CaptiveAire PCU-2 Installation Manual

A0011036
April 2011 Rev. 15
Pollution Control Unit
Installation, Operation, and Maintenance Manual
Pollution Control Unit
Save these instructions. This document is the property of the owner of this equipment and is
required for future maintenance. Leave this document with the owner when installation or service is complete.
RECEIVING AND INSPECTION
Upon receiving unit, check for any interior and exterior damage, and if found, report it immediately to the carrier. Also check that all accessory items are accounted for and are damage free.
WARNING!!
Installation of this unit should only be performed by a qualified professional who has read and understands these instructions and is familiar with proper safety precautions. Read this manual thoroughly before installing or servicing this equipment.
2
TABLE OF CONTENTS
WARRANTY ................................................................................................................................................ 3!
LISTINGS..................................................................................................................................................... 4!
APPLICATION ............................................................................................................................................. 4!
INSTALLATION ........................................................................................................................................... 5!
Site Preparation ....................................................................................................................................... 5!
Joint Sealant ............................................................................................................................................ 5!
Sealant Features ..................................................................................................................................... 5!
Ductwork.................................................................................................................................................. 6!
Unit Drains ............................................................................................................................................... 6!
Recommended MIN Ductwork Sizes................................................................................................... 6!
Equipment Rails....................................................................................................................................... 7!
Roof Mount Installation (Typical) ............................................................................................................. 7!
Indoor (Inline) Installation (Typical).......................................................................................................... 7!
Air Pressure Switch Option...................................................................................................................... 8!
Advanced Filter Pressure Monitoring Option ........................................................................................... 9!
HMI MENUS...................................................................................................................................... 10!
PCUFMM Wiring ............................................................................................................................... 11!
Troubleshooting................................................................................................................................. 12!
Fire System............................................................................................................................................ 13!
Climate Controlled Utility Cabinet...................................................................................................... 13!
OPERATION .............................................................................................................................................. 15!
Start Up.................................................................................................................................................. 15!
Special Tools Required ..................................................................................................................... 15!
Start Up Procedure............................................................................................................................ 15!
Troubleshooting ..................................................................................................................................... 16!
Troubleshooting Chart ....................................................................................................................... 16!
MAINTENANCE ......................................................................................................................................... 17!
General Maintenance ............................................................................................................................ 17!
Filter Information.................................................................................................................................... 17!
Standard Filter Part Numbers............................................................................................................ 18!
Optional Pre-Filters, High Eff, and HEPA Filter Part Numbers.......................................................... 18!
Optional Odor Control Media Part Numbers ..................................................................................... 18!
Gasket Type Chart................................................................................................................................. 19!
2 Weeks After Startup............................................................................................................................ 19!
Every Month........................................................................................................................................... 19!
Duct Cleaning ........................................................................................................................................ 19!
Yearly..................................................................................................................................................... 19!
Start-Up and Maintenance Documentation............................................................................................ 20!
Job Information.................................................................................................................................. 20!
PCU Information ................................................................................................................................ 20!
Maintenance Record ......................................................................................................................... 20!
Factory Service Department.............................................................................................................. 20!
3
WARRANTY
This equipment is warranted to be free from defects in materials and workmanship, under normal use and service, for a period of 12 months from date of shipment. This warranty shall not apply if:
1. The equipment is not installed by a qualified installer per the MANUFACTURER’S installation instructions shipped with the product,
2. The equipment is not installed in accordance with federal, state and local codes and regulations,
3. The equipment is misused or neglected,
4. The equipment is not operated within its published capacity,
5. The invoice is not paid within the terms of the sales agreement.
The MANUFACTURER shall not be liable for incidental and consequential losses and damages potentially attributable to malfunctioning equipment. Should any part of the equipment prove to be defective in material or workmanship within the 12-month warranty period, upon examination by the MANUFACTURER, such part will be repaired or replaced by MANUFACTURER at no charge. The BUYER shall pay all labor costs incurred in connection with such repair or replacement. Equipment shall not be returned without MANUFACTURER’S prior authorization and all returned equipment shall be shipped by the BUYER, freight prepaid to a destination determined by the MANUFACTURER.
4
LISTINGS
This pollution control unit (PCU) is ETL listed to standard UL-710 when installed in accordance with these installation instructions and National Fire Protection Association Standard “NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations.”
APPLICATION
The listed pollution control unit is suitable for use in commercial cooking installations for the removal of smoke and grease laden vapors.
Grease duct installations require provisions for cleaning the interior of the duct. NFPA 96 cleanout requirements are as follows:
1. A cleanout must be provided at each change of direction except where the entire length of duct can be inspected and cleaned from either the hood or the discharge end.
2. On horizontal duct runs, at least one (1) 20” diameter opening must be provided. Where the opening is smaller than 20” diameter, openings large enough to permit cleaning must be provided at intervals of no more than 12’.
3. Openings in the duct must be at the side or the top, whichever is more accessible. When the opening is on the side of the duct, the lower edge of the opening must be at least 1 ½” above the bottom of the duct. For listed grease duct, this is accomplished by the use of the grease manifold tee and cleanout cap.
4. On vertical duct runs where personnel entry is possible, access must be from the top of the riser. Where entry is not possible, access must be provided at each floor.
NOTE: ACCESS REQUIREMENTS ARE SUBJECT TO CHANGE IN ACCORDANCE WITH LOCAL CODE. LOCAL AUTHORITIES SHOULD BE CONSULTED FOR EXACT REQUIREMENTS. GREASE DUCT MAY BE CONNECTED ONLY TO HOODS IN A SINGLE FIRE ZONE ON ONE FLOOR. DO NOT CONNECT GREASE DUCTS TO ANY OTHER PART OF THE BUILDING VENTILATION OR EXHAUST SYSTEM.
A grease fire can burn at extremely high temperatures. This system should be dismantled and inspected after any exposure to a grease fire. Any section that is distorted or discolored should be replaced. All joints in the system should be examined. Because the sealant expands to assure a positive seal in the case of a fire, any sealant that has been exposed to high temperature must be replaced. This will ensure that the system maintains its integrity against fire conditions in the future. The manufacturer of this PCU cannot be responsible for grease duct systems that are not properly maintained or have been subjected to one or more grease fires. Warranty and listing is void in a fire situation without consulting factory.
Grease duct systems size and capacity information may be obtained from the “ASHRAE Handbook – Fundamentals” or from the “Air Pollution Engineering Manual” of the “US Environmental Protection Agency.” Refer to the grease duct systems catalog for descriptions and dimensional data of parts.
5
INSTALLATION
It is imperative that this unit is installed and operated with the designed airflow, filters, exhaust fan placement, and construction in accordance with this manual. If there are any questions about any items, please call the service department at 1-866-784-6900 for warranty and technical support issues.
WARNING: DO NOT RAISE PCU BY THE DOOR, FILTER FRAMES, OR UTILITY CABINET – USE LIFTING LUGS PROVIDED OR A SLING.
Site Preparation
1. Provide clearance around installation site to safely rig and lift equipment into its final position. Supports must adequately support equipment. Refer to manufacturer’s estimated weights.
2. Consider general service and installation space when locating unit. Allow a minimum of 36 inches of clearance on the filter removal side of the unit to replace filters.
3. Locate unit close to the space it will serve to reduce long, twisted duct runs.
4. Support unit above ground or at roof level high enough to prevent precipitation from being drawn into unit.
5. The PCU is designed to operate in a negative pressure environment. Be sure to install the PCU between the exhaust fan and hoods. This will also keep the fan cleaner during operation.
6. The PCU drains must be connected to the building grease interceptor or an approved building drain. Black Iron or Stainless Steel Pipe must be used for this connection.
Joint Sealant
The joint sealant used to seal all internal joint assemblies is a 3M product. 3M Fire Barrier 2000 + Silicone Sealant is a ready-to-use, gun-grade, one-component silicone elastomer that cures upon exposure to atmospheric humidity to form a flexible seal. 3M Fire Barrier 2000 + Silicone Sealant, when installed properly, will control the spread of fire before, during and after exposure to open flames. It will stop the spread of noxious gas, smoke and water and maintain the integrity of fire rated assemblies and construction. NO SEALANT SUBSTITUTES MAY BE USED.
Sealant Features
1. Superior adhesion.
2. Capable of withstanding 2000 °F + temperatures.
3. Class 25 sealant, per ASTM 920.
4. Re-enterable/repairable.
5. Provides up to 4-hours fire-rating.
6. Cures upon exposure to atmospheric humidity.
7. Working time 30 minutes.
8. Cure time 14 to 21 days.
9. Applied with a standard caulk gun.
6
Recommended MIN Ductwork Sizes
PCU Size
Duct Height
Duct Width
PCU-1
23 in.
23 in.
PCU-2
30 in.
30 in.
PCU-3
35 in.
35 in.
PCU-4
43 in.
43 in.
PCU-5
50 in.
52 in.
PCU-6
46 in.
58 in.
Ductwork
The ductwork attached to this unit will significantly affect the airflow performance. Flexible ductwork and square elbows should not be used. Any
change in direction must be at least 5 duct diameters away from the pollution control unit inlet. The chart to the right shows the
recommended duct sizes for optimal performance.
The maximum velocity at the inlet of the pollution control unit must be less than 1000 Feet Per Minute. Follow SMACNA guides and
recommendations for the remaining duct run. Ensure duct connections are properly aligned and sealed. When the pollution control unit is used in commercial grease ductwork, the ductwork connections must be FULLY WELDED to the PCU. Clearance ratings of ductwork connected to the unit apply to the PCU as well. Ductwork must be listed or installed in accordance with the IMC.
Unit Drains
Each module of the Pollution Control Unit contains a drain that must be connected to an approved grease interceptor or to an approved drainage point. The drain connections must be made with Black
Iron or Stainless Steel piping. This will allow the water collected in the unit, either from Self Cleaning hood, ductwork cleaning, or from the Core Protection Fire System, to drain away from the unit. If installed outdoors, the drains must be piped so that water cannot buildup in the pipes and burst due to freezing.
Loading...
+ 14 hidden pages