Piston number required
for condenser/evaporator system being installed.
Piston change is not necessary if table indicates that
required piston is factory installed in evaporator coil.
When evaporator is more than one size larger
than condensing unit (i.e. 38VH002I28AR036), re
move AccuRater and use a bleed-type thermal
expansion valve (TXV) for refrigerant control. Size
TXV to nominal capacity of condensing unit.
A replacement AccuRater piston is factory sup
plied on Models 38VHOO 1,002,003 and 004. This
piston is correctly sized for an evaporator of the
same capacity as the condensing unit at an outdoor
air design temperature of 95 F. Mix-matching and
outdoor air design temperatures other than 95 F
may require another piston number or thermal ex
pansion valve. (Refer to Table 2.)
Replace piston as required before connecting
refrigerant lines. Bypass type AccuRater com
ponents are shown in Fig. 2. Piston replacement
i Standard factory-installed AccuRater piston
*The 28VH piston designations are applicable to full temperature
range
fSize 70 piston factory supplied with 28VH004 .
NOTE: Piston numbers effective December 1, 1979
instructions are included in evaporator Installation
book. After system installation is complete, use
Chargemaster charging device or charging chart to
check and/or adjust refrigerant charge.
Condensing Units Connected to Carrier-Approved
Evaporators — Condensing units contain correct
system refrigerant charge for operation with evap
orator of same size when they are connected by 50 ft
of field-supplied tubing of recommended size (see
Piping Connections) or 50 ft or less of Carrier acces
sory tubing. Check refrigerant charge for maximum
system efficiency. See Refrigerant Charging for
details.
Fig. 2 — AccuRater (Bypass Type)
Components
Condensing Units Connected to Non-Carrier Evap
orators — Check refrigerant charge when the con
densing unit is added to a system in which other than
a Carrier-approved evaporator is to be used or
where the evaporator has been previously installed.
Check that field-supplied refrigerant piping is in
accordance with refrigerant piping data (Table 3).
Step 2 — Make Tubing Connections — Con
densing units may be connected to evaporator sec
tions using Carrier accessory tubing package or
field-supplied tubing of refrigerant grade. See Table
4 for accessory tubing sizes. Table 3 for recom
mended field-supplied tubing sizes.
Isolate interconnecting tubing from framing and
ductwork or where tubing runs thru stud spaces,
enclosed ceilings or pipe chases. Use isolation type
hanger (Fig. 3) since rigid fastening transmits pulsa
tions to structure creating objectionable sound.
A capacity and efficiency reduction results if
undersized Carrier accessory tubing is used in 38VH
systems. (Example: When a 25-ft accessory tubing
Fig. 3 — Refrigerant Line Hangers
package is used on a 38VH004 system, the smaller
suction line will result in a capacity reduction of 3%.)
For maximum capacity and efficiency from this sys
tem, use suction line recommended in Table 3.
Length of interconnecting tubing may necessitate
refrigerant charge adjustment. Follow special re
quirements described in Initial Start-Up, Refrig
erant Charging. Do not use less than 10 ft of interconnecting tubing. On Carrier accessory tubing
packages, do not cut 5/16-in. or 1 / 4-in. liquid line or
7/8-in. suction line. These tubing packages have
swaged ends. If swage at end of tubing is cut off, the
tubing will not fit into unit refrigerant line fittings.
Bend or coil excess tubing to fit.
Table 3 — Field-Supplied Tubing Data
NOTES
1 Maximum allowable vertical separation for evaporator over the
condensing unit is 50 feet
2 Over 50-ft vertical separation, the condensing unit must be
located above evaporator
3 The maximum total tubing length between units is 150 feet
REFRIGERANT LINE LENGTH (ft)
CONO
UNIT
38VH
001024
002
0030367/8
004
045
nriR
002
003
00428VH004
EVAP
SIZE
018
0305/8
024
0307/8
0367/8
0307/8
042
0361-1/8
0421-1/8
048
042
0481-1/8
0601-1/8
0481-1/8
0601-1/8
28VH0021-1/8
28VH0041-1/8
Suction
(in.)
5/8
5/8
7/8
7/8
1-1/8
1-1/8
1-1/8
10 to 50 ft
Liquid
(in.)
3/8
3/852
3/8TXV
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8TXV
3/882
3/884
3/8
3/8
3/8
4 All suction tubing must be insulated with 3/8-in thick, flexible
foam tubing (Armaflex 22 or equivalent)
5 Piston numbers effective December 1, 1979
Vertical separation from 51 to 100 feet (Condensing unit
iabove evaporator)
51 to 150 ft
Line Diameter
Indoor
Piston*
523/4
57
59
TXV
63
65
TXV
76
78
TXV
76
78
63
70
781-1/85/16
Suction
(in.)
3/4
3/4
7/85/1657 ■
7/8
7/8
1-1/8
1-1/85/1665 ■
1-1/85/16TXV ■
1-1/85/1676 U.
1-1/8
1-1/85/16TXV ■
1-1/8
1-1/8
1-1/8
1-1/8
1-1/8
1-1/85/1663 W
1-1/85/1670 W
Liquid
(in.)
5/16
5/1652 ■
5/16
5/1659 ■
5/16
5/1663 ■
5/1678 ■
3/876 ■
3/8
3/8
3/8
3/884 fm
Indoor
Piston*
TXV ■
TXV ■
78 m .
TXV »
52 ^
82 ■
78 B
*At 95 F outdoor air design temperature At other design temperatures, piston sizes may vary See Table 2
Table 4 — Accessories
PART NO.
HH01AD040
HH93AZ040
HH51AR001
HH07AT070
HH07AT074
HH93AZ076
HH01AD042
HH93AZ042
HH01YA092
HH93YZ094
38GS900102
38GS900212
38HQ900011
38UE900001
32LT900301Motormaster® Head Pressure Control Special field-installed fan motor HC42VE233 required
38GS900321Liquid Line Filter-Drier (Six 38GS900332)
Low-Voltage Control — Floneywell Deluxe Thermostat
Thermostat Subbase
Comfort Control Center (Use with FIFI01AD040)
Low-Voltage Control — Honeywell Thermostat
Thermostat Subbase (with Automatic Changeover)
Low-Voltage Control — Honeywell Thermostat
Thermostat Subbase
Low-Voltage Control — Grayson Thermostat
Thermostat Subbase
Indoor Fan Relay (Six HN61KJ210)
Low-Voltage Transformer (Six 38GS900091)
Hot Shot — domestic water pre-heater
Chillermate refrigerant-to-water heat exchanger
Liquid
Length
(ft)
153/83/8
203/83/8
253/83/8
30
35
25
303/83/8
353/83/8
50
153/83/8
20
25
303/83/8
353/83/8
403/83/8
50
OD
(in )
5/16
5/16
1/4
3/8
3/83/8
3/83/87/8
3/8
3/83/8
DESCRIPTION
TUBING*
Tube End
OD (in.)
3/8
3/8
3/8
3/8
3/8
Suctionf
OD
(in.)
5/83/4t
5/83/4t
5/83/4t
5/83/4J
5/8
5/8
3/4
3/43/4
3/4
3/4
3/4
7/8
7/8
7/8
7/8
7/8
7/8
EvapCond
3/4i
3/4i
3/43/4
3/43/4
3/43/4
3/43/4
3/4
3/4
3/4
3/43/438VH005
3/43/4
3/43/4
3/43/4
Tube End,
OD (in.)
5/838VH001
5/8
5/8
5/8
5/838VH001
5/8
5/8
3/4
3/438VH003
3/438VH004
3/438VH045
UNIT
C
All
38VH003,004,
045,005
38VH002,003,004,
045,005
All
UNIT
38VH002
38VH002
(See Note 2)
*For maximum capacities, use suction line sizes recommended in
Table 3 If accessory tubing package is used on 38VH004,045,
005 units, a reduction in capacity can result Field-supplied
1-1/8 in suction line is recommended with all 28VFI coil
installations
Do not use damaged or contaminated tubing.
Always evacuate or purge evaporator coil and
tubing system. When purging, use field-supplied
refrigerant, not unit holding charge refrigerant.
When making tubing connections, be sure to pro
vide clearance at unit for electrical connections.
REPLACE THE ACCURATER™ REFRIGER
ANT CONTROL PISTON IN THE INDOOR
COIL, if required, before connecting refrigerant
lines. See Carrier Cooling System Optimization,
page 2.
CONNECT REFRIGERANT LINES to fittings on
condensing unit suction and liquid service valves
fSuction line is insulated and has a 90 degree bend at one end
JFor 5/8-in evaporator connection, cut off 3/4-in end
NOTE Do not cut 3/8-in OD liquid lines to a length shorter than
10 feet Do not cut 5/16-or 1/4-in liquid line Do not cut 7/8-in
OD suction lines
(Fig. 1). Unit Compatible Fittings permit mechani
cal (quick connect) or sweat connections.
Models 38VH002,003,004,045,005 — When using
1-1/8 in. field-supplied suction line, remove suction
line adapter taped to compressor suction line. Sweat
connect refrigerant suction line to 1-1/8 in. end of
adapter. Be sure to provide a heat sink at the service
valve to prevent damage during sweating operation.
Connect 3/4-in. end of adapter to unit suction line
Compatible Fitting. Connect liquid refrigerant line
to unit. When a 7/8-in. field-supplied suction line
is used, provide a field-supplied 3/4-in. to 7/8-in.
suction line adapter. (Not necessary if 38LS acces
sory tubing is used.)
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.