24ACC6
Performancet16 Air Conditioner
with Puronr Refrigerant
1 --- 1 / 2 to 5 To n s
Product Data
the environmentally sound refrigerant
Carrier’s Air Conditioners with Puronr refrigerant provide a
collection of features unmatched by any other family of
equipment. The 24ACC has been designed utilizing Carrier’s
Puron refrigerant. The environmentally sound refrigerant allows
you to make a responsible decision in the protection of the earth’s
ozone layer.
This product has been designed and manufactured to meet
Energy Starr criteria for energy efficiency when matched with
appropriate coil components. Refer to the combination ratings in
the Product Data for system combinations that meet Energy Starr
guidelines.
NOTE: Ratings contained in this document are subject to
change at any time. Always refer to the AHRI directory
(www.ahridirectory.org) for the most up--to--date ratings
information.
INDUSTRY LEADING
FEATURES / BENEFITS
Efficiency
14 -- 16.5 SEER / 11.5-- 13.5 EER
S
SMicrotube Technologyt refrigeration system
SIndoor air quality accessories available
deplete the ozone layer and low lifetime servce cost.
SScroll compressor
SInternal pressure relief valve
SInternal thermal overload
SFilter drier
SHigh and low pressure switches
SBalanced refrigeration system for maximum reliability
Durability
WeatherArmor Ultrat protection package:
SSolid, durable sheet metal construction
SLouvered coil guard
SBaked--on, complete outer coverage, powder paint
Applications
Long--line -- up to 250 feet (76.20 m) total equivalent
S
length, up to 200 feet (60.96 m) condenser above
evaporator, or up to 80 ft. (24.38 m) evaporator above
condenser (See Longline Guide for more information.)
SLow ambient (down to --20_F/--28.9_C)) with
accessory kit
MODEL NUMBER NOMENCLATURE
123 4 567891011 1213
NNAAA/NNNNA/NA/NA/NNN
24ACC636A 0030
Product
Series
24=ACA=RES AC C=Performance C=Puron 6=16 SEERA = Standard
the environmentally sound refrigerant
24ACC6
Product
Famil y
Tier
Use of the AHRI Certified
TM Mark indicates a
manufacturer’s
participation in the
program For verification
of certification for individual
products, go to
www.ahridirectory.org.
Major
Series
SEER
Cooling
Capacity
Grille
Variations
OpenOpenVoltageSeries
0=Not
Defined
0=Not
Defined
This produc t h as been desi gned and manufact ured to
meet Energy S tar® criteria for energy efficiency when
matched wi th appropriate coi l com ponents. However,
proper refri gerant charge and proper ai r flow are cri tical
to achieve rated capacity and efficiency. Installation of
this product should foll ow all manufacturing refrigerant
charging and air flow instructions. Failure to confirm
proper charge and air flow may reduce energy
efficiency and shorten equipment life.
* Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset.
Note: See unit Installation Instruction for proper installation.
{ See Liquid Line Sizing For Cooling Only Systems with Puron Refrigerant tables.
Liquid Line Sizing and Maximum Total Equivalent Lengths
The maximum allowable length of a residential split system depends on the liquid line diameter and vertical separation between indoor and
outdoor units.
See Table below for liquid line sizing and maximum lengths :
Maximum Total Equivalent Length
Outdoor Unit BELOW Indoor Unit
Liquid
Size
18000
AC with
Puron
24000
AC with
Puron
30000
AC with
Puron
36000
AC with
Puron
42000
AC with
Puron
48000
AC with
Puron
60000
AC with
Puron
* Maximum actual length not to excee d 200 ft (61 m)
{ T otal equivalent length accounts for losses due to elbows or fitting. See the Long Line G uideline for details.
--- --- = o u t s i d e a c c e p t a b l e r a n g e
AC with Puron Refrige rant Maximum T otal Equivalent Length{: Outdoor unit BELOW Indoor
0 --- 5
6 --- 1 0
(1.8--- 3.0)
11--- 20
(3.4--- 6.1)
{
for Cooling Only Systems with Puronr Refrigerant:
Vertical Separation ft (m)
21--- 30
(6.4--- 9.1)
31--- 40
(9.4--- 12.2)
41--- 50
(12.5--- 15.2)
51--- 60
(15.5--- 18.3)
(18.6--- 21.3)
61--- 70
71--- 80
(21.6--- 24.4)
24ACC6
Maximum Total Equivalent Length
Outdoor Unit ABOVE Indoor Unit
Liquid
Size
18000
AC with
Puron
24000
AC with
Puron
30000
AC with
Puron
36000
AC with
Puron
42000
AC with
Puron
48000
AC with
Puron
60000
AC with
Puron
* Maximum actual length not to exceed 200 ft (61 m)
{ T otal equivalent length accounts for losses due to elbows or fitting. See the Long Line G uideline for details.
--- --- = o u t s i d e a c c e p t a b l e r a n g e
AC with Puron Refrige rant Maximum T otal Equivalent Length{: Outdoor unit ABOVE Indoor
25
(7.6)
26--- 50
(7.9--- 15.2)
51--- 75
(15.5--- 22.9)
Vertical Separation ft (m)
76--- 100
(23.2--- 30.5)
101--- 125
(30.8--- 38.1)
126--- 150
(38.4--- 45.7)
151--- 175
(46.0--- 53.3)
176--- 200
(53.6--- 61.0)
3
REFRIGERANT CHARGE ADJUSTMENTS
Liquid Line SizePuron Charge oz/ft
3/8
5/160.40
1/40.27
(Factory charge for lineset = 9 oz)
0.60
Units are factory charged for 15 ft (4.6 m) of 3/8” liquid line. The factory charge for 3/8” lineset 9 oz. When using other length or diameter
liquid lines, charge adjustments are required per the chart above.
Charging
Formula:
[(Lineset oz/ft x total length) – (factory charge for lineset)] = charge adjustment
Example 1: System has 15 ft of line set using existing 1/4“ liquid line. What charge adjustment is required?
Formula:(.27 oz/ft x 15ft) – (9 oz) = (-4.95) oz.
Net result is to remove 4.95 oz of refrigerant from the system
Example 2: System has 45 ft of existing 5/16” liquid line. What is the charge adjustment?
Formula:(.40 oz/ft. x 45ft) – (9 oz.) = 9 oz.
Net result is to add 9 oz of refrigerant to the system
LONG LINE APPLICATIONS
An application is considered Long Line, when the refrigerant level in the system requires the use of accessories to maintain acceptable
24ACC6
refrigerant management for systems reliability. See Accessory Usage Guideline table for required accessories. Defining a system as long line
depends on the liquid line diameter, actual length of the tubing, and vertical separation between the indoor and outdoor units.
For Air Conditioner systems, the chart below shows when an application is considered Long Line.
AC WITH PURONr REFRIGERANT LONG LINE DESCRIPTION ft (m)
Beyond these lengths, long line accessories are required
Liquid Line SizeUnits On Same LevelOutdoor Below IndoorOutdoor Above Indoor
1/4
5/16120 (36.6)50 (15.2)120 (36.6)
3/880 (24.4)35 (10.7)80 (24.4)
Note: SeeLongLineGuidelinefordetails
No accessories needed within allowed
lengths
No accessories needed within allowed
lengths
175 (53.3)
VAPOR LINE SIZING AND COOLING CAPACITY LOSS
Acceptable vapor line diameters provide adequate oil return to the compressor while avoiding excessive capacity loss. The suction line
diameters shown in the chart below are acceptable for AC systems with Puron refrigerant:
Unit
Nominal
Size (Btuh)
18000
1Stage
AC with
Puron
24000
1Stage
AC with
Puron
30000
1Stage
AC with
Puron
36000
1Stage
AC with
Puron
42000
1Stage
AC with
Puron
48000
1Stage
AC with
Puron
60000
1Stage
AC with
Puron
Applications in this area may be long line and may have heigh t restrictions. See the Residential Piping and Long Line Guideline.
Maximum
Liquid Line
Diameters
(In. OD)
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Vapo r Line
Diameters
(In. OD)
1/21235678911
5/8011122233
3/4000011111
5/8012233455
3/4001111122
7/8000001111
5/8123345678
3/4001112223
7/8000011111
5/812456891012
3/4011223344
7/8000111122
3/4012234456
7/8001112223
11/8000000000
3/4012345567
7/8001122233
11/8000000011
3/412456791011
7/8012234455
11/8000111111
26---50
(7.9--- 15.2)
51---80
(15.5--- 24.4)
81---100
(24.7--- 30.5)
Cooling Capacity Loss (%)
Total Equivalent Line Length ft. (m)
101---125
(30.8--- 38.1)
126---150
(38.4--- 45.7)
151---175
(46.0--- 53.3)
176---200
(53.6--- 61.0)
201---225
(61.3--- 68.6)
226---250
(68.9--- 76.2)
4
ACCESSORY THERMOSTATS
PAR T N UMB ERPROGRAMGASELECTRICHEAT PUMP
Perfor mance
T P --- P R H 0 1 --- A7 --- D a y
T P --- PA C 0 17 --- D a y
T P --- N R H 0 1 --- ANP
T P --- N A C 0 1NP
PAR T N UMB ERBRIEF DESCRIPTIONTHERMOSTATS USED WITH
SYSTXCCRRS01Indoor Remote Room Temperature SensorA l l T P --- t h e r m o s t a t s
T P --- E X P 0 1 --- AExP Computer Programming AccessoryTP--- P thermostats
{ Required accessories include ball bearing fan motor, compressor start assist (CAP / Relay), crankcase heater, evaporator freeze stat, hard shut ---off TXV.
X = Accessory / S --- Standard
24ACC6
5
ACCESSORY USAGE GUIDELINE
REQUIRED FOR LOW ---AMBI-
ACCESSORY
Ball Bearing Fan MotorYes{NoNo
Compressor Start Assist Capacitor and R elayYesYesNo
Crankcase HeaterYesYe sNo
Evaporator Freeze ThermostatYe sNoNo
H a r d S h u t --- O f f T X VYesYe sYes
Liquid Line Solenoid ValveNoNoNo
Motor Master®Control or
L o w --- a m b i e n t P r e s s u r e S w i t c h
Support FeetRecommendedNoRecommended
* For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. (6.09 m) vertical differential, refer to Residential Split ---System Longline
Accessory Description and Usage (Listed Alphabetically)
1. Ball--Bearing Fan Motor
A fan motor with ball bearings which permits speed reduction
24ACC6
while maintaining bearing lubrication.
Usage Guideline:
Required on all units when MotorMasterris used.
2. Compressor Start Assist -- Capacitor and Relay
Start capacitor and relay gives a ”hard” boost to compressor
motor at each start up.
Usage Guideline:
Required for reciprocating compressors in the
following applications:
Long line
Low ambient cooling
Hard shut off expansion valve on indoor coil
Liquid line solenoid on indoor coil
Required for single--phase scroll compressors in the
following applications:
Long line
Low ambient cooling
Suggested for all compressors in areas with a history of
low voltage problems.
3. Compressor Start Assist — PTC Type
Solid state electrical device which gives a ”soft” boost to the
compressor at each start--up.
Usage Guideline:
Suggested in installations with marginal power supply.
4. Crankcase Heater
An electric resistance heater which mounts to the base of the
compressor to keep the lubricant warm during off cycles.
Improves compressor lubrication on restart and minimizes the
chance of liquid slugging.
Usage Guideline:
Required in low ambient cooling applications.
Required in long line applications.
Suggested in all commercial applications.
5. Cycle Protector
The cycle protector is designed to prevent compressor short
cycling. This control provides an approximate 5--minute delay
after power to the compressor has been interrupted for any
reason, including power outage, protector control trip, thermostat
jiggling, or normal cycling.
6. Evaporator Freeze Thermostat
An SPST temperature--actuated switch that stops unit operation
when evaporator reaches freeze--up conditions.
7. Low--Ambient Pressure Switch Kit
A long life pressure switch which is mounted to outdoor unit
service valve. It is designed to cycle the outdoor fan motor in
order to maintain head pressure within normal operating limits
(approximately 100 psig to 225 psig). The control will maintain
working head pressure at low--ambient temperatures down to 0_F
(--18_C) when properly installed.
Low--Ambient Controller must be used when cooling operation is
used at outdoor temperatures below 55_F (12.8_C).
8. MotorMasterr Low--Ambient Controller
A fan--speed control device activated by a temperature sensor,
designed to control condenser fan motor speed in response to the
saturated, condensing temperature during operation in cooling
mode only. For outdoor temperatures down to --20_F (--28.9_C),
it maintains condensing temperature at 100_F ±10_F (37.8_C ±
5.5_C).
9. Outdoor Air Temperature Sensor
Designed for use with Carrier Thermostats listed in this
publication. This device enables the thermostat to display the
outdoor temperature. This device also
is required to enable special thermostat features such as auxiliary
heat lock out.
REQUIRED FOR LONG
LINE
APPLICATIONS*
(Over 80 ft./24.38 m)
(Within2miles/3.22km)
Usage Guideline:
Required when low ambient kit has been added.
Usage Guideline:
A Low--Ambient Pressure Switch or MotorMasterr
Usage Guideline:
A MotorMasterrLow Ambient Controller or
Low--Ambient Pressure Switch must be used when
cooling operation is used at outdoor temperatures
below 55_F (12.8_C).
Suggested for all commercial applications.
Usage Guideline:
Suggested for all Carrier thermostats listed in this
publication.
REQUIRED FOR
SEA COAST
APPLICATIONS
6
Accessory Description and Usage (Listed Alphabetically) (Continued)
10. Support Feet
Four stick--on plastic feet that raise the unit 4 in. (101.6 mm)
above the mounting pad. This allows sand, dirt, and other debris
to be flushed from the unit base, minimizing corrosion.
Usage Guideline:
Suggested in the following applications:
Coastal installations.
Windy areas or where debris is normally circulating.
Rooftop installations.
For improved sound ratings.
11. Thermostatic Expansion Valve (TXV)
A modulating flow--control valve which meters refrigerant liquid
flow rate into the evaporator in response to the superheat of the
refrigerant gas leaving the evaporator.
Kit includes valve, adapter tubes, and external equalizer tube.
Hard shut off types are available.
NOTE: When using a hard shut off TXV with single phase
reciprocating compressors, a Compressor Start Assist Capacitor
and Relay is required.
Usage Guideline:
Required to achieve AHRI ratings in certain equipment
combinations. Refer to combination ratings.
Hard shut off TXV or LLS required in air conditioner
long line applications.
Required for use on all zoning systems.
12. Time--Delay Relay
An SPST delay relay which briefly continues operation of indoor
blower motor to provide additional cooling after the compressor
cycles off.
NOTE: Most indoor unit controls include this feature. For those
that do not, use the guideline below.
Usage Guideline:
For improved efficiency ratings for certain
combinations of indoor and outdoor units. Refer to
AHRI Unitary Directory.
13. Winter Start Control
This control is designed to alleviate nuisance opening of the
low--pressure switch by bypassing it for the first 3 minutes of
operation.
* Permissible limits of the voltage range at which the un it will oper ate satisfactorily
{ If wire is applied at ambient greater than 30_C, consult table 310---16 of the NEC (NFPA 70). The ampacity of non ---metallic ---sheathed cable (NM), trade
name ROMEX, shall be that of 60_C conditions, per the NEC (NFPA 70) Article 336 ---26. If other than uncoated (no ---plated), 60 or 75_C insulation, copper
wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (NFPA 70).
}Length shown is as measured one way along wire path between unit and service panel for voltage drop not to exceed 2%.
* * T i m e --- D e l a y f u s e .
FLA --- Fu l l L o a d A m p s
LRA --- L o c k e d Ro t o r A m p s
MCA --- Min imum Circuit Amps
RLA ---RatedLoadAmps
NOTE: Control circuit is 24 ---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
Complies with 2010 requirements of ASHRAE Standards 90.1
24ACC6600XOOO35"45 15/16"3 7/8"7/8"6 9/16"28 7/16"9 1/8"2 15/16"5/8"17 7/8"18 5/8"20 1/4"33737236 1/8" X 39 5/16" X 49 9/16"
DIMENSIONS -- ENGLISH
9
AIR IN
F
SHIPPING
N
E
DIMENSIONS (L x W x H)
AIR
SHIPPING
DISCHARGE
WEIGHT (Kgs)
C, MAX. 52
OPERATING
WEIGHT (Kgs)
24ACC6
NOTES:
1219.2 ABOVE UNIT, 152.4 ON ONE SIDE, 304.8 ON REMAINING SIDE,
AND 609.6 BETWEEN UNITS FOR PROPER AIRFLOW.
1. ALLOW 762.0 CLEARANCE TO SERVICE SIDE OF UNIT,
MODE IS 13
2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING
UNIT MODEL NUMBER.
3. SERIES DESIGN ATION IS THE 10TH POSITION OF THE
4. CENTER OF GRAVITY .
AIR IN
5. ALL DIMEN SIONS ARE IN "MM" UNLESS N OTED.
M
G
AIR IN
K
(2) PLACES
8.0
ABCDEFGKLMNP
ELECTRICAL
CHARACTERISTICS
X = YES
L
AIR IN
76.2
9.53 TIEDOWN KNOCKOUTS
P
47.6
SQ.
A
AIR DISCHARGE
O=NO
460-3-60
208/230-3-60
230-1-60
208-230-1-60
22.23 HOLE
SUPPLY CONN.
FIELD CONTROL
28.58 KNOCKOUT
22.23 HOLE WITH
FIELD POWER SUPPLY CONN.
88.9
C
B
MINIMUM
DIMENSIONS
MOUNTING PAD
D
VAPOR LINE C ONN.
18660.4 X 660.4
24,30800.1 X 800.1
UNIT SIZE
36 THRU 60889.0 X 889.0
UNITSERIES
24ACC6180XOOO654.0728.795.219.0112.7539.8198.471.412.7336.6349.3323.961.773.9682.6 X 763.6 X 827.1
24ACC6240XOOO792.2719.295.219.0166.7627.1231.871.412.7396.9393.7355.673.989.8822.3 X 901.7 X 827.1
24ACC6300XOOO792.2820.895.219.0166.7627.1231.871.412.7419.1381.0374.775.792.5822.3 X 901.7 X 912.8
24ACC6360XOOO889.0719.298.622.2166.7722.3231.874.615.9463.6428.6355.681.699.3917.6 X 998.6 X 827.1
24ACC6420XOOO889.0993.898.622.2166.7722.3231.874.615.9457.2406.4444.5106.1127.5917.6 X 998.6 X 1085.8
24ACC6480XOOO889.0820.898.622.2166.7722.3231.874.615.9431.8444.5355.6112.5132.0917.6 X 998.6 X 912.8
24ACC6600XOOO889.01166.898.622.2166.7722.3231.874.615.9454.0473.1514.4152.9168.7917.6 X 998.6 X 1173.2
DIMENSIONS -- SI
10
Wall
6”
(152.4)
24”
Wall
Clearances (various examples)
Service
12”
(304.8)
6”
Wall
(152.4 mm)
12”
(304.8)
12”
(304.8)
12”
(304.8)
Wall
24”
(609.6)
24”
(609.6)
24”
(609.6)
Service
Service
Service
24ACC6
24”
(609.6)
24”
(609.6)
CLEARANCES
24”
(609.6)
Service
11
24”
(609.6)
Note: Numbers in ( ) = mm
IMPORTANT: When installing multiple units in an alcove, roof well, or partially enclosed area, ensure there is adequate ventilation to prevent re--circulation of discharge air.
TESTED AHRI COMBINATION RATINGS*
NOTE: Ratings contained in this document are subject to change at any time.
For AHRI ratings certificates, please refer to the AHRI directory www.ahridirectory.org
Additional ratings and system combinations can be accessed via the Carrier database at:
* AHRI = Air Conditioning, Heating & Refrigeration Institute
EER — Energy Efficiency Ratio --- ’A’ conditions --- 80_F(26.6_C) indoor db/67_F (19.4_C) indoor wb & 95_F(35_C) outdoor wb.
SEER — Seasonal Energy Efficiency Ratio
TDR — Time ---Delay Relay. In most cases, only one method should be used to achieve TDR function. Using more than one method in a system may cause degradation in
performance. Use either the accessory Time ---Delay Relay, KAATD0101TDR, or a furnace equipped with TDR. Most Carrier furnaces are equipped with TDR.
NOTES:
1. Ratings are net values reflecting the effects of circulating fan motor heat. Supplemental electric heat is not included.
24ACC6
2. Tested outdoor/indoor combinations have been tested in accordance with DOE test procedures for central air conditioners. Ratings for other
combinations are determined under DOE computer simulation procedures.
3. Determine actual CFM values obtainable for your system by referring to fan performance data in fan coil or furnace coil literature.
4. Do not apply with capillary tube coils as performance and reliability are significantly affected.
ch.php
http://rpmob.wrightsoft.com/
12
Total
KW**
System
Total
KW**
System
Capacity MBtuh
To tal
System
Capacity MBtuh
To tal
System
Capacity MBtuh
To tal
System
Capacity MBtuh
KW**
KW**
KW**
To tal
System
Capacity MBtuh
To tal
System
Capacity MBtuh
To tal
System
KW**
KW**
KW**
24ACC6
CONDENSER ENTERING AIR TEMPERATURES ° F (° C)
Capacity MBtuh
24ACC618A**30 Outdoor Section With CNPV*1917A** Indoor Section
{ Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
# Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per AHRI standard 210/240 --- 2008. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may
occur.
(27_C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air per degree above 80_F(27_C).
} Sensible capacities shown are based on 80_F(27_C) entering air at the indoor coil. For sensible capacities at other than 80_F(27_C), deduct 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80_F
EWB —EnteringWetBulb
** System kw is total of indoor and outdoor unit kilowatts.
{{ At TVA rating indoor condition (75_F edb/63_F ewb). All other indoor air temperatures are at 80_F edb.
Outdoor--mounted, air--cooled, split--system air conditioner unit
suitable for ground or rooftop installation. Unit consists of a
hermetic compressor, an air--cooled coil, propeller--type
condenser fan, and a control box. Unit will discharge supply air
upward as shown on contract drawings. Unit will be used in a
refrigeration circuit to match up to a packaged fan coil or coil
unit.
Quality Assurance
— Unit will be rated in accordance with the latest edition
of AHRI Standard 210.
— Unit will be certified for capacity and efficiency, and
listed in the latest AHRI directory.
— Unit construction will comply with latest edition of
ANSI/ ASHRAE and with NEC.
— Unit will be constructed in accordance with UL
standards and will carry the UL label of approval. Unit
will have c--UL--us approval.
— Unit cabinet will be capable of withstanding Federal
Test Method Standard No. 141 (Method 6061) 500--hr
salt spray test.
— Air--cooled condenser coils will be leak tested at 150
psig and pressure tested at 450 psig.
— Unit constructed in ISO9001 approved facility.
Delivery, Storage, and Handling
— Unit will be shipped as single package only and is
Factory assembled, single piece, air--cooled air conditioner unit.
Contained within the unit enclosure is all factory wiring, piping,
controls, compressor, refrigerant charge Puronr (R--410A), and
special features required prior to field start--up.
Cabinet
Unit
— Unit cabinet will be constructed of galvanized steel,
bonderized, and coated with a powder coat paint.
AIR--COOLED, SPLIT--SYSTEM AIR CONDITIONER
1--1/2 TO 5 NOMINAL TONS
Fans
— Condenser fan will be direct--drive propeller type,
discharging air upward.
— Condenser fan motors will be totally enclosed, 1--phase
type with class B insulation and permanently lubricated
bearings. Shafts will be corrosion resistant.
— Fan blades will be statically and dynamically balanced.
— Condenser fan openings will be equipped with coated
steel wire safety guards.
Compressor
— Compressor will be hermetically sealed.
— Compressor will be mounted on rubber vibration
isolators.
Condenser
Refrigeration
Operating Characteristics
Electrical Requirements
Special Features
Coil
— Condenser coil will be air cooled.
— Coil will be constructed of aluminum fins mechanically
bonded to copper tubes which are then cleaned,
dehydrated, and sealed.
Components
— Refrigerationcircuitcomponentswillinclude
liquid--line shutoff valve with sweat connections,
vapor--line shutoff valve with sweat connections,
system charge of Puronr (R--410A) refrigerant, and
compressor oil.
— Unit will be equipped with high--pressure switch, low
pressure switch and filter drier for Puron refrigerant.
— The capacity of the unit will meet or exceed _____
Btuh at a suction temperature of _____ _F/_C. The
power consumption at full load will not exceed _____
kW.
— Combination of the unit and the evaporator or fan coil
unit will have a total net cooling capacity of _____
Btuh or greater at conditions of _____ CFM entering
air temperature at the evaporator at _____ _F/_Cwet
bulb and _____ _F/_C dry bulb, and air entering the
unit at _____ _F/_C.
— The system will have a SEER of _____ Btuh/watt or
greater at DOE conditions.
— Nominal unit electrical characteristics will be _____ v,
single phase, 60 hz. The unit will be capable of
satisfactory operation within voltage limits of _____ v
to _____ v.
— Unit electrical power will be single point connection.
— Control circuit will be 24v.
— Refer to section of this literature identifying accessories
and descriptions for specific features and available
enhancements.
24ACC6
24ACC6
19
SYSTEM DESIGN SUMMARY
1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01--in. wc.
2. Minimum outdoor operating air temperature for cooling mode without low--ambient operation accessory is 55_F (12.8_C).
3. Maximum outdoor operating air temperature is 125_F (51.7_C).
4. For reliable operation, unit should be level in all horizontal planes.
5. For interconnecting refrigerant tube lengths greater than 80 ft (23.4 m) and/or 35 ft (10.7 m) vertical differential, consult Residential
Piping and Longline Guideline and Service Manual available from equipment distributor.
6. If any refrigerant tubing is buried, provide a 6 in. (152.4 mm) vertical rise to the valve connections at the unit. Refrigerant tubing
lengths up to 36 in. (914.4 mm) may be buried without further consideration. Do not bury refrigerant lines longer than 36 in. (914.4
mm).
7. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector
provided.
8. Do not apply capillary tube indoor coils to these units.
9. Factory--supplied filter drier must be installed.
24ACC6
Copyright 2012 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Edition Date: 09/12
20
Catalog No: 24ACC6 --- 4PD
Replaces: 24ACC6 --- 3PD
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.