Imperial [IP] Dimensions
Metric (SI) in Parentheses
SPECIFICATION SHEET
MODEL ACWH UNDERFLOOR
CONSTANT VOL. FAN TERMINALS W/ HOT WATER REHEAT
PSC FAN SIZES A-F
CARNES COMPANY, 448 S. Main St., P. O. Box 930040, Verona, WI 53593-0040 Phone (608) 845.6411 Fax: (608 ) 845.6470 carnes@carnes.com www.carnes.com
CARNES COMPANY © 2006 COPYRIGHT
ALL RIGHTS RESERVED
SUPERSEDES 20011-A 20011-B
DIMENSIONS LISTED IN INCHES (Millimeters)
Secondary Outlet Inlet
Unit Fan Inlet Primary CFM (L/s) @ Fan C C E E
Size Size Size CFM (L/s) .25 E.S.P. H.P. A B 1-Row 2-Row D 1-Row 2-Row G H J K L M
U1
A 05
350 290
1/6
4-7/8
(165) (137) (124)
U2 B 06
500 420
1/6
5-7/8
(236) (198) 12 10 56-1/2 58 (149) 46-1/8 47-1/2 27 19-1/4 16 10-1/2 1/2 1/2
U3 C 07
700 680
1/6
(305) (254) (1435) (1473) 6-7/8 (1172) (1207) (685) (489) (406) (267) (13) (13)
(330) (321) (175)
U4
D 08
1000 1000
1/4
7-7/8 1/2
(472) (472) (200) (13)
U5 E 10
1500 1525
1/2
14 12-1/2 56-1/2 58 9-7/8 46-1/8 47-1/2 27 19-1/4 17 12-1/2
- - - -
(708) (720) (356) (318) (1435) (1473) (251) (1172) (1207) (685) (489) (432) (318)
SECONDARY
AIR FLOW
ACCESS
OPENING
J H
D
INLET
6” (152)
B
OUTLET
18”
(457)
10-1/2”
(267)
11-1/2”
(292)
C
E
G
L
M
A
12”
(305)
K
NOTE: Outlet is designed for slip and drive duct connection.
PRIMARY
AIR FLOW
FILTER CLIP
FILTER RACK
INSULATED
INLET COLLAR
PRIMARY
AIR FLOW
RIGHT HAND ONLY
OUTLET
10-1/2”(267)