Carnes ABBD Installation Manual

COPYRIGHT © 2010
SUPERSEDES 18647-L 18647- M, Page 1
All Rights Reserved
Models AVCD, AVWE, AVED, ABBD, ABWD,
ADCC and ADCD
READ AND SAVE THESE INSTRUCTIONS
INSTALLATION and OPERATION MANUAL
FOR
THROTTLING UNITS
CARNES COMPANY, 448 S. Main St., P.O.Box 930040, Verona, WI 53593-0040 Phone: 608/845-6411 Fax: 608/845-6470 carnes@carnes.com www.carnes.com
FORM 18647-M, Page 2
INSPECT UNIT
UNPACKING AND INSPECTION
1. Open shipping carton or crate and check for concealed shipping damage. Report damage immediately to the carrier that delivered the unit.
2. Inspect the unit for loose or missing components.
3. Optional accessories may be packed within the unit or in the same shipping carton.
GENERAL
1. Each VAV unit and accessory is shipped with an identification label showing the Carnes order number, unit item number from the order, unit model number, maximum and minimum CFM settings on terminal units with pressure independent control options, and unit tagging (or mark).
INSTALLATION
MOUNTING
1. Units are to be supported in a horizontal and level position. For convenience, it is suggested that the units be installed prior to installation of the ceiling tile grid system.
2. Avoid abrupt transitions or duct turns at the inlet of the unit that would alter the cross-section area.
3. A minimum of three duct diameters of straight duct upstream of inlet sensor is recommended. (i.e., 6” inlet dia. = 18” or more straight upstream duct.) Figure 1
4. Close coupling the terminal unit inlet to the side of the main duct is NOT recommended. Figure 2
5. The control unit must be mounted such that the velocity sensor is at the inlet of the terminal unit, upstream of the damper blade.
6. Dual duct units may have a velocity sensor mounted downstream at the discharge opening. The dual duct unit should be mounted with the two inlets upstream of the damper blades.
7. The diameter of the inlet duct in inches must be equal to the listed inlet collar diameter of the terminal unit.
8. A minimum clearance of six inches (6”) is required at the top discharge opening (by-pass) on Models ABB and ABW.
9. All control enclosures require adequate clearance to allow for field adjustments and service.
10. Terminal units may be provided with optional hanger brackets which are suitable for supporting the terminal unit by wire hangers or threaded rods.
11. Strap hangers may be used for supporting the units when hanger brackets are not provided.
CAUTION: Do not install hangers so as to impair the
movement or performance of control components.
CAUTION: Do not install hangers with screws into
the uninsulated coil casing. Permanent coil damage may result.
CAUTION: Do not install hangers so as to impair or
restrict the movement of the slide balancing damper on By-Pass terminal units. (Models ABB & ABW).
Figure 1
Figure 2
CARNES COMPANY, VERONA, WI
ORDER ITEM
MODEL MAX. CFM/MIN. CFM MARK
STRAIGHT DUCT UPSTREAM
CLOSE COUPLING NOT RECOMMENDED
Loading...
+ 2 hidden pages