FORM 18647-M, Page 3
DUCT CONNECTIONS
1. Units are provided with slip and drive discharge duct
connections.
2. It is suggested that discharge ductwork be lined with
a minimum of 1/2” thick, 1-1/2 lb. density fiberglass
insulation with an erosion resistant surface in
accordance with NFPA 90A (non-residential type air
conditioning and ventilating systems) to provide both
thermal and acoustical insulation.
3. Attenuators are field mounted with slip and drive cleats
provided by others.
4. Sealing of duct work to preclude air leaks should be
done in accordance with the job specifications.
5. It is recommended that flexible ductwork connected to
the inlet be secured using compression band. Rigid
duct should be slipped over the inlet, secured in place
with sheet metal screws, and sealed in accordance
with the job specifications.
BALANCING THE MODELS ABB and ABW
BY-PASS TERMINAL UNITS
I. SYSTEM BALANCING
Prior to setting design flow conditions at each unit the bypass slide dampers must be balanced against downstream
duct resistance.
1. Adjust all thermostats for full cooling so that there is a
maximum air flow to the zone.
2. Using the two air flow pressure taps at each unit, green
(high pressure) and yellow (low pressure), read and
record the air flow pressure to the zone (this value may
be in excess of design flow requirements).
3. After this reading has been taken, adjust the
thermostat for full heat (full by-pass position).
4. When unit is in full by-pass position, adjust the by-pass
slide damper so that the pressure reading is the same
as it was for full cooling to the zone.
5. Continue this procedure at each ABB and ABW unit.
II. SYSTEM DESIGN FLOWS
Once the by-pass slide dampers have been balanced, then
the zone design flow conditions can be set.
1. Again, adjust zone thermostats to full cool (maximum
air flow to the zone).
2. Adjust actuator to the maximum CFM as measured at
the diffusers.
3. Adjust zone thermostat to full heat (minimum air flow to
zone).
4. Adjust actuator to the minimum CFM as measured at
the diffusers.
5. Continue this procedure at each ABB and ABW unit.
HOT WATER COIL
FIELD or FACTORY
MOUNTED
BASIC UNIT
BASIC UNIT
(Model ABB)
HOT WATER COIL TUBING CONNECTIONS
ARE LOCATED ON CONTROL SIDE OF
TERMINAL UNIT
SINGLE DUCT
DUAL DUCT
BY-PASS
BASIC UNIT
(Model ADC)
ATTENUATOR, RECTANGULAR
DUCT (All Field Mounted)
HOT WATER COIL,
FACTORY MOUNTED
(Model ABW)
6” MINIMUM VERTICAL
CLEARANCE
ATTENUATOR
RECTANGULAR DUCT
(All Field Mounted)
SINGLE DUCT WITH ELECTRIC REHEAT
ATTENUATOR,
RECTANGULAR
DUCT (All Field
Mounted)
ATTENUATOR,
RECTANGULAR
DUCT (All Field Mounted)
BASIC UNIT
ELECTRIC HEATER CONTROL
PANEL IS LOCATED ON CONTROL
SIDE OF TERMINAL UNIT