Centrifugal liquid chillers are designed to provide
safe and reliable service when operated within design
specifications. When operating this equipment, use good
judgment and safety precautions to avoid damage to
equipment and property or injury to personnel.
Be sure you understand and follow the procedures and
safety precautions contained in the chiller instructions
as well as those listed in this guide.
DO NOT VENT refrigerant relief valves within a building. Outlet
from rupture disc or relief valve must be vented outdoors in
accordance with the latest edition of ANSI/ASHRAE 15
(American National Standards Institute/American Society of Heating, Refrigeration, and Air Conditioning Engineers). The accumulation of refrigerant in an enclosed space can displace oxygen and
cause asphyxiation.
PROVIDE adequate ventilation in accordance withANSI/ASHRAE
15, especially for enclosed and low overhead spaces. Inhalation
of high concentrations of vapor is harmful and may cause heart
irregularities, unconsciousness, or death. Misuse can be fatal.
Vapor is heavier than air and reduces the amount of oxygen available for breathing. Product causes eye and skin irritation. Decomposition products are hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a chiller
for any purpose. Oxygen gas reacts violently with oil, grease, and
other common substances.
NEVER EXCEED specified test pressures, VERIFY the allowable
test pressure by checking the instruction literature and the design
pressures on the equipment nameplate.
DO NOT USE air for leak testing. Use only refrigerant or dry
nitrogen.
DO NOT VALVE OFF any safety device.
BE SURE that all pressure relief devices are properly installed and
functioning before operating any chiller.
DO NOT WELD OR FLAMECUT any refrigerant line or vessel
until all refrigerant(liquidandvapor)has been removed from chiller.
Traces of vapor should be displaced with dry air or nitrogen and
the work area should be well ventilated. Refrigerant in contact with
an open flame produces toxic gases.
DO NOT USE eyebolts or eyebolt holes to rig chiller sections or
the entire assembly.
DO NOT work on high-voltage equipment unless you are a qualified electrician.
DO NOTWORK ON electrical components, including control panels, switches, starters, or oil heater until you are sure ALL POWER
IS OFF and no residual voltage can leak from capacitors or solidstate components.
LOCK OPENAND T AGelectrical circuits during servicing. IF WORK
IS INTERRUPTED, confirm that all circuits are deenergized before resuming work.
AVOID SPILLING liquid refrigerant on skin or getting it into the
eyes. USE SAFETY GOGGLES. Wash any spills from the skin
with soap and water. If liquid refrigerant enters the eyes, IMMEDIATELY FLUSH EYES with water and consult a physician.
NEVER APPLY an open flame or live steam to a refrigerant
cylinder. Dangerous over pressure can result. When it is necessary
to heat refrigerant, use only warm (110 F [43 C]) water.
DO NOT REUSE disposable (nonreturnable) cylinders or
attempt to refill them. It is DANGEROUS AND ILLEGAL. When
cylinder is emptied, evacuate remaining gas pressure, loosen
the collar and unscrew and discard the valve stem. DO NOT
INCINERATE.
CHECK THE REFRIGERANT TYPE before adding refrigerant to
the chiller. The introduction of the wrong refrigerant can cause damage or malfunction to this chiller.
Operation of this equipment with refrigerants other than those
cited herein should comply with ANSI/ASHRAE-15 (latest edition). Contact Carrier for further information on use of this chiller
with other refrigerants.
DO NOT ATTEMPTTOREMOVE fittings, covers, etc., while chiller
is under pressure or while chiller is running. Be sure pressure is at
0 psig (0 kPa) before breaking any refrigerant connection.
CAREFULLY INSPECT all relief devices, rupture discs, and other
relief devices AT LEAST ONCE A YEAR. If chiller operates in a
corrosive atmosphere, inspect the devices at more frequent
intervals.
DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief
device when corrosion or build-up of foreign material (rust, dirt,
scale, etc.) is found within the valve body or mechanism. Replace
the device.
DO NOT install relief devices in series or backwards.
USE CARE when working near or in line with a compressed spring.
Sudden release of the spring can cause it and objects in its path to
act as projectiles.
DO NOT STEP on refrigerant lines. Broken lines can whip about
and release refrigerant, causing personal injury.
DO NOT climb over a chiller. Use platform, catwalk, or staging.
Follow safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or
move inspection covers or other heavy components. Even if components are light, use mechanical equipment when there is a risk of
slipping or losing your balance.
BE AWARE that certain automatic start arrangements CAN ENGAGE THE STARTER, TOWER FAN, OR PUMPS. Open the
disconnect ahead of the starter, tower fans, or pumps.
USE only repair or replacement parts that meet the code requirements of the original equipment.
DO NOT VENT OR DRAIN waterboxes containing industrial brines,
liquid, gases, or semisolids without the permission of your process
control group.
DO NOT LOOSEN waterbox cover bolts until the waterbox has
been completely drained.
DOUBLE-CHECK that coupling nut wrenches, dial indicators, or
other items have been removed before rotating any shafts.
DO NOT LOOSEN a packing gland nut before checking that the
nut has a positive thread engagement.
PERIODICALLY INSPECT all valves, fittings, and piping for corrosion, rust, leaks, or damage.
PROVIDE A DRAIN connection in the vent line near each pressure relief device to prevent a build-up of condensate or rain
water.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
Tab 5a
PC 211Catalog No. 531-971Printed in U.S.A.Form 19XL-4SSPg 17-96Replaces: 19XL-3SS
CONTENTS
Page
SAFETY CONSIDERATIONS ...................1
INTRODUCTION ..............................4
ABBREVIATIONS AND EXPLANATIONS .......4
CHILLER FAMILIARIZATION ..................5
Chiller Information Plate ......................5
System Components .........................5
Cooler .......................................5
Condenser ...................................5
Motor-Compressor ...........................5
Control Center ...............................5
Factory-Mounted Starter (Optional) ............5
Storage Vessel (Optional) .....................5
REFRIGERATION CYCLE .....................5
MOTOR/OIL REFRIGERATION
COOLING CYCLE ...........................5-8
LUBRICATION CYCLE .......................8,9
Summary ....................................8
Details ......................................8
Oil Reclaim System ..........................9
• DURING NORMAL CHILLER OPERATION
• DURING LIGHT LOAD CONDITIONS
STARTING EQUIPMENT ....................10,11
Unit Mounted Solid-State Starter
(Optional) ..................................10
Unit Mounted Wye-Delta Starter
(Optional) ..................................11
CONTROLS ...............................11-39
Definitions ..................................11
• ANALOG SIGNAL
• DIGITAL SIGNAL
• VOLATILE MEMORY
General .....................................11
PIC System Components ....................11
• PROCESSOR MODULE (PSIO)
• STARTER MANAGEMENT MODULE (SMM)
• LOCAL INTERFACE DEVICE (LID)
• 6-PACK RELAY BOARD
• 8-INPUT MODULES
• OIL HEATER CONTACTOR (1C)
• OIL PUMP CONTACTOR (2C)
• HOT GAS BYPASS CONTACTOR RELAY (3C)
(Optional)
• CONTROL TRANSFORMERS (T1-T4)
• CONTROL AND OIL HEATER VOLTAGE
SELECTOR (S1)
LID Operation and Menus ...................14
• GENERAL
• ALARMS AND ALERTS
• MENU STRUCTURE
• TO VIEW POINT STATUS
• OVERRIDE OPERATIONS
• TIME SCHEDULE OPERATION
• TO VIEW AND CHANGE SET POINTS
• SERVICE OPERATION
PIC System Functions .......................28
• CAPACITY CONTROL
• ENTERING CHILLED WATER CONTROL
• DEADBAND
• PROPORTIONAL BANDS AND GAIN
• DEMAND LIMITING
• CHILLER TIMERS
• OCCUPANCY SCHEDULE
Safety Controls .............................29
• SHUNT TRIP
Default Screen Freeze .......................29
Page
Motor Cooling Control .......................29
Ramp Loading Control ......................31
Capacity Override ...........................31
High Discharge Temperature Control .........32
Oil Sump Temperature Control ...............32
• PSIO SOFTWARE VERSIONS 08 AND LOWER
• PSIO SOFTWARE VERSIONS 09 AND HIGHER
Oil Cooler ..................................32
Remote Start/Stop Controls ..................32
Spare Safety Inputs .........................32
• SPARE ALARM CONTACTS
Condenser Pump Control ....................32
Condenser Freeze Protection ................32
Tower Fan Relay ............................33
Auto. Restart After Power Failure ............33
Water/Brine Reset ...........................33
• RESET TYPE 1
• RESET TYPE 2
• RESET TYPE 3
Demand Limit Control, Option
(Requires Optional 8-Input Module) ..........33
Surge Prevention Algorithm .................33
Surge Protection ............................34
Lead/Lag Control ...........................34
• COMMON POINT SENSOR INSTALLATION
• CHILLER COMMUNICATION WIRING
• LEAD/LAG OPERATION
• FAULTED CHILLER OPERATION
• LOAD BALANCING
• AUTO. RESTART AFTER POWER FAILURE
Ice Build Control ............................36
• ICE BUILD INITIATION
• START-UP/RECYCLE OPERATION
• TEMPERATURE CONTROL DURING ICE
BUILD
• TERMINATION OF ICE BUILD
• RETURN TO NON-ICE BUILD OPERATIONS
Attach to Network Device Control ............37
• CHANGING REFRIGERANT TYPES
• ATTACHING TO OTHER CCN MODULES
Service Operation ...........................38
• TO LOG ON
• TO LOG OFF
• HOLIDAY SCHEDULING
START-UP/SHUTDOWN/RECYCLE
SEQUENCE ...............................39-41
Local Start-Up ..............................39
Shutdown Sequence ........................40
Automatic Soft-Stop Amps Threshold
(PSIO Software Version 09 and Higher) ......40
Chilled Water Recycle Mode .................40
Safety Shutdown ............................41
BEFORE INITIAL START-UP ................41-54
Job Data Required ..........................41
Equipment Required ........................41
Using the Optional Storage Tank
and Pumpout System .......................41
Remove Shipping Packaging ................41
Open Oil Circuit Valves ......................41
Tighten All Gasketed Joints and
Guide Vane Shaft Packing ..................41
Check Chiller Tightness .....................41
Refrigerant Tracer ...........................41
Leak Test Chiller ............................41
Standing Vacuum Test ......................43
Chiller Dehydration .........................47
Inspect Water Piping ........................47
2
CONTENTS (cont)
Page
Check Optional Pumpout Compressor
Water Piping ...............................47
Check Relief Devices ........................47
Inspect Wiring ..............................47
Carrier Comfort Network Interface ...........48
Check Starter ...............................48
• MECHANICAL-TYPE STARTERS
• BENSHAW, INC. SOLID-STATE STARTER
Oil Charge ..................................50
Power Up the Controls and
Check the Oil Heater ........................50
• SOFTWARE VERSION
Set Up Chiller Control Configuration .........50
Input the Design Set Points ..................50
Input the Local Occupied Schedule
(OCCPC01S) ...............................50
Selecting Refrigerant Type ...................50
• TO CONFIRM REFRIGERANT TYPE
• TO CHANGE REFRIGERANT TYPE
Input Service Configurations ................50
• PASSWORD
• INPUT TIME AND DATE
• CHANGE LID CONFIGURATION
IF NECESSARY
• MODIFY CONTROLLER IDENTIFICATION
IF NECESSARY
• INPUT EQUIPMENT SERVICE PARAMETERS
IF NECESSARY
• MODIFY EQUIPMENT CONFIGURATION
IF NECESSARY
• CHECK VOLTAGE SUPPLY
• PERFORM AN AUTOMATED CONTROL TEST
Check Optional Pumpout System
Controls and Compressor ...................52
High Altitude Locations .....................53
Charge Refrigerant Into Chiller ...............53
• 19XL CHILLER EQUALIZATION WITHOUT
PUMPOUT UNIT
• 19XL CHILLER EQUALIZATION WITH
PUMPOUT UNIT
• TRIMMING REFRIGERANT CHARGE
INITIAL START-UP .........................55,56
Preparation .................................55
Manual Operation of the Guide Vanes ........55
Dry Run to Test Start-Up Sequence ..........55
Check Rotation .............................55
• IF ROTATION IS PROPER
• IF THE MOTOR ROTATION IS NOT
CLOCKWISE
• NOTES ON SOLID-STATE STARTERS
(Benshaw, Inc.)
Check Oil Pressure and Compressor Stop ....56
Calibrate Motor Current .....................56
To Prevent Accidental Start-Up ..............56
Check Chiller Operating Condition ...........56
Instruct the Customer Operator ..............56
• COOLER-CONDENSER
• OPTIONAL STORAGE TANK AND
PUMPOUT SYSTEM
• MOTOR COMPRESSOR ASSEMBLY
• MOTOR COMPRESSOR LUBRICATION SYSTEM
• CONTROL SYSTEM
• AUXILIARY EQUIPMENT
• DESCRIBE CHILLER CYCLES
• REVIEW MAINTENANCE
• SAFETY DEVICES AND PROCEDURES
• CHECK OPERATOR KNOWLEDGE
• REVIEW THE START-UP, OPERATION,
AND MAINTENANCE MANUAL
Page
OPERATING INSTRUCTIONS ...............56-58
Operator Duties .............................56
Prepare the Chiller for Start-Up ..............56
To Start the Chiller ..........................56
Check the Running System ..................56
To Stop the Chiller ..........................57
After Limited Shutdown .....................57
Extended Shutdown .........................57
After Extended Shutdown ...................57
Cold Weather Operation .....................57
Manual Guide Vane Operation ...............57
Refrigeration Log ...........................57
PUMPOUT AND REFRIGERANT
TRANSFER PROCEDURES ................59-61
Preparation .................................59
Operating the Optional Pumpout
Compressor ................................59
• TO READ REFRIGERANT PRESSURES
Chillers with Pumpout Storage Tanks ........59
• TRANSFER REFRIGERANT FROM
STORAGE TANK TO CHILLER
• TRANSFER THE REFRIGERANT FROM
CHILLER TO STORAGE TANK
Chillers with Isolation Valves ................60
• TRANSFER ALL REFRIGERANT TO
CHILLER CONDENSER VESSEL
• TRANSFER ALL REFRIGERANT TO CHILLER
COOLER/COMPRESSOR VESSEL
• RETURN REFRIGERANT TO NORMAL
OPERATING CONDITIONS
GENERAL MAINTENANCE .................61,62
Refrigerant Properties .......................61
Adding Refrigerant ..........................61
Removing Refrigerant .......................61
Adjusting the Refrigerant Charge ............61
Refrigerant Leak Testing ....................61
Leak Rate ..................................61
Test After Service, Repair, or Major Leak .....61
• REFRIGERANT TRACER
• TO PRESSURIZE WITH DRY NITROGEN
Repair the Leak, Retest, and Apply
Standing Vacuum Test ....................62
Checking Guide Vane Linkage ...............62
• CHECKING THE AUXILIARY SWITCH ON
GUIDE VANE ACTUATOR
Trim Refrigerant Charge .....................62
WEEKLY MAINTENANCE ....................62
Check the Lubrication System ...............62
SCHEDULED MAINTENANCE ..............63-65
Service Ontime .............................63
Inspect the Control Center ...................63
Check Safety and Operating Controls
Monthly ..................................63
Changing Oil Filter ..........................63
Oil Specification ............................63
Oil Changes ................................63
• TO CHANGE THE OIL
Refrigerant Filter ............................63
Oil Reclaim Filters ..........................63
Inspect Refrigerant Float System ............64
Inspect Relief Valves and Piping .............64
Compressor Bearing and Gear
Maintenance ...............................64
Inspect the Heat Exchanger Tubes ...........64
• COOLER
• CONDENSER
3
CONTENTS (cont)
Page
Water Leaks ................................64
Water Treatment ............................65
Inspect the Starting Equipment ..............65
Check Pressure Transducers ................65
Optional Pumpout System Maintenance ......65
• OPTIONAL PUMPOUT COMPRESSOR OIL
CHARGE
• OPTIONAL PUMPOUT SAFETY CONTROL
SETTINGS
Ordering Replacement Chiller Parts ..........65
TROUBLESHOOTING GUIDE ...............66-97
Overview ...................................66
Checking the Display Messages .............66
Checking Temperature Sensors ..............66
• RESISTANCE CHECK
• VOLTAGE DROP
• CHECK SENSOR ACCURACY
• DUAL TEMPERATURE SENSORS
Checking Pressure Transducers .............66
• TRANSDUCER REPLACEMENT
Control Algorithms Checkout Procedure .....67
Control Test ................................67
Page
Control Modules ............................78
• RED LED
• GREEN LEDs
Notes on Module Operation ..................78
Processor Module (PSIO) ....................79
• INPUTS
• OUTPUTS
Starter Management Module (SMM) ..........79
• INPUTS
• OUTPUTS
Options Modules (8-Input) ...................79
Replacing Defective Processor Modules ......80
• INSTALLATION
Solid-State Starters .........................81
• TESTING SILICON CONTROL RECTIFIERS
IN BENSHAW, INC. SOLID-STATE STARTERS
Physical Data ...............................85
INDEX ....................................98,99
INITIAL START-UP CHECKLIST FOR
19XL HERMETIC CENTRIFUGAL
LIQUID CHILLER ...................CL-1-CL-12
INTRODUCTION
Prior to initial start-up of the 19XL unit, those involved in
the start-up, operation, and maintenance should be thoroughly familiar with these instructions and other necessary
job data. This book is outlined so that you may become
familiar with the control system before performing start-up
procedures. Procedures in this manual are arranged in the
sequence required for proper chiller start-up and operation.
This unit uses a microprocessor control system. Do not
short or jumper between terminations on circuit boards
or modules; control or board failure may result.
Be aware of electrostatic discharge (static electricity) when
handling or making contact with circuit boards or module connections. Always touch a chassis (grounded) part
to dissipate body electrostatic charge before working
inside control center.
Use extreme care when handling tools near boards and
when connecting or disconnecting terminal plugs. Circuit boards can easily be damaged. Always hold boards
by the edges and avoid touching components and
connections.
This equipment uses, and can radiate, radio frequency
energy. If not installed and used in accordance with
the instruction manual, it may cause interference to
radio communications. It has been tested and found to
comply with the limits for a Class A computing device
pursuant to Subpart J of Part 15 of FCC (Federal Communication Commission) Rules, which are designed to
provide reasonable protection against such interference
when operated in a commercial environment. Operation
of this equipment in a residential area is likely to cause
interference, in which case the user, at his own expense,
will be required to take whatever measures may be required to correct the interference.
Always store and transport replacement or defective boards
in anti-static shipping bag.
ABBREVIATIONS AND EXPLANATIONS
Frequently used abbreviations in this manual include:
CCN— Carrier Comfort Network
CCW— Counterclockwise
CW— Clockwise
ECW— Entering Chilled Water
ECDW — Entering Condenser Water
EMS— Energy Management System
HGBP — Hot Gas Bypass
I/O— Input/Output
LCD— Liquid Crystal Display
LCDW — Leaving Condenser Water
LCW— Leaving Chilled Water
LED— Light-Emitting Diode
LID— Local Interface Device
OLTA— Overload Trip Amps
PIC— Product Integrated Control
PSIO— Processor Sensor Input/Output Module
RLA— Rated Load Amps
SCR— Silicon Control Rectifier
SI— International System of Units
SMM— Starter Management Module
TXV— Thermostatic Expansion Valve
The 19XL chillers use HCFC-22 and HFC-134a refrigerant. When referencing refrigerant charges in this manual,
the HCFC-22 charge will be listed first and the HFC-134a
value will be shown next to it in brackets [].
Words printed in all capital letters and italics represent values that may be viewed on the LID.
The PSIO software version number of your 19XL unit will
be located on the front cover.
4
CHILLER FAMILIARIZATION
(Fig. 1, 2A, and 2B)
Chiller Information Plate —
is located on the right side of the chiller control center
panel.
Fig. 1 — 19XL Identification
The information plate
System Components — The components include the
cooler and condenser heat exchangers in separate vessels,
motor-compressor, lubrication package, control center, and
motor starter.All connections from pressure vessels have external threads to enable each component to be pressure tested
with a threaded pipe cap during factory assembly.
Cooler — This vessel (also known as the evaporator) is
located underneath the compressor. The cooler is maintained at lower temperature/pressure so that evaporating
refrigerant can remove heat from water flowing through its
internal tubes.
Condenser — The condenser operates at a higher
temperature/pressure than the cooler, and has water flowing
through its internal tubes in order to remove heat from the
refrigerant.
Motor-Compressor— This component maintains sys-
tem temperature/pressure differences and moves the heat
carrying refrigerant from the cooler to the condenser.
Control Center — The control center is the user inter-
face for controlling the chiller. It regulates the chiller’s
capacity as required to maintain proper leaving chilled water
temperature. The control center:
• registers cooler, condenser, and lubricating system
pressures
• shows chiller operating condition and alarm shutdown
conditions
• records the total chiller operating hours
• sequences chiller start, stop, and recycle under microprocessor control
• provides access to other CCN (Carrier Comfort Network)
devices
Factory-Mounted Starter (Optional)— The starter
allows the proper start and disconnect of electrical energy
for the compressor-motor, oil pump, oil heater, and control
panels.
Storage Vessel (Optional) — There are 2 sizes
of storage vessels available. The vessels have double relief
valves, a magnetically coupled dial-type refrigerant level
gage, a one-inch FPT drain valve, and a
vapor connection for the pumpout unit. A 30-in.-0-400 psi
(–101-0-2750 kPa) gage also is supplied with each unit.
NOTE: If a storage vessel is not used at the jobsite, factoryinstalled isolation valves on the chiller may be used to isolate the chiller charge in either the cooler or condenser.
An optional pumpout compressor system is used to transfer
refrigerant from vessel to vessel.
1
⁄2-in. male flare
REFRIGERATION CYCLE
The compressor continuously draws refrigerant vapor from
the cooler, at a rate set by the amount of guide vane opening.
As the compressor suction reduces the pressure in the cooler,
the remaining refrigerant boils at a fairly low temperature
(typically 38 to 42 F [3 to 6 C]). The energy required for
boiling is obtained from the water flowing through the cooler
tubes. With heat energy removed, the water becomes cold
enough for use in an air conditioning circuit or process liquid cooling.
After taking heat from the water, the refrigerant vapor
is compressed. Compression adds still more heat energy
and the refrigerant is quite warm (typically 98 to 102 F
[37 to 40 C]) when it is discharged from the compressor into
the condenser.
Relatively cool (typically 65 to 90 F [18 to 32 C]) water
flowing into the condenser tubes removes heat from the
refrigerant and the vapor condenses to liquid.
The liquid refrigerant passes through orifices into the
FLASC (Flash Subcooler) chamber (Fig. 3). Since the FLASC
chamber is at a lower pressure, part of the liquid refrigerant
flashes to vapor, thereby cooling the remaining liquid. The
FLASC vapor is recondensed on the tubes which are cooled
by entering condenser water. The liquid drains into a float
chamber between the FLASC chamber and cooler. Here a
float valve forms a liquid seal to keep FLASC chamber
vapor from entering the cooler. When liquid refrigerant passes
through the valve, some of it flashes to vapor in the reduced
pressure on the cooler side. In flashing, it removes heat from
the remaining liquid. The refrigerant is now at a temperature
and pressure at which the cycle began.
MOTOR/OIL REFRIGERATION
COOLING CYCLE
The motor and the lubricating oil are cooled by liquid
refrigerant taken from the bottom of the condenser vessel
(Fig. 3). Flow of refrigerant is maintained by the pressure
differentialthat exists due to compressor operation.After the
refrigerant flows past an isolation valve, an in-line
filter, and a sight glass/moisture indicator, the flow is split
between motor cooling and oil cooling systems.
Flow to the motor flows through an orifice and into the
motor.There is also another orifice and a solenoid valve which
will open if additional motor cooling is required. Once past
the orifice, the refrigerant is directed over the motor by a
spray nozzle. The refrigerant collects in the bottom of the
motor casing and then is drained back into the cooler through
the motor refrigerant drain line. A back pressure valve or an
orifice in this line maintains a higher pressure in the motor
shell than in the cooler/oil sump. The motor is protected by
a temperature sensor imbedded in the stator windings. Higher
motor temperatures (above 125 F [51 C]) energize a solenoid to provide additional motor cooling. A further increase
in temperature past the motor override set point will override the temperature capacity control to hold, and if the
motor temperature rises 10° F (5.5° C) above this set point,
will close the inlet guide vanes. If the temperature rises above
the safety limit, the compressor will shut down.
Fig. 3 — Refrigerant Motor Cooling and Oil Cooling Cycles
Refrigerant that flows to the oil cooling system is regulated by a thermostatic expansion valve. There is always
a minimum flow bypassing the TXV, which flows through
an orifice. The TXV valve regulates flow into the oil/
refrigerant plate and frame-type heat exchanger. The bulb
for the expansion valve controls oil temperature to the bearings. The refrigerant leaving the heat exchanger then returns
to the cooler.
LUBRICATION CYCLE
Summary—
up a package located partially in the transmission casting of
the compressor-motor assembly. The oil is pumped into a
filter assembly to remove foreign particles, and is then forced
into an oil cooler heat exchanger where the oil is cooled to
proper operational temperatures. After the oil cooler, part of
the flow is directed to the gears and the high speed shaft
bearings; the remaining flow is directed to the motor shaft
bearings. Oil drains into the transmission oil sump to complete the cycle (Fig. 4).
The oil pump, oil filter, and oil cooler make
Details— Oil is charged into the lubrication system through
a hand valve. Two sight glasses in the oil reservoir permit oil
level observation. Normal oil level is between the middle of
the upper sight glass and the top of the lower sight glass
when the compressor is shut down. The oil level should be
visible in at least one of the 2 sight glasses during operation.
Oil sump temperature is displayed on the LID default
screen. Oil sump temperature ranges during compressor
operation between 100 to 120 F (37 to 49 C) [120 to 140 F
(49 to 60 C)].
The oil pump suction is fed from the oil reservoir. An
oil pressure relief valve maintains 18 to 25 psid (124 to
172 kPad) differential pressure in the system at the pump
discharge.This dif ferentialpressure can be read directly from
the Local Interface Device (LID) default screen. The oil pump
discharges oil to the oil filter assembly. This filter can be
valved closed to permit removal of the filter without draining the entire oil system (see Maintenance sections, pages
61 to 65, for details). The oil is then piped to the oil cooler.
This heat exchanger uses refrigerant from the condenser as
the coolant. The refrigerant cools the oil to a temperature
between 100 and 120 F (37 to 49 C).
As the oil leaves the oil cooler, it passes the oil pressure
transducer and the thermal bulb for the refrigerant expansion valve on the oil cooler. The oil is then divided, with a
portion flowing to the thrust bearing, forward pinion bearing, and gear spray. The balance then lubricates the motor
shaft bearings and the rear pinion bearing. The oil temperature is measured as the oil leaves the thrust and forward
8
Fig. 4 — Lubrication System
journal bearings within the bearing housing. The oil then drains
into the oil reservoir at the base of the compressor. The PIC
(Product Integrated Control) measures the temperature of the
oil in the sump and maintains the temperature during shutdown (see Oil Sump Temperature Control section, page 32).
This temperature is read on the LID default screen.
During the chiller start-up, the PIC will energize the oil
pump and provide 15 seconds of prelubrication to the bearings after pressure is verified before starting the compressor.
During shutdown, the oil pump will run for 60 seconds to
post-lubricate after the compressor shuts down. The oil pump
can also be energized for testing purposes in the Control Test.
Ramp loading can slow the rate of guide vane opening
to minimize oil foaming at start-up. If the guide vanes
open quickly, the sudden drop in suction pressure can cause
any refrigerant in the oil to flash. The resulting oil foam
cannot be pumped efficiently; therefore, oil pressure falls
off and lubrication is poor. If oil pressure falls below
15 psid (103 kPad) differential, the PIC will shut down the
compressor.
Oil Reclaim System — The oil reclaim system oper-
ates to return oil back to the oil reservoir by recovering it
from 2 areas on the chiller. The primary area of recovery is
from the guide vane housing. Oil also is recovered, along
with refrigerant, from the cooler.
Any refrigerant that enters the oil reservoir/transmission
area is flashed into gas. The demister line at the top of the
casing will vent this refrigerant into the suction of the compressor. Oil entrained in the refrigerant is eliminated by the
demister filter.
DURING NORMAL CHILLER OPERATION, oil is
entrained with the refrigerant. As the compressor pulls
the refrigerant into the guide vane housing to be compressed, the oil will normally drop out at this point and
fall to the bottom of the housing where it accumulates. Using discharge gas pressure to power an eductor, the oil is
vacuumed from the housing by the eductor and is discharged into the oil reservoir. Oil and refrigerant are also
recovered from the top of the cooler refrigerant level and are
discharged into the guide vane housing. The oil will drop to
the bottom of the guide vane housing and be recovered by
the eductor system.
DURING LIGHT LOAD CONDITIONS, the suction gas into
the compressor does not have enough velocity to return oil,
which is floating in the cooler back to the compressor. In
addition, the eductor may not have enough power to pull the
oil from the guide vane housing back into the oil reservoir
due to extremely low pressure at the guide vanes. Two solenoids, located on the oil reclaim piping, are operated so
that the eductor can pull oil and refrigerant directly from the
cooler and discharge the mixture into the oil reservoir. The
oil reclaim solenoids are operated by an auxiliary contact
integral to the guide vane actuator. This switchover of the
solenoids occurs when the guide vanes are opened beyond
30 degrees from the closed position.
9
STARTING EQUIPMENT
The 19XL requires a motor starter to operate the centrifugal hermetic compressor motor, the oil pump, and various
auxiliary equipment. The starter serves as the main field
wiring interface for the contractor.
Three types of starters are available from Carrier Corporation: solid-state, wye-delta, and across-the-line starters.
See Carrier Specification Z-375 for specific starter requirements. All starters must meet these specifications in order
to properly start and satisfy mechanical safety requirements.
Starters may be supplied as separate, free-standing units, or
may be mounted directly on the chiller (unit mounted) for
low-voltage units only.
Inside the starter are 3 separate circuit breakers. Circuit
breaker CB1 is the compressor motor circuit breaker. The
disconnect switch on the starter front cover is connected to
this breaker. Circuit breaker CB1 supplies power to the compressor motor.
The main circuit breaker (CB1) on the front of the starter
disconnects the main motor current only. Power is still
energized for the other circuits. Two more circuit breakers inside the starter must be turned off to disconnect
power to the oil pump, PIC controls, and oil heater.
Circuit breaker CB2 supplies power to the control center,
oil heater, and portions of the starter controls. Circuit breaker
CB3 supplies power to oil pump. Both of these circuit breakers are wired in parallel with CB1 so that power is supplied
to them if the CB1 disconnect is open.
All starters are shipped with a Carrier control module called
the Starter Management Module (SMM). This module
controls and monitors all aspects of the starter. See the Controls section on page 11 for additional SMM information.
All starter replacement parts are supplied by the starter
manufacturer.
LEGEND
1—Field Wiring Terminal Strips (TB2 and TB3)
2—Circuit Breaker 1, 2, 3, 4
3—Overload Unit
4—Solid-State Controller
5—Silicon Controlled Rectifier (SCR) LED (One of 6)
6—Starter Fault and Run LEDs
7—Voltmeter (Optional)
8—Ammeter (Optional)
9—SCR (One of 6)
10 — Voltage LED
11 — Starter Management Module (SMM)
12 — Pilot Relays (PR1 to PR5)
13 — Starter Access Door
Fig. 5 — Benshaw, Inc. Solid-State Starter,
Internal View
Unit-Mounted Solid-State Starter (Optional)
The 19XL may be equipped with a solid-state, reduced-
—
voltage starter (Fig. 5 and 6). This starter provides on-off
control of the compressor motor as its primary function.
Using this type of starter reduces the peak starting torque,
reduces the motor inrush current, and decreases mechanical
shock. This is summed up by the phrase ‘‘soft starting.’’
Two varieties of solid-state starters are available as a 19XL
option (factory supplied and installed). When a unit-mounted,
optional, solid-state starter is purchased with the 19XL, a
Benshaw,Inc. solid-state starter will be shipped with the unit.
See Fig. 5. The solid-state starter’s manufacturer name will
be located inside the starter access door. See Fig. 6.
These starters operate by reducing the starting voltage. The
starting torque of a motor at full voltage is typically 125%
to 175% of the running torque. When the voltage and the
current are reduced at start-up, the starting torque is reduced
as well. The object is to reduce the starting voltage to just
the voltage necessary to develop the torque required to get
the motor moving. The voltage and current are then ramped
up in a desired period of time. The voltage is reduced through
the use of silicon controlled rectifiers (SCR). Once full voltage is reached, a bypass contactor is energized to bypass the
SCRs.
When voltage is supplied to the solid-state circuitry, the
heat sinks within the starter are at line voltage. Do not
touch the heat sinks while voltage is present or serious
injury will result.
Fig.6—Typical Starter External View
(Solid-State Starter Shown)
There are a number of LEDs (light-emitting diodes) that
are useful in troubleshooting and starter check-out on
Benshaw, Inc. solid-state starters. These are used to
indicate:
• voltage to the SCRs
• SCR control voltage
• power indication
• proper phasing for rotation
• start circuit energized
10
• overtemperature
• ground fault
• current unbalance
• run state
These LEDs are further explained in the Check Starter and
Troubleshooting Guide section, page 66.
Unit-MountedWye-DeltaStarter (Optional) — The
19XLchiller may be equipped with a wye-delta starter mounted
on the unit (Fig. 7). This starter is intended for use with lowvoltage motors (under 600 v). It reduces the starting current
inrush by connecting each phase of the motor windings into
a wye configuration. This occurs during the starting period
when the motor is accelerating up to speed. After a time delay, once the motor is up to speed, the starter automatically
connects the phase windings into a delta configuration.
1234567
17
16
15
1011121314
1—Pilot Relays
2—SMM Power Circuit Breaker and Voltage Calibration
9—Ammeter (Optional)
10 — Current Transformers (T1, T2, T3)
11 — Phase Monitor Relay (Optional)
12 — Overload Unit
13 — Starter Management Module
14 — Starter Access Door
15 — Control Transformer Secondary Circuit Breaker
16 — Signal Resistor
17 — Field Wiring Terminal Strip (TB6)
LEGEND
Fig.7—Wye-Delta Starter, Internal View
Definitions
CONTROLS
ANALOG SIGNAL — An analog signal varies in proportion to the monitored source. It quantifies values between
operating limits. (Example: A temperature sensor is an analog device because its resistance changes in proportion to
the temperature, generating many values.)
DIGIT ALSIGNAL—A digital (discrete) signal is a 2-position
representation of the value of a monitored source. (Example: A switch is a digital device because it only indicates
whether a value is above or below a set point or boundary
by generating an on/off, high/low, or open/closed signal.)
VOLATILE MEMORY — Volatile memory is memory in-
capable of being sustained if power is lost and subsequently
restored.
9
The memory of the PSIO and LID modules are volatile.
If the battery in a module is removed or damaged, all
programming will be lost.
General — The 19XL hermetic centrifugal liquid chiller
contains a microprocessor-based control center that monitors and controls all operations of the chiller. The microprocessor control system matches the cooling capacity of the
chiller to the cooling load while providing state-of-the-art
chiller protection. The system controls cooling load within
the set point plus the deadband by sensing the leaving chilled
water or brine temperature, and regulating the inlet guide
vane via a mechanically linked actuator motor. The guide
vane is a variable flow prewhirl assembly that controls the
refrigeration effect in the cooler by regulating the amount of
refrigerant vapor flow into the compressor. An increase in
guide vane opening increases capacity. A decrease in guide
vane opening decreases capacity. Chiller protection is provided by the processor which monitors the digital and analog inputs and executes capacity overrides or safety shutdowns,
if required.
PIC System Components — The Product Integrated
Control (PIC) is the control system on the chiller. See
8
T able1. The PIC controls the operation of the chiller by monitoring all operating conditions. The PIC can diagnose a problem and let the operator know what the problem is and what
to check. It promptly positions the guide vanes to maintain
leaving chilled water temperature. It can interface with auxiliary equipment such as pumps and cooling tower fans to
turn them on only when required. It continually checks all
safeties to prevent any unsafe operating condition. It also
regulates the oil heater while the compressor is off, and the
hot gas bypass valve, if installed.
The PIC can be interfaced with the Carrier Comfort Network (CCN) if desired. It can communicate with other PICequipped chillers and other CCN devices.
The PIC consists of 3 modules housed inside the 3 major
components. The component names and the control voltage
contained in each component are listed below (also see
Table 1):
• control center — all extra low-voltage wiring (24 v or less)
• power panel — 230 or 115 v control voltage (per job
requirement)
— up to 600 v for oil pump power
• starter cabinet — chiller power wiring (per job
requirement)
Table 1 — Major PIC Components and
Panel Locations*
PIC COMPONENT
Processor Sensor Input/Output Module
(PSIO)
Starter Management Module (SMM)Starter Cabinet
Local Interface Device (LID)Control Center
6-Pack Relay BoardControl Center
8-Input Modules (Optional)Control Center
Oil Heater Contactor (1C)Power Panel
Oil Pump Contactor (2C)Power Panel
Hot Gas Bypass Relay (3C) (Optional)Power Panel
Control Transformers (T1-T4)Power Panel
Control and Oil Heater Voltage Selector (S1) Power Panel
Temperature SensorsSee Fig. 8
Pressure TransducersSee Fig. 8
*See Fig. 5, 6, and Fig. 8-12.
PANEL
LOCATION
Control Center
11
Fig. 8 — 19XL Controls and Sensor Locations
Fig. 9 — Control Sensors
(Temperature)
Fig. 10 — Control Sensors
(Pressure Transducer, Typical)
12
LEGEND
1—LID
2—PSIO
3—8-Input Module (One of 2 Available)
4—5-Volt Transducer Power Supply
5—6-Pack Relay Board
6—Circuit Breakers (4)
Fig. 11 — Control Center (Front View),
with Options Module
PROCESSOR MODULE (PSIO) — The PSIO is the brain
of the PIC (Fig. 11). This module contains all the operating
software needed to control the chiller.The 19XLuses 3 pressure transducers and 8 thermistors to sense pressures and temperatures. These are connected to the PSIO module. The PSIO
also provides outputs to the guide vane actuator, oil pump,
oil heater, hot gas bypass (optional), motor cooling solenoid,
and alarm contact. The PSIO communicates with the LID,
the SMM, and the optional 8-input modules for user interface and starter management.
ST ARTER MANAGEMENT MODULE (SMM) — This module is located within the starter cabinet. This module initiates PSIO commands for starter functions such as start/
stop of the compressor, start/stop of the condenser and chilled
water pumps, start/stop of the tower fan, spare alarm contacts, and the shunt trip. The SMM monitors starter inputs
such as flow switches, line voltage, remote start contact, spare
safety, condenser high pressure, oil pump interlock, motor
current signal, starter 1M and run contacts, and kW transducer input (optional). The SMM contains logic capable of
safely shutting down the machine if communications with
the PSIO are lost.
LOCALINTERFACEDEVICE (LID) — The LID is mounted
to the control center and allows the operator to interface with
the PSIO or other CCN devices (Fig. 11). It is the input center for all local chiller set points, schedules, set-up functions, and options. The LID has a STOP button, an alarm
light, 4 buttons for logic inputs, and a display. The function
of the 4 buttons or ‘‘softkeys’’are menu driven and are shown
on the display directly above the key.
6-PACK RELAY BOARD — This device is a cluster of
6 pilot relays located in the control center (Fig. 11). It is
energized by the PSIO for the oil pump, oil heater, alarm,
optional hot gas bypass relay, and motor cooling solenoid.
8-INPUT MODULES — One optional module is factory installed in the control center panel when ordered (Fig. 11).
There can be up to 2 of these modules per chiller with
8 spare inputs each. They are used whenever chilled water
reset, demand reset, or reading a spare sensor is required.
The sensors or 4 to 20 mA signals are field-installed.
The spare temperature sensors must have the same
temperature/resistance curve as the other temperature sensors on this unit. These sensors are 5,000 ohm at 75 F
(25 C).
OIL HEATER CONTACTOR (1C) — This contactor is located in the power panel (Fig. 12) and operates the heater at
either 115 or 230 v. It is controlled by the PIC to maintain
oil temperature during chiller shutdown.
OIL PUMP CONTACTOR (2C) — This contactor is located
in the power panel (Fig. 12). It operates all 200 to 575-v oil
pumps. The PIC energizes the contactor to turn on the oil
pump as necessary.
HOT GAS BYPASS CONTACTOR RELAY (3C) (Optional) — This relay, located in the power panel, (Item 5,
Fig. 12) controls the opening of the hot gas bypass valve.
The PIC energizes the relay during low load, high lift
conditions.
CONTROL TRANSFORMERS (T1-T4) — These transformers convert incoming control voltage to either 21 vac
power for the PSIO module and options modules, or 24 vac
power for 3 power panel contactor relays, 3 control solenoid
valves, and the guide vane actuator. They are located in the
power panel. See Fig. 12.
CONTROLANDOIL HEATERVOLTAGE SELECTOR (S1)
— It is possible to use either 115 v or 230 v incoming control power in the power panel. The switch is set to the voltage used at the jobsite.
LEGEND
1—T2 — 24 vac Power Transformer for Hot Gas Bypass Relay,
4—T1 — 24 vac, Control Center Transformer
5—3C Hot Gas Bypass Relay Location
6—Oil Pump Terminal Block
7—Factory Terminal Connections
8—T3 — 24 vac Guide Vane Actuator Transformer
LID Operation and Menus (Fig. 13-19)
GENERAL
• The LID display will automatically revert to the default
screen after 15 minutes if no softkey activity takes place
and if the chiller is not in the Pumpdown mode
(Fig. 13).
• When not in the default screen, the upper right-hand corner of the LID always displays the name of the screen that
you have entered (Fig. 14).
• The LID may be configured in English or SI units, through
the LID configuration screen.
• Local Operation — By pressing the LOCAL
PIC is now in the LOCAL operation mode. The control
will accept changes to set points and configurations from
the LID only. The PIC will use the Local Time Schedule
to determine chiller start and stop times.
• CCN Operation — By pressing the CCN
is now in the CCN operation mode, and the control will
accept modifications from any CCN interface or module
(with the proper authority), as well as the LID. The PIC
will use the CCN time schedule to determine start and stop
times.
softkey,the
softkey,the PIC
ALARMS AND ALERTS — Alarm (*) and alert (!) status
are indicated on the Status tables.An alarm (*) will shut down
the compressor.An alert (!) notifies the operator that an unusual condition has occurred. The chiller will continue to
operate when an alert is shown.
Alarms are indicated when the control center alarm light
(!) flashes. The primary alarm message is viewed on the default screen and an additional, secondary, message and
troubleshooting information are sent to the Alarm History
table.
When an alarm is detected, the LID default screen will
freeze (stop updating) at the time of alarm. The freeze enables the operator to view the chiller conditions at the time
of alarm. The Status tables will show the updated information. Once all alarms have been cleared (by pressing the
RESET softkey), the default LID screen will return to nor-
mal operation.
MENU STRUCTURE — To perform any of the operations
described below, the PIC must be powered up and have successfully completed its self test. The self test takes place
automatically, after power-up.
• Press QUIT
out saving any changes.
to leave the selected decision or field with-
Fig. 13 — LID Default Screen
• Press ENTER to leave the selected decision or field and
save changes.
• Press NEXT to scroll the cursor bar down in order to
highlight a point or to view more points below the current
screen.
• Press PREVIOUS to scroll the cursor bar up in order to
highlight a point or to view points above the current screen.
• Press SELECT to view the next screen level (high-
lighted with the cursor bar), or to override (if allowable)
the highlighted point value.
Fig. 14 — LID Service Screen
14
• Press EXIT to return to the previous screen level.
• Press INCREASE or DECREASE to change the highlighted point value.
TO VIEW POINT STATUS (Fig. 15) — Point Status is the
actual value of all of the temperatures, pressures, relays, and
actuators sensed and controlled by the PIC.
1. On the Menu screen, press STATUS
to view the list of
Point Status tables.
4. OnthePointStatustablepressNEXTor
PREVIOUS
until desired point is displayed on the screen.
OVERRIDE OPERATIONS
To Override a Value or Status
1. OnthePointStatustablepressNEXTor
PREVIOUS
to highlight the desired point.
2. Press SELECT to select the highlighted point. Then:
2. Press NEXT or PREVIOUS to highlight the desired
status table. The list of tables is:
• Status01 — Status of control points and sensors
• Status02 — Status of relays and contacts
• Status03 — Status of both optional 8-input modules and
sensors
3. Press SELECT to view the Point Status table desired.
For Discrete Points — Press START or STOP to select the desired state.
ForAnalogPoints—PressINCREASEor
DECREASE
to select the desired value.
3. Press ENTER to register new value.
NOTE: When overriding or changing metric values, it is
necessary to hold the softkey down for a few seconds in order to see a value change, especially on kilopascal
values.
To Remove an Override
1. OnthePointStatustablepressNEXTor
PREVIOUS
to highlight the desired point.
Fig. 15 − Example of Point Status Screen
(Status01)
2. Press SELECT to access the highlighted point.
15
3. Press RELEASE to remove the override and return the
point to the PIC’s automatic control.
4. Press NEXT or PREVIOUS to highlight the desired period or override that you wish to change.
Override Indication— An override value is indicated by
‘ ‘SUPVSR,’’‘‘SERVC,’’or‘‘BEST’’flashing next to the point
value on the Status table.
TIME SCHEDULE OPERATION (Fig. 16)
1. On the Menu screen, press SCHEDULE
.
2. Press NEXT or PREVIOUS to highlight the desired schedule.
PSIO Software Version 08 and lower:
OCCPC01S — LOCAL Time Schedule
OCCPC02S — CCN Time Schedule
PSIO Software Version 09 and higher:
OCCPC01S — LOCAL Time Schedule
OCCPC02S — ICE BUILD Time Schedule
OCCPC03-99S — CCN Time Schedule (Actual
number is defined in
Config table.)
5. Press SELECT to access the highlighted period or
override.
a. Press INCREASE
6.
or DECREASE to change the
time values. Override values are in one-hour increments, up to 4 hours.
b. Press ENABLE to select days in the day-of-week
fields. Press DISABLE
to eliminate days from the
period.
7. Press ENTER to register the values and to move
horizontally (left to right) within a period.
3. Press SELECT to access and view the time schedule.
Fig. 16 — Example of Time Schedule
Operation Screen
8. Press EXIT to leave the period or override.
9. Either return to Step 4 to select another period or
override, or press EXIT
again to leave the current time
schedule screen and save the changes.
10. Holiday Designation (HOLIDEF table) may be found in
the Service Operation section, page 38. You must assign
the month, day, and duration for the holiday.The Broadcast function in the Brodefs table also must be enabled
for holiday periods to function.
16
*Only available on PSIO Software Version 09 and higher.
†Available on PSIO Software Versions 07 and 08.
Fig. 17 — 19XL Menu Structure
17
18
Fig. 18 — 19XL Service Menu Structure
19
Fig. 18 — 19XL Service Menu Structure (cont)
*Only available on PSIO Software Version 09 and higher.
†Available on PSIO Software Versions 07 and 08.
TO VIEW AND CHANGE SET POINTS (Fig. 19)
1. To view the Set Point table, at the Menu screen press
SETPOINT
2. There are 4 set points on this screen: Base Demand Limit;
LCW Set Point (leaving chilled water set point); ECW
Set Point (entering chilled water set point); and ICE BUILD
set point (PSIO Software Version 09 and higher only).
Only one of the chilled water set points can be active at
one time, and the type of set point is activated in the Service menu. ICE BUILD is also activated and configured in
the Service menu.
.
3. Press NEXT
set point entry.
4. Press SELECT to modify the highlighted set point.
5. Press INCREASE or DECREASE to change the selected set point value.
6. Press ENTER to save the changes and return to the
previous screen.
or PREVIOUS to highlight the desired
Fig. 19 — Example of Set Point Screen
SERVICE OPERATION — To view the menu-driven programs available for Service Operation, see Service Operation section, page 38. For examples of LID display screens,
see Table 2.
20
Table 2 — LID Screens
NOTES:
1. Only 12 lines of information appear on the LID screen at any given time. Press NEXT or PREVIOUS to highlight a point or to view points
below or above the current screen.
2. The LID may be configured in English or SI units, as required, through the LID configuration screen.
3. Data appearing in the Reference Point Names column is used for CCN operations only.
4. All options associated with ICE BUILD, Lead/Lag, CCN Occupancy Configuration, and Soft Stopping are only available on PSIO Software
Version 9 and higher.
EXAMPLE1—STATUS01 DISPLAY SCREEN
To access this display from the LID default screen:
1. PressMENU
2. Press STATUS (STATUS01 will be highlighted).
3. Press SELECT
.
.
DESCRIPTIONRANGEUNITS
Control ModeReset, Off, Local, CCNMODE
Run Status
Occupied ?No/YesOCC
Alarm StateNormal/AlarmALM
*Chiller Start/StopStop/StartCHIL S S
Base Demand Limit40-100%DLM
*Active Demand Limit40-100%DEM LIM
Compressor Motor Load0-999%CA L
Current0-999%CA P
Amps0-999AMPSCA A
*Target Guide Vane Pos0-100%GV TRG
Actual Guide Vane Pos0-100%GV ACT
Water/Brine: Setpoint10-120 (–12.2-48.9)DEG F (DEG C)SP
*Control Point10-120 (–12.2-48.9)DEG F (DEG C)LCW STPT
Entering Chilled Water–40-245 (–40-118)DEG F (DEG C)ECW
Leaving Chilled Water–40-245 (–40-118)DEG F (DEG C)LCW
Entering Condenser Water–40-245 (–40-118)DEG F (DEG C)ECDW
Leaving Condenser Water–40-245 (–40-118)DEG F (DEG C)LCDW
Evaporator Refrig Temp–40-245 (–40-118)DEG F (DEG C)ERT
Evaporator Pressure–6.7-420 (–46-2896)PSI (kPa)ERP
Condenser Refrig Temp–40-245 (–40-118)DEG F (DEG C)CRT
Condenser Pressure–6.7-420 (–46-2896)PSI (kPa)CRP
Discharge Temperature–40-245 (–40-118)DEG F (DEG C)CMPD
Bearing Temperature–40-245 (–40-118)DEG F (DEG C)MTRB
Motor Winding Temp–40-245 (–40-118)DEG F (DEG C)MTRW
Oil Sump Temperature–40-245 (–40-118)DEG F (DEG C)OILT
Oil Pressure Transducer–6.7-420 (–46-2896)PSI (kPa)OILP
Oil Pressure–6.7-420 (–46-2896)PSID (kPad)OILPD
Line Voltage: Percent0-999%V P
*Remote Contacts InputOff/OnREMCON
Total Compressor Starts0-65535c starts
Starts in 12 Hours0-8STARTS
Compressor Ontime0-500000.0HOURSc hrs
*Service Ontime0-32767HOURSS HRS
*Compressor Motor kW0-9999kWCKW
NOTE: All values are variables available for read operation to a CCN. Descriptions shown with (*) support write operations for BEST programming
language, data transfer, and overriding.
*Temp Reset 4-20 mA4-20mARES OPT
*Common CHWS Sensor–40-245 (–40-118)DEG F (DEG C)CHWS
*Common CHWR Sensor–40-245 (–40-118)DEG F (DEG C)CHWR
*Remote Reset Sensor–40-245 (–40-118)DEG F (DEG C)R RESET
*Temp Sensor — Spare 1–40-245 (–40-118)DEG F (DEG C)SPARE1
*Temp Sensor — Spare 2–40-245 (–40-118)DEG F (DEG C)SPARE2
*Temp Sensor — Spare 3–40-245 (–40-118)DEG F (DEG C)SPARE3
OPTIONS BOARD 2
*4-20 mA — Spare 14-20mASPARE1 M
*4-20 mA — Spare 24-20mASPARE2 M
*Temp Sensor — Spare 4–40-245 (–40-118)DEG F (DEG C)SPARE4
*Temp Sensor — Spare 5–40-245 (–40-118)DEG F (DEG C)SPARE5
*Temp Sensor — Spare 6–40-245 (–40-118)DEG F (DEG C)SPARE6
*Temp Sensor — Spare 7–40-245 (–40-118)DEG F (DEG C)SPARE7
*Temp Sensor — Spare 8–40-245 (–40-118)DEG F (DEG C)SPARE8
*Temp Sensor — Spare 9–40-245 (–40-118)DEG F (DEG C)SPARE9
NOTE: All values shall be variables available for read operation to a CCN network. Descriptions shown with (*) support write operations for BEST
programming language, data transfer, and overriding.
.
.
.
DESCRIPTIONRANGEUNITS
POINT TYPE
INPUTOUTPUT
EXAMPLE3—STATUS03 DISPLAY SCREEN
UNITS
REFERENCE POINT NAME
(ALARM HISTORY)
REFERENCE POINT NAME
(ALARM HISTORY)
EXAMPLE 4 — SETPOINT DISPLAY SCREEN
To access this display from the LID default screen:
1. PressMENU
2. Press SETPOINT
DESCRIPTIONCONFIGURABLE RANGEUNITSREFERENCE POINT NAMEDEFAULT VALUE
Base Demand Limit40-100%DLM100
LCW Setpoint20-120 (–6.7-48.9)DEG F (DEG C)lcw sp
ECW Setpoint20-120 (–6.7-48.9)DEG F (DEG C)ecw sp
ICE BUILD Setpoint20- 60 (–6.7-15.6)DEG F (DEG C)ice sp40.0 ( 4.4)
.
.
50.0 (10.0)
60.0 (15.6)
22
Table 2 — LID Screens (cont)
EXAMPLE 5 — CONFIGURATION (CONFIG) DISPLAY SCREEN
To access this display from the LID default screen:
1. PressMENU
2. Press SERVICE
3. Scroll down to highlight EQUIPMENT CONFIGURATION.
4. Press SELECT
5. Scroll down to highlight CONFIG.
6. Press SELECT
DESCRIPTIONCONFIGURABLE RANGEUNITSREFERENCE POINT NAMEDEFAULT VALUE
RESET TYPE 1
Degrees Reset at 20 mA–30-30 (–17-17)DEG F (DEG C)deg 20ma
RESET TYPE 2
Remote Temp (No Reset)–40-245 (–40-118)DEG F (DEG C)res rt1
Remote Temp (Full Reset)–40-245 (–40-118)DEG F (DEG C)res rt265 (18)
Degrees Reset–30-30 (–17-17)DEG F (DEG C)res rt10D(6D)
RESET TYPE 3
CHW Delta T (No Reset)0-15 (0-8)DEG F (DEG C)restd 1
CHW Delta T (Full Reset)0-15 (0-8)DEG F (DEG C)restd 20D(0D)
Degrees Reset–30-30 (–17-17)DEG F (DEG C)deg chw5D(3D)
Select/Enable Reset Type0-3res sel
ECW CONTROL OPTIONDISABLE/ENABLEecw opt
Demand Limit At 20 mA40-100%dem 20ma40
20 mA Demand Limit OptionDISABLE/ENABLEdem selDISABLE
Surge/HGBP Delta T20.5-15 (0.3-8.3)DEG F (DEG C)hgb dt2
Surge/HGBP Delta P2
Full Load Points (T2/P2)
Surge/HGBP Deadband1-3 (0.6-1.6)DEG F (DEG C)hgb dp
Surge Delta Percent Amps10-50%surge a
Surge Time Period1-5MINsurge t2
Demand Limit Source0/1dem src
Select: Amps=0, Load=1
Amps Correction Factor1-8corfact3
Motor Rated Load Amps1-9999AMPSa fs
Motor Rated Line Voltage1-9999VOLTSv fs
Meter Rated Line kW1-9999kWkw fs600
Spare Temp 4 Enable0-2spr4 en
Spare Temp 4 Alert–40-245 (–40-118)DEG F (DEG C)spr4 al
Spare Temp 5 Enable0-2spr5 en0
Spare Temp 5 Alert–40-245 (–40-118)DEG F (DEG C)spr5 al245 (118)
Spare Temp 6 Enable0-2spr6 en
Spare Temp 6 Alert–40-245 (–40-118)DEG F (DEG C)spr6 al245 (118)
Spare Temp 7 Enable0-2spr7 en
Spare Temp 7 Alert–40-245 (–40-118)DEG F (DEG C)spr7 al245 (118)
Spare Temp 8 Enable0-2spr8 en0
Spare Temp 8 Alert–40-245 (–0-118)DEG F (DEG C)spr8 al
Spare Temp 9 Enable0-2spr9 en0
Spare Temp 9 Alert–40-245 (–40-118)DEG F (DEG C)spr9 al245 (118)
NOTE: This screen provides the means to generate alert messages based on exceeding the ‘‘Temp Alert’’ threshold for each point listed. If the
‘‘Enable’’is set to 1, a value above the ‘‘Temp Alert’’ threshold shall generate an alert message. If the ‘‘Enable’’ is set to 2, a value below the ‘‘Temp
Alert’’ threshold shall generate an alert message. If the ‘‘Enable’’ is set to 0, alert generation is disabled.
.
.
.
.
0
0
0
245 (118)
0
245 (118)
245 (118)
0
0
245 (118)
0
0
245 (118)
EXAMPLE 9 — SERVICE3 DISPLAY SCREEN
To access this display from the LID default screen:
1. PressMENU
2. Press SERVICE
3. Scroll down to highlight EQUIPMENT SERVICE.
4. Press SELECT
5. Scroll down to highlight SERVICE3.
DESCRIPTIONCONFIGURABLE RANGEUNITSREFERENCE POINT NAMEDEFAULT VALUE
Proportional Inc Band2-10gv inc
Proportional Dec Band2-10gv de
Proportional ECW Gain1-3gv ecw
Guide Vane Travel Limit30-100%gv lim
.
.
.
25
6.5
6.0
2.0
50
Table 2 — LID Screens (cont)
EXAMPLE 10 — MAINTENANCE (MAINT01) DISPLAY SCREEN
To access this display from the LID default screen:
1. PressMENU
2. Press SERVICE
3. Scroll down to highlight ALGORITHM STATUS.
4. Press SELECT
5. Scroll down to highlight MAINT01.
CAPACITY CONTROL
Control Point10-120 (–12.2-48.9)DEG F (DEG C)ctrlpt
Leaving Chilled Water–40-245 (–40-118)DEG F (DEG C)LCW
Entering Chilled Water–40-245 (–40-118)DEG F (DEG C)ECW
Control Point Error–99-99 (–55-55)DEG F (DEG C)cperr
ECW Delta T–99-99 (–55-55)DEG F (DEG C)ecwdt
ECW Reset–99-99 (–55-55)DEG F (DEG C)ecwres
LCW Reset–99-99 (–55-55)DEG F (DEG C)lcwres
Total Error + Resets–99-99 (–55-55)DEG F (DEG C)error
Guide Vane Delta–2-2%gvd
Target Guide Vane Pos0-100%GVTRG
Actual Guide Vane Pos0-100%GVACT
Proportional Inc Band2-10gv inc
Proportional Dec Band2-10gv dec
Proportional ECW Gain1-3gv ecw
Water/Brine Deadband0.5-2 (0.3-1.1)DEG F (DEG C)cwdb
NOTE: Overriding is not supported on this maintenance screen.Active overrides show the associated point in alert (*). Only values with capital letter
reference point names are variables available for read operation.
.
.
.
DESCRIPTIONRANGE/STATUSUNITSREFERENCE POINT NAME
EXAMPLE 11 — MAINTENANCE (MAINT02) DISPLAY SCREEN
To access this display from the LID default screen:
1. PressMENU
2. Press SERVICE
3. Scroll down to highlight CONTROL ALGORITHM STATUS.
4. Press SELECT
5. Scroll down to highlight MAINT02.
6. Press SELECT
OVERRIDE/ALERT STATUS
MOTOR WINDING TEMP–40-245 (–40-118)DEG F (DEG C)MTRW
Override Threshold150-200 (66-93)DEG F (DEG C)mt over
CONDENSER PRESSURE–6.7-420 (–42-2896)PSI (kPa)CRP
Override Threshold90-245 (621-1689)PSI (kPa)cp over
EVAPORATOR REFRIG TEMP–40-245 (–40-118)DEG F (DEG C)ERT
Override Threshold2-45 (1-7.2)DEG F (DEG C)rt over
DISCHARGE TEMPERATURE–40-245 (–40-118)DEG F (DEG C)CMPD
Alert Threshold125-200 (52-93)DEG F (DEG C)cd alert
BEARING TEMPERATURE–40-245 (–40-118)DEG F (DEG C)MTRB
Alert Threshold175-185 (79-85)DEG F (DEG C)tb alert
NOTE: Overriding is not supported on this maintenance screen.Active overrides show the associated point in alert (*). Only values with capital letter
reference point names are variables available for read operation.
.
.
.
.
DESCRIPTIONRANGE/STATUSUNITSREFERENCE POINT NAME
26
Table 2 — LID Screens (cont)
EXAMPLE 12 — MAINTENANCE (MAINT03) DISPLAY SCREEN
To access this display from the LID default screen:
1. PressMENU
2. Press SERVICE
3. Scroll down to highlight CONTROL ALGORITHM STATUS.
4. Press SELECT
5. Scroll down to highlight MAINT03.
6. Press SELECT
SURGE/HGBP ACTIVE ?NO/YES
Active Delta P0-200 (0-1379)PSI (kPa)dp a
Active Delta T0-200 (0-111)DEG F (DEG C)dt a
Calculated Delta T0-200 (0-111)DEG F (DEG C)dt c
Surge Protection Counts0-12spc
NOTE: Override is not supported on this maintenance screen. Only values with capital letter reference point names are variables available for read
operation.
To access this display from the LID default screen:
1. PressMENU
2. Press SERVICE
3. Scroll down to highlight CONTROL ALGORITHM STATUS.
1. Only values with capital letter reference point names are variables available for read operation. Forcing is not supported on this maintenance
screen.
2. The MAINT04 screen is available on PSIO Software Version 09 and higher.
3. D = delta degrees.
Current ModeDISABLE,LEAD,LAG,STANDBY, CONFIGllmode
Satisfied?No/Yes(D DEG C/min)pull sat
Run StatusTimeout,Recycle,Startup,Ramping,Running
Start/StopStop,Start,Retainlag s s
Run StatusTimeout,Recycle,Startup,Ramping,Running
Start/StopStop,Start,Retainstd s s
Demand,Override,Shutdown,Abnormal,Pumpdown
Demand,Override,Shutdown,Abnormal,Pumpdown
lagstat
stdstat
27
PIC System Functions
NOTE: Throughout this manual, words printed in capital letters and italics represent values that may be viewed on the
LID. See Table 2 for examples of LID screens. Point names
are listed in the Description column. An overview of LID
operation and menus is given in Fig. 13-19.
CAPACITY CONTROL — The PIC controls the chiller
capacity by modulating the inlet guide vanes in response to
chilled water temperature changes away from the CON-TROL POINT. The CONTROL POINT may be changed by
a CCN network device, or is determined by the PIC adding
any active chilled water reset to the ECW (Entering Chilled
Water) SET POINT or LCW SET POINT. The PIC uses the
PROPORTIONAL INC (Increase) BAND, PROPORTIONAL
DEC (Decrease)BAND, and the PROPORTIONAL ECW GAIN
to determine how fast or slow to respond. CONTROL POINT
may be viewed/overridden on the Status table, Status01
selection.
ENTERING CHILLED WATER CONTROL — If this option is enabled, the PIC uses ENTERING CHILLED WATER
temperature to modulate the vanes instead of LEAV-
ING CHILLED WATERtemperature. ENTERING CHILLED
W ATER control option may be viewed/modified on the Equip-
ment Configuration table, Config table.
DEADBAND — This is the tolerance on the chilled water/
brine temperature CONTROL POINT. If the water temperature goes outside of the DEADBAND, the PIC opens or closes
the guide vanes in response until it is within tolerance. The
PIC may be configured with a 0.5 to 2 F (0.3 to 1.1 C) deadband. DEADBAND may be viewed or modified on the Equipment Service1 table.
For example, a 1° F (0.6° C) deadband setting controls
the water temperature within ±0.5° F (0.3° C) of the control point. This may cause frequent guide vane movement if
the chilled water load fluctuates frequently. A value of
1° F (0.6° C) is the default setting.
PROPORTIONALBANDSAND GAIN — Proportional band
is the rate at which the guide vane position is corrected in
proportion to how far the chilled water/brine temperature is
from the control point. Proportional gain determines how
quickly the guide vanes react to how quickly the temperature is moving from CONTROL POINT.
The proportional band can be viewed/modified on the LID.
There are two response modes, one for temperature response above the control point, the other for response below
the control point.
The first type is called PROPORTIONAL INC BAND, and
it can slow or quicken vane response to chilled water/
brine temperature above DEADBAND. It can be adjusted
from a setting of 2 to 10; the default setting is 6.5. PRO-PORTIONAL DEC BAND can slow or quicken vane response to chilled water temperature below deadband plus control
point. It can be adjusted on the LID from a setting of 2 to 10,
and the default setting is 6.0. Increasing either of these settings will cause the vanes to respond slower than at a lower
setting.
The PROPORTIONAL ECW GAIN can be adjusted at the LID
display from a setting of 1.0 to 3.0, with a default setting of
2.0. Increase this setting to increase guide vane response to
a change in entering chilled water temperature. The proportional bands and gain may be viewed/modified on the Equipment Service3 table.
DEMAND LIMITING — The PIC will respond to the
ACTIVE DEMAND LIMIT set point by limiting the opening of the guide vanes. It will compare the set point
to either COMPRESSOR MOTOR LOAD or COMPRES-SOR MOTOR CURRENT (percentage), depending on how
the control is configured for the DEMAND LIMIT SOURCE
which is accessed on the SERVICE1 table. The default setting is current limiting.
CHILLER TIMERS — The PIC maintains 2 runtime clocks,
known as COMPRESSOR ONTIME and SERVICE ON-TIME. COMPRESSOR ONTIME indicates the total lifetime compressor run hours. This timer can register up
to 500,000 hours before the clock turns back to zero. The
SERVICE ONTIME is a resettable timer that can be used to
indicate the hours since the last service visit or any other
reason. The time can be changed through the LID to
whatever value is desired. This timer can register up to
32,767 hours before it rolls over to zero.
The chiller also maintains a start-to-start timer and a stopto-start timer. These timers limit how soon the chiller can be
started. See the Start-Up/Shutdown/Recycle Sequence section, page 39, for operational information.
OCCUPANCY SCHEDULE — This schedule determines when
the chiller is either occupied or unoccupied.
Each schedule consists of from one to 8 occupied/unoccupied
time periods, set by the operator. These time periods can be
enabled to be in effect, or not in effect, on each day of the
week and for holidays. The day begins with 0000 hours and
ends with 2400 hours. The chiller is in OCCUPIED mode
unless an unoccupied time period is in effect.
The chiller will shut down when the schedule goes to UNOCCUPIED. These schedules can be set up to follow the
building schedule or to be 100% OCCUPIED if the operator
wishes. The schedules also can be bypassed by forcing the
Start/Stop command on the PIC Status screen to start. The
schedules also can be overridden to keep the unit in an OCCUPIED mode for up to 4 hours, on a one-time basis.
Figure 18 shows a schedule for a typical office building
time schedule, with a 3-hour, off-peak cool down period
from midnight to 3 a.m., following a weekend shutdown.
Example: Holiday periods are unoccupied 24 hours per day.
The building operates Monday through Friday, 7:00 a.m. to
6:00 p.m., with a Saturday schedule of 6:00 a.m. to
1:00 p.m., and includes the Monday midnight to 3:00 a.m.
weekend cool-down schedule.
NOTE: This schedule is for illustration only, and is not intended to be a recommended schedule for chiller operation.
PSIO Software Version 08 and Lower — Whenever the chiller
is in the LOCAL mode, the chiller will start when the
Occupancy Schedule 01 indicates OCCUPIED. When in the
CCN mode, Occupancy Schedule 02 is used.
PSIO Software Version 09 and Higher — The Local Time
Schedule is still the Occupancy Schedule 01. The Ice Build
Time Schedule is Schedule 02 and the CCN Default Time
Schedule is Schedule 03. The CCN schedule number is defined on the Config table in the Equipment Configuration
table on page 23. The schedule number can change to any
value from 03 to 99. If this schedule number is changed on
the Config table, the operator must use the Attach to Network Device table to upload the new number into the Schedule screen. See Fig. 17.
28
Safety Controls — The PIC monitors all safety control
inputs, and if required, shuts down the chiller or limits the
guide vanes to protect the chiller from possible damage from
any of the following conditions:
• high bearing temperature
• high motor winding temperature
• high discharge temperature
• low oil pressure
• low cooler refrigerant temperature/pressure
• condenser high pressure or low pressure
• inadequate water/brine cooler and condenser flow
• high, low, or loss of voltage
• excessive motor acceleration time
• excessive starter transition time
• lack of motor current signal
• excessive motor amps
• excessive compressor surge
• temperature and transducer faults
Starter faults or optional protective devices within the starter
can shut down the chiller. These devices are dependent on
what has been purchased as options.
If compressor motor overload occurs, check the motor
for grounded or open phases before attempting a
restart.
If the controller initiates a safety shutdown, it displays
the fault on the LID display with a primary and a secondary
message, and energizes an alarm relay in the starter and blinks
the alarm light on the control center. The alarm is stored in
memory and can be viewed in the PIC alarm table along with
a message for troubleshooting.
To give a better warning as to the operating condition of
the chiller, the operator also can define alert limits on various monitored inputs. Safety contact and alert limits are
defined in Table 3.Alarm and alert messages are listed in the
Troubleshooting Guide section, page 66.
SHUNTTRIP — The shunt trip function of the PIC is a safety
trip. The shunt trip is wired from an output on the SMM to
a shunt trip-equipped motor circuit breaker. If the PIC tries
to shut down the compressor through normal shutdown procedure but is unsuccessful for 30 seconds, the shunt trip output is energized and causes the circuit breaker to trip off. If
ground fault protection has been applied to the starter, the
ground fault trip will also energize the shunt trip to trip the
circuit breaker.
Default Screen Freeze — Whenever an alarm
occurs, the LID default screen will freeze displaying the
condition of the chiller at the time of alarm. Knowledge of
the operating state of the chiller at the time an alarm occurs
is useful when troubleshooting. Current chiller information
can be viewed on the Status tables. Once all existing alarms
are cleared (by pressing the RESET
LID will return to normal operation.
softkey), the default
Motor Cooling Control — Motor temperature is
reduced by refrigerant entering the motor shell and evaporating. The refrigerant is regulated by the motor cooling
relay. This relay will energize when the compressor is running and motor temperature is above 125 F (51.7 C). The
relay will close when motor temperature is below 100 F
(37.8 C). Note that there is always a minimum flow of
refrigerant when the compressor is operating for motor cooling; the relay only controls additional refrigerant to the
motor.
29
Table 3 — Protective Safety Limits and Control Settings
MONITORED PARAMETERLIMITAPPLICABLE COMMENTS
TEMPERATURE SENSORS
OUT OF RANGE
PRESSURE TRANSDUCERS
OUT OF RANGE
COMPRESSOR DISCHARGE
TEMPERATURE
MOTOR WINDING TEMPERATURE.220 F (104.4 C)Preset, alert setting configurable
BEARING TEMPERATURE.185 F (85 C)Preset, alert setting configurable
.110% for 30 secondsPreset
,10% with compressor runningPreset
.10% with compressor offPreset
.45 seconds
.10 seconds
Energizes condenser pump relay if condenser
refrigerant temperature or condenser entering
water temperature is below the configured condenser freeze point temperature. Deenergizes
when the temperature is5F(3C)above condenser freeze point temperature.
Must be outside range for 2 seconds.
Ratio = Input Voltage ÷ Voltage
Reference
Preset, configure chilled medium for
water (Service1 table)
Configure chilled medium for brine
(Service1 table). Adjust brine refrigerant
trippoint for proper cutout
Preset
Preset
Preset, no calibration needed
Preset
Preset, based on transformed line voltage to 24 vac rated-input to the Starter
Management Module. Also monitored at
PSIO power input.
For chillers with reduced voltage mechanical and solid-state starters
For chillers with full voltage starters
(Configured on Service1 table)
CONDENSER FREEZE POINT configured in Service01 table with a default
setting of 34 F (1 C).
Flow Switches (Field Supplied)
Operate water pumps with chiller off. Manually
reduce water flow and observe switch for proper
cutout.Safety shutdown occurs when cutout time
exceeds 3 seconds.
30
CUT-OUT
SETTING
ADJUSTMENT
SCREW
Loading...
+ 70 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.