CaptiveAire MC1000 User Manual

MC1000 FAULT MESSAGES
MC1000 PARAMETERS
FAULT
LO VOLTS
HI VOLTS
HI TEMP
OVERLOAD
PWR TRAN
PWR SAG
LANGUAGE
EXTERNAL
DB ERROR
CONTROL
INTERNAL
INTERN (#)
Output Transistor fault; Output current exceeded 200%. May be ground fault or short circuit.
Low DC Bus Voltage fault: DC bus voltage dropped below 60%. May be low line voltage.
High DC Bus Voltage fault: DC bus voltage exceeded 120%. May be overhauling load.
High Temperature fault: Heatsink or ambient temperature too high.
Current Overload fault: Output current exceeded 100% for too long. VFD may be undersized.
Power Transient fault.
Power Sag fault: New control board installed. Perform factory reset using Parameter 65.
Language EEPROM fault.
External fault: TB-13D activated (Parameter 50).
Dynamic Brake fault: DB Resistors overloaded.
Control Board fault: New software installed. Perform factory reset using Parameter 65.
Internal fault.
Internal fault.
DESCRIPTION
MC1000 FAULT HISTORY
Parameter 70 - FAULT HISTORY stores the last eight faults that tripped the drive. The FAULT HISTORY indicates the number of the fault (number 1 is the most recent fault), the fault message, and the status of the drive at the time of the fault. An example is shown below:
FAULT NUMBER
FAULT MESSAGE
DRIVE STATUS
2 OUTPUT ACCEL
In the example above, the second fault is being viewed, which is an OUTPUT fault that ocurred while the drive was accelerating.
PARAMETER
NO.
NOTE 1: REFER TO THE MC1000 MANUAL.
NOTE 2: THESE PARAMETERS ARE VIEW-ONLY.
NAME
LINE VOLTS AUTO0 HZ MULT 1.0032
SPEED #1 20.00 HZ1
SPEED #2 20.00 HZ2
SPEED #3 20.00 HZ3
SPEED #4 20.00 HZ4
SKIP #1 .00 HZ5
SKIP #2 .00 HZ6
BAND WID 1.00 HZ7 TB5 MAX 60.00 HZ40
ACCEL 30.0 SEC8 AIN FLTR 0.02 SEC41
DECEL 30.0 SEC9 TB10A OUT NONE42
MIN FRQ .50 HZ10 @TB10A 60.00 HZ43
MAX FRQ 60.00 HZ11 TB10B OUT NONE44
DC BRAKE .0 VDC12 @TB10B 125 %45
DC TIME .0 SEC13 TB13A NONE47
DYN BRAKE OFF14 TB13B NONE48
CURRENT 180 %16 TB13C NONE49
MOTOR OL 100 %17 TB13D EXT FAULT50
BASE 60.00 HZ18 TB14 OUT NONE52
FX BOOST (NOTE 1)19 TB15 OUT NONE53
AC BOOST .0 %20 RELAY NONE54
SLIP CMP .0 %21 SERIAL DISABLE57
TORQUE CONSTANT22 ADDRESS 3058
CARRIER 2.5 KHZ23 PASSWORD 001961
START NORMAL25 SOFTWARE (NOTE 2)63
STOP COAST26 MONITOR ON64
ROTATION FORWARD27 PROGRAM RESET 6065
AUTO / MAN BOTH28 HISTORY MAINTAIN66
MANUAL KEYPAD29 LANGUAGE ENGLISH69
CONTROL LOCAL30
UNITS HERTZ31
FACTORY DEFAULT
NO.
PARAMETER
SPEED DP XXXXX33
LOAD MLT 100 %34
CONTRAST MED35
SLEEP TH .00 HZ36
SLEEP DL 30.0 SEC37
TB5 MIN .00 HZ39
HISTORY
NAME
FAULT
FACTORY DEFAULT
(NOTE 2)70
QRM1-OBOC
mc series
RUN > 60.00 HZ
Intelligent Drive
PROG
RUN
ENTER
AUTO
MAN
FWD REV
START
STOP
MC1000 Series
Quick Reference Guide
NOTE: Before installing and operating the MC1000 drive, please read and become familiar with the MC1000 Series Installation and Operation Manual.
AC Technology Corporation
660 Douglas St, Uxbridge, MA 01569
800-217-9100, FAX: 508-278-7873
www.actechdrives.com
THE MC1000 KEYPAD
MC1000 KEYPAD FUNCTIONS
MC1000 DISPLAYS
STOP > 20.00 HZ
PROG
RUN
ENTER
PROGRAMMING THE MC1000 DRIVE
1. Press the PROG/RUN key. This will cause the PASSWORD prompt to appear (unless the password protection has been disabled), as shown below:
2. Use the V and W keys to scroll to the correct password value (the factory default password is 0019) and press ENTER. The PROGRAM mode will be entered at the start of the parameter menu. A cursor will highlight the parameter name.
AUTO
MAN
FWD REV
PASSWORD 0000
CURSOR
START
STOP
START
STOP
FWD REV
AUTO
MAN
Press the START key to start the drive. The START key is only active in LOCAL mode.
Press the STOP key to stop the drive.
NOTE: The STOP key is active in both LOCAL and REMOTE mode.
The STOP key is also used to reset faults. If the fault condition has passed, pressing the STOP key will clear the fault and return the drive to a STOP condition.
UP and DOWN ARROWS - Used to change the speed setpoint in MANUAL mode, scroll through the parameter menu, and change parameter values.
Toggles between FORWARD and REVERSE rotation.
NOTE: Parameter 27 - ROTATION must be set to FWD & REV, and the drive must be in LOCAL mode for this key to be active.
Toggles between AUTOMATIC (terminal strip) and MANUAL (keypad) speed control.
NOTE: Parameter 28 - AUTO/MAN must be set to BOTH for this key to be active.
Shown below are examples of MC1000 displays. To scroll through the SPEED, LOAD, and MOTOR VOLTAGE displays, press and release the ENTER key.
SPEED DISPLAY
○○○
ENTER
○○○
LOAD DISPLAY
○○○ ○○○
ENTER
MOTOR VOLTAGE DISPLAY
DRIVE STATUS
SPEED SETPOINT
RUN > 60.00 HZ
ROTATION DIRECTION
(“>” = Forward, “<” = Reverse)
DRIVE STATUS
RUN > 85% LOAD
DRIVE STATUS
RUN > 460 VAC
SPEED UNITS
PERCENT LOAD
MOTOR VOLTAGE
3. Use the V and W keys to scroll to the desired parameter and press ENTER. The cursor will shift from the parameter name to the parameter value, as the example below illustrates:
ACCEL 30.0 SEC
CURSOR
ENTER
4. Use the V and W keys to scroll to the desired parameter value, and press ENTER to store the new value.
5. Press PROG/RUN to exit the PROGRAM mode.
PROG
RUN
ENTER
Used to enter and exit the PROGRAM mode to set the parameters.
Used for: toggling the display between SPEED, LOAD, and MOTOR VOLTAGE; confirming new parameter values; confirming AUTO and MANUAL speed control selections; confirming LOCAL and REMOTE start/stop mode selections.
Press and hold the ENTER key to activate the AUXILIARY MODE, which consists of two displays that cycle in one second intervals. One indicates LOCAL/REMOTE mode, AUTO/MANUAL mode, and the speed reference source, and the other is an elapsed time meter that indicates total run time.
Press and hold the ENTER key to activate the AUXILIARY MODE display, which indicates the control source (LOCAL, REMOTE, or SERIAL), AUTO or MANUAL mode, and the speed reference source. An example is shown below (IDC = 4-20 mA signal):
PRESS & HOLD
ENTER
CONTROL SOURCE
AUTO/MAN MODE
SPEED REFERENCE SOURCE
AUXILIARY MODE DISPLAY
LOCAL -- AUTO -- IDC
Loading...