24ACB3, 24ACC6 24APB6
Single---Stage Performancet Series Air Conditioners
with Puronr Refrigerant
1---1/2 To 5 Nominal Tons (Sizes 18 to 60)
InstallationInstructions
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory--authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions included in
literature and attached to the unit. Consult local building codes
and current editions of the National Electrical Code ( NEC ) NFPA
70. In Canada, refer to current editions of the Canadian electrical
code CSA 22.1.
Recognize safety information. This is the safety--alert symbol
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury. Understand
these signal words; DANGER, WARNING, and CAUTION. These
words are used with the safety--alert symbol. DANGER identifies
the most serious hazards which will result in severe personal injury
or death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify unsafe
practices which would result in minor personal injury or product
and property damage. NOTE is used to highlight suggestions
which will result in enhanced installation, reliability, or operation.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF position.
There may be more than 1 disconnect switch. Lock out and
tag switch with a suitable warning label.
WARNING
GENERAL
NOTE: In some cases noise in the living area has been traced to
gas pulsations from improper installation of equipment.
1. Locate unit away from windows, patios, decks, etc. where
unit operation sound may disturb customer.
2. Ensure that vapor and liquid tube diameters are appropriate
for unit capacity.
3. Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends.
4. Leave some slack between structure and unit to absorb vibration.
5. When passing refrigerant tubes through the wall, seal opening with RTV or other pliable silicon--based caulk. (See Fig.
1.)
6. Avoid direct tubing contact with water pipes, duct work,
floor joists, wall studs, floors, and walls.
7. Do not suspend refrigerant tubing from joists and studs with
a rigid wire or strap which comes in direct contact with
tubing. (See Fig. 1.)
8. Ensure that tubing insulation is pliable and completely surrounds vapor tube.
9. When necessary, use hanger straps which are 1 in. (25.4
mm) wide and conform to shape of tubing insulation. (See
Fig. 1.)
10. Isolate hanger straps from insulation by using metal sleeves
bent to conform to shape of insulation.
Avoid contact between tubing and structureNOTE:
OUTDOOR WALL
CAULK
INSULATION
THROUGH THE WALL
HANGER STRAP
(AROUND VAPOR
TUBE ONLY)
INDOOR WALL
LIQUID TUBE
VAPOR TUBE
JOIST
INSULATION
VAPOR TUBE
!
WARNING
EXPLOSION HAZARD
Failure to follow this warning could
result in death, serious personal injury,
and/or property damage.
Never use air or gases containing
oxygen for leak testing or operating
refrigerant compressors. Pressurized
mixtures of air or gases containing
oxygen can lead to an explosion.
1” (25.4 mm) MIN.
Fig. 1 -- Piping Installation
SUSPENSION
LIQUID TUBE
A94026
For proper unit operation, check refrigerant charge using charging
information located on control box cover and/or in the Check
Charge section of this instruction.
IMPORTANT: Maximum liquid --line size is 3/8--in. OD for all
residential applications including long line. Refer to Residential
Piping and Longline Guideline for further information.
IMPORTANT: Always install the factory--supplied liquid--line
filter drier. If replacing the filter drier, refer to Product Data Digest
for appropriate part number. Obtain replacement filter driers from
your distributor or branch.
INSTALLATION
IMPORTANT: Effective January 1, 2015, all split system and
packaged air conditioners must be installed pursuant to applicable
regional efficiency standards issued by the Department of Energy.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and
wear appropriate protective clothing and gloves when
handling parts.
Check Equipment and Job Site
UNPACK UNIT
Move to final location. Remove carton taking care not to damage
unit.
Inspect Equipment
File claim with shipping company prior to installation if shipment
is damaged or incomplete. Locate unit rating plate on unit corner
panel. It contains information needed to properly install unit.
Check rating plate to be sure unit matches job specifications.
Install on a Solid, Level Mounting Pad
If conditions or local codes require the unit be attached to pad, tie
down bolts should be used and fastened through knockouts
provided in unit base pan. Refer to unit mounting pattern in Fig. 2
to determine base pan size and knockout hole location.
For hurricane tie downs, contact local distributor for details and PE
(Professional Engineer) certification, if required by local
authorities.
On rooftop applications, mount on level platform or frame. Place
unit above a load--bearing wall and isolate unit and tubing set from
structure. Arrange supporting members to adequately support unit
and minimize transmission of vibration to building. Consult local
codes governing rooftop applications.
Roof mounted units exposed to winds may require wind baffles.
Consult the Application Guideline and Service Manual -Residential Split System Air Conditioners and Heat Pumps for
wind baffle construction.
NOTE: Unit must be level to within 2_ (3/8 in./ft.) per
compressor manufacturer specifications.
Clearance Requirements
When installing, allow sufficient space for airflow clearance,
wiring, refrigerant piping, and service. Allow 24 in. (609.6 mm)
clearance to service end of unit and 48 in. (1219.2 mm) (above
unit. For proper airflow, a 6-- in. (152.4 mm) clearance on 1 side of
unit and 12--in. (304.8 mm) on all remaining sides must be
maintained. Maintain a distance of 24 in. (609.6 mm) between
units. Position so water, snow, or ice from roof or eaves cannot fall
directly on unit.
On rooftop applications, locate unit at least 6 in. (152.4 mm) above
roof surface.
Operating Ambient
The minimum outdoor operating ambient in cooling mode without
accessory is 55_F (12.78_C). The maximum outdoor operating
ambient in cooling mode is 125_F (51.7_C) for non--13 SEER
models and 115_F (46.11_C) for 13 SEER models.
Make Piping Connections
!
PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could result in personal injury
or death.
Relieve pressure and recover all refrigerant before system
repair or final unit disposal. Use all service ports and open
all flow--control devices, including solenoid valves.
Federal regulations require that you do not vent refrigerant
to the atmosphere. Recover during system repair or final
unit disposal.
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
If ANY refrigerant tubing is buried, provide a 6-- in. vertical
rise at service valve. Refrigerant tubing lengths up to 36--in.
may be buried without further special consideration. Do not
bury lines more than 36--in. (914.4 mm).
UNIT BASE PAN
Dimension in. (mm)
23---1/2 X 23---1/2
(596.9 X 596.9)
26 X 26
(660.4 X 660.4)
31–1/2 X 31–1/2
(800.1 X 800.1)
35 X 35
(889 X 889)
Fig. 2 -- Tiedown Knockout Locations
Outdoor units may be connected to indoor section using accessory
tubing package or field--supplied refrigerant grade tubing of correct
size and condition. Rated tubing diameters shown in Table 1 are
recommended up to 80 ft. (24.38 m). See Product Data for
acceptable alternate vapor diameters and associated capacity losses.
For tubing requirements beyond 80 ft. (24.38 m), substantial
capacity and performance losses can occur. Following the
recommendations in the Longline Guideline will reduce these
losses. Refer to Table 1 for field tubing diameters. Refer to Table 5
for accessory requirements.
WARNING
CAUTION
3/8---in. (9.53 mm) Dia.
Tiedown Knockouts in
Basepan(2) Places
View From Top
TIEDOWN KNOCKOUT LOCATIONS in. (mm)
ABC
7---13/16 (198.4) 4–7/16 (112.7) 18–1/16 (458.8)
9–1/8 (231.8)4–7/16 (112.7)21–1/4 (539.8)
9–1/8 (231.8)6–9/16 (166.7) 24–11/16 (627.1)
9–1/8 (231.8)6–9/16 (166.7) 28–7/16 (722.3)
A05177
2
There are no buried--line applications greater than 36--in. (914.4
T
mm) allowed.
If refrigerant tubes or indoor coil are exposed to atmosphere, they
must be evacuated to 500 microns to eliminate contamination and
moisture in the system.
Outdoor Unit Connected to Factory Approved Indoor
Unit
Outdoor unit contains correct system refrigerant charge for
operation with factory approved AHRI rated indoor unit when
connected by 15 ft. (4.57 m) of field --supplied or factory--accessory
tubing, and factory supplied filter drier. Check refrigerant charge
for maximum efficiency.
Refrigerant Tubing Connection Outdoor
Connect vapor and liquid tubes to fittings on vapor and liquid
service valves (see Table 1). Use refrigerant grade tubing
Sweat Connection
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Service valves must be wrapped in a heat--sinking material
such as a wet cloth while brazing.
CAUTION
Install Liquid--Line Filter Drier Indoor
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
1. Installation of filter drier in liquid line is required.
2. Filter drier must be wrapped in a heat--sinking material
such as a wet cloth while brazing.
Refer to Fig. 3 and install filter drier as follows:
1. Braze 5--in. liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to above 5--in. (127 mm) liquid tube.
Flow arrow must point towards indoor coil.
4. Connect and braze liquid refrigerant tube to the filter drier.
CAUTION
Use refrigeration grade tubing. Service valves are closed from
factory and ready for brazing. After wrapping service valve with a
wet cloth, braze sweat connections using industry accepted
methods and materials. Consult local code requirements.
Refrigerant tubing and indoor coil are now ready for leak testing.
This check should include all field and factory joints.
Table 1 – Refrigerant Connections and Recommended Liquid
and Vapor Tube Diameters (In.)
24ACB
LIQUID
UNIT SIZE
18, 243/83/43/4
30, 363/83/43/4
42, 483/87/87/8
603/87/81 --- 1 / 8
UNIT SIZE
18, 24, 303/83/43/4
36, 42, 483/87/87/8
603/87/81 --- 1 / 8
* Units are rated with 25 ft. (7.6 m) of lineset. See Product Data sheet for
performance data when using different size and length linesets.
Notes:
1. Do not apply capillary tube to these units.
2. For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m)
horizontal or 35 ft. (10.7 m) vertical differential 250 ft. (76.2 m) Total
Equivalent Length), refer to the Residential Piping and Longline Guide
line--- Air Conditioners and Heat Pumps using Puron refrigerant.
3. For alternate liquid line options on 18 ---42 size units, see Product Data or
Residential Piping and Application Guideline
Connection
&Tube
Diameter
24ACC, 24APB
LIQUID
Connection
&Tube
Diameter
RATED VAPOR
up to 80 ft. (24.38 m)*
Connection
Diameter
RATED VAPOR
up to 80 ft. (24.38 m)*
Connection
Diameter
Tub e
Diameter
Tub e
Diameter
A05178
Fig. 3 -- Liquid Line Filter Drier
Evacuate Refrigerant Tubing and Indoor Coil
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Never use the system compressor as a vacuum pump.
Refrigerant tubes and indoor coil should be evacuated using the
recommended deep vacuum method of 500 microns. The alternate
triple evacuation method may be used (see triple evacuation
procedure in service manual). Always break a vacuum with dry
nitrogen.
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of
pulling a vacuum of 500 microns and a vacuum gage capable of
accurately measuring this vacuum depth. The deep vacuum method
is the most positive way of assuring a system is free of air and
liquid water. A tight dry system will hold a vacuum of 1000
microns after approximately 7 minutes. See Fig. 4.
5000
4500
4000
3500
3000
2500
MICRONS
2000
1500
1000
500
01234567
MINUTES
Fig. 4 -- Deep Vacuum Graph
LEAK IN
SYSTEM
VACUUM TIGH
TOO WET
TIGHT
DRY SYSTEM
A95424
3
Loading...
+ 7 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.