Carrier 19QA User Manual

Page 1

Refrigerant Management System

Installation, Operating and Maintenance

Instructions

For Use With Low-Pressure Centrifugal Liquid Chillers

SAFETY CONSIDERATIONS

Refrigerant recovery devices are designed to provide safe and reliable service when operated within design spec ifications. When operating this equipment, use good judg ment and safety precautions to avoid damage to equip ment and property or injury to personnel.
Be sure you understand and follow the procedures and
safety precautions contained in this guide.

A DANGER

DO NOT VENT refrigerant relief valves within a building. Outlet from rupture disc or relief valve must be vented outdoors in ac cordance with the latest edition of ASHRAE 15 (Safety Code for Mechanical Refrigeration). The accumulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation.
PROVIDE adequate ventilation in accordance with ASHRAE 15, especially for enclosed and low overhead spaces. Inhalation of
high concentrations of vapor is harmful and may cause heart ir regularities, unconsciousness, or death. Misuse can be fatal. Va por is heavier than air and reduces the amount of oxygen available for breathing. Product causes eye and skin irritation. Decomposi tion products are hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a ma chine for any purpose. Oxygen gas reacts violently with oil, grease, and other common substances.
NEVER EXCEED specified test pressures, VERIFY the allow able test pressure by checking the instruction literature and the de sign pressures on the equipment nameplate.
DO NOT USE air for leak testing. Use only tracer gases and dry nitrogen.
DO NOT VALVE OFF any safety device. BE SURE that all pressure relief devices are properly installed
and functioning before operating any machine.

A WARNING

DO NOT WELD OR FLAMECUT any refrigerant line or vessel
until all refrigerant (liquid and vapor) has been removed from chiller. Traces of vapor should be displaced with dry air or nitrogen and the work area should be well ventilated.
with an open flame produces toxic gases.
DO NOT USE eyebolts or eyebolt holes to rig machine sections or the entire assembly.
DO NOT work on high-voltage equipment unless you are a qual ified electrician.
DO NOT WORK ON electrical components, including control pan
els, switches, starters, or oil heater until you are sure ALL POWER IS OFF and no residual voltage can leak from capacitors or solid­state components.
LOCK OPEN AND TAG electrical circuits during servicing. IF WORK IS INTERRUPTED, confirm that all circuits are de energized before resuming work.
DO NOT siphon refrigerant by mouth. AVOID SPILLING liquid refrigerant on skin or getting it into the
eyes. USE SAFETY GOGGLES. Wash any spills from the skin
Refrigerant in contact
with soap and water. If any enters the eyes, IMMEDIATELY FLUSH EYES with water and consult a physician.
NEVER APPLY an open flame or live steam to a refrigerant cyl inder. Dangerous overpressure can result. When necessary to heat refrigerant, use only warm (110 F [43 C]) water,
DO NOT REUSE disposable (nonreturnable) cylinders or attempt to refill them. It is DANGEROUS AND ILLEGAL. When cylinder is emptied, evacuate remaining gas pressure, loosen the collar and unscrew and discard the valve stem. DO NOT INCINERATE.
CHECK THE REFRIGERANT TYPE before adding refrigerant to the machine. The introduction of the wrong refrigerant can cause damage or malfunction to this machine.
Operation of this equipment with refrigerants other than those cited herein should comply with ASHRAE-15 (latest edition). Con tact Carrier for further information on use of this machine with other refrigerants.
DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while machine is under pressure or while machine is running. Be sure pressure is at 0 psig (0 kPa) before breaking any refrigerant
connection. CAREFULLY INSPECT all relief devices, rupture discs, and other
relief devices AT LEAST ONCE A YEAR. If machine operates in a corrosive atmosphere, inspect the devices at more frequent intervals.
DO NOT ATTEMPT TO REPAIR OR RECONDITION any re lief device when corrosion or build-up of foreign material (rust, dirt, scale, etc.) is found within the valve body or mechanism. Replace the device.
DO NOT install relief devices in series or backwards. USE CARE when working near or in line with a compressed spring.
Sudden release of the spring can cause it and objects in its path to act as projectiles.

A CAUTION

DO NOT STEP on refrigerant lines. Broken lines can whip about and cause personal injury.
DO NOT climb over a machine. Use platform, catwalk, or stag ing. Follow safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or
move inspection covers or other heavy components. Even if com ponents are light, use such equipment when there is a risk of slip ping or losing your balance.
BE AWARE that certain automatic start arrangements CAN EN GAGE THE STARTER. Open the disconnect ahead of the starter in addition to shutting off the machine or pump.
USE only repair or replacement parts that meet the code require ments of the original equipment.
DOUBLE-CHECK that coupling nut wrenches, dial indicators, or
other items have been removed before rotating any shafts. DO NOT LOOSEN a packing gland nut before checking that the
nut has a positive thread engagement. PERIODICALLY INSPECT all valves, fittings, and piping for
corrosion, rust, leaks, or damage.

19QA

50/60 Hz

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book|2 |2 PC 221 Catalog No 531-963 Printed in U S A Form 19QA-2SI Pg 1 9-94 Replaces: 19QA-1 SI Tab |5a|5d
Page 2
CONTENTS
Page
SAFETY CONSIDERATIONS INTRODUCTION
.........................................................
.....................................
INSTALLATION ..........................................................2-7
Complete Pre-Installation Checks............................2
• IDENTIFY UNIT
• INSPECT SHIPMENT
Make Piping Connections Make Electrical Connections Optional Caster Installation
CONTROLS AND COMPONENTS
.........................................
....................................
......................................
.............................
7,8
Pump and Motor .........................................................7
Oil Separator...............................................................7
Heater ..........................................................................7
Tube-in-Tube Condenser...........................................7
Level Gage ..................................................................7
Water Separation Sight Glass Purge Separator Assembly
..................................
.......................................
7
Refrigerant Hoses ......................................................8
Liquid Indicator
..........................................................
8
Filter Drier ...................................................................8
OPERATION .............................................................9-14
Evacuation ..................................................................9
Liquid Refrigerant Transfer.......................................9
• BEFORE TRANSFERRING LIQUID REFRIGERANT
• TO TRANSFER LIQUID REFRIGERANT
Refrigerant Vapor Transfer
• BEFORE TRANSFERRING REFRIGERANT VAPOR
• TRANSFER REFRIGERANT
......................................
10
Purge Separator Assembly ......................................12
Oil Separation ............................................................12
Water Separation .......................................................13
MAINTENANCE Maintaining the Pump Pump Coupling High-Pressure Cutout Switches
.........................................................
..............................................
.........................................................
..............................
15 15 15
15
Refrigerant Storage Tank.........................................15
Refrigerant Hoses
.....................................................
15
TROUBLESHOOTING................................................16
Table 1 — Interconnecting Refrigerant Hoses,
Valves, and Fittings
NUMBER
1 2
2 2 2
1 2 1 KA73PS012 1 19QA020-152 Liquid Indicator 8 1 19QA015-142
NOTE: Refer to Fig. 1 for model number description and accessory caster package part numbers.
PART NUMBER PART
KA73PS003 3 ft (.91 m) Hose KA73PS006 6 ft (1.88 m) Hose
12 ft (3.66 m) hose
19QA020-132 Valve and Coupler
Chiller Vapor Valve
INSTALLATION
Complete Pre-Installation Checks
IDENTIFY UNIT — Identify the model number and serial number printed on the nameplate. Check this information against the job requirements.
7
INSPECT SHIPMENT — Inspect unit for damage before removing unit from shipping conveyance. If unit appears damaged, it should be inspected by a shipping inspector be fore removal. File claim with shipping company if ship ment is damaged or incomplete. The manufacturer is not responsible for damage incurred during transit.
Check all components. Notify the supplier immediately if any item is missing. To prevent loss or damage, leave all parts in their original package until they are needed.
Make Piping Connections — All connections be
tween the pump, tube-in-tube condenser, storage tank, and
chiller can be made using the factory supplied refrigerant hoses. A hand valve with coupler is factory supplied, but must be field installed at each end of the 4 hoses. See Fig. 5. Field supplied copper tubing and valve manifolds must be used if a permanent installation is required.
The 19QA is factory equipped with a dual relief valve assembly. See Fig. 4. The outlet of the valves is 1-1/2 in. MPT. Vent the dual relief assembly outdoors in accordance with ASHRAE 15 (Safety Code for Mechanical Refrigera tion), latest edition, and all applicable local codes. Use a minimum 1-1/2 in. pipe for the relief valve outlet. Provide fittings so vent piping can be disconnected periodically for inspection and testing of valves.
Cover the outdoor vent with a rain cap and place a field
supplied condensate drain at the low point in vent piping to prevent water build up on the atmospheric side of the valve.
INTRODUCTION
The 19QA Refrigerant Management System (RMS) has been designed to help owners and operators of centrifugal chillers conserve low pressure refrigerants and prevent the
release of excessive amounts of refrigerant into the atmo sphere. The proper use of this equipment will minimize the loss of CFCs and HCFCs. The 19QA will also recycle re frigerant contaminated with water, oil, or acid. See Fig. 1 and Table 1 for component information.
The 19QA is ARI (Air Conditioning & Refrigeration In stitute) certified as a refrigerant recovery/recycling device and is registered with ETL (Electrical Testing Laboratory) for safety. The Refrigerant Management System’s storage tanks are rated for 20, 30, or 40 cu ft (.57, .85, 1.13 cu meters). See Table 2. Casters are available as an option on all storage tanks. See Fig. 1-3. See Fig. 4 and 5 for addi
tional RMS component descriptions and dimensions.
Make Electrical Connections — The 19QA has 2
electrical cords. See Table 3 and Fig. 6. One electrical cord is attached to the pump and the other is attached to the stor age tank heater. If both electrical cords are used at the same time, separate outlets are required. Connect electrical power in accordance with minimum circuit amps (MCA) and max
imum overcurrent protection amps (MOCP) as specified on the unit nameplate. Be sure that the unit is connected and grounded in accordance with all applicable electrical codes.
Optional Caster Installation — if optional casters
have been provided, bolt the 4 caster assemblies to the stor age tank. See Fig. 1-3. Size 020 and 030 storage tanks have 2 rigid casters mounted on one end of the tank and 2 swivel casters with brakes mounted on the other end of the storage tank. The size 040 storage tanks have 2 swivel casters with brakes mounted on one end of the storage tank and 2 swivel
casters with locks mounted on the other end of the storage tank.
Page 3
Table 2 — Physical Data
19QA
DRY WEIGHT OF RMS DRY WEIGHT OF RST TANK SIZE TANK STORAGE CAPACITY
CFC-11 Liquid DESIGN PRESSURE MAX. OPERATING PRESSURE CONNECTION SIZES HIGH-PRESSURE SWITCHES
Tank Heater and Pump
Cutout Manual Reset
PUMP
Motor Hp Max. Discharge Pressure Min. Vacuum (Gage) Flow Rate
60 Hz 50 Hz
RMS — Refrigerant Management System RST — Refrigerant Storage Tank
ENGLISH
Size lb 740 lb cu ft 20 30 40
lb 1600 2450 3300 psig 15 kPa 103 psig 10 kPa 69 in. Va Flare in.
psig psig
psig in. Hg 29 kPa -98 cfm
020 030
841 942
495 546 586
10 <4
% 10 kPa
10.5
8.8
040
Size kg kg
CU m .57
kg
kPa kPa
L/s
SI 020 030 336 225 248 266
727 1114
382
.85 1.13
У2 Flare
69
<28
%
69
4.96
4.16
040 428
1500
19QA - 020 - 2 74
19QA
Size
020 — 20 cu ft (.57 cu meters) 030 — 30 cu ft (.85 cu meters) 040 — 40 cu ft (1.13 cu meters)
- Refrigerant Management
System
NOTE: Accessory caster packages are avaiiabie for use with the 19QA. Refer to the following table for specific part numbers.
ACCESSORY CASTER
PACKAGE PART NUMBER
19QA 020 213 020 19QA 030 213 19QA 040 213
RMS — Refrigerant Management System RST — Refrigerant Storage Tank
Fig. 1 — Model Number Description
74 — Refrigerant Management
System
84 — Refrigerant Storage Tank
V-Ph-Hz 2 — 115-1-50/60
3 — 230-1-50/60
RMS/RST SIZE
030 040
Page 4
UNIT SIZE
19QA020
19QA030
19QA040
A B
4'-9"
[1448]
7'-3"
[2209]
Q'-Q"
[2972]
5'-4%''
[1648]
7'-10%"
[2410]
10'-4%"
[3172]
NOTE: Dimensions in [ ] are in mm.
Fig. 2 — 19QA Refrigerant Management System Dimensions
WEIGHT
EMPTY
MAXIMUM REFRIGERANT
lbs kg lbs
740 336 1600
841 382 2450
942 428 3300
CHARGE
ACCESSORY
CASTERS
kg
727 34 15
1114 48
1500
lbs kg
62 28
22
Page 5
PRESSURE GAGE
VAPOR VALVE
UNIT SIZE
19QA020
19QA030
19QA040
A
4'-9"
[1448]
7'-3"
[2209]
Q'.Q"
[2972]
B
5'-4%"
[1648]
7'-10%”
[2410]
10'-4%"
[3172]
NOTE: Dimensions in [ ] are in mm.
WEIGHT
EMPTY
lbs
495 225 1600 727
546 248 2450 1114
586 266
MAXIMUM REFRIGERANT
kg
lbs kg
3300 1500 62
CHARGE
RELIEF
-VALVE ASSEMBLY
■ LEVEL GAGE
ACCESSORY
CASTERS
lbs
34 15
48 22
kg
28
Fig. 3 — 19QA Refrigerant Storage Tank Dimensions
Page 6
NO. ITEM NO.
1 — Pressure Gage 12 — 2 — Purge Separator Assembly 3 — Refrigerant (Vapor) In 13 — 4 — Tube-in-Tube Condenser 14 — 5 — Filter Drier Vi SAE Flare (Hidden) 6 — Refrigerant (Liquid) Out 7 — Oil Separator 8 — Pump 9 — Pump Motor
10 — Heater High-Pressure 11 — Heater ON/OFF Switch (Hidden) 15 —
Cutout Switch (Hidden)
Fig. 4 — 19QA Refrigerant Management System Components
ITEM
Pump High-Pressure
Cutout Switch
Pump ON/OFF Switch Storage Area
Components Included:
Refrigerant Hose, 3 ft Refrigerant Hose, 6 ft (2)
Refrigerant Hose, 12 ft Valve With Coupler (8) Chiller Vapor Valve Liquid Indicator With Coupler Vapor Valve
NO. ITEM 16 — Refrigerant Capacity Chart
17 — Relief Valve Assembly 18 — Level Gage 19 — Liquid Valve
20 — Accessory Casters 21 — Water Separation Sight Glass
22 — Heater With Cover 23 — Storage Tank 24 — Water In 25 — Water Out
(Available On All Tank Sizes)
Table 3 — Electrical Data
Fig. 5 — Interconnecting Refrigerant Hoses,
Valves, and Fittings
VOLTS-PH-HZ 115-1-50 PUMP MOTOR
Hp 3/4 Amps 9.6 8.6 4.8 4.3 MCA
HEATER
Amps MCA 12 12 11 11
MOCP 15* 15*
MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection (Amps)
*Two circuits required for simultaneous operation. NOTE: Use time-delay fuses.
10
12 12 6
LEGEND
115-1-60 230-1-50
3/4
10
3/4 3/4
5 5
15
230-1-60
6
15
Page 7
HUiH LEVEL
SWITCH
L2
MOTOR WIRING SCHEMATIC
Ll
TOGGLE SWITCH
NOTE; The 115 and 230 v control wiring are identicai.
PRESSURE
SWITCH
HEATER WIRING SCHEMATIC
Fig. 6 — Typical Control Wiring Schematic
CONTROLS AND COMPONENTS
Pump and Motor — The pump is designed for vac
uum and pressure duty. The pump is splash lubricated and
operates in conjunction with an oil separator. It is directly coupled to and driven by a 3/4-hp motor. The coupling be tween the pump and motor has a rubber insert to compen
sate for slight misalignment. Start and stop the pump by using the toggle switch located next to the pump. A tank pressure switch set at 10 psig (69 kPa) and a tank level switch set 90% full will shut off the pump if either limit is reached. See Table 1 for additional information on the pump and motor.
Oil Separator — The oil separator removes the oil that
is mixed with the discharge gas leaving the pump. The dif ferential pressure between the oil separator and the pump crankcase returns the oil to the pump through the float valve in the oil separator when the specified oil level is achieved in the oil separator.
Heater — A 1500 watt, etched-foil, electric heater is at
tached to the bottom of the storage tank. See Fig. 2. The heater is encased in an insulated protective cover and is con trolled by a toggle switch.
Use the heater when refrigerant recycling by distillation
is necessary. When the heater toggle switch is in the ON
position, the indicating light, located next to the toggle switch, will be lit. A pressure switch will shut off the heater if the tank pressure reaches 10 psig (69 kPa) when heating refrigerant.
L2
-ORN-
-WHT
---^-------
HEATER
——
LAMP
WHT-
Tube-in-Tube Condenser — A tube-in-tube con
denser allows refrigerant vapor to be condensed when re moving vapor from a chiller or when distilling refrigerant. Garden hose connections (3/4 in.) are provided for condens ing water. Condensing water temperature should be as low as possible to minimize the time required to complete an
operation. A water flow rate of 2 gpm (.012 L/s) at 70 F
(21 C) is normally adequate.
Level Gage — A geared, float level gage displays the
storage tank’s percentage of full capacity of liquid refrig erant. The actual level of refrigerant will vary based upon temperature and the type of refrigerant used. See Fig. 4 and 7.
Water Separation Sight Glass — A water separa
tion sight glass is located above the liquid valve. Use the water separation sight glass to view the refrigerant/water interface when separating water from the refrigerant. See
Fig. 4.
Purge Separator Assembly — Use the manual hand
valve on the purge separator assembly to remove noncon densable gases that may accumulate in the storage tank dur ing vapor recovery. The purge separator assembly contains a water coil, 1/16-in. orifice, and 1/2-in. ball valve. The bottom of the purge separator assembly opens into the stor age tank. See Fig. 8.
Page 8
CFC-11 or HCFC-123
CFC-113
Ib(Kg)
This graph is based on 70 F The following multipliers may be used to more accurately determine weights at temperatures other than 70 F
TEMPERATURE F (C)
MULTIPLIER
40 (4.4)
1 026
50 (10) 60 (15 5)
1 018
1 009 1 000
70 (21,1)
80 (26.6) 90 (32 2) 100 (37 7)
991 982
973
Fig. 7 — Storage Tank Capacity
Refrigerant Hoses — Four, l/2-in. refrigerant hoses
and 8 ball valves with couplers are factory supplied with the RMS unit. See Table 1. The refrigerant hoses are used
to transfer liquid and vapor through the Refrigerant Man agement System. They are designed to withstand high vac uum pressure without collapsing.
When used with the refrigerant hoses, the ball valve and coupler assembly prevent refrigerant loss. Connect the ball valve and coupler assembly to each end of the 4 refrigerant hoses. Hand tighten the ball valve and coupler assembly to
the refrigerant hose. The ball valve and coupler assembly connect to the RMS unit or chiller, depending upon the type of operation. The coupler should be hand tightened to the RMS unit or chiller. Excessive tightening will damage the rubber gaskets.
Liquid Indicator — The 1/2 in. liquid indicator (in line
sight glass) is factory supplied. Use the liquid indicator dur ing either the liquid refrigerant transfer or the vapor con densing process to determine the end point of the process. When liquid is no longer visible in the glass, the process is almost complete.
Filter Drier — The filter drier should be used to recycle
refrigerant. Use the factory supplied filter drier when re moving moisture and small particles from the refrigerant. The filter drier is most effective when used with liquid re frigerant. The filter drier holds approximately .39 oz (11 g) of water. See Table 4.
When cleaning large quantities of saturated refrigerant,
use a field supplied, replaceable core filter drier assembly. The assembly should have four, 100 in.^ cores. It will re move approximately 4.2 oz (118 g) of water.
WATER OUT
WATER IN
NOTE: [ ] indicates millimeters
Fig. 8 — Purge Separator Assembly
Table 4 — Water Solubility In Refrigerant
SOLUBILITY
REFRIGERANT
TYPE
CFC-11,
CFC-113,
[HCFC-123]
LEGEND
ppm — Parts Per Million
TEMPERATURE
60 F 70 32
(16 C) [660]
70 F
(21 C) [770]
80 F
(27 C) [900]
90 F 140 64
(32 C) [1000]
OF WATER IN
REFRIGERANT
(ppm)
90
113 51 1 80
NOTE: [ ] indicates HCFC-123 refrigerant
GRAMS OF
WATER
PER
1000 LB
[303] [10.7]
41
[349] [12.3]
[408]
[453] [16 0]
OZ
1.13
1.15
[14.4]
2.26
Page 9
OPERATION
Evacuation — To minimize refrigerant loss, air must
not be allowed to mix with the refrigerant vapor. All spaces that could contain refrigerant (such as chillers, storage tanks,
and refrigerant hoses) must be completely evacuated before
charging the RMS with refrigerant.
To evacuate air from the storage tank or chiller, connect the suction service valve of the pump to a vapor valve on the storage tank or chiller using the shortest possible 1/2-in. diameter refrigerant hose. Use of hoses or fittings smaller than 1/2 in. diameter will greatly increase the time required to pull a complete vacuum of 29 in. Hg (25 mm Hg abso lute). Refer to Table 5 for additional information. See Fig. 9.
Once the connections are made, turn on the pump and discharge the air into the atmosphere.
■ — Tank Size — 20 cu ft (.57 cu meters)
NOTE: A 29 in. Hg vacuum (25 mm Hg absolute) may be obtained at a rate of approximateiy 1 minute per cu ft of volume.
Typical 400 Ton Chiller
Fig. 9 — Evacuation of Chiller and Storage Tank
Liquid Refrigerant Transfer

A CAUTION

To prevent release of refrigerant from the dual relief valve assembly due to expansion, the storage tank must not be filled above 90% full at 90 F (32 C).
The storage tank is 90% full when the level gage is read
ing 100%. See Fig. 7.
BEFORE TRANSFERRING LIQUID REFRIGERANT ­Before using the pump for liquid or vapor transfer, run the pump using air only for approximately 15 minutes. Run ning the pump on air will allow it to achieve a normal op erating temperature of 120 F (49 C). If refrigerant is used when the pump is cold, excessive amounts of refrigerant will be absorbed into the oil, causing dilution of the oil. This condition may cause oil loss and shorten the life of the pump.

A WARNING

Do not connect the pump suction service valve directly to a liquid refrigerant source. Liquid refrigerant will cause damage to the pump.
Use the same process when transferring liquid refrigerant from the chiller to the storage tank or from the storage tank to the chiller. Completely evacuate any vessel that will have refrigerant transferred to it.

A WARNING

Do not transfer liquid refrigerant into an evacuated chiller that contains water in the cooler tubes. Freezing water will cause the cooler tubes to rupture.
NOTE: Make sure the ball valve and coupler assembly are connected to all refrigerant hoses.
Prior to transferring liquid refrigerant from the storage vessel to the chiller, make sure all water is completely drained from the cooler tubes or raise the chiller pressure by using refrigerant gas (24 in. Hg [ — 81 kPa] for CFC-113,
18 in. Hg [-61 kPa] for HCFC-123, and 15 in. Hg
[-51 kPa] for CFC-11).
TO TRANSFER LIQUID REFRIGERANT Storage Tank to Chiller — To transfer liquid refrigerant from
the storage tank to the chiller, connect a 6-ft refrigerant hose from the liquid valve on the storage tank to the chiller charg ing valve. Install the liquid indicator on the refrigerant hose. See Fig. 10. Connect a 12-ft refrigerant hose to the vapor service valve on the chiller and the suction service valve on the pump. Copper tubing is factory installed from the pump to the oil separator. Connect another 6-ft refrigerant hose from the discharge connection on the oil separator to the
vapor valve on the storage tank. Open the liquid valve on the storage tank, the charging valve on the chiller, and the two interconnecting hose valves.
Once liquid refrigerant enters the chiller, open the chiller vapor valve, the storage tank vapor valve, all valves be tween the chiller vapor valve and the storage tank vapor valve. Turn on the pump. The pump will remove refriger ant gas from the chiller and discharge it into the storage tank. This will create a pressure differential between the
chiller and the storage tank and provide the specified flow rate.
The end of the liquid refrigerant transfer can be deter
mined by observing the liquid indicator. When liquid is no longer visible, the transfer is complete. Close the liquid valve on the chiller and turn off the pump.
Chiller to Storage Tank — To transfer liquid refrigerant from the chiller to the storage tank, connect a 6-ft refrigerant hose from the storage tank liquid valve to the chiller charging valve. Install the liquid indicator to determine when liquid transfer is complete. Connect a 12-ft refrigerant hose to the
vapor service valve on the chiller and the suction service valve on the pump. Copper tubing is factory installed from the pump to the oil separator. Connect another 6-ft refrig erant hose from the discharge connection on the oil sepa rator to the vapor valve on the chiller. Open the charging valve on the chiller, the liquid valve on the storage tank, and the two interconnecting hose valves.
Once liquid refrigerant enters the storage tank, open the storage tank vapor valve, chiller vapor valve, and all valves between the storage tank vapor valve and chiller vapor valve.
Turn on the pump. The pump will remove refrigerant gas from the storage tank and discharge it into the chiller. This will create a pressure differential between the storage tank and provide the specified flow rate.
The end of the liquid refrigerant transfer can be deter
mined by observing the liquid indicator. When liquid is no longer visible, the transfer is complete. Close the bottom valve on the chiller and turn off the pump.
Page 10
Refrigerant Vapor Transfer

A WARNING

If the required vacuum level cannot be reached due to the presence of a large leak in the chiller, the vapor
recovery process should be stopped. The constant in filtration of air into the chiller may contaminate the refrigerant.
Refrigerant vapor recovery is required after the liquid re
frigerant has been removed. Most refrigerant vapor can be recovered by evacuating the chiller or storage tank and con densing the vapor. The United States EPA requires the evac uation level for low pressure chillers to be 29 in. Hg (25 mm Hg absolute). Refer to Table 5 for additional information.
Before using the pump for vapor recovery, make sure it
is at the correct operating temperature of 120 F (49 C). This can be achieved by running the pump on air only for ap proximately 15 minutes. If the pump is operating below op
erating temperature with refrigerant, excessive amounts of refrigerant will be absorbed into the oil, causing dilution of the oil. This condition may cause reduced vacuum capabil ity and may shorten the life of the pump.
NOTE: If oil dilution is affecting the pump’s ability to achieve 29 in. Hg (25 mm Hg absolute), an oil change may be re quired. See the Maintenance section on page 15.
BEFORE TRANSFERRING REFRIGERANT VAPOR ­When transferring refrigerant vapor from a chiller to a stor age tank, connect the 12-ft refrigerant hose from the vapor
valve on the chiller to the suction service valve on the pump. See Fig. 11. Copper tubing is factory installed from the pump to the oil separator. Connect a 6-ft refrigerant hose from the discharge connection of the oil separator to the in let of the tube-in-tube condenser. See Fig. 4 for location. Connect another 6-ft refrigerant hose from the refrigerant outlet of the tube-in-tube condenser to the vapor valve on the storage tank. See Fig. 4. Close the bottom valve on the chiller and turn off the pump. The tube-ln-tube condenser must be evacuated before starting this process.
The tube-in-tube condenser must be evacuated. Make sure all refrigerant hose valves are closed. Remove the refriger ant hose end connected to the pump suction service valve.
Remove the refrigerant hose end connected to the top valve on the storage tank and connect it to the pump suction serv ice valve. Close the pump discharge service valve and re move the 1/4-in. cap on top of the pump discharge service valve. Open all valves between the suction and discharge service valves of the pump. Turn on the pump for about 5 seconds to evacuate the tube-in-tube condenser. The air will be discharged through the 1/4 in. discharge port on the pump discharge service valve. Once the evacuation is com plete, reconnect the refrigerant hoses to their original con nections. Replace the 1/4-in. cap on the pump discharge service valve. Open the pump discharge service valve.
Connect a water hose to the water inlet connection (lo cated on the bottom of the tube-in-tube condenser) and the other water hose to the water outlet connection (located on top of the tube-in-tube condenser). A water flow rate of ap proximately 2 gpm (.012 L/s) is required at 70 F (21 C).
Refrigerant Hose Direct Coupled Connection Factory-Installed Copper Tubing
Fig. 10 — Liquid Refrigerant Transfer
(From Storage Tank to Chiller)
10
Page 11
WATER CONNECTIONS
DISCHARGE
Refrigerant Hose Water Hose Direct Coupled Connection Factory-Installed Copper Tubing
Fig. 11 — Refrigerant Vapor Transfer/Evacuation Connections
TO TRANSFER REFRIGERANT - Open all valves be tween the chiller and storage tank. Turn on the water to the tube-in-tube condenser. Turn on the pump. After a few min utes, the condensed vapor will be seen in its liquid form flowing through the liquid indicator to the storage tank. The end of the vapor transfer can be determined by observing the liquid indicator. When liquid is no longer visible, the transfer is complete.

A CAUTION

Be sure to run the chiller water pumps when removing refrigerant vapor. Trapped liquid may boil and can cause tube freeze-up.
The vapor recovery process is complete when the vac uum in the chiller has reached 29 in. Hg (25 mm Hg). Be fore turning off the pump, shut off the water to the tube­in-tube condenser and then drain the water from the condenser.
As the condenser warms up, it will help drain any liquid remaining in the condenser and refrigerant hose into the stor age tank. Turn off the pump. Close the valves to the stor age tank and chiller. Disconnect the refrigerant hoses. Any refrigerant vapor remaining in the refrigerant hoses and the tube-in-tube condenser are considered to be de minimis. See Fig. 12.
Use the same process when transferring vapor refrigerant
from the storage tank to the chiller.
10
20 30
WEIGHT (Kg OF CFC-11)
Fig. 12 — Refrigerant Vapor Remaining
in Chiller After Removal
of Liquid Refrigerant (400 Ton Unit)
40
11
Page 12
Purge Separator Assembly — A purge separator
assembly is used to remove noncondensable gases that may be mixed with the refrigerant being recovered. See Fig. 4.
If vapor is being recovered from a leaking chiller, air will enter the machine. The air will mix with the refrigerant gas and collect in the storage tank. The air will raise the pres sure of the storage tank until the pressure reaches 10 psig (69 kPa). At this point, the high pressure cutout switch will turn off the pump. To avoid this situation, a purge separa tor assembly is factory installed. See Fig. 8.
During the vapor recovery process, the pressure in the storage tank should not be higher than the corresponding pressure/temperature relationship for a given refrigerant, based on ambient conditions. If the room temperature is approx imately 75 F (24 C) and CFC-11 is being recovered, the pressure in the storage tank should be approximately 0 psig (0 kPag). If the pressure is higher than 0 psig (0 kPag), a noncondensable gas is present in the storage tank. See
Table 5.
A pressure gage is mounted on top of the purge separator assembly. When the pressure reaches 8 psig (55 kPag) and the pressure/temperature relationship shows this as exces sive, the purge valve on top of the purge separator assem bly should be opened to remove the noncondensable gas. See Fig. 4. Based on the ambient temperature, the purge separator assembly should be operated until the saturated pressure is achieved. If the ambient temperature is 75 F (24 C), the purge valve should be opened until the storage tank pressure reaches 0 psig (0 kPa).
Oil Separation — The refrigerant management system
separates oil from refrigerant through distillation. The re frigerant can be transferred from the chiller to the storage tank and then distilled back to the chiller or another storage tank.
Connect the 3-ft refrigerant hose from the storage tank vapor valve to the pump suction service valve. See Fig. 13. Copper tubing is factory installed from the pump to the oil separator. Connect the 6-ft refrigerant hose from the oil sep arator discharge connection to the top connection on the tube-in-tube condenser. Connect the 12-ft refrigerant hose with the liquid indicator to the refrigerant outlet connection on the condenser and to the chiller charging valve or an other storage tank. Provide water at approximately 2 gpm (.012 L/s) and a maximum temperature of 70 F (21 C) to the tube-in-tube condenser using suitable water hoses. Turn on the pump and heater using the toggle switches provided. If the distilled refrigerant is being returned to the chiller,
run cool water through the evaporator heat exchanger. Ap proximately 1.2 lb per minute (.54 kg per minute) of CFC-11 can be distilled per hour. When liquid refrigerant is no longer seen in the liquid indicator, the distillation process is complete.
After the distillation process is complete, the oil remain ing in the bottom of the storage tank should be drained us ing the liquid valve on the storage tank. After the oil is drained, the tank can be wiped clean by opening the access cover located on the opposite end of the level gage.
WATER CONNECTIONS
Refrigerant Hose
Water Hose Direct Coupled Connection Factory-lnstailed Copper Tubing
Fig. 13 — Oil Separation Connections
12
Page 13
Water Separation — Water is only slightly soluble in
refrigerant. See Table 4. If additional water is present, it will float on top of the refrigerant and can be easily re moved by the RMS unit.
Transfer the water contaminated refrigerant to the stor age tank using the procedures described in the Liquid Re frigerant Transfer section. If the refrigerant contamination was caused by a chiller failure, the chiller must be repaired,
dehydrated, and vacuum broken with refrigerant. Use
24 in. Hg (-81 kPa) for CFC-113, 18 in. Hg (-61 kPa)
for HCFC-123, and 15 in. Hg (-51 kPa) for CFC-H to avoid freezing the tubes in chiller before the cleaned liquid refrigerant can be returned to the chiller. If the chiller is not repaired, the clean refrigerant should be transferred to an other clean tank.
Connect the 12-ft refrigerant hose from the chiller or clean storage tank vapor valve to the suction service valve on the pump. See Fig. 14. Copper tubing is factory installed from the pump to the oil separator. Connect a 6-ft refrigerant hose from the discharge connection of the oil separator to
the vapor valve on the storage tank. Connect the 3-ft refrig erant hose and liquid level indicator from the liquid valve of the storage tank to the filter drier canister. See Fig. 5. Connect the remaining 6-ft refrigerant hose from the filter drier canister to the chiller charging valve or the liquid valve, if using a storage tank. Open all valves between the storage tank and the chiller. Turn on the pump.
While the liquid refrigerant is being transferred into the chiller or another storage tank, use the water separation glass at the bottom of the tank to determine when the water/
refrigerant level is close to the liquid valve. See Fig. 4. Re duce the liquid flow rate as the water level approaches the liquid valve. Close the liquid valve when the water/ refrigerant level is at the bottom of the water separation glass to prevent water from entering the other storage tank.
To prevent the loss of remaining refrigerant, transfer the water/refrigerant mixture into an open container. Skim the water off the top of the refrigerant. Transfer the remaining refrigerant into the storage tank.
Refrigerant Hose Direct Coupled Connection Factory-Installed Copper Tubing
FILTER DRIER
Fig. 14 — Water Separation
13
Page 14
Table 5 — Vapor Pressure
TEMPERATURE
°F
-20
-15
-10
-5
0
5 10 15 20 25
30 35 40 45 50
55 60 65 70 75
80 85 90 95
100 105
110 115 120 125
130 135 140 145 150
NOTE: Italics indicates in. Hg vacuum.
°c
-28.9
-26.1
-23.3
-20.6
-17.8
-15.0
-12.2 23.0
-9.4
-6.7 21.0
-3.9
-1.1
-1.7
10.0
12.8
15.6
18.3
21.1
23.9
26.7
29.4
32.2
35.0
37.8
40.6
43.3
46.1
48.9
51.7
54.4
57.2
60.0
62.8
65.6
Psi
Gage
26.9
26.5
25.9
25.3
24.6
23.9
22.1 3.8
19.8
18.5
17.1
15.6
4.4
13.8 7.9
7.2
12.0
9.9
7.7 10.9
5.3
2.7
0.1
1.6
3.2
4.9
6.8
8.8
10.9
13.2 27.9 91.0
15.7 30.3 108.3
18.3
21.1
24.0
27.1
30.5 45.1 210.3
34.0
37.7
Psi kPa
Absolute Gage
1.4
1.7 -89.7 11.7
1.9
2.2 -85.7 15.2
2.6
2.9 -80.9^ 19.9
3.4 -77.9
4.3
4.9
5.6 -62.6 38.6
6.3 -57.9
7.0 -52.8 48.3
8.8
9.8 -33.5 67.6
12.0 -17.9
13.4 -9.1
14.7
16.2
17.9
19.6 33.8
21.5
23.5 60.7 162.0
25.6 75.2
32.9 126.2
35.7
38.7 165.5
41.8
48.6
52.7
CFC-11
145.5
186.9
234.4 335.1
259.9
kPa
Absolute Gage
-91.1
-87.7 13.1
-83.3 17.9
-74.8 26.2
-71.1 29.6
-67.0 33.8
-46.7 54.5
-40.6
-26.1
.6
11.0
22.1 123.4
46.9
9.7
23.4 27.5
43.4
60.7 22.9
75.2 20.9
82.7 19.8
92.4 18.6
101.4
111.7
135.1
148.2 10.5
176.5
192.4 3.8
208.9
226.8
246.2 2.2
266.8 3.8
288.2 5.5
310.9
363.4
CFC-113
Psi
29.0
28.8
28.6
28.4
28.1 08 -95.1
27.9
27.1
26.7
26.3 1.8 -89.1
25.7 2.0
25.1 2.4
24.4 2.7
23.7
21.9
17.2 6.2 -58.2
15.8 6.9
14.2
12.2 8.5
8.5
6.3
1.2
0.8
7.3
9.2 23.9
11.2 25.9
Psi
Absolute Gage
0.4
0.5
0.6 07 -96.2
0.9
1.1
1.3
1.5
3.1 -80.2
3.4
3.9
4.4
5.0
5.5
7.7
9.5
10.5
12.2 -21.3
13.8 -12.9
14.6
15.4 5.5
16.6
18.5 26.2
20.2
21.9 50.3
kPa
-98.2 2.8
-97.5
-96.8 4.1
-94.5
-93.1
-91.8 8.9
-90.4 10.3
-87.0 13.8
-85.0 16.5
-82.6 18.6
-77.6 23.4
-74.2 26.9
-70.8 30.3
-67.0 34.5
-62.9 37.9
-53.5
-48.1
-41.9
-35.6
-28.8
-4.1
15.2 114.5
37.9
63.4 164.8
77.2
kPa
Absolute
3.4 27.3
4.8
5.5
6.2
7.6
12.4
21.4 16.5
42.7 4.0
47.6
53.1
58.6
65.5
72.4
84.1 8.1
95.2 10.3
100.7
106.2 15.1
127.6
139.3
151.0
178.6
HCFC-123
Psi Psi kPa
Absolute Gage Absolute
Gage
27.6
26.8
26.3
25.8
25.1 2.3
24.4
23.3
22.7 3.5
21.7
20.6 4.5
19.4
18.0 5.8
14.9
13.0
11.0
8.9
6.6
1.2
0.9
2.5
4.2
6.1
12.6
17.7
20.6
23.4
26.8
30.2 45.0 208.2
33.8
1.1 -93.5 7.6
1.3
1.5
1.8
2.0
2.6 -82.6 17.9
3.1
4.0
5.2 -65.7 35.9
6.6
7.3
8.3
9.2 -37.2
10.3
11.4
12.8
14.1 -4.1
15.7 6.2 108.3
17.2 17.2
19.0 28.9
20.8 42.1
23.0
25.0
27.4
29.8
32.6 122.2
35.3 142.0
38.4
41.5 184.8
48.5 233.1
-92.4 9.0
-90.7 10.3
-89.1
-87.4 13.8
-84.9 15.9
-80.0 21.4
-76.8
-73.4 27.6
-69.8 31.0
-60.9 39.9
-55.9 45.5
-50.5 50.3
-44.0 57.2
-30.1
-22.3 78.6
-13.5 88.3
55.8
71.0
86.9
104.1
161.3
kPa
12.4
24.1
63.4
71.0
97.2
118.6
131.0
143.4
158.6
172.4
188.9
205.5
224.8
243.4
264.8
286.2
310.3
334.4
14
Page 15
MAINTENANCE
Periodic maintenance is necessary to keep all compo nents functioning as designed. A maintenance log is rec ommended to ensure a proper maintenance schedule is followed.
Maintaining the Pump — Clean lubricating oil is es
sential to maintaining the required vacuum capabilities. If the oil is diluted with refrigerant, it will not be able to ob tain a 29 in. Hg (25 mm Hg absolute) rating. Refer to
Table 5 for additional information.
Change the oil in the pump and separator before each
use. Both the pump and the oil separator use 16 oz. of
300 SSU oil at 100 F (38 C). The pump and oil separator have drain ports for oil removal. The drain port for the oil separator is located on top of the separator. The drain port for the pump is located on the bottom of the pump. Drain the oil from the separator by using the pump to pressurize the oil separator with air.
Install a 3-ft refrigerant hose on the discharge connection of the oil separator and close the refrigerant hose valves. Open the pump’s suction and discharge service valves. Turn the pump on and let it run until it shuts down due to the high pressure cutout at 10 psig (69 kPa). Use this pressure to drain the oil from the separator. When this is complete, drain the oil from the pump. Use the oil drain fittings and a hand pump to add new oil to the pump and separator.
Check pump’s vacuum capability once per year. Place a test gage capable of reading 29 in. Hg (25 mm Hg) on the suction service valve. Open the pump suction and dis
charge service valves. Start the pump and measure the vac
uum. If the pump does not achieve the proper vacuum, a
new valve plate assembly should be installed. Installation instructions are provided with the new valve plate assembly from the manufacturer.
secured on a tapered shaft with a key and lock nut. The mo
tor half of the coupling is secured on a straight shaft with a key and set screw. The rubber insert, found between each coupling half, should be inspected for damage and replaced as needed. Remove the coupling guard and pump to access the pump coupling. Leave the base brackets in place.
High-Pressure Cutout Switches — Check the pres
sure cutout setting for the pump and heater pressure switches once per year. Each switch should shut the pump off at
10 psig (69 kPa). To check the pump and heater switches, disconnect the capillary tube and use a regulated pressure source. Verify with an ohmmeter that the switch opened at
10 psig (69 kPa).
Refrigerant Storage Tank — The refrigerant stor
age tank contains a cleanout cover. Remove the cover to clean the tank when required. Use a clean cloth to wipe the inside of the tank. Reinstall cleanout cover.
Refrigerant Hoses — Each refrigerant hose has a fac
tory supplied, field installed ball valve and coupler assem bly at each end. These couplers contain a rubber seat that
must be replaced periodically. Inspect the rubber seats be fore each use. Replace the seats if they appear to be dam aged. See Fig. 15.
Periodically check refrigerant hoses for cuts or abrasions
that may allow refrigerant to leak into the atmosphere.
Pump Coupling — The aluminum, self-aligning cou
pling should be inspected for wear at least once a year or as required based on usage. The pump half of the coupling is
SIDE VIEW END VIEW
Fig. 15 — Refrigerant Hose Seats
15
Page 16

TROUBLESHOOTING

SYMPTOM
Unit hums and vibrates
excessiveiy.
Pump does not puli a 29 in. Hg vacuum (25 mm Hg absolute).
Unit is plugged into electri cal outlet but does not start.
Unit shuts off on the high pressure switch.
Motor draws high amps at start-up.
Compressor is damaged at start-up.
Storage tank relief valve is relieving refrigerant gas.
Liquid and vapor recovery rates are slower than
specified.
Purge unit is constantly
open to remove noncon densable gas from the stor age tank.
PROBABLE CAUSE
Motor/pump assembly out of alignment. Motor/pump assembly holddown bolts are
loose.
Pump and oil separator oil is diluted with refrigerant.
Valves and valve plates are worn. The ON/OFF switch, high-pressure switch,
motor thermal overload and/or motor wind ing are faulty.
Unit is plugged into a nonoperational
outlet. All valves on the discharge side of the
pump are not open.
Cutout setting on the switches is incorrect.
Inadequate water flow through the
condenser. Noncondensable gas has accumulated in
the storage tank. Pump oil is very cold. Warm up pump by running it with the suction and discharge
Liquid refrigerant entered the suction valve. Check pump for internal damage.
Storage tank contains excessive noncon densable gas.
Storage tank is placed in a hot room (above 115 F [46 C]).
Vapor valve connection on the chiller is smaller than V2 inches in diameter.
There is a restriction in the refrigerant hose system.
Chiller probably has a severe leak.
Check alignment and adjust if necessary. Check hoiddown bolts and tighten as necessary.
Change oil in pump and oil separator as specified in mainte nance section on page 15.
Replace valves and valve plates in pump.
Test all components for proper operation and replace as needed.
Try another outlet and test for presence of voltage.
Open ail valves on the discharge side of the pump.
Adjust switch as necessary.
Increase water flow or use a colder water source.
Purge noncondensable gases from storage tank.
service valves open to the atmosphere.
Bleed noncondensable gases from storage tank.
Move storage tank to a cooler room.
Install a V2 in. vapor valve on the chiller.
Check all refrigerant hose valves and verify that they are open.
Stop the recovery process.
REMEDY
Copyright 1994 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigations.
Book|2 |2 PC 221 Cataiog No 531-963 Printed in U S A. Form 19QA-2SI Pg 16 9-94 Replaces: 19QA-1 SI Tab 5a 5d
Loading...