Positive pressure storage systems are designed to provide safe and reliable service when operated within design specifications. When operating this equipment, use
good judgment and safety precautions to avoid damage
to equipment and property or injury to personnel.
Be sure you understand and follow the procedures and
safety precautions contained in this guide.
DO NOT VENT refrigerant relief valves within a building. Outlet
from rupture disc or relief valve must be vented outdoors in accordance with the latest edition ofASHRAE 15 (American Society
of Heating, Refrigeration, and Air Conditioning Engineers). The
accumulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation.
PROVIDE adequate ventilation in accordance with ASHRAE 15,
especially forenclosed and low overheadspaces. Inhalation of high
concentrations of vapor is harmful and may cause heart irregularities, unconsciousness,or death. Misusecan be fatal.Vaporis heavier
than air and reduces the amount of oxygen available for breathing.
Product causes eye and skin irritation. Decomposition products are
hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a machine
for any purpose. Oxygen gas reacts violently with oil, grease, and
other common substances.
NEVER EXCEED specified test pressures, VERIFY the allowable
test pressure by checking the instruction literature and the design
pressures on the equipment nameplate.
DO NOT USE air for leak testing. Use only tracer gases and dry
nitrogen.
DO NOT VALVE OFF any safety device.
BE SURE that all pressure relief devices are properly installed and
functioning before operating any machine.
with soapand water.If any entersthe eyes, IMMEDIATELYFLUSH
EYES with water and consult a physician.
NEVER APPLY an open flame or live steam to a refrigerant cylinder. Dangerous overpressure can result. When necessary to heat
refrigerant, use only warm (110 F [43 C]) water.
DO NOT REUSE disposable (nonreturnable) cylinders or
attempt to refill them. It is DANGEROUSAND ILLEGAL. When
cylinder is emptied, evacuate remaining gas pressure, loosen
the collar and unscrew and discard the valve stem. DO NOT
INCINERATE.
CHECK THE REFRIGERANT TYPE before transferring refrigerant to the machine. Theintroduction of the wrong refrigerant can
cause damage or malfunction to this machine.
Operation of this equipment with refrigerants other than those
cited herein shouldcomply with ASHRAE 15 (latest edition). Contact Carrierfor further information on use of thismachine with other
refrigerants.
DO NOTATTEMPT TO REMOVE fittings, covers, etc., while machine is under pressure or while machine is running. Be sure pressure is at 0 psig (0 kPa) before breaking any refrigerant
connection.
CAREFULLY INSPECT all relief devices, rupture discs, and other
relief devices AT LEAST ONCE A YEAR. If machine operates in
a corrosive atmosphere, inspect the devices at more frequent
intervals.
DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief
device when corrosion or build-up of foreign material (rust, dirt,
scale, etc.) is found within the valve body or mechanism. Replace
the device.
DO NOT install relief devices in series or backwards.
USE CAREwhen working near orin line witha compressed spring.
Sudden release of the spring can cause it and objects in its path to
act as projectiles.
19XB
DO NOT WELD OR FLAMECUT any refrigerant line or vessel
until allrefrigerant (liquid andvapor) has beenremoved from chiller.
Traces of vapor should be displaced with dry air or nitrogen and
the work area should be well ventilated. Refrigerant in contact with
an open flame produces toxic gases.
DO NOT USE eyebolts or eyebolt holes to rig machine sections or
the entire assembly.
DO NOT work on high-voltage equipment unless you are a qualified electrician.
DO NOTWORK ON electricalcomponents, including control panels, switches, starters, or oil heater until you are sureALL POWER
IS OFF and no residual voltage can leak from capacitors or solidstate components.
LOCK OPEN ANDTAGelectrical circuits during servicing.IF WORK
IS INTERRUPTED, confirm that all circuits are deenergized before resuming work.
DO NOT syphon refrigerant by mouth.
AVOID SPILLING liquid refrigerant on skin or getting it into the
eyes. USE SAFETY GOGGLES. Wash any spills from the skin
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
Tab 5a
PC 211Catalog No. 531-927Printed in U.S.A.Form 19XB-1SIPg 16-96Replaces: New
DO NOT STEP on refrigerant lines. Broken lines can whip about
and cause personal injury and damage to the machine.
DO NOT climb over a machine. Use platform, catwalk, or staging.
Follow safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or
move inspection covers or other heavy components. Even if components are light, use such equipment when there is a risk of slipping or losing your balance.
BE AWARE that certain automatic start arrangements CAN ENGAGE THE STARTER. Open the disconnect ahead of the starter
in addition to shutting off the machine or pump.
USE only repair or replacement parts that meet the code requirements of the original equipment.
DOUBLE-CHECK that coupling nut wrenches, dial indicators, or
other items have been removed before rotating any shafts.
DO NOT LOOSEN a packing gland nut before checking that the
nut has a positive thread engagement.
PERIODICALLY INSPECT all valves, fittings, and piping for corrosion, rust, leaks, or damage.
DO NOTMIX REFRIGERANTfrom chillers thatuse differentcompressor oils. Compressor damage can result.
Page 2
CONTENTS
Page
SAFETY CONSIDERATIONS ...................1
INTRODUCTION ..............................2
INSTALLATION .............................2-10
Complete Pre-Installation Checks .............2
• IDENTIFY UNIT
• INSPECT SHIPMENT
Mount the Pumpout Unit .....................3
• MOUNTING ON THE CHILLER
• FLOOR MOUNTING
Rig the Storage Tank .........................3
Make Piping Connections ....................7
• INSTALL VENT PIPING TO RELIEF DEVICES
Make Electrical Connections ..................7
CONTROLS AND COMPONENTS ..............11
Pumpout Unit ................................11
• CONTROLS
• SAFETY CONTROL SETTINGS
• COMPRESSOR
• CONDENSER
• OIL SEPARATOR
• SUCTION AND DISCHARGE VALVES
Storage Tank ................................11
• DRAIN VALVE
• DUAL RELIEF VALVES
• PRESSURE GAGE
• LEVEL GAGE
OPERATION ...............................11-15
Overview ...................................11
• REFRIGERANT TRANSFER
• TRANSFERRING LIQUID REFRIGERANT FROM
THE CHILLER COOLER TO THE CHILLER
CONDENSER OR PUMPOUT STORAGE TANK
• TRANSFERRING LIQUID REFRIGERANT FROM
THE CHILLER CONDENSER OR PUMPOUT
STORAGE TANK TO THE CHILLER COOLER
• DISTILLING THE REFRIGERANT
Pumpout and Refrigerant Transfer
Procedures ...............................12
• OPERATING THE PUMPOUT UNIT
• TO READ REFRIGERANT PRESSURES
• POSITIVE PRESSURE CHILLERS WITH STORAGE
TANKS
• CHILLERS WITH ISOLATION VALVES
• DISTILLING THE REFRIGERANT
MAINTENANCE ............................15,16
Pumpout Unit ...............................15
• PUMPOUT COMPRESSOR OIL CHARGE
Storage Tank ...............................16
Ordering Replacement Parts .................16
TROUBLESHOOTING ........................16
INTRODUCTION
The 19XB Positive Pressure Storage (PPS) System has
been designed to help owners and operators of positive pressure chillers store refrigerants HCFC-22 and HFC-134a during service and repair work. The 19XB system conserves
these refrigerantsand prevents the releaseofexcessive amounts
of refrigerant into the atmosphere. The proper use of this
equipment minimizes the loss of HFCs and HCFCs.
The 19XB PPS systemshownin Fig. 1 consists of a pumpout unit mounted on a storage tank. The pumpout unit is offered as a free-standing unit that can be used with chillers
that have an existing storage tank or with chillers that have
isolation valves that permit built-in refrigerant storage.
The 19XB PPS systems are factory tested and certified to
theAmerican Society of Mechanical Engineers(ASME)pressure vessel code. The tanks are constructed of certified steel
and are pressure rated at 300 psig (2068 kPa). The PPS storage tank is equipped with dual relief valves for proper venting per ASHRAE 15 (American Society of Heating Refrigeration, and Air Conditioning Engineers) guidelines. An
automatic level switch is prewired to the control circuit to
ensure proper storage levels.
The 19EA pumpout unit is a complete, hermetic, compact
unit that consists of:
• a spring-mounted reciprocating compressor with a direct-
drive motor
• a water-cooled refrigerant condenser
• an oil separator
• suction and discharge valves to control refrigerant flow
• prewired safety and control devices.
When referencing refrigerant charges in this manual, the
HCFC-22 charge will be listed first and the HFC-134a value
will follow in brackets.
INSTALLATION
Complete Pre-Installation Checks
IDENTIFY UNIT — Identify the assembly number
(T able1) printed on the pumpout unit andstoragetank nameplates. Check this information against the job requirements.
Fig. 1 shows the PPS system and its major components.
Refer to Tables 2 and 3 for physical data.
INSPECT SHIPMENT — Inspect unit for damage before
removing unitfromshipping conveyance. If unit appearsdamaged, it should be inspected by a shipping inspector before
removal. File a claim with the shipping company if shipment is damaged or incomplete. The manufacturer is not responsible for damage incurred during transit.
Check all components. Notify the supplier immediately if
any item is missing. To prevent loss or damage, leave all
parts in their original package until they are needed.
2
Page 3
Table 1 — Positive Pressure System Assembly Numbers
POSITIVE PRESSURE
SYSTEM ASSEMBLY
NUMBER
19XB0428020519EA42-748R-22208-3-6013.263.528 cu ft
19XB0428020619EA44-748R-22230-3-6011.557.528 cu ft
19XB0428020719EA46-748R-22400/460-3-50/605.828.828 cu ft
19XB0428020819EA47-748R-22575-3-604.623.028 cu ft
19XB0428021319EA48-748R-134a208-3-6013.263.528 cu ft
19XB0428021419EA49-748R-134a230-3-6011.557.528 cu ft
19XB0428021519EA51-748R-134a400/460-3-50/605.828.828 cu ft
19XB0428021619EA52-748R-134a575-3-604.623.028 cu ft
19XB0428060119EA42-748R-22208-3-6013.263.5None
19XB0428060219EA44-748R-22230-3-6011.557.5None
19XB0428060319EA46-748R-22400/460-3-50/605.828.8None
19XB0428060419EA47-748R-22575-3-604.623.0None
19XB0428060519EA48-658R-134a208-3-6013.263.5None
19XB0428060619EA49-658R-134a230-3-6011.557.5None
19XB0428060719EA51-658R-134a400/460-3-50/605.828.8None
19XB0428060819EA52-658R-134a575-3-604.623.0None
19XB0452020519EA42-748R-22208-3-6013.263.552 cu ft
19XB0452020619EA44-748R-22230-3-6011.557.552 cu ft
19XB0452020719EA46-748R-22400/460-3-50/605.828.852 cu ft
19XB0452020819EA47-748R-22575-3-604.623.052 cu ft
19XB0452021319EA48-748R-134a208-3-6013.263.552 cu ft
19XB0452021419EA49-748R-134a230-3-6011.557.552 cu ft
19XB0452021519EA51-748R-134a400/460-3-50/605.828.852 cu ft
19XB0452021619EA52-748R-134a575-3-604.623.052 cu ft
LEGEND
LRA — Locked RotorAmps
RLA — Rated LoadAmps
PUMPOUT UNIT
ASSEMBLY NO.
REFRIGERANT
COMPRESSOR MOTOR
(V-Ph-Hz)
NOTES:
1. Allstorage vesselsare 300 psig (2068 kPa)designs perthe ASME
(American Society of Mechanical Engineers) Boiler Pressure
Vessel Code, Section VIII Division 1.
3. Nominal horsepower for all pumpout units is 3.0.
MAXIMUM
RLA
LRA
STORAGE
TANK
MountthePumpoutUnit— The pumpout unit, if pur-
chased separately, may be mounted directly on the chiller or
it may be floor mounted.
MOUNTING ON THE CHILLER — See instructions provided with the chiller for mountingthepumpout unit. Atypical chiller mount is shown in Fig. 2.
FLOOR MOUNTING — Select a ventilated and accessible
area, free of traffic or other hazards. Removeand discard the
4 angle supports at the base of the pumpout unit and bolt the
unit to the floor through the 4
pumpout unit. Special isolation is unnecessary. Contact surface and dimensions for the pumpout unit are given in
Fig. 3.
7
⁄16in. holes at the base of the
Rig the Storage Tank — The complete 19XB system
can be rigged as a single assembly. See the rigging instructions on the label attached to the assembly. Also refer to the
rigging guide (Fig. 4), physical data in Tables 2 and 3, and
contact surface and dimensions for the complete system in
Fig. 5. Lift the assembly only from the 4 points indicated inthe rigging guide. Each rigging cable must be capable of
supporting the entire weight of the assembly.
Lifting the assembly from points other than those specified may result in serious damage to the assembly and
personal injury. Riggingequipmentand procedures must
be adequate forassembly. See Tables 2 and 3for weights.
NOTE: These weights are broken down into pumpout
unit and storage tank weights. For the complete assembly weight, add all components together.
3
Page 4
VALVES
VENT VALVE
VALVES
CONDENSER
WATER
CONNECTIONS
(FIELD PIPING)
REFRIGERANT
INLET VALVE
19EA PUMPOUT UNIT
CONTROL BOX
(WIRING BY
CONTRACTOR)
COMPRESSOR
19EA PUMPOUT UNITS
19EA CONTROL BOX (INTERIOR)
Fig. 1 — 19XB Positive Pressure Storage System
4
Page 5
*3⁄8-16 bolts × 1-in. lg; 4 required.
Fig. 2 — 19EA Pumpout Unit: Typical Chiller Mount
ELECTRICAL CONNECTION
OPTION LIST
TRADE SIZEQTYLOCATION
1
⁄2(1TOP
3
⁄
4
( 1BOTTOM
1(1MIDDLE
1
1
⁄4(1MIDDLE
Fig. 3 — Pumpout Unit Contact Surfaces and Dimensions
5
Page 6
NOTES:
1. Each chainmust be capable of supporting the entireweight of the
machine.
2. Minimum chain length:
3
tank — 108-09
28 ft
3
52 ft
tank — 158-69
3. Total weight equals empty weight from chart and charge weight
given on label.
STORAGE
TANK SIZE
3
28 Ft
3
52 Ft
CENTER OF GRAVITY
APPROX. DIM. — ft-in. (mm)
AB
4- 51⁄
(1353)
6-101⁄
(2086)
4
8
1-77⁄
(505)
1-83⁄
(527)
8
4
EMPTY WEIGHT
LB (Kg)
(1080)
(1569)
Fig. 4 — Rigging Guide
Table 2 — Physical Data
19EA Pumpout Unit
ENGLISH(SI)
Pumpout Unit Weight*lb (kg)210(95)
Pumpout Condenser Water Flow Rategpm (L/s)5 to 7(.32 to .44)
Pumpout Condenser Water Pressure Droppsig (kPa)6 to 10.7(41.4 to 73.8)
Maximum Entering Condenser Water TemperatureF (C)85(29)
Maximum Leaving Condenser Water TemperatureF (C)100(37)
Condenser Relief Valve (Fusible Plug)psig (kPa)385(2655)
Condenser Pressure Rating
ANSI— American National Standards Institute
ASHRAE — American Society of Heating, Refrigeration,
UL— Underwriters’ Laboratories
*The above dry weight includes the pumpout unit weight of 210 lbs (95 kg).
and Air Conditioning Engineers
TANK OD
(in.)
TANK OD
(mm)
LEGEND
DRY WEIGHT*
(lb)
DRY WEIGHT*
(kg)
SI
MakePipingConnections— Figure 6representstypi-
cal pumpout unit/chiller piping connections. Standard connections for1⁄2-in. OD copper tubing are provided. Install
the field-supplied FPT tee with pipe plug in the piping as
shown in Fig. 6. This tee is used for refrigerant charging.
NOTE: If any field piping runs exceed 50 ft in length, use
7
⁄8-in. OD copper tubing to minimize pressure drop.
Pumpout unit water piping connections are shown in
Fig. 6. Both connections are
valve should be installed in the water line. Provide a means
for blowing water from the condenser coil at winter shutdown to prevent freeze-up damage. Refer to the Job Data for
water piping particulars.
INSTALL VENT PIPING TO RELIEF DEVICES — The
pumpout storage tank is factory-equipped with relief devices. Refer to Fig. 5 and Table 2 for size and location of the
relief devices. Vent the relief devices to the outdoors in accordance with ANSI/ASHRAE 15 Safety Code (latest edition) for Mechanical Refrigeration and all other applicable
codes. Relief devices are set to relieve at 300 psig
(2068 kPa).
Refrigerant discharged into confined spaces can displace oxygen and cause asphyxiation.
1
⁄2-in. NPT (female). A shutoff
MAXIMUM REFRIGERANT CAPACITY (lb)
ASHRAE/ANSI 15UL 1963
R-22R-134aR-22R-134a
MAXIMUM REFRIGERANT CAPACITY (kg)
ASHRAE/ANSI 15UL 1963
R-22R-134aR-22R-134a
1. If relief devices are manifolded, the cross-sectional area
of the relief pipe must at least equal the sum of the areas
required for individual relief pipes.
2. Provide a pipe plug near outlet side of each relief device
for leak testing. Provide pipe fittings that allow vent piping to be disconnectedperiodicallyfor inspection of valve
mechanism.
3. Piping to relief devices must not apply stress to the device. Adequately support piping.Alength of flexible tubing or piping near the device is essential on springisolated machines.
4. Cover the outdoor vent with a rain cap and place a condensation drain at the low point in the vent piping to prevent water build-up on the atmospheric side of the relief
device.
Make Electrical Connections — See nameplate on
compressor of pumpout unit and Table 1 for motor electrical
data. Wire unit according to the diagram inside the control
box.
Fig. 7 is the wiring schematic for a complete system that
includes the 19XB storage tank and the pumpout unit.
Fig. 8 is the wiring schematic for the pumpout unit. Use this
schematic for installations that do not include an auxiliary
pumpout storage tank.
CHILLERS WITHOUT ISOLATION VALVESCHILLERS WITH ISOLATION VALVES
(WITH OR WITHOUT PUMPOUT STORAGE TANKS)
GENERAL PIPING CONNECTION SIZES
CONNECTIONSIZE (in.)
Refrigerant Transfer Connections
Condenser Water Cooling Connectors
Safety Relief Head Pumpdown Condenser
ODS — Outside Diameter, Sweat
NOTES:
1. The field-suppliedtubing is to be
be arranged and supported to avoid stresses on the equipment,
transmission of vibrations, and interference with routine access
during the reading, adjusting, and servicing of the equipment. If
the distance from the chiller to thepumpout unit is over 50ft, then
7
⁄8-in. OD tubing (min.)must be used. Provisions should be made
for adjustment in each plane of the tubing and for both periodic
and majorservicing of the equipment.Special care mustbe taken
so that the safety head does not experience tubing strain. Vent
the safety head per ASHRAE 15 (American Society of Heating,
Refrigeration, and Air Conditioning Engineers), latest revision.
2. The tubing and valve from the storage tank to the pumpout compressor is factory supplied when the unit is factory mounted.
Service Valve (Factory Supplied)
Service Valve (Field Supplied)
9
Page 10
Table 4 — Relief Devices
STORAGE
TANK SIZE
28
52
RELIEF VALVE
OUTLET SIZE
1 in. NPT
Female Connector
1 in. NPT
Female Connector
QUANTITY
lb air
min
231.414.2
252.323.7
REQUIRED FACTOR
Kg air
min
LEGEND
Ground
Field Wiring
Factory Wiring
Contactor Term.
Overload Term.
Pumpdown Term.
Pumpdown Comp’r.
Term.
Fig. 7 — 19XB Pumpout System Wiring Schematic
LEGEND
C—Contactor
Fu— Fuse, 3 Amps
HP— High-Pressure Cutout
L—Compressor Motor Voltage Line (3-phase)
LL— Low-Line Control Voltage (single-phase)
OL— Compressor Overload
T’stat — Internal Thermostat
*Bimetal thermal protector imbedded in motor winding.
Compressor Terminal
Contactor Terminal
Overload Terminal
Pumpout Unit Terminal
Fig. 8 — Pumpout Unit Wiring Schematic
10
Page 11
CONTROLS AND COMPONENTS
Figure 1 shows the major components of the PPS system.
PumpoutUnit— The pumpout unit consists of a spring-
mounted directmotor-driven reciprocating compressor,a watercooled refrigerant condenser, an oil separator, suction and
dischargevalvesto control refrigerant flow, and prewired safety
and control devices. The pumpout unit comes equipped with
a 4-way transfer valve manifold to interconnect both liquid
and vapor transfer and to pressurize the chiller during transfer of refrigerant from chiller to storage tank.
CONTROLS — The pumpout unit has the following controls: an on/off switch, a 3-amp fuse, compressor overloads,
an internal thermostat, a compressor contactor, and a refrigerant high pressure cutout.
SAFETYCONTROL SETTINGS — Thepumpoutunit highpressure switch (Fig. 1) is set to open at the settings listed
in Table 5. The switch setting is checked by operating the
pumpout condenser and slowly throttling the pumpout condenser water.
Table 5 — High Condition Pressure Switch Settings
English
REFRIGERANT
R-134a161 ± 5 psig
R-22220 ± 5 psig
REFRIGERANT
R-134a1110±34kPa
R-221517 ± 34 kPa
NOTES:
1. R-22 units use high-pressure cutout switch HK01UA181.
2. R-134a units use high-pressure cutout switch HK01UA187.
HIGH-PRESSURE SWITCH
CutoutCutIn
+0
130 − 5 psig
+0
185 − 5 psig
SI
HIGH-PRESSURE SWITCH
CutoutCut-In
+0
896 − 34 kPa
+0
1276 − 34 kPa
COMPRESSOR — The pumpout compressor assembly has
a positive displacement of 1750 rpm (29 r/s) and 8.7 cfm
(0.004 m3/s). It comes equipped with thermal protection on
the motor and an in-line oil separator.
CONDENSER —The water-cooled condenser is fullyASME
constructed. During transfer, it condenses refrigerant vapor
to liquid.The condenser transfer tank safety reliefvalves comply with ASHRAE 15 standards.
OIL SEPARATOR — The pumpout unit includes an in-line
oil separator to remove oil that becomes mixed with refrigerant and returns the oil to the compressor.
SUCTION AND DISCHARGE VALVES — The pumpout
unit comes with a 4-way transfer valve manifold to interconnect both liquid and vapor transfer and to pressurize the
chiller during transfer of refrigerant from chiller to storage
tank or from one chiller vessel to another.
Storage Tank — The storage tank is rated for positive
pressure refrigerants underASME Section VIII pressure vessel codes with a minimum of 300 psig (2068 kPa) rating.
The tank components include:
DRAIN VALVE — Located at its lowest point of drain with
a minimum of 1 in. NPT.
DUAL RELIEF VALVES — Two relief valves and a 3-way
shut-off valve.
LEVEL GAGE — Liquid level gage (magnetically coupled
dial type) with electronic shut-off at 90% liquid capacity.
During transfer of refrigerant into and out of the pumpout storage tank, carefullymonitorthe storage tank level
gage. Do not fill the tank more than 90% of capacity to
allow for refrigerant expansion. Overfilling may result
in damage to the tank and personal injury. For maximum refrigerant capacity, refer to Table 2.
OPERATION
Overview —
another is accomplished by using either gravity or pressure
differential. A difference in elevation between 2 vessels results in agravityflow of liquid; a dif ferencein pressure forces
the liquid from one vessel to the other. The latter method
requires lowering the pressure in one vessel. If there is liquid in that vessel, its temperature must be lowered, and the
pressure in the other vessel must be simultaneously
increased.
Under most circumstances, creating the pressure differential is not a difficult process. Some applications, such as
ice storage, outdoor installations, or installations with high
temperature differentials between the storage tank and the
chiller may require additional consideration. In some instances, it may be necessary to add auxiliary heat to one of
the vessels or to insulate the storage tank at job sites where
high ambient temperature or sun load make it difficult to reduce the temperature and pressure in the tank. Outdoor installations must have a roof or cover over thestorage tank to
ensure that thepressurein the tank does not exceed the chiller
relief pressure setting.
REFRIGERANT TRANSFER — When refrigerant is being
evacuated from the chiller cooler or condenser vessels, any
liquid refrigerant left in a vessel will flash off, lowering the
temperature in that vessel enough to freeze the fluid (usually
water) flowing through the cooler or condenser tubes. This
event, called tube freeze-up, can cause extensive damage to
the chiller; therefore, all liquid refrigerant must be removed
from a vesselbeforeevacuation of refrigerant vapor is started.
If all the liquid cannot be removed, then the cooler water
and condenser water pumps mustbeoperated throughout the
process of evacuating refrigerant vapor to keep fluid moving
through the cooler and condenser tubes.
TRANSFERRING LIQUID REFRIGERANT FROM THE
CHILLER COOLERT OTHE CHILLER CONDENSER OR
PUMPOUT STORAGE TANK — Chiller and pumpout unit
valves are set to permit the pumpout compressor to discharge refrigerantvaporinto the cooler vessel, lowering pressure in the condenser vessel/storage tank. The pressure differential forcesliquidfrom the cooler vesselintothe condenser
vessel/storage tank. After all the liquid is transferred, the refrigerant vapor remaining in the cooler vessel can be drawn
off by reducing pressure in the chiller and discharging the
vapor through the pumpout unit condenser into the condenser vessel/storage tank.
TRANSFERRING LIQUID REFRIGERANT FROM THE
CHILLER CONDENSERORPUMPOUT STORAGETANK
TO THE CHILLER COOLER — Chiller and pumpout unit
valves are set to increase pressure in the chiller condenser
vessel/storage tank and to reduce pressure in the cooler vessel. Pressure in the cooler vessel is lowered to correspond to
a saturated refrigerant liquid temperature 2 F (1.1 C) above
the freezing temperature of the liquidcirculatingthrough the
chiller cooler/condenser tubes (34 F [1.1 C] for water). The
valves are set sothatthe pressure in the cooler vessel is lower
than that of the condenser vessel/storage tank, forcing the
liquid into the cooler vessel.
Transferring refrigerant from one vessel to
11
Page 12
NOTE: During this operation, maintain water circulation
through the chiller cooler and condenser vessels to prevent
tube freeze-up.
DISTILLING THE REFRIGERANT — Refrigerant vapor
is transferred from the chiller cooler vessel or pumpout storage tank through the pumpout condenser, condensed to a liquid, and pumped to the chiller condenser vessel. During this
operation, water circulation mustbemaintained in the pumpout condenser.Refrigerant impurities left in the chiller cooler
vessel or storage tank are then drained off. This operation
can takefrom4 to 14 hours, dependingon the type and amount
of refrigerant being distilled.
The Pumpout and Refrigerant Transfer Procedures section gives step-by-step instructions on performing these
operations.
Pumpout and Refrigerant Transfer Procedures
Three possibilities are available:
—
1. If there are no isolation valves on the chiller, a complete
pumpout system with a pumpout storage tank and pumpout unit is needed.
2. Whether or not isolation valvesare available on the chiller,
the refrigerant can be pumped to and isolated in a pumpout storage tank by using the pumpout unit.
3. If isolation valves are available on the chiller, the refrig-
erant can be pumped to either the cooler vessel or the
condenser vessel using the pumpout unit.
The following procedures describe how to transfer refrigerant from one vessel to another and how to evacuate the
chiller.
OIL RETURN
LINE
CONNECTION
CONDENSER
WATER
CONNECTIONS
VENT VALVE 8
REFRIGERANT
INLET VALVE
PUMPOUT
CONTROL BOX
(WIRING BY
CONTRACTOR)
Fig. 9 — Pumpout Unit
2. Attach a 30 in.-0-400 psi (101-0-2760 kPa) gage to the
storage tank to determine its pressure.
POSITIVE PRESSURE CHILLERS WITH STORAGE
TANKS — In the Valve/Condition tables that accompany
these instructions, the letter 9C9 indicates a closed valve.
Figures 9 and 10 show the locations of the valves.
Do not mix refrigerants from chillers that use different
compressor oils. Compressor damage canresult.For example, the compressor oil in a 23XL chiller that uses
HCFC-22 refrigerant can cause severe lubrication problems in a 19XL chiller that uses HCFC-22 refrigerant.
OPERATING THE PUMPOUT UNIT
1. Be sure that the suction and the discharge service valves
on the pumpout compressor (Fig. 9) are open (backseated) during operation.Rotatethe valve stem fully counterclockwise to open. Frontseating the valve closes the
refrigerant line and opens the gage port to compressor
pressure.
2. Make sure that the pumpout compressor holddown bolts
(Fig. 2) have been loosened to allow free spring travel.
Transfer, addition, or removal of refrigerant in springisolated chillers may place severe stressonexternal piping if springs on the chiller have not been blocked in
both up and down directions.
3. Open the refrigerant inlet valve (Fig. 9) on the pumpout
compressor.
4. Oil should be visible in the pumpout compressor sight
glass under all operating conditions and during shutdown. If oil is low, add oil as described in the Maintenance section.
TO READREFRIGERANTPRESSURES — During pumpout or leak testing:
1. Refer to the display on the chiller control center to determine refrigerant-side pressures and low (soft)vacuum.
Use a quality vacuum indicator or manometer to measure
evacuation and dehydrationand to ensure the desired range
and accuracy.
Always run chiller cooler and condenser water pumps
and always charge or transfer refrigerant as a gas when
chiller vessel pressure is less than 60 psig (414 kPa)
[30 psig (207 kPa)]. Below these pressures, liquid refrigerant flashes intogas,resulting in extremely low temperatures inthe cooler/condenser tubesand possibly causing
tube freeze-up.
Transfer Refrigerant from Pumpout Storage Tank to Chiller:
During transfer of refrigerant into and out of the 19XB
storage tank,carefullymonitor the storage tanklevel gage.
Do not fill the tank more than 90% of capacity to allow
for refrigerant expansion. Overfillingmayresult in damage to the tank and personal injury.
1. Equalize refrigerant pressure.
a. Turn on chiller water pumps and monitor chiller
pressures.
b. Close pumpout and storage tank valves 2, 4, 5, 8, and
10, and close refrigerant chargingvalve 7; open chiller
isolation valve 1 1and any other chiller isolationvalves,
if present.
c. Open pumpout and storage tank valves 3 and 6; open
chiller valves 1a and 1b.
VALVE 1a1b23456781011
CONDITIONCCCCCC
d. Gradually crack open valve 5 to increase chiller pres-
sure to 60 psig (414 kPa),[30psig (207 kPa)]. Slowly
feed refrigerant to prevent freeze-up.
12
Page 13
Fig. 10 — Valve Locations for 19XB Pumpout Unit With 19XB Storage Tank
e. Open valve 5 fully after thechillerpressure rises above
the freezing point of the refrigerant. Let the storage
tank andchiller pressure equalize.Openrefrigerant charging valve 7 and storage tank charging valve 10 to let
liquid refrigerant drain into the chiller.
VALVE 1a1b23456781011
CONDITIONCCC
2. Transfer remaining refrigerant.
a. Close valve 5 and open valve 4.
VALVE 1a1b23456781011
CONDITIONCCC
b. Turn off the pumpout condenser water,and turn on the
pumpout compressor to push liquid refrigerant out of
the storage tank. Monitor the storage tank level until
the tank is empty.
c. Close refrigerant charging valves 7 and 10.
d. Turn off the pumpout compressor.
e. Turn off the chiller water pumps.
f. Close valves 3 and 4.
g. Open valves 2 and 5.
VALVE 1a1b23456781011
CONDITIONCCCCC
h. Turn on pumpout condenser water.
i. Run the pumpout compressoruntil the storage tank pres-
Transfer the Refrigerant from Chiller to Pumpout Storage
Tank.
1. Equalize refrigerant pressure.
a. Valve positions:
VALVE 1a1b23456781011
CONDITIONCCCCCC
b. Slowly open valve 5 and refrigerant chargingvalves7
and 10 to allow liquid refrigerant to drain by gravity
into the storage tank.
VALVE 1a1b23456781011
CONDITIONCCC
2. Transfer the remaining liquid.
a. Turn offpumpout condenser water. Place valves in the
following positions:
VALVE 1a1b23 456781011
CONDITIONCCC
b. Run the pumpoutcompressor for approximately 30 min-
utes, then close valve 7 and 10.
VALVE 1a1b23456781011
CONDITIONCCCCC
13
c. Turn off the pumpout compressor.
Page 14
3. Remove any remaining refrigerant.
a. Turn on chiller water pumps.
b. Turn on pumpout condenser water.
c. Place valves in the following positions:
VALVE 1a1b23456781011
CONDITIONCCCCC
d. Run the pumpout compressor until the chiller pres-
sure reaches 60 psig (414 kPa), [30 psig (207 kPa)];
then, shut off the pumpout compressor. Warm chiller
condenser water will boil off any entrapped liquid refrigerant and chiller pressure will rise.
e. When chiller pressure rises to 70 psig (483 kPa),
[40 psig (276 kPa)]; turn on the pumpout compressor
until the pressure again reaches 60 psig (414 kPa)
[30 psig (207 kPa)]; then, turn off the pumpout compressor. Repeat this process until the chiller pressure
no longer rises; then, turn on the pumpout compressor
and pump out until the chiller pressure reaches
18 in. Hg (41 kPa absolute).
f. Close valves 1a, 1b, 3, 4, and 6.
VALVE 1a1b23456781011
CONDITIONCCCCCCCCC C
g. Turn off the pumpout condenser water.
4. Establish vacuum for service. To conserve refrigerant, operate the pumpout compressor as describedinStep 3e until the chiller pressure is reduced to 18 in. Hg (41 kPa
absolute).
CHILLERS WITH ISOLATION VALVES — Thevalvesreferred to in the following instructions are shown in Fig. 9
and 11. Valve 7 remains closed.
Transfer All Refrigerant to Chiller Condenser Vessel:
1. Push refrigerant into chiller condenser vessel.
a. Turn on thechillerwater pumps and monitor the chiller
pressure.
b. Valve positions:
VALVE 1a1b2345811
CONDITIONCCC
c. Equalize the refrigerant in the chiller cooler and
condenser.
d. Turn off chiller water pumps and pumpout condenser
water supply.
e. Turn on pumpout compressor to push liquid out of the
chiller cooler vessel.
f. When all liquid has been pushed into the chiller con-
(11).
g. Turn on the chiller water pumps.
h. Turn off the pumpout compressor.
2. Evacuate gas from chiller cooler vessel.
a. Close pumpout valves 2 and 5; open valves 3 and 4.
VALVE 1a1b2345811
CONDITIONCCCC
b. Turn on pumpout condenser water.
c. Run pumpout compressor until the chiller cooler ves-
sel pressure reaches 18 in. Hg vac (41 kPa absolute).
Monitor pressures on the chiller control panel and on
refrigerant gages.
Fig. 11 — Valve Locations for 19XB Pumpout Unit Without Storage Tank
14
Page 15
d. Close valve 1a.
e. Turn off pumpout compressor.
f. Close valves 1b, 3, and 4.
VALVE 1a1b2345811
CONDITIONCCCCCCCC
g. Turn off pumpout condenser water.
h. Turn off chiller water pumps and lock out chiller
compressor.
Transfer All Refrigerant to Chiller Cooler Vessel:
1. Push refrigerant into the chiller cooler vessel.
a. Turn on thechillerwater pumps and monitor the chiller
pressure.
b. Valve positions:
VALVE 1a1b2345811
CONDITIONCCC
c. Equalize the refrigerant in the chiller cooler and
condenser.
d. Turn off chiller water pumps and pumpout condenser
water.
e. Turn on pumpout compressor to push refrigerant out
of the chiller condenser.
f. When all liquid is out of the chiller condenser, close
valve 11 and any other liquid isolation valves on the
chiller.
g. Turn off the pumpout compressor.
2. Evacuate gas from chiller condenser vessel.
a. Turn on chiller water pumps.
b. Make sure that pumpout valves 3 and 4 are closedand
valves 2 and 5 are open.
VALVE 1a1b2345811
CONDITIONCCCC
c. Turn on pumpout condenser water.
d. Run the pumpout compressor until the chiller con-
denser reaches 18 in. Hg (41 kPa absolute). Monitor
pressure atthe chiller control paneland refrigerant gages.
e. Close valve 1b.
f. Turn off pumpout compressor.
g. Close valves 1a, 2, and 5.
VALVE 1a1b2345811
CONDITIONCCCCCCCC
h. Turn off pumpout condenser water.
i. Turn off chiller water pumps and lock out chiller com-
pressor.
Return Refrigerant to Normal Operating Conditions
1. Be sure that the chiller vessel that was opened has been
evacuated.
2. Turn on chiller water pumps.
3. Open valves 1a, 1b, and 3.
VALVE1a1b2345811
CONDITIONCCCCC
4. Crack open valve 5, gradually increasing pressure in the
evacuated chiller vessel to 60 psig (414 kPa), [30 psig
(207 kPa)]. Feed refrigerant slowly to prevent tube
freeze-up.
5. Leak test to ensure chiller vessel integrity.
6. Open valve 5 fully.
VALVE 1a1b2345811
CONDITIONCCCC
7. Close valves 1a, 1b, 3, and 5.
8. Open chiller isolation valve 11 and any other isolation
valves, if present.
VALVE 1a1b2345811
CONDITIONCCCCCCC
9. Turn off chiller water pumps.
DISTILLING THE REFRIGERANT
1. Transfer the refrigerant from the chiller to the pumpout
storage tank as described in the Transfer the Refrigerant
from Chiller to Pumpout Storage Tank section.
2. Equalize the refrigerant pressure.
a. Turn on chiller water pumps and monitor chiller
pressures.
b. Close pumpout and storage tank valves 2, 4, 5, 8, and
10, and close chillerchargingvalve 7; open chiller isolation valve 11 and any other chiller isolation valves,
if present.
c. Open pumpout and storage tank valves 3 and 6; open
chiller valves 1a and 1b.
VALVE 1a1b23456781011
CONDITIONCCCCCC
d. Gradually crack open valve 5 to increase chiller pres-
sure to 60 psig (414 kPa), [30 psig (207 kPa)]. Slowly
feed refrigerant to prevent freeze-up.
e. Open valve 5 fully after thechillerpressure rises above
the freezing point of the refrigerant. Let the storage
tank and chiller pressure equalize.
3. Transfer remaining refrigerant.
a. Close valve 3.
b. Open valve 2.
VALVE 1a1b23456781011
CONDITIONCCCCC
c. Turn on pumpout condenser water.
d. Run the pumpout compressor until the storage tank
absolute).
e. Turn off the pumpout compressor.
f. Close valves 1a, 1b, 2, 5, and 6.
g. Turn off pumpout condenser water.
VALVE 1a1b23456781011
CONDITIONCCCCCCCCC C
4. Drain the contaminants from the bottom of the storage
tank into a container. Dispose of contaminants safely.
MAINTENANCE
Periodic maintenance is necessary to keep all components
functioning as designed. A maintenance log is recommended to ensure a proper maintenance schedule is
followed.
Pumpout Unit — For maintenance details, refer to the
06D, 07D Installation, Start-Up, and Service Instructions.
15
Page 16
PUMPOUT COMPRESSOR OILCHARGE — Use oil conforming to Carrier specifications for reciprocating compressor use. Oil requirements are listed in Table 6.
Table 6 — Pumpout Compressor Oil Requirements
REFRIGERANT
R-2286PP49-7PP23BZ101
R-134a68PP47-31PP23BZ103
ISO
VISCOSITY
CARRIER
SPECIFICATION
NO.
CARRIER
PART NO.
The total oil charge, 4.5 pints (2.6 L), consists of 3.5 pints
(2.0 L) for the compressor and one additional pint (0.6 L)
for the oil separator.
Oil should be visible in one of the pumpout compressor
sight glasses both during operation and at shutdown.Always
check the oil level before operating the pumpout compressor. Before adding or changing oil, relieve the refrigerant
pressure as follows:
1. Attach a pressure gage to the gage port of either pumpout
compressor service valve (Fig. 10).
2. Close the suction service valve and open the discharge
line to the pumpout storage tank or the chiller.
3. Operate the compressor until the crankcasepressuredrops
to 2 psig (13 kPa).
4. Stop the pumpout compressor and isolate the pumpout
system by closing the discharge service valve.
5. Slowly remove the oil return lineconnection(Fig. 9). Add
oil as required.
6. Replace the connections and reopen the pumpout compressor service valves.
Storage Tank — To prevent moisture and contami-
nants from entering the storage tank, maintain positive pressure in the tank when not transferring refrigerant. Leak test
the storage tank according to your normal vessel leak test
procedures and schedule.
Ordering Replacement Parts — The following in-
formation mustaccompanyan order for Carrier-specifiedparts:
• machine model number and serial number
• name, quantity, and part number of the part required
• delivery address and method of shipment
TROUBLESHOOTING
Information on troubleshooting for the PPS is included in
Table 7.
Table7—Troubleshooting
SYMPTOMPROBABLE CAUSEREMEDY
Compressor does not runMain power line openReplace fuse or reset circuit breaker.
Loose terminal connectionCheck connections.
Improperly wired controlsCheck wiring and rewire.
Low line voltageCheck line voltage; determine location of voltage drop.
Compressor motor defectiveCheck motor winding for open or short. Replace compressor if
Seized compressorReplace compressor.
High level gage alarmCheck refrigerant level and remove excess.
Compressor cycles on
high-pressure control
Unit operates too longIsolation valves partially openClose valves.
System NoisesPiping vibrationsSupport piping as required. Check for loose pipe connectors.
Compressor Loses OilLeak in systemLocate and repair leak.
High-pressure control erratic in actionCheck capillary tube for pinches. Set control as required..
Discharge valve partially closed.Open valve.
Air in systemPurge system.
Condenser scaled.Clean condenser.
Condenser water pump or fans not operat-