Application
For proportional modulation of dampers in HVAC systems with fast running requirements, or some Laboratory fume hoods. The NMQ24-MFT US is a non-spring return type actuator. When supply power is removed the actuator will maintain its last position.
Default/Configuration
The default parameters for 2 to 10 VDC applications of the NMQ24-MFT US actuator are assigned during manufacturing. If necessary, custom versions of the actuators can be ordered. The parameters noted in the Technical Data table are variable.
These parameters can only be changed by pre-set configu­rations from Belimo.
Operation
The NMQ24-MFT US actuator provides 95° of rotation and is pro­vided with a position indicator. Upon installation and wiring the manual override push button must be pressed twice, so the actua­tor will perform an adaptation and use the new mechanical points for zero position during normal control operations.
The actuator uses a brushless DC motor which is controlled by an Application Specific Integrated Circuit (ASIC) and a micro­processor. The microprocessor provides the intelligence to the ASIC to provide a constant rotation rate and to know the actua­tors exact position. The ASIC monitors and controls the brushless DC motors rotation and provides a Digital Rotation Sensing (DRS) function to prevent damage to the actuator in a stall condition. The position feedback signal is generated with out the need for mechanical feedback potentiometers using DRS. The actuator may be stalled anywhere in its normal rota­tion without the need of mechanical end switches.
Installation
The NMQ24-MFT US is mounted directly to control shafts up to 3/4 diameter by means of its universal clamp and anti-rota­tion bracket. The actuator provides constant torque to the application with and without power applied to the actuator. The NMQ24-MFT US actuator is shipped in a Mid position, com­pression against seats or gaskets for tight shut-off is accom­plished manually.
After mounting and completing electrical installation the NMQ24-MFT US must have the adaptation function initiated. This is accomplished by pressing the manual override consec­utively two times within four seconds.
Technical Data NMQ24-MFT US
Power supply 24 VAC, ±5%, 50/60 Hz
24 VDC, ± 5% Power consumption running: 9 W; holding: 1.2 W Transformer sizing 12 VA (Class 2 power source) Electrical 3 ft, 18 GA, plenum cable,
connection 1/2 conduit connector Overload protection electronic throughout 0 to 95° rotation
Operating range Y*2 to 10 VDC, 4 to 20 mA
(w/500 , 1/4 W resistor) ZG-R01 Control resolution Response sensitivity, 80 mV
Reverse sensitivity, 80 mV
Sensitivity when driving off mechanical
position, 140 mV Input impedance 100kfor 2 to 10 VDC (0.1 mA)
500for 4 to 20 mA
Feedback output U* 2 to 10 VDC, 0.5 mA max Torque* min 35 in-lb (4 Nm) Direction of rotation* reversible with switch L/R
L=CW with increase in signal
R=CCW with a increase in signal
Angle of rotation* 0 to 95°, adjust with mechanical stops Running time* 5.0 seconds constant for 95° rotation Angle of Rotation On-manual (Default) when less
Adaptation* than 95% angle
Manual override Manual push button Position indication clip on indicator Humidity 5 to 95% RH, non-condensing Ambient temperature -4 to +122°F (-20 to +50°C) Storage temperature-40 to +176° F (-40 to +80° C) Housing NEMA 2, IP54 Housing material UL 94-5VB (flammability rating) Noise level less than 52 dB (A) Agency listings UL 873 listed, CE, CSA C22.2
No .24 certified Quality standard ISO 9001 Servicing maintenance free Weight 1.8 lbs. (0.8kg.)
* Variable when configured with MFT options Only VDC proportional control signal is available, and
variable (eg: 0-10 VDC)
Dimensions [All numbers in brackets are in millimeters.]
Torque min. 35 in-lb
Running time 5.0 to 8.0 seconds (5 sec. DEFAULT)
Control 2 to 10 VDC (DEFAULT)
Feedback 2 to 10 VDC (DEFAULT)
NMQ24-MFT US
Fast acting, proportional damper actuator, non-spring return, Multi-Function Technology
®
NMQ24-MFT US
D016
LISTED 94D5
U
TEMP. IND & REG. EQUIP.
L
3/8" to 3/4" [9.5 – 20]
3/8" to 5/8" [9.5 – 16]
7/8" [22]
5 1/2" [140]
6 13/32'' [163]
1 1/16" [27]
5/32"
[9]
7/32"
[5.2]
2 3/32"
[58]
3 3/16"
[81]
®
NM
147
G20492-Subject to change. © Belimo Aircontrols (USA), Inc.
®
Override to open or closed position
2 to 10 VDC and 4 to 20 mA Control
Notes
2
3
1
Provide overload protection and disconnect as required. Actuators may be connected in parallel if not mechanically
mounted to the same shaft. Power consumption and input impedance must be observed.
Actuator may also be powered by 24 VDC. ZG-R01 may be used.
4
NMQ24-MFT US
Fast acting, proportional damper actuator, non-spring return, Multi-Function Technology
®
Control Motion
Input Position Running
Configuration range feedback time Torque P-11001 2-10 VDC 2-10 VDC 5.0 sec 35 in-lbs P-11002 0-10 VDC 0-10 VDC 5.0 sec 35 in-lbs P-11003 2-10 VDC 2-10 VDC 6.0 sec 44 in-lbs P-11004 2-10 VDC 2-10 VDC 7.0 sec 53 in-lbs P-11005 2-10 VDC 2-10 VDC 8.0 sec 58 in-lbs
Run times available up to 60 sec. @ 58 in-lbs
Available configurations for the NMQ24-MFT US
Start point span adjustable control input is available. Please consult Belimo for the proper configuration code.
PWM and Floating point control inputs are not available with this actuator.
Response sensitivity and reverse hysteresis, for VDC applications
All listed mV values are converted to “degrees of rotation” for all other control modes.
The reverse hysteresis away from
mechanical end position is 140mV
W171
W170
24 VAC Transformer
1
Line Volts
3
Control Signal
2 to 10 VDC
2 to 10 VDC Feedback signal
(–) (+)
24 VAC Transformer
1
Line Volts
3
Control Signal
4 to 20 mA
(–) (+)
4
2 to 10 VDC Feedback signal
Standard Wiring - VDC
Blk (1) Common
(2) + Hot
Red
2
Wht
(3) Y1 Input, 2 to 10V
Grn (5) U Output, 2 to 10V
CCW CW
NMQ24-MFT US
Standard Wiring - mA
Blk
(1) Common
(2) + Hot
500
1/4 watt
Red
2
Wht
(3) Y1 Input, 2 to 10V
Grn (5) U Output, 2 to 10V
CCW CW
NMQ24-MFT US
24 VAC Transformer
1
3
Line Volts
3
Control Signal
4 to 20 mA
A Open = 4 mA Position
A Closed = Normal Operation
Override to zero position
500
1/4 watt
2
A
(–) (+)
4
Blk (1) Common
(2) + Hot
Red
(3) Y1 Input, 2 to 10V
Wht
Override to 100% position
24 VAC Transformer
1
Line
3
Volts
3
Control Signal
4 to 20 mA
B Closed = 20 mA Position C Closed = Normal Operation
(–) (+)
500
4
1/4 watt
B
C
Blk (1) Common
(2) + Hot
Red
2
(3) Y1 Input, 2 to 10V
Wht
With a 4-20 mA Input, up to 4 actuators may be wired in parallel. A 2% shift in the signal is seen when using a 500resistor. Power consumption must be observed.
Actuator responds to a 80 mV signal
when not changing direction.
Control
Direction
Satisfied
Control Position
80 mV
Minimum
Control
Resolution
Actuator responds to a 80 mV signal when
reversing direction from stop position.
Minimum Reversed
Control Deadband
80 mV
Satisfied
Control Position
Previous
Control
Direction