SPECIFICATION SHEET
SINGLE DUCT AIR TERMINAL - w/HOT WATER REHEAT
PRESSURE DEPENDENT ELECTRIC CONTROLS
ER — CONTROL OPTION (ONE-STAGE)
24 VAC
CARNES COMPANY 448 S. Main St., P. O. Box 930040, Verona, WI 53593-0040 Phone: (608)845-6411 Fax: (608)845-6470 www.carnes.com
24V
COMMON
CONTROL DIAGRAM
SEQUENCE OF OPERATION
ON A CALL FOR COOLING, AIRFLOW WILL INCREASE AS THE DAMPER OPENS TOWARDS THE MAXIMUM SETTING TO SATISFY ROOM SET-POINT (SP).
ON A CALL FOR LESS COOLING, AIRFLOW WILL DECREASE AS THE DAMPER CLOSES TOWARDS THE MINIMUM SETTING TO SATISFY ROOM SET-POINT (SP).
AS THE DAMPER CLOSES, FIELD ADJUSTABLE CAMS WILL ACTIVATE END SWITCHES WHICH WILL ENERGIZE UP TO TWO STAGES OF REHEAT SEQUENCING.
THE “ER” OPTION HAS ONE END OF SWITCH TO ACTIVATE STAGE ONE (H1).
THE “EK” OPTION HAS TWO END SWITCHES, ONE FOR EACH STAGE ONE (H1) AND STAGE TWO (H2).
THE MAXIMUM AND MINIMUM SETTINGS ARE DETERMINED BY FIELD ADJUSTED MECHANICAL STOPS.
TERMINALS R & Y MAKE ON TEMP RISE TERMINALS R & W MAKE ON TEMP DROP
2
(HORIZONTAL MOUNT)
1
FOR MODELS AB (BYPASS) WITH LEFT HAND CONTROLS (ER2C, EK2C), “W” GOES TO THE “YELLOW” WIRE, “Y” GOES TO THE “BLUE” WIRE.
* *
ITEM PART NO. DESCRIPTION
1 AXBAB ACTUATOR (ONE END SWITCH) 1 AXBAC ACTUATOR (TWO END SWITCH) 2 AXWBE ELECTRIC THERMOSTAT
By Carnes By Others Optional
*
COPYRIGHT © 2009 CARNES COMPANY
ALL RIGHTS RESERVED
SUPERSEDES 20104-E
20104-F, Page 2
A2
A1
SPECIFICATION SHEET
SINGLE DUCT AIR TERMINAL - w/ELECTRIC REHEAT
PRESSURE DEPENDENT ELECTRIC CONTROLS
ER — CONTROL OPTION (ONE-STAGE)
CARNES COMPANY 448 S. Main St., P. O. Box 930040, Verona, WI 53593-0040 Phone: (608)845-6411 Fax: (608)845-6470 www.carnes.com
By Carnes By Others Optional
CONTROL DIAGRAM
SEQUENCE OF OPERATION
ON A CALL FOR COOLING, AIRFLOW WILL INCREASE AS THE DAMPER OPENS TOWARDS THE MAXIMUM SETTING TO SATISFY ROOM SET-POINT (SP).
ON A CALL FOR LESS COOLING, AIRFLOW WILL DECREASE AS THE DAMPER CLOSES TOWARDS THE MINIMUM SETTING TO SATISFY ROOM SET-POINT (SP).
AS THE DAMPER CLOSES, FIELD ADJUSTABLE CAMS WILL ACTIVATE END SWITCHES WHICH WILL ENERGIZE UP TO TWO STAGES OF ELECTRIC HEAT.
THE “ER” OPTION HAS ONE END OF SWITCH TO ACTIVATE STAGE ONE (H1).
THE “EK” OPTION HAS TWO END SWITCHES, ONE FOR EACH STAGE ONE (H1) AND STAGE TWO (H2).
THE MAXIMUM AND MINIMUM SETTINGS ARE DETERMINED BY FIELD ADJUSTED MECHANICAL STOPS.
TERMINALS R & Y MAKE ON TEMP RISE TERMINALS R & W MAKE ON TEMP DROP
2
(HORIZONTAL MOUNT)
1
FOR MODELS AB (BYPASS) WITH LEFT HAND CONTROLS (ER2C, EK2C), “W” GOES TO THE “YELLOW” WIRE, “Y” GOES TO THE “BLUE” WIRE.
* *
ITEM PART NO. DESCRIPTION
1 AXBAB ACTUATOR (ONE END SWITCH) 1 AXBAC ACTUATOR (TWO END SWITCH) 2 AXWBE ELECTRIC THERMOSTAT
*