Carrier 19XB User Manual

Page 1
Positive Pressure Storage System
50/60 Hz
Installation, Operating, and Maintenance
Instructions
For Use With Positive Pressure Chillers
SAFETY CONSIDERATIONS
Positive pressure storage systems are designed to pro­vide safe and reliable service when operated within de­sign specifications. When operating this equipment, use good judgment and safety precautions to avoid damage to equipment and property or injury to personnel. Be sure you understand and follow the procedures and safety precautions contained in this guide.
DO NOT VENT refrigerant relief valves within a building. Outlet from rupture disc or relief valve must be vented outdoors in ac­cordance with the latest edition ofASHRAE 15 (American Society of Heating, Refrigeration, and Air Conditioning Engineers). The accumulation of refrigerant in an enclosed space can displace oxy­gen and cause asphyxiation.
PROVIDE adequate ventilation in accordance with ASHRAE 15, especially forenclosed and low overheadspaces. Inhalation of high concentrations of vapor is harmful and may cause heart irregulari­ties, unconsciousness,or death. Misusecan be fatal.Vaporis heavier than air and reduces the amount of oxygen available for breathing. Product causes eye and skin irritation. Decomposition products are hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a machine for any purpose. Oxygen gas reacts violently with oil, grease, and other common substances.
NEVER EXCEED specified test pressures, VERIFY the allowable test pressure by checking the instruction literature and the design pressures on the equipment nameplate.
DO NOT USE air for leak testing. Use only tracer gases and dry nitrogen.
DO NOT VALVE OFF any safety device. BE SURE that all pressure relief devices are properly installed and
functioning before operating any machine.
with soapand water.If any entersthe eyes, IMMEDIATELYFLUSH EYES with water and consult a physician.
NEVER APPLY an open flame or live steam to a refrigerant cyl­inder. Dangerous overpressure can result. When necessary to heat refrigerant, use only warm (110 F [43 C]) water.
DO NOT REUSE disposable (nonreturnable) cylinders or attempt to refill them. It is DANGEROUSAND ILLEGAL. When cylinder is emptied, evacuate remaining gas pressure, loosen the collar and unscrew and discard the valve stem. DO NOT INCINERATE.
CHECK THE REFRIGERANT TYPE before transferring refrig­erant to the machine. Theintroduction of the wrong refrigerant can cause damage or malfunction to this machine.
Operation of this equipment with refrigerants other than those cited herein shouldcomply with ASHRAE 15 (latest edition). Con­tact Carrierfor further information on use of thismachine with other refrigerants.
DO NOTATTEMPT TO REMOVE fittings, covers, etc., while ma­chine is under pressure or while machine is running. Be sure pres­sure is at 0 psig (0 kPa) before breaking any refrigerant connection.
CAREFULLY INSPECT all relief devices, rupture discs, and other relief devices AT LEAST ONCE A YEAR. If machine operates in a corrosive atmosphere, inspect the devices at more frequent intervals.
DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief device when corrosion or build-up of foreign material (rust, dirt, scale, etc.) is found within the valve body or mechanism. Replace the device.
DO NOT install relief devices in series or backwards. USE CAREwhen working near orin line witha compressed spring.
Sudden release of the spring can cause it and objects in its path to act as projectiles.
19XB
DO NOT WELD OR FLAMECUT any refrigerant line or vessel until allrefrigerant (liquid andvapor) has beenremoved from chiller. Traces of vapor should be displaced with dry air or nitrogen and the work area should be well ventilated. Refrigerant in contact with
an open flame produces toxic gases.
DO NOT USE eyebolts or eyebolt holes to rig machine sections or the entire assembly.
DO NOT work on high-voltage equipment unless you are a quali­fied electrician.
DO NOTWORK ON electricalcomponents, including control pan­els, switches, starters, or oil heater until you are sureALL POWER IS OFF and no residual voltage can leak from capacitors or solid­state components.
LOCK OPEN ANDTAGelectrical circuits during servicing.IF WORK IS INTERRUPTED, confirm that all circuits are deenergized be­fore resuming work.
DO NOT syphon refrigerant by mouth. AVOID SPILLING liquid refrigerant on skin or getting it into the
eyes. USE SAFETY GOGGLES. Wash any spills from the skin
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Tab 5a
PC 211 Catalog No. 531-927 Printed in U.S.A. Form 19XB-1SI Pg 1 6-96 Replaces: New
DO NOT STEP on refrigerant lines. Broken lines can whip about and cause personal injury and damage to the machine.
DO NOT climb over a machine. Use platform, catwalk, or staging. Follow safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or move inspection covers or other heavy components. Even if com­ponents are light, use such equipment when there is a risk of slip­ping or losing your balance.
BE AWARE that certain automatic start arrangements CAN EN­GAGE THE STARTER. Open the disconnect ahead of the starter in addition to shutting off the machine or pump.
USE only repair or replacement parts that meet the code require­ments of the original equipment.
DOUBLE-CHECK that coupling nut wrenches, dial indicators, or other items have been removed before rotating any shafts.
DO NOT LOOSEN a packing gland nut before checking that the nut has a positive thread engagement.
PERIODICALLY INSPECT all valves, fittings, and piping for cor­rosion, rust, leaks, or damage.
DO NOTMIX REFRIGERANTfrom chillers thatuse differentcom­pressor oils. Compressor damage can result.
Page 2
CONTENTS
Page
SAFETY CONSIDERATIONS ...................1
INTRODUCTION ..............................2
INSTALLATION .............................2-10
Complete Pre-Installation Checks .............2
• IDENTIFY UNIT
• INSPECT SHIPMENT
Mount the Pumpout Unit .....................3
• MOUNTING ON THE CHILLER
• FLOOR MOUNTING
Rig the Storage Tank .........................3
Make Piping Connections ....................7
• INSTALL VENT PIPING TO RELIEF DEVICES
Make Electrical Connections ..................7
CONTROLS AND COMPONENTS ..............11
Pumpout Unit ................................11
• CONTROLS
• SAFETY CONTROL SETTINGS
• COMPRESSOR
• CONDENSER
• OIL SEPARATOR
• SUCTION AND DISCHARGE VALVES
Storage Tank ................................11
• DRAIN VALVE
• DUAL RELIEF VALVES
• PRESSURE GAGE
• LEVEL GAGE
OPERATION ...............................11-15
Overview ...................................11
• REFRIGERANT TRANSFER
• TRANSFERRING LIQUID REFRIGERANT FROM THE CHILLER COOLER TO THE CHILLER CONDENSER OR PUMPOUT STORAGE TANK
• TRANSFERRING LIQUID REFRIGERANT FROM THE CHILLER CONDENSER OR PUMPOUT STORAGE TANK TO THE CHILLER COOLER
• DISTILLING THE REFRIGERANT
Pumpout and Refrigerant Transfer
Procedures ...............................12
• OPERATING THE PUMPOUT UNIT
• TO READ REFRIGERANT PRESSURES
• POSITIVE PRESSURE CHILLERS WITH STORAGE TANKS
• CHILLERS WITH ISOLATION VALVES
• DISTILLING THE REFRIGERANT
MAINTENANCE ............................15,16
Pumpout Unit ...............................15
• PUMPOUT COMPRESSOR OIL CHARGE
Storage Tank ...............................16
Ordering Replacement Parts .................16
TROUBLESHOOTING ........................16
INTRODUCTION
The 19XB Positive Pressure Storage (PPS) System has been designed to help owners and operators of positive pres­sure chillers store refrigerants HCFC-22 and HFC-134a dur­ing service and repair work. The 19XB system conserves these refrigerantsand prevents the releaseofexcessive amounts of refrigerant into the atmosphere. The proper use of this equipment minimizes the loss of HFCs and HCFCs.
The 19XB PPS systemshownin Fig. 1 consists of a pump­out unit mounted on a storage tank. The pumpout unit is of­fered as a free-standing unit that can be used with chillers that have an existing storage tank or with chillers that have isolation valves that permit built-in refrigerant storage.
The 19XB PPS systems are factory tested and certified to theAmerican Society of Mechanical Engineers(ASME)pres­sure vessel code. The tanks are constructed of certified steel and are pressure rated at 300 psig (2068 kPa). The PPS stor­age tank is equipped with dual relief valves for proper vent­ing per ASHRAE 15 (American Society of Heating Refrig­eration, and Air Conditioning Engineers) guidelines. An automatic level switch is prewired to the control circuit to ensure proper storage levels.
The 19EA pumpout unit is a complete, hermetic, compact unit that consists of:
• a spring-mounted reciprocating compressor with a direct-
drive motor
• a water-cooled refrigerant condenser
• an oil separator
• suction and discharge valves to control refrigerant flow
• prewired safety and control devices.
When referencing refrigerant charges in this manual, the HCFC-22 charge will be listed first and the HFC-134a value will follow in brackets.
INSTALLATION
Complete Pre-Installation Checks
IDENTIFY UNIT — Identify the assembly number (T able1) printed on the pumpout unit andstoragetank name­plates. Check this information against the job requirements. Fig. 1 shows the PPS system and its major components. Refer to Tables 2 and 3 for physical data.
INSPECT SHIPMENT — Inspect unit for damage before removing unitfromshipping conveyance. If unit appearsdam­aged, it should be inspected by a shipping inspector before removal. File a claim with the shipping company if ship­ment is damaged or incomplete. The manufacturer is not re­sponsible for damage incurred during transit.
Check all components. Notify the supplier immediately if any item is missing. To prevent loss or damage, leave all parts in their original package until they are needed.
2
Page 3
Table 1 — Positive Pressure System Assembly Numbers
POSITIVE PRESSURE
SYSTEM ASSEMBLY
NUMBER
19XB04280205 19EA42-748 R-22 208-3-60 13.2 63.5 28 cu ft 19XB04280206 19EA44-748 R-22 230-3-60 11.5 57.5 28 cu ft 19XB04280207 19EA46-748 R-22 400/460-3-50/60 5.8 28.8 28 cu ft 19XB04280208 19EA47-748 R-22 575-3-60 4.6 23.0 28 cu ft 19XB04280213 19EA48-748 R-134a 208-3-60 13.2 63.5 28 cu ft 19XB04280214 19EA49-748 R-134a 230-3-60 11.5 57.5 28 cu ft 19XB04280215 19EA51-748 R-134a 400/460-3-50/60 5.8 28.8 28 cu ft 19XB04280216 19EA52-748 R-134a 575-3-60 4.6 23.0 28 cu ft 19XB04280601 19EA42-748 R-22 208-3-60 13.2 63.5 None 19XB04280602 19EA44-748 R-22 230-3-60 11.5 57.5 None 19XB04280603 19EA46-748 R-22 400/460-3-50/60 5.8 28.8 None 19XB04280604 19EA47-748 R-22 575-3-60 4.6 23.0 None 19XB04280605 19EA48-658 R-134a 208-3-60 13.2 63.5 None 19XB04280606 19EA49-658 R-134a 230-3-60 11.5 57.5 None 19XB04280607 19EA51-658 R-134a 400/460-3-50/60 5.8 28.8 None 19XB04280608 19EA52-658 R-134a 575-3-60 4.6 23.0 None 19XB04520205 19EA42-748 R-22 208-3-60 13.2 63.5 52 cu ft 19XB04520206 19EA44-748 R-22 230-3-60 11.5 57.5 52 cu ft 19XB04520207 19EA46-748 R-22 400/460-3-50/60 5.8 28.8 52 cu ft 19XB04520208 19EA47-748 R-22 575-3-60 4.6 23.0 52 cu ft 19XB04520213 19EA48-748 R-134a 208-3-60 13.2 63.5 52 cu ft 19XB04520214 19EA49-748 R-134a 230-3-60 11.5 57.5 52 cu ft 19XB04520215 19EA51-748 R-134a 400/460-3-50/60 5.8 28.8 52 cu ft 19XB04520216 19EA52-748 R-134a 575-3-60 4.6 23.0 52 cu ft
LEGEND
LRA — Locked RotorAmps RLA — Rated LoadAmps
PUMPOUT UNIT ASSEMBLY NO.
REFRIGERANT
COMPRESSOR MOTOR
(V-Ph-Hz)
NOTES:
1. Allstorage vesselsare 300 psig (2068 kPa)designs perthe ASME (American Society of Mechanical Engineers) Boiler Pressure Vessel Code, Section VIII Division 1.
2. Allunits aboveare shippedwitha 15psig (103kPa) nitrogencharge.
3. Nominal horsepower for all pumpout units is 3.0.
MAXIMUM
RLA
LRA
STORAGE
TANK
MountthePumpoutUnit— The pumpout unit, if pur-
chased separately, may be mounted directly on the chiller or it may be floor mounted.
MOUNTING ON THE CHILLER — See instructions pro­vided with the chiller for mountingthepumpout unit. Atypi­cal chiller mount is shown in Fig. 2.
FLOOR MOUNTING — Select a ventilated and accessible area, free of traffic or other hazards. Removeand discard the 4 angle supports at the base of the pumpout unit and bolt the unit to the floor through the 4 pumpout unit. Special isolation is unnecessary. Contact sur­face and dimensions for the pumpout unit are given in Fig. 3.
7
⁄16in. holes at the base of the
Rig the Storage Tank — The complete 19XB system
can be rigged as a single assembly. See the rigging instruc­tions on the label attached to the assembly. Also refer to the rigging guide (Fig. 4), physical data in Tables 2 and 3, and contact surface and dimensions for the complete system in Fig. 5. Lift the assembly only from the 4 points indicated in the rigging guide. Each rigging cable must be capable of supporting the entire weight of the assembly.
Lifting the assembly from points other than those speci­fied may result in serious damage to the assembly and personal injury. Riggingequipmentand procedures must be adequate forassembly. See Tables 2 and 3for weights. NOTE: These weights are broken down into pumpout unit and storage tank weights. For the complete assem­bly weight, add all components together.
3
Page 4
VALVES
VENT VALVE
VALVES
CONDENSER WATER CONNECTIONS (FIELD PIPING)
REFRIGERANT INLET VALVE
19EA PUMPOUT UNIT
CONTROL BOX (WIRING BY CONTRACTOR)
COMPRESSOR
19EA PUMPOUT UNITS
19EA CONTROL BOX (INTERIOR)
Fig. 1 — 19XB Positive Pressure Storage System
4
Page 5
*3⁄8-16 bolts × 1-in. lg; 4 required.
Fig. 2 — 19EA Pumpout Unit: Typical Chiller Mount
ELECTRICAL CONNECTION
OPTION LIST
TRADE SIZE QTY LOCATION
1
⁄2( 1TOP
3
4
( 1 BOTTOM
1( 1 MIDDLE
1
1
⁄4( 1 MIDDLE
Fig. 3 — Pumpout Unit Contact Surfaces and Dimensions
5
Page 6
NOTES:
1. Each chainmust be capable of supporting the entireweight of the machine.
2. Minimum chain length:
3
tank — 108-09
28 ft
3
52 ft
tank — 158-69
3. Total weight equals empty weight from chart and charge weight given on label.
STORAGE
TANK SIZE
3
28 Ft
3
52 Ft
CENTER OF GRAVITY
APPROX. DIM. — ft-in. (mm)
AB
4- 51⁄
(1353)
6-101⁄
(2086)
4
8
1-77⁄ (505)
1-83⁄ (527)
8
4
EMPTY WEIGHT
LB (Kg)
(1080) (1569)
Fig. 4 — Rigging Guide
Table 2 — Physical Data
19EA Pumpout Unit
ENGLISH (SI)
Pumpout Unit Weight* lb (kg) 210 (95) Pumpout Condenser Water Flow Rate gpm (L/s) 5 to 7 (.32 to .44)
Pumpout Condenser Water Pressure Drop psig (kPa) 6 to 10.7 (41.4 to 73.8) Maximum Entering Condenser Water Temperature F (C) 85 (29) Maximum Leaving Condenser Water Temperature F (C) 100 (37) Condenser Relief Valve (Fusible Plug) psig (kPa) 385 (2655) Condenser Pressure Rating
Refrigerant Side psig (kPa) 385 (2655) Waterside psig (kPa) 150 (1034)
Compressor Rating 1750 rpm (29 r/s) Reciprocating cfm (L/s) 8.7 (.25) Valves (4-Valve Manifold, Copper with
Brass Turn Knob Valves)
in. OD
*The pumpout unit weight includes the compressor/condenser, control box, and the oil separator. NOTES:
1. The motor is hermetic with thermal protection.
2. The control box is mounted and wired with a fuse on/off switch according to NEMA 1 (National Electrical Manufacturing Association).
3. The starter contactor is located in the control box. The overloads on the motor are wired and the disconnect switch is supplied by the customer.
4. The condenser tube is copper.
1
2
2380 3460
1
2
6
Page 7
Table 3 — 19XB Storage Tank Rated Dry Weight and Refrigerant Capacity
English
SIZE CODE
0428 24.00 2380 1842 1860 1704 1716 0452 27.25 3460 3527 3563 3264 3286
SIZE CODE
0428 610 1080 836 844 773 778 0452 592 1569 1600 1616 1481 1491
ANSI American National Standards Institute ASHRAE — American Society of Heating, Refrigeration,
UL Underwriters’ Laboratories
*The above dry weight includes the pumpout unit weight of 210 lbs (95 kg).
and Air Conditioning Engineers
TANK OD
(in.)
TANK OD
(mm)
LEGEND
DRY WEIGHT*
(lb)
DRY WEIGHT*
(kg)
SI
MakePipingConnections— Figure 6representstypi-
cal pumpout unit/chiller piping connections. Standard con­nections for1⁄2-in. OD copper tubing are provided. Install the field-supplied FPT tee with pipe plug in the piping as shown in Fig. 6. This tee is used for refrigerant charging.
NOTE: If any field piping runs exceed 50 ft in length, use
7
⁄8-in. OD copper tubing to minimize pressure drop.
Pumpout unit water piping connections are shown in Fig. 6. Both connections are valve should be installed in the water line. Provide a means for blowing water from the condenser coil at winter shut­down to prevent freeze-up damage. Refer to the Job Data for water piping particulars.
INSTALL VENT PIPING TO RELIEF DEVICES — The pumpout storage tank is factory-equipped with relief de­vices. Refer to Fig. 5 and Table 2 for size and location of the relief devices. Vent the relief devices to the outdoors in ac­cordance with ANSI/ASHRAE 15 Safety Code (latest edi­tion) for Mechanical Refrigeration and all other applicable codes. Relief devices are set to relieve at 300 psig (2068 kPa).
Refrigerant discharged into confined spaces can dis­place oxygen and cause asphyxiation.
1
⁄2-in. NPT (female). A shutoff
MAXIMUM REFRIGERANT CAPACITY (lb)
ASHRAE/ANSI 15 UL 1963
R-22 R-134a R-22 R-134a
MAXIMUM REFRIGERANT CAPACITY (kg)
ASHRAE/ANSI 15 UL 1963
R-22 R-134a R-22 R-134a
1. If relief devices are manifolded, the cross-sectional area of the relief pipe must at least equal the sum of the areas required for individual relief pipes.
2. Provide a pipe plug near outlet side of each relief device for leak testing. Provide pipe fittings that allow vent pip­ing to be disconnectedperiodicallyfor inspection of valve mechanism.
3. Piping to relief devices must not apply stress to the de­vice. Adequately support piping.Alength of flexible tub­ing or piping near the device is essential on spring­isolated machines.
4. Cover the outdoor vent with a rain cap and place a con­densation drain at the low point in the vent piping to pre­vent water build-up on the atmospheric side of the relief device.
Make Electrical Connections — See nameplate on
compressor of pumpout unit and Table 1 for motor electrical data. Wire unit according to the diagram inside the control box.
Fig. 7 is the wiring schematic for a complete system that includes the 19XB storage tank and the pumpout unit. Fig. 8 is the wiring schematic for the pumpout unit. Use this schematic for installations that do not include an auxiliary pumpout storage tank.
NOTE: Use copper conductors only.
7
Page 8
DIMENSIONS
ENGLISH (ft-in.)
TANK
SIZE 0428 10- 5 9-10 4-9 2-4 0452 14-111⁄414- 41⁄25-07⁄82-81⁄21-41⁄43-47⁄167- 21⁄44-0 3-117⁄83-15⁄163-57⁄80-33⁄87-11⁄21-83⁄41-79⁄163-8 5-01⁄
TANK
SIZE 0428 3175 2997 1448 730 365 945 1499 1121 1118 849 965 89 1442 505 491 1111 1530 0452 4553 4382 1546 826 413 1027 2191 1219 1216 948 1064 86 2172 528 497 1118 1537
NOTES:
1. Denotes center of gravity.
2. Dimensions in ( ) are in millimeters.
3. The weights and centerof gravity values given are for an empty storage
4. For additional information on the pumpout unit, see certified drawings.
5. The available conduit knockout sizes are:
A B CDE F G H J K LMNPR ST
3
⁄41-23⁄83-13⁄164-11 3-81⁄83- 8 2-97⁄163-2 0-31⁄24-83⁄41-77⁄81-75⁄163-73⁄45-01⁄
SI (mm)
ABCDEFGHJKLMNPRST
tank.
4 2
TRADE
SIZE
1
⁄2( 1 top
3
⁄4( 1 bottom
1( 1 middle
11⁄4( 1 middle
QTY LOCATION
Fig. 5 — PPS Contact Surface and Dimensions
8
Page 9
CHILLERS WITHOUT ISOLATION VALVES CHILLERS WITH ISOLATION VALVES
(WITH OR WITHOUT PUMPOUT STORAGE TANKS)
GENERAL PIPING CONNECTION SIZES
CONNECTION SIZE (in.) Refrigerant Transfer Connections Condenser Water Cooling Connectors Safety Relief Head Pumpdown Condenser
ODS — Outside Diameter, Sweat
NOTES:
1. The field-suppliedtubing is to be be arranged and supported to avoid stresses on the equipment, transmission of vibrations, and interference with routine access during the reading, adjusting, and servicing of the equipment. If the distance from the chiller to thepumpout unit is over 50ft, then
7
⁄8-in. OD tubing (min.)must be used. Provisions should be made for adjustment in each plane of the tubing and for both periodic and majorservicing of the equipment.Special care mustbe taken so that the safety head does not experience tubing strain. Vent the safety head per ASHRAE 15 (American Society of Heating, Refrigeration, and Air Conditioning Engineers), latest revision.
2. The tubing and valve from the storage tank to the pumpout com­pressor is factory supplied when the unit is factory mounted.
1
⁄2-in. ODtubing (min.) and must
1
⁄2ODS (female)
1
⁄2NPT (female)
3
⁄8Flare (male)
Fig.6—Typical Pumpout Unit/Chiller Connection Schematic
LEGEND
Factory-Supplied Tubing Field-Supplied Tubing Field-Supplied Tubing (Multiple Chillers)
Service Valve (Factory Supplied) Service Valve (Field Supplied)
9
Page 10
Table 4 — Relief Devices
STORAGE
TANK SIZE
28
52
RELIEF VALVE
OUTLET SIZE
1 in. NPT
Female Connector
1 in. NPT
Female Connector
QUANTITY
lb air
min
2 31.4 14.2 2 52.3 23.7
REQUIRED FACTOR
Kg air
min
LEGEND Ground Field Wiring
Factory Wiring Contactor Term.
Overload Term. Pumpdown Term.
Pumpdown Comp’r. Term.
Fig. 7 — 19XB Pumpout System Wiring Schematic
LEGEND
C—Contactor Fu Fuse, 3 Amps HP High-Pressure Cutout L—Compressor Motor Voltage Line (3-phase) LL Low-Line Control Voltage (single-phase) OL Compressor Overload T’stat — Internal Thermostat
*Bimetal thermal protector imbedded in motor winding.
Compressor Terminal Contactor Terminal
Overload Terminal Pumpout Unit Terminal
Fig. 8 — Pumpout Unit Wiring Schematic
10
Page 11
CONTROLS AND COMPONENTS
Figure 1 shows the major components of the PPS system.
PumpoutUnit— The pumpout unit consists of a spring-
mounted directmotor-driven reciprocating compressor,a water­cooled refrigerant condenser, an oil separator, suction and dischargevalvesto control refrigerant flow, and prewired safety and control devices. The pumpout unit comes equipped with a 4-way transfer valve manifold to interconnect both liquid and vapor transfer and to pressurize the chiller during trans­fer of refrigerant from chiller to storage tank.
CONTROLS — The pumpout unit has the following con­trols: an on/off switch, a 3-amp fuse, compressor overloads, an internal thermostat, a compressor contactor, and a refrig­erant high pressure cutout.
SAFETYCONTROL SETTINGS — Thepumpoutunit high­pressure switch (Fig. 1) is set to open at the settings listed in Table 5. The switch setting is checked by operating the pumpout condenser and slowly throttling the pumpout con­denser water.
Table 5 — High Condition Pressure Switch Settings
English
REFRIGERANT
R-134a 161 ± 5 psig
R-22 220 ± 5 psig
REFRIGERANT
R-134a 1110±34kPa
R-22 1517 ± 34 kPa
NOTES:
1. R-22 units use high-pressure cutout switch HK01UA181.
2. R-134a units use high-pressure cutout switch HK01UA187.
HIGH-PRESSURE SWITCH
Cutout CutIn
+0
130 − 5 psig
+0
185 − 5 psig
SI
HIGH-PRESSURE SWITCH
Cutout Cut-In
+0
896 − 34 kPa
+0
1276 − 34 kPa
COMPRESSOR — The pumpout compressor assembly has a positive displacement of 1750 rpm (29 r/s) and 8.7 cfm (0.004 m3/s). It comes equipped with thermal protection on the motor and an in-line oil separator.
CONDENSER —The water-cooled condenser is fullyASME constructed. During transfer, it condenses refrigerant vapor to liquid.The condenser transfer tank safety reliefvalves com­ply with ASHRAE 15 standards.
OIL SEPARATOR — The pumpout unit includes an in-line oil separator to remove oil that becomes mixed with refrig­erant and returns the oil to the compressor.
SUCTION AND DISCHARGE VALVES — The pumpout unit comes with a 4-way transfer valve manifold to inter­connect both liquid and vapor transfer and to pressurize the chiller during transfer of refrigerant from chiller to storage tank or from one chiller vessel to another.
Storage Tank — The storage tank is rated for positive
pressure refrigerants underASME Section VIII pressure ves­sel codes with a minimum of 300 psig (2068 kPa) rating. The tank components include:
DRAIN VALVE — Located at its lowest point of drain with a minimum of 1 in. NPT.
DUAL RELIEF VALVES — Two relief valves and a 3-way shut-off valve.
PRESSURE GAGE —A 30in.-0-400psig (101-0-2760 kPa) compound pressure gage.
LEVEL GAGE — Liquid level gage (magnetically coupled dial type) with electronic shut-off at 90% liquid capacity.
During transfer of refrigerant into and out of the pump­out storage tank, carefullymonitorthe storage tank level gage. Do not fill the tank more than 90% of capacity to allow for refrigerant expansion. Overfilling may result in damage to the tank and personal injury. For maxi­mum refrigerant capacity, refer to Table 2.
OPERATION
Overview —
another is accomplished by using either gravity or pressure differential. A difference in elevation between 2 vessels re­sults in agravityflow of liquid; a dif ferencein pressure forces the liquid from one vessel to the other. The latter method requires lowering the pressure in one vessel. If there is liq­uid in that vessel, its temperature must be lowered, and the pressure in the other vessel must be simultaneously increased.
Under most circumstances, creating the pressure differ­ential is not a difficult process. Some applications, such as ice storage, outdoor installations, or installations with high temperature differentials between the storage tank and the chiller may require additional consideration. In some in­stances, it may be necessary to add auxiliary heat to one of the vessels or to insulate the storage tank at job sites where high ambient temperature or sun load make it difficult to re­duce the temperature and pressure in the tank. Outdoor in­stallations must have a roof or cover over thestorage tank to ensure that thepressurein the tank does not exceed the chiller relief pressure setting.
REFRIGERANT TRANSFER — When refrigerant is being evacuated from the chiller cooler or condenser vessels, any liquid refrigerant left in a vessel will flash off, lowering the temperature in that vessel enough to freeze the fluid (usually water) flowing through the cooler or condenser tubes. This event, called tube freeze-up, can cause extensive damage to the chiller; therefore, all liquid refrigerant must be removed from a vesselbeforeevacuation of refrigerant vapor is started. If all the liquid cannot be removed, then the cooler water and condenser water pumps mustbeoperated throughout the process of evacuating refrigerant vapor to keep fluid moving through the cooler and condenser tubes.
TRANSFERRING LIQUID REFRIGERANT FROM THE CHILLER COOLERT OTHE CHILLER CONDENSER OR PUMPOUT STORAGE TANK — Chiller and pumpout unit valves are set to permit the pumpout compressor to dis­charge refrigerantvaporinto the cooler vessel, lowering pres­sure in the condenser vessel/storage tank. The pressure dif­ferential forcesliquidfrom the cooler vesselintothe condenser vessel/storage tank. After all the liquid is transferred, the re­frigerant vapor remaining in the cooler vessel can be drawn off by reducing pressure in the chiller and discharging the vapor through the pumpout unit condenser into the con­denser vessel/storage tank.
TRANSFERRING LIQUID REFRIGERANT FROM THE CHILLER CONDENSERORPUMPOUT STORAGETANK TO THE CHILLER COOLER — Chiller and pumpout unit valves are set to increase pressure in the chiller condenser vessel/storage tank and to reduce pressure in the cooler ves­sel. Pressure in the cooler vessel is lowered to correspond to a saturated refrigerant liquid temperature 2 F (1.1 C) above the freezing temperature of the liquidcirculatingthrough the chiller cooler/condenser tubes (34 F [1.1 C] for water). The valves are set sothatthe pressure in the cooler vessel is lower than that of the condenser vessel/storage tank, forcing the liquid into the cooler vessel.
Transferring refrigerant from one vessel to
11
Page 12
NOTE: During this operation, maintain water circulation through the chiller cooler and condenser vessels to prevent tube freeze-up.
DISTILLING THE REFRIGERANT — Refrigerant vapor is transferred from the chiller cooler vessel or pumpout stor­age tank through the pumpout condenser, condensed to a liq­uid, and pumped to the chiller condenser vessel. During this operation, water circulation mustbemaintained in the pump­out condenser.Refrigerant impurities left in the chiller cooler vessel or storage tank are then drained off. This operation can takefrom4 to 14 hours, dependingon the type and amount of refrigerant being distilled.
The Pumpout and Refrigerant Transfer Procedures sec­tion gives step-by-step instructions on performing these operations.
Pumpout and Refrigerant Transfer Procedures
Three possibilities are available:
1. If there are no isolation valves on the chiller, a complete
pumpout system with a pumpout storage tank and pump­out unit is needed.
2. Whether or not isolation valvesare available on the chiller,
the refrigerant can be pumped to and isolated in a pump­out storage tank by using the pumpout unit.
3. If isolation valves are available on the chiller, the refrig-
erant can be pumped to either the cooler vessel or the condenser vessel using the pumpout unit.
The following procedures describe how to transfer refrig­erant from one vessel to another and how to evacuate the chiller.
OIL RETURN LINE CONNECTION
CONDENSER WATER CONNECTIONS
VENT VALVE 8
REFRIGERANT INLET VALVE
PUMPOUT CONTROL BOX (WIRING BY CONTRACTOR)
Fig. 9 — Pumpout Unit
2. Attach a 30 in.-0-400 psi (101-0-2760 kPa) gage to the storage tank to determine its pressure.
POSITIVE PRESSURE CHILLERS WITH STORAGE TANKS — In the Valve/Condition tables that accompany these instructions, the letter 9C9 indicates a closed valve. Figures 9 and 10 show the locations of the valves.
Do not mix refrigerants from chillers that use different compressor oils. Compressor damage canresult.For ex­ample, the compressor oil in a 23XL chiller that uses HCFC-22 refrigerant can cause severe lubrication prob­lems in a 19XL chiller that uses HCFC-22 refrigerant.
OPERATING THE PUMPOUT UNIT
1. Be sure that the suction and the discharge service valves on the pumpout compressor (Fig. 9) are open (back­seated) during operation.Rotatethe valve stem fully coun­terclockwise to open. Frontseating the valve closes the refrigerant line and opens the gage port to compressor pressure.
2. Make sure that the pumpout compressor holddown bolts (Fig. 2) have been loosened to allow free spring travel.
Transfer, addition, or removal of refrigerant in spring­isolated chillers may place severe stressonexternal pip­ing if springs on the chiller have not been blocked in both up and down directions.
3. Open the refrigerant inlet valve (Fig. 9) on the pumpout compressor.
4. Oil should be visible in the pumpout compressor sight glass under all operating conditions and during shut­down. If oil is low, add oil as described in the Mainte­nance section.
TO READREFRIGERANTPRESSURES — During pump­out or leak testing:
1. Refer to the display on the chiller control center to de­termine refrigerant-side pressures and low (soft)vacuum. Use a quality vacuum indicator or manometer to measure evacuation and dehydrationand to ensure the desired range and accuracy.
Always run chiller cooler and condenser water pumps and always charge or transfer refrigerant as a gas when chiller vessel pressure is less than 60 psig (414 kPa) [30 psig (207 kPa)]. Below these pressures, liquid re­frigerant flashes intogas,resulting in extremely low tem­peratures inthe cooler/condenser tubesand possibly causing tube freeze-up.
Transfer Refrigerant from Pumpout Storage Tank to Chiller:
During transfer of refrigerant into and out of the 19XB storage tank,carefullymonitor the storage tanklevel gage. Do not fill the tank more than 90% of capacity to allow for refrigerant expansion. Overfillingmayresult in dam­age to the tank and personal injury.
1. Equalize refrigerant pressure. a. Turn on chiller water pumps and monitor chiller
pressures.
b. Close pumpout and storage tank valves 2, 4, 5, 8, and
10, and close refrigerant chargingvalve 7; open chiller isolation valve 1 1and any other chiller isolationvalves, if present.
c. Open pumpout and storage tank valves 3 and 6; open
chiller valves 1a and 1b.
VALVE 1a1b23456781011
CONDITION C C C C C C
d. Gradually crack open valve 5 to increase chiller pres-
sure to 60 psig (414 kPa),[30psig (207 kPa)]. Slowly feed refrigerant to prevent freeze-up.
12
Page 13
Fig. 10 — Valve Locations for 19XB Pumpout Unit With 19XB Storage Tank
e. Open valve 5 fully after thechillerpressure rises above
the freezing point of the refrigerant. Let the storage tank andchiller pressure equalize.Openrefrigerant charg­ing valve 7 and storage tank charging valve 10 to let liquid refrigerant drain into the chiller.
VALVE 1a1b23456781011
CONDITION C C C
2. Transfer remaining refrigerant. a. Close valve 5 and open valve 4.
VALVE 1a1b23456781011
CONDITION C C C
b. Turn off the pumpout condenser water,and turn on the
pumpout compressor to push liquid refrigerant out of the storage tank. Monitor the storage tank level until
the tank is empty. c. Close refrigerant charging valves 7 and 10. d. Turn off the pumpout compressor. e. Turn off the chiller water pumps. f. Close valves 3 and 4. g. Open valves 2 and 5.
VALVE 1a1b23456781011
CONDITION C C C C C
h. Turn on pumpout condenser water. i. Run the pumpout compressoruntil the storage tank pres-
sure reaches 5 psig (34 kPa), 18 in. Hg (41 kPa absolute).
j. Turn off the pumpout compressor.
k. Close valves 1a, 1b, 2, 5, and 6.
VALVE 1a1b23456781011
CONDITION C C CCCCCCC C
l. Turn off pumpout condenser water.
Transfer the Refrigerant from Chiller to Pumpout Storage Tank.
1. Equalize refrigerant pressure. a. Valve positions:
VALVE 1a1b23456781011
CONDITION C C C C C C
b. Slowly open valve 5 and refrigerant chargingvalves7
and 10 to allow liquid refrigerant to drain by gravity into the storage tank.
VALVE 1a1b23456781011
CONDITION C C C
2. Transfer the remaining liquid. a. Turn offpumpout condenser water. Place valves in the
following positions:
VALVE 1a1b23 456781011
CONDITION C C C
b. Run the pumpoutcompressor for approximately 30 min-
utes, then close valve 7 and 10.
VALVE 1a1b23456781011
CONDITION C C C C C
13
c. Turn off the pumpout compressor.
Page 14
3. Remove any remaining refrigerant. a. Turn on chiller water pumps. b. Turn on pumpout condenser water. c. Place valves in the following positions:
VALVE 1a1b23456781011
CONDITION C C C C C
d. Run the pumpout compressor until the chiller pres-
sure reaches 60 psig (414 kPa), [30 psig (207 kPa)]; then, shut off the pumpout compressor. Warm chiller condenser water will boil off any entrapped liquid re­frigerant and chiller pressure will rise.
e. When chiller pressure rises to 70 psig (483 kPa),
[40 psig (276 kPa)]; turn on the pumpout compressor until the pressure again reaches 60 psig (414 kPa) [30 psig (207 kPa)]; then, turn off the pumpout com­pressor. Repeat this process until the chiller pressure no longer rises; then, turn on the pumpout compressor and pump out until the chiller pressure reaches 18 in. Hg (41 kPa absolute).
f. Close valves 1a, 1b, 3, 4, and 6.
VALVE 1a1b23456781011
CONDITION C C CCCCCCC C
g. Turn off the pumpout condenser water.
4. Establish vacuum for service. To conserve refrigerant, op­erate the pumpout compressor as describedinStep 3e un­til the chiller pressure is reduced to 18 in. Hg (41 kPa absolute).
CHILLERS WITH ISOLATION VALVES — Thevalvesre­ferred to in the following instructions are shown in Fig. 9 and 11. Valve 7 remains closed.
Transfer All Refrigerant to Chiller Condenser Vessel:
1. Push refrigerant into chiller condenser vessel. a. Turn on thechillerwater pumps and monitor the chiller
pressure.
b. Valve positions:
VALVE 1a1b2345811
CONDITION C C C
c. Equalize the refrigerant in the chiller cooler and
condenser.
d. Turn off chiller water pumps and pumpout condenser
water supply.
e. Turn on pumpout compressor to push liquid out of the
chiller cooler vessel.
f. When all liquid has been pushed into the chiller con-
denser vessel, closethe cooler refrigerant isolation valve
(11). g. Turn on the chiller water pumps. h. Turn off the pumpout compressor.
2. Evacuate gas from chiller cooler vessel. a. Close pumpout valves 2 and 5; open valves 3 and 4.
VALVE 1a1b2345811
CONDITION C C C C
b. Turn on pumpout condenser water. c. Run pumpout compressor until the chiller cooler ves-
sel pressure reaches 18 in. Hg vac (41 kPa absolute). Monitor pressures on the chiller control panel and on refrigerant gages.
Fig. 11 — Valve Locations for 19XB Pumpout Unit Without Storage Tank
14
Page 15
d. Close valve 1a. e. Turn off pumpout compressor. f. Close valves 1b, 3, and 4.
VALVE 1a1b2345811
CONDITION C C CCCCCC
g. Turn off pumpout condenser water. h. Turn off chiller water pumps and lock out chiller
compressor.
Transfer All Refrigerant to Chiller Cooler Vessel:
1. Push refrigerant into the chiller cooler vessel. a. Turn on thechillerwater pumps and monitor the chiller
pressure.
b. Valve positions:
VALVE 1a1b2345811
CONDITION C C C
c. Equalize the refrigerant in the chiller cooler and
condenser.
d. Turn off chiller water pumps and pumpout condenser
water.
e. Turn on pumpout compressor to push refrigerant out
of the chiller condenser.
f. When all liquid is out of the chiller condenser, close
valve 11 and any other liquid isolation valves on the chiller.
g. Turn off the pumpout compressor.
2. Evacuate gas from chiller condenser vessel. a. Turn on chiller water pumps. b. Make sure that pumpout valves 3 and 4 are closedand
valves 2 and 5 are open.
VALVE 1a1b2345811
CONDITION C C C C
c. Turn on pumpout condenser water. d. Run the pumpout compressor until the chiller con-
denser reaches 18 in. Hg (41 kPa absolute). Monitor
pressure atthe chiller control paneland refrigerant gages. e. Close valve 1b. f. Turn off pumpout compressor. g. Close valves 1a, 2, and 5.
VALVE 1a1b2345811
CONDITION C C CCCCCC
h. Turn off pumpout condenser water. i. Turn off chiller water pumps and lock out chiller com-
pressor.
Return Refrigerant to Normal Operating Conditions
1. Be sure that the chiller vessel that was opened has been evacuated.
2. Turn on chiller water pumps.
3. Open valves 1a, 1b, and 3.
VALVE 1a 1b 2 3 4 5 8 11
CONDITION C C C C C
4. Crack open valve 5, gradually increasing pressure in the evacuated chiller vessel to 60 psig (414 kPa), [30 psig (207 kPa)]. Feed refrigerant slowly to prevent tube freeze-up.
5. Leak test to ensure chiller vessel integrity.
6. Open valve 5 fully.
VALVE 1a1b2345811
CONDITION C C C C
7. Close valves 1a, 1b, 3, and 5.
8. Open chiller isolation valve 11 and any other isolation valves, if present.
VALVE 1a1b2345811
CONDITION C C CCCCC
9. Turn off chiller water pumps.
DISTILLING THE REFRIGERANT
1. Transfer the refrigerant from the chiller to the pumpout storage tank as described in the Transfer the Refrigerant from Chiller to Pumpout Storage Tank section.
2. Equalize the refrigerant pressure. a. Turn on chiller water pumps and monitor chiller
pressures.
b. Close pumpout and storage tank valves 2, 4, 5, 8, and
10, and close chillerchargingvalve 7; open chiller iso­lation valve 11 and any other chiller isolation valves, if present.
c. Open pumpout and storage tank valves 3 and 6; open
chiller valves 1a and 1b.
VALVE 1a1b23456781011
CONDITION C C C C C C
d. Gradually crack open valve 5 to increase chiller pres-
sure to 60 psig (414 kPa), [30 psig (207 kPa)]. Slowly feed refrigerant to prevent freeze-up.
e. Open valve 5 fully after thechillerpressure rises above
the freezing point of the refrigerant. Let the storage tank and chiller pressure equalize.
3. Transfer remaining refrigerant. a. Close valve 3. b. Open valve 2.
VALVE 1a1b23456781011
CONDITION C C C C C
c. Turn on pumpout condenser water. d. Run the pumpout compressor until the storage tank
pressure reaches 5 psig (34 kPa), 18 in. Hg (41 kPa
absolute). e. Turn off the pumpout compressor. f. Close valves 1a, 1b, 2, 5, and 6. g. Turn off pumpout condenser water.
VALVE 1a1b23456781011
CONDITION C C CCCCCCC C
4. Drain the contaminants from the bottom of the storage tank into a container. Dispose of contaminants safely.
MAINTENANCE
Periodic maintenance is necessary to keep all components functioning as designed. A maintenance log is recom­mended to ensure a proper maintenance schedule is followed.
Pumpout Unit — For maintenance details, refer to the
06D, 07D Installation, Start-Up, and Service Instructions.
15
Page 16
PUMPOUT COMPRESSOR OILCHARGE — Use oil con­forming to Carrier specifications for reciprocating compres­sor use. Oil requirements are listed in Table 6.
Table 6 — Pumpout Compressor Oil Requirements
REFRIGERANT
R-22 86 PP49-7 PP23BZ101
R-134a 68 PP47-31 PP23BZ103
ISO
VISCOSITY
CARRIER
SPECIFICATION
NO.
CARRIER
PART NO.
The total oil charge, 4.5 pints (2.6 L), consists of 3.5 pints (2.0 L) for the compressor and one additional pint (0.6 L) for the oil separator.
Oil should be visible in one of the pumpout compressor sight glasses both during operation and at shutdown.Always check the oil level before operating the pumpout compres­sor. Before adding or changing oil, relieve the refrigerant pressure as follows:
1. Attach a pressure gage to the gage port of either pumpout
compressor service valve (Fig. 10).
2. Close the suction service valve and open the discharge
line to the pumpout storage tank or the chiller.
3. Operate the compressor until the crankcasepressuredrops
to 2 psig (13 kPa).
4. Stop the pumpout compressor and isolate the pumpout system by closing the discharge service valve.
5. Slowly remove the oil return lineconnection(Fig. 9). Add oil as required.
6. Replace the connections and reopen the pumpout com­pressor service valves.
Storage Tank — To prevent moisture and contami-
nants from entering the storage tank, maintain positive pres­sure in the tank when not transferring refrigerant. Leak test the storage tank according to your normal vessel leak test procedures and schedule.
Ordering Replacement Parts — The following in-
formation mustaccompanyan order for Carrier-specifiedparts:
• machine model number and serial number
• name, quantity, and part number of the part required
• delivery address and method of shipment
TROUBLESHOOTING
Information on troubleshooting for the PPS is included in
Table 7.
Table7—Troubleshooting
SYMPTOM PROBABLE CAUSE REMEDY
Compressor does not run Main power line open Replace fuse or reset circuit breaker.
Loose terminal connection Check connections. Improperly wired controls Check wiring and rewire. Low line voltage Check line voltage; determine location of voltage drop. Compressor motor defective Check motor winding for open or short. Replace compressor if
Seized compressor Replace compressor. High level gage alarm Check refrigerant level and remove excess.
Compressor cycles on high-pressure control
Unit operates too long Isolation valves partially open Close valves. System Noises Piping vibrations Support piping as required. Check for loose pipe connectors.
Compressor Loses Oil Leak in system Locate and repair leak.
High-pressure control erratic in action Check capillary tube for pinches. Set control as required.. Discharge valve partially closed. Open valve. Air in system Purge system. Condenser scaled. Clean condenser. Condenser water pump or fans not operat-
ing.
Compressor noisy Check valve plates for valve noise. Replace compressor (worn Insufficient compressor oil Add oil.
Plugged or stuck compressor oil return check valve
Dirty accumulator Clean accumulator.
necessary.
Start pump or fans.
bearings). Check for loose compressor holddown bolts.
Repair or replace valve.
Copyright 1996 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Tab 5a
PC 211 Catalog No. 531-927 Printed in U.S.A. Form 19XB-1SI Pg 16 6-96 Replaces: New
Loading...