Carrier 19XL User Manual

Page 1
19XL
Hermetic Centrifugal Liquid Chillers
50/60 Hz
With HCFC-22 and HFC-134a
Start-Up, Operation, and Maintenance Instructions
SAFETY CONSIDERATIONS
Centrifugal liquid chillers are designed to provide safe and reliable service when operated within design specifications. When operating this equipment, use good judgment and safety precautions to avoid damage to equipment and property or injury to personnel.
Be sure you understand and follow the procedures and safety precautions contained in the chiller instructions as well as those listed in this guide.
DO NOT VENT refrigerant relief valves within a building. Outlet from rupture disc or relief valve must be vented outdoors in accordance with the latest edition of ANSI/ASHRAE 15 (American National Standards Institute/American Society of Heat­ing, Refrigeration, and Air Conditioning Engineers). The accumu­lation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation.
PROVIDE adequate ventilation in accordance withANSI/ASHRAE 15, especially for enclosed and low overhead spaces. Inhalation of high concentrations of vapor is harmful and may cause heart irregularities, unconsciousness, or death. Misuse can be fatal. Vapor is heavier than air and reduces the amount of oxygen avail­able for breathing. Product causes eye and skin irritation. Decom­position products are hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a chiller for any purpose. Oxygen gas reacts violently with oil, grease, and other common substances.
NEVER EXCEED specified test pressures, VERIFY the allowable test pressure by checking the instruction literature and the design pressures on the equipment nameplate.
DO NOT USE air for leak testing. Use only refrigerant or dry nitrogen.
DO NOT VALVE OFF any safety device. BE SURE that all pressure relief devices are properly installed and
functioning before operating any chiller.
DO NOT WELD OR FLAMECUT any refrigerant line or vessel until all refrigerant(liquidandvapor)has been removed from chiller. Traces of vapor should be displaced with dry air or nitrogen and the work area should be well ventilated. Refrigerant in contact with
an open flame produces toxic gases.
DO NOT USE eyebolts or eyebolt holes to rig chiller sections or the entire assembly.
DO NOT work on high-voltage equipment unless you are a quali­fied electrician.
DO NOTWORK ON electrical components, including control pan­els, switches, starters, or oil heater until you are sure ALL POWER IS OFF and no residual voltage can leak from capacitors or solid­state components.
LOCK OPENAND T AGelectrical circuits during servicing. IF WORK IS INTERRUPTED, confirm that all circuits are deenergized be­fore resuming work.
AVOID SPILLING liquid refrigerant on skin or getting it into the eyes. USE SAFETY GOGGLES. Wash any spills from the skin with soap and water. If liquid refrigerant enters the eyes, IMME­DIATELY FLUSH EYES with water and consult a physician.
NEVER APPLY an open flame or live steam to a refrigerant cylinder. Dangerous over pressure can result. When it is necessary to heat refrigerant, use only warm (110 F [43 C]) water.
DO NOT REUSE disposable (nonreturnable) cylinders or attempt to refill them. It is DANGEROUS AND ILLEGAL. When cylinder is emptied, evacuate remaining gas pressure, loosen the collar and unscrew and discard the valve stem. DO NOT INCINERATE.
CHECK THE REFRIGERANT TYPE before adding refrigerant to the chiller. The introduction of the wrong refrigerant can cause dam­age or malfunction to this chiller.
Operation of this equipment with refrigerants other than those cited herein should comply with ANSI/ASHRAE-15 (latest edi­tion). Contact Carrier for further information on use of this chiller with other refrigerants.
DO NOT ATTEMPTTOREMOVE fittings, covers, etc., while chiller is under pressure or while chiller is running. Be sure pressure is at 0 psig (0 kPa) before breaking any refrigerant connection.
CAREFULLY INSPECT all relief devices, rupture discs, and other relief devices AT LEAST ONCE A YEAR. If chiller operates in a corrosive atmosphere, inspect the devices at more frequent intervals.
DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief device when corrosion or build-up of foreign material (rust, dirt, scale, etc.) is found within the valve body or mechanism. Replace the device.
DO NOT install relief devices in series or backwards. USE CARE when working near or in line with a compressed spring.
Sudden release of the spring can cause it and objects in its path to act as projectiles.
DO NOT STEP on refrigerant lines. Broken lines can whip about and release refrigerant, causing personal injury.
DO NOT climb over a chiller. Use platform, catwalk, or staging. Follow safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or move inspection covers or other heavy components. Even if com­ponents are light, use mechanical equipment when there is a risk of slipping or losing your balance.
BE AWARE that certain automatic start arrangements CAN EN­GAGE THE STARTER, TOWER FAN, OR PUMPS. Open the disconnect ahead of the starter, tower fans, or pumps.
USE only repair or replacement parts that meet the code require­ments of the original equipment.
DO NOT VENT OR DRAIN waterboxes containing industrial brines, liquid, gases, or semisolids without the permission of your process control group.
DO NOT LOOSEN waterbox cover bolts until the waterbox has been completely drained.
DOUBLE-CHECK that coupling nut wrenches, dial indicators, or other items have been removed before rotating any shafts.
DO NOT LOOSEN a packing gland nut before checking that the nut has a positive thread engagement.
PERIODICALLY INSPECT all valves, fittings, and piping for cor­rosion, rust, leaks, or damage.
PROVIDE A DRAIN connection in the vent line near each pres­sure relief device to prevent a build-up of condensate or rain water.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Tab 5a
PC 211 Catalog No. 531-971 Printed in U.S.A. Form 19XL-4SS Pg 1 7-96 Replaces: 19XL-3SS
Page 2
CONTENTS
Page
SAFETY CONSIDERATIONS ...................1
INTRODUCTION ..............................4
ABBREVIATIONS AND EXPLANATIONS .......4
CHILLER FAMILIARIZATION ..................5
Chiller Information Plate ......................5
System Components .........................5
Cooler .......................................5
Condenser ...................................5
Motor-Compressor ...........................5
Control Center ...............................5
Factory-Mounted Starter (Optional) ............5
Storage Vessel (Optional) .....................5
REFRIGERATION CYCLE .....................5
MOTOR/OIL REFRIGERATION
COOLING CYCLE ...........................5-8
LUBRICATION CYCLE .......................8,9
Summary ....................................8
Details ......................................8
Oil Reclaim System ..........................9
• DURING NORMAL CHILLER OPERATION
• DURING LIGHT LOAD CONDITIONS
STARTING EQUIPMENT ....................10,11
Unit Mounted Solid-State Starter
(Optional) ..................................10
Unit Mounted Wye-Delta Starter
(Optional) ..................................11
CONTROLS ...............................11-39
Definitions ..................................11
• ANALOG SIGNAL
• DIGITAL SIGNAL
• VOLATILE MEMORY
General .....................................11
PIC System Components ....................11
• PROCESSOR MODULE (PSIO)
• STARTER MANAGEMENT MODULE (SMM)
• LOCAL INTERFACE DEVICE (LID)
• 6-PACK RELAY BOARD
• 8-INPUT MODULES
• OIL HEATER CONTACTOR (1C)
• OIL PUMP CONTACTOR (2C)
• HOT GAS BYPASS CONTACTOR RELAY (3C) (Optional)
• CONTROL TRANSFORMERS (T1-T4)
• CONTROL AND OIL HEATER VOLTAGE SELECTOR (S1)
LID Operation and Menus ...................14
• GENERAL
• ALARMS AND ALERTS
• MENU STRUCTURE
• TO VIEW POINT STATUS
• OVERRIDE OPERATIONS
• TIME SCHEDULE OPERATION
• TO VIEW AND CHANGE SET POINTS
• SERVICE OPERATION
PIC System Functions .......................28
• CAPACITY CONTROL
• ENTERING CHILLED WATER CONTROL
• DEADBAND
• PROPORTIONAL BANDS AND GAIN
• DEMAND LIMITING
• CHILLER TIMERS
• OCCUPANCY SCHEDULE
Safety Controls .............................29
• SHUNT TRIP
Default Screen Freeze .......................29
Page
Motor Cooling Control .......................29
Ramp Loading Control ......................31
Capacity Override ...........................31
High Discharge Temperature Control .........32
Oil Sump Temperature Control ...............32
• PSIO SOFTWARE VERSIONS 08 AND LOWER
• PSIO SOFTWARE VERSIONS 09 AND HIGHER
Oil Cooler ..................................32
Remote Start/Stop Controls ..................32
Spare Safety Inputs .........................32
• SPARE ALARM CONTACTS
Condenser Pump Control ....................32
Condenser Freeze Protection ................32
Tower Fan Relay ............................33
Auto. Restart After Power Failure ............33
Water/Brine Reset ...........................33
• RESET TYPE 1
• RESET TYPE 2
• RESET TYPE 3
Demand Limit Control, Option
(Requires Optional 8-Input Module) ..........33
Surge Prevention Algorithm .................33
Surge Protection ............................34
Lead/Lag Control ...........................34
• COMMON POINT SENSOR INSTALLATION
• CHILLER COMMUNICATION WIRING
• LEAD/LAG OPERATION
• FAULTED CHILLER OPERATION
• LOAD BALANCING
• AUTO. RESTART AFTER POWER FAILURE
Ice Build Control ............................36
• ICE BUILD INITIATION
• START-UP/RECYCLE OPERATION
• TEMPERATURE CONTROL DURING ICE
BUILD
• TERMINATION OF ICE BUILD
• RETURN TO NON-ICE BUILD OPERATIONS
Attach to Network Device Control ............37
• CHANGING REFRIGERANT TYPES
• ATTACHING TO OTHER CCN MODULES
Service Operation ...........................38
• TO LOG ON
• TO LOG OFF
• HOLIDAY SCHEDULING
START-UP/SHUTDOWN/RECYCLE
SEQUENCE ...............................39-41
Local Start-Up ..............................39
Shutdown Sequence ........................40
Automatic Soft-Stop Amps Threshold
(PSIO Software Version 09 and Higher) ......40
Chilled Water Recycle Mode .................40
Safety Shutdown ............................41
BEFORE INITIAL START-UP ................41-54
Job Data Required ..........................41
Equipment Required ........................41
Using the Optional Storage Tank
and Pumpout System .......................41
Remove Shipping Packaging ................41
Open Oil Circuit Valves ......................41
Tighten All Gasketed Joints and
Guide Vane Shaft Packing ..................41
Check Chiller Tightness .....................41
Refrigerant Tracer ...........................41
Leak Test Chiller ............................41
Standing Vacuum Test ......................43
Chiller Dehydration .........................47
Inspect Water Piping ........................47
2
Page 3
CONTENTS (cont)
Page
Check Optional Pumpout Compressor
Water Piping ...............................47
Check Relief Devices ........................47
Inspect Wiring ..............................47
Carrier Comfort Network Interface ...........48
Check Starter ...............................48
• MECHANICAL-TYPE STARTERS
• BENSHAW, INC. SOLID-STATE STARTER
Oil Charge ..................................50
Power Up the Controls and
Check the Oil Heater ........................50
• SOFTWARE VERSION
Set Up Chiller Control Configuration .........50
Input the Design Set Points ..................50
Input the Local Occupied Schedule
(OCCPC01S) ...............................50
Selecting Refrigerant Type ...................50
• TO CONFIRM REFRIGERANT TYPE
• TO CHANGE REFRIGERANT TYPE
Input Service Configurations ................50
• PASSWORD
• INPUT TIME AND DATE
• CHANGE LID CONFIGURATION
IF NECESSARY
• MODIFY CONTROLLER IDENTIFICATION
IF NECESSARY
• INPUT EQUIPMENT SERVICE PARAMETERS
IF NECESSARY
• MODIFY EQUIPMENT CONFIGURATION
IF NECESSARY
• CHECK VOLTAGE SUPPLY
• PERFORM AN AUTOMATED CONTROL TEST
Check Optional Pumpout System
Controls and Compressor ...................52
High Altitude Locations .....................53
Charge Refrigerant Into Chiller ...............53
• 19XL CHILLER EQUALIZATION WITHOUT
PUMPOUT UNIT
• 19XL CHILLER EQUALIZATION WITH
PUMPOUT UNIT
• TRIMMING REFRIGERANT CHARGE
INITIAL START-UP .........................55,56
Preparation .................................55
Manual Operation of the Guide Vanes ........55
Dry Run to Test Start-Up Sequence ..........55
Check Rotation .............................55
• IF ROTATION IS PROPER
• IF THE MOTOR ROTATION IS NOT
CLOCKWISE
• NOTES ON SOLID-STATE STARTERS
(Benshaw, Inc.)
Check Oil Pressure and Compressor Stop ....56
Calibrate Motor Current .....................56
To Prevent Accidental Start-Up ..............56
Check Chiller Operating Condition ...........56
Instruct the Customer Operator ..............56
• COOLER-CONDENSER
• OPTIONAL STORAGE TANK AND
PUMPOUT SYSTEM
• MOTOR COMPRESSOR ASSEMBLY
• MOTOR COMPRESSOR LUBRICATION SYSTEM
• CONTROL SYSTEM
• AUXILIARY EQUIPMENT
• DESCRIBE CHILLER CYCLES
• REVIEW MAINTENANCE
• SAFETY DEVICES AND PROCEDURES
• CHECK OPERATOR KNOWLEDGE
• REVIEW THE START-UP, OPERATION,
AND MAINTENANCE MANUAL
Page
OPERATING INSTRUCTIONS ...............56-58
Operator Duties .............................56
Prepare the Chiller for Start-Up ..............56
To Start the Chiller ..........................56
Check the Running System ..................56
To Stop the Chiller ..........................57
After Limited Shutdown .....................57
Extended Shutdown .........................57
After Extended Shutdown ...................57
Cold Weather Operation .....................57
Manual Guide Vane Operation ...............57
Refrigeration Log ...........................57
PUMPOUT AND REFRIGERANT
TRANSFER PROCEDURES ................59-61
Preparation .................................59
Operating the Optional Pumpout
Compressor ................................59
• TO READ REFRIGERANT PRESSURES
Chillers with Pumpout Storage Tanks ........59
• TRANSFER REFRIGERANT FROM
STORAGE TANK TO CHILLER
• TRANSFER THE REFRIGERANT FROM
CHILLER TO STORAGE TANK
Chillers with Isolation Valves ................60
• TRANSFER ALL REFRIGERANT TO
CHILLER CONDENSER VESSEL
• TRANSFER ALL REFRIGERANT TO CHILLER
COOLER/COMPRESSOR VESSEL
• RETURN REFRIGERANT TO NORMAL
OPERATING CONDITIONS
GENERAL MAINTENANCE .................61,62
Refrigerant Properties .......................61
Adding Refrigerant ..........................61
Removing Refrigerant .......................61
Adjusting the Refrigerant Charge ............61
Refrigerant Leak Testing ....................61
Leak Rate ..................................61
Test After Service, Repair, or Major Leak .....61
• REFRIGERANT TRACER
• TO PRESSURIZE WITH DRY NITROGEN
Repair the Leak, Retest, and Apply
Standing Vacuum Test ....................62
Checking Guide Vane Linkage ...............62
• CHECKING THE AUXILIARY SWITCH ON
GUIDE VANE ACTUATOR
Trim Refrigerant Charge .....................62
WEEKLY MAINTENANCE ....................62
Check the Lubrication System ...............62
SCHEDULED MAINTENANCE ..............63-65
Service Ontime .............................63
Inspect the Control Center ...................63
Check Safety and Operating Controls
Monthly ..................................63
Changing Oil Filter ..........................63
Oil Specification ............................63
Oil Changes ................................63
• TO CHANGE THE OIL
Refrigerant Filter ............................63
Oil Reclaim Filters ..........................63
Inspect Refrigerant Float System ............64
Inspect Relief Valves and Piping .............64
Compressor Bearing and Gear
Maintenance ...............................64
Inspect the Heat Exchanger Tubes ...........64
• COOLER
• CONDENSER
3
Page 4
CONTENTS (cont)
Page
Water Leaks ................................64
Water Treatment ............................65
Inspect the Starting Equipment ..............65
Check Pressure Transducers ................65
Optional Pumpout System Maintenance ......65
• OPTIONAL PUMPOUT COMPRESSOR OIL CHARGE
• OPTIONAL PUMPOUT SAFETY CONTROL SETTINGS
Ordering Replacement Chiller Parts ..........65
TROUBLESHOOTING GUIDE ...............66-97
Overview ...................................66
Checking the Display Messages .............66
Checking Temperature Sensors ..............66
• RESISTANCE CHECK
• VOLTAGE DROP
• CHECK SENSOR ACCURACY
• DUAL TEMPERATURE SENSORS
Checking Pressure Transducers .............66
• TRANSDUCER REPLACEMENT
Control Algorithms Checkout Procedure .....67
Control Test ................................67
Page
Control Modules ............................78
• RED LED
• GREEN LEDs
Notes on Module Operation ..................78
Processor Module (PSIO) ....................79
• INPUTS
• OUTPUTS
Starter Management Module (SMM) ..........79
• INPUTS
• OUTPUTS
Options Modules (8-Input) ...................79
Replacing Defective Processor Modules ......80
• INSTALLATION
Solid-State Starters .........................81
• TESTING SILICON CONTROL RECTIFIERS IN BENSHAW, INC. SOLID-STATE STARTERS
Physical Data ...............................85
INDEX ....................................98,99
INITIAL START-UP CHECKLIST FOR
19XL HERMETIC CENTRIFUGAL
LIQUID CHILLER ...................CL-1-CL-12
INTRODUCTION
Prior to initial start-up of the 19XL unit, those involved in the start-up, operation, and maintenance should be thor­oughly familiar with these instructions and other necessary job data. This book is outlined so that you may become familiar with the control system before performing start-up procedures. Procedures in this manual are arranged in the sequence required for proper chiller start-up and operation.
This unit uses a microprocessor control system. Do not short or jumper between terminations on circuit boards or modules; control or board failure may result.
Be aware of electrostatic discharge (static electricity) when handling or making contact with circuit boards or mod­ule connections. Always touch a chassis (grounded) part to dissipate body electrostatic charge before working inside control center.
Use extreme care when handling tools near boards and when connecting or disconnecting terminal plugs. Cir­cuit boards can easily be damaged. Always hold boards by the edges and avoid touching components and connections.
This equipment uses, and can radiate, radio frequency energy. If not installed and used in accordance with the instruction manual, it may cause interference to radio communications. It has been tested and found to comply with the limits for a Class A computing device pursuant to Subpart J of Part 15 of FCC (Federal Com­munication Commission) Rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user, at his own expense, will be required to take whatever measures may be re­quired to correct the interference.
Always store and transport replacement or defective boards in anti-static shipping bag.
ABBREVIATIONS AND EXPLANATIONS
Frequently used abbreviations in this manual include:
CCN — Carrier Comfort Network CCW — Counterclockwise CW — Clockwise ECW — Entering Chilled Water ECDW — Entering Condenser Water EMS — Energy Management System HGBP — Hot Gas Bypass I/O — Input/Output LCD — Liquid Crystal Display LCDW — Leaving Condenser Water LCW — Leaving Chilled Water LED — Light-Emitting Diode LID — Local Interface Device OLTA — Overload Trip Amps PIC — Product Integrated Control PSIO — Processor Sensor Input/Output Module RLA — Rated Load Amps SCR — Silicon Control Rectifier SI — International System of Units SMM — Starter Management Module TXV — Thermostatic Expansion Valve
The 19XL chillers use HCFC-22 and HFC-134a refrig­erant. When referencing refrigerant charges in this manual, the HCFC-22 charge will be listed first and the HFC-134a value will be shown next to it in brackets [ ].
Words printed in all capital letters and italics represent val­ues that may be viewed on the LID.
The PSIO software version number of your 19XL unit will be located on the front cover.
4
Page 5
CHILLER FAMILIARIZATION
(Fig. 1, 2A, and 2B)
Chiller Information Plate —
is located on the right side of the chiller control center panel.
Fig. 1 — 19XL Identification
The information plate
System Components — The components include the
cooler and condenser heat exchangers in separate vessels, motor-compressor, lubrication package, control center, and motor starter.All connections from pressure vessels have ex­ternal threads to enable each component to be pressure tested with a threaded pipe cap during factory assembly.
Cooler — This vessel (also known as the evaporator) is
located underneath the compressor. The cooler is main­tained at lower temperature/pressure so that evaporating refrigerant can remove heat from water flowing through its internal tubes.
Condenser — The condenser operates at a higher
temperature/pressure than the cooler, and has water flowing through its internal tubes in order to remove heat from the refrigerant.
Motor-Compressor— This component maintains sys-
tem temperature/pressure differences and moves the heat carrying refrigerant from the cooler to the condenser.
Control Center — The control center is the user inter-
face for controlling the chiller. It regulates the chiller’s capacity as required to maintain proper leaving chilled water temperature. The control center:
• registers cooler, condenser, and lubricating system pressures
• shows chiller operating condition and alarm shutdown conditions
• records the total chiller operating hours
• sequences chiller start, stop, and recycle under micro­processor control
• provides access to other CCN (Carrier Comfort Network) devices
Factory-Mounted Starter (Optional)— The starter
allows the proper start and disconnect of electrical energy for the compressor-motor, oil pump, oil heater, and control panels.
Storage Vessel (Optional) — There are 2 sizes
of storage vessels available. The vessels have double relief
valves, a magnetically coupled dial-type refrigerant level gage, a one-inch FPT drain valve, and a vapor connection for the pumpout unit. A 30-in.-0-400 psi (–101-0-2750 kPa) gage also is supplied with each unit.
NOTE: If a storage vessel is not used at the jobsite, factory­installed isolation valves on the chiller may be used to iso­late the chiller charge in either the cooler or condenser. An optional pumpout compressor system is used to transfer refrigerant from vessel to vessel.
1
⁄2-in. male flare
REFRIGERATION CYCLE
The compressor continuously draws refrigerant vapor from the cooler, at a rate set by the amount of guide vane opening. As the compressor suction reduces the pressure in the cooler, the remaining refrigerant boils at a fairly low temperature (typically 38 to 42 F [3 to 6 C]). The energy required for boiling is obtained from the water flowing through the cooler tubes. With heat energy removed, the water becomes cold enough for use in an air conditioning circuit or process liq­uid cooling.
After taking heat from the water, the refrigerant vapor is compressed. Compression adds still more heat energy and the refrigerant is quite warm (typically 98 to 102 F [37 to 40 C]) when it is discharged from the compressor into the condenser.
Relatively cool (typically 65 to 90 F [18 to 32 C]) water flowing into the condenser tubes removes heat from the refrigerant and the vapor condenses to liquid.
The liquid refrigerant passes through orifices into the FLASC (Flash Subcooler) chamber (Fig. 3). Since the FLASC chamber is at a lower pressure, part of the liquid refrigerant flashes to vapor, thereby cooling the remaining liquid. The FLASC vapor is recondensed on the tubes which are cooled by entering condenser water. The liquid drains into a float chamber between the FLASC chamber and cooler. Here a float valve forms a liquid seal to keep FLASC chamber vapor from entering the cooler. When liquid refrigerant passes through the valve, some of it flashes to vapor in the reduced pressure on the cooler side. In flashing, it removes heat from the remaining liquid. The refrigerant is now at a temperature and pressure at which the cycle began.
MOTOR/OIL REFRIGERATION
COOLING CYCLE
The motor and the lubricating oil are cooled by liquid refrigerant taken from the bottom of the condenser vessel (Fig. 3). Flow of refrigerant is maintained by the pressure differentialthat exists due to compressor operation.After the refrigerant flows past an isolation valve, an in-line filter, and a sight glass/moisture indicator, the flow is split between motor cooling and oil cooling systems.
Flow to the motor flows through an orifice and into the motor.There is also another orifice and a solenoid valve which will open if additional motor cooling is required. Once past the orifice, the refrigerant is directed over the motor by a spray nozzle. The refrigerant collects in the bottom of the motor casing and then is drained back into the cooler through the motor refrigerant drain line. A back pressure valve or an orifice in this line maintains a higher pressure in the motor shell than in the cooler/oil sump. The motor is protected by a temperature sensor imbedded in the stator windings. Higher motor temperatures (above 125 F [51 C]) energize a sole­noid to provide additional motor cooling. A further increase in temperature past the motor override set point will over­ride the temperature capacity control to hold, and if the motor temperature rises 10° F (5.5° C) above this set point, will close the inlet guide vanes. If the temperature rises above the safety limit, the compressor will shut down.
5
Page 6
19XL FRONT VIEW
LEGEND
1—Unit-Mounted Starter 2—Refrigerant Filter Drier 3—Rigging Guide Bolt 4—Refrigerant Moisture Indicator 5—Motor Sight Glass 6—Refrigerant Motor Drain 7—Oil Filter Access Cover 8—Refrigerant Oil Cooler
9—Oil Level Sight Glasses 10 — Guide Vane Actuator 11 — Typical Flange Connection 12 — Control Center 13 — ASME Nameplate, Cooler 14 — Take-Apart, Rabbet Fit Connector
(Lower)
15 — Refrigerant Charging Valve 16 — Cooler Refrigerant Isolation Valve 17 — Cooler Pressure Schrader Fittings 18 — Oil Drain/Charging Valve 19 — Power Panel 20 — Retro-Fit, Rig-in-Place Beams 21 — Typical Waterbox Drain Port 22 — Take-Apart, Shell Leveling Feet 23 — Cooler Return-End Waterbox Cover 24 — ASME Nameplate, Condenser 25 — Condenser Return-End Waterbox Cover 26 — Take-Apart, Rabbet Fit Connector
(Upper)
27 — Protective Truck Holddown Lugs 28 — Refrigerant Cooling Isolation Valve
(Hidden)
19XL REAR VIEW
Fig. 2A — Typical 19XL Components — Design I
LEGEND
29 — Pumpdown System Connection 30 — Cooler Relief Valves 31 — Chiller Identification Nameplate 32 — Cooler Pressure Transducer 33 — Suction Elbow 34 — Transmission Vent Line 35 — Discharge Pressure Switch and
Discharge Pressure Transducer
36 — Condenser Isolation Valve 37 — Low-Voltage Access Door, Starter 38 — Medium-Voltage Access Door, Starter 39 — Amp/Volt Gages 40 — Refrigerant Supply Sump 41 — Condenser Pressure Transducer 42 — Liquid Seal Float Chamber 43 — ASME Nameplate, Float Chamber 44 — Condenser Relief Valves 45 — Condenser In/Out Temperature Sensors 46 — Cooler In/Out Temperature Sensors
6
Page 7
LEGEND
56789
4
24 23
22
21
11
10
12
13
14
151617181920
19XL FRONT VIEW
1—Unit-Mounted Starter 2—Refrigerant Filter Drier 3—Rigging Guide Bolt 4—Motor Sight Glass 5—Refrigerant Moisture Indicator 6—Refrigerant Oil Cooler 7—Oil Filter Access Cover 8—Oil Level Sight Glasses
9—Guide VaneActuator 10 — Typical Flange Connection 11 — Control Center 12 — Cooler Pressure Schrader Fitting
(Hidden)
13 — ASME Nameplate, Cooler 14 — Cooler 15 — Take-Apart Rabbet Fit Connector
(Lower)
16 — Refrigerant Charging Valve 17 — Oil Drain/Charging Valve 18 — Power Panel 19 — Cooler Waterbox Cover 20 — Cooler In/Out Temperature Sensors 21 — Condenser In/Out Temperature Sensors 22 — Condenser Waterbox Cover 23 — Take-Apart Rabbet Fit Connector
(Upper)
24 — Refrigerant Cooling Isolation Valve
(Hidden)
2928272625
42
41
40 39
38
36 35 34 333215
37
30
25 — Cooler Relief Valve
31
26 — Chiller Identification Plate 27 — Suction Elbow 28 — Transmission Vent Line 29 — Condenser Relief Valves 30 — Low Voltage Access Door, Starter 31 — Medium Voltage Access Door, Starter 32 — Amp/Volt Gages 33 — Condenser Isolation Valve 34 — Linear Float Valve Chamber 35 — Condenser Pressure Transducer 36 — Discharge Pressure Switch and
Discharge Pressure Transducer
37 — Cooler Refrigerant Isolation Valve 38 — Condenser Return End Waterbox Cover 39 — Typical Waterbox Drain Port 40 — Cooler Return End Waterbox Cover 41 — Cooler Pressure Transducer 42 — Pumpdown Valve
LEGEND
19XL REAR VIEW
Fig. 2B — Typical 19XL Components — Design II
7
Page 8
Fig. 3 — Refrigerant Motor Cooling and Oil Cooling Cycles
Refrigerant that flows to the oil cooling system is reg­ulated by a thermostatic expansion valve. There is always a minimum flow bypassing the TXV, which flows through an orifice. The TXV valve regulates flow into the oil/ refrigerant plate and frame-type heat exchanger. The bulb for the expansion valve controls oil temperature to the bear­ings. The refrigerant leaving the heat exchanger then returns to the cooler.
LUBRICATION CYCLE
Summary—
up a package located partially in the transmission casting of the compressor-motor assembly. The oil is pumped into a filter assembly to remove foreign particles, and is then forced into an oil cooler heat exchanger where the oil is cooled to proper operational temperatures. After the oil cooler, part of the flow is directed to the gears and the high speed shaft bearings; the remaining flow is directed to the motor shaft bearings. Oil drains into the transmission oil sump to com­plete the cycle (Fig. 4).
The oil pump, oil filter, and oil cooler make
Details— Oil is charged into the lubrication system through
a hand valve. Two sight glasses in the oil reservoir permit oil level observation. Normal oil level is between the middle of the upper sight glass and the top of the lower sight glass
when the compressor is shut down. The oil level should be visible in at least one of the 2 sight glasses during operation. Oil sump temperature is displayed on the LID default screen. Oil sump temperature ranges during compressor operation between 100 to 120 F (37 to 49 C) [120 to 140 F (49 to 60 C)].
The oil pump suction is fed from the oil reservoir. An oil pressure relief valve maintains 18 to 25 psid (124 to 172 kPad) differential pressure in the system at the pump discharge.This dif ferentialpressure can be read directly from the Local Interface Device (LID) default screen. The oil pump discharges oil to the oil filter assembly. This filter can be valved closed to permit removal of the filter without drain­ing the entire oil system (see Maintenance sections, pages 61 to 65, for details). The oil is then piped to the oil cooler. This heat exchanger uses refrigerant from the condenser as the coolant. The refrigerant cools the oil to a temperature between 100 and 120 F (37 to 49 C).
As the oil leaves the oil cooler, it passes the oil pressure transducer and the thermal bulb for the refrigerant expan­sion valve on the oil cooler. The oil is then divided, with a portion flowing to the thrust bearing, forward pinion bear­ing, and gear spray. The balance then lubricates the motor shaft bearings and the rear pinion bearing. The oil temper­ature is measured as the oil leaves the thrust and forward
8
Page 9
Fig. 4 — Lubrication System
journal bearings within the bearing housing. The oil then drains into the oil reservoir at the base of the compressor. The PIC (Product Integrated Control) measures the temperature of the oil in the sump and maintains the temperature during shut­down (see Oil Sump Temperature Control section, page 32). This temperature is read on the LID default screen.
During the chiller start-up, the PIC will energize the oil pump and provide 15 seconds of prelubrication to the bear­ings after pressure is verified before starting the compressor. During shutdown, the oil pump will run for 60 seconds to post-lubricate after the compressor shuts down. The oil pump can also be energized for testing purposes in the Control Test.
Ramp loading can slow the rate of guide vane opening to minimize oil foaming at start-up. If the guide vanes open quickly, the sudden drop in suction pressure can cause any refrigerant in the oil to flash. The resulting oil foam cannot be pumped efficiently; therefore, oil pressure falls off and lubrication is poor. If oil pressure falls below 15 psid (103 kPad) differential, the PIC will shut down the compressor.
Oil Reclaim System — The oil reclaim system oper-
ates to return oil back to the oil reservoir by recovering it from 2 areas on the chiller. The primary area of recovery is from the guide vane housing. Oil also is recovered, along with refrigerant, from the cooler.
Any refrigerant that enters the oil reservoir/transmission area is flashed into gas. The demister line at the top of the
casing will vent this refrigerant into the suction of the com­pressor. Oil entrained in the refrigerant is eliminated by the demister filter.
DURING NORMAL CHILLER OPERATION, oil is entrained with the refrigerant. As the compressor pulls the refrigerant into the guide vane housing to be com­pressed, the oil will normally drop out at this point and fall to the bottom of the housing where it accumulates. Us­ing discharge gas pressure to power an eductor, the oil is vacuumed from the housing by the eductor and is dis­charged into the oil reservoir. Oil and refrigerant are also recovered from the top of the cooler refrigerant level and are discharged into the guide vane housing. The oil will drop to the bottom of the guide vane housing and be recovered by the eductor system.
DURING LIGHT LOAD CONDITIONS, the suction gas into the compressor does not have enough velocity to return oil, which is floating in the cooler back to the compressor. In addition, the eductor may not have enough power to pull the oil from the guide vane housing back into the oil reservoir due to extremely low pressure at the guide vanes. Two so­lenoids, located on the oil reclaim piping, are operated so that the eductor can pull oil and refrigerant directly from the cooler and discharge the mixture into the oil reservoir. The oil reclaim solenoids are operated by an auxiliary contact integral to the guide vane actuator. This switchover of the solenoids occurs when the guide vanes are opened beyond 30 degrees from the closed position.
9
Page 10
STARTING EQUIPMENT
The 19XL requires a motor starter to operate the centrif­ugal hermetic compressor motor, the oil pump, and various auxiliary equipment. The starter serves as the main field wiring interface for the contractor.
Three types of starters are available from Carrier Cor­poration: solid-state, wye-delta, and across-the-line starters. See Carrier Specification Z-375 for specific starter require­ments. All starters must meet these specifications in order to properly start and satisfy mechanical safety requirements. Starters may be supplied as separate, free-standing units, or may be mounted directly on the chiller (unit mounted) for low-voltage units only.
Inside the starter are 3 separate circuit breakers. Circuit breaker CB1 is the compressor motor circuit breaker. The disconnect switch on the starter front cover is connected to this breaker. Circuit breaker CB1 supplies power to the com­pressor motor.
The main circuit breaker (CB1) on the front of the starter disconnects the main motor current only. Power is still energized for the other circuits. Two more circuit break­ers inside the starter must be turned off to disconnect power to the oil pump, PIC controls, and oil heater.
Circuit breaker CB2 supplies power to the control center, oil heater, and portions of the starter controls. Circuit breaker CB3 supplies power to oil pump. Both of these circuit break­ers are wired in parallel with CB1 so that power is supplied to them if the CB1 disconnect is open.
All starters are shipped with a Carrier control module called the Starter Management Module (SMM). This module controls and monitors all aspects of the starter. See the Con­trols section on page 11 for additional SMM information. All starter replacement parts are supplied by the starter manufacturer.
LEGEND
1—Field Wiring Terminal Strips (TB2 and TB3) 2—Circuit Breaker 1, 2, 3, 4 3—Overload Unit 4—Solid-State Controller 5—Silicon Controlled Rectifier (SCR) LED (One of 6) 6—Starter Fault and Run LEDs 7—Voltmeter (Optional) 8—Ammeter (Optional)
9—SCR (One of 6) 10 — Voltage LED 11 — Starter Management Module (SMM) 12 — Pilot Relays (PR1 to PR5) 13 — Starter Access Door
Fig. 5 — Benshaw, Inc. Solid-State Starter,
Internal View
Unit-Mounted Solid-State Starter (Optional)
The 19XL may be equipped with a solid-state, reduced-
voltage starter (Fig. 5 and 6). This starter provides on-off control of the compressor motor as its primary function. Using this type of starter reduces the peak starting torque, reduces the motor inrush current, and decreases mechanical shock. This is summed up by the phrase ‘‘soft starting.’’
Two varieties of solid-state starters are available as a 19XL option (factory supplied and installed). When a unit-mounted, optional, solid-state starter is purchased with the 19XL, a Benshaw,Inc. solid-state starter will be shipped with the unit. See Fig. 5. The solid-state starter’s manufacturer name will be located inside the starter access door. See Fig. 6.
These starters operate by reducing the starting voltage. The starting torque of a motor at full voltage is typically 125% to 175% of the running torque. When the voltage and the current are reduced at start-up, the starting torque is reduced as well. The object is to reduce the starting voltage to just the voltage necessary to develop the torque required to get the motor moving. The voltage and current are then ramped up in a desired period of time. The voltage is reduced through the use of silicon controlled rectifiers (SCR). Once full volt­age is reached, a bypass contactor is energized to bypass the SCRs.
When voltage is supplied to the solid-state circuitry, the heat sinks within the starter are at line voltage. Do not touch the heat sinks while voltage is present or serious injury will result.
Fig.6—Typical Starter External View
(Solid-State Starter Shown)
There are a number of LEDs (light-emitting diodes) that are useful in troubleshooting and starter check-out on Benshaw, Inc. solid-state starters. These are used to indicate:
• voltage to the SCRs
• SCR control voltage
• power indication
• proper phasing for rotation
• start circuit energized
10
Page 11
• overtemperature
• ground fault
• current unbalance
• run state These LEDs are further explained in the Check Starter and
Troubleshooting Guide section, page 66.
Unit-MountedWye-DeltaStarter (Optional) — The
19XLchiller may be equipped with a wye-delta starter mounted on the unit (Fig. 7). This starter is intended for use with low­voltage motors (under 600 v). It reduces the starting current inrush by connecting each phase of the motor windings into a wye configuration. This occurs during the starting period when the motor is accelerating up to speed. After a time de­lay, once the motor is up to speed, the starter automatically connects the phase windings into a delta configuration.
123456 7
17
16
15
1011121314
1—Pilot Relays 2—SMM Power Circuit Breaker and Voltage Calibration
Potentiometer
3—Transistor Resistor Fault Protector (TRFP) 4—Transformer (T2) 5—Control Power Circuit Breaker 6—Oil Pump Circuit Breaker 7—Main Circuit Breaker Disconnect 8—Voltmeter (Optional)
9—Ammeter (Optional) 10 — Current Transformers (T1, T2, T3) 11 — Phase Monitor Relay (Optional) 12 — Overload Unit 13 — Starter Management Module 14 — Starter Access Door 15 — Control Transformer Secondary Circuit Breaker 16 — Signal Resistor 17 — Field Wiring Terminal Strip (TB6)
LEGEND
Fig.7—Wye-Delta Starter, Internal View
Definitions
CONTROLS
ANALOG SIGNAL — An analog signal varies in propor­tion to the monitored source. It quantifies values between operating limits. (Example: A temperature sensor is an ana­log device because its resistance changes in proportion to the temperature, generating many values.)
DIGIT ALSIGNAL—A digital (discrete) signal is a 2-position representation of the value of a monitored source. (Ex­ample: A switch is a digital device because it only indicates whether a value is above or below a set point or boundary by generating an on/off, high/low, or open/closed signal.)
VOLATILE MEMORY — Volatile memory is memory in- capable of being sustained if power is lost and subsequently restored.
9
The memory of the PSIO and LID modules are volatile. If the battery in a module is removed or damaged, all programming will be lost.
General — The 19XL hermetic centrifugal liquid chiller
contains a microprocessor-based control center that moni­tors and controls all operations of the chiller. The micro­processor control system matches the cooling capacity of the chiller to the cooling load while providing state-of-the-art chiller protection. The system controls cooling load within the set point plus the deadband by sensing the leaving chilled water or brine temperature, and regulating the inlet guide vane via a mechanically linked actuator motor. The guide vane is a variable flow prewhirl assembly that controls the refrigeration effect in the cooler by regulating the amount of refrigerant vapor flow into the compressor. An increase in guide vane opening increases capacity. A decrease in guide vane opening decreases capacity. Chiller protection is pro­vided by the processor which monitors the digital and ana­log inputs and executes capacity overrides or safety shutdowns, if required.
PIC System Components — The Product Integrated
Control (PIC) is the control system on the chiller. See
8
T able1. The PIC controls the operation of the chiller by moni­toring all operating conditions. The PIC can diagnose a prob­lem and let the operator know what the problem is and what to check. It promptly positions the guide vanes to maintain leaving chilled water temperature. It can interface with aux­iliary equipment such as pumps and cooling tower fans to turn them on only when required. It continually checks all safeties to prevent any unsafe operating condition. It also regulates the oil heater while the compressor is off, and the hot gas bypass valve, if installed.
The PIC can be interfaced with the Carrier Comfort Net­work (CCN) if desired. It can communicate with other PIC­equipped chillers and other CCN devices.
The PIC consists of 3 modules housed inside the 3 major components. The component names and the control voltage contained in each component are listed below (also see Table 1):
• control center — all extra low-voltage wiring (24 v or less)
• power panel — 230 or 115 v control voltage (per job
requirement)
— up to 600 v for oil pump power
• starter cabinet — chiller power wiring (per job
requirement)
Table 1 — Major PIC Components and
Panel Locations*
PIC COMPONENT
Processor Sensor Input/Output Module
(PSIO)
Starter Management Module (SMM) Starter Cabinet Local Interface Device (LID) Control Center 6-Pack Relay Board Control Center 8-Input Modules (Optional) Control Center Oil Heater Contactor (1C) Power Panel Oil Pump Contactor (2C) Power Panel Hot Gas Bypass Relay (3C) (Optional) Power Panel Control Transformers (T1-T4) Power Panel Control and Oil Heater Voltage Selector (S1) Power Panel Temperature Sensors See Fig. 8 Pressure Transducers See Fig. 8
*See Fig. 5, 6, and Fig. 8-12.
PANEL
LOCATION
Control Center
11
Page 12
Fig. 8 — 19XL Controls and Sensor Locations
Fig. 9 — Control Sensors
(Temperature)
Fig. 10 — Control Sensors
(Pressure Transducer, Typical)
12
LEGEND
1—LID 2—PSIO 3—8-Input Module (One of 2 Available) 4—5-Volt Transducer Power Supply 5—6-Pack Relay Board 6—Circuit Breakers (4)
Fig. 11 — Control Center (Front View),
with Options Module
Page 13
PROCESSOR MODULE (PSIO) — The PSIO is the brain of the PIC (Fig. 11). This module contains all the operating software needed to control the chiller.The 19XLuses 3 pres­sure transducers and 8 thermistors to sense pressures and tem­peratures. These are connected to the PSIO module. The PSIO also provides outputs to the guide vane actuator, oil pump, oil heater, hot gas bypass (optional), motor cooling solenoid, and alarm contact. The PSIO communicates with the LID, the SMM, and the optional 8-input modules for user inter­face and starter management.
ST ARTER MANAGEMENT MODULE (SMM) — This mod­ule is located within the starter cabinet. This module ini­tiates PSIO commands for starter functions such as start/ stop of the compressor, start/stop of the condenser and chilled water pumps, start/stop of the tower fan, spare alarm con­tacts, and the shunt trip. The SMM monitors starter inputs such as flow switches, line voltage, remote start contact, spare safety, condenser high pressure, oil pump interlock, motor current signal, starter 1M and run contacts, and kW trans­ducer input (optional). The SMM contains logic capable of safely shutting down the machine if communications with the PSIO are lost.
LOCALINTERFACEDEVICE (LID) — The LID is mounted to the control center and allows the operator to interface with the PSIO or other CCN devices (Fig. 11). It is the input cen­ter for all local chiller set points, schedules, set-up func­tions, and options. The LID has a STOP button, an alarm light, 4 buttons for logic inputs, and a display. The function of the 4 buttons or ‘‘softkeys’’are menu driven and are shown on the display directly above the key.
6-PACK RELAY BOARD — This device is a cluster of 6 pilot relays located in the control center (Fig. 11). It is energized by the PSIO for the oil pump, oil heater, alarm, optional hot gas bypass relay, and motor cooling solenoid.
8-INPUT MODULES — One optional module is factory in­stalled in the control center panel when ordered (Fig. 11). There can be up to 2 of these modules per chiller with 8 spare inputs each. They are used whenever chilled water reset, demand reset, or reading a spare sensor is required. The sensors or 4 to 20 mA signals are field-installed.
The spare temperature sensors must have the same temperature/resistance curve as the other temperature sen­sors on this unit. These sensors are 5,000 ohm at 75 F (25 C).
OIL HEATER CONTACTOR (1C) — This contactor is lo­cated in the power panel (Fig. 12) and operates the heater at either 115 or 230 v. It is controlled by the PIC to maintain oil temperature during chiller shutdown.
OIL PUMP CONTACTOR (2C) — This contactor is located in the power panel (Fig. 12). It operates all 200 to 575-v oil pumps. The PIC energizes the contactor to turn on the oil pump as necessary.
HOT GAS BYPASS CONTACTOR RELAY (3C) (Op­tional) — This relay, located in the power panel, (Item 5, Fig. 12) controls the opening of the hot gas bypass valve. The PIC energizes the relay during low load, high lift conditions.
CONTROL TRANSFORMERS (T1-T4) — These trans­formers convert incoming control voltage to either 21 vac power for the PSIO module and options modules, or 24 vac power for 3 power panel contactor relays, 3 control solenoid valves, and the guide vane actuator. They are located in the power panel. See Fig. 12.
CONTROLANDOIL HEATERVOLTAGE SELECTOR (S1) — It is possible to use either 115 v or 230 v incoming con­trol power in the power panel. The switch is set to the volt­age used at the jobsite.
LEGEND
1—T2 — 24 vac Power Transformer for Hot Gas Bypass Relay,
Oil Pump Relay, Oil Heater Relay, Motor Cooling Solenoid, Oil Reclaim Solenoid
2—Oil Pressure Switch 3—T4 — 24 vac, Optional 8-Input Module Transformer
Fig. 12 — Power Panel with Options
13
4—T1 — 24 vac, Control Center Transformer 5—3C Hot Gas Bypass Relay Location 6—Oil Pump Terminal Block 7—Factory Terminal Connections 8—T3 — 24 vac Guide Vane Actuator Transformer
Page 14
LID Operation and Menus (Fig. 13-19)
GENERAL
• The LID display will automatically revert to the default screen after 15 minutes if no softkey activity takes place and if the chiller is not in the Pumpdown mode (Fig. 13).
• When not in the default screen, the upper right-hand cor­ner of the LID always displays the name of the screen that you have entered (Fig. 14).
• The LID may be configured in English or SI units, through the LID configuration screen.
• Local Operation — By pressing the LOCAL PIC is now in the LOCAL operation mode. The control
will accept changes to set points and configurations from the LID only. The PIC will use the Local Time Schedule to determine chiller start and stop times.
• CCN Operation — By pressing the CCN is now in the CCN operation mode, and the control will
accept modifications from any CCN interface or module (with the proper authority), as well as the LID. The PIC will use the CCN time schedule to determine start and stop times.
softkey,the
softkey,the PIC
ALARMS AND ALERTS — Alarm (*) and alert (!) status are indicated on the Status tables.An alarm (*) will shut down the compressor.An alert (!) notifies the operator that an un­usual condition has occurred. The chiller will continue to operate when an alert is shown.
Alarms are indicated when the control center alarm light (!) flashes. The primary alarm message is viewed on the de­fault screen and an additional, secondary, message and troubleshooting information are sent to the Alarm History table.
When an alarm is detected, the LID default screen will freeze (stop updating) at the time of alarm. The freeze en­ables the operator to view the chiller conditions at the time of alarm. The Status tables will show the updated informa­tion. Once all alarms have been cleared (by pressing the
RESET softkey), the default LID screen will return to nor-
mal operation. MENU STRUCTURE — To perform any of the operations
described below, the PIC must be powered up and have suc­cessfully completed its self test. The self test takes place automatically, after power-up.
• Press QUIT
out saving any changes.
to leave the selected decision or field with-
Fig. 13 — LID Default Screen
• Press ENTER to leave the selected decision or field and
save changes.
• Press NEXT to scroll the cursor bar down in order to
highlight a point or to view more points below the current screen.
• Press PREVIOUS to scroll the cursor bar up in order to
highlight a point or to view points above the current screen.
• Press SELECT to view the next screen level (high-
lighted with the cursor bar), or to override (if allowable) the highlighted point value.
Fig. 14 — LID Service Screen
14
Page 15
• Press EXIT to return to the previous screen level.
• Press INCREASE or DECREASE to change the high­lighted point value.
TO VIEW POINT STATUS (Fig. 15) — Point Status is the actual value of all of the temperatures, pressures, relays, and actuators sensed and controlled by the PIC.
1. On the Menu screen, press STATUS
to view the list of
Point Status tables.
4. On the Point Status table press NEXT or PREVIOUS
until desired point is displayed on the screen.
OVERRIDE OPERATIONS To Override a Value or Status
1. On the Point Status table press NEXT or PREVIOUS
to highlight the desired point.
2. Press SELECT to select the highlighted point. Then:
2. Press NEXT or PREVIOUS to highlight the desired status table. The list of tables is:
• Status01 — Status of control points and sensors
• Status02 — Status of relays and contacts
• Status03 — Status of both optional 8-input modules and
sensors
3. Press SELECT to view the Point Status table desired.
For Discrete Points — Press START or STOP to se­lect the desired state.
For Analog Points Press INCREASE or
DECREASE
to select the desired value.
3. Press ENTER to register new value.
NOTE: When overriding or changing metric values, it is necessary to hold the softkey down for a few seconds in or­der to see a value change, especially on kilopascal values.
To Remove an Override
1. On the Point Status table press NEXT or PREVIOUS
to highlight the desired point.
Fig. 15 − Example of Point Status Screen
(Status01)
2. Press SELECT to access the highlighted point.
15
Page 16
3. Press RELEASE to remove the override and return the point to the PIC’s automatic control.
4. Press NEXT or PREVIOUS to highlight the de­sired period or override that you wish to change.
Override Indication— An override value is indicated by ‘ ‘SUPVSR,’’‘‘SERVC,’’or‘‘BEST’’flashing next to the point
value on the Status table. TIME SCHEDULE OPERATION (Fig. 16)
1. On the Menu screen, press SCHEDULE
.
2. Press NEXT or PREVIOUS to highlight the de­sired schedule.
PSIO Software Version 08 and lower:
OCCPC01S — LOCAL Time Schedule OCCPC02S — CCN Time Schedule
PSIO Software Version 09 and higher:
OCCPC01S — LOCAL Time Schedule OCCPC02S — ICE BUILD Time Schedule OCCPC03-99S — CCN Time Schedule (Actual
number is defined in Config table.)
5. Press SELECT to access the highlighted period or override.
a. Press INCREASE
6.
or DECREASE to change the
time values. Override values are in one-hour incre­ments, up to 4 hours.
b. Press ENABLE to select days in the day-of-week
fields. Press DISABLE
to eliminate days from the
period.
7. Press ENTER to register the values and to move horizontally (left to right) within a period.
3. Press SELECT to access and view the time schedule.
Fig. 16 — Example of Time Schedule
Operation Screen
8. Press EXIT to leave the period or override.
9. Either return to Step 4 to select another period or override, or press EXIT
again to leave the current time
schedule screen and save the changes.
10. Holiday Designation (HOLIDEF table) may be found in the Service Operation section, page 38. You must assign the month, day, and duration for the holiday.The Broad­cast function in the Brodefs table also must be enabled for holiday periods to function.
16
Page 17
*Only available on PSIO Software Version 09 and higher.
†Available on PSIO Software Versions 07 and 08.
Fig. 17 — 19XL Menu Structure
17
Page 18
18
Fig. 18 — 19XL Service Menu Structure
Page 19
19
Fig. 18 — 19XL Service Menu Structure (cont)
*Only available on PSIO Software Version 09 and higher.
†Available on PSIO Software Versions 07 and 08.
Page 20
TO VIEW AND CHANGE SET POINTS (Fig. 19)
1. To view the Set Point table, at the Menu screen press SETPOINT
2. There are 4 set points on this screen: Base Demand Limit;
LCW Set Point (leaving chilled water set point); ECW Set Point (entering chilled water set point); and ICE BUILD set point (PSIO Software Version 09 and higher only). Only one of the chilled water set points can be active at one time, and the type of set point is activated in the Serv­ice menu. ICE BUILD is also activated and configured in the Service menu.
.
3. Press NEXT set point entry.
4. Press SELECT to modify the highlighted set point.
5. Press INCREASE or DECREASE to change the se­lected set point value.
6. Press ENTER to save the changes and return to the previous screen.
or PREVIOUS to highlight the desired
Fig. 19 — Example of Set Point Screen
SERVICE OPERATION — To view the menu-driven pro­grams available for Service Operation, see Service Opera­tion section, page 38. For examples of LID display screens, see Table 2.
20
Page 21
Table 2 — LID Screens
NOTES:
1. Only 12 lines of information appear on the LID screen at any given time. Press NEXT or PREVIOUS to highlight a point or to view points below or above the current screen.
2. The LID may be configured in English or SI units, as required, through the LID configuration screen.
3. Data appearing in the Reference Point Names column is used for CCN operations only.
4. All options associated with ICE BUILD, Lead/Lag, CCN Occupancy Configuration, and Soft Stopping are only available on PSIO Software Version 9 and higher.
EXAMPLE1—STATUS01 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
2. Press STATUS (STATUS01 will be highlighted).
3. Press SELECT
.
.
DESCRIPTION RANGE UNITS
Control Mode Reset, Off, Local, CCN MODE Run Status Occupied ? No/Yes OCC
Alarm State Normal/Alarm ALM *Chiller Start/Stop Stop/Start CHIL S S Base Demand Limit 40-100 % DLM *Active Demand Limit 40-100 % DEM LIM Compressor Motor Load 0-999 % CA L
Current 0-999 % CA P
Amps 0-999 AMPS CA A *Target Guide Vane Pos 0-100 % GV TRG Actual Guide Vane Pos 0-100 % GV ACT Water/Brine: Setpoint 10-120 (–12.2-48.9) DEG F (DEG C) SP * Control Point 10-120 (–12.2-48.9) DEG F (DEG C) LCW STPT Entering Chilled Water –40-245 (–40-118) DEG F (DEG C) ECW Leaving Chilled Water –40-245 (–40-118) DEG F (DEG C) LCW Entering Condenser Water –40-245 (–40-118) DEG F (DEG C) ECDW Leaving Condenser Water –40-245 (–40-118) DEG F (DEG C) LCDW Evaporator Refrig Temp –40-245 (–40-118) DEG F (DEG C) ERT Evaporator Pressure –6.7-420 (–46-2896) PSI (kPa) ERP Condenser Refrig Temp –40-245 (–40-118) DEG F (DEG C) CRT Condenser Pressure –6.7-420 (–46-2896) PSI (kPa) CRP Discharge Temperature –40-245 (–40-118) DEG F (DEG C) CMPD Bearing Temperature –40-245 (–40-118) DEG F (DEG C) MTRB Motor Winding Temp –40-245 (–40-118) DEG F (DEG C) MTRW Oil Sump Temperature –40-245 (–40-118) DEG F (DEG C) OILT Oil Pressure Transducer –6.7-420 (–46-2896) PSI (kPa) OILP Oil Pressure –6.7-420 (–46-2896) PSID (kPad) OILPD Line Voltage: Percent 0-999 % V P
*Remote Contacts Input Off/On REMCON Total Compressor Starts 0-65535 c starts Starts in 12 Hours 0-8 STARTS Compressor Ontime 0-500000.0 HOURS c hrs *Service Ontime 0-32767 HOURS S HRS *Compressor Motor kW 0-9999 kW CKW
NOTE: All values are variables available for read operation to a CCN. Descriptions shown with (*) support write operations for BEST programming language, data transfer, and overriding.
Actual 0-9999 VOLTS V A
Timeout, Recycle, Startup,
Ramping, Running, Demand, Override, Shutdown, Abnormal, Pumpdown
REFERENCE POINT NAME
(ALARM HISTORY)
STATUS
21
Page 22
EXAMPLE2—STATUS02 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
2. Press STATUS
3. Scroll down to highlight STATUS02.
4. Press SELECT
.
.
.
Table 2 — LID Screens (cont)
DESCRIPTION
Hot Gas Bypass Relay X OFF/ON HGBR *Chilled Water Pump X OFF/ON CHWP Chilled Water Flow X NO/YES EVFL *Condenser Water Pump X OFF/ON CDP Condenser Water Flow X NO/YES CDFL Compressor Start Relay X OFF/ON CMPR Compressor Start Contact X OPEN/CLOSED 1CR AUX Compressor Run Contact X OPEN/CLOSED RUN AUX Starter Fault Contact X OPEN/CLOSED STR FLT Pressure Trip Contact X OPEN/CLOSED PRS TRIP Single Cycle Dropout X NORMAL/ALARM V1 CYCLE Oil Pump Relay X OFF/ON OILR Oil Heater Relay X OFF/ON OILH Motor Cooling Relay X OFF/ON MTRC *Tower Fan Relay X OFF/ON TFR Compr. Shunt Trip Relay X OFF/ON TRIPR Alarm Relay X NORMAL/ALARM ALM Spare Prot Limit Input X ALARM/NORMAL SPR PL
NOTE: All values are variables available for read operation to a CCN. Descriptions shown with (*) support write operations from the LID only.
To access this display from the LID default screen:
1. Press MENU
2. Press STATUS
3. Scroll down to highlight STATUS03.
4. Press SELECT
OPTIONS BOARD 1 *Demand Limit 4-20 mA 4-20 mA DEM OPT
*Temp Reset 4-20 mA 4-20 mA RES OPT *Common CHWS Sensor –40-245 (–40-118) DEG F (DEG C) CHWS *Common CHWR Sensor –40-245 (–40-118) DEG F (DEG C) CHWR *Remote Reset Sensor –40-245 (–40-118) DEG F (DEG C) R RESET *Temp Sensor — Spare 1 –40-245 (–40-118) DEG F (DEG C) SPARE1 *Temp Sensor — Spare 2 –40-245 (–40-118) DEG F (DEG C) SPARE2 *Temp Sensor — Spare 3 –40-245 (–40-118) DEG F (DEG C) SPARE3
OPTIONS BOARD 2 *4-20 mA — Spare 1 4-20 mA SPARE1 M
*4-20 mA — Spare 2 4-20 mA SPARE2 M *Temp Sensor — Spare 4 –40-245 (–40-118) DEG F (DEG C) SPARE4 *Temp Sensor — Spare 5 –40-245 (–40-118) DEG F (DEG C) SPARE5 *Temp Sensor — Spare 6 –40-245 (–40-118) DEG F (DEG C) SPARE6 *Temp Sensor — Spare 7 –40-245 (–40-118) DEG F (DEG C) SPARE7 *Temp Sensor — Spare 8 –40-245 (–40-118) DEG F (DEG C) SPARE8 *Temp Sensor — Spare 9 –40-245 (–40-118) DEG F (DEG C) SPARE9
NOTE: All values shall be variables available for read operation to a CCN network. Descriptions shown with (*) support write operations for BEST programming language, data transfer, and overriding.
.
.
.
DESCRIPTION RANGE UNITS
POINT TYPE
INPUT OUTPUT
EXAMPLE3—STATUS03 DISPLAY SCREEN
UNITS
REFERENCE POINT NAME
(ALARM HISTORY)
REFERENCE POINT NAME
(ALARM HISTORY)
EXAMPLE 4 — SETPOINT DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
2. Press SETPOINT
DESCRIPTION CONFIGURABLE RANGE UNITS REFERENCE POINT NAME DEFAULT VALUE
Base Demand Limit 40-100 % DLM 100 LCW Setpoint 20-120 (–6.7-48.9) DEG F (DEG C) lcw sp ECW Setpoint 20-120 (–6.7-48.9) DEG F (DEG C) ecw sp ICE BUILD Setpoint 20- 60 (–6.7-15.6) DEG F (DEG C) ice sp 40.0 ( 4.4)
.
.
50.0 (10.0)
60.0 (15.6)
22
Page 23
Table 2 — LID Screens (cont)
EXAMPLE 5 — CONFIGURATION (CONFIG) DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
2. Press SERVICE
3. Scroll down to highlight EQUIPMENT CONFIGURATION.
4. Press SELECT
5. Scroll down to highlight CONFIG.
6. Press SELECT
DESCRIPTION CONFIGURABLE RANGE UNITS REFERENCE POINT NAME DEFAULT VALUE
RESET TYPE 1 Degrees Reset at 20 mA –30-30 (–17-17) DEG F (DEG C) deg 20ma
RESET TYPE 2 Remote Temp (No Reset) –40-245 (–40-118) DEG F (DEG C) res rt1 Remote Temp (Full Reset) –40-245 (–40-118) DEG F (DEG C) res rt2 65 (18) Degrees Reset –30-30 (–17-17) DEG F (DEG C) res rt 10D(6D)
RESET TYPE 3 CHW Delta T (No Reset) 0-15 (0-8) DEG F (DEG C) restd 1 CHW Delta T (Full Reset) 0-15 (0-8) DEG F (DEG C) restd 2 0D(0D) Degrees Reset –30-30 (–17-17) DEG F (DEG C) deg chw 5D(3D)
Select/Enable Reset Type 0-3 res sel ECW CONTROL OPTION DISABLE/ENABLE ecw opt
Demand Limit At 20 mA 40-100 % dem 20ma 40 20 mA Demand Limit Option DISABLE/ENABLE dem sel DISABLE
Auto Restart Option DISABLE/ENABLE astart DISABLE Remote Contacts Option DISABLE/ENABLE r contact Temp Pulldown Deg/Min 2-10 tmp ramp
Load Pulldown %/Min 5-20 kw ramp 10 Select Ramp Type: 0/1 ramp opt 1
Temp=0,Load=1
Loadshed Group Number 0-99 ldsgrp 0 Loadshed Demand Delta 0-60 % ldsdelta 20 Maximum Loadshed Time 0-120 MIN maxldstm 60
CCN Occupancy Config:
Schedule Number 3-99 occpcxxe 3 Broadcast Option DISABLE/ENABLE occbrcst DISABLE
ICE BUILD Option DISABLE/ENABLE ibopt DISABLE ICE BUILD TERMINATION
0 =Temp, 1 =Contacts, 2 =Both 0-2 ibterm 0
ICE BUILD Recycle Option DISABLE/ENABLE ibrecyc DISABLE
NOTE: D = delta degrees.
.
.
.
.
10D(6D) 85 (29)
10D(6D)
0 DISABLE
DISABLE 3
EXAMPLE 6 — LEAD/LAG CONFIGURATION DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
2. Press SERVICE
3. Scroll down to highlight EQUIPMENT CONFIGURATION.
4. Press SELECT
5. Scroll down to highlight Lead/Lag.
6. Press SELECT
DESCRIPTION CONFIGURABLE RANGE UNITS REFERENCE POINT NAME DEFAULT VALUE
LEAD/LAG SELECT
DISABLE =0, LEAD =1, LAG =2, STANDBY =3
Load Balance Option DISABLE/ENABLE loadbal DISABLE Common Sensor Option DISABLE/ENABLE commsens DISABLE
LAG Percent Capacity 25-75 % lag per LAG Address 1-236 lag add LAG START Timer 2-60 MIN lagstart 10 LAG STOP Timer 2-60 MIN lagstop 10 PRESTART FAULT Timer 0-30 MIN preflt 5 STANDBY Chiller Option DISABLE/ENABLE stndopt DISABLE STANDBY Percent Capacity 25-75 % stnd per STANDBY Address 1-236 stnd add
NOTE: The Lead/Lag Configuration table is available on PSIO Software Version 09 and higher.
.
.
.
.
LEAD/LAG CONFIGURATION SCREEN
0-3 leadlag 0
50 92
50 93
23
Page 24
Table 2 — LID Screens (cont)
EXAMPLE 7 — SERVICE1 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
2. Press SERVICE
3. Scroll down to highlight EQUIPMENT SERVICE.
4. Press SELECT
5. Scroll down to highlight SERVICE1.
6. Press SELECT
DESCRIPTION CONFIGURABLE RANGE UNITS REFERENCE POINT NAME DEFAULT VALUE
Motor Temp Override 150-200 (66-93) DEG F (DEG C) mt over Cond Press Override Refrig Override Delta T 2-5 (1-3) DEG F (DEG C) ref over 3D (1.6D)
Chilled Medium Water/Brine medium WATER Brine Refrig Trippoint 8-40 (–13.3-4) DEG F (DEG C) br trip
Compr Discharge Alert 125-200 (52-93) DEG F (DEG C) cd alert Bearing Temp Alert 175-185 (79-85) DEG F (DEG C) tb alert 175 (79)
Water Flow Verify Time 0.5-5 MIN wflow t Oil Press Verify Time 15-300 SEC oilpr t 15
Water/Brine Deadband 0.5-2.0 (0.3-1.1) DEG F (DEG C) cw db Recycle Restart Delta T 2.0-10.0 (1.1-5.6) DEG F (DEG C) rcyc dt Recycle Shutdown Delta T 0.5-4.0 (0.27-2.2) DDEGF(DDEG C) rcycs dt 1.0 (0.6)
Surge Limit/HGBP Option 0/1 srg hgbp Select: Surge=0, HGBP=1 Surge/HGBP Delta T1 0.5-15 (0.3-8.3) DEG F (DEG C) hgb dt1 1.5 (0.8)
Surge/HGBP Delta P1 Min. Load Points (T1/P1)
Surge/HGBP Delta T2 0.5-15 (0.3-8.3) DEG F (DEG C) hgb dt2 Surge/HGBP Delta P2 Full Load Points (T2/P2)
Surge/HGBP Deadband 1-3 (0.6-1.6) DEG F (DEG C) hgb dp Surge Delta Percent Amps 10-50 % surge a
Surge Time Period 1-5 MIN surge t 2 Demand Limit Source 0/1 dem src
Select: Amps=0, Load=1 Amps Correction Factor 1-8 corfact 3 Motor Rated Load Amps 1-9999 AMPS a fs Motor Rated Line Voltage 1-9999 VOLTS v fs Meter Rated Line kW 1-9999 kW kw fs 600
Line Frequency 0/1 HZ freq 0 Select: 0=60 Hz, 1=50 Hz
Compr Starter Type REDUCE/FULL starter REDUCE Condenser Freeze Point –20-35 (–28.9-1.7) DEG F (DEG C) cdfreeze 34 (1) Soft Stop Amps Threshold 40-100 % softstop 100
NOTES:
1. Condenser Freeze Point and Softstop Amps Threshold are only selectable/readable on PSIO Software Versions 09 and higher.
2. Values in [ ] indicate HFC-134a values.
3. D = delta degrees.
.
.
.
.
150-245 (1034-1689)
[90-200 (620-1379)]
50-170 (345-1172)
[30-170 (207-1172)]
50-170 (345-1172) [30-170 (207-1172)]
PSI (kPa) cp over
PSI (kPA) hgb dp1
PSI (kPa) hgb dp2 170 (1172) [85 (586)]
200 (93) 195 (1345) [125 (862)]
33 (1) 200 (93)
5
1.0 (0.6) 5 (2.8)
0
75 (517) [50 (345)]
10 (5.6)
1 (0.6) 25
0
200 460
24
Page 25
Table 2 — LID Screens (cont)
EXAMPLE 8 — SERVICE2 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
2. Press SERVICE
3. Scroll down to highlight EQUIPMENT SERVICE.
4. Press SELECT
5. Scroll down to highlight SERVICE2.
6. Press SELECT
DESCRIPTION CONFIGURABLE RANGE UNITS REFERENCE POINT NAME DEFAULT VALUE OPTIONS BOARD 1 20 mA POWER CONFIGURATION
External = 0, Internal = 1 RESET 20 mA Power Source 0,1 res 20 ma DEMAND 20 mA Power Source 0,1 dem 20 ma SPARE ALERT ENABLE
Disable = 0, Low = 1, High = 2 Temp = Alert Threshold
CHWS Temp Enable 0-2 chws en CHWS Temp Alert –40-245 (–40-118) DEG F (DEG C) chws al 245 (118) CHWR Temp Enable 0-2 chwr en 0 CHWR Temp Alert –40-245 (–40-118) DEG F (DEG C) chwr al Reset Temp Enable 0-2 rres en 0 Reset Temp Alert –40-245 (–40-118) DEG F (DEG C) rres al 245 (118) Spare Temp 1 Enable 0-2 spr1 en Spare Temp 1 Alert –40-245 (–40-118) DEG F (DEG C) spr1 al 245 (118) Spare Temp 2 Enable 0-2 spr2 en 0 Spare Temp 2 Alert –40-245 (–40-118) DEG F (DEG C) spr2 al Spare Temp 3 Enable 0-2 spr3 en 0 Spare Temp 3 Alert –40-245 (–40-118) DEG F (DEG C) spr3 al
OPTIONS BOARD 2 20 mA POWER CONFIGURATION
External = 0, Internal = 1 SPARE 1 20 mA Power Source 0,1 sp1 20 ma SPARE 2 20 mA Power Source 0,1 sp2 20 ma 0
SPARE ALERT ENABLE Disable = 0, Low = 1, High = 2 Temp = Alert Threshold
Spare Temp 4 Enable 0-2 spr4 en Spare Temp 4 Alert –40-245 (–40-118) DEG F (DEG C) spr4 al Spare Temp 5 Enable 0-2 spr5 en 0 Spare Temp 5 Alert –40-245 (–40-118) DEG F (DEG C) spr5 al 245 (118) Spare Temp 6 Enable 0-2 spr6 en Spare Temp 6 Alert –40-245 (–40-118) DEG F (DEG C) spr6 al 245 (118) Spare Temp 7 Enable 0-2 spr7 en Spare Temp 7 Alert –40-245 (–40-118) DEG F (DEG C) spr7 al 245 (118) Spare Temp 8 Enable 0-2 spr8 en 0 Spare Temp 8 Alert –40-245 (–0-118) DEG F (DEG C) spr8 al Spare Temp 9 Enable 0-2 spr9 en 0 Spare Temp 9 Alert –40-245 (–40-118) DEG F (DEG C) spr9 al 245 (118)
NOTE: This screen provides the means to generate alert messages based on exceeding the ‘‘Temp Alert’’ threshold for each point listed. If the ‘‘Enable’’is set to 1, a value above the ‘‘Temp Alert’’ threshold shall generate an alert message. If the ‘‘Enable’’ is set to 2, a value below the ‘‘Temp Alert’’ threshold shall generate an alert message. If the ‘‘Enable’’ is set to 0, alert generation is disabled.
.
.
.
.
0 0
0
245 (118)
0
245 (118) 245 (118)
0
0 245 (118)
0 0
245 (118)
EXAMPLE 9 — SERVICE3 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
2. Press SERVICE
3. Scroll down to highlight EQUIPMENT SERVICE.
4. Press SELECT
5. Scroll down to highlight SERVICE3.
DESCRIPTION CONFIGURABLE RANGE UNITS REFERENCE POINT NAME DEFAULT VALUE
Proportional Inc Band 2-10 gv inc Proportional Dec Band 2-10 gv de Proportional ECW Gain 1-3 gv ecw Guide Vane Travel Limit 30-100 % gv lim
.
.
.
25
6.5
6.0
2.0 50
Page 26
Table 2 — LID Screens (cont)
EXAMPLE 10 — MAINTENANCE (MAINT01) DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
2. Press SERVICE
3. Scroll down to highlight ALGORITHM STATUS.
4. Press SELECT
5. Scroll down to highlight MAINT01.
CAPACITY CONTROL Control Point 10-120 (–12.2-48.9) DEG F (DEG C) ctrlpt Leaving Chilled Water –40-245 (–40-118) DEG F (DEG C) LCW Entering Chilled Water –40-245 (–40-118) DEG F (DEG C) ECW Control Point Error –99-99 (–55-55) DEG F (DEG C) cperr ECW Delta T –99-99 (–55-55) DEG F (DEG C) ecwdt ECW Reset –99-99 (–55-55) DEG F (DEG C) ecwres LCW Reset –99-99 (–55-55) DEG F (DEG C) lcwres Total Error + Resets –99-99 (–55-55) DEG F (DEG C) error Guide Vane Delta –2-2 % gvd Target Guide Vane Pos 0-100 % GV TRG Actual Guide Vane Pos 0-100 % GV ACT Proportional Inc Band 2-10 gv inc Proportional Dec Band 2-10 gv dec Proportional ECW Gain 1-3 gv ecw Water/Brine Deadband 0.5-2 (0.3-1.1) DEG F (DEG C) cwdb
NOTE: Overriding is not supported on this maintenance screen.Active overrides show the associated point in alert (*). Only values with capital letter reference point names are variables available for read operation.
.
.
.
DESCRIPTION RANGE/STATUS UNITS REFERENCE POINT NAME
EXAMPLE 11 — MAINTENANCE (MAINT02) DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
2. Press SERVICE
3. Scroll down to highlight CONTROL ALGORITHM STATUS.
4. Press SELECT
5. Scroll down to highlight MAINT02.
6. Press SELECT
OVERRIDE/ALERT STATUS MOTOR WINDING TEMP –40-245 (–40-118) DEG F (DEG C) MTRW
Override Threshold 150-200 (66-93) DEG F (DEG C) mt over CONDENSER PRESSURE –6.7-420 (–42-2896) PSI (kPa) CRP
Override Threshold 90-245 (621-1689) PSI (kPa) cp over EVAPORATOR REFRIG TEMP –40-245 (–40-118) DEG F (DEG C) ERT
Override Threshold 2-45 (1-7.2) DEG F (DEG C) rt over DISCHARGE TEMPERATURE –40-245 (–40-118) DEG F (DEG C) CMPD
Alert Threshold 125-200 (52-93) DEG F (DEG C) cd alert BEARING TEMPERATURE –40-245 (–40-118) DEG F (DEG C) MTRB
Alert Threshold 175-185 (79-85) DEG F (DEG C) tb alert
NOTE: Overriding is not supported on this maintenance screen.Active overrides show the associated point in alert (*). Only values with capital letter reference point names are variables available for read operation.
.
.
.
.
DESCRIPTION RANGE/STATUS UNITS REFERENCE POINT NAME
26
Page 27
Table 2 — LID Screens (cont)
EXAMPLE 12 — MAINTENANCE (MAINT03) DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
2. Press SERVICE
3. Scroll down to highlight CONTROL ALGORITHM STATUS.
4. Press SELECT
5. Scroll down to highlight MAINT03.
6. Press SELECT
SURGE/HGBP ACTIVE ? NO/YES Active Delta P 0-200 (0-1379) PSI (kPa) dp a Active Delta T 0-200 (0-111) DEG F (DEG C) dt a
Calculated Delta T 0-200 (0-111) DEG F (DEG C) dt c Surge Protection Counts 0-12 spc
NOTE: Override is not supported on this maintenance screen. Only values with capital letter reference point names are variables available for read operation.
To access this display from the LID default screen:
1. Press MENU
2. Press SERVICE
3. Scroll down to highlight CONTROL ALGORITHM STATUS.
4. Press SELECT
5. Scroll down to highlight MAINT04.
6. Press SELECT
.
.
.
.
DESCRIPTION RANGE/STATUS UNITS REFERENCE POINT NAME
EXAMPLE 13 — MAINTENANCE (MAINT04 DISPLAY SCREEN
.
.
.
.
DESCRIPTION RANGE/STATUS UNITS REFERENCE POINT NAME
LEAD/LAG: Configuration DISABLE,LEAD,LAG,STANDBY, INVALID leadlag Load Balance Option DISABLE/ENABLE loadbal
LAG Start Time 0-60 MIN lagstart LAG Stop Time 0-60 MIN lagstop Prestart Fault Time 0-30 MIN preflt Pulldown: Delta T/Min 2-10 F/min (1.1-5.5 C/min) D DEG F/min pull dt
LEAD CHILLER in Control No/Yes leadctrl LAG CHILLER: Mode Reset,Off,Local,CCN lagmode
Recovery Start Request No/Yes lag rec STANDBY CHILLER: Mode Reset,Off,Local,CCN stdmode
Recovery Start Request No/Yes std rec
NOTES:
1. Only values with capital letter reference point names are variables available for read operation. Forcing is not supported on this maintenance screen.
2. The MAINT04 screen is available on PSIO Software Version 09 and higher.
3. D = delta degrees.
Current Mode DISABLE,LEAD,LAG,STANDBY, CONFIG llmode
Satisfied? No/Yes (D DEG C/min) pull sat
Run Status Timeout,Recycle,Startup,Ramping,Running Start/Stop Stop,Start,Retain lag s s
Run Status Timeout,Recycle,Startup,Ramping,Running Start/Stop Stop,Start,Retain std s s
Demand,Override,Shutdown,Abnormal,Pumpdown
Demand,Override,Shutdown,Abnormal,Pumpdown
lagstat
stdstat
27
Page 28
PIC System Functions
NOTE: Throughout this manual, words printed in capital let­ters and italics represent values that may be viewed on the LID. See Table 2 for examples of LID screens. Point names are listed in the Description column. An overview of LID operation and menus is given in Fig. 13-19.
CAPACITY CONTROL — The PIC controls the chiller capacity by modulating the inlet guide vanes in response to chilled water temperature changes away from the CON- TROL POINT. The CONTROL POINT may be changed by a CCN network device, or is determined by the PIC adding any active chilled water reset to the ECW (Entering Chilled
Water) SET POINT or LCW SET POINT. The PIC uses the PROPORTIONAL INC (Increase) BAND, PROPORTIONAL DEC (Decrease)BAND, and the PROPORTIONAL ECW GAIN
to determine how fast or slow to respond. CONTROL POINT may be viewed/overridden on the Status table, Status01 selection.
ENTERING CHILLED WATER CONTROL — If this op­tion is enabled, the PIC uses ENTERING CHILLED WATER temperature to modulate the vanes instead of LEAV-
ING CHILLED WATERtemperature. ENTERING CHILLED W ATER control option may be viewed/modified on the Equip-
ment Configuration table, Config table. DEADBAND — This is the tolerance on the chilled water/
brine temperature CONTROL POINT. If the water temper­ature goes outside of the DEADBAND, the PIC opens or closes the guide vanes in response until it is within tolerance. The PIC may be configured with a 0.5 to 2 F (0.3 to 1.1 C) dead­band. DEADBAND may be viewed or modified on the Equip­ment Service1 table.
For example, a 1° F (0.6° C) deadband setting controls the water temperature within ±0.5° F (0.3° C) of the con­trol point. This may cause frequent guide vane movement if the chilled water load fluctuates frequently. A value of 1° F (0.6° C) is the default setting.
PROPORTIONALBANDSAND GAIN — Proportional band is the rate at which the guide vane position is corrected in proportion to how far the chilled water/brine temperature is from the control point. Proportional gain determines how quickly the guide vanes react to how quickly the tempera­ture is moving from CONTROL POINT.
The proportional band can be viewed/modified on the LID. There are two response modes, one for temperature re­sponse above the control point, the other for response below the control point.
The first type is called PROPORTIONAL INC BAND, and it can slow or quicken vane response to chilled water/ brine temperature above DEADBAND. It can be adjusted from a setting of 2 to 10; the default setting is 6.5. PRO- PORTIONAL DEC BAND can slow or quicken vane re­sponse to chilled water temperature below deadband plus control point. It can be adjusted on the LID from a setting of 2 to 10, and the default setting is 6.0. Increasing either of these set­tings will cause the vanes to respond slower than at a lower setting.
The PROPORTIONAL ECW GAIN can be adjusted at the LID display from a setting of 1.0 to 3.0, with a default setting of
2.0. Increase this setting to increase guide vane response to a change in entering chilled water temperature. The propor­tional bands and gain may be viewed/modified on the Equip­ment Service3 table.
DEMAND LIMITING — The PIC will respond to the ACTIVE DEMAND LIMIT set point by limiting the open­ing of the guide vanes. It will compare the set point to either COMPRESSOR MOTOR LOAD or COMPRES- SOR MOTOR CURRENT (percentage), depending on how the control is configured for the DEMAND LIMIT SOURCE which is accessed on the SERVICE1 table. The default set­ting is current limiting.
CHILLER TIMERS — The PIC maintains 2 runtime clocks, known as COMPRESSOR ONTIME and SERVICE ON- TIME. COMPRESSOR ONTIME indicates the total life­time compressor run hours. This timer can register up to 500,000 hours before the clock turns back to zero. The SERVICE ONTIME is a resettable timer that can be used to indicate the hours since the last service visit or any other reason. The time can be changed through the LID to whatever value is desired. This timer can register up to 32,767 hours before it rolls over to zero.
The chiller also maintains a start-to-start timer and a stop­to-start timer. These timers limit how soon the chiller can be started. See the Start-Up/Shutdown/Recycle Sequence sec­tion, page 39, for operational information.
OCCUPANCY SCHEDULE — This schedule determines when the chiller is either occupied or unoccupied.
Each schedule consists of from one to 8 occupied/unoccupied time periods, set by the operator. These time periods can be enabled to be in effect, or not in effect, on each day of the week and for holidays. The day begins with 0000 hours and ends with 2400 hours. The chiller is in OCCUPIED mode unless an unoccupied time period is in effect.
The chiller will shut down when the schedule goes to UN­OCCUPIED. These schedules can be set up to follow the building schedule or to be 100% OCCUPIED if the operator wishes. The schedules also can be bypassed by forcing the Start/Stop command on the PIC Status screen to start. The schedules also can be overridden to keep the unit in an OC­CUPIED mode for up to 4 hours, on a one-time basis.
Figure 18 shows a schedule for a typical office building time schedule, with a 3-hour, off-peak cool down period from midnight to 3 a.m., following a weekend shutdown. Example: Holiday periods are unoccupied 24 hours per day. The building operates Monday through Friday, 7:00 a.m. to 6:00 p.m., with a Saturday schedule of 6:00 a.m. to 1:00 p.m., and includes the Monday midnight to 3:00 a.m. weekend cool-down schedule.
NOTE: This schedule is for illustration only, and is not in­tended to be a recommended schedule for chiller operation.
PSIO Software Version 08 and Lower — Whenever the chiller is in the LOCAL mode, the chiller will start when the Occupancy Schedule 01 indicates OCCUPIED. When in the CCN mode, Occupancy Schedule 02 is used.
PSIO Software Version 09 and Higher — The Local Time Schedule is still the Occupancy Schedule 01. The Ice Build Time Schedule is Schedule 02 and the CCN Default Time Schedule is Schedule 03. The CCN schedule number is de­fined on the Config table in the Equipment Configuration table on page 23. The schedule number can change to any value from 03 to 99. If this schedule number is changed on the Config table, the operator must use the Attach to Net­work Device table to upload the new number into the Sched­ule screen. See Fig. 17.
28
Page 29
Safety Controls — The PIC monitors all safety control
inputs, and if required, shuts down the chiller or limits the guide vanes to protect the chiller from possible damage from any of the following conditions:
• high bearing temperature
• high motor winding temperature
• high discharge temperature
• low oil pressure
• low cooler refrigerant temperature/pressure
• condenser high pressure or low pressure
• inadequate water/brine cooler and condenser flow
• high, low, or loss of voltage
• excessive motor acceleration time
• excessive starter transition time
• lack of motor current signal
• excessive motor amps
• excessive compressor surge
• temperature and transducer faults Starter faults or optional protective devices within the starter
can shut down the chiller. These devices are dependent on what has been purchased as options.
If compressor motor overload occurs, check the motor for grounded or open phases before attempting a restart.
If the controller initiates a safety shutdown, it displays
the fault on the LID display with a primary and a secondary message, and energizes an alarm relay in the starter and blinks the alarm light on the control center. The alarm is stored in memory and can be viewed in the PIC alarm table along with a message for troubleshooting.
To give a better warning as to the operating condition of the chiller, the operator also can define alert limits on vari­ous monitored inputs. Safety contact and alert limits are defined in Table 3.Alarm and alert messages are listed in the Troubleshooting Guide section, page 66.
SHUNTTRIP — The shunt trip function of the PIC is a safety trip. The shunt trip is wired from an output on the SMM to a shunt trip-equipped motor circuit breaker. If the PIC tries to shut down the compressor through normal shutdown pro­cedure but is unsuccessful for 30 seconds, the shunt trip out­put is energized and causes the circuit breaker to trip off. If ground fault protection has been applied to the starter, the ground fault trip will also energize the shunt trip to trip the circuit breaker.
Default Screen Freeze — Whenever an alarm
occurs, the LID default screen will freeze displaying the condition of the chiller at the time of alarm. Knowledge of the operating state of the chiller at the time an alarm occurs is useful when troubleshooting. Current chiller information can be viewed on the Status tables. Once all existing alarms
are cleared (by pressing the RESET LID will return to normal operation.
softkey), the default
Motor Cooling Control — Motor temperature is
reduced by refrigerant entering the motor shell and evap­orating. The refrigerant is regulated by the motor cooling relay. This relay will energize when the compressor is run­ning and motor temperature is above 125 F (51.7 C). The relay will close when motor temperature is below 100 F (37.8 C). Note that there is always a minimum flow of refrigerant when the compressor is operating for motor cool­ing; the relay only controls additional refrigerant to the motor.
29
Page 30
Table 3 — Protective Safety Limits and Control Settings
MONITORED PARAMETER LIMIT APPLICABLE COMMENTS
TEMPERATURE SENSORS OUT OF RANGE
PRESSURE TRANSDUCERS OUT OF RANGE
COMPRESSOR DISCHARGE TEMPERATURE
MOTOR WINDING TEMPERATURE .220 F (104.4 C) Preset, alert setting configurable BEARING TEMPERATURE .185 F (85 C) Preset, alert setting configurable
EVAPORATOR REFRIGERANT TEMPERATURE
TRANSDUCER VOLTAGE ,4.5 vdc . 5.5 vdc Preset CONDENSER PRESSURE — SWITCH
— CONTROL
OIL PRESSURE — SWITCH Cutout ,11 psid (76 kPad) ± 1.5 psid (10.3 kPad)
— CONTROL
LINE VOLTAGE — HIGH .110% for one minute
— LOW ,90% for one minute or <85% for 3 seconds — SINGLE-CYCLE ,50% for one cycle
COMPRESSOR MOTOR LOAD
STARTER ACCELERATION TIME (Determined by inrush current going below 100% compressor motor load)
STARTER TRANSITION .75 seconds Reduced voltage starters only
CONDENSER FREEZE PROTECTION
–40 to 245 F (–40 to 118.3 C) Must be outside range for 2 seconds
0.08 to 0.98 Voltage Ratio
.220 F (104.4 C) Preset, alert setting configurable
,33 F (for water chilling) (0.6° C) ,Brine Refrigerant Trippoint (set point adjustable
from 0 to 40 F [–18 to 4 C] for brine chilling)
.263 ± 7 psig (1813 ± 48 kPa), reset at 180 ± 10 (1241 ± 69 kPa)
.260 psig (1793 kPa) for HCFC-22; 215 psig (1482 kPa) for HFC-134a
Cut-in .16.5 psid (114 kPad) ± 4 psid (27.5 kPad) Cutout ,15 psid (103 kPad)
Alert ,18 psid (124 kPad)
.110% for 30 seconds Preset ,10% with compressor running Preset .10% with compressor off Preset
.45 seconds .10 seconds
Energizes condenser pump relay if condenser refrigerant temperature or condenser entering water temperature is below the configured con­denser freeze point temperature. Deenergizes when the temperature is5F(3C)above con­denser freeze point temperature.
Must be outside range for 2 seconds. Ratio = Input Voltage ÷ Voltage Reference
Preset, configure chilled medium for water (Service1 table)
Configure chilled medium for brine (Service1 table). Adjust brine refrigerant trippoint for proper cutout
Preset Preset Preset, no calibration needed Preset
Preset, based on transformed line volt­age to 24 vac rated-input to the Starter Management Module. Also monitored at PSIO power input.
For chillers with reduced voltage me­chanical and solid-state starters
For chillers with full voltage starters (Configured on Service1 table)
CONDENSER FREEZE POINT config­ured in Service01 table with a default setting of 34 F (1 C).
Flow Switches (Field Supplied)
Operate water pumps with chiller off. Manually reduce water flow and observe switch for proper cutout.Safety shutdown occurs when cutout time exceeds 3 seconds.
30
CUT-OUT SETTING ADJUSTMENT SCREW
Page 31
Ramp Loading Control — The ramp loading control
slows down the rate at which the compressor loads up. This control can prevent the compressor from loading up during the short period of time when the chiller is started, and the chilled water loop has to be brought down to normal design conditions. This helps reduce electrical demand charges by slowly bringing the chilled water to control point. However, the total power draw during this period remains almost unchanged.
There are 2 methods of ramp loading with the PIC. Ramp loading can be based on chilled water temperature or on mo­tor load.
1. Temperature ramp loading limits the rate at which either
leaving chilled water or entering chilled water temper­ature decreases by an operator-configured rate. The low­est temperature ramp table will be used the first time the chiller is started (at commissioning). The lowest tem­perature ramp rate will also be used if chiller power has been off for 3 hours or more (even if the motor ramp load is selected).
2. Motor load ramp loading limits the rate at which the
compressor motor current or compressor motor load increases by an operator-configured rate.
The TEMP (Temperature) PULLDOWN, LOAD PULL DOWN, and SELECT RAMP TYPE may be viewed/modified
on the LID Equipment Configuration table, Config table (see Table 2). Motor load is the default type.
Capacity Override (Table 4) — Capacity overrides
can prevent some safety shutdowns caused by exceeding motor amperage limit, refrigerant low temperature safety limit, motor high temperature safety limit, and condenser high pres­sure limit. In all cases there are 2 stages of compressor vane control.
1. The vanes are held from opening further, and the status line on the LID indicates the reason for the override.
2. The vanes are closed until condition decreases below the first step set point, and then the vanes are released to nor­mal capacity control.
Whenever the motor current demand limit set point is reached, it activates a capacity override, again with a 2-step process. Exceeding 110% of the rated load amps for more than 30 seconds will initiate a safety shutdown.
The compressor high lift (surge prevention) set point will cause a capacity override as well. When the surge preven­tion set point is reached, the controller normally will only hold the guide vanes from opening. If so equipped, the hot gas bypass valve will open instead of holding the vanes.
OVERRIDE
CAPACITY CONTROL
HIGH
CONDENSER
PRESSURE
HIGH MOTOR
TEMPERATURE
LOW
REFRIGERANT
TEMPERATURE
(Refrigerant
Override Delta
Temperature)
HIGH
COMPRESSOR
LIFT
(Surge
Prevention)
MANUAL
GUIDE VANE
TARGET
MOTOR LOAD —
ACTIVE
DEMAND LIMIT
Table 4 — Capacity Overrides
FIRST STAGE SET POINT
View/Modify
on
LID Screen
Equipment
Service1
Equipment
Service1
Equipment
Service1
Minimum:
Equipment
Service1
Control
Algorithm
Maint01
Status01 100% 40 to 100%
Maximum:
Default Value Configurable Range Value Value
HCFC-22 HFC-134a HCFC-22 HFC-134a
.195 psig (1345 kPa)
.200 F (93.3 C) 150 to 200 F (66 to 93 C)
,3° F (1.6° C)
(Above Trippoint)
HCFC-22 HFC-134a HCFC-22 HFC-134a
T1 — 1.5° F
(0.8° C)
P1 — 75 psid
(517 kPad)
T2 — 10° F
(5.6° C)
P2 — 170 psid
(1172 kPad)
Automatic 0 to 100% None
125 psig
(862 kPa)
Minimum:
T1 — 1.5° F
(0.8° C)
P1 — 50 psid
(345 kPad)
Maximum:
T2 — 10° F
(5.6° C)
P2 — 85 psid
(586 kPad)
150 to 245 psig
(1034 to 1689 kPa)
2° to 5° F
(1° to 3° C)
0.5° to 15° F
(0.3° to 8.3° C)
50 to 170 psid
(345 to 1172 kPad)
0.5° to 15° F
(0.3° to 8.3° C)
50 to 170 psid
(345 to 1172 kPad)
90 to 200 psig
(620 to 1379 kPa)
0.5° to 15° F
(0.3° to 8.3° C)
30 to 170 psid
(207 to 1172 kPad)
0.5° to 15° F
(0.3° to 8.3° C)
30 to 170 psid
(207 to 1172 kPad)
SECOND
STAGE
SET POINT
.Override
Set Point
+ 4 psig
(28 kPa)
.Override
Set Point
+10° F
(6° C)
<Trippoint + Override
DT –1° F (0.56° C)
None
>5% of
Set Point
OVERRIDE
TERMINATION
,Override
Set Point
,Override
Set Point
.Trippoint + Override
DT +2° F
(1.2° C)
Within
Lift Limits
Plus Surge/
HGBP
Deadband
Setting
Release of
Manual Control
2% Lower
Than
Set Point
31
Page 32
High Discharge Temperature Control — If the
discharge temperature increases above 160 F (71.1 C) (PSIO Software Version 09 and higher) or 180 F (82 C) (PSIO Software Version 08 or lower), the guide vanes are propor­tionally opened to increase gas flow through the compressor. If the leaving chilled water temperature is then brought 5° F (2.8° C) below the control set point temperature, the con­trols will bring the chiller into the recycle mode.
OilSump TemperatureControl — The oil sump tem-
perature control is regulated by the PIC which uses the oil heater relay when the chiller is shut down.
As part of the pre-start checks executed by the controls, oil sump temperature is compared against evaporator refrig­erant temperature. If the difference between these 2 tem­peratures is 50 F (27.8 C) or less, the start-up will be delayed until the oil temperature is 50 F (27.8 C) or more. Once this temperature is confirmed, the start-up continues.
PSIO SOFTWAREVERSION 08 AND LOWER — The oil heater relay is energized whenever the chiller compressor is off, and the oil sump temperature is less than 140 F (60 C) or sump temperature is less than the cooler refrigerant tem­perature plus 60° F (33.3° C). The heater is then turned off when the oil sump temperature is: 1) more than 160 F (71.1 C); or 2) the sump temperature is more than 145 F (62.8 C) and more than the cooler refrigerant tem­perature plus 65° F (36.1° C). The heater is always off dur­ing start-up or when the compressor is running.
PSIO SOFTWARE VERSION 09 AND HIGHER — The oil heater relay is energized whenever the chiller compressor is off and the oil sump temperature is less than 150 F (65.6 C) or the oil sump temperature is less than the cooler refrig­erant temperature plus 70° F (39° C). The oil heater is turned off when the oil sump temperature is either 1) more than 160 F (71.1 C); or 2) the oil sump temperature is more than 155 F (68.3 C) and more than the cooler refrigerant tem­perature plus 75° F (41.6° C). The oil heater is always off during start-up or when the compressor is running.
When a power failure to the PSIO module has occurred for more than 3 hours (i.e., initial start-up), the oil sump is heated to 100° F (56° C) above the evaporator refrigerant temperature or 190 F (88 C), whichever is lower. Once this temperature is reached, the oil pump will be energized for 1 to 2 minutes or until the oil sump temperature cools to below 145 F (63 C). The normal heating algorithm is now followed once ramp loading has been completed.
After a 3-hour power failure, the oil temperature must rise to the higher oil temperature. The controls will delay the start of the compressor until this temperature is met.
Oil Cooler — The oil must be cooled when the compres-
sor is running. This is accomplished through a small, plate­type heat exchanger located behind the oil pump. The heat exchanger uses liquid condenser refrigerant as the cooling liquid.Arefrigerant thermostatic expansion valve (TXV) regu­lates refrigerant flow to control oil temperature entering the bearings. There is always a flow of refrigerant bypassing the thermostaticTXV .The bulb for the expansion valve is strapped to the oil supply line leaving the heat exchanger and the valve is set to maintain 110 F (43 C).
NOTE: The TXV is not adjustable. Oil sump temperature may be at a lower temperature.
RemoteStart/Stop Controls — A remote device, such
as a time clock which uses a set of contacts, may be used to start and stop the chiller. However, the device should not be programmed to start and stop the chiller in excess of 2 or
3 times every 12 hours. If more than 8 starts in 12 hours occur, then an Excessive Starts alarm is displayed, prevent­ing the chiller from starting. The operator must reset the alarm at the LID in order to override the starts counter and start the chiller. If Automatic Restart After a Power Failure is not activated when a power failure occurs, and the remote con­tact is closed, the chiller will indicate an alarm because of the loss of voltage.
The contacts for Remote Start are wired into the starter at terminal strip TB5, terminals 8A and 8B. See the certified drawings for further details on contact ratings. The contacts must be dry (no power).
Spare Safety Inputs — Normally closed (NC) digital
inputs for additional field-supplied safeties may be wired to the spare protective limits input channel in place of the factory­installed jumper. (Wire multiple inputs in series.) The open­ing of any contact will result in a safety shutdown and LID display. Refer to the certified drawings for safety contact ratings.
Analog temperature sensors may also be added to the options modules, if installed. These may be programmed to cause an alert on the CCN network, but will not shut the chiller down.
SPARE ALARM CONTACTS — Two spare sets of alarm contacts are provided within the starter. The contact ratings are provided in the certified drawings. The contacts are located on terminal strip TB6, terminals 5A and 5B, and terminals 5C and 5D.
Condenser Pump Control — The chiller will moni-
tor the CONDENSER PRESSURE and may turn on this pump if the pressure becomes too high whenever the compressor is shut down. CONDENSER PRESSURE OVERRIDEis used to determine this pressure point. This value is found on the Equipment Service1 LID table and has a default value (Table 4). If the CONDENSER PRESSURE is greater than or equal to the CONDENSER PRESSURE OVERRIDE, and the ENTERING CONDENSER WATER TEMP (Temper- ature) is less than 115 F (46 C), then the condenser pump will energize to try to decrease the pressure. The pump will turn off when the condenser pressure is less than the pressure override less 5 psi (34 kPa), or the CONDENSER
REFRIG (Refrigerant) TEMP is within 3° F (2° C) of the ENTERING CONDENSER WATER temperature.
Condenser Freeze Prevention — This control
algorithm helps prevent condenser tube freeze-up by ener­gizing the condenser pump relay. If the pump is controlled by the PIC, starting the pump will help prevent the water in the condenser from freezing. Condenser freeze prevention can occur whenever the chiller is not running except when it is either actively in pumpdown or in Pumpdown Lockout with the freeze prevention disabled (refer to ControlTest table, Pumpdown/Terminate Lockout tables).
When the CONDENSER REFRIG TEMP is less than or equal to the CONDENSER FREEZE POINT,orthe ENTERING CONDENSER WATER temperature is less than or equal to the CONDENSER FREEZE POINT, then the
CONDENSER WATER PUMP shall be energized until the CONDENSER REFRIG TEMP is greater than the CON­DENSER FREEZE POINT plus 5° F (2.7° C). An alarm will
be generated if the chiller is in PUMPDOWN mode and the pump is energized. An alert will be generated if the chiller is not in PUMPDOWN mode and the pump is energized. If in recycle shutdown, the mode shall transition to a non­recycle shutdown.
32
Page 33
Tower Fan Relay — Low condenser water tempera-
ture can cause the chiller to shut down on low refrigerant temperature. The tower fan relay, located in the starter, is controlled by the PIC to energize and deenergize as the pres­sure differentialbetween cooler and condenser vessels changes in order to prevent low condenser water temperature and to maximize chiller efficiency. The tower fan relay can only accomplish this if the relay has been added to the cooling tower temperature controller. The TOWER FAN RELAY is turned on whenever the CONDENSER WATER PUMP is running, flow is verified, and the difference between cooler and condenser pressure is more than 45 psid (310 kPad) [30 psid (207 kPad)] or entering condenser water temper­ature is greater than 85 F (29 C). The TOWER FAN RELAY is deenergized when the condenser pump is off, flow is lost, the evaporator refrigerant temperature is less than the over­ride temperature, or the differential pressure is less than 40 psid (279 kPad) [28 psid (193 kPad)] and entering con­densing water is less than 80 F (27 C).
IMPORTANT:Afield-supplied water temperature con­trol system for condenser water should be installed. The system should maintain the leaving condenser wa­ter temperature at a temperature that is 20° F (11° C) above the leaving chilled water temperature.
The tower-fan relay control is not a substitute for a con­denser water temperature control. When used with a Water Temperature Control system, the tower fan relay control can be used to help prevent low condenser wa­ter temperatures.
Auto. Restart After Power Failure — This option
may be enabled or disabled, and may be viewed/modified in the Config table of Equipment Configuration. If enabled, the chiller will start up automatically after a single cycle drop­out, low,high, or loss of voltage has occurred, and the power is within ±10% of normal. The 15- and 3-minute inhibit tim­ers are ignored during this type of start-up.
When power is restored after the power failure, and if the compressor had been running, the oil pump will be ener­gized for one minute prior to the evaporator pump ener­gizing. Auto restart will then continue like a normal start-up.
If power to the PSIO module has been off for more than 3 hours, the oil heat algorithm, discussed in the Oil Sump Temperature Control section on page 32, will take effect be­fore the compressor can start. Refrigerant normally migrates into the oil when the oil heater is left off for extended pe­riods of time. The PIC operates the oil pump for 1 to 2 min­utes to ensure that the oil is free of excess refrigerant. Once this algorithm is completed, the RESTART of the chiller will continue.
Water/Brine Reset — Three types of chilled water or
brine reset are available and can be viewed or modified on the Equipment Configuration table Config selection.
The LID default screen status message indicates when the chilled water reset is active. The Control Point tempera­ture on the Status01 table indicates the chiller’s current reset temperature.
To activate a reset type, input all configuration informa­tion for that reset type in the Config table. Then input the reset type number in the SELECT/ENABLE RESET TYPE input line.
RESET TYPE 1—Reset Type 1 requires an optional 8-input module. It is an automatic chilled water temperature reset based ona4to20mAinput signal. This type permits up to ± 30° F (± 16° C) of automatic reset to the chilled water or brine temperature set point, based on the input froma4to 20 mA signal. This signal is hardwired into the number one 8-input module.
If the 4-20 mAsignal is externally powered from the 8-input module, the signal is wired to terminals J1-5(+) and J1-6(–). If the signal is to be internally powered by the 8-input mod­ule (for example, when using variable resistance), the signal is wired to J1-7(+) and J1-6(–). The PIC must now be con­figured on the Service2 table to ensure that the appropriate power source is identified.
RESET TYPE 2—Reset Type requires an optional 8-input module. It is an automatic chilled water temperature reset based on a remote temperature sensor input. This reset type permits ± 30° F (± 16° C) of automatic reset to the set point based on a temperature sensor wired to the number one 8-input module (see wiring diagrams or certified drawings). The tem­perature sensor must be wired to terminal J1-19 and J1-20. To configure Reset Type 2, enter the temperature of the remote sensor at the point where no temperature reset will occur. Next, enter the temperature at which the full amount of reset will occur. Then, enter the maximum amount of re­set required to operate the chiller. Reset Type 2 can now be activated.
RESET TYPE 3—Reset Type 3 is an automatic chilled water temperature reset based on cooler temperature differ­ence. This type of reset will add ± 30° F (± 16° C) based on the temperature differencebetween entering and leaving chilled water temperature. This is the only type of reset available without the need of the number one 8-input module. No wir­ing is required for this type as it already uses the cooler water sensors. To configure Reset Type 3, enter the chilled water temperature difference (the difference between enter­ing and leaving chilled water) at which no temperature reset occurs. This chilled water temperature difference is usually the full design load temperature difference. The difference in chilled water temperature at which the full amount of reset will occur is now entered on the next input line. Next, the amount of reset is entered. Reset Type 3 can now be activated.
Demand Limit Control, Option — (Requires Optional 8-Input Module) —
be externally controlled witha4to20mAsignal from an energy management system (EMS). The option is set up on the Config table. When enabled, the control is set for 100% demand with 4 mAand an operator configured minimum de­mand set point at 20 mA.
The Demand Reset input from an energy management system is hardwired into the number one, 8-input module. The signal may be internally powered by the module or externally powered. If the signal is externally powered, the signal is wired to terminals J1-1 (+) and J1-2 (–). If the sig­nal is internally powered, the signal is wired to terminals J1-3 (+) and J1-2 (–). When enabled, the control is set for 100% demand with 4 mA and an operator configured mini­mum demand set point at 20 mA.
The demand limit may
Surge Prevention Algorithm — This is an operator
configurable feature which can determine if lift conditions are too high for the compressor and then take corrective action. Lift is defined as the difference between the pressure at the impeller eye and the impeller discharge. The maxi­mum lift that a particular impeller can perform varies with the gas flow across the impeller and the size of the impeller.
33
Page 34
The algorithm first determines if corrective action is nec­essary. This is done by checking 2 sets of operator con­figured data points, which are the MINIMUM and the MAXIMUM Load Points, (T1/P1;T2/P2). These points have default settings for each type of refrigerant, HCFC-22 or HFC-134a, as defined on the Service1 table, or on Table 4. These settings and the algorithm function are graphically displayed in Fig. 20 and 21. The two sets of load points on this graph (default settings are shown) describe a line which the algorithm uses to determine the maximum lift of the com­pressor. Whenever the actual differential pressure between the cooler and condenser, and the temperature difference between the entering and leaving chilled water are above the line on the graph (as defined by the MINIMUM and MAXI­MUM Load Points) the algorithm will go into a corrective action mode. If the actual values are below the line, the algorithm takes no action. Modification of the default set points of the MINIMUM and MAXIMUM load points is described in the Input Service Configuration section on page 50.
Corrective action can be taken by making one of 2 choices. If a hot gas bypass line is present, and the hot gas is con­figured on the Service1 table, then the hot gas bypass valve can be energized. If a hot gas bypass if not present, then the action taken is to hold the guide vanes. See Table 4 — Capacity Overrides. Both of these corrective actions will reduce the lift experienced by the compressor and help to prevent a surge condition. Surge is a condition when the lift becomes so high that the gas flow across the impeller reverses. This condition can eventually cause chiller dam­age. The surge prevention algorithm is intended to notify the operator that chiller operating conditions are marginal, and to take action to help prevent chiller damage such as low­ering entering condenser water temperature.
LEGEND
ECW Entering Chilled Water HGBP — Hot Gas Bypass LCW Leaving Chilled Water
DP = (Condenser Psi) — (Cooler Psi) DT = (ECW) − (LCW)
Fig. 20 — 19XL Hot Gas Bypass/Surge
Prevention
Surge Protection — Surging of the compressor can be
determined by the PIC through operator configured settings. Surge will cause amperage fluctuations of the compressor motor. The PIC monitors these amperage swings, and if the swing is greater than the configurable setting in one sec­ond, then one surge count has occurred. The SURGE DELTA PERCENTAMPS setting is displayed and configured on the Service1 screen. It has a default setting of 25% amps, SURGE PROTECTION COUNTS can be monitored on the Maint03 table.
Asurge protection shutdown of the chiller will occur when­ever the surge protection counter reaches 12 counts with­in an operator specified time, known as the SURGE TIME PERIOD. The SURGE TIME PERIOD is displayed and configured on the Service1 screen. It has a default of 2 minutes.
Lead/Lag Control
NOTE: Lead/lag control is only available on chillers with PSIO Software Version 09 or higher.
Lead/lag is a control system process that automatically starts and stops a lag or second chiller in a 2-chiller water system. Refer to Fig. 16 and 17 for menu, table, and screen selection information. On chillers that have PSIO software with Lead/ Lag capability, it is possible to utilize the PIC controls to perform the lead/lag function on 2 chillers. A third chiller can be added to the lead/lag system as a standby chiller to start up in case the lead or lag chiller in the system has shut down during an alarm condition and additional cooling is required.
NOTE: Lead/lag configuration is viewed and edited under Lead/Lag in the Equipment Configuration table (located in the Service menu). Lead/lag status during chiller operation is viewed in the MAINT04 table in the Control Algorithm Status table. See Table 2.
LEGEND
ECW Entering Chilled Water HGBP — Hot Gas Bypass LCW Leaving Chilled Water
DP = (Condenser kPa) — (Cooler kPa) DT = (ECW) — (LCW)
Fig. 21 — 19XL with Default Metric Settings
Lead/Lag System Requirements:
• all chillers must have PSIO software capable of perform­ing the lead/lag function
• water pumps MUST be energized from the PIC controls
• water flows should be constant
• CCN Time Schedules for all chillers must be identical
34
Page 35
Operation Features:
• 2 chiller lead/lag
• addition of a third chiller for backup
• manual rotation of lead chiller
• load balancing if configured
• staggered restart of the chillers after a power failure
• chillers may be piped in parallel or in series chilled water flow
COMMON POINT SENSOR INSTALLATION — Lead/ lag operation does not require a common chilled water point sensor. Common point sensors can be added to the 8-input option module, if desired. Refer to the certified drawings for termination of sensor leads.
NOTE: If the common point sensor option is chosen on a chilled water system, both chillers should have their own 8-input option module and common point sensor installed. Each chiller will use its own common point sensor for control, when that chiller is designated as the lead chiller.The PIC cannot read the value of common point sensors installed on other chill­ers in the chilled water system.
When installing chillers in series, a common point sensor should be used. If a common point sensor is not used, the leaving chilled water sensor of the upstream chiller must be moved into the leaving chilled water pipe of the downstream chiller.
If return chilled water control is required on chillers piped in series, the common point return chilled water sensor should be installed. If this sensor is not installed, the return chilled water sensor of the downstream chiller must be relocated to the return chilled water pipe of the upstream chiller.
To properly control the common supply point temperature sensor when chillers are piped in parallel, the water flow through the shutdown chillers must be isolated so that no water by­pass around the operating chiller occurs. The common point sensor option must not be used if water bypass around the operating chiller is occurring.
CHILLER COMMUNICATION WIRING — Refer to the chiller’s Installation Instructions or to the Carrier Comfort Network Interface section on page 48 of this manual for information on chiller communication wiring.
LEAD/LAG OPERATION — The PIC control provides the ability to operate 2 chillers in the LEAD/LAG mode. It also provides the additional ability to start a designated standby chiller when either the lead or lag chiller is faulted and capacity requirements are not met. The lead/lag option op­erates in CCN mode only. If any other chiller configured for lead/lag is set to the LOCAL or OFF modes, it will be un­available for lead/lag operation.
NOTE: Lead/lag configuration is viewed and edited in Lead/ Lag, under the Equipment Configuration table of the Service menu. Lead/lag status during chiller operation is viewed in the MAINT04 table in the Control Algorithm Status table.
Lead/Lag Chiller Configuration and Operation — The con­figured lead chiller is identified when the LEAD/LAG SELECT value for that chiller is configured to the value of ‘‘1.’’The configured lag chiller is identified when the LEAD/ LAG SELECT for that chiller is configured to the value of ‘‘2.’’The standby chiller is configured to a value of ‘‘3.’’A value of ‘‘0’’ disables the lead/lag in that chiller.
To configure the LAG ADDRESS value on the LEAD/ LAG Configuration table, always use the address of the other chiller on the system for this value. Using this address will make it easier to rotate the lead and lag chillers.
If the address assignments placed into the LAG ADDRESS and STANDBYADDRESS values conflict, the lead/ lag will be disabled and an alert (!) message will occur. For example, if the LAG ADDRESS matches the lead chiller’s address, the lead/lag will be disabled and an alert (!) message will occur. The lead/lag maintenance screen (MAINT04) will display the message ‘INVALID CONFIG’ in the LEAD/LAG CONFIGURATION and CURRENT MODE fields.
The lead chiller responds to normal start/stop controls such as occupancy schedule, forced start/stop, and remote start contact inputs. After completing start up and ramp loading, the PIC evaluates the need for additional capacity. If addi­tional capacity is needed, the PIC initiates the start up of the chiller configured at the LAG ADDRESS. If the lag chiller is faulted (in alarm) or is in the OFF or LOCAL modes, then the chiller at the STANDBY ADDRESS (if configured) is requested to start. After the second chiller is started and is running, the lead chiller shall monitor conditions and evalu­ate whether the capacity has reduced enough for the lead chiller to sustain the system alone. If the capacity is reduced enough for the lead chiller to sustain the CONTROL POINT temperatures alone, then the operating lag chiller is stopped.
If the lead chiller is stopped in CCN mode for any reason other than an alarm (*) condition, then the lag and standby chillers are stopped. If the configured lead chiller stops for and alarm condition, then the configured lag chiller takes the lead chiller’s place as the lead chiller and the standby chiller serves as the lag chiller.
If the configured lead chiller does not complete the start­up before the PRESTART FAULT TIMER (user configured value) elapses, then the lag chiller shall be started and the lead chiller will shut down. The lead chiller then monitors the start request from the acting lead chiller to start.The PRE- START FAULT TIMER is initiated at the time of a start request. The PRESTART FAULT TIMER’s function is to provide a timeout in the event that there is a prestart alert condition preventing the chiller from starting in a timely man­ner. The timer is configured under Lead/Lag, found in the Equipment Configuration table of the Service menu.
If the lag chiller does not achieve start-up before the PRESTART FAULT TIMER elapses, then the lag chiller shall be stopped and the standby chiller will be requested to start, if configured and ready.
Standby Chiller Configuration and Operation — The con­figured standby chiller is identified as such by having the LEAD/LAG SELECT configured to the value of ‘‘3.’’ The standby chiller can only operate as a replacement for the lag chiller if one of the other two chillers is in an alarm (*) condition (as shown on the LID panel). If both lead and lag chillers are in an alarm (*) condition, the standby chiller shall default to operate in CCN mode based on its configured Occupancy Schedule and remote contacts input.
Lag Chiller Start-Up Requirements — Before the lag chiller can be started, the following conditions must be met:
1. Lead chiller ramp loading must be complete.
2. Lead chiller CHILLED WATERtemperature must be greater
than the CONTROL POINT plus 1/2 the WATER/BRINE DEADBAND.
NOTE: The chilled water temperature sensor may be the leaving chilled water sensor, the return water sensor, the common supply water sensor, or the common return water sensor, depending on which options are configured and enabled.
3. Lead chiller ACTIVE DEMAND LIMITvalue must be greater
than 95% of full load amps.
35
Page 36
4. Lead chiller temperature pulldown rate of the CHILLED WATER temperature is less than 0.5° F (0.27° C) per minute.
5. The lag chiller status indicates it is in CCN mode and is not faulted. If the current lag chiller is in an alarm con­dition, then the standby chiller becomes the active lag chiller, if it is configured and available.
6. The configured LAG START TIMER entry has elapsed. The LAG START TIMER shall be started when the lead chiller ramp loading is completed. TheLAG STARTTIMER entry is accessed by selecting Lead/Lag from the Equip­ment Configuration table of the Service menu.
When all of the above requirements have been met, the lag chiller is forced to a STARTmode. The PIC control then monitors the lag chiller for a successful start. If the lag chiller fails to start, the standby chiller, if configured, is started.
Lag Chiller Shutdown Requirements — The following con­ditions must be met in order for the lag chiller to be stopped.
1. Lead chiller COMPRESSOR MOTOR LOAD value is less
than the lead chiller percent capacity plus 15%. NOTE: Lead chiller percent capacity = 100 – LAG PER-
CENT CAPACITY
The LAG PERCENT CAPACITY value is configured on the Lead/Lag Configuration screen.
2. The lead chiller chilled water temperature is less than
the CONTROL POINT plus
1
⁄2of the WATER/BRINE
DEADBAND.
3. The configured LAG STOP TIMER entry has elapsed.
The LAG STOP TIMER is started when the CHILLED WATER TEMPERATURE is less than the CHILLED WATER CONTROL POINT plus
1
⁄2of the WATER/
BRINE DEADBAND and the lead chiller COMPRESSOR
MOTOR LOAD is less than the lead chiller percent
capacity plus 15%. The timer is ignored if the chilled
water temperature reaches 3° F (1.67° C) below theCON-
TROL POINT and the lead chiller COMPRESSOR
MOTOR LOAD value is less than the lead chiller percent
capacity plus 15%.
FAULTED CHILLER OPERATION — If the lead chiller shuts down on an alarm (*) condition, it stops communica­tion to the lag and standby chillers. After 30 seconds, the lag chiller will now become the acting lead chiller and will start and stop the standby chiller, if necessary.
If the lag chiller faults when the lead chiller is also faulted, the standby chiller reverts to a stand-alone CCN mode of operation.
If the lead chiller is in an alarm (*) condition (as shown on the LID panel), the RESET
softkey is pressed to clear
the alarm, and the chiller is placed in the CCN mode, the lead chiller will now communicate and monitor the RUN STATUS of the lag and standby chillers. If both the lag and standby chillers are running, the lead chiller will not attempt to start and will not assume the role of lead chiller until either the lag or standby chiller shuts down. If only one chiller is running, the lead chiller will wait for a start request from the operating chiller.When the configured lead chiller starts, it assumes its role as lead chiller.
LOAD BALANCING — When the LOAD BALANCE
OPTION is enabled, the lead chiller will set the ACTIVE DEMAND LIMIT in the lag chiller to the lead chiller’sCOM­PRESSOR MOTOR LOAD value. This value has limits of 40% to 100%. When setting the lag chiller ACTIVE DEMAND LIMIT, the CONTROL POINT will be modi-
fied to a value of 3° F (1.67° C) less than the lead chiller’s CONTROL POINT value. If the LOAD BALANCE OPTION
is disabled, the ACTIVE DEMAND LIMIT and the CON- TROL POINT are forced to the same value as the lead chiller.
AUTO. RESTART AFTER POWER FAILURE — When an auto. restart condition occurs, each chiller may have a delay added to the start-up sequence, depending on its lead/ lag configuration. The lead chiller does not have a delay. The lag chiller has a 45-second delay. The standby chiller has a 90-second delay. The delay time is added after the chiller water flow verification. The PIC controls ensure that the guide vanes are closed. After the guide vane position is confirmed, the delay for lag and standby chiller occurs prior to ener­gizing the oil pump. The normal start-up sequence then continues. The auto. restart delay sequence occurs whether the chiller is in CCN or LOCAL mode and is intended to stagger the compressor motors from being energized simul­taneously. This will help reduce the inrush demands on the building power system.
Ice Build Control
IMPORTANT:The Ice Build control option is only avail­able on chillers with PSIO Software Version 09 and higher.
Ice build control automatically sets the chilled WATER/ BRINE CONTROL POINT of the chiller to a temperature where an ice building operation for thermal storage can be accomplished.
The PIC can be configured for ice build operation. Con­figuration of ice build control is accomplished through entries in the Config table, Ice Build Setpoint table, and the Ice Build Time Schedule table. Figures 16 and 17 show how to access each entry.
The Ice Build Time Schedule defines the period during which ice build is active if the ice build option is ENABLED. If the Ice Build Time Schedule overlaps other schedules defining time, then the Ice Build Time Schedule shall take priority. During the ice build period, the WATER/ BRINE CONTROLPOINT is set to the ICE BUILD SET POINT for temperature control. The ICE BUILD RECYCLE OPTION and ICE BUILD TERMINATION entries from a screen in the Config (configuration) table provide options for chiller recycle and termination of ice build cycle, respec­tively.Termination of ice build can result from the ENTER­ING CHILLED WATER/BRINE temperature being less than the ICE BUILD SET POINT, opening of the REMOTE CON- TACT inputs from an ice level indicator, or reaching the end of the Ice Build Time Schedule.
ICE BUILD INITIATION — The Ice Build Time Schedule provides the means for activating ice build. The ice build time table is named OCCPC02S.
If the Ice Build TimeSchedule is OCCUPIED and the ICE BUILD OPTION is ENABLED, then ice build is active and the following events automatically take place (unless over­ridden by a higher authority CCN device):
1. Force CHILLER START/STOP to START.
2. Force WA TER/BRINECONTROL POINT to the ICE BUILD
SET POINT.
3. Remove any force (Auto) on the ACTIVE DEMAND LIMIT. NOTE: Items 1-3 (shown above) shall not occur if the chiller
is configured and operating as a lag or standby chiller for lead/lag and is actively controlled by a lead chiller. The lead chiller communicates the ICE BUILD SET POINT, desired CHILLER START/STOPstate, and ACTIVE DEMAND LIMIT to the lag or standby chiller as required for ice build, if con­figured to do so.
36
Page 37
START-UP/RECYCLE OPERATION — If the chiller is not running when ice build activates, then the PIC checks the following parameters, based on the ICE BUILD TERMINA- TION value, to avoid starting the compressor unnecessarily:
•ifICE BUILD TERMINATION is set to the temperature only option (zero) and the ENTERING CHILLED WATER temperature is less than or equal to the ICE BUILD SET
POINT;
•ifICE BUILD TERMINATION is set to the contacts only option (1) and the remote contacts are open;
• if the ICE BUILD TERMINATION is set to the both tem­perature and contacts option (2) andENTERING CHILLED
WATERtemperature is less than or equal to theICE BUILD SET POINT and remote contacts are open.
The ICE BUILD RECYCLE OPTION determines whether or not the PIC will go into a RECYCLE mode. If the ICE BUILD RECYCLE OPTION is set to DSABLE (disable) when the ice build terminates, the PIC will revert back to normal temperature control duty. If the ICE BUILD RECYCLE OPTION is set to ENABLE, when ice build terminates, the PIC will go into an ICE BUILD RECYCLE mode and the chilled water pump relay will remain energized to keep the chilled water flowing. If the entering CHILLED WATER/
BRINE TEMPERATUREincreases above the ICE BUILD SET POINT plus the RECYCLE RESTART DELTA T value, the compressor will restart and control the CHILLED WATER/ BRINE TEMPERATURE to the ICE BUILD SET POINT.
TEMPERATURE CONTROL DURING ICE BUILD —During ice build, the capacity control algorithm uses the WATER/BRINECONTROL POINT minus 5 F (2.7 C) to con­trol the LEAVING CHILLED WATER temperature. The ECW OPTION and any temperature reset option are ignored dur­ing ice build. The 20 mA DEMAND LIMIT OPTION is also ignored during ice build.
TERMINATION OF ICE BUILD — Ice build termination occurs under the following conditions:
1. Ice Build Time Schedule — When the Ice Build Time
Schedule transitions to UNOCCUPIED, ice build opera­tion shall terminate.
2. ECW TEMPERATURE — Termination of compressor
operation, based on temperature, shall occur if the ICE BUILD TERMINATION is set to the ice build termination temperature option (0) and the ENTERING
CHILLED WATER TEMPERATURE is less than the ICE BUILD SET POINT.IftheICE BUILD RECYCLE
OPTION is set to ENABLE and recycle start-up shall be based on LEAVINGCHILLED
WATER temperature being greater than the WATER/ BRINE CONTROL POINT plus RECYCLE RESTART DELTA T.
3. Remote Contacts/Ice Level Input — Termination of
compressor operation occurs when ICE BUILD TERMI- NATION is set to the contacts only option (1) and the remote contacts are open. In this case, the contacts are provided for ice level termination control. The remote con­tacts can still be opened and closed to start and stop the chiller when the Ice Build Time Schedule is UNOCCU­PIED. The contacts are used to stop the ICE BUILD mode when the Ice Build Time Schedule is OCCUPIED.
4. ECW TEMPERATURE and Remote Contacts — Termi-
nation of compressor operation shall occur when ICE BUILD TERMINATIONis set to both the temperature and contacts (2) option and the previously described condi­tions for ENTERING CHILLED WATER temperature and remote contacts have occurred.
, a recycle shutdown occurs
NOTE: Overriding the CHILLER START/STOP, WATER/ BRINE CONTROL POINT, and ACTIVE DEMAND LIMIT variables by CCN devices (with a priority less than 4) during the ice build period is not possible. However, over­riding can be accomplished with CCN during two chiller lead/ lag.
RETURN TO NON-ICE BUILD OPERATIONS — Upon termination of ice build, the chiller shall return to normal temperature control and start/stop schedule operation. If the CHILLER START/STOP or WATER/BRINE CONTROL POINT has been forced (with a priority less than 4), prior to entering ice build operation, then chiller START/STOP and WATER/BRINE CONTROL POINT forces will be removed.
Attach to Network Device Control — On the Serv-
ice menu, one of the selections is ATTACH TO NETWORK DEVICE. This table serves the following purposes:
• to upload new parameters when switching the controller to HFC-134a refrigerant.
• to upload the Occupancy Schedule Number (if changed) for OCCPC03S software (version 09 and later), as defined in the Service01 table
• to attach the LID to any CCN device, if the chiller has been connected to a CCN Network. This may include other PIC controlled chillers.
• to change to a new PSIO or LID module or upgrade software.
Figure 22 illustrates the ATTACH TO NETWORK DEVICE table. The Local description is always the PSIO module address of the chiller the LID is mounted on. When­ever the controller identification of the PSIO is changed, this change is reflected on the bus and address for the LOCAL DEVICE of the ATTACH TO DEVICE screen automat­ically. See Fig. 17.
Whenever the ATTACH TO NETWORK DEVICE table is entered, no information can be read from the LID on any device until you attach one of the devices listed on the display.The LID erases information about the module to which it was attached to make room for information on another de­vice. Therefore, a CCN module must be attached when this screen is entered. To attach a device, highlight it using the
SELECT
message, ‘‘UPLOADING TABLES, PLEASE WAIT’’ dis­plays. The LID then uploads the highlighted device or module. If the module address cannot be found, the mes­sage, ‘‘COMMUNICATION FAILURE’’appears. The LID then reverts to the ATTACH TO DEVICE screen. Try another device or check the address of the device that would not attach. The upload process time for each CCN module is different. In general, the uploading process takes 3 to 5 minutes. Before leaving the ATTACH TO NET­WORK DEVICE screen, select the LOCAL device. Other­wise, the LID will be unable to display information on the local chiller.
CHANGING REFRIGERANT TYPES — To select refrig­erant type, go to the Control Test table. Whenever the refrigerant type is changed, the ATTACH TO NETWORK DEVICE table must be used. After changing the refrigerant type in the Control Testtable, move to theATTACH TO NET­WORK DEVICE table. Make sure the highlight bar is
located on the LOCAL selection. Press the ATTACH key. The information in the PSIO module will now be up-
loaded. The default screen will appear. The new refrigerant type change for the controller is complete.
softkey and then press the ATTACH softkey .The
soft-
37
Page 38
ATTACHINGTO OTHER CCN MODULES — If the chiller PSIO has been connected to a CCN Network or other PIC controlled chillers through CCN wiring, the LID can be used to view or change parameters on the other controllers. Other PIC chillers can be viewed and set points changed (if the other unit is in CCN control), if desired from this particular LID module.
To view the other devices, move to the ATTACH TO
NETWORK DEVICE table. Move the highlight bar to any device number. Press the SELECT softkey to change the bus number and address of the module to be viewed. Press
EXIT softkey to move back to the ATTACH TO NET­WORK DEVICE table. If the module number is not valid, the ‘‘COMMUNICATION FAILURE’’ message will show and a new address number should be entered or the wiring checked. If the model is communicating properly, the ‘‘UP­LOAD IN PROGRESS’’messagewill flash and the new mod­ule can now be viewed.
Whenever there is a question regarding which module on the LID is currently being shown, check the device name descriptor on the upper left hand corner of the LID screen. See Fig. 22.
When the CCN device has been viewed, the ATTACH TO NETWORK DEVICE table should now be used to attach to the PIC that is on the chiller. Move to the ATTACH TO NETWORK DEVICE table and press the
ATTACH
for the 19XL will now be uploaded. NOTE: The LID will not automatically reattach to the PSIO
module on the chiller. Press the ATTACH to LOCAL DEVICE and view the chiller PSIO.
softkey to upload the LOCAL device. The PSIO
softkey to attach
If the password is entered incorrectly,an error message is displayed. If this occurs, return to Step 1 and try logging on again.
NOTE: The initial factory set password is 1-1-1-1. TO LOG OFF — Access the Log Out of Device table of the
Service menu in order to password-protect the Service menu. The LID will automatically sign off and password-protect itself if a key is not pressed for 15 minutes. The LID default screen is then displayed.
HOLIDAY SCHEDULING (Fig. 23) — The time schedules may be configured for special operation during a holiday period. When modifying a time period, the ‘‘H’’ at the end of the days of the week field signifies that the period is ap­plicable to a holiday. (See Fig. 18.)
The Broadcast function must be activated for the holidays configured in the Holidef tables to work properly. Access the Brodefs table in the Equipment Configuration table and answer ‘‘Yes’’ to the activated function. However, when the chiller is connected to a CCN Network, only one chiller or CCN device can be configured to be the broadcast device. The controller that is configured to be the broadcaster is the device responsible for transmitting holiday,time, and daylight­savings dates throughout the network.
To view or change the holiday periods for up to 18 dif­ferent holidays, perform the following operation:
1. At the Menu screen, press SERVICE ice menu.
to access the Serv-
Fig. 22 — Example of Attach to Network
Device Screen
Service Operation — An overview of the menu-
driven programs available for Service Operation is shown in Fig. 17.
TO LOG ON
1. On the Menu screen, press SERVICE correspond to the numerals 1, 2, 3, 4.
2. Press the four digits of your password, one at a time. An asterisk (*) appears as you enter each digit.
The menu bar (Next-Previous-Select-Exit) is displayed to indicate that you have successfully logged on.
. The keys now
2. If not logged on, follow the instructions for To Log On or To Log Off. Once logged on, press NEXT til Equipment Configuration is highlighted.
3. Once Equipment Configuration is highlighted, press
SELECT
4. Press NEXT until Holidef is highlighted. This is the Holiday Definition table.
5. Press SELECT to enter the Data Table Select screen. This screen lists 18 holiday tables.
to access.
un-
38
Page 39
6. Press NEXT to highlight the holiday table that you wish to view or change. Each table is one holiday pe-
riod, starting on a specific date, and lasting up to 99 days.
7. Press SELECT to access the holiday table. The Con­figuration Select table now shows the holiday start month
and day,and how many days the holiday period will last.
8. Press NEXT or PREVIOUS to highlight the month, day, or duration.
9. Press SELECT to modify the month, day, or duration.
START-UP/SHUTDOWN/RECYCLE
SEQUENCE (Fig. 24)
Local Start-Up —
is initiated by pressing the LOCAL on the default LID screen. Local start-up can proceed when
Time Schedule 01 is in OCCUPIED mode, and after the in­ternal 15-minute start-to-start and the 3-minute stop-to-start inhibit timers have expired (on PSIO software Version 08 and lower or a 1-minute stop-to-start timer on PSIO Soft­ware Version 09 and higher).
The chiller start/stop status point on the Status01 table may be overridden to start, regardless of the time schedule, in order to locally start the unit. Also, the remote contacts may be enabled through the LID and closed to initiate a start-up.
Whenever the chiller is in LOCAL control mode, the PIC will wait for Time Schedule 01 to become occupied and the remote contacts to close, if enabled. The PIC will then per­form a series of pre-start checks to verify that all pre-start alerts and safeties are within the limits shown in Table 3. The run status line on the LID now reads ‘‘Starting.’’ If the checks are successful, the chilled water/brine pump relay will be energized. Five seconds later, the condenser pump relay is energized. Thirty seconds later the PIC monitors the chilled water and condenser water flow switches, and waits until the WATER FLOW VERIFY TIME (operator configured, default 5 minutes) to confirm flow.After flow is verified, the chilled water/brine temperature is compared to CONTROL POINT plus DEADBAND. If the temperature is less than or equal to this value, the PIC will turn off the condenser pump relay
Local start-up (or a manual start-up)
menu softkey which is
10. Press INCREASE or DECREASE to change the se­lected value.
11. Press ENTER to save the changes.
12. Press EXIT to return to the previous menu.
Fig. 23 — Example of Holiday Period Screen
A—START INITIATED — Prestart checks made; evaporator B—Condenser water pump started (5 seconds after A)
C—Water flows verified (30 seconds to 5 minutes maximum
D—Oil pressure verified (30 seconds minimum, 300 seconds E—Compressor motor starts, compressor ontime and serv-
F—SHUTDOWNINITIATED— Compressor motor stops, com-
G—Oil pump and evaporator pumps deenergized (60 seconds
O/A — Restart permitted (both inhibit timers expired) (minimum of
pump started
after B). Chilled water temperatures checked against con­trolpoint. Guidevanes checkedfor closure.Oil pumpstarted; tower fan control enabled.
maximum after C) ice ontime start, 15-minute inhibit timer starts (10 seconds
after D), total compressor starts advances by one, number of starts over a 12-hour period advances by one
pressor ontime and service ontime stops, 3-minute inhibit timer starts on PSIO Software Version 08 and lower and 1-minute inhibit timer starts for PSIO Software Version 09 and higher.
after F). Condenser pump and tower fan control may con­tinue to operate if condenser pressure is high. Evaporator pump may continue if in RECYCLE mode.
15 minutes after E; [minimum of 3 minutes after F on PSIO Software Version 08 and lower] [minimum of 1 minute after F on PSIO Software Version 09 and higher]
Fig. 24 — Control Sequence
39
Page 40
and go into a RECYCLE mode. If the water/brine tempera­ture is high enough, the start-up sequence continues on to check the guide vane position. If the guide vanes are more than 6% open, the start-up waits until the PIC closes the vanes. If the vanes are closed, and the oil pump pressure is less than 3 psid (21 kPad), the oil pump relay will then be en­ergized. The PIC then waits until the OIL PRESS (Pressure) VERIFY TIME (operator configured, default 15 seconds) for oil pressure to reach 18 psid (124 kPad). After oil pressure is verified, the PIC waits 15 seconds, and then the compres­sor start relay (1CR) is energized to start the compressor. Compressor ontime and service ontime timers start and the compressor starts counter and the number of starts over a 12-hour period counter are advanced by one.
Failure to verify any of the requirements up to this point will result in the PIC aborting the start and displaying the applicable pre-start mode of failure on the LID default screen. A pre-start failure does not advance the starts in 12 hours counter. Any failure, after the 1CR relay has energized, re­sults in a safety shutdown, energizes the alarm light, and dis­plays the applicable shutdown status on the LID display.
Shutdown Sequence — Shutdown of the chiller can
occur if any of the following events happen:
• the STOP button is pressed for at least one second (the
alarm light will blink once to confirm stop command)
• recycle condition is present (see Chilled WaterRecycle Mode
section)
• time schedule has gone into UNOCCUPIED mode (chiller
protective limit has been reached and chiller is in alarm)
• the start/stop status is overridden to stop from the CCN
network or the LID
When a stop signal occurs, the shutdown sequence first stops the compressor by deactivating the start relay. A status message of ‘‘SHUTDOWN IN PROGRESS, COMPRES­SOR DEENERGIZED’’isdisplayed. Compressor ontime and service ontime stop. The guide vanes are then brought to the closed position. The oil pump relay and the chilled water/ brine pump relay are shut down 60 seconds after the com­pressor stops. The condenser water pump will be shut down when the CONDENSER REFRIGERANT TEMP is less than the CONDENSER PRESSURE OVERRIDE minus 5 psi (34 kPa) or is less than or equal to the ENTERING CONDENSER WATER TEMP plus 3° F (2° C). The stop­to-start timer will now begin to count down. If the start-to­start timer is still greater than the value of the start-to-stop timer, then this time is now displayed on the LID.
Certain conditions during shutdown will change this sequence:
• if the COMPRESSOR MOTOR LOAD is greater than 10%
after shutdown, or the starter contacts remain energized, the oil pump and chilled water pump remain energized and the alarm is displayed
• if the ENTERING CONDENSER WATER temperature is
greater than 115 F (46 C) at shutdown, the condenser pump will be deenergized after the 1CR compressor start relay
• if the chiller shuts down due to low refrigerant tempera-
ture, the chilled water pump will stay running until the
LEAVING CHILLED WATER is greater than CONTROL POINT, plus 5° F (3° C)
AutomaticSoft StopAmps Threshold (PSIO Soft­ware Version 09 and Higher) —
AMPS THRESHOLD closes the guide vanes of the com­pressor automatically when a non-recycle, non-alarm stop signal occurs before the compressor motor is deenergized.
The SOFT STOP
If the STOP button is pressed, the guide vanes close to a preset amperage percent or until the guide vane is less than 2% open. The compressor will then shut off.
If the chiller enters an alarm state or if the compressor enters a RECYCLE mode, the compressor will be de­energized immediately.
To activate SOFT STOP AMPS THRESHOLD, view the bottom of Service1 table. Set the SOFT STOP AMPS THRESHOLD value to the percentage amps at which the motor will shut down. The default setting is 100% amps (no Soft Stop).
When the SOFT STOP AMPS THRESHOLD is being applied, a status message ‘‘SHUTDOWN IN PROGRESS, COMPRESSOR UNLOADING’’ is shown.
ChilledWaterRecycle Mode— The chiller may cycle
off and wait until the load increases to restart again when the compressor is running in a lightly loaded condition. This cycling of the chiller is normal and is known as recycle. A recycle shutdown is initiated when any of the following con­ditions are true:
• when in LCW control, the difference between the LEAV-
ING CHILLED WATER temperature and ENTERING CHILLED WATER temperature is less than the RECYCLE SHUTDOWN DELTA T (found in the Service1 table) and the LEAVING CHILLED WATER TEMP is below the CONTROL POINT, and the CONTROL POINT has not
increased in the last 5 minutes.
• when ECW CONTROL OPTION is enabled, the difference
between the ENTERING CHILLED WATER temperature and the LEAVING CHILLED WATER temperature is less than the RECYCLE SHUTDOWN DELTA T (found in the Service1 table) and the ENTERING CHILLED WATER
TEMPERATURE is below the CONTROL POINT, and the CONTROL POINT has not increased in the last 5 minutes.
• when the LEAVINGCHILLED WATERtemperatureis within
3° F (2° C) of the BRINE REFRIG TRIPPOINT
When the chiller is in RECYCLE mode, the chilled water pump relay remains energized so that the chilled water tem­perature can be monitored for increasing load. The recycle control uses RECYCLE RESTART DELTA T to check when the compressor should be restarted. This is an operator­configured function which defaults to 5° F (3° C). This value is viewed/modified on the Service1 table. The compressor will restart when:
• in LCW CONTROL the LEAVINGCHILLED WATERtem-
perature is greater than the CONTROL POINT plus the RECYCLE RESTART DELTA T; or
• in ECW CONTROL, the ENTERING CHILLED WATER
temperature is greater than the CONTROL POINT plus the
RECYCLE RESTART DELTA T
Once these conditions are met, the compressor will ini­tiate a start-up, with a normal start-up sequence.
An alert condition may be generated if 5 or more RECYCLE STARTUPs occur in less than 4 hours. This excessive recycling can reduce chiller life. Compressor re­cycling due to extremely low loads should be reduced. To reduce compressor recycling, use the time schedule to shut the chiller down during low load operation or increase the chiller load by running the fan systems. If the hot gas bypass is installed, adjust the values to ensure that hot gas is ener­gized during light load conditions. Increase the RECYCLE RESTART DELTA T on the Service1 table to lengthen the time between restarts.
The chiller should not be operated below design mini­mum load without a hot gas bypass installed on the chiller.
40
Page 41
Safety Shutdown — A safety shutdown is identical to
a manual shutdown with the exception that the LID will dis­play the reason for the shutdown, the alarm light will blink continuously, and the spare alarm contacts will be ener-
gized. A safety shutdown requires that the RESET be pressed in order to clear the alarm. If the alarm is still
present, the alarm light will continue to blink. Once the alarm is cleared, the operator must press the CCN
LOCAL
Do not reset starter loads or any other starter safety for 30 seconds after the compressor has stopped. Voltage output to the compressor start signal is maintained for 10 seconds to determine starter fault.
softkeys to restart the chiller.
softkey
or
BEFORE INITIAL START-UP
Job Data Required
• list of applicable design temperatures and pressures (pro­duct data submittal)
• chiller certified prints
• starting equipment details and wiring diagrams
• diagrams and instructions for special controls or options
• 19XL Installation Instructions
• pumpout unit instructions
Equipment Required
• mechanic’s tools (refrigeration)
• digital volt-ohmmeter (DVM)
• clamp-on ammeter
• electronic leak detector
• absolute pressure manometer or wet-bulb vacuum indica­tor (Fig. 25)
• 500 v insulation tester (megohmmeter) for compressor motors with nameplate voltage of 600 v or less, or a 5000-v insulation tester for compressor motor rated above 600 v
Using the Optional Storage Tankand Pumpout System —
Procedures section, page 59 for: pumpout system prepara­tion, refrigerant transfer, and chiller evacuation.
Refer to Pumpout and Refrigerant Transfer
Remove Shipping Packaging — Remove any
packaging material from the control center, power panel, guide vane actuator, motor cooling and oil reclaim solenoids, motor and bearing temperature sensor covers, and the factory­mounted starter.
Open Oil Circuit Valves — Check that the oil filter
isolation valves (Fig. 4) are open by removing the valve cap and checking the valve stem.
Tighten All Gasketed Joints and Guide Vane Shaft Packing —
by the time the chiller arrives at the jobsite. Tighten all gasketed joints and guide vane shaft packing to ensure a leak­tight chiller.
Gaskets and packing normally relax
Check Chiller Tightness — Figure 26 outlines the
proper sequence and procedures for leak testing.
19XL chillers are shipped with the refrigerant contained in the condenser shell and the oil charge shipped in the compressor. The cooler will have a 15 psig (103 kPa) refrigerant charge. Units may be ordered with the refrigerant shipped separately, along with a 15 psig (103 kPa) nitrogen­holding charge in each vessel. To determine if there are any leaks, the chiller should be charged with refrigerant. Use an electronic leak detector to check all flanges and solder joints after the chiller is pressurized. If any leaks are detected, fol­low the leak test procedure.
If the chiller is spring isolated, keep all springs blocked in both directions in order to prevent possible piping stress and damage during the transfer of refrigerant from vessel to vessel during the leak test process, or any time refrigerant is transferred. Adjust the springs when the refrigerant is in operating condition, and when the water circuits are full.
Refrigerant Tracer — Carrier recommends the use of
an environmentally acceptable refrigerant tracer for leak test­ing with an electronic detector or halide torch.
Ultrasonic leak detectors also can be used if the chiller is under pressure.
Fig. 25 — Typical Wet-Bulb Type
Vacuum Indicator
Do not use air or oxygen as a means of pressurizing the chiller. Some mixtures of HCFC-22 or HFC-134a and air can undergo combustion.
Leak Test Chiller — Due to regulations regarding
refrigerant emissions and the difficultiesassociated with sepa­rating contaminants from refrigerant, Carrier recommends the following leak test procedures. See Fig. 26 for an outline of the leak test procedures. Refer to Fig. 27 and 28 during pumpout procedures and Tables 5A, B, C, and D for refrig­erant pressure/temperature values.
1. If the pressure readings are normal for chiller
condition: a. Evacuate the holding charge from the vessels, if present. b. Raise the chiller pressure, if necessary, by adding re-
frigerant until pressure is at equivalent saturated pres­sure for the surrounding temperature. Follow the pumpout
41
Page 42
42
Fig. 26 — 19XL Leak Test Procedures
Page 43
procedures in the Transfer Refrigerant from Storage Tank to Chiller section, Steps 1a-e, page 59.
Never charge liquid refrigerant into the chiller if the pressure in the chiller is less than 68 psig (469 kPa) for HCFC-22 and 35 psig (241 kPa) for HFC-134a. Charge as a gas only, with the cooler and condenser pumps running, until this pressure is reached, using PUMPDOWN LOCKOUT and TERMINATE LOCKOUT mode on the PIC. Flash­ing of liquid refrigerant at low pressures can cause tube freezeup and considerable damage.
c. Leak test chiller as outlined in Steps 3-9.
2. If the pressure readings are abnormal for chiller condition:
a. Prepare to leak test chillers shipped with refrigerant
(Step 2h).
b. Check for large leaks by connecting a nitrogen bottle
and raising the pressure to 30 psig (207 kPa). Soap test all joints. If the test pressure holds for 30 minutes,
prepare the test for small leaks (Steps 2g-h). c. Plainly mark any leaks which are found. d. Release the pressure in the system. e. Repair all leaks. f. Retest the joints that were repaired. g. After successfully completing the test for large leaks,
remove as much nitrogen, air, and moisture as pos-
sible, given the fact that small leaks may be present in
the system. This can be accomplished by following
the dehydration procedure, outlined in the Chiller
Dehydration section, page 47. h. Slowly raise the system pressure to a maximum of
210 psig (1448 kPa) but no less than 68 psig (469 kPa)
for HCFC-22, 35 psig (241 kPa) for HFC-134a by add-
ing refrigerant. Proceed with the test for small leaks
(Steps 3-9).
3. Check the chiller carefully with an electronic leak detec­tor, halide torch, or soap bubble solution.
4. Leak Determination — If an electronic leak detector indicates a leak, use a soap bubble solution, if possible, to confirm. Total all leak rates for the entire chiller. Leak­age at rates greater than 1 lb/year (0.45 kg/year) for the entire chiller must be repaired. Note total chiller leak rate on the start-up report.
5. If no leak is found during initial start-up procedures, com­plete the transfer of refrigerant gas from the storage tank to the chiller (see Pumpout and Refrigerant Transfer Pro­cedures, Transfer Refrigerant from Storage Tank to Chiller section, Step 1e, page 59). Retest.
6. If no leak is found after a retest: a. Transfer the refrigerant to the storage tank and
perform a standing vacuum test as outlined in the Standing Vacuum Test section, this page.
b. If the chiller fails this test, check for large leaks
(Step 2b).
c. Dehydrate the chiller if it passes the standing vacuum
test. Follow the procedure in the Chiller Dehydration section. Charge chiller with refrigerant (see Pumpout and Refrigerant Transfer Procedures, Transfer Refrig­erant from Storage Tank to Chiller section, Steps 1a-e or page 59).
7. If a leak is found, pump the refrigerant back into the stor­age tank, or if isolation valves are present, pump into the non-leaking vessel (see Pumpout and Refrigerant Trans­fer procedures section).
8. Transfer the refrigerant until chiller pressure is at 18 in. Hg (40 kPa absolute).
9. Repair the leak and repeat the procedure, beginning from Step 2h to ensure a leaktight repair. (If chiller is opened to the atmosphere for an extended period, evacuate it be­fore repeating leak test.)
StandingVacuumTest— When performing the stand-
ing vacuum test, or chiller dehydration, use a manometer or a wet bulb indicator. Dial gages cannot indicate the small amount of acceptable leakage during a short period of time.
1. Attach an absolute pressure manometer or wet bulb in­dicator to the chiller.
2. Evacuate the vessel (see Pumpout and Refrigerant Trans­fer Procedures section, page 59) to at least 18 in. Hg vac, ref 30-in. bar (41 kPa), using a vacuum pump or the pumpout unit.
3. Valve off the pump to hold the vacuum and record the manometer or indicator reading.
4. a. If the leakage rate is less than 0.05 in. Hg (.17 kPa) in
24 hours, the chiller is sufficiently tight.
b. If the leakage rate exceeds 0.05 in. Hg (.17 kPa) in
24 hours, repressurize the vessel and test for leaks. If refrigerant is available in the other vessel, pressurize by following Steps 2-10 of Return Refrigerant To Normal Operating Conditions section, page 61. If not, use nitrogen and a refrigerant tracer. Raise the vessel pressure in increments until the leak is detected. If refrigerant is used, the maximum gas pressure is approximately 120 psig (827 kPa) for HCFC-22, 70 psig (483 kPa) for HFC-134a at normal ambient temperature. If nitrogen is used, limit the leak test pres­sure to 230 psig (1585 kPa) maximum.
5. Repair leak, retest, and proceed with dehydration.
43
Page 44
TEMPERATURE
(F)
−50 11.67 6.154*
−48 12.34 4.829*
−46 13.00 3.445*
−44 13.71 2.002*
−42 14.45 0.498*
−40 15.22 0.526
−38 16.02 1.328
−36 16.86 2.163
−34 17.73 3.032
−32 18.63 3.937
−30 19.57 4.877
−28 20.55 5.853
−26 21.56 6.868
−24 22.62 7.921
−22 23.71 9.015
−20 24.85 10.15
−18 26.02 11.32
−16 27.24 12.54
−14 28.50 13.81
−12 29.81 15.11
−10 31.16 16.47
−8 32.56 17.87
−6 34.01 19.32
−4 35.51 20.81
−2 37.06 22.36 0 38.66 23.96
2 40.31 25.61 4 42.01 27.32 6 43.78 29.08 8 45.59 30.90
10 47.46 32.77 12 49.40 34.70 14 51.39 36.69 16 53.44 38.74 18 55.55 40.86
20 57.73 43.03 22 59.97 45.27 24 62.27 47.58 26 64.64 49.95 28 67.08 52.39
PRESSURE (psi)
Absolute Gage
Table 5A — HCFC-22 Pressure — Temperature (F)
TEMPERATURE
(F)
30 69.59 54.90 32 72.17 57.47 34 74.82 60.12 36 77.54 62.84 38 80.34 65.64
40 83.21 68.51 42 86.15 71.46 44 89.18 74.48 46 92.28 77.58 48 95.46 80.77
50 98.73 84.03 52 102.07 87.38 54 105.50 90.81 56 109.02 94.32 58 112.62 97.93
60 116.31 101.62 62 120.09 105.39 64 123.96 109.26 66 127.92 113.22 68 131.97 117.28
70 136.12 121.43 72 140.37 125.67 74 144.71 130.01 76 149.15 134.45 78 153.69 138.99
80 158.33 143.63 82 163.07 148.37 84 167.92 153.22 86 172.87 158.17 88 177.93 163.23
90 183.09 168.40 92 188.37 173.67 94 193.76 179.06 96 199.26 184.56 98 204.87 190.18
100 210.60 195.91 102 216.45 201.76 104 222.42 207.72 106 228.50 213.81 108 234.71 220.02
PRESSURE (psi)
Absolute Gage
TEMPERATURE
*Inches of mercury below one atmosphere.
(F)
110 241.04 226.35 112 247.50 232.80 114 254.08 239.38 116 260.79 246.10 118 267.63 252.94
120 274.60 259.91 122 281.71 267.01 124 288.95 274.25 126 296.33 281.63 128 303.84 289.14
130 311.50 296.80 132 319.29 304.60 134 327.23 312.54 136 335.32 320.63 138 343.56 328.86
140 351.94 337.25 142 360.48 345.79 144 369.17 354.48 146 378.02 363.32 148 387.03 372.33 150 396.19 381.50 152 405.52 390.83 154 415.02 400.32 156 424.68 409.99 158 434.52 419.82 160 444.53 420.83
PRESSURE (psi)
Absolute Gage
TEMPERATURE
(C)
−18 264 163
−17 274 173
−16 284 183
−15 296 195
−14 307 206
−13 318 217
−12 330 229
−11 342 241
−10 354 253
−9 367 266
−8 380 279
−7 393 292
−6 407 306
−5 421 320
−4 436 335
−3 451 350
−2 466 365
−1 482 381 0 498 397
1 514 413 2 531 430 3 548 447 4 566 465 5 584 483
6 602 501 7 621 520 8 641 540 9 660 559
10 681 580 11 701 600
PRESSURE (kPa)
Absolute Gage
Table 5B — HCFC-22 Pressure — Temperature (C)
TEMPERATURE
(C)
12 723 622 13 744 643 14 766 665 15 789 688
16 812 711 17 836 735 18 860 759 19 885 784 20 910 809
21 936 835 22 962 861 23 989 888 24 1020 919 25 1040 939
26 1070 969 27 1100 1000 28 1130 1030 29 1160 1060 30 1190 1090
31 1220 1120 32 1260 1160 33 1290 1190 34 1320 1220 35 1360 1260
36 1390 1290 37 1420 1320 38 1460 1360 39 1500 1400 40 1530 1430 41 1570 1470
PRESSURE (kPa)
Absolute Gage
TEMPERATURE
(C)
42 1610 1510 43 1650 1550 44 1690 1590 45 1730 1630
46 1770 1670 47 1810 1710 48 1850 1750 49 1900 1800 50 1940 1840
51 1980 1890 52 2030 1930 53 2080 1980 54 2130 2030 55 2170 2070
56 2220 2120 57 2270 2170 58 2320 2220 59 2370 2270 60 2430 2330
61 2480 2380 62 2530 2430 63 2590 2490 64 2640 2540 65 2700 2600
66 2760 2660 67 2820 2720 68 2870 2770 69 2930 2830 70 3000 2900
PRESSURE (kPa)
Absolute Gage
44
Page 45
TEMPERATURE
(F)
0 6.50 2 7.52 4 8.60 6 9.66 8 10.79
10 11.96 12 13.17 14 14.42 16 15.72 18 17.06
20 18.45 22 19.88 24 21.37 26 22.90 28 24.48
30 26.11 32 27.80 34 29.53 36 31.32 38 33.17
40 35.08 42 37.04 44 39.06 46 41.14 48 43.28
50 45.48 52 47.74 54 50.07 56 52.47 58 54.93
Table 5C — HFC-134a Pressure — Temperature (F)
PRESSURE
(psig)
TEMPERATURE
(F)
60 57.46 62 60.06 64 62.73 66 65.47 68 68.29
70 71.18 72 74.14 74 77.18 76 80.30 78 83.49
80 86.17 82 90.13 84 93.57 86 97.09 88 100.70
90 104.40 92 108.18 94 112.06 96 116.02 98 120.08
100 124.23 102 128.47 104 132.81 106 137.25 108 141.79
110 146.43 112 151.17 114 156.01 116 160.96 118 166.01
PRESSURE
(psig)
TEMPERATURE
(F)
120 171.17 122 176.45 124 181.83 126 187.32 128 192.93
130 198.66 132 204.50 134 210.47 136 216.55 138 222.76 140 229.09
PRESSURE
(psig)
TEMPERATURE
(C)
−18.0 44.8
−16.7 51.9
−15.6 59.3
−14.4 66.6
−13.3 74.4
−12.2 82.5
−11.1 90.8
−10.0 99.4
−8.9 108.0
−7.8 118.0
−6.7 127.0
−5.6 137.0
−4.4 147.0
−3.3 158.0
−2.2 169.0
−1.1 180.0
0.0 192.0
1.1 204.0
2.2 216.0
3.3 229.0
4.4 242.0
5.0 248.0
5.6 255.0
6.1 261.0
6.7 269.0
7.2 276.0
7.8 284.0
8.3 290.0
8.9 298.0
9.4 305.0
Table 5D — HFC-134a Pressure — Temperature (C)
PRESSURE GAGE (kPa)
TEMPERATURE
(C)
10.0 314.0
11.1 329.0
12.2 345.0
13.3 362.0
14.4 379.0
15.6 396.0
16.7 414.0
17.8 433.0
18.9 451.0
20.0 471.0
21.1 491.0
22.2 511.0
23.3 532.0
24.4 554.0
25.6 576.0
26.7 598.0
27.8 621.0
28.9 645.0
30.0 669.0
31.1 694.0
32.2 720.0
33.3 746.0
34.4 773.0
35.6 800.0
36.7 828.0
37.8 857.0
38.9 886.0
40.0 916.0
41.1 946.0
42.2 978.0
PRESSURE
GAGE (kPa)
TEMPERATURE
(C)
43.3 1010.0
44.4 1042.0
45.6 1076.0
46.7 1110.0
47.8 1145.0
48.9 1180.0
50.0 1217.0
51.1 1254.0
52.2 1292.0
53.3 1330.0
54.4 1370.0
55.6 1410.0
56.7 1451.0
57.8 1493.0
58.9 1536.0
60.0 1580.0
PRESSURE
GAGE (kPa)
45
Page 46
Fig. 27 — Typical Optional Pumpout System Piping Schematic
with Storage Tank
Fig. 28 — Typical Optional Pumpout System Piping Schematic
without Storage Tank
46
Page 47
Chiller Dehydration — Dehydration is recommended
if the chiller has been open for a considerable period of time, if the chiller is known to contain moisture, or if there has been a complete loss of chiller holding charge or refrigerant pressure.
Do not start or megohm test the compressor motor or oil pump motor, even for a rotation check, if the chiller is under dehydration vacuum. Insulation breakdown and severe damage may result.
InspectWaterPiping — Refer to piping diagrams pro-
vided in the certified drawings, and the piping instructions in the 19XL Installation Instructions manual. Inspect the piping to the cooler and condenser. Be sure that flow direc­tions are correct and that all piping specifications have been met.
Piping systems must be properly vented, with no stress on waterbox nozzles and covers. Water flows through the cooler and condenser must meet job requirements. Measure the pres­sure drop across cooler and across condenser.
Dehydration is readily accomplished at room tempera­tures. Use of a cold trap (Fig. 29) may substantially reduce the time required to complete the dehydration. The higher the room temperature, the faster dehydration takes place. At low room temperatures, a very deep vacuum is required for boiling off any moisture. If low ambient temperatures are involved, contact a qualified service representative for the dehydration techniques required.
Perform dehydration as follows:
1. Connect a high capacity vacuum pump (5 cfm
[.002 m charging valve (Fig. 2A or 2B). Tubing from the pump to the chiller should be as short and as large a diameter as possible to provide least resistance to gas flow.
2. Use an absolute pressure manometer or a wet bulb vacuum
indicator to measure the vacuum. Open the shutoff valve to the vacuum indicator only when taking a reading. Leave the valve open for 3 minutes to allow the indicator vacuum to equalize with the chiller vacuum.
3. Open all isolation valves (if present), if the entire chiller
is to be dehydrated.
4. With the chiller ambient temperature at 60 F (15.6 C) or
higher,operate the vacuum pump until the manometer reads
29.8 in. Hg vac, ref 30 in. bar. (0.1 psia) (–100.61 kPa) or a vacuum indicator reads 35 F (1.7 C). Operate the pump an additional 2 hours.
Do not apply greater vacuum than 29.82 in. Hg vac (757.4 mm Hg) or go below 33 F (.56 C) on the wet bulb vacuum indicator. At this temperature/pressure, isolated pockets of moisture can turn into ice. The slow rate of evaporation (sublimination) of ice at these low temperatures/ pressures greatly increases dehydration time.
5. Valve off the vacuum pump, stop the pump, and record
the instrument reading.
6. After a 2-hour wait, take another instrument reading. If
the reading has not changed, dehydration is complete. If the reading indicates vacuum loss, repeat Steps 4 and 5.
7. If the reading continues to change after several attempts,
perform a leak test up to the maximum 230 psig (1585 kPa) pressure. Locate and repair the leak, and re­peat dehydration.
3
/s] or larger is recommended) to the refrigerant
Fig. 29 — Dehydration Cold Trap
Water must be within design limits, clean, and treated to ensure proper chiller performance and reduce the potential of tubing damage due to corrosion, scaling, or erosion. Carrier assumes no responsibility for chiller dam­age resulting from untreated or improperly treated water.
CheckOptional Pumpout Compressor Water Pip­ing —
are installed, check to ensure the pumpout condenser water has been piped in. Check for field-supplied shutoff valves and controls as specified in the job data. Check for refrig­erant leaks on field-installed piping. See Fig. 27 and 28.
If the optional storage tank and/or pumpout system
Check Relief Devices — Be sure that relief devices
have been piped to the outdoors in compliance with the lat­est edition of ANSI/ASHRAE Standard 15 and applicable local safety codes. Piping connections must allow for access to the valve mechanism for periodic inspection and leak testing.
19XL relief valves are set to relieve at the 300 psig
(2068 kPa) chiller design pressure.
Inspect Wiring
Do not check voltage supply without proper equipment and precautions. Serious injury may result. Follow power company recommendations.
Do not apply any kind of test voltage, even for a rota­tion check, if the chiller is under a dehydration vacuum. Insulation breakdown and serious damage may result.
1. Examine wiring for conformance to job wiring dia­grams and to all applicable electrical codes.
2. On low-voltage compressors (600 v or less) connect voltmeter across the power wires to the compressor starter and measure the voltage. Compare this reading with the voltage rating on the compressor and starter nameplates.
3. Compare the ampere rating on the starter nameplate with the compressor nameplate. The overload trip amps must be 108% to 120% of the rated load amps.
4. The starter for a centrifugal compressor motor must con­tain the components and terminals required for PIC refrigeration control. Check certified drawings.
5. Check the voltage to the following components and compare to the nameplate values: oil pump contact, pumpout compressor starter, and power panel.
47
Page 48
6. Be sure that fused disconnects or circuit breakers have been supplied for the oil pump, power panel, and pumpout unit.
7. Check that all electrical equipment and controls are prop­erly grounded in accordance with job drawings, certi­fied drawings, and all applicable electrical codes.
8. Make sure that the customer’s contractor has verified proper operation of the pumps, cooling tower fans, and associated auxiliary equipment. This includes ensuring that motors are properly lubricated and have proper elec­trical supply and proper rotation.
9. For field-installed starters only, test the chiller compres­sor motor and its power lead insulation resistance with a 500-v insulation tester such as a megohmmeter. (Use a 5000-v tester for motors rated over 600 v.) Factory­mounted starters do not require a megohm test.
a. Open the starter main disconnect switch and follow
lockout/tagout rules.
To attach the CCN communication bus wiring, refer to the certified drawings and wiring diagrams. The wire is in­serted into the CCN communications plug (COMM1) on the PSIO module. This plug also is referred to as J5.
NOTE: Conductors and drain wire must be 20 AWG (American Wire Gage) minimum stranded, tinned copper. Individual conductors must be insulated with PVC, PVC/ nylon, vinyl, Teflon,or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl or Teflon with a minimum operating tempera­ture range of –20 C to 60 C is required. See table below for cables that meet the requirements.
MANUFACTURER CABLE NO.
Alpha 2413 or 5463
American A22503
Belden 8772
Columbia 02525
If the motor starter is a solid-state starter, the motor leads must be disconnected from the starter before an insulation test is performed. The voltage generated from the tester can damage the starter solid-state components.
b. With the tester connected to the motor leads, take
10-second and 60-second megohm readings as follows:
6-Lead Motor — Tie all 6 leads together and test be­tween the lead group and ground. Next tie leads in pairs, 1 and 4, 2 and 5, and 3 and 6. Test between each pair while grounding the third pair.
3-Lead Motor — Tie terminals 1, 2, and 3 together and test between the group and ground.
c. Divide the 60-second resistance reading by the
10-second reading. The ratio, or polarization index, must be one or higher. Both the 10- and 60-second readings must be at least 50 megohms.
If the readings on a field-installed starter are unsat­isfactory, repeat the test at the motor with the power leads disconnected. Satisfactory readings in this sec­ond test indicate the fault is in the power leads.
NOTE: Unit-mounted starters do not have to be meg­ohm tested.
10. Tighten up all wiring connections to the plugs on the SMM, 8-input, and PSIO modules.
11. Ensure that the voltage selector switch inside the power panel is switched to the incoming voltage rating.
12. On chillers with free-standing starters, inspect the power panel to ensure that the contractor has fed the wires into the bottom of the panel. Wiring into the top of the panel can cause debris to fall into the contactors. Clean and inspect the contactors if this has occurred.
Carrier Comfort Network Interface — The Carrier
Comfort Network (CCN) communication bus wiring is sup­plied and installed by the electrical contractor. It consists of shielded, 3-conductor cable with drain wire.
The system elements are connected to the communication bus in a daisy chain arrangement. The positive pin of each system element communication connector must be wired to the positive pins of the system element on either side of it; the negative pins must be wired to the negative pins; the sig­nal ground pins must be wired to signal ground pins.
When connecting the CCN communication bus to a sys­tem element, a color code system for the entire network is recommended to simplify installation and checkout. The fol­lowing color code is recommended:
SIGNAL
TYPE
+ RED 1
Ground WHITE 2
BLACK 3
CCN BUS CONDUCTOR
INSULATION COLOR
PSIO MODULE
COMM 1 PLUG (J5)
PIN NO.
Check Starter
BE AWARE that certain automatic start arrangements can engage the starter. Open the disconnect ahead of the starter in addition to shutting offthe chiller or pump.
Use the instruction and service manual supplied by the starter manufacturer to verify that the starter has been in­stalled correctly.
The main disconnect on the starter front panel may not deenergize all internal circuits. Open all internal and re­mote disconnects before servicing the starter.
Whenever a starter safety trip device activates, wait at least 30 seconds before resetting the safety. The microprocessor maintains its output to the 1CR relay for 10 seconds to de­termine the fault mode of failure.
MECHANICAL-TYPE STARTERS
1. Check all field wiring connections for tightness, clear-
ance from moving parts, and correct connection.
2. Check the contactor(s) to be sure they move freely. Check
the mechanical interlock between contactors to ensure that 1S and 2M contactors cannot be closed at the same time. Check all other electro-mechanical devices, e.g., relays, timers, for free movement. If the devices do not move freely, contact the starter manufacturer for replacement components.
48
Page 49
3. Some dashpot-type magnetic overload relays must be filled with oil on the jobsite. If the starter is equipped with de­vices of this type, remove the fluid cups from these mag­netic overload relays. Add dashpot oil to cups per instructions supplied with the starter. The oil is usually shipped in a small container attached to the starter frame near the re­lays. Use only dashpot oil supplied with the starter. Do not substitute.
Factory-filled dashpot overload relays need no oil at start-up and solid-state overload relays do not have oil.
4. Reapply starter control power (not main chiller power)to check electrical functions. When using a reduced-voltage starter (such as a wye-delta type) check the transition timer for proper setting. The factory setting is 30 seconds (± 5 seconds), timed closing. The timer is adjustable in a range between 0 and 60 seconds and settings other than the nominal 30 seconds may be chosen as needed (typi­cally 20 to 30 seconds are used).
When the timer has been set, check that the starter (with relay 1CR closed) goes through a complete and proper start cycle.
BENSHAW, INC. SOLID-STATE STARTER
This equipment is at line voltage when AC power is connected. Pressing the STOP button does not remove voltage. Use caution when adjusting the potentiometers on the equipment.
1. Check that all wiring connections are properly termi­nated to the starter.
2. Verifythat the ground wire to the starter is installed prop­erly and is of sufficient size.
3. Verifythat the motors are properly grounded to the starter.
4. Check that all of the relays are properly seated in their sockets.
5. Verify that the proper ac input voltage is brought into the starter per the certified drawings.
6. Verifythe initial factory settings of the starting torque and ramp potentiometers are set per the note on the schematic for the starters.
NOTE: The potentiometers are located at the lower left hand corner on the circuit board mounted in front of the starter power stack (Fig. 30 and 31).
The starting torque potentiometer should be set so that when the PIC calls for the motor to start, the rotor should just start to turn. The nominal dial position for a 60 Hz motor is approximately the 11:30 position. The nominal dial position for a 50 Hz motor is approximately in the 9:30 position because the board is turned on its side, so that the 9:00 o’clock position is located where the 6:00 o’clock position would normally be located. The ramp potentiometer should be set so that the motor is up to full speed in 15 to 20 seconds, the bypass contactors have energized, and the auxiliary LCD is energized.
7. Proceed to apply power to the starter.
8. The Power +15 and Phase Correct LEDs should be on. If not, see the starter Troubleshooting Guide section.
LEGEND
1—Phase Voltage Indicator 2—Starter Fault and Run LEDs (5)
• Overtemp
• Ground Fault
• Current Unbalance (CUB) While Stopped
• Current Unbalance
• Run (Start Initiated)
3—Starting Torque Potentiometer 4—Ramp Up Potentiometer 5—Phase Correct LED 6—Relay On LED 7—Power +15 and Auxiliary (Starter
in RUN State) LEDs (Hidden)
8—SCR Indicator LEDs (Hidden) 9—Reset Button
Fig. 30 — Benshaw, Inc. Solid-State Starter
Power Stack
NOTE: Adjustments:
Starting torque — 0% to 100% rated motor torque. Ramp time to full motor voltage — 0.5 seconds to 60 seconds.
Fig. 31 — Ramp Up and Starting Torque
Potentiometers
49
Page 50
Oil Charge — The 19XL compressor holds approxi-
mately 8 gal. (30 L) of oil. The chiller will be shipped with oil in the compressor. When the sump is full, the oil level should be no higher than the middle of the upper sight glass and minimum level is the bottom of the lower sight glass (Fig. 2A or 2B). If oil is added, it must meet Carrier’s speci­fication for centrifugal compressor usage as described in the Oil Specification section on page 63. Charge the oil through the oil charging valve, located near the bottom of the trans­mission housing (Fig. 2A or Fig. 2B). The oil must be pumped from the oil container through the charging valve due to higher refrigerant pressure. The pumping device must be able to lift from 0 to 200 psig (0 to 1380 kPa) or above unit pressure. Oil should only be charged or removed when the chiller is shut down.
Power Up the Controls and Check the Oil Heater
Ensure that an oil level is visible in the compressor
before energizing controls. A circuit breaker in the starter energizes the oil heater and the control circuit. When first powered, the LID should display the default screen within a short period of time.
The oil heater is energized by powering the control cir­cuit. This should be done several hours before start-up to minimize oil-refrigerant migration. The oil heater is con­trolled by the PIC and is powered through a contactor in the power panel. Starters contain a separate circuit breaker to power the heater and the control circuit. This set up allows the heater to energize when the main motor circuit breaker is offfor service work or extended shutdowns. The oil heater relay status can be viewed on the Status02 table on the LID. Oil sump temperature can be viewed on the LID default screen.
When the Time/Date is configured for the first time or if power is lost for more than 3 hours, the oil heat algorithm will take effect before the compressor can start. See the Oil Sump Temperature Control section on page 32 for addi­tional information. The oil pump will then energize for 1 to 2 minutes to bring the oil temperature to normal operating temperature. A LOW OIL TEMPERATURE alert will show on the default LID screen if the operator has the controls set to start.
SOFTWARE VERSION — The software version will always be labeled on the PSIO module, and on the back side of the LID module. On both the Controller ID and LID ID display screens, the software version number will also appear.
Set Up Chiller Control Configuration
Do not operate the chiller before the control configu­rations have been checked and a Control Test has been satisfactorily completed. Protection by safety controls cannot be assumed until all control configurations have been confirmed.
As configuration of the 19XL unit is performed, write down all configuration settings. A log, such as the one shown on pages CL-1 to CL-2, provides a convenient list for configu­ration values.
Input the Design Set Points — Access the LID set
point screen and view/modify the base demand limit set point, and either the LCW set point or the ECW set point. The PIC can control a set point to either the leaving or entering chilled water.This control method is set in the Equipment Configu­ration table, Config table.
Inputthe Local OccupiedSchedule (OCCPC01S)
Access the schedule OCCPC01S screen on the LID
and set up the occupied time schedule per the customer’s requirements. If no schedule is available, the default is fac­tory set for 24 hours occupied 7 days per week including holidays.
For more information about how to set up a time sched-
ule, see the Controls section, page 11.
The CCN Occupied Schedule should be configured if a CCN system is being installed or if a secondary time sched­ule is needed.
NOTE: The default CCN Occupied Schedule is OCCPC03S for Software Version 09 and above; the default is OCCPC02S for Software Version 08 and below.
SelectingRefrigerant Type— The 19XL control must
be configured for the refrigerant being used, either HCFC-22 or HFC-134a.
TO CONFIRM REFRIGERANT TYPE — Confirm that the correct refrigerant type is indicated by entering the Controls Test tables on the Service menu, Fig. 17. Select REFRIG­ERANT TYPE. The screen will display the current refrig-
erant setting. Press EXIT out changes.
TO CHANGE REFRIGERANT TYPE — Enter the Con­trols Test tables on the Service Menu. See Fig. 17. Select
REFRIGERANT TYPE. The screen will display the current refrigerant setting. Press YES rent setting. Next, move to the ATTACH TO NETWORK
DEVICE screen on the Service menu and the ATTACH TO LOCAL DEVICE to upload the new refrigerant tables.
softkey to leave the screen with-
softkey to change the cur-
InputService Configurations — The following con-
figurations require the LID screen to be in the Service por­tion of the menu.
• password
• input time and date
• LID configuration
• controller identification
• service parameters
• equipment configuration
• automated control test PASSWORD — When accessing the Service tables, a pass-
word must be entered. All LIDs are initially set for a pass­word of 1-1-1-1. This password may be changed in the LID configuration screen, if desired.
INPUT TIME AND DATE — Access the Time and Date table on the Service menu. Input the present time of day, date, and day of the week. ‘‘Holiday Today’’should only be configured to ‘‘Yes’’ if the present day is a holiday.
CHANGE LID CONFIGURATION IF NECESSARY— The LID Configuration screen is used to view or modify the LID CCN address, change to English or SI units, and to change the password. If there is more than one chiller at the jobsite, change the LID address on each chiller so that each chiller has its own address. Note and record the new address. Change the screen to SI units as required, and change the password if desired.
50
Page 51
MODIFY CONTROLLER IDENTIFICATION IF NECES­SARY—The controller identification screen is used to change the PSIO module address. Change this address for each chiller if there is more than one chiller at the jobsite. Write the new address on the PSIO module for future reference.
Change the LID address if there is more than one chiller on the jobsite. Access the LID configuration screen to view or modify this address.
INPUT EQUIPMENT SERVICE PARAMETERS IF NEC­ESSARY — The Equipment Service table has three service tables: Service1, Service2, and Service3.
Configure SERVICE1 Table — Access Service1 table to modify/view the following to jobsite parameters:
Chilled Medium Water or Brine? Brine Refrigerant Trippoint Usually 3° F (1.7° C) below
Surge Limiting or Hot Gas
Bypass (HGBP) Option
Minimum Load Points
(T1/P1)
Maximum Load Points
(T2/P2)
Amps Correction Factor See Table 6 Motor Rated Load Amps Per job data Motor Rated Line Voltage Per job data Motor Rated Line kW Per job data
Line Frequency 50 or 60 Hz Compressor Starter Type Reduced voltage or full?
NOTE:Other values are left atthe defaultvalues.These maybe changed bythe operator as required. Service2 and Service3tables canbe modi­fied by the owner/operator as required.
design refrigerant temperature
Is HGBP installed? Per job data —
See Modify Load Points section
Per job data —
See Modify Load Points section
(if kW meter installed)
Modify Minimum and Maximum Load Points (DT1/P1; D T2/P2) If Necessary —These pairs of chiller load points,
located on the Service1 table, determine when to limit guide vane travel or to open the hot gas bypass valve when surge prevention is needed. These points should be set based on individual chiller operating conditions.
If, after configuring a value for these points, surge pre­vention is operating too soon or too late for conditions, these parameters should be changed by the operator.
Example of configuration: Chiller operating parameters Refrigerant used: HCFC-22
Estimated Minimum Load Conditions:
44 F (6.7 C) LCW
45.5 F (7.5 C) ECW
43 F (6.1 C) Suction Temperature
70 F (21.1 C) Condensing Temperature
Estimated Maximum Load Conditions:
44 F (6.7 C) LCW
54 F (12.2 C) ECW
42 F (5.6 C) Suction Temperature
98 F (36.7 C) Condensing Temperature Calculate Maximum Load — To calculate maximum load
points, use design load condition data. If the chiller full load cooler temperature difference is more than 15° F (8.3 C),
estimate the refrigerant suction and condensing tempera­tures at this difference. Use the proper saturated pressure and temperature for the particular refrigerant used.
Suction Temperature:
42 F (5.6 C) = 71.5 psig (521 kPa) saturated
refrigerant pressure (HCFC-22)
Condensing Temperature:
98 F (36.7 C) = 190 psig (1310 kPa) saturated
refrigerant pressure (HCFC-22)
Maximum Load DT2:
54 – 44 = 10° F (12.2 – 6.7 = 5.5° C)
Maximum Load DP2:
190 – 71.5 = 118.5 psid (1310 – 521 = 789 kPad) To avoid unnecessary surge prevention, add about 10 psid
(70 kPad) to DP2 from these conditions:
DT2 = 10° F (5.5° C) DP2 = 130 psid (900 kPad)
Calculate Minimum Load — To calculate minimum load con­ditions, estimate the temperature difference that the cooler will have at 10% load, then estimate what the suction and condensing temperatures will be at this point. Use the proper saturated pressure and temperature for the particular refrig­erant used.
Suction Temperature:
43 F (6.1 C) = 73 psig (503 kPa) saturated
refrigerant pressure (HCFC-22)
Condensing Temperature:
70 F (21.1 C) = 121 psig (834 kPa) saturated
refrigerant pressure (HCFC-22)
Minimum Load DT1:
45.5 – 44 = 1.5° F (7.5 – 6.7 = 0.8° C)
Minimum Load DP1:
121 – 73 = 45 psid (834 – 503 = 331 kPad) Again, to avoid unnecessary surge prevention, add 10 psid
(70 kPad) at DP1 from these conditions:
DT1 = 1.5 F (0.8 C) DP1 = 60 psid (410 kPad)
If surge prevention occurs too soon or too late:
LOAD At low
loads
(,50%) At high
loads
(.50%)
SURGE PREVENTION SURGE PREVENTION
OCCURS TOO SOON OCCURS TOO LATE
Increase P1 by
10 psid (70 kPad)
Increase P2 by
10 psid (70 kPad)
Decrease P1 by
10 psid (70 kPad)
Decrease P2 by
10 psid (70 kPad)
Modify Amp Correction Factors — To modify the amp cor­rection factor, use the values listed in Table 6. Enter the appropriate amp correction factor in the Service1 table of Equipment Service.
51
Page 52
Table 6 — Amps Correction Factors
for 19XL Motors
VOLT/
Hz
CB CC CD CE CL CM CN CP CQ CR
200/60 4536323222 208/60 5558424222 220/60 3422231111 230/60 5644352222
240/60 5644382222 360/60 4242221111 380/60 7464453222 400/60 7584453234
440/60 3322111134 460/60 5432222256 480/60 7543333378 550/60 4232123222
575/60 4442234333
600/60 8564346544 3300/60 4441233322 2400/60 4433232233
4160/60 4433232233
220/50 3122232111
230/50 4223243211
240/50 5354353322
320/50 2222111133
346/50 4433321234
360/50 5544422288
380/50 5233324222
400/50 6445436433
415/50 8556547544 3000/50 3223231212 3300/50 4333342212
MOTOR CODE
MODIFY EQUIPMENT CONFIGURATION IF NECES­SARY — The Equipment Configuration table has tables to select and view or modify. Carrier’s certified drawings will have the configuration values required for the jobsite. Modify these tables only if requested.
Config T ableModifications — Change the values in this table per job data. See certified drawings for values. Modifica­tions include:
• chilled water reset
• entering chilled water control (Enable/Disable)
• 4-20 mA demand limit
• auto. restart option (Enable/Disable)
• remote contact option (Enable/Disable) Owner-Modified CCN Tables—The following tables are de-
scribed for reference only. Occdef Table Modifications — The Occdef tables contain
the Local and CCN time schedules, which can be modified here, or in the Schedule screen as described previously.
Holidef TableModifications — The Holidef tables configure the days of the year that holidays are in effect. See the holi­day paragraphs in the Controls section for more details.
Brodefs Table Modifications — The Brodefs table defines the outside-air temperature sensor and humidity sensor if one is to be installed. It will define the start and end of day­light savings time. Enter the dates for the start and end of daylight savings if required for the location. Brodefs also will activate the Broadcast function which enables the holi­day periods that are defined on the LID.
Other Tables— TheAlarmdef, Cons-def, and Runt-def con­tain tables for use with a CCN system. See the applicable CCN manual for more information on these tables. These tables can only be defined through a CCN Building Supervisor.
CHECK VOLTAGE SUPPLY — Access the Status 01 screen and read the actual line voltage. This reading should be equal
to the incoming power to the starter. Use a voltmeter to check incoming power at the starter power leads. If the readings are not equal, an adjustment can be made to the 24-v input to the SMM at the potentiometer located in the low-voltage section to equalize the two readings.
PERFORMAN AUTOMATED CONTROL TEST — Check the safety controls status by performing an automated con­trols test. Access the Control Test table and select the Automated Tests function (Table 8).
The Automated Control Test will check all outputs and inputs for function. It will also set the refrigerant type. The compressor must be in the OFF mode in order to operate the controls test and the 24-v input to the SMM must be in range (per line voltage percent on Status01 table). The OFF mode is caused by pressing the STOP pushbutton on the LID. Each test will ask the operator to confirm that the operation is oc­curring, and whether or not to continue. If an error occurs, the operator has the choice to try to address the problem as the test is being done, or to note the problem and proceed to the next test.
NOTE: If during the Control Test the guide vanes do not open, check to see that the low pressure alarm is not active. (This will cause the guide vanes to close).
NOTE: The oil pump test will not energize the oil pump if cooler pressure is below –5 psig (–35 kPa).
When the test is finished, or the EXIT
softkey is pressed,
the test will be stopped and the Control Test menu will be displayed. If a specific automated test procedure is not completed, access the particular control test to test the func­tion when ready. The Control Test menu is described as follows:
Automated Tests As described above, a complete PSIO Thermistors Check of all PSIO thermistors only.
Options Thermistors Check of all options boards Transducers Check of all transducers.
Guide Vane Actuator Check of the guide vane operation. Pumps Check operation of pump outputs,
Discrete Outputs Activation of all on/off outputs or Pumpdown/Lockout Pumpdown prevents the low refrig-
Terminate Lockout To charge refrigerant and enable
Refrigerant Type* Sets type of refrigerant used:
*Make sure to Attach to Local Device after changing refrigerant type.
Refer to Selecting Refrigerant Type section on page 50.
control test.
thermistors.
either all pumps can be activated, or individual pumps. The test will also test the associated input such as flow or pressure.
individually. erant alarm during evacuation so
refrigerant can be removed from the unit, locks the compressor off, and starts the water pumps.
the chiller to run after pumpdown lockout.
HCFC-22 or HFC-134a.
Check Optional Pumpout System Controls and Compressor—
fuse, the compressor overloads, an internal thermostat, a com­pressor contactor, and a refrigerant high pressure cutout. The high pressure cutout is factory set to open at 220 ± 5 psig (1250 ± 34 kPa), and automatically reset at 185 + 0,
−7 psig (1280 +0,–48 kPa) with HCFC-22. HFC-134a units open at 161 psig (1110 kPa) and reset at 130 psig (896 kPa). Check that the water-cooled condenser has been connected.
Controls include an on/offswitch, a 3-amp
52
Page 53
Loosen the compressor holddown bolts to allow free spring travel. Open the compressor suction and discharge service valves. Check that oil is visible in the compressor sight glass. Add oil if necessary.
See Pumpout and Refrigerant Transfer Procedures and Optional Pumpout System Maintenance sections, pages 59 and 65, for details on transfer of refrigerant, oil specifica­tions, etc.
HighAltitude Locations — Recalibration of the pres-
sure transducers will be necessary as the chiller was initially calibrated at sea level. Please see the calibration procedure in the Troubleshooting Guide section.
Charge Refrigerant into Chiller
The transfer, addition, or removal of refrigerant in spring isolated chillers may place severe stress on external pip­ing if springs have not been blocked in both up and down directions.
The standard 19XL chiller will have the refrigerant already charged in the vessels. The 19XL may be ordered with a nitrogen holding charge of 15 psig (103 kPa). Evacu­ate the entire chiller, and charge chiller from refrigerant cylinders.
19XL CHILLER EQUALIZATION WITHOUT PUMP­OUT UNIT
When equalizing refrigerant pressure on the 19XL chiller after service work or during the initial chiller start-up, do not use the discharge isolation valve to equalize. The motor cooling isolation valve or charging hose (con­nected between pumpout valves on top of cooler and condenser) is to be used as the equalization valve.
To equalize the pressure differential on a refrigerant isolated 19XL chiller, use the TERMINATE LOCKOUT function of the Control Test in the SERVICE menu. This will help to turn on pumps and advise the proper procedure. The following procedure describes how to equalize refrig­erant pressure on an isolated 19XL chiller without a pump­out unit:
1. Access TERMINATE LOCKOUT function on the Con-
trol Test.
2. Turn on the chilled water and condenser water pumps to
ensure against freezing.
3. Slowly open the refrigerant cooling isolation valve.
The chiller cooler and condenser pressures will grad­ually equalize. This process will take approximately 15 minutes.
4. Once the pressures have equalized, the cooler isolation
valve, the condenser isolation valve, and the hot gas by­pass isolation valve may now be opened. Refer to Fig. 27 and 28, valves 11, 12, and 14.
Whenever turning the discharge isolation valve, be sure to reattach the valve locking device. This will prevent the valve from opening or closing during serv­ice work or during chiller operation.
Table 7 — Control Test Menu Functions
TESTS TO BE
PERFORMED
1. Automated Tests* Operates the second through
2. PSIO Thermistors Entering chilled water
3. Options Thermistors Common chilled water supply
4. Transducers Evaporator pressure
5. Guide Vane Actuator Open
6. Pumps All pumps or individual pumps may
7. Discrete Outputs All outputs or individual outputs may
8. Pumpdown/Lockout When using pumpdown/lockout,
9. Terminate Lockout Starts pumps and monitors flows
10. Refrigerant Type Sets refrigerant type used:
*During any of the tests that are not automated, an out-of-range read-
ing will have an asterisk (*) next to the reading and a message will be displayed.
seventh tests Leaving chilled water
Entering condenser water Leaving condenser water Discharge temperature Bearing temperature Motor winding temperature Oil sump temperature
sensor Common chilled water return sensor Remote reset sensor Temperature sensor — Spare 1
Condenser pressure Oil pressure differential Oil pump pressure
Close be activated:
be energized:
observe freeze up precautions when removing charge:
Instructs operator as to which valves to close and when
Starts chilled water and condenser water pumps and confirms flows
Monitors — Evaporator pressure
Turns pumps off after pumpdown Locks out compressor
Instructs operator as to which values to open and when
Monitors — Evaporator pressure
Terminates compressor lockout
NOTE: Be sure to ATTACH TO LOCAL DEVICE after changing refrigerant type.
See Attach to Network Device Control section, page 37.
DEVICES TESTED
Spare 2 Spare 3 Spare 4 Spare 5 Spare 6 Spare 7 Spare 8 Spare 9
Oil pump — Confirm pressure Chilled water pump — Confirm flow Condenser water pump — Confirm
flow
Hot gas bypass relay Oil heater relay Motor cooling relay Tower fan relay Alarm relay Shunt trip relay
Condenser pressure Evaporator temperature during pumpout procedures
Condenser pressure Evaporator temperature during charging process
HCFC-22 or HFC-134a.
53
Page 54
19XL CHILLER EQUALIZATION WITH PUMPOUT UNIT — The following procedure describes how to equal­ize refrigerant pressure on an isolated 19XL chiller using the pumpout unit.
1. Access the TERMINATE LOCKOUT mode in the Con­trol Test.
2. Turn on the chilled water and condenser water pumps to prevent possible freezing.
3. Open valve 4 on the pumpout unit and open valves 1a and 1b on the chiller cooler and condenser, Fig. 27 and
28. Slowly open valve 2 on the pumpout unit to equalize the pressure. This process will take approximately 15 minutes.
4. Once the pressures have equalized, the discharge isola­tion valve, cooler isolation valve, optional hot gas bypass isolation valve, and the refrigerant isolation valve can be opened. Close valves 1a and 1b, and all pumpout unit valves.
Whenever turning the discharge isolation valve, be sure to reattach the valve locking device. This will prevent the valve from opening or closing during serv­ice work or during chiller operation.
The full refrigerant charge on the 19XL will vary with chiller components and design conditions, indicated on the job data specifications. An approximate charge may be found by adding the condenser charge to the cooler charge listed in Table 8.
Always operate the condenser and chilled water pumps during charging operations to prevent freeze-ups. Use the Control Test Terminate Lockout to monitor conditions and start the pumps.
If the chiller has been shipped with a holding charge, the refrigerant will be added through the refrigerant charging valve (Fig. 27 and 28, valve 7) or to the pumpout charging con­nection. First evacuate the nitrogen holding charge from the
vessels. Charge the refrigerant as a gas until the system pres­sure exceeds 68 psig (469 kPa); [35 psig (141 kPa)]. After the chiller is beyond this pressure the refrigerant should be charged as a liquid until all of the recommended refrigerant charge has been added.
TRIMMING REFRIGERANT CHARGE — The 19XL is shipped with the correct charge for the design duty of the chiller.Trimming the charge can be best accomplished when design load is available. To trim, check the temperature difference between leaving chilled water temperature and cooler refrigerant temperature at full load design conditions. If necessary, add or remove refrigerant to bring the tempera­ture difference to design conditions or minimum differential.
Table 8 — Refrigerant Charges*
19XL TOTAL REFRIGERANT CHARGE
COOLER
SIZE
40 1420 640 1100 499 900 409 41 1490 680 1150 522 950 431 42 1550 700 1250 568 1000 454
43 1600 730 1350 613 1050 477 50 1850 840 1500 681 1100 499 51 1900 860 1600 726 1200 545
52 1980 900 1750 795 1300 590 53 2050 930 1850 840 1350 613 55 1900 863 1550 704
56 2200 999 1650 749 57 2500 1135 1750 795 58 2700 1226 1900 863
*DesignI chillers use HCFC-22. Design II chillers use either HCFC-22
or HFC-134a.
NOTES:
1. The size of the cooler determines refrigerant charge for the entire chiller.
2. Design I chillers have float chambers.
3. Design II chillers have linear floats.
Design I
Chiller
lb kg lb kg lb kg
HCFC-22 HFC-134a
Design II
Chiller
54
Page 55
INITIAL START-UP
Preparation—
1. Power is on to the main starter, oil pump relay, tower fan starter, oil heater relay, and the chiller control center.
2. Cooling tower water is at proper level, and at or below design entering temperature.
3. Chiller is charged with refrigerant and all refrigerant and oil valves are in their proper operating position.
4. Oil is at the proper level in the reservoir sight glasses.
5. Oil reservoir temperature is above 140 F (60 C) or re­frigerant temperature plus 50° F (28° C).
6. Valves in the evaporator and condenser water circuits are open.
NOTE: If pumps are not automatic, make sure water is circulating properly.
7. Solid-state starter checks: The Power +15 and the Phase Correct LEDs must be lit before the starter will energize. If the Power +15 LED is not on, incoming voltage is not present or is incorrect. If the Phase Correct LED is not lit, rotate any 2 incoming phases to correct the phasing.
Do not permit water or brine that is warmer than 110 F (43 C) to flow through the cooler or con­denser. Refrigerant overpressure may discharge through the relief devices and result in the loss of refrigerant charge.
8. Press RELEASE to automate the chiller start/stop value on the Status01 table to enable the chiller to start. The
initial factory setting of this value is overridden to stop in order to prevent accidental start-up.
Before starting the chiller, check that the:
Manual Operation of the Guide Vanes — Manual
operation of the guide vanes is helpful to establish a steady motor current for calibration of the motor amps value.
In order to manually operate the guide vanes, it is nec­essary to override the TARGET GUIDE VANE POSITION value which is accessed on the Status01 table. Manual con­trol is indicated by the word ‘‘SUPVSR!’’ flashing after the target value position. Manual control is also indicated on the default screen on the run status line.
1. Access the Status01 table and look at the target guide vane
position (Fig. 16). If the compressor is off, the value will read zero.
2. Move the highlight bar to the TARGET GUIDE VANE
POSITION line and press the SELECT
3. Press ENTER
will now read a value of zero, and the word ‘‘SUPVSR!’’ will flash.
4. Press the SELECT
RELEASE
MATIC mode. After a few seconds the ‘‘SUPVSR!’’ will disappear.
to override the automatic target. The screen
softkey, and then press
softkey to release the vanes to AUTO-
softkey.
Dry Run to Test Start-Up Sequence
1. Disengage the main motor disconnect on the starter front
panel. This should only disconnect the motor power. Power to the controls, oil pump, and starter control circuit should still be energized.
2. Look at the default screen on the LID: the Status mes-
sage in the upper left-hand corner will read, ‘‘Manually Stopped.’’ Press CCN or Local to start. If the chiller
controls do not go into start mode, go to the Schedule screen and override the schedule or change the oc-
cupied time. Press the LOCAL up sequences.
3. Check that chilled water and condenser water pumps energize.
4. Check that the oil pump starts and pressurizes the lubri­cation system. After the oil pump has run about 11 sec­onds, the starter will be energized and go through its start-up sequence.
5. Check the main contactor for proper operation.
6. The PIC will eventually show an alarm for motor amps not sensed. Reset this alarm and continue with the initial start-up.
softkey to begin the start-
Check Rotation
1. Engage the main motor disconnect on the front of the starter panel. The motor is now ready for rotation check.
2. After the default screen Status message states ‘‘Ready for Start’’pressthe LOCAL be made by the control.
3. When the starter is energized and the motor begins to turn. Check for clockwise rotation (Fig. 32).
IF ROTATION IS PROPER, allow the compressor to come up to speed.
IF THE MOTOR ROTATION IS NOT CLOCKWISE (as viewed through the sight glass), reverse any 2 of the 3 incoming power leads to the starter and recheck rotation.
NOTE: Solid-state starters have phase protection and will not allow a start if the phase is not correct. Instead, a Starter Fault message will occur if this happens.
Do not check motor rotation during coastdown. Rota­tion may have reversed during equalization of vessel pressures.
Fig. 32 — Correct Motor Rotation
NOTES ON SOLID-STATE STARTERS (Benshaw, Inc.)
1. When the compressor is energized to start by the 1CR relay, confirm that the Relay On LED is lit on the starter SCR control board. The compressor motor should start to turn immediately when this light comes on. If not, adjust the start torque potentiometer in a clockwise direction.
softkey; start-up checks will
55
Page 56
2. Observe that all 6-gate LEDs are lit on the starter SCR control board.
3. The factory setting should bring the motor to full voltage in 15 to 30 seconds. If the setting is not correct, adjust the ramp potentiometer counterclockwise for a shorter time, clockwise for a longer time. (See Fig. 5 for starter com­ponent placement.)
Check Oil Pressure and Compressor Stop
1. When the motor is up to full speed, note the differential oil pressure reading on the LID default screen. It should be between 18 and 30 psid (124 to 206 kPad).
2. Press the Stop button and listen for any unusual sounds from the compressor as it coasts to a stop.
Calibrate Motor Current
1. Make sure that the compressor motor rated load amps in the Service1 table has been configured. Place an ammeter on the line that passes through the motor load current trans­fer on the motor side of the power factor correction ca­pacitors (if provided).
2. Start the compressor and establish a steady motor current value between 70% and 100% RLA by manually over­riding the guide vane target value on the LID and setting the chilled water set point to a low value. Do not exceed 105% of the nameplate RLA.
3. When a steady motor current value in the desired range is met, compare the compressor motor amps value on the Status01 table to the actual amps shown on the ammeter on the starter. Adjust the amps value on the LID to the actual value seen at the starter if there is a difference.
Highlight the amps value then press SELECT Press INCREASE to that indicated on the ammeter. Press ENTER
equal.
4. Make sure that the target guide vane position is released into AUTOMATIC mode.
or DECREASE to bring the value
when
To Prevent Accidental Start-Up — The PIC can be
set up so that start-up of the unit is more difficult than just pressing the LOCAL ice or when necessary. By accessing the Status01 table, and
highlighting the chiller Start/Stop line, the value can be over­ridden to stop by pressing SELECT
STOP
after the value. When attempting to restart, remember to release the override. The default chiller message line will also state that the Start/Stop has been set to ‘‘Start’’or ‘‘Stop’’ when the value is overridden.
and ENTER softkeys. ‘‘SUPVSR’’ will appear
or CCN softkeys during chiller serv-
and then the
Check Chiller Operating Condition — Check to
be sure that chiller temperatures, pressures, water flows, and oil and refrigerant levels indicate that the system is func­tioning properly.
Instructthe Customer Operator— Check to be sure
that the operator(s) understand all operating and main­tenance procedures. Point out the various chiller parts and explain their function as part of the complete system.
COOLER-CONDENSER — Float chamber, relief devices, refrigerant charging valve, temperature sensor locations, pres­sure transducer locations, Schrader fittings, waterboxes and tubes, and vents and drains.
OPTIONAL STORAGE TANK AND PUMPOUT SYS­TEM — Transfer valves and pumpout system, refrigerant charging and pumpdown procedure, and relief devices.
MOTOR COMPRESSOR ASSEMBLY — Guide vane actuator, transmission, motor cooling system, oil cool­ing system, temperature and pressure sensors, oil sight glasses, integral oil pump, isolatable oil filter, extra oil and motor temperature sensors, synthetic oil, and compressor serviceability.
MOTOR COMPRESSOR LUBRICATION SYSTEM — Oil pump, cooler filter, oil heater, oil charge and specification, operating and shutdown oil level, temperature and pressure, and oil charging connections.
CONTROL SYSTEM — CCN and Local start, reset, menu, softkey functions, LID operation, occupancy schedule, set points, safety controls, and auxiliary and optional controls.
AUXILIARYEQUIPMENT— Starters and disconnects, sepa­rate electrical sources, pumps, and cooling tower.
DESCRIBE CHILLER CYCLES — Refrigerant, motor cool­ing, lubrication, and oil reclaim.
REVIEW MAINTENANCE — Scheduled, routine, and ex­tended shutdowns, importance of a log sheet, importance of water treatment and tube cleaning, and importance of main­taining a leak-free chiller.
SAFETYDEVICES AND PROCEDURES — Electrical dis­connects, relief device inspection, and handling refrigerant.
CHECK OPERATOR KNOWLEDGE — Start, stop, and shut­down procedures; safety and operating controls; refrigerant and oil charging; and job safety.
REVIEW THE START-UP, OPERATION,AND MAINTE­NANCE MANUAL
.
OPERATING INSTRUCTIONS
Operator Duties
1. Become familiar with refrigeration chiller and related equip­ment before operating the chiller.
2. Prepare the system for start-up, start and stop the chiller, and place the system in a shutdown condition.
3. Maintain a log of operating conditions and document any abnormal readings.
4. Inspect the equipment, make routine adjustments, and per­form a Control Test. Maintain the proper oil and refrig­erant levels.
5. Protect the system from damage during shutdown periods.
6. Maintain the set point, time schedules, and other PIC functions.
Prepare the Chillerfor Start-Up — Follow the steps
described in the Initial Start-Up section, page 55.
To Start the Chiller
1. Start the water pumps, if they are not automatic.
2. On the LID default screen, press the LOCAL
softkey to start the system. If the chiller is in
CCN
the OCCUPIED mode, and the start timers have expired, the start sequence will start. Follow the procedure de­scribed in the Start-Up/Shutdown/Recycle section, page 39.
or
Check the Running System — After the compres-
sor starts, the operator should monitor the LID display and observe the parameters for normal operating conditions:
1. The oil reservoir temperature should be above 140 F (60 C) during shutdown, and above 100 F (38 C) during compressor operation.
56
Page 57
2. The bearing oil temperature accessed on the Status01 table should be 120 to 165 F (49 to 74 C). If the bearing temperature reads more than 180 F (83 C) with the oil pump running, stop the chiller and determine the cause of the high temperature. Do not restart the chiller until corrected.
3. The oil level should be visible anywhere in one of the two sight glasses. Foaming of the oil is acceptable as long as the oil pressure and temperature are within limits.
4. The oil pressure should be between 18 and 30 psid (124 to 207 kPad), as seen on the LID default screen. Typically the reading will be 18 to 25 psid (124 to 172 kPad) at initial start-up.
5. The moisture indicator sight glass on the refrigerant motor cooling line should indicate refrigerant flow and a dry condition.
6. The condenser pressure and temperature varies with the chiller design conditions. Typically the pressure will range between 100 and 210 psig (690 to 1450 kPa) with a corresponding temperature range of 60 to 105 F (15 to 41 C). The condenser entering water temperature should be controlled below the specified design entering water temperature to save on compressor kilowatt requirements.
7. Cooler pressure and temperature also will vary with the design conditions. Typical pressure range will be be­tween 60 and 80 psig (410 and 550 kPa), with temper­ature ranging between 34 and 45 F (1 and 8 C).
8. The compressor may operate at full capacity for a short time after the pulldown ramping has ended, even though the building load is small. The active electrical demand setting can be overridden to limit the compressor IkW, or the pulldown rate can be decreased to avoid a high demand charge for the short period of high demand operation. Pulldown rate can be based on load rate or temperature rate. It is accessed on the Equipment Con­figuration, Config table (Table 2, Example 5).
To Stop the Chiller
1. The occupancy schedule will start and stop the chiller automatically once the time schedule is set up.
2. By pressing the STOP button for one second, the alarm light will blink once to confirm that the button has been pressed, then the compressor will follow the normal shut­down sequence as described in the Controls section. The
chiller will not restart until the CCN or LOCAL soft­key is pressed. The chiller is now in the OFF mode.
If the chiller fails to stop, in addition to action that the PIC will initiate, the operator should close the guide vanes by overriding the guide vane target to zero to re­duce chiller load; then by opening the main disconnect. Do not attempt to stop the chiller by opening an isolating knife switch. High intensity arcing may occur. Do not re- start the chiller until the problem is diagnosed and corrected.
After Limited Shutdown — No special preparations
should be necessary. Follow the regular preliminary checks and starting procedures.
ExtendedShutdown— The refrigerant should be trans-
ferred into the storage vessel (if supplied; see Pumpout and Refrigerant Transfer Procedures) in order to reduce chiller pressure and possibility of leaks. Maintain a holding charge
of 5 to 10 lbs (2.27 to 4.5 kg) of refrigerant to prevent air from leaking into the chiller.
If freezing temperatures are likely to occur in the chiller area, drain the chilled water, condenser water, and the pumpout condenser water circuits to avoid freeze-up. Keep the waterbox drains open.
Leave the oil charge in the chiller with the oil heater and controls energized to maintain the minimum oil reser­voir temperature.
After Extended Shutdown — Be sure that the water
system drains are closed. It may be advisable to flush the water circuits to remove any soft rust which may have formed. This is a good time to brush the tubes if necessary.
Check the cooler pressure on the LID default screen, and compare to the original holding charge that was left in the chiller. If (after adjusting for ambient temperature changes) any loss in pressure is indicated, check for refrigerant leaks. See Check Chiller Tightness section, page 41.
Recharge the chiller by transferring refrigerant from the storage tank (if supplied). Follow the Pumpout and Refrig­erant Transfer Procedures section, page 59. Observe freeze-up precautions.
Carefully make all regular preliminary and running sys­tem checks. Perform a Control Test before start-up. If the compressor oil level appears abnormally high, the oil may have absorbed refrigerant. Make sure that the oil tempera­ture is above 140 F (60 C) or cooler refrigerant temperature plus 50° F (27° C).
Cold Weather Operation — When the entering con-
denser water drops very low, the operator should auto­matically cycle the cooling tower fans off to keep the temperature up. Piping may also be arranged to bypass the cooling tower. The PIC controls have a low limit tower fan relay (PR3) that can be used to assist in this control.
Manual Guide Vane Operation — Manual opera-
tion of the guide vanes in order to check control operation or control of the guide vanes in an emergency operation is possible by overriding the target guide vane position. Access the Status01 table on the LID and highlight TARGET GUIDE VANE POSITION. To control the position, enter a percentage of guide vane opening that is desired. Zero percent is fully closed, 100% is fully open. To re­lease the guide vanes to AUTOMATIC mode, press the
RELEASE
NOTE: Manual control will increase the guide vanes and override the pulldown rate during start-up. Motor current above the electrical demand setting, capacity overrides, and chilled water below control point will override the manual target and close the guide vanes. For descriptions of capacity over­rides and set points, see the Controls section.
softkey.
Refrigeration Log — A refrigeration log, such as
the one shown in Fig. 33, provides a convenient check­list for routine inspection and maintenance and provides a continuous record of chiller performance. It is an aid in scheduling routine maintenance and in diagnosing chiller problems.
Keep a record of the chiller pressures, temperatures, and liquid levels on a sheet similar to that shown. Automatic recording of PIC data is possible through the use of CCN devices such as the Data Collection module and a Building Supervisor. Contact your Carrier representative for more information.
57
Page 58
Date
REMARKS
ATOR
OPER-
FLA
Oil Motor
BEARING
INITIALS
(or vane
position)
Amperage
Level
Temp
(reservoir)
Diff.
Press.
TEMP
REFRIGERATION LOG CARRIER 19XT HERMETIC CENTRIFUGAL REFRIGERATION MACHINE
CHILLER MODEL NO. CHILLER SERIAL NO. REFRIGERANT TYPE
Refrigerant Water Refrigerant Water
Pressure Temp
Fig. 33 — Refrigeration Log
Press. Temp
Pressure Temp
In Out GPM In Out In Out GPM In Out
Press. Temp
TIME
Plant
DATE COOLER CONDENSER COMPRESSOR
REMARKS: Indicate shutdowns on safety controls, repairs made, oil or refrigerant added or removed, air exhausted and water drained from dehydrator. Include amounts.
58
Page 59
PUMPOUT AND REFRIGERANT TRANSFER
PROCEDURES
Preparation —
an optional storage tank or pumpout system, or a pump­out compressor. The refrigerant can be pumped for service work to either the cooler/compressor vessel or the condenser vessel by using the optional pumpout system. If a storage tank is supplied, the refrigerant can be isolated in the external storage tank. The following procedures describe how to transfer refrigerant from vessel to vessel and perform chiller evacuations.
The 19XL may come equipped with
Operating the Optional Pumpout Compressor
1. Be sure that the suction and the discharge service valves on the optional pumpout compressor are open (back­seated) during operation. Rotate the valve stem fully coun­terclockwise to open. Frontseating the valve closes the refrigerant line and opens the gage port to compressor pressure.
2. Make sure that the compressor holddown bolts have been loosened to allow free spring travel.
3. Open the refrigerant inlet valve on the pumpout compressor.
4. Oil should be visible in the pumpout compressor sight glass under all operating conditions and during shut­down. If oil is low, add oil as described under Optional Pumpout System Maintenance section, page 65. The pumpout unit control wiring schematic is detailed in Fig. 34.
LEGEND
C—Contactor FU Fuse, 3 Amps HP High-Pressure Cutout OL Compressor Overload T’STAT — Internal Thermostat
Compressor Terminal Contactor Terminal
Overload Terminal Pumpout Unit Terminal
*Bimetal thermal protector imbedded in motor winding.
Fig. 34 — 19XL Pumpout Unit
Wiring Schematic
TO READ REFRIGERANT PRESSURES during pumpout or leak testing:
1. The LID display on the chiller control center is suitable for determining refrigerant-side pressures and low (soft) vacuum. For evacuation or dehydration measurement, use a quality vacuum indicator or manometer to ensure the desired range and accuracy. This can be placed on the Schrader connections on each vessel by removing the pres­sure transducer.
2. To determine storage tank pressure, a 30 in.-0-400 psi (-101-0-2760 kPa) gage is attached to the vessel.
3. Refer to Fig. 27, 28, and 35 for valve locations and numbers.
Transfer, addition, or removal of refrigerant in spring­isolated chillers may place severe stress on external pip­ing if springs have not been blocked in both up and down directions.
Chillers with Pumpout Storage Tanks — If the
chiller has isolation valves, leave them open for the follow­ing procedures. The letter ‘‘C’’ describes a closed valve. See Fig. 16, 17, 27, and 28.
TRANSFER REFRIGERANT FROM STORAGETANKTO CHILLER
1. Equalize refrigerant pressure. a. Use the Control Test Terminate Lockout to turn on
water pumps and monitor pressures.
b. Close pumpout unit/storage tank valves 2, 4, 5, 8, and
10 and close chiller charging valve 7; open chiller iso­lation valves 11, 12, 13, and 14 (if present).
c. Open pumpout unit/storage tank valves 3 and 6, open
chiller valves 1a and 1b.
OIL RETURN LINE CONNECTION
CONDENSER WATER CONNECTIONS
VENT VALVE 8
REFRIGERANT INLET VALVE
PUMPOUT STARTER PANEL
Fig. 35 — Optional Pumpout Unit
VALVE 1a1b234 567 81011121314 CONDITION CCCCCC
d. Gradually crack open valve 5 to increase chiller pres-
sure to 68 psig (469 kPa), [35 psig (141 kPa)]. Slowly feed refrigerant to prevent freeze up.
e. Open valve 5 fully after the pressure rises above the
freeze point of the refrigerant. Open liquid line valves 7 and 10 until refrigerant pressure equalizes.
VALVE 1a1b23456781011121314 CONDITION CC C
59
Page 60
2. Transfer remaining refrigerant. a. Close valve 5 and open valve 4.
VALVE 1a1b23456781011121314 CONDITION CCC
b. Turn off the chiller water pumps through the LID. c. Turn off the pumpout condenser water, and turn on the
pumpout compressor to push liquid out of the storage
tank. d. Close liquid line valve 7. e. Turn off the pumpout compressor. f. Close valves 3 and 4. g. Open valves 2 and 5.
VALVE 1a 1b 2 3 4 5 6 7 8 10 11 12 13 14 CONDITION CC CC
h. Turn on pumpout condenser water. i. Run the pumpout compressor until the storage tank
pressure reaches 5 psig (34 kPa) (18 in. Hg [40 kPa
absolute] if repairing the tank). j. Turn off the pumpout compressor. k. Close valves 1a, 1b, 2, 5, 6, and 10.
VALVE 1a1b23456781011121314 CONDITION C C CCCCCCCC
l. Turn off pumpout condenser water.
TRANSFER THE REFRIGERANT FROM CHILLER TO STORAGE TANK
1. Equalize refrigerant pressure. a. Valve positions:
VALVE 1a1b234 567 81011121314 CONDITION CCCCCC
b. Slowly open valve 5 and liquid line valves 7 and 10
to allow liquid refrigerant to drain by gravity into the pumpout storage tank.
VALVE 1a1b23456781011121314 CONDITION CC C
2. Transfer the remaining liquid. a. Turn off pumpout condenser water. Place valves in the
following positions:
VALVE 1a1b23 45678101121314 CONDITION CC C
b. Run the pumpout compressor for approximately30 min-
utes; then, close valve 10.
VALVE 1a1b23456781011121314 CONDITION CC CC
c. Turn off the pumpout compressor.
3. Remove any remaining refrigerant. a. Turn on chiller water pumps using the Control Test
Pumpdown. b. Turn on pumpout condenser water. c. Place valves in the following positions:
VALVE 1a1b23456781011121314 CONDITION CCCC
d. Run the pumpout compressor until the chiller pres-
sure reaches 65 psig (448 kPa) [30 psig (207 kPa)],
then shut off the pumpout compressor. Warm con­denser water will boil off any entrapped liquid refrig­erant and chiller pressure will rise.
e. When the pressure rises to 70 psig (483 kPa) [40 psig
(276 kPa)], turn on the pumpout compressor until the pressure again reaches 65 psig (448 kPa) [30 psig (207 kPa)], and then turn off the compressor. Repeat this process until the pressure no longer rises, then turn on the pumpout compressor and pump out until the pressure reaches 18 in. Hg (40 kPa absolute).
f. Close valves 1a, 1b, 3, 4, 6, and 7.
VALVE 1a1b23456781011121314 CONDITION C C CCCCCCCC
g. Turn off the pumpout condenser water and continue
with the Control Test for Pumpdown, which will lock out the chiller compressor for operation.
4. Establish vacuum for service. a. In order to conserve refrigerant, operate the pump-
out compressor until the chiller pressure is reduced to 18 in. Hg vac, ref 30 in. bar. (40 kPa abs.) following Step 3e.
Chillers with Isolation Valves
TRANSFER ALL REFRIGERANT TO CHILLER CON­DENSER VESSEL — For chillers with isolation valves, re­frigerant can be transferred from one chiller vessel to another without the need for an external storage tank and valve 7 stays closed. See Fig. 27, 28, and 35 for valve locations.
1. Push refrigerant into chiller condenser. a. Valve positions:
VALVE 1a 1b 2 3 4 5 8 11 12 13 14 CONDITION CC C CCC
b. Turn off chiller water pumps and pumpout unit con-
denser water.
c. Turn on pumpout compressor to push liquid out of the
cooler/compressor.
d. When all liquid has been pushed into the condenser,
close cooler isolation valve 11.
e. Access the Control Test, Pumpdown table on the LID
display to turn on the chiller water pumps.
f. Turn off the pumpout compressor.
2. Evacuate gas from cooler/compressor vessel. a. Close pumpout valves 2 and 5, and open valves 3
and 4.
VALVE 1a 1b 2 3 4 5 8 11 12 13 14 CONDITION C CCCCCC
b. Turn on pumpout condenser water. c. Run pumpout until the compressor reaches 18 in. Hg
vac (40 kPa abs.). Monitor pressures on the LID and
on refrigerant gages. d. Close valve 1a. e. Turn off pumpout compressor. f. Close valves 1b, 3, and 4.
VALVE 1a1b2345811121314 CONDITION C C CCCCCC C C C
g. Turn off pumpout condenser water. h. Proceed to Pumpdown test on the LID to turn offchiller
water pumps and lock out chiller compressor.
60
Page 61
TRANSFER ALL REFRIGERANT TO CHILLER COOLER/COMPRESSOR VESSEL
1. Push refrigerant into the chiller cooler vessel. a. Valve positions:
VALVE 1a 1b 2 3 4 5 8 11 12 13 14 CONDITION C CC CCC
b. Turn off chiller water pumps and pumpout condenser
water.
c. Turn on pumpout compressor to push refrigerant out
of the condenser.
d. When all liquid is out of the condenser, close cooler
isolation valve 11.
e. Turn off the pumpout compressor.
2. Evacuate gas from the chiller condenser vessel. a. Access the Control Test Pumpdown table on the LID
display to turn on the chiller water pumps.
b. Close pumpout valves 3 and 4; open valves 2 and 5.
VALVE 1a 1b 2 3 4 5 8 11 12 13 14 CONDITION CC CCCCC
c. Turn on pumpout condenser water. d. Run the pumpout compressor until the chiller com-
pressor reaches 18 in. Hg vac (40 kPa abs.). Monitor
pressure at the LID and refrigerant gages. e. Close valve 1b. f. Turn off pumpout compressor. g. Close valves 1a, 2, and 5.
VALVE 1a1b2345811121314 CONDITION C C CCCCCC C C C
h. Turn off pumpout condenser water. i. Proceed to the Pumpdown test on the LID to turn off
chiller water pumps and lockout chiller compressor.
RETURN REFRIGERANT TO NORMAL OPERATING CONDITIONS
1. Be sure that the chiller vessel that was opened has been evacuated.
2. Access the Control TestTerminateLockout table to view vessel pressures and turn on chiller water pumps.
3. Open valves 1a, 1b, and 3.
VALVE 1a 1b 2 3 4 5 8 11 12 13 14 CONDITION C CCCC C C C
4. Crack open valve 5, gradually increasing pressure in the evacuated vessel to 68 psig (469 kPa) [35 psig (141 kPa)]. Feed refrigerant slowly to prevent tube freeze up.
5. Leak test to ensure vessel integrity.
6. Open valve 5 fully.
VALVE 1a1b2345811121314 CONDITION CCCCCCC
7. Open valve 11 to equalize the liquid refrigerant level between vessels.
8. Close valves 1a, 1b, 3, and 5.
9. Open isolation valves 11, 12, 13, and 14 (if present).
VALVE 1a1b2345811121314 CONDITION C C CCCCC
10. Proceed to Terminate Pumpdown Lockout test to turn off water pumps and enable the chiller compressor for start-up.
GENERAL MAINTENANCE
Refrigerant Properties —
is the standard refrigerant in the 19XL. At normal atmo­spheric pressure, HCFC-22 will boil at –41 F (–40 C) and HFC-134a will boil at –14 F (–25 C) and must, therefore, be kept in pressurized containers or storage tanks. The refrig­erants are practically odorless when mixed with air. Both refrigerants are non-combustible at atmospheric pressure. Read the Material Safety Data Sheet and the latestASHRAE Safety Guide for Mechanical Refrigeration to learn more about safe handling of these refrigerants.
HCFC-22 and HFC-134a will dissolve oil and some non-metallic materials, dry the skin, and, in heavy con­centrations, may displace enough oxygen to cause asphyxiation. When handling this refrigerant, protect the hands and eyes and avoid breathing fumes.
HCFC-22 or HFC-134a
Adding Refrigerant — Follow the procedures de-
scribed in Trimming Refrigerant Charge section, page 54.
Always use the compressor Pumpdown function in the Control Test table to turn on the evaporator pump and lock out the compressor when transferring refrigerant. Liquid refrigerant may flash into a gas and cause pos­sible freeze-up when the chiller pressure is below 65 psig (448 kPa) [30 psig (207 kPa)].
RemovingRefrigerant — If the optional pumpout unit
is used, the 19XL refrigerant charge may be transferred to a pumpout storage tank or to the chiller condenser or cooler vessels. Follow procedures in the Pumpout and Refrigerant TransferProcedures section when removing refrigerant from the pumpout storage tank to the chiller vessel.
Adjusting the Refrigerant Charge — If the addi-
tion or removal of refrigerant is required for improved chiller performance, follow the procedures given under the Trim Refrigerant Charge section, page 62.
Refrigerant Leak Testing — Because HCFC-22 and
HFC-134a are above atmospheric pressure at room tempera­ture, leak testing can be performed with refrigerant in the chiller. Use an electronic, halide leak detector, soap bubble solution, or ultra-sonic leak detector. Be sure that the room is well ventilated and free from concentration of refrigerant to keep false readings to a minimum. Before making any necessary repairs to a leak, transfer all refrigerant from the leaking vessel.
Leak Rate — ASHRAE recommends that chillers should
be immediately taken off line and repaired if the refrigerant leakage rate for the entire chiller is more than 10% of the operating refrigerant charge per year.
Additionally,Carrier recommends that leaks totalling less than the above rate but more than a rate of 1 lb (0.5 kg) per year should be repaired during annual maintenance or whenever the refrigerant is pumped over for other service work.
Test After Service, Repair, or Major Leak — If
all refrigerant has been lost or if the chiller has been opened for service, the chiller or the affected vessels must be pres­sured and leak tested. Refer to the Leak Test Chiller section to perform a leak test.
61
Page 62
HCFC-22 and HFC-134a should not be mixed with air or oxygen and pressurized for leak testing. In gen­eral, neither refrigerant should not be allowed to be pre­sent with high concentrations of air or oxygen above atmospheric pressures, as the mixture can undergo combustion.
REFRIGERANT TRACER — Use an environmentally acceptable refrigerant as a tracer for leak test procedures.
TO PRESSURIZE WITH DRY NITROGEN — Another method of leak testing is to pressurize with nitrogen only and use a soap bubble solution or an ultrasonic leak detector to determine if leaks are present. This should only be done if all refrigerant has been evacuated from the vessel.
1. Connect a copper tube from the pressure regulator on the cylinder to the refrigerant charging valve. Never apply full cylinder pressure to the pressurizing line. Follow the listed sequence.
2. Open the charging valve fully.
3. Slowly open the cylinder regulating valve.
4. Observe the pressure gage on the chiller and close the regulating valve when the pressure reaches test level. Do not exceed 140 psig (965 kPa).
5. Close the charging valve on the chiller. Remove the cop­per tube if no longer required.
Repair the Leak, Retest, and Apply Standing Vacuum Test —
leaks with an electronic, halide leak detector, soap bubble solution, or an ultrasonic leak detector. Bring the chiller back to atmospheric pressure, repair any leaks found, and retest.
After retesting and finding no leaks, apply a standing vacuum test, and then dehydrate the chiller. Refer to the Standing Vacuum Test and Chiller Dehydration in the Before Initial Start-Up section, pages 43 and 47.
After pressurizing the chiller, test for
Fig. 36 — Guide Vane Actuator Linkage
Refrigerant may be added either through the storage tank or directly into the chiller as described in the Charge Refrigerant into Chiller section.
To remove any excess refrigerant, follow the procedure in Transfer Refrigerant from Chiller to Storage Tank section, Steps 1a and b, page 60.
WEEKLY MAINTENANCE
Checking Guide VaneLinkage — When the chiller
is off, the guide vanes are closed and the actuator mecha­nism is in the position shown in Fig. 36. If slack develops in the drive chain, backlash can be eliminated as follows:
1. With the machine shut down and the actuator fully closed, remove the chain guard and loosen the actuator bracket holddown bolts.
2. Loosen guide vane sprocket adjusting bolts.
3. Pry bracket upwards to remove slack, then retighten the bracket holddown bolts.
4. Retighten the guide vane sprocket adjusting bolts. Make sure that the guide vane shaft is rotated fully in the clock­wise direction in order for it to be fully closed.
CHECKINGTHE AUXILIARYSWITCHON GUIDE VANE ACTUATOR — The auxiliary switch used to activate the oil reclaim system solenoids should move to the OPEN posi­tion when the actuator is 70 degrees open. (At this point the guide vanes should be 30 degrees open.)
Trim Refrigerant Charge — If it becomes necessary
to adjust the refrigerant charge to obtain optimum chiller per­formance, operate the chiller at design load and then add or remove refrigerant slowly until the difference between leav­ing chilled water temperature and the cooler refrigerant tem­perature reaches design conditions or becomes a minimum.
Do not overcharge.
Checkthe Lubrication System —
on the reservoir sight glass, and observe the level each week while the chiller is shut down.
If the level goes below the lower sight glass, the oil reclaim system will need to be checked for proper operation. If additional oil is required, add it through the oil drain charging valve (Fig. 2A or Fig. 2B). A pump is required for adding oil against refrigerant pressure. The oil charge is approximately 8 gallons (30 L). The added oil must meet Carrier specifications for the 19XL. Refer to Changing Oil Filter and Oil Changes sections on page 63. Any additional oil that is added should be logged by noting the amount and date. Any oil that is added due to oil loss that is not related to service will eventually return to the sump. It must be removed when the level is high.
A 1200-watt oil heater is controlled by the PIC to main­tain oil temperature (see the Controls section) when the compressor is off. The LID Status02 table displays whether the heater is energized or not. If the PIC shows that the heater is energized, but the sump is not heating up, the power to the oil heater may be off or the oil level may be too low. Check the oil level, the oil heater contactor voltage, and oil heater resistance.
The PIC will not permit compressor start-up if the oil temperature is too low.The control will continue with start-up only after the temperature is within limits.
Mark the oil level
62
Page 63
SCHEDULED MAINTENANCE
Establish a regular maintenance schedule based on the actual chiller requirements such as chiller load, run hours, and water quality. The time intervals listed in this section are offered as guides to service only.
Service Ontime — The LID will display a SERVICE
ONTIME value on the Status01 table. This value should be
reset to zero by the service person or the operator each time major service work is completed so that time between serv­ice can be viewed.
Inspect the Control Center — Maintenance is lim-
ited to general cleaning and tightening of connections. Vacuum the cabinet to eliminate dust build-up. In the event of chiller control malfunctions, refer to the Troubleshooting Guide sec­tion for control checks and adjustments.
Be sure power to the control center is off when cleaning and tightening connections inside the control center.
Check Safety and Operating Controls Monthly
To ensure chiller protection, the Control TestAutomated
Test should be done at least once per month. See Table 3 for safety control settings. See Table 7 for Control Test functions.
Changing Oil Filter — Change the oil filter on a yearly
basis or when the chiller is opened for repairs. The 19XL has an isolatable oil filter so that the filter may be changed with the refrigerant remaining in the chiller. Use the follow­ing procedure:
1. Make sure that the compressor is off, and the disconnect for the compressor is open.
2. Disconnect the power to the oil pump.
3. Close the oil filter isolation valves (Fig. 4).
4. Connect an oil charging hose from the oil charging valve (Fig. 4), and place the other end in a clean container suitable for used oil. The oil drained from the filter hous­ing should be used as an oil sample to be sent to a labo­ratory for proper analysis.Do not contaminate this sample.
5. Slowly open the charging valve to drain the oil from the housing.
The oil filter housing is at a high pressure. Relieve this pressure slowly.
6. Once all oil has been drained, place some rags or ab­sorbent material under the oil filter housing to catch any drips once the filter is opened. Remove the 4 bolts from the end of the filter housing and remove the filter cover.
7. Remove the filter retainer by unscrewing the retainer nut. The filter may now be removed and disposed of properly.
8. Replace the old filter with a new filter. Install the filter retainer and tighten down the retainer nut. Install the fil­ter cover and tighten the 4 bolts.
9. Evacuate the filter housing by placing a vacuum pump on the charging valve. Follow the normal evacuation pro­cedures. Shut the charging valve when done, and recon­nect the valve so that new oil can be pumped into the filter housing. Fill with the same amount that was removed, then close the charging valve.
10. Remove the hose from the charging valve, open the iso­lation valves to the filter housing, and turn on the power to the pump and the motor.
Oil Specification — The 19XL compressor holds ap-
proximately 11.7 gal. (44.3 L) of oil. If oil is added, it must meet the following Carrier specifications:
• Oil type for HCFC-22 Chillers only ...........Alkyl-
ISO Viscosity Grade ..........................86
• Oil Type for units using R-134a ............Inhibited
ISO Viscosity Grade ..........................68
The alkyl-benzene type oil (part number PP23BZ101) or the polyolester-based oil (part number PP23BZ103) may be ordered from your local Carrier representative.
benzene-based synthetic compressor oil
specifically formatted for use in HCFC-22 gear-driven machines
polyolester-based synthetic compressor
oil formatted for use with HFC, gear-
driven, hermetic compressors.
Oil Changes — Carrier recommends changing the oil
after the first year of operation and every 3 years thereafter as a minimum in addition to a yearly oil analysis. However, if a continuous oil monitoring system is functioning and a yearly oil analysis is performed, time between oil changes can be extended.
TO CHANGE THE OIL
1. Transfer the refrigerant into the condenser (for isolatable
vessels) or a storage tank.
2. Mark the existing oil level.
3. Open the control and oil heater circuit breaker.
4. When the chiller pressure is 5 psi (34 kPa) or less, drain
the oil reservoir by opening the oil charging valve (Fig. 2A or Fig. 2B). Slowly open the valve against refrigerant pressure.
5. Change the oil filter at this time. See Changing Oil Filter
section.
6. Change the refrigerant filter at this time; see the next sec-
tion, Refrigerant Filter.
7. Charge the chiller with oil. Charge until the oil level is
equal to the oil level marked in Step 2. Turn on the power to the oil heater and let the PIC warm it up to at least 140 F (60 C). Operate the oil pump manually,through the Control Test, for 2 minutes. The oil level should be full in the lower sight glass for shutdown conditions. If the oil level is above remove the excess oil. The oil level should now be equal to the amount shown in Step 2.
1
⁄2full in the upper sight glass,
Refrigerant Filter — A refrigerant filter drier, located
on the refrigerant cooling line to the motor (Fig. 2A or 2B), should be changed once a year, or more often if filter condition indicates a need for more frequent replacement. Change the filter with the chiller pressure at 0 psig (0 kPa) by transferring the refrigerant to the condenser vessel, (if iso­lation valves are present), or a storage tank. A moisture indicator sight glass is located beyond this filter to indicate the volume and moisture in the refrigerant. If the moisture indicator (dry-eye) indicates moisture, locate the source of water immediately by performing a thorough leak check.
Oil Reclaim Filters — The oil reclaim system has a
strainer on the eductor suction line and a filter on the cooler scavaging line. Replace these filters once per year, or more often if filter condition indicates a need for more frequent replacement. Change these filters by transferring the refrig­erant charge to a storage vessel or the condenser.
63
Page 64
Inspect Refrigerant Float System — Perform
inspection every 5 years or when the condenser is opened for service. Transfer the refrigerant into the cooler vessel or into a storage tank. Remove the float access cover. Clean the chamber and valve assembly thoroughly. Be sure that the valve moves freely. Make sure that all openings are free of obstructions. Examine the cover gasket and replace if nec­essary. See Fig. 37 for views of both float valve designs. On the linear float valve design, inspect orientation of the float slide pin. It must be pointed toward the bubbler tube for proper operation.
Compressor Bearing and Gear Mainten­ance —
proper lubrication. Use the proper grade of oil, maintained at recommended level, temperature, and pressure. Inspect the lubrication system regularly and thoroughly.
To inspect the bearings, a complete compressor teardown is required. Only a trained service technician should remove and examine the bearings. The cover plate on older com­pressor bases was used for factory-test purposes, and is not usable for bearing or gear inspection. The bearings and gears should be examined on a scheduled basis for signs of wear. The frequency of examination is determined by the hours of chiller operation, load conditions during operation, and the condition of the oil and the lubrication system. Excessive bearing wear can sometimes be detected through increased vibration or increased bearing temperature. If either symp­tom appears, contact an experienced and responsible service organization for assistance.
The key to good bearing and gear maintenance is
Inspect the Heat Exchanger Tubes
COOLER — Inspect and clean the cooler tubes at the end of the first operating season. Because these tubes have internal ridges, a rotary-type tube cleaning system is necessary to fully clean the tubes. Upon inspection, the tube condition will determine the scheduled frequency for cleaning, and will indicate whether water treatment is adequate in the chilled water/brine circuit. Inspect the entering and leaving chilled water temperature sensors for signs of corrosion or scale. Replace the sensor if corroded or remove any scale if found.
Fig. 37 — 19XL Float Valve Designs
InspectRelief Valvesand Piping— The relief valves
on this chiller protect the system against the potentially dan­gerous effects of overpressure. To ensure against damage to the equipment and possible injury to personnel, these devices must be kept in peak operating condition.
As a minimum, the following maintenance is required.
1. At least once a year, disconnect the vent piping at the valve outlet and carefully inspect the valve body and mechanism for any evidence of internal corrosion or rust, dirt, scale, leakage, etc.
2. If corrosion or foreign material is found, do not attempt to repair or recondition. Replace the valve.
3. If the chiller is installed in a corrosive atmosphere or the relief valves are vented into a corrosive atmosphere, make valve inspections at more frequent intervals.
CONDENSER — Since this water circuit is usually an open­type system, the tubes may be subject to contamination and scale. Clean the condenser tubes with a rotary tube clean­ing system at least once per year, and more often if the water is contaminated. Inspect the entering and leaving condenser water sensors for signs of corrosion or scale. Replace the sensor if corroded or remove any scale if found.
Higher than normal condenser pressures, together with the inability to reach full refrigeration load, usually indicate dirty tubes or air in the chiller. If the refrigeration log indicates a rise above normal condenser pressures, check the condenser refrigerant temperature against the leaving condenser water temperature. If this reading is more than what the design difference is supposed to be, then the condenser tubes may be dirty, or water flow may be incorrect. Because HCFC-22 and HFC134-a are high-pressure refrigerants, air usually does not enter the chiller, rather, the refrigerant leaks out.
During the tube cleaning process, use brushes especially designed to avoid scraping and scratching the tube wall. Con­tact your Carrier representative to obtain these brushes. Do not use wire brushes.
Hard scale may require chemical treatment for its pre­vention or removal. Consult a water treatment specialist for proper treatment.
Water Leaks — Water is indicated during chiller opera-
tion by the refrigerant moisture indicator (Fig. 2A or 2B) on the refrigerant motor cooling line. Water leaks should be re­paired immediately.
Chiller must be dehydrated after repair of water leaks. See Chiller Dehydration section, page 47.
64
Page 65
WaterTreatment— Untreated or improperly treated wa-
ter may result in corrosion, scaling, erosion, or algae. The services of a qualified water treatment specialist should be obtained to develop and monitor a treatment program.
Water must be within design flow limits, clean, and treated to ensure proper chiller performance and reduce the potential of tubing damage due to corrosion, scaling, ero­sion, and algae. Carrier assumes no responsibility for chiller damage resulting from untreated or improperly treated water.
Inspect the Starting Equipment — Before work-
ing on any starter, shut off the chiller, and open all discon­nects supplying power to the starter.
Oil should be visible in one of the compressor sight glasses both during operation and at shutdown. Always check the oil level before operating the compressor. Before adding or changing oil, relieve the refrigerant pressure as follows:
1. Attach a pressure gage to the gage port of either com-
pressor service valve (Fig. 35).
2. Close the suction service valve and open the discharge
line to the storage tank or the chiller.
3. Operate the compressor until the crankcase pressure drops
to 2 psig (13 kPa).
4. Stop the compressor and isolate the system by closing
the discharge service valve.
5. Slowly remove the oil return line connection (Fig. 35).
Add oil as required.
6. Replace the connection and reopen the compressor serv-
ice valves.
The disconnect on the starter front panel does not de­energize all internal circuits. Open all internal and re­mote disconnects before servicing the starter.
Never open isolating knife switches while equipment is operating. Electrical arcing can cause serious injury.
Inspect starter contact surfaces for wear or pitting on mechanical-type starters. Do not sandpaper or file silver­plated contacts. Follow the starter manufacturer’s instruc­tions for contact replacement, lubrication, spare parts order­ing, and other maintenance requirements.
Periodically vacuum or blow off accumulated debris on the internal parts with a high-velocity, low-pressure blower.
Power connections on newly installed starters may relax and loosen after a month of operation. Turn power off and retighten. Recheck annually thereafter.
Loose power connections can cause voltage spikes, over­heating, malfunctioning, or failures.
Check Pressure Transducers — Once a year, the
pressure transducers should be checked against a pressure gage reading. Check all three transducers: oil pressure, con­denser pressure, cooler pressure.
Note the evaporator and condenser pressure readings on the Status01 table on the LID. Attach an accurate set of refrigeration gages to the cooler and condenser Schrader fittings. Compare the two readings. If there is a difference in readings, the transducer can be calibrated, as described in the Troubleshooting Guide section.
OPTIONAL PUMPOUT SAFETY CONTROL SETTINGS (Fig. 38) — The optional pumpout system high-pressure switch should open at 220 ± 5 psig (1517 ± 34 kPa) and should reset automatically on pressure drop to 190 psig (1310 kPa) for HCFC-22 chillers. For chillers using HFC-134a, the switch opens at 161 psig (1110 kPa) and closes at 130 psig (896 kPa). Check the switch setting by operating the pumpout compressor and slowly throttling the pumpout condenser water.
Fig. 38 — Optional Pumpout System
Controls
Optional Pumpout System Maintenance —
For compressor maintenance details, refer to the 06D, 07D Installation, Start-Up, and Service Instructions.
OPTIONALPUMPOUT COMPRESSOR OILCHARGE — The pumpout compressor uses oil with the same specifi­cations as the centrifugal compressor oil. For more details on oil selection, see Oil Specification section, page 63.
The total oil charge, 4.5 pints (2.6 L), consists of
3.5 pints (2.0 L) for the compressor and one additional pint (0.6 L) for the oil separator.
Ordering Replacement Chiller Parts — When
ordering Carrier specified parts, the following information must accompany an order:
• chiller model number and serial number
• name, quantity, and part number of the part required
• delivery address and method of shipment.
65
Page 66
TROUBLESHOOTING GUIDE
Overview —
operator and the technician in troubleshooting a 19XL chiller.
• By using the LID display, the chiller actual operating con­ditions can be viewed while the unit is running.
• When an alarm occurs, the default LID screen will freeze at the time of alarm. The freeze enables the operator to view the chiller conditions at the time of alarm. The Status tables will still show the current information. Once all alarms have been cleared, the default LID screens will return to normal operation.
• The Control Algorithm Status tables will display various screens of information in order to diagnose problems with chilled water temperature control, chilled water temper­ature control overrides, hot gas bypass, surge algorithm status, and time schedule operation.
• The Control Test feature allows proper operation and test­ing of temperature sensors, pressure transducers, the guide vane actuator, oil pump, water pumps, tower control, and other on/off outputs while the compressor is stopped. It also has the ability to lock off the compressor and turn on water pumps for pumpout operation. The display will show the required temperatures and pressures during these operations.
• Other Service menu tables can access configured items, such as chilled water resets, override set points, etc.
• If an operating fault is detected, an alarm message is gen­erated and displayed on the LID default screen. A more detailed message — along with a diagnostic message — also is stored into the Alarm History table.
The PIC has many features to aid the
Checking the Display Messages — The first area
to check when troubleshooting the 19XL is the LID display. If the alarm light is flashing, check the primary and second­ary message lines on the LID default screen (Fig. 13). These messages will indicate where the fault is occurring. The Alarm History table on the LID Service menu will also carry an alarm message to further expand on this alarm. For a com­plete listing of messages, see Table 9. If the alarm light starts to flash while accessing a menu screen, depress
EXIT
to return to the Default screen to read the failure
message. The compressor will not run with an alarm con­dition existing, unless the alarm type is an unauthorized start or a failure to shut down.
Checking Temperature Sensors — All tempera-
ture sensors are of the thermistor type. This means that the resistance of the sensor varies with temperature. All sensors have the same resistance characteristics. Determine sensor temperature by measuring voltage drop if the controls are powered, or resistance if the controls are powered off. Com­pare the readings to the values listed in Tables 10A or 10B.
RESISTANCE CHECK — Turn off the control power and disconnect the terminal plug of the sensor in question from the module. Measure sensor resistance between recep­tacles designated by the wiring diagram with a digital ohm­meter.The resistance and corresponding temperature is listed in Tables 10A or 10B. Check the resistance of both wires to ground. This resistance should be infinite.
VOLTAGE DROP — Using a digital voltmeter, the voltage drop across any energized sensor can be measured while the control is energized. Tables 10A or 10B lists the relation­ship between temperature and sensor voltage drop (volts dc measured across the energized sensor). Exercise care when measuring voltage to prevent damage to the sensor leads, connector plugs, and modules. Sensors should also be checked
at the sensor plugs. Check the sensor wire at the sensor for 5 vdc if the control is powered.
Relieve all refrigerant pressure or drain the water prior to replacing the temperature sensors.
CHECK SENSOR ACCURACY — Place the sensor in a medium of a known temperature and compare that temper­ature to the measured reading. The thermometer used to determine the temperature of the medium should be of lab­oratory quality with 0.5° F (.25° C) graduations. The sensor in question should be accurate to within 2° F (1.2° C).
See Fig. 8 for sensor locations. The sensors are immersed directly in the refrigerant or water circuits. The wiring at each sensor is easily disconnected by unlatching the connector. These connectors allow only one-way connection to the sensor.When installing a new sensor, apply a pipe sealant or thread sealant to the sensor threads.
DUAL TEMPERATURE SENSORS — There are 2 sensors each on the bearing and motor temperature sensors for servicing convenience. In case one of the dual sensors is damaged, the other one can be used by moving a wire.
The number 2 terminal in the sensor terminal box is the common line. To use the second sensor, move the wire from the number 1 position to the number 3 position.
Checking Pressure Transducers — There are 3
pressure transducers on the 19XL. These determine cooler, condenser, and oil pressure. The cooler and condenser trans­ducers also are used by the PIC to determine the refrigerant temperatures. All 3 can be calibrated if necessary. It is not usually necessary to calibrate at initial start-up. However, at high altitude locations, calibration of the transducer will be necessary to ensure the proper refrigerant temperature/ pressure relationship. Each transducer is supplied with 5 vdc power from a power supply. If the power supply fails, a transducer voltage reference alarm will occur. If the trans­ducer reading is suspected of being faulty, check the supply voltage. It should be 5 vdc ± .5 v. If the supply voltage is correct, the transducer should be recalibrated or replaced.
IMPORTANT:Whenever the oil pressure or the cooler pressure transducer is calibrated, the other sensor should be calibrated to prevent problems with oil differential pressure readings.
Calibration can be checked by comparing the pressure readings from the transducer against an accurate refrig­eration gage. These readings are all viewed or calibrated from the Status01 table on the LID. The transducer can be checked and calibrated at 2 pressure points. These calibration points are 0 psig (0 kPa) and between 240 and 260 psig (1655 to 1793 kPa). To calibrate these transducers:
1. Shut down the compressor.
2. Disconnect the transducer in question from its Schrader
fitting. NOTE: If the cooler or condenser vessels are at 0 psig
(0 kPa) or are open to atmospheric pressure, the trans­ducers can be calibrated for zero without removing the transducer from the vessel.
3. Access the Status01 table, and view the particular trans-
ducer reading; it should read 0 psi (0 kPa). If the reading is not 0 psi (0 kPa), but within ± 5 psi (35 kPa), the value
may be zeroed by pressing the SELECT the highlight bar is located on the transducer, and then by pressing the ENTER
. The value will now go to zero.
softkey while
66
Page 67
If the transducer value is not within the calibration range, the transducer will return to the original reading. If the LID pressure value is within the allowed range (noted above), check the voltage ratio of the transducer. To ob­tain the voltage ratio, divide the voltage (dc) input from the transducer by the supply voltage signal, measured at the PSIO terminals J7-J34 and J7-J35. For example, the condenser transducer voltage input is measured at PSIO terminals J7-1 and J7-2. The voltage ratio must be be­tween 0.80 vdc and 0.11 vdc for the software to allow calibration. Pressurize the transducer until the ratio is within range. Then attempt calibration again.
4. A high pressure point can also be calibrated between 240 and 260 psig (1655 and 1793 kPa) by attaching a regulated 250 psig (1724 kPa) pressure (usually from a nitrogen cylinder). The high pressure point can be cali­brated by accessing the transducer on the Status01 screen,
highlighting the transducer, pressing the SELECT soft­key, and then increasing or decreasing the value to the exact pressure on the refrigerant gage. Press ENTER to finish. High altitude locations must compensate the
pressure so that the temperature/pressure relationship is correct.
If the transducer reading returns to the previous value and the pressure is within the allowed range, check the volt­age ratio of the transducer. Refer to Step 3 above. The voltage ratio for this high pressure calibration must be between 0.585 and 0.634 vdc to allow calibration. Change the pressure at the transducer until the ratio is within the acceptable range. Then attempt calibrate to the new pres­sure input.
The PIC will not allow calibration if the transducer is too far out of calibration. A new transducer must be installed and re-calibrated.
TRANSDUCER REPLACEMENT — Since the transduc­ers are mounted on Schrader-type fittings, there is no need to remove refrigerant from the vessel. Disconnect the trans­ducer wiring by pulling up on the locking tab while pulling up on the weather-tight connecting plug from the end of the transducer. Do not pull on the transducer wires. Unscrew the transducer from the Schrader fitting. When installing a new transducer, do not use pipe sealer, which can plug the sensor. Put the plug connector back on the sensor and snap into place. Check for refrigerant leaks.
Make sure to use a backup wrench on the Schrader fit­ting whenever removing a transducer.
ControlAlgorithms Checkout Procedure — The
Control Algorithm Status table is in the LID Service menu. The ControlAlgorithm Status table contains maintenance tables that may be viewed in order to see how the particular control algorithm is operating. The tables are:
MAINT01 Capacity
MAINT02 Override MAINT03 Surge/
MAINT04 (PSIO Software Version 09 and Higher)
OCCDEFM Time
WSMDEFME Water
Control
Status HGBP
Status LEAD/LAG
Status
Schedules Status
System Manager Status
This table shows all values that are used to calculate the chilled water/brine control point.
Details of all chilled water control override values are viewed here.
The surge and hot gas bypass control algorithm status is viewed from this screen. All values deal­ing with this control are displayed.
This screen indicates LEAD/LAG operation status.
The Local and CCN occupied schedules are displayed here in a manner that the operator can quickly determine whether the schedule is in the OCCUPIED mode or not.
The water system manager is a CCN module which can turn on the chiller and change the chilled water control point. This screen indicates the status of this system.
These maintenance tables are very useful in determining how the control temperature is calculated, the position of the guide vane, reaction from load changes, control point over­rides, hot gas bypass reaction, surge prevention, etc.
Control Test — The Control Test feature can check all
of the thermistor temperature sensors, including those on the Options modules, pressure transducers, pumps and their associated flow switches, the guide vane actuator, and other control outputs, such as hot gas bypass. The tests can help to determine whether a switch is defective, or a pump relay is not operating, among other useful troubleshooting tests. During pumpdown operations, the pumps are energized to prevent freeze-up and the vessel pressures and temperatures are displayed. The lockout feature will prevent start-up of the compressor when no refrigerant is present in the chiller, or if the vessels are isolated. The lockout is then terminated by the operator by using the Terminate Lockout function after the pumpdown procedure is reversed and refrigerant is added.
67
Page 68
Table 9 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides
A. SHUTDOWN WITH ON/OFF/RESET-OFF
PRIMARY MESSAGE SECONDARY MESSAGE PROBABLE CAUSE/REMEDY
MANUALLY STOPPED — PRESS CCN OR LOCAL TO START TERMINATE PUMPDOWN MODE TO SELECT CCN OR LOCAL SHUTDOWN IN PROGRESS COMPRESSOR UNLOADING SHUTDOWN IN PROGRESS COMPRESSOR DEENERGIZED
ICE BUILD OPERATION COMPLETE Chiller shutdown from Ice Build operation.
B. TIMING OUT OR TIMED OUT
PRIMARY MESSAGE SECONDARY MESSAGE PROBABLE CAUSE/REMEDY
READY TO START IN XX MIN UNOCCUPIED MODE READY TO START IN XX MIN REMOTE CONTACTS OPEN READY TO START IN XX MIN STOP COMMAND IN EFFECT
READY TO START IN XX MIN RECYCLE RESTART PENDING Chiller in recycle mode. READY TO START UNOCCUPIED MODE
READY TO START REMOTE CONTACTS OPEN READY TO START STOP COMMAND IN EFFECT
READY TO START IN XX MIN REMOTE CONTACTS CLOSED Chiller timer counting down unit. Ready for start. READY TO START IN XX MIN OCCUPIED MODE Chiller timer counting down unit. Ready for start. READY TO START REMOTE CONTACTS CLOSED Chiller timers complete, unit start will commence. READY TO START OCCUPIED MODE Chiller timers complete, unit start will commence.
STARTUP INHIBITED LOADSHED IN EFFECT
READY TO START IN XX MIN START COMMAND IN EFFECT
PIC in OFF mode, press the CCN or local softkey to start unit.
Enter the Control Test table and select Terminate Lockout to unlock compressor.
Chiller unloading before shutdown due to Soft Stop feature.
Chiller compressor is being commanded to stop. Water pumps are deenergized within one minute.
Time schedule for PIC is unoccupied. Chillers will start only when occupied.
Remote contacts have stopped chiller. Close con­tacts to start.
Chiller START/STOP on Status01 manually forced to stop. Release value to start.
Time schedule for PIC is UNOCCUPIED. Chiller will start when occupied. Make sure the time and date have been set on the Service menu.
Remote contacts have stopped chiller. Close con­tacts to start.
Chiller START/STOP on Status01 manually forced to stop. Release value to start.
CCN loadshed module commanding chiller to stop.
Chiller START/STOP on Status01 has been manually forced to start. Chiller will start regard­less of time schedule or remote contact status.
1CR AUX Compressor Start Contact CA P CCN Carrier Comfort Network CDFL Condenser Water Flow CHIL S S CHW Chilled Water CHWS Chilled Water Supply CHWR Chiller Water Return CMPD Discharge Temperature CRP Condenser Pressure CRT Condenser Refrigerant
Compressor Current
Chiller Start/Stop
Temperature
LEGEND
ECW Entering Chilled Water ERT Evaporator Refrigerant
EVFL Chilled Water Flow GV TRG LID Local Interface Device MTRB Bearing Temperature MTRW Motor Winding Temperature OILPD Oil Pressure OILT Oil Sump Temperature PIC Product Integrated Control
Temperature
Target Guide Vane Position
68
PSIO Processor Sensor RLA Rated Load Amps
RUN AUX SPR PL SMM Starter Management
STR FLT TXV Thermostatic Expansion
VP V REF Voltage Reference
Input/Output Module
Compressor Run ContactSpare Protective Limit Input
Module
Starter Fault
Valve
Line Voltage: Percent
Page 69
Table 9 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides (cont)
C. IN RECYCLE SHUTDOWN
PRIMARY MESSAGE SECONDARY MESSAGE PROBABLE CAUSE/REMEDY
RECYCLE RESTART PENDING OCCUPIED MODE RECYCLE RESTART PENDING REMOTE CONTACT CLOSED
RECYCLE RESTART PENDING START COMMAND IN EFFECT
RECYCLE RESTART PENDING ICE BUILD MODE
D. PRE-STARTALERTS:These alerts only delay start-up. When alert is corrected, the start-up will continue. No reset is necessary.
PRIMARY MESSAGE SECONDARY MESSAGE ALARM MESSAGE/PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY PRESTART ALERT STARTS LIMIT EXCEEDED
PRESTART ALERT HIGH MOTOR TEMPERATURE
PRESTART ALERT HIGH BEARING TEMPERATURE
PRESTART ALERT HIGH DISCHARGE TEMP
PRESTART ALERT LOW REFRIGERANT TEMP
PRESTART ALERT LOW OIL TEMPERATURE
PRESTART ALERT LOW LINE VOLTAGE
PRESTART ALERT HIGH LINE VOLTAGE
PRESTART ALERT HIGH CONDENSER PRESSURE
*[LIMIT] is shown on the LID as temperature, pressure, voltage, etc., predefined or selected by the operator as an override or an alert. [VALUE] is
the actual temperature, pressure, voltage, etc., at which the control tripped.
STARTS EXCESSIVE Compressor Starts (8 in 12 hours)
MTRW [VALUE]* exceeded limit of [LIMIT]*. Check motor temperature.
MTRB [VALUE]* exceeded limit of [LIMIT]*. Check thrust bearing temperature.
CMPD [VALUE]* exceeded limit of [LIMIT]*. Check discharge temperature.
ERT [VALUE]* exceeded limit of [LIMIT]*. Check refrigerant temperature.
OILT [VALUE]* exceeded limit of [LIMIT]*. Check oil temperature.
V P [VALUE]* exceeded limit of [LIMIT]*. Check voltage suppy.
V P [VALUE]* exceeded limit of [LIMIT]*. Check voltage supply.
CRP [VALUE]* exceeded limit of [LIMIT]*. Check condenser water and transducer.
Unit in recycle mode, chilled water temperature is not high enough to start.
Unit in recycle mode, chilled water temperature is not high enough to start.
Chiller START/STOP on Status01 manually forced to start, chilled water temperature is not high enough to start.
Chiller in ICE BUILD mode. Chilled Water/Brine Tem­perature is satisfied for Ice Build Setpoint temperature.
Depress the RESET softkey if addi­tional start is required. Reassess start-up requirements.
Check motor cooling line for proper operation. Check for excessive starts within a short time span.
Check oil heater for proper opera­tion, check for low oil level, partially closed oil supply valves, etc. Check sensor accuracy.
Check sensor accuracy.Allow dis­charge temperature to cool. Check for excessive starts.
Check transducer accuracy. Check for low chilled water/brine supply temperature.
Check oil heater power, oil heater relay. Check oil level.
Check voltage supply. Check volt­age transformers. Consult power utility if voltage is low. Adjust voltage potentiometer in starter for SMM voltage input.
Check voltage supply. Check volt­age transformers. Consult power utility if voltage is low. Adjust voltage potentiometer in starter for SMM voltage input.
Check for high condenser water temperature. Check transducer accuracy.
E. NORMAL OR AUTO.-RESTART
PRIMARY MESSAGE SECONDARY MESSAGE PROBABLE CAUSE/REMEDY
STARTUP IN PROGRESS OCCUPIED MODE Chiller starting. Time schedule is occupied. STARTUP IN PROGRESS REMOTE CONTACT CLOSED Chiller starting. Remote contacts are closed.
STARTUP IN PROGRESS START COMMAND IN EFFECT AUTORESTART IN PROGRESS OCCUPIED MODE Chiller starting. Time schedule is occupied.
AUTORESTART IN PROGRESS REMOTE CONTACT CLOSED Chiller starting. Remote contacts are closed. AUTORESTART IN PROGRESS START COMMAND IN EFFECT
NOTE: See Legend on page 68.
Chiller starting. Chiller START/STOP on Status01 manu­ally forced to start.
Chiller starting. Chiller START/STOP on Status01 manu­ally forced to start.
69
Page 70
Table 9 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides (cont)
F. START-UP FAILURES: This is an alarm condition. A manual reset is required to clear.
PRIMARY MESSAGE SECONDARY MESSAGE ALARM MESSAGE/PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY FAILURE TO START LOW OIL PRESSURE
FAILURE TO START OIL PRESS SENSOR FAULT
FAILURE TO START
FAILURE TO START
FAILURE TO START STARTER FAULT
FAILURE TO START STARTER OVERLOAD TRIP
FAILURE TO START LINE VOLTAGE DROPOUT
FAILURE TO START
FAILURE TO START
FAILURE TO START FAILURE TO START 1CR AUX CONTACT FAULT
FAILURE TO START MOTOR AMPS NOT SENSED
FAILURE TO START
FAILURE TO START LOW OIL PRESSURE
*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped. [OPEN] indicates that an input circuit is open.
NOTE: See Legend on page 68.
LOW CHILLED WATER FLOW
LOW CONDENSER WATER FLOW
HIGH CONDENSER PRESSURE
EXCESS ACCELERATION TIME
STARTER TRANSITION FAULT
CHECK REFRIGERANT TYPE
OILPD [VALUE] exceeded limit of [LIMIT]*. Check oil pump system.
OILPD [VALUE] exceeded limit of [LIMIT]*. Check oil pressure sensor.
EVFL Evap Flow Fault: Check water pump/flow switch.
CDFL Cond. Flow Fault: Check water pump/flow switch.
STR FLT Starter Fault: Check Starter for Fault Source.
STR FLT Starter Overload Trip: Check amps calibration/reset overload.
V P Single-Cycle Dropout Detected: Check voltage supply.
High Condenser Pressure [OPEN]*: Check switch, oil pressure contact, and water temperature/flow.
High Condenser Pressure [VALUE]*: Check switch, water flow, and transducer.
CA P Excess Acceleration: Check guide vane closure at start-up.
RUN AUX Starter Transition Fault: Check 1CR/1M/Interlock mechanism.
1CR AUX Starter Contact Fault: Check 1CR/1M aux. contacts.
CA P Motor Amps Not Sensed: Check motor load signal.
Current Refrigerant Properties Abnormal — Check Selection of refrigerant type
Low Oil Pressure [LIMIT]*: Check oil pressure switch/pump and 2C aux.
Check for closed oil supply valves. Check oil filter. Check for low oil temperature. Check transducer accuracy.
Check for excessive refrigerant in oil sump. Run oil pump manually for 5 minutes. Check transducer calibration. Check cooler pressure transducer calibration. Check wiring. Replace transducer if necessary.
Check wiring to flow switch. Check through Control Test for proper switch operation.
Check wiring to flow switch. Check through Control Test for proper switch operation.
A starter protective device has faulted. Check starter for ground fault, voltage trip, temperature trip, etc.
Reset overloads before restart. Check voltage supply. Check transformers
for supply. Check with utility if voltage supply is erratic. Monitor must be installed to confirm consistent, single-cycle drop­outs. Check low oil pressure switch.
Check the high-pressure switch. Check for proper condenser pressures and con­denser waterflow. Check for fouled tubes. Check the 2C aux contact and the oil pressure switch in the power panel. This alarm is not caused by the transducer.
Check water flow in condenser. Check for fouled tubes. Transducer should be checked for accuracy. This alarm is not caused by the high pressure switch.
Check that guide vanes are closed at start-up. Check starter for proper operation. Reduce unit pressure if possible.
Check starter for proper operation. Run contact failed to close.
Check starter for proper operation. Start contact failed to close.
Check for proper motor amps signal to SMM. Check wiring from SMM to current transformer. Check main motor circuit breaker for trip.
Pressures at transducers indicate another refrigerant type in Control Test. Make sure to access the ATTACH TO NETWORK DEVICE table after changing refrigerant type.
The oil pressure differential switch is open when the compressor tried to START. Check the switch for proper operation. Also, check the oil pump interlock (2C aux) in the power panel and the high condenser pressure switch.
70
Page 71
Table 9 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides (cont)
G. COMPRESSOR JUMPSTART AND REFRIGERANT PROTECTION
PRIMARY MESSAGE SECONDARY MESSAGE ALARM MESSAGE/PRIMARYCAUSE ADDITIONAL CAUSE/REMEDY
Compressor is running with more than
UNAUTHORIZED OPERATION
POTENTIAL FREEZE-UP
FAILURE TO STOP DISCONNECT POWER
LOSS OF COMMUNCIATION
STARTER CONTACT FAULT
POTENTIAL FREEZE UP
*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
UNIT SHOULD BE STOPPED
EVAP PRESS/TEMP TOO LOW
WITH STARTER ABNORMAL 1CR OR
RUN AUX
COND PRESS/TEMP TOO LOW
CA P Emergency: Compressor running without control authorization.
ERT Emergency: Freeze-up prevention.
RUN AUX Emergency: DISCON­NECT POWER.
Loss of Communication with Starter: Check chiller.
1CR AUX Starter Contact Fault: Check 1CR/1M aux. contacts.
CRT [VALUE] exceeded limit of [LIMIT]* Emergency: Freeze-up
prevention.
10% RLA and control is trying to shut it down. Throw power off to compressor if unable to stop. Determine cause before repowering.
Determine cause. If pumping refrigerant out of chiller, stop operation and go over pumpout procedures.
Starter and run and start contacts are energized while control tried to shut down. Disconnect power to starter.
Check wiring from PSIO to SMM. Check SMM module troubleshooting procedures.
Starter run and start contacts energized while chiller was off. Disconnect power.
The condenser pressure transducer is reading a pressure that could freeze the water in the condenser tubes. Check for condenser refrigerant leaks, bad trans­ducers, or transferred refrigerant. Place the unit in Pumpdown mode to eliminate ALARM if vessel is evacuated.
H. NORMAL RUN WITH RESET, TEMPERATURE, OR DEMAND
PRIMARY MESSAGE SECONDARY MESSAGE PROBABLE CAUSE/REMEDY
RUNNING — RESET ACTIVE 4-20MA SIGNAL
Reset program active based upon Config table setup.RUNNING — RESET ACTIVE REMOTE SENSOR CONTROL RUNNING — RESET ACTIVE CHW TEMP DIFFERENCE RUNNING — TEMP CONTROL LEAVING CHILLED WATER Default method of temperature control. RUNNING — TEMP CONTROL ENTERING CHILLED WATER ECW control activated on Config table. RUNNING — TEMP CONTROL TEMPERATURE RAMP LOADING Ramp loading in effect. Use Service1 table to modify. RUNNING — DEMAND LIMITED BY DEMAND RAMP LOADING Ramp loading in effect. Use Service1 table to modify. RUNNING — DEMAND LIMITED BY LOCAL DEMAND SETPOINT Demand limit setpoint is , actual demand. RUNNING — DEMAND LIMITED BY 4-20MA SIGNAL
Demand limit is active based on Config table setup.RUNNING — DEMAND LIMITED BY CCN SIGNAL RUNNING — DEMAND LIMITED BY LOADSHED/REDLINE
RUNNING — TEMP CONTROL HOT GAS BYPASS RUNNING — DEMAND LIMITED BY LOCAL SIGNAL
RUNNING — TEMP CONTROL ICE BUILD MODE Chiller is running under Ice Build temperature control.
NOTE: See Legend on page 68.
Hot Gas Bypass is energized. See surge prevention
in the control section.
Active demand limit manually overridden or Status01
table.
71
Page 72
Table 9 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides (cont)
I. NORMAL RUN OVERRIDES ACTIVE (ALERTS)
PRIMARY MESSAGE SECONDARY MESSAGE ALARM MESSAGE/PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY RUN CAPACITY
LIMITED
RUN CAPACITY
LIMITED
RUN CAPACITY
LIMITED
RUN CAPACITY
LIMITED
RUN CAPACITY
LIMITED
*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual temperature, pressure, voltage, etc., at which the control tripped.
HIGH CONDENSER PRESSURE HIGH MOTOR TEMPERATURE LOW EVAP REFRIG TEMP HIGH COMPRESSOR LIFT MANUAL GUIDE VANE TARGET
J. OUT-OF-RANGE SENSOR FAILURES
PRIMARY MESSAGE SECONDARY MESSAGE ALARM MESSAGE/PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY SENSOR FAULT LEAVING CHW TEMPERATURE
SENSOR FAULT ENTERING CHW TEMPERATURE SENSOR FAULT CONDENSER PRESSURE SENSOR FAULT EVAPORATOR PRESSURE SENSOR FAULT BEARING TEMPERATURE SENSOR FAULT MOTOR WINDING TEMP SENSOR FAULT DISCHARGE TEMPERATURE SENSOR FAULT OIL SUMP TEMPERATURE SENSOR FAULT OIL PRESSURE TRANSDUCER
NOTE: See Legend on page 68.
CRP [VALUE]* exceeded limit of [LIMIT]*. Condenser pressure override.
MTRW [VALUE]* exceeded limit of [LIMIT]*. Motor temperature override.
ERT [VALUE]* exceeded limit of [LIMIT]*. Check refrigerant charge level.
Surge Prevention Override; lift too high for compressor.
GV TRG Run Capacity Limited: Manual guide vane target.
Sensor Fault: Check leaving CHW sensor.
Sensor Fault: Check entering CHW sensor.
Sensor Fault: Check condenser pressure transducer.
Sensor Fault: Check evaporator pressure transducer.
Sensor Fault: Check bearing temperature sensor.
Sensor Fault: Check motor temperature sensor.
Sensor Fault: Check discharge temperature sensor.
Sensor Fault: Check oil sump temperature sensor.
Sensor Fault: Check oil pressure transducer.
See Capacity Overrides, Table 4. Correct operating condition, modify setpoint, or release override.
See sensor test procedure and check sensors for proper operation and wiring.
72
Page 73
Table 9 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides (cont)
K. CHILLER PROTECT LIMIT FAULTS
Excessive numbers of the same fault can lead to severe chiller damage. Seek service expertise.
PRIMARY MESSAGE SECONDARYMESSAGE ALARM MESSAGE/PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY
PROTECTIVE LIMIT
PROTECTIVE LIMIT
PROTECTIVE LIMIT
PROTECTIVE LIMIT
PROTECTIVE LIMIT LOW OIL PRESSURE
PROTECTIVE LIMIT NO MOTOR CURRENT
PROTECTIVE LIMIT POWER LOSS PROTECTIVE LIMIT LOW LINE VOLTAGE PROTECTIVE LIMIT HIGH LINE VOLTAGE PROTECTIVE LIMIT PROTECTIVE LIMIT
PROTECTIVE LIMIT
PROTECTIVE LIMIT PROTECTIVE LIMIT
PROTECTIVE LIMIT CCN OVERRIDE STOP
PROTECTIVE LIMIT
PROTECTIVE LIMIT
PROTECTIVE LIMIT PROTECTIVE LIMIT STARTER FAULT
PROTECTIVE LIMIT
PROTECTIVE LIMIT
*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm
condition. [VALUE] is the actual temperature, pressure, voltage, etc., at which the control tripped. [OPEN] indicates that an input circuit is open.
NOTE: See Legend on page 68.
HIGH DISCHARGE TEMP
LOW REFRIGERANT TEMP
HIGH MOTOR TEMPERATURE
HIGH BEARING TEMPERATURE
LOW CHILLED WATER FLOW
LOW CONDENSER WATER FLOW
HIGH CONDENSER PRESSURE
1CR AUX CONTACT FAULT
RUN AUX CONTACT FAULT
SPARE SAFETY DEVICE
EXCESSIVE MOTOR AMPS
EXCESSIVE COMPR SURGE
STARTER OVERLOAD TRIP
TRANSDUCER VOLTAGE FAULT
CMPD [VALUE] exceeded limit of [LIMIT]*. Check discharge temperature.
ERT [VALUE] exceeded limit of [LIMIT]*. Check evap pump and flow switch.
MTRW [VALUE] exceeded limit of [LIMIT]*. Check motor cooling and solenoid.
MTRB [VALUE] exceeded limit of [LIMIT]*. Check oil cooling control.
OILPD [VALUE] exceeded limit of [LIMIT]*. Check oil pump and transducer.
Low Oil Pressure [OPEN]*. Check oil pressure switch/pump and 2C aux.
CA P Loss of Motor Current: Check sensor.
V P Power Loss: Check voltage supply.
V P [VALUE] exceeded limit of [LIMIT]*. Check voltage supply.
V P [VALUE] exceeded limit of [LIMIT]*. Check voltage supply.
EVFL Flow Fault: Check evap pump/flow switch.
CDFL Flow Fault: Check cond pump/ flow switch.
High Cond Pressure [OPEN]*. Check switch, oil pressure contact, and water temp/flow.
High Cond Pressure [VALUE]: Check switch, water flow, and transducer.
1CR AUX Starter Contact Fault: Check 1CR/1M aux contacts.
RUN AUX Starter Contact Fault Check 1CR/1M aux contacts.
CHIL S S CCN Override Stop while in LOCAL run mode.
SRP PL Spare Safety Fault: Check contacts.
CA P [VALUE] exceeded limit of [LIMIT]*. High Amps; Check guide vane drive.
Compressor Surge: Check condenser water temp and flow.
STR FLT Starter Fault: Check starter for fault source.
STR FLT Starter Overload Trip: Check amps calibration/reset overload.
V REF [VALUE] exceeded limit of [LIMIT]*. Check transducer power supply.
Check discharge temperature immediately. Check sen­sor for accuracy; check for proper condenser flow and temperature; check oil reservoir temperature. Check condenser for fouled tubes or air in chiller. Check for proper guide vane actuator operation.
Check for proper amount of refrigerant charge; check for proper water flow and temperatures. Check for proper guide vane actuator operation.
Check motor temperature immediately. Check sensor for accuracy. Check for proper condenser flow and temperature. Check motor cooling system for restric­tions. Check motor cooling solenoid for proper opera­tion. Check refrigerant filter.
Check for throttled oil supply isolation valves. Valves should be wide open. Check oil cooler thermal expan­sion valve. Check sensor accuracy. Check journal and thrust bearings. Check refrigerant filter. Check for ex­cessive oil sump level.
Check power to oil pump and oil level. Check for dirty filters or oil foaming at start-up. Check for thermal overload cutout. Reduce ramp load rate if foaming noted.
NOTE: This alarm is not related to pressure switch problems.
Check the oil pressure switch for proper operation. Check oil pump for proper pressure. Check for exces­sive refrigerant in oil system.
Check wiring: Check torque setting on solid-state starter. Check for main circuit breaker trip. Check power supply to PSIO module.
Check 24-vdc input sensor on the SMM; adjust potenti­ometer if necessary. Check transformers to SMM. Check power to PSIO module. Check distribution bus. Consult power company.
Perform pumps Control Test and verify proper switch operation. Check all water valves and pump operation.
Check the high-pressure switch. Check for proper con­denser pressures and condenser waterflow. Check for fouled tubes. Check the 2C aux. contact and the oil pressure switch in the power panel. This alarm is not caused by the transducer.
Check water flow in condenser. Check for fouled tubes. Transducer should be checked for accuracy. This alarm is not caused by the high pressure switch.
1CR auxiliary contact opened while chiller was run­ning. Check starter for proper operation.
Run auxiliary contact opened while chiller was running. Check starter for proper operation.
CCN has signaled chiller to stop. Reset and restart when ready. If the signal was sent by the LID, release the Stop signal on STATUS01 table.
Spare safety input has tripped or factory-installed jumper not present.
Check motor current for proper calibration. Check guide vane drive and actuator for proper operation.
Check condenser flow and temperatures. Check con­figuration of surge protection.
Check starter for possible ground fault, reverse rota­tion, voltage trip, etc.
Reset overloads and reset alarm. Check motor current calibration or overload calibration (do not field-calibrate overloads).
Check transformer power (5 vdc) supply to trans­ducers. Power must be 4.5 to 5.5 vdc.
73
Page 74
Table 9 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides (cont)
L. CHILLER ALERTS
PRIMARY MESSAGE SECONDARY MESSAGE ALARM MESSAGE/PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY
RECYCLE ALERT HIGH AMPS AT SHUTDOWN
SENSOR FAULT ALERT
SENSOR FAULT ALERT LOW OIL PRESSURE
ALERT AUTORESTART PENDING POWER LOSS V P Power Loss: Check voltage supply.
AUTORESTART PENDING LOW LINE VOLTAGE AUTORESTART PENDING HIGH LINE VOLTAGE
SENSOR ALERT HIGH DISCHARGE TEMP
SENSOR ALERT
CONDENSER PRESSURE ALERT
RECYCLE ALERT
*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual temperature, pressure, voltage, etc., at which the control tripped.
LEAVING COND WATER TEMP
ENTERING COND WATER TEMP
CHECK OIL FILTER Low Oil Pressure Alert: Check oil
HIGH BEARING TEMPERATURE
PUMP RELAY ENERGIZED
EXCESSIVE RECYCLE STARTS
High Amps at Recycle: Check guide vane drive.
Sensor Fault: Check leaving condenser water sensor.
Sensor Fault: Check entering condenser water sensor.
V P [VALUE]* exceeded limit of [LIMIT].* Check voltage supply.
V P [VALUE]* exceeded limit of [LIMIT].* Check voltage supply.
CMPD [VALUE]* exceeded limit of [LIMIT].* Check discharge temperature.
MTRB [VALUE]* exceeded limit of [LIMIT]*. Check thrust bearing temperature.
CRP High Condenser Pressure [LIMIT]*. Pump energized to reduce pressure.
Excessive recycle starts.
Check that guide vanes are closing. Check motor amps correction cali­bration is correct. Check actuator for proper operation.
Check sensor. See sensor test procedure.
Check oil filter. Check for improper oil level or temperature.
Check power supply if there are ex­cessive compressor starts occurring.
Discharge temperature exceeded the alert threshold. Check entering condenser water temperature.
Thrust bearing temperature ex­ceeded the alert threshold. Check for closed valves, improper oil level or temperatures.
Check ambient conditions. Check condenser pressure for accuracy.
The chiller load is too small to keep the chiller on line and there have been more than 5 restarts in 4 hours. Increase chiller load, adjust hot gas bypass, increase RECYCLE RESTART DELTA T.
M. SPARE SENSOR ALERT MESSAGES
PRIMARY MESSAGE SECONDARY MESSAGE ALARM MESSAGE/PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY
SPARE SENSOR ALERT COMMON CHWS SENSOR SPARE SENSOR ALERT COMMON CHWR SENSOR SPARE SENSOR ALERT REMOTE RESET SENSOR SPARE SENSOR ALERT TEMP SENSOR — SPARE 1 SPARE SENSOR ALERT TEMP SENSOR — SPARE 2 SPARE SENSOR ALERT TEMP SENSOR — SPARE 3 SPARE SENSOR ALERT TEMP SENSOR — SPARE 4 SPARE SENSOR ALERT TEMP SENSOR — SPARE 5 SPARE SENSOR ALERT TEMP SENSOR — SPARE 6 SPARE SENSOR ALERT TEMP SENSOR — SPARE 7 SPARE SENSOR ALERT TEMP SENSOR — SPARE 8 SPARE SENSOR ALERT TEMP SENSOR — SPARE 9
NOTE: See Legend on page 68.
Sensor Fault: Check common CHWS sensor.
Sensor Fault: Check common CHWR sensor.
Sensor Fault: Check remote reset temperature sensor.
Sensor Fault: Check temperature sensor — Spare 1.
Sensor Fault: Check temperature sensor — Spare 2.
Sensor Fault: Check temperature sensor — Spare 3.
Sensor Fault: Check temperature sensor — Spare 4.
Sensor Fault: Check temperature sensor — Spare 5.
Sensor Fault: Check temperature sensor — Spare 6.
Sensor Fault: Check temperature sensor — Spare 7.
Sensor Fault: Check temperature sensor — Spare 8.
Sensor Fault: Check temperature sensor — Spare 9.
Check alert temperature set points on Equipment Service, SERVICE2 LID table. Check sensor for accu­racy if reading is not accurate.
74
Page 75
Table 9 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
N. OTHER PROBLEMS/MALFUNCTIONS
DESCRIPTION/MALFUNCTION PROBABLE CAUSE/REMEDY
Chilled Water/Brine Temperature Too High (Machine Running)
Chilled Water/Brine Temperature Too Low (Machine Running)
Chilled Water Temperature Fluctuates. Vanes Hunt
Low Oil Sump Temperature While Running (Less than 100 F [38 C])
At Power Up, Default Screen Does Not Appear, ‘‘Tables Loading’’ Message Continually Appears
SMM Communications Failure
High Oil Temperature While Running
Blank LID Screen
‘‘Communications Failure’’ Highlighted Message At Bottom of LID Screen
Controls Test Disabled
Vanes Will Not Open In Control Test
Oil Pump Does Not Run
NOTE: See Legend on page 68.
with Troubleshooting Guides (cont)
Chilled water set point set too high. Access set point on LID and verify. Capacity override or excessive cooling load (chiller at design capacity).
Check LID status messages. Check for outside air infiltration into conditioned space.
Condenser temperature too high. Check for proper flow, examine cooling tower operation, check for air or water leaks, check for fouled tubes.
Refrigerant level low. Check for leaks, add refrigerant, and trim charge. Liquid bypass in waterbox. Examine division plates and gaskets for
leaks. Guide vanes fail to open. Use Control Test to check operation. Chilled water control point too high. Access control algorithm status
and check chilled water control operation. Guide vanes fail to open fully. Be sure that the guide vane target is
released. Check guide vane linkage. Check limit switch in actuator. Check that sensor is in the proper terminals.
Chilled water set point set too low. Access set point on LID and verify. Chilled water control point too low. Access control algorithm status and
check chilled water control for proper resets. High discharge temperature keeps guide vanes open. Guide vanes fail to close. Be sure that guide vane target is released.
Check chilled water sensor accuracy. Check guide vane linkage. Check actuator operation.
Deadband too narrow. Configure LID for a larger deadband. Proportional bands too narrow. Either INC or DEC proportional bands
should be increased. Loose guide vane drive. Adjust chain drive. Defective vane actuator. Check through Control Test. Defective temperature sensor. Check sensor accuracy. Check for proper oil level (not enough oil). Check for proper refrigerant
level (too much refrigerant). Check for proper communications wiring on PSIO module. Check that
the COMM1 communications wires from the LID are terminated to the COMM1 PSIO connection.
Check that PSIO communication plugs are connected correctly. Check SMM communication plug. Check for proper SMM power supply. See Control Modules section on page 78.
Check for proper oil level (too much oil). Check that TXV valve is operating properly.
Increase contrast potentiometer. See Fig. 40. Check red LED on LID for proper operation, (power supply). If LED is blinking, but green LED’s are not, replace LID module, (memory failure)
LID is not properly addressed to the PSIO. Make sure that ‘‘Attach to Network Device,’’ ‘‘Local Device’’ is set to read the PSIO address. Check LED’s on PSIO. Is red LED operating properly? Are green LED’s blinking? See control module troubleshooting section.
Press the ‘‘Stop’’ pushbutton. The PIC must be in the OFF mode for the controls test to operate. Clear all alarms. Check line voltage percent on Status01 screen. The percent must be within 90% to 110%. Check voltage input to SMM, calibrate starter voltage potentiometer for accuracy.
Low pressure alarm is active. Put chiller into pumpdown mode or equalize pressure. Check guide vane actuator wiring.
Check oil pump voltage supply. Cooler vessel pressure under vacuum. Pressurize vessel. Check temperature overload cutout switch.
75
Page 76
Table 10A — Thermistor Temperature (F) vs Resistance/Voltage Drop
TEMPERATURE VOLTAGE RESISTANCE
(F) DROP (V) (Ohms)
−25 4.821 98,010
−24 4.818 94,707
−23 4.814 91,522
−22 4.806 88,449
−21 4.800 85,486
−20 4.793 82,627
−19 4.786 79,871
−18 4.779 77,212
−17 4.772 74,648
−16 4.764 72,175
−15 4.757 69,790
−14 4.749 67,490
−13 4.740 65,272
−12 4.734 63,133
−11 4.724 61,070
−10 4.715 59,081
−9 4.705 57,162
−8 4.696 55,311
−7 4.688 53,526
−6 4.676 51,804
−5 4.666 50,143
−4 4.657 48,541
−3 4.648 46,996
−2 4.636 45,505
−1 4.624 44,066 0 4.613 42,679 1 4.602 41,339 2 4.592 40,047 3 4.579 38,800 4 4.567 37,596 5 4.554 36,435 6 4.540 35,313 7 4.527 34,231 8 4.514 33,185 9 4.501 32,176
10 4.487 31,202 11 4.472 30,260 12 4.457 29,351 13 4.442 28,473 14 4.427 27,624 15 4.413 26,804 16 4.397 26,011 17 4.381 25,245 18 4.366 24,505 19 4.348 23,789 20 4.330 23,096 21 4.313 22,427 22 4.295 21,779 23 4.278 21,153 24 4.258 20,547 25 4.241 19,960 26 4.223 19,393 27 4.202 18,843 28 4.184 18,311 29 4.165 17,796 30 4.145 17,297 31 4.125 16,814 32 4.103 16,346 33 4.082 15,892 34 4.059 15,453 35 4.037 15,027 36 4.017 14,614 37 3.994 14,214 38 3.968 13,826 39 3.948 13,449 40 3.927 13,084 41 3.902 12,730 42 3.878 12,387 43 3.854 12,053 44 3.828 11,730 45 3.805 11,416 46 3.781 11,112 47 3.757 10,816 48 3.729 10,529 49 3.705 10,250 50 3.679 9,979 51 3.653 9,717 52 3.627 9,461 53 3.600 9,213 54 3.575 8,973 55 3.547 8,739 56 3.520 8,511 57 3.493 8,291 58 3.464 8,076
TEMPERATURE VOLTAGE RESISTANCE
(F) DROP (V) (Ohms)
59 3.437 7,868 60 3.409 7,665 61 3.382 7,468 62 3.353 7,277 63 3.323 7,091 64 3.295 6,911 65 3.267 6,735 66 3.238 6,564 67 3.210 6,399 68 3.181 6,238 69 3.152 6,081 70 3.123 5,929 71 3.093 5,781 72 3.064 5,637 73 3.034 5,497 74 3.005 5,361 75 2.977 5,229 76 2.947 5,101 77 2.917 4,976 78 2.884 4,855 79 2.857 4,737 80 2.827 4,622 81 2.797 4,511 82 2.766 4,403 83 2.738 4,298 84 2.708 4,196 85 2.679 4,096 86 2.650 4,000 87 2.622 3,906 88 2.593 3,814 89 2.563 3,726 90 2.533 3,640 91 2.505 3,556 92 2.476 3,474 93 2.447 3,395 94 2.417 3,318 95 2.388 3,243 96 2.360 3,170 97 2.332 3,099 98 2.305 3,031
99 2.277 2,964 100 2.251 2,898 101 2.217 2,835 102 2.189 2,773 103 2.162 2,713 104 2.136 2,655 105 2.107 2,597 106 2.080 2,542 107 2.053 2,488 108 2.028 2,436 109 2.001 2,385 110 1.973 2,335 111 1.946 2,286 112 1.919 2,239 113 1.897 2,192 114 1.870 2,147 115 1.846 2,103 116 1.822 2,060 117 1.792 2,018 118 1.771 1,977 119 1.748 1,937 120 1.724 1,898 121 1.702 1,860 122 1.676 1,822 123 1.653 1,786 124 1.630 1,750 125 1.607 1,715 126 1.585 1,680 127 1.562 1,647 128 1.538 1,614 129 1.517 1,582 130 1.496 1,550 131 1.474 1,519 132 1.453 1,489 133 1.431 1,459 134 1.408 1,430 135 1.389 1,401 136 1.369 1,373 137 1.348 1,345 138 1.327 1,318 139 1.308 1,291 140 1.291 1,265 141 1.289 1,240 142 1.269 1,214
TEMPERATURE VOLTAGE RESISTANCE
(F) DROP (V) (Ohms)
143 1.250 1,190 144 1.230 1,165 145 1.211 1,141 146 1.192 1,118 147 1.173 1,095 148 1.155 1,072 149 1.136 1,050 150 1.118 1,029 151 1.100 1,007 152 1.082 986 153 1.064 965 154 1.047 945 155 1.029 925 156 1.012 906 157 0.995 887 158 0.978 868 159 0.962 850 160 0.945 832 161 0.929 815 162 0.914 798 163 0.898 782 164 0.883 765 165 0.868 750 166 0.853 734 167 0.838 719 168 0.824 705 169 0.810 690 170 0.797 677 171 0.783 663 172 0.770 650 173 0.758 638 174 0.745 626 175 0.734 614 176 0.722 602 177 0.710 591 178 0.700 581 179 0.689 570 180 0.678 561 181 0.668 551 182 0.659 542 183 0.649 533 184 0.640 524 185 0.632 516 186 0.623 508 187 0.615 501 188 0.607 494 189 0.600 487 190 0.592 480 191 0.585 473 192 0.579 467 193 0.572 461 194 0.566 456 195 0.560 450 196 0.554 445 197 0.548 439 198 0.542 434 199 0.537 429 200 0.531 424 201 0.526 419 202 0.520 415 203 0.515 410 204 0.510 405 205 0.505 401 206 0.499 396 207 0.494 391 208 0.488 386 209 0.483 382 210 0.477 377 211 0.471 372 212 0.465 367 213 0.459 361 214 0.453 356 215 0.446 350 216 0.439 344 217 0.432 338 218 0.425 332 219 0.417 325 220 0.409 318 221 0.401 311 222 0.393 304 223 0.384 297 224 0.375 289 225 0.366 282
76
Page 77
Table 10B — Thermistor Temperature (C) vs Resistance/Voltage Drop
TEMPERATURE VOLTAGE RESISTANCE
(C) DROP (V) (Ohms)
−40 4.896 168 230
−39 4.889 157 440
−38 4.882 147 410
−37 4.874 138 090
−36 4.866 129 410
−35 4.857 121 330
−34 4.848 113 810
−33 4.838 106 880
−32 4.828 100 260
−31 4.817 94 165
−30 4.806 88 480
−29 4.794 83 170
−28 4.782 78 125
−27 4.769 73 580
−26 4.755 69 250
−25 4.740 65 205
−24 4.725 61 420
−23 4.710 57 875
−22 4.693 54 555
−21 4.676 51 450
−20 4.657 48 536
−19 4.639 45 807
−18 4.619 43 247
−17 4.598 40 845
−16 4.577 38 592
−15 4.554 38 476
−14 4.531 34 489
−13 4.507 32 621
−12 4.482 30 866
−11 4.456 29 216
−10 4.428 27 633
−9 4.400 26 202
−8 4.371 24 827
−7 4.341 23 532
−6 4.310 22 313
−5 4.278 21 163
−4 4.245 20 079
−3 4.211 19 058
−2 4.176 18 094
−1 4.140 17 184 0 4.103 16 325 1 4.065 15 515 2 4.026 14 749 3 3.986 14 026 4 3.945 13 342 5 3.903 12 696 6 3.860 12 085 7 3.816 11 506 8 3.771 10 959 9 3.726 10 441
10 3.680 9 949 11 3.633 9 485 12 3.585 9 044 13 3.537 8 627 14 3.487 8 231 15 3.438 7 855 16 3.387 7 499 17 3.337 7 161
TEMPERATURE VOLTAGE RESISTANCE
(C) DROP (V) (Ohms)
18 3.285 6 840 19 3.234 6 536 20 3.181 6 246 21 3.129 5 971 22 3.076 5 710 23 3.023 5 461 24 2.970 5 225 25 2.917 5 000 26 2.864 4 786 27 2.810 4 583 28 2.757 4 389 29 2.704 4 204 30 2.651 4 028 31 2.598 3 861 32 2.545 3 701 33 2.493 3 549 34 2.441 3 404 35 2.389 3 266 36 2.337 3 134 37 2.286 3 008 38 2.236 2 888 39 2.186 2 773 40 2.137 2 663 41 2.087 2 559 42 2.039 2 459 43 1.991 2 363 44 1.944 2 272 45 1.898 2 184 46 1.852 2 101 47 1.807 2 021 48 1.763 1 944 49 1.719 1 871 50 1.677 1 801 51 1.635 1 734 52 1.594 1 670 53 1.553 1 609 54 1.513 1 550 55 1.474 1 493 56 1,436 1 439 57 1.399 1 387 58 1.363 1 337 59 1.327 1 290 60 1.291 1 244 61 1.258 1 200 62 1.225 1 158 63 1.192 1 118 64 1.160 1 079 65 1.129 1 041 66 1.099 1 006 67 1.069 971 68 1.040 938 69 1.012 906 70 0.984 876 71 0.949 836 72 0.920 805 73 0.892 775 74 0.865 747 75 0.838 719
TEMPERATURE VOLTAGE RESISTANCE
(C) DROP (V) (Ohms)
76 0.813 693 77 0.789 669 78 0.765 645 79 0.743 623 80 0.722 602 81 0.702 583 82 0.683 564 83 0.665 547 84 0.648 531 85 0.632 516 86 0.617 502 87 0.603 489 88 0.590 477 89 0.577 466 90 0.566 456 91 0.555 446 92 0.545 436 93 0.535 427 94 0.525 419 95 0.515 410 96 0.506 402 97 0.496 393 98 0.486 385
99 0.476 376 100 0.466 367 101 0.454 357 102 0.442 346 103 0.429 335 104 0.416 324 105 0.401 312 106 0.386 299 107 0.370 285
77
Page 78
Control Modules
red LED is normal, check the module address switches (Fig. 39-43). Proper addresses are:
Turn controller power off before servicing controls. This ensures safety and prevents damage to controller.
The Processor module (PSIO), 8-input (Options) mod­ules, Starter Management Module (SMM), and the Local Interface Device (LID) module perform continuous di­agnostic evaluations of the hardware to determine its con­dition. See Fig. 39-43. Proper operation of all modules is indicated by LEDs (light-emitting diodes) located on the side of the LID, and on the top horizontal surface of the PSIO, SMM, and 8-input modules.
RED LED — If the LED is blinking continuously at a 2-second rate, it is indicating proper operation. If it is lit continuously it indicates a problem requiring replacement of the module. Off continuously indicates that the power should be checked. If the red LED blinks 3 times per sec­ond, a software error has been discovered and the module must be replaced. If there is no input power, check fuses and the circuit breaker. If fuse is good, check for shorted sec­ondary of transformer, or if power is present to the module, replace the module.
GREEN LEDs — There are one or 2 green LEDs on each type of module. These LEDs indicate communication status between differentparts of the controller and the network mod­ules as follows:
LID Module Upper LED — Communication with CCN network, if present;
blinks when communication occurs. Lower LED — Communication with PSIO module; must
blink every 5 to 8 seconds when the LID default screen is displayed.
PSIO Module GreenLED Closest to Communications Connection —Com-
munication with SMM and 8-input module; must blink continuously.
Other Green LED — Communication with LID; must blink every 3 to 5 seconds.
MODULE
SMM (Starter Management Module) 32 8-input Options Module 1 64 8-input Options Module 2 72
ADDRESS
S1 S2
If all modules indicate communications failure, check com­munications plug on the PSIO module for proper seating. Also check the wiring (CCN bus — 1:red, 2:wht, 3:blk; Sensor bus — 1:red, 2:blk, 3:clr/wht). If a good connec­tion is assured and the condition persists, replace the PSIO module.
If only one 8-input module or SMM indicates commu­nication failure, check the communications plug on that module. If a good connection is assured and the condi­tion persists, replace the module.
All system operating intelligence rests in the PSIO mod­ule. Some safety shutdown logic resides in the SMM in case communications are lost between the 2 modules. The PSIO monitors conditions using input ports on the PSIO, the SMM, and the 8-input modules. Outputs are con­trolled by the PSIO and SMM as well.
3. Power is supplied to modules within the control panel via 21-vac power sources.
The transformers are located within the power panel, with the exception of the SMM, which operates from a 24-vac power source and has its own 24-vac transformer located within the starter.
Within the power panel, T1 supplies power to the LID, the PSIO, and the 5-vac power supply for the transduc­ers. The other 21-vac transformer is T4, which supplies power to both 8-input modules (if present). T4 is capable of supplying power to two modules; if additional mod­ules are added, another power supply will be required.
Power is connected to Terminals 1 and 2 of the power input connection on each module.
8-Input Modules and SMM GreenLED — Communication with PSIO module; will blink
continuously.
Notes on Module Operation
1. The chiller operator monitors and modifies configura­tions in the microprocessor through the 4 softkeys and the LID. Communication with the LID and the PSIO is accomplished through the CCN bus. The communication between the PSIO, SMM, and both 8-input modules is accomplished through the sensor bus, which is a 3-wire cable.
On sensor bus terminal strips, Terminal 1 of PSIO mod­ule is connected to Terminal 1 of each of the other modules. Terminals 2 and 3 are connected in the same manner.See Fig. 39-43. If a Terminal 2 wire is connected to Terminal 1, the system does not work.
2. If a green LED is solid on, check communication wiring. If a green LED is off, check the red LED operation. If the
Fig. 39 — PSIO Module Address Selector Switch
Locations and LED Locations
78
Page 79
NOTE: Address switches on this module can be at any position. Addresses are only changed through the LID screen or CCN.
Fig. 40 — LID Module (Rear View) and
LED Locations
Starter Management Module (SMM) (Fig. 42)
INPUTS — Inputs on strips J2 and J3 are a mix of analog and discrete (on/off) inputs. Application of the chiller de­termines which terminals are used. Always refer to the individual unit wiring diagram for terminal numbers.
OUTPUTS — Outputs are 24 vdc and wired to strip J1. There are 2 terminals used per output.
Processor Module (PSIO) (Fig. 41)
INPUTS — Each input channel has 3 terminals; only 2 of the terminals are used.Application of chiller determines which terminals are normally used. Always refer to individual unit wiring for terminal numbers.
OUTPUTS — Output is 20 vdc. There are 3 terminals per output, only 2 of which are used, depending on the appli­cation. Refer to the unit wiring diagram.
NOTE: SMM address switches should be set as follows:
S1 set at 3; S2 set at 2.
Fig. 42 — Starter Management Module
(SMM)
Options Modules (8-Input) — The options modules
are optional additions to the PIC, and are used to add tem­perature reset inputs, spare sensor inputs, and demand limit inputs. Each option module contains 8 inputs, each input meant for a specific duty. See the wiring diagram for exact module wire terminations. Inputs for each of the options modules available include the following:
OPTIONS MODULE 1
4 to 20 mA Auto. Demand Reset 4 to 20 mA Auto. Chilled Water Reset Common Chilled Water Supply Temperature Common Chilled Water Return Temperature Remote Temperature Reset Sensor Spare Temperature 1 Spare Temperature 2 Spare Temperature 3
NOTE: Address switches on this module can be at any position. Addresses are only changed through the LID screen or CCN.
Fig. 41 — Processor (PSIO) Module
79
OPTIONS MODULE 2 4 to 20 mA Spare 1
4 to 20 mA Spare 2 Spare Temperature 4 Spare Temperature 5 Spare Temperature 6 Spare Temperature 7 Spare Temperature 8 Spare Temperature 9
Page 80
Terminal block connections are provided on the options modules. All sensor inputs are field wired and installed. Options module number 1 can be factory or field-installed. Options module 2 is shipped separately and must be field installed. For installation, refer to the unit or field wiring diagrams. Be sure to address the module for the proper mod­ule number (Fig. 43) and to configure the chiller for each feature being used.
SWITCH
SETTING
S1 67 S2 42
OPTIONS
MODULE 1
OPTIONS
MODULE 2
Fig. 43 — Options Module
Replacing Defective Processor Modules — The
replacement part number is printed in a small label on front of the PSIO module. The model and serial numbers are printed on the unit nameplate located on an exterior corner post. The proper software is factory-installed by Carrier in the replacement module. When ordering a replacement proces­sor module (PSIO), specify complete replacement part number,full unit model number, and serial number.This new unit requires reconfiguration to the original chiller data by the installer. Follow the procedures described in the Set Up Chiller Control Configuration section on page 50.
Electrical shock can cause personal injury. Disconnect all electrical power before servicing.
INSTALLATION
1. Verify that the existing PSIO module is defective by us­ing the procedure described in the Troubleshooting Guide section, page 66, and Control Modules section, page 78. Do not select the Attach to Network Device table if the LID displays communication failure.
2. Data regarding the PSIO configuration should have been recorded and saved. This data will have to be recon­figured into the LID. If this data is not available, follow the procedures described in the Set Up Chiller Control Configuration section.
If a CCN Building Supervisor or Service Tool is present, the module configuration should have already been uploaded into memory; then, when the new module is installed, the configuration can be downloaded from the computer.
Any communication wires from other chillers or CCN modules should be disconnected to prevent the new PSIO module from uploading incorrect run hours into memory.
3. To install this module, first record the TOTAL COM- PRESSOR STARTS and the COMPRESSOR ONTIME from the Status01 table screen on the LID.
4. Power off the controls.
5. Remove the old PSIO. DO NOT install the new PSIO at this time.
6. Turn on the control power. When the LID screen re­appears, press the MENU
SERVICE
softkey. Enter the password, if applicable.
softkey, then press the
Move the highlight bar down to the ATTACH TO NET­WORK DEVICE line. Press the SELECT Now, press the ATTACH
softkey. The LID will dis-
softkey.
play ‘‘UPLOADING TABLES, PLEASE WAIT’’ and then display ‘‘COMMUNICATIONS FAILURE.’’ Press
the EXIT softkey.
7. Turn the control power off.
8. Install the new PSIO module. Turn the control power back on.
9. The LID will now automatically upload the new PSIO module.
10. Access the Status01 table and move the highlight bar down to the TOTALCOMPRESSOR STARTSline. Press
the SELECT
softkey. Increase the value to indicate
the correct starts value recorded in Step 2. Press the
ENTER
softkey when you reach the correct value. Now, move the highlight bar to the COMPRESSOR ON- TIME line. Press the SELECT
softkey.Increase the run
hours value to the value recorded in Step 2. Press the
ENTER
softkey when the correct value is reached.
11. Complete the PSIO installation. Following the instruc­tions in the Start-up, Operation, and Maintenance manual, input all the proper configurations such as time, date, etc. Re-calibrate the motor amps and check the pres­sure transducer calibrations. PSIO installation is now complete.
80
Page 81
Solid-StateStarters — Troubleshooting guides and in-
formation pertaining to the operation of the solid-state starter may be found in Fig. 44-46 and Table 11.
Attempt to solve the problem by using the following preliminary checks before consulting the troubleshooting table.
When the power is off:
• Inspect for physical damage and signs of arcing, overheat-
ing, etc.
• Is the wiring to the starter correct?
• Are all connections in the starter tight?
• Is the current feedback resistor properly adjusted and
installed?
• Is a heater coil installed in each leg of the motor?
• Is the control transformer fuse blown?
• Is the motor connected to the starter? TESTING SILICON CONTROL RECTIFIERS IN
BENSHAW, INC. SOLID-STATE STARTERS — If a sili­con control rectifier (SCR) is suspected of being defective, use the following procedure as part of a general trouble­shooting guide.
IMPORTANT: Before performing the SCR check be­low,remove power from the starter and disconnect the motor terminals T1, T2, and T3.
1. Connect ohmmeter across terminals L1 and T1. Resis-
tance reading should be greater than 50,000 ohms.
2. If reading is less than 50,000 ohms, remove connecting
bus heatsink between SCR3 and SCR6 and check anode to cathode of SCR3 and SCR6 separately to determine which device is defective. See Fig. 44. Replace defective device and retest controller.
3. Repeat Steps 1 and 2 across terminals L2 and T2 for SCRs
2 and 5.
4. Repeat Steps 1 and 2 across terminals L3 and T3 for SCRs
1 and 4. If the SCRs tested were not defective but the problem
still persists, refer to the following Steps 5 and 6.
5. Disconnect the SCR1 from the white gate and red cath-
ode wires on the AK control logic card. With an ohm­meter set on Rx1, check between white and red wires.
LEGEND
SCR — Silicon Control Rectifier
Fig. 44 — Typical Benshaw, Inc. Solid-State
Starter (internal View)
Resistance should normally be between 8 and 20 ohms average. Excessively high or low resistance may be indicative of a defective logic card. Replace and retest.
6. Repeat Step 5 for SCR leads 2 through 6. Care should be taken to ensure that the gate and cathode wires are replaced exactly as they were: white wire to gate (G1 through G6); red wire to cathode (K1 through K6).
Damage to the starter may result if wires are reversed.
If the problem is still not resolved, consult the starter manu-
facturer for servicing.
81
Page 82
LEGEND SCR — Silicon Control Rectifier *See test procedure described in Testing SCRs in Solid-State Starters section on page 81.
Fig. 45 — Solid-State Starter, General Operation Troubleshooting Guide (Typical)
82
Page 83
Fig. 46 — Solid-State Starter, Starter Fault (Motor Will Not Start)
Troubleshooting Guide (Typical)
83
Page 84
Table 11 — Benshaw, Inc. Solid-State Starter Troubleshooting Guide
PROBLEM PROBABLE CAUSES AREA OF CORRECTION
AK board phase correct not on.
AK board relay not on. Ribbon cable not properly
AK board power +15 vdc not on.
1L boards LEDs not on. 1. A short exists between line
BC board over-temperature LED (L3) on prior to run command.
BC board LEDs on prior to run command.
BC board LEDs not on after run command but before starter reaches full voltage.
1L board LEDs remain on after starter reaches full voltage.
BC board run LED (L5) not lit. BC board not functioning
AK board power applied, run command given, starter at full voltage, but aux LED not lit.
1L boards LEDs lit. Motor terminal voltage phase
BC board LED L4 and L5 not lit.
BC board LED L3 lit. 1. FU5 and FU6 fuses not
BC board L2 lit. SCR phases not functioning BC board L1 lit. Motor lead grounded. Megger motor to test for motor lead going to ground.
Start command given. Motor does not begin rotation. Turn ‘Starting Torque’ potentiometer RV2 clockwise until motor
Motor does not reach full speed within 25 seconds.
115 vac missing from LL1 and LL2.
SMM not responding. 1. CB4 is not on.
1. L1 and L3 switch phases reversed.
2. Missing phase voltage.
3. Improper line voltage.
seated.
1. Improper line voltage.
2. Transformer malfunction.
and load terminals.
2. An SCR is shorted in the phase assembly.
1. Temperature switch not functioning properly.
2. BC board not functioning properly.
BC board not functioning properly.
1. Phase assembly malfunction.
2. BC board not functioning properly.
Imbalance between phases exists in motor terminal voltages.
properly.
AK board not functioning properly.
imbalance exists. BC board not functioning
properly.
functioning properly.
2. Phase assembly not functioning properly.
3. Fan not functioning properly.
properly.
Ramp up setting is not correct. Turn ‘Ramp’ potentiometer RV1 counterclockwise. Restart motor
1. CB2 is not on.
2. Fuse no. 4 (FU4) blown.
2. Potentiometer RV1 needs adjustment.
1. Switch incoming phases L1 and L3 at top of CD1 or CB1.
2. Check for missing phase voltage.
3. Verify proper line voltage applied against synchronizing transformer voltage.
Check ribbon cable for proper seating. Replace board if necessary.
1. Make sure proper line voltage is present at primary synchronizing transformer.
2. Check synchronizing transformer secondary voltage as follows: On the BC board, measure from TB11-1 to TB11-2 and TB11-1 to TB11-3. Both readings should be within 30 to 36 vac. On the BC board, measure from TB11-1 to TB11-4 and TB11-2 to TB11-4. Both readings should be within 18 to 24 vac. Replace synchronizing transformer if voltages are not within the specified tolerances.
1. Remove power and check resistance with ohmmeter. Locate and remove stray wire strands if required.
2. Remove power. Use ohmmeter to measure the resistance or each SCR phase assembly from anode to cathode. The reading should be 50,000 ohm or greater. If not, replace phase assembly.
1. Disconnect power and check for continuity between TB11-10 and TB11-11. If no continuity exists, the overtemperature switch is not functioning properly. Replace defective switch if necessary.
2. Make sure BC board is functioning properly. Replace board if necessary.
Board not functioning properly. Replace board, if necessary.
1. Remove power and check SCRs. Ohmmeter reading of each SCR gate to cathode resistance at terminals is 8 to 20 ohm. If not, replace the phase assembly.
2. Replace board, if necessary.
Check for loose SCR gate lead or open SCR gate. Replace phase assembly, if necessary.
Measure 24 vdc at TB11-8 to TB11-4. If voltage is present, replace board. If not present, replace relay 1CR.
Replace board.
Check motor terminal voltages for imbalance between phases. If an imbalance exists, check for loose SCR gate or open SCR gate. Replace phase assembly, if necessary.
Replace board.
1. Check fuses FU5 and FU6. Replace if necessary.
2. Verify that bypass is pulling in by measuring the voltage drop across the contacts. The reading should be 50 mV or less. Replace phase assembly, if necessary.
3. Verify fan operation on each phase for 200 amp units. Replace fan, if necessary.
Measure resistance from anode to cathode for each SCR phase assembly. Replace shorted phase, if necessary.
rotation begins. and verify that motor reaches full speed within 25 seconds.
1. Verify CB2 is on.
2. Check FU4 for continuity. Replace, if necessary.
1. Verify CB4 is on.
2. Adjust potentiometer RV1 for 24 vac at SMM terminals J3-23 and J3-24.
AK Vendor Board Designation BC Vendor Board Designation CB Circuit Breaker CD Disconnect Switch CR Control Relay FU Fuse LED — Light-Emitting Diode
LEGEND
L1, L3 Terminal Board LL1, LL2 — Control Power Terminals RV1 Line Voltage Signal Calibration SCR Silicon Control Rectifier SMM Starter Management Module TB Terminal Board
84
Page 85
Physical Data — Tables 12-17 and Fig. 47-51 pro-
vide additional information regarding compressor fits and
Table 12 — Heat Exchanger Data
RIGGING WEIGHTS VESSEL CHARGE
Dry Wt. Refrigerant
VESSEL
COOLER
HEAT
EXCHANGER
CODE
40 201 5000 2275 5340 2422 1020 463 750 341 550 250 53 201 41 227 5150 2350 5485 2488 1090 494 800 363 600 272 58 220 42 257 5325 2425 5655 2565 1150 522 900 408 650 295 64 242 43 290 5500 2500 5845 2651 1200 544 1000 454 700 318 71 269 50 314 6625 3000 7020 3184 1450 658 1150 522 750 341 79 299 51 355 6850 3100 7255 3291 1500 680 1250 568 850 386 87 329 52 400 7100 3225 7510 3406 1580 717 1400 636 950 431 96 363 53 445 7375 3350 7770 3524 1650 748 1500 681 1000 454 104 394 55 201 8510 3860 1410 640 1060 481 104 395 56 227 8845 4012 1710 776 1160 527 115 438 57 257 9205 4175 2010 913 1260 572 128 486 58 290 9575 4343 2210 1003 1410 640 140 531
NUMBER
OF TUBES
Design I Design II
Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Gal L
COOLER
clearances, physical and electrical data, and wiring sche­matics for operator convenience during troubleshooting.
Design I Design II HCFC-22 HCFC-22 HFC-134a
Volume
of Water
CONDENSER
VESSEL
CONDENSER
NOTES:
1. Design I chillers are equipped with a float box, and chiller weight is based on a 150 psi (1034 kPa) waterbox with 2 pass arrangement.
2. Design II chillers are equipped with a linear float, and chiller weight is based on a 300 psi (2068 kPa) waterbox with 1 pass arrangement.
3. Total refrigerant charge is equal to the cooler charge added to the condenser charge.
HEAT
EXCHANGER
CODE
40 218 5050 2100 4855 2202 400 181 350 159 56 212 41 246 5200 2350 5010 2272 400 181 350 159 62 235 42 279 5375 2450 5180 2350 400 181 350 159 68 257 43 315 5575 2525 5370 2436 400 181 350 159 75 284 50 347 7050 3200 6750 3062 400 181 350 159 84 318 51 387 7275 3300 6960 3157 400 181 350 159 92 348 52 432 7500 3400 7200 3266 400 181 350 159 101 382 53 484 7775 3525 7475 3391 400 181 350 159 110 416 55 218 8345 3785 490 222 112 423 56 246 8635 3917 490 222 123 466 57 279 8980 4073 490 222 135 513 58 315 9370 4250 490 222 149 565
NUMBER
OF TUBES
RIGGING WEIGHTS VESSEL CHARGE
Dry Wt. Refrigerant
Design I Design II Design I Design II
Lb Kg Lb Kg Lb Kg Lb Kg Gal L
Table 13 — Additional Data for Marine Waterboxes*
Volume
of Water
ENGLISH SI
HEAT EXCHANGER
FRAME, PASS
FRAME 4, 2 PASS 1115 660 69 51 506 300 261 193 FRAME 4,1&3PASS 2030 1160 138 101 922 527 524 384 FRAME 5, 2 PASS 1220 935 88 64 554 424 331 243 FRAME 5,1&3PASS 2240 1705 175 128 1017 774 663 486
*Add to heat exchanger weights and volumes for total weight or volume.
Rigging Wt
(lb)
Cooler Condenser Cooler Condenser Cooler Condenser Cooler Condenser
Water Volume
(gal)
Rigging Wt
(kg)
Water Volume
(L)
85
Page 86
HEAT
EXCHANGER
COOLERS
CONDENSERS
HEAT
EXCHANGER
COOLERS
CONDENSERS
LEGEND
NIH Nozzle-in-Head MWB — Marine Waterbox CS Contact Syracuse
DESCRIPTION
NIH, 1 PASS COVER 284 414 324 491 412 578 452 655 NIH, 2 PASS COVER 285 411 341 523 410 573 466 685 NIH, 3 PASS COVER 292 433 309 469 423 602 440 638 NIH, PLAIN END COVER 243 292 243 292 304 426 304 426 MWB COVER CS 621 CS 621 CS 766 CS 766 PLAIN END COVER CS 482 CS 482 CS 471 CS 471 NIH, 1 PASS COVER 306 446 346 523 373 472 413 549 NIH, 2 PASS COVER 288 435 344 547 368 469 428 541 NIH, 3 PASS COVER 319 466 336 502 407 493 419 549 NIH, PLAIN END COVER 226 271 226 271 271 379 271 379 MWB COVER CS 474 CS 474 CS 590 CS 590 PLAIN END COVER CS 359 CS 359 CS 428 CS 428
WATERBOX
DESCRIPTION
NIH, 1 PASS COVER 129 188 147 223 187 262 205 297 NIH, 2 PASS COVER 129 187 155 237 186 260 212 311 NIH, 3 PASS COVER 133 197 140 213 192 273 200 290 NIH, PLAIN END COVER 110 133 110 133 138 193 138 193 MWB COVER CS 282 CS 282 CS 348 CS 348 PLAIN END COVER CS 219 CS 219 CS 214 CS 214 NIH, 1 PASS COVER 139 202 157 237 169 214 188 249 NIH, 2 PASS COVER 131 197 156 248 167 213 194 246 NIH, 3 PASS COVER 145 212 153 228 185 224 190 249 NIH, PLAIN END COVER 103 123 103 123 123 172 123 172 MWB COVER CS 215 CS 215 CS 268 CS 268 PLAIN END COVER CS 163 CS 163 CS 194 CS 194
WATERBOX
Table 14 — Waterbox Cover Weights*
ENGLISH (lb)
FRAME 4,
STANDARD
NOZZLES
150 psig 300 psig 150 psig 300 psig 150 psig 300 psig 150 psig 300 psig
FRAME 4, FLANGED
SI (kg)
FRAME 4,
STANDARD
NOZZLES
1034 kPa 2068 kPa 1034 kPa 2068 kPa 1034 kPa 2068 kPa 1034 kPa 2068 kPa
*These weights are for reference only. To determine frame size, see Fig. 1. NOTE: For Design I chillers, the 150 psig (1034 kPa) standard waterbox cover weights (NIH, 2-pass
cover) have been included in the heat exchanger weights shown in Table 12. Design II chillers are equipped with a linear float, and chiller weight is based on a 300 psig (2066 kPa) waterbox with 1-pass arrangement.
FRAME 4, FLANGED
FRAME 5,
STANDARD
NOZZLES
FRAME 5,
STANDARD
NOZZLES
FRAME 5, FLANGED
FRAME 5,
FLANGED
86
Page 87
Table 15 — Compressor/Motor Weights
ENGLISH SI
MOTOR
SIZE
CB 2660 1135 1147 171 233 250 1208 515 520 78 106 114 CC 2660 1143 1150 197 239 250 1208 518 522 90 109 114 CD 2660 1153 1213 234 252 250 1208 523 551 106 114 114 CE 2660 1162 1227 237 255 250 1208 528 557 108 116 114 CL 2660 1202 1283 246 270 250 1208 546 582 112 123 114 CM 2660 1225 1308 254 275 250 1208 556 594 115 125 114 CN 2660 1276 1341 263 279 250 1208 579 609 119 127 114 CP 2660 1289 1356 266 284 250 1208 585 616 121 129 114 CQ 2660 1306 1363 273 287 250 1208 593 619 124 130 114 CR 2660 1335 1384 282 294 250 1208 606 628 128 133 114
NOTE: For medium voltage motors add 85 lbs (39 kg) to above for 60 Hz motors and 145 lbs (66 kg) for 50 Hz motors. Total compressor/motor weight is the sum of the compressor, stator, rotor, and end bell cover weight. Compressor weight includes suction and discharge elbow weights.
Compressor
Weight
(lb)
Stator Weight
(lb)
60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz
Rotor Weight
(lb)
End Bell
Cover
(lb)
Compressor
Weight
(kg)
Stator Weight
(kg)
Rotor Weight
(kg)
End Bell
Cover
(lb)
Table 16 — Compressor Weights
COMPONENT
SUCTION ELBOW 55 25 DISCHARGE ELBOW 50 23 TRANSMISSION 730 331 SUCTION HOUSING 350 159 IMPELLER SHROUD 80 36 COMPRESSOR BASE 1050 476 DIFFUSER 70 32 OIL PUMP 150 68 MISCELLANEOUS 135 61 TOTAL WEIGHT
(Less Motor)
WEIGHT
Lb Kg
2660 1207
Table 17 — Optional Pumpout System
Electrical Data
MOTOR
CODE
1 19EA47-748 575-3-60 3.8 23.0 4 19EA42-748 200/208-3-60 10.9 63.5 5 19EA44-748 230-3-60 9.5 57.5 6 19EA46-748 400/460-3-50/60 4.7 28.8
LRA — Locked Rotor Amps RLA — Rated Load Amps
CONDENSER
UNIT
LEGEND
VOLTS-PH-Hz
MAX RLA
LRA
87
Page 88
NOTES:
1. Dimensions are in inches with rotor in the thrust position.
2. All clearances listed are new chiller tolerances.
3. All radial clearances are diametrical.
NOTE: Radial clearances shown are diametrical.
Fig. 47 — Compressor Fits and Clearances
88
Page 89
COMPRESSOR ASSEMBLY TORQUES
ITEM DESCRIPTION
1* Oil Heater Grommet Nut 10 14
2 Impeller Retaining Bolt 44-46 60-62 3 Bull Gear Retaining Bolt 80-85 108-115 4 Motor Terminals (Low Voltage) 50 68
5 Demister Bolts 15-19 20-26 6* Guide Vane Shaft Seal Nut 25 34 7* Motor Terminals (High Voltage)
LEGEND N•m — Newton Meters *Not shown.
— Insulator 2-4 2.7-5.4 — Packing Nut 5 6.8 — Brass Jam Nut 10 13.6
TORQUE
ft-lb N•m
*‘‘Z’’clearance is determined by a combination of impeller diameter and shroud size. The
table lists ‘‘Z’’ clearances for each compressor code. Figure 1 shows the location (on the chiller information plate) of the compressor code for each chiller.
COMPRESSOR
CODE
203-204 .025 0.635 223-274 .015 0.381 283-307 .025 0.635 321-377 .015 0.381 381-397 .025 0.635 410-469 .015 0.381 470-499 .025 0.635
‘‘Z’’
(in.)
‘‘Z’’
(mm)
COMPRESSOR
CODE
516-517 .015 0.381 518-519 .025 0.635 526-527 .015 0.381 528-529 .025 0.635 536-537 .015 0.381 538-539 .025 0.635
‘‘Z’’ (in.)
(mm)
Fig. 47 — Compressor Fits and Clearances (cont)
89
‘‘Z’’
COMPRESSOR
CODE
546-547 .015 0.381 548-549 .025 0.635 556-557 .015 0.381 558-559 .025 0.635 566-567 .015 0.381 568-569 .025 0.635
‘‘Z’’
(in.)
‘‘Z’’
(mm)
Page 90
BRG Bearing C—Contact CB Circuit Breaker CLR Clear COM Common COMM — Communication Connector EXT External G.V. Guide Vane HGBP — Hot Gas Bypass INT Internal J—Module Connector K—Relay Designation LID Local Interface Device MA Milliampere NC Normally Closed
LEGEND
NO Normally Open PSIO — Processor Sensor Input/
RBPL — Relay Board Plug S—Compressor Motor Start Contactor SMM — Starter Management Module SOL Solenoid TB Terminal Board
Output Module
Carrier Factory Wiring Optional (Factory or Field-Installed)
Wiring Thermistor
t*
Fig. 48 — Electronic PIC Controls Wiring Schematic
(For 19XL with No Backlight or with Fluorescent Backlight)
90
Page 91
(For 19XL with No Backlight or with Fluorescent Backlight) (cont)
Fig. 48 — Electronic PIC Controls Wiring Schematic
91
Page 92
BRG Bearing C—Contact CB Circuit Breaker CLR Clear COM Common COMM — Communication Connector EXT External G.V. Guide Vane HGBP — Hot Gas Bypass INT Internal J—Module Connector K—Relay Designation LID Local Interface Device MA Milliampere NC Normally Closed
LEGEND
NO Normally Open PSIO — Processor Sensor Input/
RBPL — Relay Board Plug S—Compressor Motor Start Contactor SMM — Starter Management Module SOL Solenoid TB Terminal Board
Output Module
Carrier Factory Wiring Optional (Factory or Field-Installed)
Wiring Thermistor
t*
Fig. 49 — Electronic PIC Controls Wiring Schematic
(For 19XL with Halogen Backlight)
92
Page 93
Fig. 49 — Electronic PIC Controls Wiring Schematic
(For 19XL with Halogen Backlight) (cont)
93
Page 94
1M Main Starter Contactor C—Contactor CB Circuit Board CR Control Relay COMM — Communications Connector J—Connector N.C. Normally Closed N.O. Normally Open OL Overload OS 3-Phase Current Power Source
*All starters, including across-the-line starters, require 2 separate contacts for the START AUX
DRY contact and RUN AUX DRY contact, as shown above.
LEGEND
PR Pilot Relay PWR — Power RLA — Rated Load Amps SMM — Starter Management Module TB Terminal Board X—Variable Number
Starter Cabinet Wiring Field Wiring Carrier Factory Wiring
Fig. 50 — Chiller Power Panel, Starter Assembly,
and Motor Wiring Schematic
94
Page 95
Fig. 50 — Chiller Power Panel, Starter Assembly,
and Motor Wiring Schematic (cont)
95
Page 96
PMR Phase Loss Reversal Relay
PMRVR — Phase Loss, Phase Reversal,
LEGEND
Overvoltage, Undervoltage Relay
POT Potentiometer
PR Pilot Relay
S—Compressor Motor Start Contactor
SMM Starter Management Module
ST Shunt Trip
T—Motor Terminal
TB Terminal Board
TR Transition Resistor
TRFP Transition Resistor Fault Protector
X—Variable Number
X1, X2 Power Transformer Output Terminal
Dry Contact
1M, 2M Main Compressor Contactors
CB Circuit Breaker
CR Control Relay
CT Current Transformer
DS Disconnect
GF Ground Fault
GFR Ground Fault Relay
H1, H2 Power Transformer Input
Terminal
HPS High-Pressure Switch
J—Module Connector
L1, L2, L3 — 3-Phase Line Terminals
NC Normally Closed
OL Overload
Source to Oil Pump
3-Phase Current Power
OS1, OS2,
OS3
Fig. 51 — Typical Wye-Delta Unit Mounted Starter Wiring Schematic
96
Page 97
NOTE: Optional features are indicated by bold dotted boxes.
Yellow wires remain energized when main disconnect is off.
97
(1A) remains energized for longer than one second.
1. Contactors 2M and S are mechanically interlocked.
2. Transition resistor fault protector (TRFP) is preset to trip if transition contactor
NOTES:
overvoltage, undervoltage relay (PMRVR)is not provided, terminals 3-13Aand
3-13B are jumpered together.
3. When optional phase loss reversal relay (PMR) or phase loss, phase reversal,
4. When optional ground fault is not provided, terminals 3-13B and 3-13C are
jumpered together.
5. Thisoil pump circuit breaker and terminal board TB7 are provided only onstart-
ers for centrifugal machines.
6. POT to be adjusted to 24 v at rated line voltage.
7. CT4 and CT5 are provided only when the optional watt transducer is provided.
8. These 3 wires to the ammeter switch are connected together only when the
optional 3-phase ammeter is not provided.
is provided. The combination PMRVR has an internal time delay and does not
require PMRTR.
9. PMRTR is provided only if the optional phase loss phase reversal relay (PMR)
the control wires within the starter. Wires entering terminal boards are marked
10. Connections on the above schematic are numbered to match the markings on
Fig. 51 — Typical Wye-Delta Unit Mounted Starter Wiring Schematic (cont)
with the terminal number.
11. Oil pump AUX. contact not supplied on screw machines.
Page 98
Abbreviations and Explanations, 4 Adding Refrigerant, 61 Adjusting the Refrigerant Charge, 61 After Extended Shutdown, 57 After Limited Shutdown, 57 Attach to Network Device Control, 37 Automatic Soft-Stop Amps Threshold, 40 Auto. Restart After Power Failure, 33 Before Initial Start-Up, 41 Calibrate Motor Current, 56 Capacity Override, 31 Carrier Comfort Network Interface, 48 Changing Oil Filter, 63 Charge Refrigerant Into Chiller, 53 Chilled Water Recycle Mode, 40 Chiller Dehydration, 47 Chiller Familiarization, 5 Chiller Information Plate, 5 Chiller Operating Condition (Check), 56 Chiller Tightness (Check), 41 Chillers with Isolation Valves, 60 Chillers with Pumpout Storage Tanks, 59 Cold Weather Operation, 57 Compressor Bearing and Gear Maintenance, 64 Condenser, 5 Condenser Freeze Prevention, 32 Condenser Pump Control, 32 Control Algorithms Checkout Procedure, 67 Control Center, 5, 63 Control Modules, 78 Control Test, 67 Controls, 11 Cooler, 5 Default Screen Freeze, 29 Definitions (Controls), 11 Demand Limit Control, Option, 33 Design Set Points, (Input), 50 Details (Lubrication Cycle), 8 Display Messages (Check), 66 Dry Run to Test Start-Up Sequence, 55 Equipment Required, 41 Extended Shutdown, 57 Factory-Mounted Starter, 5 General (Controls), 11 General Maintenance, 61 Guide Vane Linkage (Check), 62 Heat Exchanger Tubes (Inspect), 64 High Altitude Locations, 53 High Discharge Temperature Control, 32 Ice Build Control, 36 Initial Start-Up, 55 Instruct the Customer Operator, 56 Introduction, 4 Job Data Required, 41 Lead/Lag Control, 34 Leak Rate, 61 Leak Test Chiller, 41 LID Operation and Menus, 14 Local Occupied Schedule (Input), 50 Local Start-Up, 39 Lubrication Cycle, 8 Lubrication System (Check), 62 Manual Guide Vane Operation, 57 Manual Operation of the Guide Vanes, 55 Motor-Compressor, 5 Motor Cooling Control, 29 Motor/Oil Refrigeration Cooling Cycle, 5 Notes on Module Operation, 78
INDEX
Oil Changes, 63 Oil Charge, 50 Oil Cooler, 32 Oil Pressure and Compressor Stop (Check), 56 Oil Reclaim Filters, 63 Oil Reclaim System, 9 Oil Specification, 63 Oil Sump Temperature Control, 32 Open Oil Circuit Valves, 41 Operating Instructions, 56 Operating the Optional Pumpout Compressor, 59 Operator Duties, 56 Optional Pumpout System Maintenance, 65 Options Modules, 79 Ordering Replacement Chiller Parts, 65 Overview (Troubleshooting Guide), 66 Physical Data, 85 PIC System Components, 11 PIC System Functions, 28 Power Up the Controls and Check the Oil Heater, 50 Pumpout Compressor Water Piping (Check), 47 Pumpout System Controls and Compressor (Check), 52 Preparation (Initial Start-Up), 55 Preparation (Pumpout and Refrigerant Transfer
Procedures), 59 Prepare the Chiller for Start-Up, 56 Pressure Transducers (Check), 65, 66 Prevent Accidential Start-Up, 56 Processor Module, 79 Pumpout and Refrigerant Transfer Procedures, 59 Ramp Loading Control, 31 Refrigerant Filter, 63 Refrigerant Float System (Inpsect), 64 Refrigerant Leak Testing, 61 Refrigerant Properties, 61 Refrigerant (Removing), 61 Refrigerant Tracer, 41 Refrigeration Cycle, 5 Refrigeration Log, 57 Relief Devices (Check), 47 Relief Valves and Piping (Inspect), 64 Remote Start/Stop Controls, 32 Repair the Leak, Retest, and Apply Standing
Vacuum Test, 62 Replacing Defective Processor Modules, 80 Rotation (Check), 55 Running System (Check), 56 Safety and Operating Controls (Check Monthly), 63 Safety Considerations, 1 Safety Controls, 29 Safety Shutdown, 41 Scheduled Maintenance, 63 Selecting Refrigerant Type, 50 Service Configuration (Input), 50 Service Ontime, 63 Service Operation, 38 Set Up Chiller Control Configuration, 50 Shipping Packaging (Remove), 41 Shutdown Sequence, 40 Solid-State Starters, 81 Spare Safety Inputs, 32 Standing Vacuum Test, 43 Starter (Check), 48 Starter Management Module, 79 Starting Equipment, 10, 65 Start-Up/Shutdown/Recycle Sequence, 39 Start the Chiller, 56 Stop the Chiller, 57
98
Page 99
Storage Vessel, 5 Summary (Lubrication Cycle), 8 Surge Prevention Algorithm, 33 Surge Protection, 34 System Components, 5 Temperature Sensors (Check), 66 Test After Service, Repair, or Major Leak, 61 Tighten All Gasketed Joints and Guide Vane Shaft
Packing, 41 Tower Fan Relay, 33 Trim Refrigerant Charge, 62
INDEX (cont)
Troubleshooting Guide, 66 Unit Mounted Solid-State Starter, 10 Unit Mounted Wye-Delta Starter, 11 Using the Optional Storage Tank and Pumpout
System, 41 Water/Brine Reset, 33 Water Leaks, 64 Water Piping (Inspect), 47 Water Treatment, 65 Weekly Maintenance, 62 Wiring (Inspect), 47
99
Page 100
Copyright 1996 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Tab 5a
PC 211 Catalog No. 531-971 Printed in U.S.A. Form 19XL-4SS Pg 100 7-96 Replaces: 19XL-3SS
Loading...