Carrier 19XRT User Manual

19XRT
Hermetic Centrifugal Liquid Chillers
50/60 Hz
with PIC II Controls and HFC-134a
Start-Up, Operation, and Maintenance Instructions
SAFETY CONSIDERATIONS
Centrifugal liquid chillers are designed to provide safe and reliable service when operated within design speci­fications. When operating this equipment, use good judg­ment and safety precautions to avoid damage to equip­ment and property or injury to personnel.
Be sure you understand and follow the procedures and safety precautions contained in the chiller instructions as well as those listed in this guide.
DO NOT VENT refrigerant relief valves within a building. Outlet from rupture disc or relief valve must be vented outdoors in ac­cordance with the latest edition of ANSI/ASHRAE 15 (American National Standards Institute/American Society of Heating, Refrig­eration, and Air Conditioning Engineers). The accumulation of re­frigerant in an enclosed space can displace oxygen and cause asphyxiation.
PROVIDE adequate ventilation in accordance with ANSI/ASHRAE 15, especially for enclosed and low overhead spaces. Inhalation of high concentrations of vapor is harmful and may cause heart ir­regularities, unconsciousness, or death. Misuse can be fatal. Vapor is heavier than air and reduces the amount of oxygen available for breathing. Product causes eye and skin irritation. Decomposition products are hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a chiller for any purpose. Oxygen gas reacts violently with oil, grease, and other common substances.
NEVER EXCEED specified test pressures, VERIFY the allowable test pressure by checking the instruction literature and the design pressures on the equipment nameplate.
DO NOT USE air for leak testing. Use only refrigerant or dry nitrogen.
DO NOT VALVE OFF any safety device. BE SURE that all pressure relief devices are properly installed and
functioning before operating any chiller.
DO NOT WELD OR FLAMECUT any refrigerant line or vessel until all refrigerant (liquid andvapor)hasbeenremovedfromchiller. Traces of vapor should be displaced with dry air or nitrogen and the work area should be well ventilated. Refrigerant in contact with
an open flame produces toxic gases.
DO NOT USE eyebolts or eyebolt holes to rig chiller sections or the entire assembly.
DO NOT work on high-voltage equipment unless you are a quali­fied electrician.
DO NOTWORKON electrical components, including control pan­els, switches, starters, or oil heater until you are sure ALLPOWER IS OFF and no residual voltage can leak from capacitors or solid­state components.
LOCK OPENANDTAGelectrical circuits during servicing.IF WORK IS INTERRUPTED, confirm that all circuits are deenergized be­fore resuming work.
AVOID SPILLING liquid refrigerant on skin or getting it into the eyes. USE SAFETY GOGGLES. Wash any spills from the skin with soap and water. If liquid refrigerant enters the eyes, IMME­DIATELY FLUSH EYES with water and consult a physician.
NEVER APPLY an open flame or live steam to a refrigerant
cylinder. Dangerous over pressure can result. When it is necessary to heat refrigerant, use only warm (110 F [43 C]) water.
DO NOT REUSE disposable (nonreturnable) cylinders or attempt to refill them. It is DANGEROUS AND ILLEGAL. When cylinder is emptied, evacuate remaining gas pressure, loosen the collar and unscrew and discard the valve stem. DO NOT INCINERATE.
CHECK THE REFRIGERANT TYPE before adding refrigerant to the chiller.The introduction of the wrong refrigerant can cause dam­age or malfunction to this chiller.
Operation of this equipment with refrigerants other than those cited herein should comply with ANSI/ASHRAE 15 (latest edi­tion). Contact Carrier for further information on use of this chiller with other refrigerants.
DO NOTATTEMPTTO REMOVE fittings, covers,etc., while chiller is under pressure or while chiller is running. Be sure pressure is at 0 psig (0 kPa) before breaking any refrigerant connection.
CAREFULLY INSPECT all relief devices, rupture discs, and other relief devices AT LEAST ONCE A YEAR. If chiller operates in a corrosive atmosphere, inspect the devices at more frequent intervals.
DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief device when corrosion or build-up of foreign material (rust, dirt, scale, etc.) is found within the valve body or mechanism. Replace the device.
DO NOT install relief devices in series or backwards. USE CARE when working near or in line with a compressed spring.
Sudden release of the spring can cause it and objects in its path to act as projectiles.
DO NOT STEP on refrigerant lines. Broken lines can whip about and release refrigerant, causing personal injury.
DO NOT climb over a chiller. Use platform, catwalk, or staging. Follow safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or move inspection covers or other heavy components. Even if com­ponents are light, use mechanical equipment when there is a risk of slipping or losing your balance.
BE AWARE that certain automatic start arrangements CAN EN­GAGE THE STARTER,TOWER FAN,OR PUMPS. Open the dis­connect ahead of the starter, tower fans, or pumps.
USE only repair or replacement parts that meet the code require­ments of the original equipment.
DO NOTVENT OR DRAIN waterboxes containingindustrial brines, liquid, gases, or semisolids without the permission of your process control group.
DO NOT LOOSEN waterbox cover bolts until the waterbox has been completely drained.
DO NOT LOOSEN a packing gland nut before checking that the nut has a positive thread engagement.
PERIODICALLY INSPECT all valves, fittings, and piping for cor­rosion, rust, leaks, or damage.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Tab 5a
PC 211 Catalog No. 531-977 Printed in U.S.A. Form 19XRT-2SS Pg 1 11-98 Replaces: New
CONTENTS
Page
SAFETY CONSIDERATIONS ...................1
INTRODUCTION ..............................4
ABBREVIATIONS AND EXPLANATIONS .......4
CHILLER FAMILIARIZATION .................5-7
Chiller Information Plate ......................5
System Components .........................5
Cooler .......................................5
Condenser ...................................5
Motor-Compressor ...........................5
Turbine ......................................5
Control Panel ................................5
Factory-Mounted Starter (Optional) ............7
Storage Vessel (Optional) .....................7
REFRIGERATION CYCLE .....................7
MOTOR AND LUBRICATING OIL
COOLING CYCLE ..........................7
LUBRICATION CYCLE .......................7-9
Summary ....................................7
Details ......................................7
Oil Reclaim System ..........................9
• PRIMARY OIL RECOVERY MODE
• SECONDARY OIL RECOVERY MODE
STARTING EQUIPMENT ....................10,11
Unit-Mounted Solid-State Starter (Optional) ...10
Unit-Mounted Wye-Delta Starter (Optional) ....11
CONTROLS ...............................11-44
Definitions ..................................11
• ANALOG SIGNAL
• DISCRETE SIGNAL
General .....................................11
PIC II System Components ..................11
• CHILLER VISUAL CONTROLLER (CVC)
• INTEGRATED STARTER MODULE (ISM)
• CHILLER CONTROL MODULE (CCM)
• OIL HEATER CONTACTOR (1C)
• OIL PUMP CONTACTOR (2C)
• HOT GAS BYPASS CONTACTOR RELAY (3C) (Optional)
• CONTROL TRANSFORMERS (T1, T2)
CVC Operation and Menus ..................15
• GENERAL
• ALARMS AND ALERTS
• CVC MENU ITEMS
• BASIC CVC OPERATIONS (Using the Softkeys)
• TO VIEW STATUS
• OVERRIDE OPERATIONS
• TIME SCHEDULE OPERATION
• TO VIEW AND CHANGE SET POINTS
• SERVICE OPERATION
PIC II System Functions .....................33
• CAPACITY CONTROL
• ECW CONTROL OPTION
• CONTROL POINT DEADBAND
• PROPORTIONAL BANDS AND GAIN
• CHILLER TIMERS
• OCCUPANCY SCHEDULE
Safety Controls .............................34
Shunt Trip (Option) ..........................36
Default Screen Freeze .......................36
Ramp Loading ..............................36
Page
Capacity Override ...........................36
High Discharge Temperature Control .........36
Oil Sump Temperature Control ...............36
Oil Cooler ..................................37
Remote Start/Stop Controls ..................37
Spare Safety Inputs .........................37
Spare Safety Alarm Contacts ................37
Refrigerant Leak Detector ...................37
Condenser Pump Control ....................37
Condenser Freeze Prevention ................38
Tower-Fan Relay Low and High ..............38
Auto. Restart After Power Failure ............38
Water/Brine Reset ...........................38
• RESET TYPE 1
• RESET TYPE 2
• RESET TYPE 3
Demand Limit Control Option ................39
Surge Prevention Algorithm .................39
Surge Protection ............................40
Lead/Lag Control ...........................40
• COMMON POINT SENSOR INSTALLATION
• CHILLER COMMUNICATION WIRING
• LEAD/LAG OPERATION
• FAULTED CHILLER OPERATION
• LOAD BALANCING
• AUTO. RESTART AFTER POWER FAILURE
Ice Build Control ............................42
• ICE BUILD INITIATION
• START-UP/RECYCLE OPERATION
• TEMPERATURE CONTROL DURING ICE BUILD
• TERMINATION OF ICE BUILD
• RETURN TO NON-ICE BUILD OPERATIONS
Attach to Network Device Control ............43
• ATTACHING TO OTHER CCN MODULES
Service Operation ...........................44
• TO ACCESS THE SERVICE SCREENS
• TO LOG OUT OF NETWORK DEVICE
• HOLIDAY SCHEDULING
START-UP/SHUTDOWN/RECYCLE
SEQUENCE .............................45,46
Local Start-Up ..............................45
Shutdown Sequence ........................46
Automatic Soft Stop Amps Threshold .... ....46
Chilled Water Recycle Mode .................46
Safety Shutdown ............................46
BEFORE INITIAL START-UP ................47-59
Job Data Required ..........................47
Equipment Required ........................47
Using the Optional Storage Tank
and Pumpout System .....................47
Remove Shipping Packaging ................47
Open Oil Circuit Valves ......................47
Tighten All Gasketed Joints and
Guide Vane Shaft Packing ................47
Check Chiller Tightness .....................47
Refrigerant Tracer ...........................47
Leak Test Chiller ............................49
Standing Vacuum Test ......................49
Chiller Dehydration .........................52
Inspect Water Piping ........................52
Check Optional Pumpout Compressor
Water Piping ..............................52
Check Relief Valves .........................52
Inspect Wiring ..............................52
2
CONTENTS (cont)
Page
Carrier Comfort Network Interface ...........53
Check Starter ...............................53
• MECHANICAL STARTER
• BENSHAW, INC. REDISTART MICRO SOLID-STATE STARTER
Oil Charge ..................................54
Power Up the Controls and
Check the Oil Heater ......................54
• SOFTWARE VERSION
Software Configuration ......................54
Input the Design Set Points ..................54
Input the Local Occupied Schedule
(OCCPC01S) ..............................54
Input Service Configurations ................54
• PASSWORD
• INPUT TIME AND DATE
• CHANGE CVC CONFIGURATION IF NECESSARY
• TO CHANGE THE PASSWORD
• TO CHANGE THE CVC DISPLAY FROM ENGLISH TO METRIC UNITS
• MODIFY CONTROLLER IDENTIFICATION IF NECESSARY
• INPUT EQUIPMENT SERVICE PARAMETERS IF NECESSARY
• MODIFY EQUIPMENT CONFIGURATION IF NECESSARY
Perform A Control Test ......................57
• COOLER AND CONDENSER PRESSURE TRANSDUCER AND WATERSIDE FLOW DEVICE CALIBRATION
Check Optional Pumpout System
Controls and Compressor .................57
High Altitude Locations .....................57
Charge Refrigerant Into Chiller ...............58
• CHILLER EQUALIZATION WITHOUT
PUMPOUT UNIT
• CHILLER EQUALIZATION WITH
PUMPOUT UNIT
• TRIMMING REFRIGERANT CHARGE
INITIAL START-UP .........................59,60
Preparation .................................59
Dry Run to Test Start-Up Sequence ..........59
Check Motor Rotation .......................59
• IF THE MOTOR ROTATION IS CLOCKWISE
• IF THE MOTOR ROTATION IS NOT CLOCKWISE
Check Oil Pressure and Compressor Stop ....60
To Prevent Accidental Start-Up ..............60
Check Chiller Operating Condition ...........60
Instruct the Customer Operator ..............60
• COOLER-CONDENSER
• OPTIONAL STORAGE TANK AND
PUMPOUT SYSTEM
• MOTOR COMPRESSOR ASSEMBLY
• MOTOR COMPRESSOR LUBRICATION SYSTEM
• CONTROL SYSTEM
• AUXILIARY EQUIPMENT
• DESCRIBE CHILLER CYCLES
• REVIEW MAINTENANCE
• SAFETY DEVICES AND PROCEDURES
• CHECK OPERATOR KNOWLEDGE
• REVIEW THE START-UP, OPERATION,
AND MAINTENANCE MANUAL
OPERATING INSTRUCTIONS ...............60-62
Operator Duties .............................60
Prepare the Chiller for Start-Up ..............60
To Start the Chiller ..........................60
Check the Running System ..................60
To Stop the Chiller ..........................61
After Limited Shutdown .....................61
Page
Preparation for Extended Shutdown ..........61
After Extended Shutdown ...................61
Cold Weather Operation .....................61
Manual Guide Vane Operation ...............61
Refrigeration Log ...........................61
PUMPOUT AND REFRIGERANT TRANSFER
PROCEDURES ..........................63-65
Preparation .................................63
Operating the Optional Pumpout
Unit ......................................63
• TO READ REFRIGERANT PRESSURES
Chillers with Storage Tanks ..................64
• TRANSFER REFRIGERANT FROM PUMPOUT
STORAGE TANK TO CHILLER
• TRANSFER THE REFRIGERANT FROM
CHILLER TO PUMPOUT STORAGE TANK
Chillers with Isolation Valves ................65
• TRANSFER ALL REFRIGERANT TO CHILLER
CONDENSER VESSEL
• TRANSFER ALL REFRIGERANT TO CHILLER
COOLER VESSEL
• RETURN REFRIGERANT TO NORMAL
OPERATING CONDITIONS
GENERAL MAINTENANCE .................66,67
Refrigerant Properties .......................66
Adding Refrigerant ..........................66
Removing Refrigerant .......................66
Adjusting the Refrigerant Charge ............66
Refrigerant Leak Testing ....................66
Leak Rate ..................................66
Test After Service, Repair, or Major Leak .....66
• REFRIGERANT TRACER
• TO PRESSURIZE WITH DRY NITROGEN
Repair the Leak, Retest, and Apply
Standing Vacuum Test ....................66
Checking Guide Vane Linkage ...............66
Trim Refrigerant Charge .....................66
WEEKLY MAINTENANCE ....................67
Check the Lubrication System ...............67
SCHEDULED MAINTENANCE ..............67-71
Service Ontime .............................67
Inspect the Control Panel ....................67
Check Safety and Operating Controls
Monthly ..................................67
Changing Oil Filter ..........................67
Oil Specification ............................68
Oil Changes ................................68
• TO CHANGE THE OIL
Refrigerant Filter ............................68
Oil Reclaim Filter ...........................68
Inspect Refrigerant Float System ............68
Inspect Relief Valves and Piping .............68
Turbine Strainer .............................68
Turbine Maintenance ........................68
Compressor Bearing and Gear Maintenance ..68 Inspect the Heat Exchanger Tubes and Flow
Devices ..................................70
• COOLER AND FLOW DEVICES
• CONDENSER AND FLOW DEVICES
Water Leaks ................................70
Water Treatment ............................70
Inspect the Starting Equipment ..............70
Check Pressure Transducers ................70
Optional Pumpout System Maintenance ......70
• OPTIONAL PUMPOUT COMPRESSOR OIL
CHARGE
• OPTIONAL PUMPOUT SAFETY CONTROL
SETTINGS
3
CONTENTS (cont)
Page
Ordering Replacement Chiller Parts ..........71
TROUBLESHOOTING GUIDE ...............71-97
Overview ...................................71
Checking the Display Messages .............71
Checking Temperature Sensors ..............71
• RESISTANCE CHECK
• VOLTAGE DROP
• CHECK SENSOR ACCURACY
• DUAL TEMPERATURE SENSORS
Checking Pressure Transducers .............72
• TRANSDUCER REPLACEMENT
Control Algorithms Checkout Procedure .....72
Control Test ................................72
Control Modules ............................82
• RED LED (Labeled as STAT)
• GREEN LED (Labeled as COM)
Notes on Module Operation ..................82
Page
Chiller Control Module (CCM) ................83
• INPUTS
• OUTPUTS
Integrated Starter Module (ISM) ..............83
• INPUTS
• OUTPUTS
Replacing Defective Processor Modules ......83
• INSTALLATION
Solid-State Starters .........................83
• TESTING SILICON CONTROL RECTIFIERS IN BENSHAW, INC., SOLID-STATE STARTERS
• SCR REMOVAL/INSTALLATION
Physical Data ...............................85
INDEX ......................................98
INITIAL START-UP CHECKLIST FOR
19XRT HERMETIC CENTRIFUGAL
LIQUID CHILLER .................CL-1 to CL-12
INTRODUCTION
Prior to initial start-up of the 19XRT chiller, those in­volved in the start-up, operation, and maintenance should be thoroughly familiar with these instructions and other nec­essary job data. This book is outlined to familiarize those involved in the start-up, operation and maintenance of the unit with the control system before performing start-up pro­cedures. Procedures in this manual are arranged in the se­quence required for proper chiller start-up and operation.
This unit uses a microprocessor control system. Do not short or jumper between terminations on circuit boards or modules. Control or board failure may result.
Be aware of electrostatic discharge (static electricity) when handling or making contact with circuit boards or module connections. Always touch a chassis (grounded) part to dissipate body electrostatic charge before work­ing inside control center.
Use extreme care when handlingtoolsnearcircuitboards and when connecting or disconnecting terminal plugs. Circuit boards can be damaged easily. Always hold boards by the edges, and avoid touching components and connections.
This equipment uses, and can radiate, radio fre­quency energy. If not installed and used in accordance with the instruction manual, it may interfere with radio communications. This equipment has been tested and found to comply with the limits for a Class A comput­ing device pursuant to Subpart J of Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference when operated in a commercial envi­ronment. Operation of this equipment in a residential area is likely to cause interference, in which case the user, at his own expense, will be required to take whatever measures may be required to correct the interference.
Always store and transport replacement or defective boards in an anti-static shipping bag.
ABBREVIATIONS AND EXPLANATIONS
Frequently used abbreviations in this manual include:
CCM — Chiller Control Module CCN — Carrier Comfort Network CVC — Chiller Visual Control CCW — Counterclockwise CW — Clockwise ECDW — Entering Condenser Water ECW — Entering Chilled Water EMS — Energy Management System HGBP — Hot Gas Bypass I/O — Input/Output ISM — Integrated Starter Module LCD — Liquid Crystal Display LCDW — Leaving Condenser Water LCW — Leaving Chilled Water LED — Light-Emitting Diode OLTA — Overload Trip Amps PIC II — Product Integrated Control II RLA — Rated Load Amps SCR — Silicon Controlled Rectifier SI — International System of Units TXV — Thermostatic Expansion Valve
W ordsprinted in all capital letters orin italics may be viewed on the Chiller Visual Control (CVC) (e.g., LOCAL, CCN, ALARM, etc.).
Words printed in both all capital letters and italics can also be viewed on the CVC and are parameters (e.g., CONTROL
MODE, COMPRESSOR START RELAY, ICE BUILD OPTION, etc.) with associated values (e.g., modes, tempera-
tures, percentages, pressures, on, off, etc.).
Words printed in all capital letters and in a box represent softkeys on the CVC control panel (e.g., ENTER
, INCREASE , QUIT , etc.).
EXIT
Factory-installed additional components are referred to as options in this manual; factory-supplied but field-installed additional components are referred to as accessories.
The chiller software part number of the 19XRTunit is lo­cated on the back of the CVC.
,
4
CHILLER FAMILIARIZATION
(Fig. 1 and 2)
Chiller Information Plate —
located on the right side of the chiller control panel.
The information plate is
System Components — The components include the
cooler and condenser heat exchangers in separate vessels, motor-compressor,turbine, lubrication package, control panel, and motor starter.All connections from pressure vessels have external threads to enable each component to be pressure tested with a threaded pipe cap during factory assembly.
Cooler — This vessel (also known as the evaporator) is
located underneath the compressor. The cooler is main­tained at lower temperature/pressure so evaporating refrig­erant can remove heat from water flowing through its inter­nal tubes.
Condenser — The condenser operates at a higher
temperature/pressure than the cooler and has water flowing through its internal tubes in order to remove heat from the refrigerant.
Motor-Compressor — This component maintains sys-
tem temperature and pressure differences and moves the heat­carrying refrigerant from the cooler to the condenser.
Turbine — The turbine serves 2 purposes. First, it acts as
the expansion device to separate condenser pressure from cooler pressure. Second, using the pressure differential be­tween the cooler and condenser, the turbine converts the pressure drop to energy and uses this energy to supplement the compressor motor, thereby reducing the required horsepower.
Control Panel — The control panel is the user interface
for controlling the chiller. It regulates the chiller’s capacity as required to maintain proper leaving chilled water tem­perature. The control panel:
• registers cooler, condenser, and lubricating system pressures
• shows chiller operating condition and alarm shutdown conditions
• records the total chiller operating hours
• sequences chiller start, stop, and recycle under micro­processor control
• displays status of motor starter
• provides access to other CCN (Carrier Comfort Network) devices
Fig. 1 — 19XRT Identification
5
11514
3
2
4
6
5
2122
9
10
8
7
20 18
19
1312
11
RIGHT END VIEW
LEGEND
1—Turbine Housing 2—Power Panel 3—Motor Housing 4—Oil Level Sight Glasses 5—Guide Vane Actuator 6—Demistor Vent Line 7—Suction Elbow 8—Chiller Visual Control (CVC) 9—Condenser Pumpout Connection (Hidden)
16
10 — Condenser Relief Valves 11 — Relief Transfer Valve
17
12 — Condenser Pressure Transducer (Hidden)
16
13 — Cooler Relief Valve 14 — Cooler Pressure Transducer (Hidden) 15 — Cooler Pumpout Connection 16 — Cooler/Condenser Waterflow Device
Condenser In/Out Temperature
17 —
Thermistors
18 — Cooler In/Out Temperature Thermistors 19 — Chiller Identification Nameplate
Location
20 — Float Chamber
17
21 — Refrigerant Charging Valve 22 — Oil Drain Charging Valve
24
23 2625
31
30
27
23 — Take-Apart, Connector (Upper) 24 — Waterbox Vent Connection (Typical) 25 — Cooler Liquid Return Line 26 — Oil Filter Access Cover 27 — Refrigerant Oil Cooler 28 — Take-Apart, Rabbet-Fit Connector
(Lower)
29 — Cooler Return-End Waterbox Cover 30 — Waterbox Drain Port (Typical) 31 — Condenser Return-End Waterbox Cover
29
28
LEGEND
LEFT END VIEW
2
1
12
3
4
5
6
7
1—Turbine Suction 2—Nozzle (Typical, 1 of 6 Shown) 3—Nozzle Block 4—High Efficiency Motor 5—Transmission 6—Compressor Base 7—Guide Vane Actuator 8—Oil Filter Housing
9—Turbine Wheel 10 — Turbine Housing 11 — Turbine Discharge 12 — Turbine Sight Glass
LEGEND
TURBINE COMPONENTS
891011
Fig.2—Typical 19XRT Components
6
Factory-Mounted Starter (Optional)— The starter
allows for the proper start and disconnect of electrical en­ergy for the compressor-motor, oil pump, oil heater,and con­trol panel.
Storage Vessel (Optional) — There are 2 sizes of
storage vessels available. The vessels have double relief valves, a magnetically-coupled dial-type refrigerant level gage, a one-inch FPT drain valve, and a1⁄2-in. male flare vapor connection for the pumpout unit.
NOTE: If a storage vessel is not used at the jobsite, factory­installed isolation valves on the chiller may be used to iso­late the chiller charge in either the cooler or condenser. An optional pumpout system is used to transfer refrigerant from vessel to vessel.
REFRIGERATION CYCLE
The compressor continuously draws refrigerant vapor from the cooler, at a rate set by the amount of guide vane opening (Fig. 3). As the compressor suction reduces the pressure in the cooler, the remaining refrigerant boils at a fairly low tem­perature (typically 38 to 42 F [3 to 6 C]). The energy re­quired for boiling is obtained from the water flowing through the cooler tubes. With heat energy removed, the water be­comes cold enough for use in an air conditioning circuit or process liquid cooling.
After taking heat from the water, the refrigerant vapor is compressed. Compression adds still more heat energy and the refrigerant is quite warm (typically 98 to 102 F [37 to 40 C]) when it is discharged from the compressor into the condenser.
Relatively cool (typically 65 to 90 F [18 to 32 C]) water flowing through the condenser tubes removes heat from the refrigerant, and the vapor condenses to a liquid. Further re­moval of heat from the refrigerant occurs in the lower cham­ber of the condenser, which is called the sensible subcooler. At this point, the liquid refrigerant is subcooled by contact with the coolest (entering water) condenser tubes.
After leaving the sensible subcooler section of the con­denser, the liquid refrigerant enters the float valve chamber. The main float valve maintains a liquid level in the sub­cooler to prevent hot gas bypass from the condenser to the cooler at part load conditions. A second valve in the float valve chamber opens at part load conditions when the liquid level increases in the condenser to bypass liquid from the float chamber directly to the cooler inlet. The liquid refrig­erant from the main float valve then flows into the turbine housing chamber on the compressor. The liquid refrigerant passes through the turbine nozzles and impacts the turbine blades where energy is reclaimed as the refrigerant expands through the turbine to the lower cooler pressure. The turbine wheel is attached to the motor shaft which allows the turbine to supplement and reduce motor power requirements.At this point the refrigerant flashes to a mixture of gas and liquid which removes heat from the remaining liquid. This mixture flows back to the cooler where it is now at the same tem­perature and pressure at which the cycle began.
MOTOR AND LUBRICATING OIL
COOLING CYCLE
The motor and the lubricating oil are cooled by liquid re­frigerant taken from the bottom of the condenser vessel (Fig. 3). Refrigerant flow is maintained by the pressure
differentialthat exists due to compressor operation.After the refrigerant flows past an isolation valve, an in-line filter, and a sight glass/moisture indicator, the flow is split between the motor cooling and oil cooling systems.
Flow to the motor cooling system passes through an ori­fice and into the motor. Once past the orifice, the refrigerant is directed over the motor by a spray nozzle. The refrigerant collects in the bottom of the motor casing and is then drained back into the cooler through the motor refrigerant drain line. The refrigerant outlet from the motor casing is sized to act as an orifice to maintain a higher pressure in the motor shell than in the cooler/oil sump. The motor is protected by a tem­perature sensor imbedded in the stator windings. An in­crease in motor winding temperature past the motor override set point overrides the temperature capacity control to hold, and if the motor temperature rises 10° F (5.5° C) above this set point, closes the inlet guide vanes. If the temperature rises above the safety limit, the compressor shuts down.
Refrigerant that flows to the oil cooling system is regu­lated by thermostatic expansion valves (TXVs). The TXVs regulate flow into the oil/refrigerant plate and frame-type heat exchanger (the oil cooler in Fig. 3). The expansion valve bulbs control oil temperature to the bearings. The refrigerant leaving the oil cooler heat exchanger then returns to the chiller cooler.
LUBRICATION CYCLE
Summary —
up a package located partially in the transmission casting of the compressor-motor-turbine assembly. The oil is pumped into a filter assembly to remove foreign particles and is then forced into an oil cooler heat exchanger where the oil is cooled to proper operational temperatures. After the oil cooler, part of the flow is directed to the gears and the high speed shaft bearings; the remaining flow is directed to the motor shaft bearings. Oil drains into the transmission oil sump to com­plete the cycle (Fig. 4).
The oil pump, oil filter, and oil cooler make
Details— Oil is charged into the lubrication system through
a hand valve. Two sight glasses in the oil reservoir permit oil level observation. Normal oil level is between the middle of the upper sight glass and the top of the lower sight glass when the compressor is shut down. The oil level should be visible in at least one of the 2 sight glasses during operation. Oil sump temperature is displayed on the CVC (Chiller Visual Control) default screen. During compressor opera­tion, the oil sump temperature ranges between 125 to 150 F (52 to 66 C).
The oil pump suction is fed from the oil reservoir. An oil pressure relief valve maintains 18 to 25 psid (124 to 172 kPad) differential pressure in the system at the pump discharge.This differentialpressure can be read directly from the CVC default screen. The oil pump discharges oil to the oil filter assembly. This filter can be closed to permit removal of the filter without draining the entire oil system (see Maintenance sections, pages 66-71, for details). The oil is then piped to the oil cooler heat exchanger. The oil cooler uses refrigerant from the condenser as the coolant. The re­frigerant cools the oil to a temperature between 120 and 140 F (49 to 60 C).
7
LEGEND
Fig. 3 — Refrigerant, Motor Cooling, and Oil Cooling Cycles
1—Condenser Tubes
2—Filter/Drier
3—Moisture Indicator
4—Refrigerant Cooling Isolation Valves
5—Main Condenser Liquid Drain Line
6—Float Chamber Vent
7—Subcooler
8—Discharge Isolation Valve (Optional)
Charging Valve
9—High Condenser Level Drain
10 — Condenser Side Refrigerant
11 — Stator
12 — Transmission
13 — Diffuser
14 — Impeller
15 — Inlet Guide Vanes
16 — Cooler Distribution Pipe
17 — Refrigerant Cooling Drain Lines
18 — Oil Pump
19 — Oil Filter
20 — Rotor
21 — Oil Cooler
22 — Orificed Fitting
Oil Cooling
23 — Thermal Expansion Valve for
24 — Cooler Refrigerant Supply Line
25 — Turbine Suction Line Strainer
26 — Cooler Suction Line
27 — Cooler Refrigerant Charging
Valve
28 — Turbine Bypass Line Isolation
8
Valve
29 — Turbine Bypass Line
Bypass
30 — Pilot Drain Line From Turbine
31 — Float Chamber
32 — Turbine Float Valve
33 — Turbine Bypass Float Valve
34 — Turbine Suction Isolation Valve
(Optional)
35 — Motor Back Pressure Orifice
OIL SUPPLY LINE
THERMAL EXPANSION VALVE BULB
THRUST
FILTER ISOLATION VALVE
FILTER OIL DRAIN
OIL SUPPLY PRESSURE TRANSDUCER
ISOLATION VALVE
OIL COOLER
OIL PUMP AND MOTOR
Fig. 4 — Lubrication System
JOURNAL BEARINGS
OIL CHARGE VALVE
OIL PRESSURE RELIEF VALVE
THRUST
REAR PINION BEARING
SIGHT GLASSES
STRAINER CHECK
VALVE ISOLATION
VALVE SIGHT
GLASS FILTER
STRAINEREDUCTOR
ISOLATION VALVE
COOLER OIL RECLAIM LINE
As the oil leaves the oil cooler, it passes the oil pressure transducer and the thermal bulb for the refrigerant expan­sion valve on the oil cooler. The oil is then divided. Part of the oil flows to the thrust bearing, forward pinion bearing, and gear spray. The rest of the oil lubricates the motor shaft bearings and the rear pinion bearing. The oil temperature is measured in the bearing housing as it leaves the thrust and forward journal bearings. The oil then drains into the oil res­ervoir at the base of the compressor. The PIC II (Product Integrated Control II) measures the temperature of the oil in the sump and maintains the temperature during shutdown (see Oil Sump Temperature Control section, page 36). This temperature is read on the CVC default screen.
During the chiller start-up, the PIC IIenergizesthe oil pump and provides 45 seconds of prelubrication to the bearings after pressure is verified before starting the compressor. During shutdown, the oil pump will run for 60 seconds to post-lubricate after the compressor shuts down. The oil pump can also be energized for testing purposes during a Control Test.
Ramp loading can slow the rate of guide vane opening to minimize oil foaming at start-up. If the guide vanes open quickly, the sudden drop in suction pressure can cause any refrigerant in the oil to flash. The resulting oil foam can­not be pumped efficiently; therefore, oil pressure falls off and lubrication is poor. If oil pressure falls below 15 psid (103 kPad) differential, the PIC II will shut down the compressor.
If the controls are subject to a power failure that lasts more than 3 hours, the oil pump will be energized periodically when the power is restored. This helps to eliminate refrigerant that has migrated to the oil sump during the power failure. The controls energize the pump for 60 seconds every 30 minutes until the chiller is started.
Oil Reclaim System — The oil reclaim system re-
turns oil lost from the compressor housing back to the oil reservoir by recovering the oil from 2 areas on the chiller. The guide vane housing is the primary area of recovery. Oil is also recovered by skimming it from the operating refrig­erant level in the cooler vessel.
PRIMARY OIL RECOVERY MODE — Oil is normally recovered through the guide vane housing on the chiller.This is possible because oil is normally entrained with refrigerant in the chiller.As the compressor pulls the refrigerant up from the cooler into the guide vane housing to be compressed, the oil normally drops out at this point and falls to the bottom of the guide vane housing where it accumulates. Using dis­charge gas pressure to power an eductor, the oil is drawn from the housing and is discharged into the oil reservoir.
SECONDARYOIL RECOVERYMODE — The secondary method of oil recovery is significant under light load con­ditions, when the refrigerant going up to the compressor suc­tion does not have enough velocity in which to bring oil along. Under these conditions, oil collects in a greater concentra­tion at the top level of the refrigerant in the cooler. This oil and refrigerant mixture is skimmed from the side of the cooler and is then drawn up to the guide vane housing. There is a filter in this line. Because the guide vane housing pressure is much lower than the cooler pressure, the refrigerant boils off, leaving the oil behind to be collected by the primary oil recovery method.
9
STARTING EQUIPMENT
The 19XRT requires a motor starter to operate the cen­trifugal hermetic compressor motor, the oil pump, and vari­ous auxiliary equipment. The starter is the main field wiring interface for the contractor.
See Carrier Specification Z-415 for specific starter re­quirements. All starters must meet these specifications in order to properly start and satisfy mechanical safety require­ments. Starters may be supplied as separate, free-standing units or may be mounted directly on the chiller (unit mounted) for low-voltage units only.
Three separate circuit breakers are inside the starter. Cir­cuit breaker CB1 is the compressor motor circuit breaker. The disconnect switch on the starter front cover is connected to this breaker. Circuit breaker CB1 supplies power to the compressor motor.
The main circuit breaker (CB1) on the front of the starter disconnects the main motor current only. Power is still energized for the other circuits. Two more circuit break­ers inside the starter must be turned off to disconnect power to the oil pump, PIC II controls, and oil heater.
Circuit breaker CB2 supplies power to the control panel, oil heater, and portions of the starter controls.
Circuit breaker CB3 supplies power to the oil pump. Both CB2 and CB3 are wired in parallel with CB1 so that power is supplied to them if the CB1 disconnect is open.
All starters must include a Carrier control module called the Integrated Starter Module (ISM), excluding the Benshaw solid-state starters. This module controls and moni­tors all aspects of the starter. See the Controls section on page 11 for additional ISM information. All starter replace­ment parts are supplied by the starter manufacturer exclud­ing the ISM (contact Carrier’s Replacement Component Division [RCD]).
Unit-Mounted Solid-State Starter (Optional)
The 19XRT chiller may be equipped with a solid-state,
reduced-voltage starter (Fig. 5 and 6). This starter’s primary function is to provide on-off control of the compressor mo­tor. This type of starter reduces the peak starting torque, reduces the motor inrush current, and decreases mechanical shock. This capability is summed up by the phrase ‘‘soft start­ing.’’ The solid-state starter is available as a 19XRT option (factory supplied and installed). The solid-state starters manu­facturer name is located inside the starter access door.
A solid-state, reduced-voltage starter operates by reduc­ing the starting voltage. The starting torque of a motor at full voltage is typically 125% to 175% of the running torque. When the voltage and the current are reduced at start-up, the starting torque is reduced as well. The object is to reduce the starting voltage to just the voltage necessary to develop the torque required to get the motor moving. The voltage is re­duced by silicon controlled rectifiers (SCRs). The voltage and current are then ramped up in a desired period of time. Once full voltage is reached, a bypass contactor is energized to bypass the SCRs.
When voltage is supplied to the solid-state circuitry, the heat sinks in the starter as well as the wires leading to the motor and the motor terminal are at line voltage. Do not touch the heat sinks, power wiring, or motor terminals while voltage is present or serious injury will result.
There is a display on the front of the Benshaw,Inc., solid­state starters that is useful for troubleshooting and starter check­out. The display indicates:
• voltage to the SCRs
• SCR control voltage
• power indication
• proper phasing for rotation
• start circuit energized
• over-temperature
• ground fault
• current unbalance
• run state
• software configuration
The starter is further explained in the Check Starter and Troubleshooting Guide sections, pages 53 and 71.
6
1
2
5
4
LEGEND
1—Ready-Start Micro Input/Output Card 2—Circuit Breaker 2 (CB2):
Machine Control and Heater Power
3—Circuit Breaker 3 (CB3): Oil Pump Power 4—Ready-Start Micro Central Processing Unit Card (CPU) 5—Restart Micro Power Card (hidden, not depicted) 6—Restart Micro Bypass Card (hidden, not depicted)
3
Fig. 5 — Solid-State Starter Box,
Internal View
10
Fig.6—Typical Starter External View
(Solid-State Starter Shown)
Unit-Mounted Wye-Delta Starter (Optional)
The 19XRT chiller may be equipped with a wye-delta
starter mounted on the unit. This starter is intended for use with low-voltage motors (under 600 v). It reduces the start­ing current inrush by connecting each phase of the motor windings into a wye configuration. This occurs during the starting period when the motor is accelerating up to speed. Once the motor is up to speed, the starter automatically con­nects the phase windings into a delta configuration. Starter control, monitoring, and motor protection is provided by Carrier’s Integrated Starter Module (ISM).
CONTROLS
Definitions
ANALOG SIGNAL — An analog signal varies in propor­tion to the monitored source. It quantifies values between operating limits. (Example: A temperature sensor is an ana­log device because its resistance changes in proportion to the temperature, generating many values.)
DISCRETE SIGNAL — A discrete signal is a 2-position rep­resentation of the value of a monitored source. (Example: A switch produces a discrete signal indicating whether a value is above or below a set point or boundary by generating an on/off, high/low, or open/closed signal.)
General— The 19XRThermetic centrifugal liquid chiller
contains a microprocessor-based control center that moni­tors and controls all operations of the chiller (see Fig. 7). The microprocessor control system matches the cooling capacity of the chiller to the cooling load while providing state-of-the-art chiller protection. The system controls cool­ing load within the set point plus the deadband by sensing the leaving chilled water or brine temperature and regula­ting the inlet guide vane via a mechanically-linked actuator motor. The guide vane is a variable flow pre-whirl assem­bly that controls the refrigeration effect in the cooler by regulating the amount of refrigerant vapor flow into the com­pressor.An increase in guide vane opening increases capac­ity.Adecrease in guide vane opening decreases capacity.The microprocessor-based control center protects the chiller by monitoring the digital and analog inputs and executing capacity overrides or safety shutdowns, if required.
PIC II System Components — The chiller control
system is called PIC II (Product Integrated Control II). See Table 1. The PIC II controls the operation of the chiller by monitoring all operating conditions. The PIC II can di­agnose a problem and let the operator know what the prob­lem is and what to check. It promptly positions the guide vanes to maintain leaving chilled water temperature. It can interface with auxiliary equipment such as pumps and cool­ing tower fans to turn them on when required. It continually checks all safeties to prevent any unsafe operating condi­tion. It also regulates the oil heater while the compressor is off and regulates the hot gas bypass valve, if installed. The PIC II controls provide critical protection for the compres­sor motor and controls the motor starter.
The PIC II can interface with the Carrier Comfort Net­work (CCN) if desired. It can communicate with other PIC I or PIC II equipped chillers and other CCN devices.
The PIC II consists of 3 modules housed inside 3 major components. The component names and corresponding con­trol voltages are listed below (also see Table 1):
• control panel
— all extra low-voltage wiring (24 v or less)
• power panel
— 230 or 115 v control voltage (per job requirement) — up to 600 v for oil pump power
• starter cabinet
— chiller power wiring (per job requirement)
Table 1 — Major PIC II Components and
Chiller Visual Controller (CVC) and Display Control Panel Integrated Starter Module (ISM) Starter Cabinet Chiller Control Module (CCM) Control Panel Oil Heater Contactor (1C) Power Panel Oil Pump Contactor (2C) Power Panel Hot Gas Bypass Relay (3C) (Optional) Power Panel Control Transformers (T1, T2) Power Panel Temperature Sensors See Fig. 7. Pressure Transducers See Fig. 7.
*See Fig. 5 and Fig. 7-11.
CHILLER VISUAL CONTROLLER (CVC) — The CVC is the ‘‘brain’’ of the PIC II. This module contains all the op­erating software needed to control the chiller. The CVC is mounted to the control panel (Fig. 10) and is the input center for all local chiller set points, schedules, configurable functions, and options. The CVC has a stop button, an alarm light, four buttons for logic inputs, and a backlight display. The backlight will automatically turn off after 15 minutes of non-use. The functions of the four buttons or ‘‘softkeys’’ are menu driven and are shown on the display directly above the softkeys.
The viewing angle of the CVC can be adjusted for opti­mum viewing. Remove the 2 bolts connecting the control panel to the brackets attached to the cooler. Place them in one of the holes to pivot the control panel forward to back­ward to change the viewing angle. See Fig. 10. To change the contrast of the display, access the adjustment on the back of the CVC. See Fig. 10.
Panel Locations*
PIC II COMPONENT
PANEL
LOCATION
11
TOP VIEW
LEGEND
1—Condenser Temperature Sensor Connection 2—Condenser Pressure Transducer Connection
COMPRESSOR AREA
Fig. 7 — 19XRT Control and Sensor Locations
12
INTEGRATED STARTER MODULE (ISM) — This mod­ule is located in the starter cabinet. This module initiates com­mands from the CVC for starter functions such as starting and stopping the compressor, condenser, chilled water pumps, tower fan, spare alarm contacts, and the shunt trip. The ISM monitors starter inputs such as line voltage, motor current, ground fault, remote start contact, spare safety, condenser high pressure, oil pump interlock, starter 1M, and run con­tacts. The ISM contains logic capable of safety shutdown. It shuts down the chiller if communications with the CVC are lost.
CHILLER CONTROL MODULE (CCM) — This module is located in the control panel. The CCM provides the input and outputs necessary to control the chiller. This module moni­tors refrigerant pressure, entering and leaving water tem­peratures, and outputs control for the guide vane actuator, oil heaters, and oil pump. The CCM is the connection point for optional demand limit, chilled water reset, remote tem­perature reset, and refrigerant leak sensor.
OIL HEATER CONTACTOR (1C) — This contactor is lo­cated in the power panel (Fig. 11) and operates the heater at either 115 or 230 v. It is controlled by the PIC II to maintain oil temperature during chiller shutdown.
OIL PUMP CONTACTOR (2C) — This contactor is located in the power panel. It operates all 200 to 575-v oil pumps. The PIC II energizes the contactor to turn on the oil pump as necessary.
HOT GAS BYPASS CONTACTOR RELAY (3C) (Op­tional) — This relay, located in the power panel, controls the opening of the hot gas bypass valve. The PIC II energizes the relay during low load, high lift conditions.
CONTROL TRANSFORMERS (T1, T2) — These trans­formers convert incoming control voltage to 24 vac power for the 3 power panel contactor relays, CCM, and CVC.
Fig. 8 — Control Sensors (Temperature)
Fig. 9 — Control Sensors
(Pressure Transducers, Typical)
13
Fig. 10 — Control Panel
Fig. 11 — Power Panel
14
CVC Operation and Menus (Fig. 12-18)
GENERAL
• The CVC display automatically reverts to the default screen after 15 minutes if no softkey activity takes place and if the chiller is not in the pumpdown mode (Fig. 12).
• If a screen other than the default screen is displayed on the CVC, the name of that screen is in the upper right corner (Fig. 13).
• The CVC may be set to display either English or SI units. Use the CVC configuration screen (accessed from the Serv­ice menu) to change the units. See the Service Operation section, page 44.
• Local Operation — The PIC II can be placed in local operating mode by pressing the LOCAL PIC II then accepts commands from the CVC only and
uses the Local Time Schedule to determine chiller start and stop times.
• CCN Operation — The PIC II can be placed in the CCN operating mode by pressing the CCN PIC II then accepts modifications from any CCN interface
or module (with the proper authority), as well as from the CVC. The PIC II uses the CCN time schedule to deter­mine start and stop times.
ALARMSANDALERTS — An alarm shuts down the com­pressor. An alert does not shut down the compressor, but it notifies the operator that an unusual condition has occurred. An alarm (*) or alert (!) is indicated on the STATUS screens on the far right field of the CVC display screen.
Alarms are indicated when the control center alarm light (!) flashes. The primary alarm message is displayed on the default screen. An additional, secondary message and troubleshooting information are sent to the ALARM HIS­TORY table.
When an alarm is detected, the CVC default screen will freeze (stop updating) at the time of alarm. The freeze en­ables the operator to view the chiller conditions at the time of alarm. The STATUS tables will show the updated infor­mation. Once all alarms have been cleared (by pressing the
RESET
softkey), the default CVC screen will return to nor-
mal operation. CVC MENU ITEMS — To perform any of the operations
described below, the PIC II must be powered up and have successfully completed its self test. The self test takes place automatically, after power-up.
Press the MENU
tures: STATUS
SERVICE
.
softkey to view the list of menu struc-
, SCHEDULE , SETPOINT , and
• The STATUS menu allows viewing and limited calibra-
tion or modification of control points and sensors, relays and contacts, and the options board.
• The SCHEDULE menu allows viewing and modification
of the local and CCN time schedules and Ice Build time schedules.
• The SETPOINT menu allows set point adjustments, such
as the entering chilled water and leaving chilled water set points.
softkey. The
softkey. The
PRIMARY STATUS MESSAGE
SECONDARY STA TUS MESSAGE
ALARM LIGHT (ILLUMINATED WHEN POWER ON)
BLINKS CONTINUOUSLY
ON FOR AN ALARM BLINKS ONCE TO
CONFIRM A STOP
STOP BUTTON
HOLD FOR ONE
SECOND TO STOP
COMPRESSOR ONTIME
RUNNING TEMP CONTROL LEAVING CHILLED WATER
CHW IN CHW OUT EVAP REF
55.1 44.1 40.7
CDW IN CDW OUT COND REF
85.0 95.0 98.1
OIL PRESS OIL TEMP AMPS %
21.8 132.9 93
CCN LOCAL RESET MENU
SOFT KEYS
EACH KEY'S FUNCTION IS DEFINED BY THE MENU DESCRIPTION ON MENU LINE ABOVE
DATE TIME
01-01-95 11:48
28.8 HOURS
MENU LINE
Fig. 12 — CVC Default Screen
19XRT_II
ALARM HISTORY
CONTROL TEST CONTROL ALGORITHM STATUS EQUIPMENT CONFIGURATION ISM (STARTER) CONFIGURATION DATA EQUIPMENT SERVICE TIME AND DATE ATTACH TO NETWORK DEVICE LOG OUT OF DEVICE CVC CONFIGURATION
SERVICE
Fig. 13 — CVC Service Screen
• The SERVICE menu can be used to view or modify information on the Alarm History, Control Test, Control Algorithm Status, Equipment Configuration, ISM Starter Configuration data, Equipment Service, Time and Date, At­tach to Network Device, Log Out of Network Device, and CVC Configuration screens.
For more information on the menu structures, refer to
Fig. 15.
Press the softkey that corresponds to the menu structure
to be viewed : STATUS
SERVICE
. To view or change parameters within any of
these menu structures, use the NEXT
, SCHEDULE , SETPOINT ,or
and PREVIOUS soft-
keys to scroll down to the desired item or table. Use the
SELECT
softkey to select that item. The softkey choices
that then appear depend on the selected table or menu. The softkey choices and their functions are described below.
BASIC CVC OPERA TIONS(Using the Softkeys) — Toper­form any of the operations described below, the PIC II must be powered up and have successfully completed its self test.
15
• Press QUIT to leave the selected decision or field with­out saving any changes.
• Press ENTER to leave the selected decision or field and save changes.
• Press NEXT to scroll the cursor bar down in order to highlight a point or to view more points below the current
screen.
• Press PREVIOUS to scroll the cursor bar up in order to highlight a point or to view points above the current screen.
2. Press NEXT or PREVIOUS to highlight the desired status table. The list of tables is:
• MAINSTAT — Overall chiller status
• STAR TUP— Status required to perform startup of chiller
• COMPRESS — Status of sensors related to the
compressor
• HEAT_EX — Status of sensors related to the heat
exchangers
• POWER — Status of motor input power
• ISM_STAT — Status of motor starter
• CVC_PSWD — Service menu password forcing ac-
cess screen
3. Press SELECT to view the desired point status table.
4. On the point status table, press NEXT or
PREVIOUS
until the desired point is displayed on the
screen.
• Press SELECT to view the next screen level (high­lighted with the cursor bar), or to override (if allowable)
the highlighted point value.
• Press EXIT to return to the previous screen level.
• Press INCREASE or DECREASE to change the high­lighted point value.
TO VIEW STATUS (Fig. 14) — The status table shows the actual value of overall chiller status such as CONTROLMODE, RUN STATUS, AUTO CHILLED WATER, RESET, and RE­MOTE RESET SENSOR.
1. On the menu screen, press STATUS
to view the list of
point status tables.
19XRT_II MAINSTAT Control Mode Run Status Start Inhibit Timer Occupied? System Alert/Alarm Chiller Start/Stop Remote Start Contact Temperature Reset Control Point Chilled Water Temp Active Demand Limit Average Line Current
POINT STATUS
OFF
Ready
0.0 Min NO
NORMAL
STOP
Open
0.0 F
44.0 F
44.6 F 100%
0.0%
Fig. 14 — Example of Status Screen
OVERRIDE OPERATIONS To Override a Value or Status
1. From any point status screen, press NEXT or PREVIOUS
to highlight the desired value.
16
CCN
LOCAL RESET
MENU
DEFAULT SCREEN
Start Chiller In CCN Control
Start Chiller in Local Control
Clear Alarms
STATUS
SCHEDULE SETPOINT
SERVICE
(SOFTKEYS)
Access Main Menu
List the Status Tables
Display The Setpoint Table
List the Service Tables
• OCCPC01S – LOCAL TIME SCHEDULE
• OCCPC02S – ICE BUILD TIME SCHEDULE
• OCCPC03S – CCN TIME SCHEDULE
List the Schedules
NEXT
PREVIOUS
SELECT
EXIT
ALARM HISTORY CONTROL TEST CONTROL ALGORITHM STA TUS EQUIPMENT CONFIGURATION ISM (STARTER) CONFIG DATA EQUIPMENT SERVICE TIME AND DATE ATTACH TO NETWORK DEVICE LOG OUT OF DEVICE CVC CONFIGURATION
SEE FIGURE 16
Base Demand Limit
• LCW Setpoint
• ECW Setpoint
• Ice Build Setpoint
• Tower Fan High Setpoint
EXIT
SELECT
PREVIOUS
NEXT
Select a Schedule
1 2 3 4 5 6 7 8
Override
ENABLE DISABLE
EXIT
SELECT
PREVIOUS
NEXT
Select a Time Period/Override
Modify a Schedule Time
ENTER EXIT
INCREASE DECREASE ENTER EXIT
(ANALOG VALUES)
(DISCRETE VALUES)
Add/Eliminate a Day
1
Select a Status Table
NEXT
PREVIOUS
SELECT
EXIT
START
ON
STOP
OFF
RELEASE
ENTER
EXIT
NEXT
PREVIOUS
SELECT
ENTER
ENABLE
DISABLE
QUIT
DECREASE
INCREASE
ENTER
RELEASE
Select a Modification Point
Modify a Discrete Point
Modify an Analog Point
Modify Control Options
• MAINSTAT
• STARTUP
• COMPRESS
• HEAT_EX
• POWER
• ISM_STAT
• CVC_PSWD
Modify the Setpoint
DECREASE
INCREASE
QUIT
ENTER
NEXT
PREVIOUS
SELECT
EXIT
Select the Setpoint
(ENTER A 4-DIGIT PASSWORD)
1
1
1
Fig. 15 — 19XRT CVC Menu Structure
17
SERVICE TABLE
NEXT
PREVIOUS
ALARM HISTORY
CONTROL TEST
CONTROL ALGORITHM STA TUS
List the Control Algorithm Status Tables
CAPACITY (Capacity Control)
OVERRIDE (Override Status)
LL_MAINT (Lead Lag Status)
• ISM_HIST (ISM Alarm History)
• LOADSHED
WSMDEFME (Water System Manager Control Status)
OCCDEFCM (Time Schedule Status) Select a Table
NEXT
SELECT
Display Alarm History
(The table holds up to 25 alarms and alerts with the most recent alarm at the top of the screen.)
PREVIOUS
EXIT
SELECT
EXIT
List the Control Tests
Select a Test
NEXT
CCM Thermistors
CCM Pressure Transducers
Pumps
Discrete Outputs
Guide Vane Actuator
Diffuser Actuator
Pumpdown/Lockout
Terminate Lockout
Guide Vane Calibration
PREVIOUS
SELECT
EXIT
OCCDEFM (Time Schedule Status)
Data Select Table
NEXT
EQUIPMENT CONFIGURATION List the Equipment Configuration Tables
CONTINUED ON NEXT PAGE
PREVIOUS
SELECT
OCCPC01S (Local Status) OCCPC02S (CCN, ICE BUILD Status) OCCPC03S (CCN Status)
EXIT
Select a Table
NEXT
Select a Parameter
Modify a Parameter
INCREASE
ENABLE
Fig. 16 — 19XRT Service Menu Structure
CAPACITY (Capacity Control Algorithm)
OVERRIDE (Override Status)
LL_MAINT (LEADLAG Status)
WSMDEFM2 (Water System Manager Control Status)
Maintenance Table Data
NET_OPT
BRODEF
OCCEFCS
HOLIDAYS
CONSUME
RUNTIME
PREVIOUS
DISABLE
SELECT
EXIT
SELECT
QUIT
QUIT
PREVIOUS
NEXT
DECREASE
EXIT
ENTER
ENTER
(ANALOG VALUES)
(DISCRETE VALUES)
18
SERVICE MENU CONTINUED FROM PREVIOUS PAGE
EQUIPMENT SERVICE
Select a Service Table
NEXT
Select a Service Table Parameter
NEXT
Modify a Service Table Parameter
INCREASE
ENABLE
TIME AND DATE
ATTACH TO NETWORK DEVICE
Select a Device
NEXT
Modify Device Address
INCREASE
Use to attach CVC to another CCN network or device
Attach to "LOCAL" to enter this machine
To upload new tables
PREVIOUS
PREVIOUS
DECREASE
DISABLE
PREVIOUS
DECREASE
ISM (STARTER CONFIG DATA)
Service Tables:
OPTIONS
SETUP1
SETUP2
• LEADLAG
• RAMP_DEM
• TEMP_CTL
SELECT
SELECT
QUIT QUIT
List Network Devices
Local
• Device 1
• Device 2
• Device 3
• Device 4 •
• Device 5
• Device 6
• Device 7
• Device 8
• Device 9 Attach T o Any Device
SELECT
ENTER
EXIT
EXIT
ENTER
ENTER
ATTACH
EXIT
(ANALOG VALUES) (DISCRETE VALUES)
Display Time and Date Table:
To Modify — Current Time — Day of Week
INCREASE
YES
DECREASE
(ENTER A 4-DIGIT PASSWORD)
4
4
4
4
Service Tables:
ISM (STARTER) CONFIG PASSWORD
• ISM_CONF
— Current Date — Holiday Today
EXIT
EXIT
NO
ENTER
ENTER
(ANALOG VALUES)
(DISCRETE VALUES)
LOG OUT OF DEVICE
CVC CONFIGURATION
LEGEND
CCN — Carrier Comfort Network CVC — Chiller Visual Control IMP Imperial ISM Integrated Starter Module PIC II — Product Integrated Control II
Default Screen
CCN
CVC Configuration Table
INCREASE
To Modify — CVC CCN Address
LOCAL
DECREASE
— English (US IMP) or S.I. Metric Units — Password
RESET
ENTER
To View — CVC Software Version (last 2 digits of part number
MENU
EXIT
indicate software version)
Fig. 16 — 19XRT Service Menu Structure (cont)
19
3. Press SELECT to select the highlighted value. Then:
For Discrete Points — Press YES or NO to se- lect the desired state.
YES NO ENTER EXIT
For Analog Points Press INCREASE or
DECREASE
to select the desired value.
4. Press ENTER to register the new value.
NOTE: When overriding or changing metric values, it is nec­essary to hold down the softkey for a few seconds in order to see a value change, especially on kilopascal values.
2. Press NEXT or PREVIOUS to highlight the de­sired schedule.
OCCPC01S — LOCAL Time Schedule OCCPC02S — ICE BUILD Time Schedule OCCPC03S — CCN Time Schedule
3. Press SELECT to view the desired time schedule.
4. Press NEXT or PREVIOUS to highlight the de­sired period or override to change.
5. Press SELECT to access the highlighted period or override.
To Remove an Override
1. On the point status table press NEXT or PREVIOUS
to highlight the desired value.
2. Press SELECT to access the highlighted value.
3. Press RELEASE to remove the override and return the
point to the PIC II’s automatic control.
Override Indication — An override value is indicated by ‘ ‘SUPVSR,’’‘‘SERVC,’’or ‘‘BEST’’flashing next to the point
value on the STATUS table.
TIME SCHEDULE OPERATION (Fig. 17)
1. On the Menu screen, press SCHEDULE
.
6. a. Press INCREASE or DECREASE to change the time values. Override values are in one-hour incre-
ments, up to 4 hours.
Fig. 17 — Example of Time Schedule
Operation Screen
20
b. Press ENABLE to select days in the day-of-week
fields. Press DISABLE
to eliminate days from the
period.
7. Press ENTER to register the values and to move horizontally (left to right) within a period.
8. Press EXIT to leave the period or override.
9. Either return to Step 4 to select another period or override, or press EXIT
again to leave the current time
schedule screen and save the changes.
2. There are 5 set points on this screen: BASE DEMAND LIMIT ,LCW SETPOINT (leaving chilled water set point), ECW SETPOINT (entering chilled water set point), ICE BUILD SETPOINT, and TOWER FAN HIGH SET­POINT. Only one of the chilled water set points can be active at one time. The set point that is active is deter­mined from the SERVICE menu. See the Service Opera­tion section, page 44. The ice build (ICE BUILD) func­tion is also activated and configured from the SERVICE menu.
3. Press NEXT
or PREVIOUS to highlight the desired
set point entry.
4. Press SELECT to modify the highlighted set point.
5. Press INCREASE or DECREASE to change the se­lected set point value.
10. TheHoliday Designation (HOLIDEF table) may be found in the Service Operation section, page 44. The month, day, and duration for the holiday must be assigned. The Broadcast function in the BRODEF table also must be enabled for holiday periods to function.
TO VIEW AND CHANGE SET POINTS (Fig. 18)
1. To view the SETPOINT table, from the MENU screen
press SETPOINT
.
19XR_II
SETPOINT
Base Demand Limit
Control Point LCW Setpoint ECW Setpoint ICE BUILD Setpoint Tower Fan High Setpoint
SETPOINT SELECT
100%
50.0 F
60.0 F
40.0 F
85.0 F
6. Press ENTER to save the changes and return to the previous screen.
SERVICE OPERATION — To view the menu-driven pro­grams available for Service Operation, see Service Opera­tion section, page 44. For examples of CVC display screens, see Table 2.
Fig. 18 — Example of Set Point Screen
21
Table 2 — CVC Display Data
IMPORTANT: The following notes apply to all Table 2 examples.
1. Only 12 lines of information appear on theCVCscreen at any one time. Press the NEXT
point or to view items below or above the current screen. Press the NEXT
PREVIOUS
2. Toaccess the information shown in Examples 9 through 21, enter your 4-digit password after pressing the SERVICE no softkeys are pressed for 15 minutes, the CVC automatically
logs off (to prevent unrestricted access to PIC II controls) and re­verts to the default screen. If this happens, you must reenter your password to access the tables shown in Examples 9 through 21.
3. Termsin the Description column of these tables are listed as they appear on the CVC screen.
4. The CVC may be configured in English or Metric (SI) units using the CVC CONFIGURATION screen. See the Service Operation section, page 44, for instructions on making this change.
5. The items in the Reference Point Name column
the CVC screen
Building Supervisor (BS) software. They are listed in these tables as a convenience to the operator if it is necessary to cross ref­erenceCCN/BS documentation oruse CCN/BS programs.For more information, see the 19XRT CCN literature.
softkey twice to page forward; press the
softkey twice to page back.
. They are data or variable names used in CCN or
or PREVIOUS softkey to highlight a
softkey. If
do not appear on
6. Reference Point Names shown in these tables in all capital letters can beread by CCN andBS software. Of thesecapitalized names, those preceded by a dagger can also be changed (that is, written to) by the CCN, BS, and the CVC. Capitalized Reference Point Names preceded by two asterisks can be changed only from the CVC. Reference Point Names in lower case type can be viewed by CCN or BS only by viewing the whole table.
7. Alarms and Alerts:An asterisk
screen
indicates that the chiller is in an alarm state; an exclama­tion point in the far right field of the CVC screen indicates an alert state. The asterisk (or exclamation point) indicates that the value on that line has exceeded (or is approaching) a limit. For more information on alarms and alerts, see the Alarms and Alerts section, page 15.
12T Motor Overload CCN Carrier Comfort Network CHW Chilled Water CR Control Relay CT Current Transformer CVC Chiller Visual Control ECW Entering Chilled Water HGBP — Hot Gas Bypass ISM Integrated Starter Module LCW Leaving Chilled Water LRA Locked Rotor Amps mA Milliamps P—Pressure SS Solid State T—Temperature VFD Variable Frequency Drive WSM — Water System Manager
in the far right field of a CVC status
LEGEND
EXAMPLE 1 — CVC DEFAULT SCREEN
The following data is displayed in the CVC Default screen.
DESCRIPTION RANGE UNITS
(PRIMARY MESSAGE) (SECONDARY MESSAGE) (DATE AND TIME)
Compressor Ontime 0-500000.0 HOURS C Entering Chilled Water −40-245 DEG F ECW CHW IN Leaving Chilled Water −40-245 DEG F LCW CHW OUT Evaporator Temperature −40-245 DEG F ERT EVAP REF Entering Condenser Water −40-245 DEG F ECDW CDW IN Leaving Condenser Water −40-245 DEG F LCDW CDW OUT Condenser Temperature −40-245 DEG F CRT COND REF Oil Pressure 0-420 PSI OILPD OILPRESS Oil Sump Temp −40-245 DEG F OILT OIL TEMP Average Line Current 0-999 % AMPS
NOTE: The last three entries are used to indicate operating mode to the PIC II. These values may be forced by the CVC only.
0-1 CCN 0-1 LOCAL 0-1 RESET
REFERENCE POINT NAME
(ALARM HISTORY)
HRS
% AMPS %
DISPLAY
22
Table 2 — CVC Display Data (cont)
EXAMPLE 2 — MAINTSTAT DISPLAY SCREEN
To access this display from the CVC default screen:
1. Press MENU
2. Press STATUS
3. Press SELECT
Control Mode NOTE 1 NOTE 1 CMODE Run Status NOTE 2 NOTE 2 RUNSTAT Start Inhibit Timer 0-15 min T Occupied ? 0/1 NO/YES OCC
System Alert/Alarm 0-2 NOTE 3 SYS *Chiller Start/Stop 0/1 STOP/START CHIL S S *Remote Start Contact 0/1 OFF/ON REMCON
Temperature Reset −30-30 DEG F T *Control Point 10-120 DEG F LCW STPT
Chilled Water Temp −40-245 DEG F CHW *Active Demand Limit 40-100 % DEM LIM
Average Line Current 0-999 % AMPS %
Motor Percent Kilowatts 0-999 % KW
Auto Demand Limit Input 4-20 mA AUTODEM
Auto Chilled Water Reset 4-20 mA AUTORES
Remote Reset Sensor −40-245 DEG F R
Total Compressor Starts 0-99999 C STARTS
Starts in 12 Hours 0-8 STARTS
Compressor Ontime 0-500000.0 HOURS C *Service Ontime 0-32767 HOURS S HRS
Ice Build Contact 0-1 OPEN/CLOSE ICE
Refrigerant Leak Sensor 0-20 mA REF LEAK
NOTES:
1. Reset, Off, Local, CCN
2. Timeout, Ready, Recycle, Prestart, Start-up, Ramping, Running, Demand, Override, Shutdown, Trippout, Pumpdown, Lockout
3. Normal, Alert, Alarm
4. All variables with capital letter point names are available for CCN read operation. Those shown with (*) support write operations for all CCN devices.
.
( MAINSTAT will be highlighted). .
DESCRIPTION STATUS UNITS POINT
START
ALM
RESET
TMP
P
RESET
HRS
CON
EXAMPLE3—STARTUP DISPLAY SCREEN
To access this display from the CVC default screen:
1. Press MENU
2. Press STATUS
3. Scroll down to highlight STARTUP
4. Press SELECT
Actual Guide Vane Pos 0-100 % GV
**Chilled Water Pump 0-1 OFF/ON CHWP
Chilled Water Flow 0-1 NO/YES CHW FLOW
**Condenser Water Pump 0-1 OFF/ON CDP
Condenser Water Flow 0-1 NO/YES CDW Oil Pump Relay 0-1 OFF/ON OILR
**Oil Pump Delta P −6.7-200 ^PSI OILPD
Compressor Start Relay 0-1 OFF/ON CMPR Compressor Start Contact 0-1 OPEN/CLOSED 1M Starter Trans Relay 0-1 OFF/ON TRANS
Compressor Run Contact 0-1 OPEN/CLOSED 2M AUX **Tower Fan Relay Low 0-1 OFF/ON TFR **Tower Fan Relay High 0-1 OFF/ON TFR HIGH
Starter Fault 0-1 ALARM/NORMAL STARTFLT
Spare Safety Input 0-1 ALARM/NORMAL SAFETY
Shunt Trip Relay 0-1 OFF/ON TRIPR
Starter Fault Status 0-255 ISMFLT
NOTE:All variables with CAPITALLETTER point names are available for CCN read operation. Those shown with (**) shall support write operations for the CVC only.
.
.
.
.
DESCRIPTION STATUS UNITS POINT
POS
FLOW
AUX
LOW
23
Table 2 — CVC Display Data (cont)
EXAMPLE 4 — COMPRESS DISPLAY SCREEN
To access this display from the CVC default screen:
1. Press MENU
2. Press STATUS
3. Scroll down to highlight COMPRESS .
4. Press SELECT
Actual Guide Vane Pos 0-100 % GV Guide Vane Delta 0-100 % GV DELTA
**Target Guide Vane Pos 0-100 % GV
Oil Sump Temp −40-245 DEG F OILT
**Oil Pump Delta P −6.7-200 PSI OILPD
Comp Discharge Temp −40-245 DEG F CMPD Comp Thrust Brg Temp −40-245 DEG F MTRB Comp Motor Winding Temp −40-245 DEG F MTRW Spare Temperature 1 −40-245 DEG F SPARE Spare Temperature 2 −40-245 DEG F SPARE T2 Oil Heater Relay 0/1 OFF/ON OILHEAT
Diffuser Actuator 0-100 % DIFF **Target VFD Speed 0-110 % VFD OUT **Actual VFD Speed 0-100 % VFD
Surge Protection Counts 0-5 SPC
NOTE:All variables with CAPITALLETTER point names are available for CCN read operation. Those shown with (**) shall support write operations for the CVC only.
.
.
.
DESCRIPTION STATUS UNITS POINT
POS TRG
T1
ACT
ACT
EXAMPLE 5 — HEAT
To access this display from the CVC default screen:
1. Press MENU
2. Press STATUS
3. Scroll down to highlight HEAT
4. Press SELECT
**Chilled Water Delta P −6.7-420 PSI CHWPD
Entering Chilled Water −40-245 DEG F ECW Leaving Chilled Water −40-245 DEG F LCW Chilled Water Delta T −6.7-420 ^ F CHW Chill Water Pulldown/Min −20-20 ^ F CHW Evaporator Refrig Temp −40-245 DEG F ERT
**Evaporator Pressure −6.7-420 PSI ERP
Evaporator Approach 0-99 ^ F EVAP
**Condenser Water Delta P −6.7-420 PSI CDWPD
Entering Condenser Water −40-245 DEG F ECDW Leaving Condenser Water −40-245 DEG F LCDW Condenser Refrig Temp −40-245 DEG F CRT
**Condenser Pressure −6.7-420 PSI CRP
Condenser Approach 0-99 ^ F COND Hot Gas Bypass Relay 0/1 OFF/ON HGBYPASS Surge/HGBP Active ? 0/1 NO/YES SHG Active Delta P 0-200 PSI DP A Active Delta T 0-200 DEG F DT A Surge/HGBP Delta T 0-200 DEG F DT
NOTE:All variables with CAPITALLETTER point names are available for CCN read operation. Those shown with (**) shall support write operations for the CVC only.
.
.
EX .
.
DESCRIPTION STATUS UNITS POINT
EX DISPLAY SCREEN
C
DT PULL
APP
APP
ACT
24
Table 2 — CVC Display Data (cont)
EXAMPLE 6 — POWER DISPLAY SCREEN
To access this display from the CVC default screen:
1. Press MENU
2. Press STATUS
3. Scroll down to highlight POWER .
4. Press SELECT
Average Line Current 0-999 % AMPS Actual Line Current 0-99999 AMPS AMP A Average Line Voltage 0-999 % VOLT Actual Line Voltage 0-99999 VOLTS VOLT A Power Factor 0.0-1.0 POW FACT Motor Kilowatts 0-99999 kW KW Motor Kilowatt-Hours 0-99999 kWH KWH Demand Kilowatts 0-99999 kWH DEM Line Current Phase 1 0-99999 AMPS AMPS Line Current Phase 2 0-99999 AMPS AMPS 2 Line Current Phase 3 0-99999 AMPS AMPS Line Voltage Phase 1 0-99999 VOLTS VOLT 1 Line Voltage Phase 2 0-99999 VOLTS VOLT 2 Line Voltage Phase 3 0-99999 VOLTS VOLT Ground Fault Phase 1 0-999 AMPS GF 1 Ground Fault Phase 2 0-999 AMPS GF 2 Ground Fault Phase 3 0-999 AMPS GF Frequency 0-99 Hz FREQ 12T Sum Heat-Phase 1 0-200 % SUM1HEAT 12T Sum Heat-Phase 2 0-200 % SUM2HEAT 12T Sum Heat-Phase 3 0-200 % SUM3HEAT
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation.
.
.
.
DESCRIPTION STATUS UNITS POINT
%
P
KW
1 3
3
3
EXAMPLE7—ISM
To access this display from the CVC default screen:
1. Press MENU
2. Press STATUS
3. Scroll down to highlight ISM STAT .
4. Press SELECT
ISM Fault Status 0-223 ISMFLT Single Cycle Dropout 0-1 NORMAL/ALARM CYCLE
Phase Loss 0-1 NORMAL/ALARM PH
Overvoltage 0-1 NORMAL/ALARM OV VOLT
Undervoltage 0-1 NORMAL/ALARM UN VOLT
Current Imbalance 0-1 NORMAL/ALARM AMP Voltage Imbalance 0-1 NORMAL/ALARM VOLT UNB Overload Trip 0-1 NORMAL/ALARM OVERLOAD Locked Rotor Trip 0-1 NORMAL/ALARM LRATRIP Starter LRA Trip 0-1 NORMAL/ALARM SLRATRIP Ground Fault 0-1 NORMAL/ALARM GRND
Phase Reversal 0-1 NORMAL/ALARM PH REV Frequency Out of Range 0-1 NORMAL/ALARM FREQFLT ISM Power on Reset 0-1 NORMAL/ALARM ISM Phase 1 Fault 0-1 NORMAL/ALARM PHASE 1
Phase 2 Fault 0-1 NORMAL/ALARM PHASE 2
Phase 3 Fault 0-1 NORMAL/ALARM PHASE
ICR Start Complete 0-1 FALSE/TRUE START OK
1M Start/Run Fault 0-1 NORMAL/ALARM 1M FLT 2M Start/Run Fault 0-1 NORMAL/ALARM 2M Pressure Trip Contact 0-1 NORMAL/ALARM PRS TRIP
Starter Fault 0-1 NORMAL/ALARM STRT
Motor Amps Not Sensed 0-1 NORMAL/ALARM NO AMPS Starter Acceleration Fault 0-1 NORMAL/ALARM ACCELFLT High Motor Amps 0-1 NORMAL/ALARM HIGHAMPS 1CR Stop Complete 0-1 FALSET/TRUE STOP
1M/2M Stop Fault 0-1 NORMAL/ALARM 1M2MSTOP
Motor Amps When Stopped 0-1 NORMAL/ALARM AMPSTOP
Hardware Failure 0-1 NORMAL/ALARM HARDWARE
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation.
.
.
.
DESCRIPTION STATUS UNITS POINT
STAT SCREEN
LOSS
UNB
FLT
POR
FLT
FLT
OK
1
3
25
Table 2 — CVC Display Data (cont)
EXAMPLE 8 — SETPOINT DISPLAY SCREEN
To access this display from the CVC default screen:
1. Press MENU
2. Press SETPOINT
3. Press SELECT
Base Demand Limit
Control Point 40-100 % DLM 100
LCW Set Point 10-120 DEG F lcw ECW Set Point 15-120 DEG F ecw sp 60.0 Ice Build Set Point 15-60 DEG F ice Tower Fan High Set Point 55-105 DEG F TFH SP 75
NOTE: All variables are available for CCN read operation; forcing shall not be supported on set point screens.
To access this display from the CVC default screen:
1. Press MENU
2. Press SERVICE
3. Scroll down to highlight CONTROL ALGORITHM STATUS .
4. Press SELECT
5. Scroll down to highlight CAPACITY
.
(Base Demand Limit will be highlighted).
.
DESCRIPTION STATUS UNITS POINT DEFAULT
sp 50.0
sp 40.0
EXAMPLE 9 — CAPACITY DISPLAY SCREEN
.
.
.
.
DESCRIPTION STATUS UNITS POINT
Entering Chilled Water −40-245 DEG F ECW Leaving Chilled Water −40-245 DEG F LCW Capacity Control
Control Point 10-120 DEG F ctrlpt Control Point Error −99-99 DEG F cperr ECW Delta T −99-99 DEG F ecwdt ECW Reset −99-99 DEG F ecwres LCW Reset −99-99 DEG F lcwres Total Error + Resets −99-99 DEG F error
Guide Vane Delta −2-2 % gvd Target Guide Vane Pos 0-100 % GV Actual Guide Vane Pos 0-100 % GV POS Target VFD Speed 0-100 % VFD Actual VFD Speed 0-100 % VFD ACT VFD Gain 0.1-1.5 VFD CTRL Demand Inhibit Active 0-1 NO/YES DEM Amps/kW Ramp 0-100 % DMDLIM
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation; forcing shall not be supported on maintenance screen.
TRG
OUT
INH
26
Table 2 — CVC Display Data (cont)
EXAMPLE 10 — OVERRIDE DISPLAY SCREEN
To access this display from the CVC default screen:
1. Press MENU
2. Press SERVICE
3. Scroll down to highlight CONTROL ALGORITHM STATUS .
4. Press SELECT
5. Scroll down to highlight OVERRIDE
Comp Motor Winding Temp −40-245 DEG F MTRW Comp Motor Temp Override 150-200 DEG F MT Condenser Pressure 0-420 PSI CRP Cond Press Override 90-180 PSI CP OVER Evaporator Refrig Temp −40-245 DEG F ERT Evap Ref Override Temp 2-45 DEG F ERT Comp Discharge Temp −40-245 DEG F CMPD Comp Discharge Alert 125-200 DEG F CD Comp Thrust Brg Temp −40-245 DEG F MTRB Comp Thrust Brg Alert 165-185 DEG F TB ALERT Actual Superheat −20-99 ^ F SUPRHEAT Superheat Required 6-99 ^ F SUPR Condenser Refrig Temp −40-245 DEG F CRT
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation; forcing shall not be supported on maintenance screens.
.
.
.
.
DESCRIPTION STATUS UNITS POINT
OVER
OVER
ALEERT
REQ
EXAMPLE 11 — LL
To access this display from the CVC default screen:
1. Press MENU
2. Press SERVICE
3. Scroll down to highlight CONTROL ALGORITHM STATUS .
4. Press SELECT
5. Scroll down to highlight LL
Lead Lag Control
LEAD/LAG: NOTE 1 leadlag Configuration Current Mode NOTE 2 llmode Load Balance Option 0/1 DSABLE/ENABLE loadbal
LAG START TIME 2-60 MIN lagstart LAG STOP TIME 2-60 MIN lagstop PRESTART FAULT Time 2-30 MIN preflt
Pulldown: Delta T/Min x.xx ^ DEG pull LEAD CHILLER in Control 0/1 NO/YES leadctrl
LAG CHILLER: Mode NOTE 3 lagmode
STANDBY CHILLER: Mode NOTE 3 stdmode
Spare Temperature 1 −40-245 DEG F SPARE T1 Spare Temperature 2 −40-245 DEG F SPARE
NOTES:
1. DISABLE, LEAD, LAG, STANDBY, INVALID
2. DISABLE, LEAD, LAG, STANDBY, RECOVERY, CONFIG
3. Reset, Off, Local, CCN
4. Timeout, Ready, Recycle, Prestart, Startup Ramping, Running, Demand, Override, Shutdown, Trippout, Pumpdown, Lockout
5. Stop, Start, Retain
6. All variables with CAPITALLETTER point names are available for CCN read operation; forcing shall not be supported on maintenance screens.
.
.
.
MAINT. .
DESCRIPTION STATUS UNITS POINT
Satisfied? 0/1 NO/YES pull
Run Status NOTE 4 lagstat Start/Stop NOTE 5 lag Recovery Start Request 0/1 NO/YES lag
Run Status NOTE 4 stdstat Start/Stop NOTE 5 Std Recovery Start Request 0/1 NO/YES std rec
MAINT DISPLAY SCREEN
dt sat
s s rec
s s
T2
27
Table 2 — CVC Display Data (cont)
EXAMPLE 12 — ISM HIST DISPLAY SCREEN
To access this display from the CVC default screen:
1. Press MENU
2. Press SERVICE
3. Scroll down to highlight CONTROL ALGORITHM STATUS .
4. Press SELECT
5. Scroll down to highlight ISM
ISM FAULT HISTORY Values At Last Fault: Line Current Phase 1 0-99999 AMPS AMPS Line Current Phase 2 0-99999 AMPS AMPS Line Current Phase 3 0-99999 AMPS AMPS H3 Line Voltage Phase 1 0-99999 VOLTS VOLTS H1 Line Voltage Phase 2 0-99999 VOLTS VOLTS Line Voltage Phase 3 0-99999 VOLTS VOLTS H3 Ground Fault Phase 1 0-999 AMPS GRFT H31 Ground Fault Phase 2 0-999 AMPS GRFT Ground Fault Phase 3 0-999 AMPS GRFT H12 I2T Sum Heat-Phase 1 0-200 % SUM1HT H I2T Sum Heat-Phase 2 0-200 % SUM2HT I2T Sum Heat-Phase 3 0-200 % SUM3HT H Phase 1 Faulted? 0/1 NO/YES PHASE H1 Phase 2 Faulted? 0/1 NO/YES PHASE Phase 3 Faulted? 0/1 NO/YES PHASE H3 Line Frequency 0-99 Hz FREQ ISM Fault Status 0-9999 ISMFLT H
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation; forcing shall not be supported on maintenance screens.
.
.
.
HIST .
DESCRIPTION STATUS UNITS POINT
H1 H2
H2
H23
H2
H
H
EXAMPLE 13 — WSMDEFME DISPLAY SCREEN
To access this display from the CVC default screen:
1. Press MENU
2. Press SERVICE
3. Scroll down to highlight CONTROL ALGORITHM STATUS
4. Press SELECT
5. Scroll down to highlight WSMDEFME
WSM Active? 0/1 NO/YES WSMSTAT Chilled Water Temp 0.0-99.9 DEG F CHWTEMP
Equipment Status 0/1 OFF/ON CHLRST Commanded State XXXXXXXX TEXT CHLRENA
CHW setpt Reset Value 0.0-25.0 DEG F CHWRVAL Current CHW Set Point 0.0-99.9 DEG F CHWSTPT
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation; forcing shall not be supported on maintenance screens.
.
.
.
.
.
DESCRIPTION STATUS UNITS POINT
28
Table 2 — CVC Display Data (cont)
EXAMPLE 14 — NET OPT DISPLAY SCREEN
To access this display from the CVC default screen:
1. Press MENU
2. Press SERVICE
3. Scroll down to highlight EQUIPMENT CONFIGURATION .
4. Press SELECT
5. Scroll down to highlight NET
Loadshed Function
Group Number 0-99 LDSGRPN 0 Demand Limit Decrease 0-60 % LDSDLTA 20 Maximum Loadshed Time 0-120 MIN MAXSHED 60
CCN Occupancy Config:
Schedule Number 3-99 OCC Broadcast Option 0-1 DSABLE/ENABLE OCCBRST DSABLE
Alarm Configuration
Re-alarm Time 0-1440 MIN RETIME 30 Alarm Routing 0-1 ROUTING 10000000
NOTE: No variables are available for CCN read or write operation.
.
.
.
OPT .
DESCRIPTION STATUS UNITS POINT DEFAULT
NUM 3
EXAMPLE 15 — ISM
To access this display from the CVC default screen:
1. Press MENU
2. Press SERVICE
3. Scroll down to highlight ISM (STARTER) CONFIG DATA
4. Press SELECT
5. Scroll down to highlight ISM
Starter Type 0-2 starter 1 (0 = Full, 1 = Red, 2 = SS/VFD) Motor Rated Line Voltage 200-13200 VOLTS v Volt Transformer Ratio:1 1-33 vt Overvoltage Threshold 105-115 % overvolt 115 Undervoltage Threshold 85-95 % undvolt 85 Over/Under Volt Time 1-10 SEC uvuntime 5 Voltage % Imbalance 1-10 % v Voltage Imbalance Time 1-10 SEC v Motor Rated Load Amps 10-5000 AMPS a fs 200 Motor Locked Rotor Trip 100-60000 AMPS motor lr 1000 Locked Rotor Start Delay 1-10 cycles lrdelay 5 Starter LRA Rating 100-60000 AMPS start Motor Current CT Ratio:1 3-1000 ct turns 100 Current % Imbalance 5-40 % c Current Imbalance Time 1-10 SEC c time 5 3 Grnd Fault CT’s? (1 = No) 0-1 NO/YES gf phase YES Ground Fault CT Ratio:1 150 gf Ground Fault Current 1-25 AMPS gf amps 15 Ground Fault Start Delay 1-20 cycles gf Ground Fault Persistence 1-10 cycles gf pers 5 Single Cycle Dropout 0/1 DSABLE/ENABLE cycdrop DSABLE Frequency = 60 Hz? (No = 50) 0/1 NO/YES freq YES Line Frequency Faulting 0/1 DSABLE/ENABLE freq
NOTE: No variables are available for CCN read or write operation.
.
.
.
.
CONF .
DESCRIPTION STATUS UNITS POINT DEFAULT
CONF DISPLAY SCREEN
fs 460
rat 1
unbal 10 time 5
lr 2000
unbal 15
ctr 150 delay 10
en DSABLE
29
Table 2 — CVC Display Data (cont)
EXAMPLE 16 — OPTIONS DISPLAY SCREEN
To access this display from the CVC default screen:
1. Press MENU
2. Press SERVICE
3. Scroll down to highlight EQUIPMENT SERVICE .
4. Press SELECT
5. Scroll down to highlight OPTIONS
Auto Restart Option 0/1 DSABLE/ENABLE ASTART DSABLE Remote Contacts Option 0/1 DSABLE/ENABLE MODES DSABLE Soft Stop Amps Threshold 40-100 % STRTSTOP 100
Surge/Hot Gas Bypass
Surge Limit/HGBP Option 0/1 srg Select: Surge = 0, HGBP = 1 Min. Load Point (T1/P1) Surge/HGBP Delta T1 0.5-20 ^ F hgb Surge/HGBP Delta P1 30-170 PSI hgb Full Load Point (T2/P2) Surge/HGBP Delta T2 0.5-20 ^ F hgb dt2 10 Surge/HGBP Delta P2 50-170 PSI hgb Surge/HGBP Deadband 0.5-3 ^ F hgb db 1
Surge Protection
Surge Delta % Amps 5-20 % surge Surge Time Period 7-10 MIN surge
Ice Build Control
Ice Build Option 0/1 DSABLE/ENABLE ibopt DSABLE Ice Build Termination 0-2 ibterm 0 0 = Temp, 1 = Contacts, 2 = Both Ice Build Recycle 0/1 DSABLE/ENABLE ibrecyc DSABLE
Refrigerant Leak Option 0/1 DSABLE/ENABLE LEAK Refrigerant Leak Alarm mA 4-20 mA LEAK MA 20
NOTE: No variables are available for CCN read or write operation.
.
.
.
.
DESCRIPTION STATUS UNITS POINT DEFAULT
hgbp 0
dt1 1.5 dp1 50
dp2 85
a10 t8
EN DSABLE
EXAMPLE 17 — SETUP1 DISPLAY SCREEN
To access this display from the CVC default screen:
1. Press MENU
2. Press SERVICE
3. Scroll down to highlight EQUIPMENT SERVICE .
4. Press SELECT
5. Scroll down to highlight SETUP1
Comp Motor Temp Override 150-200 DEG F MT Cond Press Override 90-165 PSI CP OVER 125 Comp Discharge Alert 125-200 DEG F C Comp Thrust Brg Alert 165-185 DEG F TB ALERT 175
Chilled Medium 0/1 WATER/BRINE MEDIUM WATER Chilled Water Deadband .5-2.0 ^F CS Evap Refrig Trippoint 0.0-40.0 DEG F ERT Refrig Override Delta T 2.0-5.0 ^F REF OVER 3 Condenser Freeze Point −20 - 35 DEG F CDFREEZE 34
Evap Flow Delta P Cutout 0.5 - 50.0 PSI EVAP Cond Flow Delta P Cutout 0.5 - 50.0 PSI COND CUT 5.0 Water Flow Verify Time 0.5-5 MIN WFLOW Oil Press Verify Time 15-300 SEC OILPR T40 Recycle Control
Recycle Restart Delta T 2.0-10.0 DEG F RCYCR Recycle Shutdown Delta 0.5-4.0 DEG F RCYCS DT 1
SPARE ALERT/ALARM ENABLE Disable=0, Lo=1/3,Hi=2/4
Spare Temp #1 Enable 0.4 sp1 Spare Temp #1 Limit −40-245 DEG F sp1 lim 245 Spare Temp #2 Enable 0-4 sp2 Spare Temp #2 Limit -40-245 DEG F sp2 lim 245
NOTE: No variables are available for CCN read operation; forcing shall not be supported on service screens.
.
.
.
.
DESCRIPTION STATUS UNITS POINT DEFAULT
OVER 200
ALERT 200
DB 1.0
TRIP 33
CUT 5.0
T5
DT 5
en 0 en 0
30
Loading...
+ 82 hidden pages