CaptiveAire M4RT1 Installation Manual

Page 1
®
JANUARY 29, 2007
M-4000
FIREYE
M4RT1
FLAME SAFEGUARD CONTROLS
WARNING: Selection of this control for a particular application should be made by a com­petent professional, licensed by a state or other government agency. Inappropriate application of this product could result in an unsafe condition hazardous to life and property.
The Fireye® M4RT1 Flame Safeguard Control is a compact burner management system. It is designed to provide automatic ignition and continuous flame monitori ng for commercial sizes of heating and process burners that use gaseous fuels.
Flame monitoring is accomplished by a Flame Rod detector, the built in amplifier and programmer. Control functions and timing are factory set with onboard jumpers. Functions such as recycle/non­recycle, purge timing, and pilot trial for ignition (P.T.F.I.) time are determined by the jumpers. Flame Failure Response Time (F.F.R.T.) is fixed at three seconds. LED indicator lights indicate the operat­ing status of the control.
In the event of ignition failure, or following a safety shutdo wn, the unit locks out, activating an alarm circuit. Cycling the power OFF and back on will reset the control. A manual reset option can be special ordered. Remote reset (via remote pushbutton) is also available as a special order option. A detailed description of the programmer sequence is found later in this document. Test jacks are provided to permit flame signal measurement during operation.
The M4RT1 control incorporates a safety checking circuit that is operative on each start. If flame (real or simulated) is detected prior to a start or during the purge, the fuel valves will not be ener­gized, and the unit will lock out.
All M4RT1 controls do not require a wiring base due to the terminals included on the relay board. See INST ALLATION OF CONTROL, SCANNERS, AND FLAME DETECTORS (page 2) for tem­perature and wiring requirements.
1
Page 2
SPECIFICATIONS
Supply:
120V (min. 102, max. 132) 50/60 Hz
Table 1: AMBIENT TEMPERATURE LIMITS
MAXIMUM MINIMUM
Control 140°F (60°C) - 40°F (- 40°C)
Flame Rod (Tip 2460 F)
Power Consumption: 12 VA (Operating) Shipping Weight (Approx.): 2.2 lbs. (1.4kg)
Table 2: LOAD RATINGS
Fireye Terminal Typical Load Maximum Rating & 120V 60 Hz
3 or 4
Individual or combined
5 Main Fuel Valve(s)
8 Motor or contactor
A Alarm 50 VA, pilot duty
1500°F (816°C) - 40°F (- 40°C)
Pilot valve(s)
Solenoid valve
Ignition Transformer
Minimum load requirement = 100mA
®
125 VA pilot duty (solenoid valve) plus 250 VA (Transformer)
125 VA pilot duty (solenoid) or 25 VA pilot duty (solenoid) and 400 VA (opening) motorized
Motor normally energized and de-energized by the operating control whose rating must be suitable. Termi­nal 8 rated to de-energize 9.8 FLA, 58.8 LRA, on safety lockout.
APPROVALS
Underwriters Laboratories Inc.
Recognized Components Guide MCCZ2 File MP1537
ORDERING INFORMATION
CONTROL:
M4RT1 120 VAC (min.102, max 132) Supply, 50 Hz/60 Hz.
FLAME DETECTORS:
69ND1-1000K4 12 inch flame rod, 1/2” NPT connector 69ND1 -1000K6 18 inch flame rod, 1/2” NPT connector
69ND1-1000K8 24 inch flame rod, 1/2” NPT connector
2
Page 3
INSTALLATION OF CONTROL, SCANNERS, AND FLAME DETECTORS
Wiring Base
Mount the control in an enclosure/burner panel that provides the proper protection fo r the control. The location should be free from moisture, excessive vibration and within the specified ambient tem­perature rating. The control may be mounted in any angular position.
All wiring should comply with applicable electrical codes, regulations, and local ordinances. Use moisture resistant wire suitable for at least 90 degrees C. Circuit recommendations are found on pages 10 through 11. Consult the factory for assistance with non-standard applications.
WARNING: Installer must be trained and qualified. Follow the burner manufacturer's in­structions, if supplied. Otherwise, proceed as follows.
WARNING: Controls require safety limits utilizing isolated mechanical contacts. Solid state limit switches are not acceptable and should not be used due to their high leakage currents.
WARNING: Remove power from the control before proceeding.
Replaceable Fuse
The M4RT1 is designed with a field replaceable fuse. The fuse is located on the printed circuit board. The fuse will blow as a result of an overload conditio n on Terminals 3, 4 or 5. To replace the fuse, remove power from the system. Using a small screwdriver or similar tool, remove th e fuse from its holder. Install a Fireye replacement fuse (P/N 23-176) or equivalent 8 amp fuse (e.g. Lit­tlefuse 225008P, 8 amp, 125V).
®
WARNING: Turn off the power when installing or removing the control.
INSTALLATION - 69ND1 FLAME ROD
The 69ND1 flame rod proves a gas pilot flame and/or main gas flame. It is a spark plug type unit consisting of a spark plug connector for making electrical connections. The 69ND1 is available in 12,″ 18″ or 24 lengths.
The flame rod may be located to monitor only the gas pilot flame or both the gas pilot and main gas flames. It is mounted on a
The following instructions should be observed:
1. Keep flame rod as short as possible.
2. Keep flame rod at least
3. Flame rod should enter the pilot flame from the side so as to safely prove an adequate pilot
flame under all draft conditions.
4. If the flame is nonluminous (air and gas mixed before bu rning), the electro de tip should ext end
at least
1
/2″ NPT mount, a KANTHAL flame rod, a glazed porcelain insulating rod holder and
1
/2″ into the flame, but not more than halfway through.
CORRECT POSITION
OF ROD
1
/2″ NPT coupling.
1
/2″ from any refractory.
WRONG POSITION
OF ROD
INADEQUATE FLAME
PILOT BURNER
CORRECT POSITION
OF PILOT FLAME
3
Page 4
®
5. If the flame is partly luminous, the electrode tip should extend only to the edge of the flame. It is
not necessary to maintain absolutely uninterrupted contact with the flame.
6. It is preferable to angle the rod downward to minimize the effect of sagging and to prevent it
from coming in contact with any object.
7. An adequate grounding surface for the flame must be provided. The grounding surface in actual
contact with the flame must be at least four times greater than the area of the portion of the flame rod in contact with the flame. It is essential to adjust the flame rod and ground area ratio to provide a minimum signal reading of 6.0 VDC.
Note: Interference fr om the ignition spark can alter the true signal reading by adding to, or subtract­ing from it. This trend sometimes may be reversed by interchanging the primary wires (line voltage) to the ignition transformer . This interfer ence can also be r educed by the addition of grounded shield­ing between the flame rod and ignition spark.
8. Proven types of flame grounding adapters, as shown below, may be used to provide ad equate
grounding surface. High temperature stainless steel should be used to minimize the effect of metal oxidation. This assembly may be welded directly over the pilot or main burner nozzle.
WIRING OF FLAME RODS
For proper operation of flame rectification systems, it is necessary to maintain at least 20 megohms insulating resistance in the flame rectification circuit.
1. The scanner should be wired using metal cable or rigid conduit.
2. High voltage wiring must not be installed in the same conduit with scanner wiring.
Selection of Scanner Wire
1. Use #14, 16, or 18 gauge wire with 90 C, 600 volt insulation for up to 20 feet distance.
2. The type of insulation used with flame rectification is i mportant, since it must protect against
current leakage resistance to ground. Use Belden 8254-RG62 Coaxial Cable (or equal) for runs greater than 20 feet. Maximum wiring run not to exceed 100 feet.
MAINTENANCE
Type 69ND1 Flame Rod
The flame rod and its insulator should be kept clean by washing routinely with soap and water. Rods should be routinely replaced as they oxidize.
Flame Signal Strength
Routine observation of the flame signal strength will forewarn any deterioration in the capability of the flame detector or its application.
BOMB FIN
GROUNDING
ASSEMBLY
THREADED ROD
ASSEMBLY
Periodic Safety Check
It is recommended that a procedure be established to test the complete flame safeguard system at least once a month. This test should verify the proper operation of all limit switches and safety inter­locks as well as flame failure protection and fuel safety shutoff valve tightness.
4
Page 5
RESET
®
In the event of a lockout condition, the M4RT1 can be reset via a minimum one second power inter­ruption to terminal 7.
RESET OPTIONS (Special Order)
1. Optional M4RT1 reset push button. When this optional reset pushbutton is installed, the M4RT1
can be reset by depressing this button for a minimum of one second.
2. Remote reset option. With this option, the M4RT1 is provided with two additional screw termi-
nals. Using those terminals, a remote, dry contact pushbutton switch can be connected. The maximum wire length is 100 feet (no.18 AWG wire size is recommended).
CAUTION: Remote reset is recommended only on a control solely for proved ignition pro­gramming (pilot ignited burner) or a control for use only with appliances in which unburned fuel cannot accumulate and that is intended for installation in inaccessible locations such as open-flame, ceiling-suspended gas heaters.
W ARNING: Selection of the Purge time and Recycle / Non-Recycle operation for a particular application, by changes to the factory default jumpers described below, should only be per­formed by a competent professional, licensed by a state or other government agency. Inap­propriate selection of these safety critical parameters could result in an unsafe condition hazardous to life and property.
PROGRAMMER JUMPER SETTINGS
The M4RT1 has a series of 8 jumpers that are used to configure the Pu rg e timing, Pilot Trial for Igni­tion (PTFI) timing, and recycle or non-recycle operation.
Purge Timing
Jumpers JP1 through JP5 are used to select the Purge timing for the M4RT1. The available Purge timing selections are 5, 7, 30, 60, and 240 seconds and any additive combination of those ti mes. Selecting two or more Purge timing jumpers will result in a Purge time period equal to the sum of the jumpers selected. Selection of a Purge time is accomplished by cutting or not installing the associ­ated jumper. The factory set, default Purge time of 5 seconds (JP1 not installed) is always selected.
The Table below lists all available Purge times and how to select those by cutting jumpers JP2 through JP5.
Purge Time (seconds) JP2 JP3 JP4 JP5
5 Installed Installed Installed Installed 12 Cut Installed Installed Installed 35 Installed Cut Installed Installed 42 Cut Cut Installed Installed 65 Installed Installed Cut Installed 72 Cut Installed Cut Installed 95 Installed Cut Cut Installed
102 Cut Cut Cut Installed 245 Installed Installed Installed Cut 252 Cut Installed Installed Cut 275 Installed Cut Installed Cut 282 Cut Cut Installed Cut 305 Installed Installed Cut Cut 312 Cut Installed Cut Cut 335 Installed Cut Cut Cut 342 Cut Cut Cut Cut
5
Page 6
Pilot Trial for Ignition
Jumpers JP6 and JP7 are used by the factory only to select the PTFI for the M4RT1. The available PTFI timing selections are 5 and 10 seconds. The factory set, default PTFI time is 10 seconds (JP6 installed, JP7 not installed). The PTFI time may only be set by the factory.
Recycle/Non-recycle Operation
Jumper JP8 is used to select either Recycle or Non-Recycle operation of the M4RT1. The factory set, default is Recycle operation (JP8 installed). To select Non-Recycle operation, cut jumper JP8.
LED INDICATOR LIGHTS
The M4RT1 has 5 LED lights to indicate the operating status of the control. The function of these lights are:
Opr Ctrl (Operating Control): This LED is lighted whenever input terminal 7 is energized. The burner system safety interlocks and operating control should be wired in series and connected to the M4RT1 terminal 7.
Air Flow: This LED is lighted whenever all of these conditions exist:
— Input terminal 7 is energized (operating control and safety interlocks closed). — Input terminal 6 is energized (proof of airflow switch is closed). — Output terminal 8 is energized (blower motor).
PTFI: This LED is energized only during the Pilot Trial For Ignition Period. Flame: This LED is lighted whenever an adequate flame signal is detected between the M4RT1
terminals S1 & S2. Alarm: This LED is energized whenever a safety lockout occurs. (See APPLICATION AND
FUNCTION section).
NOTE: The M4RT1 is not powered until the user’s operating control is energized.
®
APPLICATION AND FUNCTION
The M4RT1 provides prepurge, ignition and flame safeguard for heating and process gas fired burn­ers. The “recycle” or “non-recycle” operation is determined by the #8 jumper on the top PCB. Purge timing, as well as trial for ignition timing is also set by the jumpers. See JUMPER SETTINGS on page 5.
The M4RT1 amplifier circuitry is designed to utilize a flame rod for flame detection. The Flame Fail­ure Response Time (F.F.R.T.) is fixed at 3 seconds.
Pilot Ignited Burners - “Recycle” Operation
With jumper #8 in the “recycle” position, the typical wiring arrangement illustrated on page 10 for pilot ignited burners provides the following function:
1. With power applied to Terminal 7 (Opr Ctrl LED lighted), the burner motor circu it (Terminal 8)
is energized. The control then waits for the proof of airflow input (Terminal 6) to be energized
2. The Pre-Purge timing starts when terminal 6 is energized.
3. Following the prepurge period (as determined by jumpers #1 through #5), KL-1 closes, ener-
gizing Terminal 3 which powers the pilot gas valve and Terminal 4 which powers the spark igni­tion. A five or ten sec. (as determined by jumpers #6 or #7) trial for ign ition is initiated ( LED lit).
4. When pilot flame is detected (Flame LED lit), KF-1 closes, energizing Terminal 5 which powers
the main fuel valve, KF-2 opens de-energizing Terminal 4 which shuts off the spark ignition.
5. When the operating control opens its circuit, or if a power failure occurs, the entire system is de-
energized. Power interruptions in the millisecond range do not affect the operation of the con­trol. Power interruptions of longer duration will cause the control to recycle.
PTFI
6
Page 7
®
6. In the event the pilot flame is not detected by the end of trial for ignition period (PTFI), the pilot
gas valve (Terminal 3) and spark ignition (Terminal 4) are de-energized. A safety shutdown occurs followed in approximately 30 seconds by a safety lo ckout that de-energizes the blower motor (Terminal 8) and energizes the lockout alarm circuit (Alarm LED lighted).
7. In the event of a flame failure during a firing period, the pilot and main fuel valves are de-ener-
gized. Following the prepurge period (as determined by jumpers #1 through #5), with proven air flow (Air Flow LED lit), the pilot gas valve and spark ignition are re-energized and a five or ten sec. (as determined by jumpers #6 or #7) trial for ignit ion is initiated (PTFI LED lit). If pilot flame is detected (Flame LED lit), the main fuel valve is energized, the spark igni tion is de-ener­gized. In the event the pilot flame is not detected by the end of trial for ignition period (PTFI), the pilot gas valve (Terminal 3) and spark ignition (Terminal 4) are de-energized. A safety shut­down occurs followed in approximately 30 seconds by a safety lockout that de-energizes the blower motor (Terminal 8) and energizes the lockout alarm circuit (Alarm LED lighted).
8. Manual Reset (supply power cycled off/on) is required following any safety lockout.
NOTE: Wait 10 seconds after lockout before restarting the control.
Pilot Ignited Burners - “Non-recycle” Operation
The function of “non-recycle” pilot ignited burners is the same as described for the “recycle” con­trols, except that the “non-recycle” operation will lock out following any flame failure. “Recycle” or “non-recycle” operation is determined by the position of jumper #8. See Programmer jumper set­tings on page 5.
Direct Spark Ignited Burners - “Recycle” Operation
With jumper #8 in the “recycle” position, the typical wiring arrangement illustrated on pages 10 and 11 for direct spark ignited burners provides the following function:
1. With power applied to Terminal 7 (Opr Ctrl LED lighted), the burner motor circuit (Terminal 8)
is energized. The control then waits for the proof of airflow input (Terminal 6) to be energized.
2. The Pre-Purge timing starts when terminal 6 is energized.
3. Following the selected prepurge period (as determined by jumper #1 through #5), KL-1 closes,
energizing T erminal 3 which powers the primary main fuel valve, and Terminal 4 which powers the spark ignition. A five or ten second (as determined by jumper #6 and #7) trial for igniti on is initiated (PTFI LED lit).
4. When pilot flame is detected (Flame LED lit), KF-1 closes, energizing Terminal 5 which pow-
ers the secondary main fuel valve, and KF-2 opens, de-energizing Terminal 4 which shuts off the spark ignition.
5. When the operating control opens its circuit, or if a power failure occurs, the control is de-ener-
gized. Power interruptions in the millisecond range do not affect the operation of the control. Power interruptions at longer duration will cause the control to recycle.
6. In the event the pilot flame is not detected by the end of trial for ignition period (PTFI), the pilot
gas valve (Terminal 3) and spark ignition (Terminal 4) are de-energized. A safety shutdown occurs followed in approximately 30 seconds by a safety lo ckout that de-energizes the blower motor (Terminal 8) and energizes the lockout alarm circuit (Alarm LED lighted).
Direct Spark Ignited Burners - “Non-recycle” Operation
The function of “non-recycle” direct spark ignited burners is the same as described for the “recycle” controls, except that the “non-recycle” operation will lock out following any flame failure. “Recy­cle” or “non-recycle” operation is determined by the position of jumper #8. See Programmer Jumper Settings on page 5.
7
Page 8
TIMING CHART
Selectable Recycle/Non-Recycle operation on loss of flame after Terminal 5 energized. Recycle on loss of air flow after flame proven.
INSTALLATION TESTING
Use of Test Meter
Testing the Fireye M4RT1 Control requires the use of a test AC-DC multimeter, with a 1,000 ohm/ volt DC rating or greater, or a digital meter with 500K input impedance or greater.
With the test meter on the DC scale, and the test meter leads inserted into the test jacks. A steady DC voltage reading of 6 to 18 volts should be obtained when the control is detecting flame, and zero volts when no flame is present.
With the test meter on the AC scale, line and load voltages may be measured at the identified test points on the chassis.
On the M4RT1 control, a micro-ammeter may be connected in series with the wire to Terminal S2. Normal flame will produce a meter reading between 4 and 10 micro-amps.
®
PROGRAMMING SEQUENCE
AIR
7
FLOW
ON
PROVEN
8
T E
3
R
M
I
4
N
A L
5
S
SELECTABLE
PURGE
PURGE
COMPLETE
SELECTABLE PTFI
5 OR10 SEC
FIRING
PERIOD
OFF
7
Flame Signal Testing
1. Manually shut off the main fuel valve for a pilot ignited burner, or the secondary fuel valve for a
direct spark ignited burner.
2. Set the test meter on the DC scale and insert the test leads into the test jacks on the amplifier
module. (If the meter reads backwards, reverse the meter leads). Red - Plus, Black - Negative.
3. Initiate a normal startup.
4. When flame is established, the test reading should be normal: a steady DC voltage reading of 6
to 18 volts.
5. Inadequate flame signal may be improved by:
a Assuring that the flame detector and wiring installati ons have followed the instructions on
pages 3 and 4. b Assuring that the flame detector is clean and within the ambient temperature limits. c Assuring that the flame is sufficiently large to detect. d Assuring that the flame quality (fuel to air ratio, combustion air velocity) is satisfactory.
8
Page 9
®
Minimum Pilot Test
This test insures that the flame detector will not sense a pilot flame too small to l ight th e main fl ame reliably. It must be made on every new installation as well as following the repositioning of the flame detector. This procedure should not be used on a direct spark ignited burner.
1. Manually shut off the fuel to the main burner.
2. Connect a test meter to the test jacks.
3. Initiate a normal startup.
4. Reduce the fuel to the pilot until the DC voltmeter reads approximately 6 volts or when the pilot
is at the minimum to provide a reliable main flame light-off. See WARNING below. This is the minimum pilot.
5. Slowly turn on the main fuel and insure that the main flame lights off promptly and normally.
WARNING: If light off is delayed, shut off the power to the installation. Realign the flame detector so that pilot flame detection requires a larger pilot flame. Repeat this test until the main flame lights reliably with minimum pilot.
W ARNING: The minimum pilot test must be accomplished by a trained and qualified burner technician.
6. After the minimum pilot test is completed satisfactorily, increase the pilot flame to normal size,
and observe that the main flame is properly established during a normal cycle ("Run-Check" switch in the "Run" position).
Flame Failure Test
1. T emporarily connect spark ignition and pilot valve to Terminal #3.
2. Initiate a normal startup.
3. Manually shut off all fuel and observe the loss of flame signal on the test meter.
4. If flame signal does not reduce to zero within the flame failure response time of the control, a
grounded metallic shield may need to be inserted between the flame ro d and spark ignition to prevent interference.
5. IMPORTANT: When the test is completed, reconnect the spark ignition to Terminal #4.
9
Page 10
FIGURE 1. TYPICAL WIRING ARRANGEMENT FOR PILOT IGNITED BURNER.
BURNER
CONTROL
SWITCH
DISCONNECT MEANS
& OVERLOAD
PROTECTION REQUIRED
LIMIT
SWITCHES
OPERATING
CONTROL
BURNER MOTOR
OR
CONTACTOR
LOCKOUT
ALARM
FUEL
INTERLOCKS
AIR FLOW
SWITCH
KF-1
KF-2
S1
S2
3
5
4
7
KB
8
2
KA
A
6
FLAME
AMPLIFIER
KL-1
ELECTRONIC
CIRCUIT
®
PILOT
GAS VALVE
MAIN
FUEL VALVE
SPARK
IGNITION
FLAME ROD
120V (MC120))
50/60 Hz SUPPLY
H
N
KL KF
Use moisture resistant wire suitable for at least 90°C.
CAUTION: When powered, 260 VAC across S1, S2.
FIGURE 2. TYPICAL WIRING ARRANGEMENT FOR DIRECT SPARK IGNITED BURNER
DISCONNECT MEANS
& OVERLOAD
PROTECTION REQUIRED
120V (MC120)
50/60 Hz
SUPPLY
LIMIT SWITCHES
BURNER
CONTROL
SWITCH
H
N
OPERATING CONTROL
BURNER MOTOR
OR
CONTACTOR
LOCKOUT
ALARM
FUEL INTERLOCKS
AIR FLOW SWITCH
KF-1
KF-2
S1
S2
3
5
4
7
KB
8
2
KA
A
6
FLAME
AMPLIFIER
KL-1
ELECTRONIC
CIRCUIT
KL KF
FLAME ROD
PRIMARY MAIN
FUEL VALVE
SECONDARY
MAIN FUEL
VALVE (IF USED)
SPARK
IGNITION
FOR INTERMITTENT IGNITION, CONNECT TO TERMINAL 3
10
Use moisture resistant wire suitable for at least 90°C.
CAUTION: When powered, 260 VAC across S1, S2.
CAUTION: Control wiring procedur es which deviate from those shown in the diagrams may bypass safety functions designed in the control. Check with the Fireye Represen tative befor e deviating from the recommended wiring diagrams.
Page 11
FIGURE 3. ALTERNATE WIRING ARRANGEMENT
A. FOR MANUAL START
S1
A START-STOP STATION MAY BE ADDED TO REQUIRE
OPERATOR START-UP EACH TIME THE BURNER FIRES.
S2
®
B. MULTIPLE BURNER SYSTEMS
HOTNEUTRAL
MOTOR
AIR FLOW
SWITCH
3
5
4
PILOT
VALVE
MAIN
FUEL VALVE
IGNITION
HOT
START
STOP
7
8
2
LR-1
LR-2
ON-OFF
LIMIT SW
ALARM
NEUTRAL
A
6
LATCH
RELAY COIL
S1
S2
3
5
4
PILOT
GAS VALVE
IGNITION
S1
S2
3
5
4 IGNITION
MAIN GAS VALVE
G
MANUAL RESET
MAIN GAS VALVE
PILOT
GAS VALVE
START
LIMIT
SWITCH
COIL OF MOTOR
CONTACTOR
STOP
AIR FLOW
SWITCH
LR-1
7
8
2
A
6
LATCH RELAY
R
MULTIPLE BURNER SYSTEMS UTILIZING SEMI-AUTOMATIC OPERATION INCORPORATE THE FIREYE MODULAR M-SERIES II CONTROLS IN A CASCADING SEQUENCE WHEN PILOT #1 IS PROVEN. TRIAL FOR IGNITION FOR PILOT #2 BEGINS. WHEN ALL PILOTS ARE PROVEN THE SAFETY SHUTOFF VALVE MAY BE MANUALLY OPENED. FLAME FAILURE OF ANY BURNER WILL TRIP THE MAIN FUEL VALVE AND SOUND ALARM. THE TOTAL CONNECTED LOAD MUST NOT EXCEED THE RATING OF THE FIRST CONTROL.
7
8
2
A
6
HOT
R
RA
S.P.D.T.
ALARM SILENCE
SWITCH
ALARM
Use moisture resistant wire suitable for at least 90°C. CAUTION: Control wiring procedures which deviate fr om those shown in the diagrams may
bypass safety functions designed in the control. Check with the Fireye Representative before deviating from the recommended wiring diagrams.
11
Page 12
®
NOTICE
WARRANTIES
When Fireye products are combined with equipment manufactured by others and/or integrated into systems designed or manufactured by others, the Fireye warranty, as stated in its General Terms and Conditions of Sale, pertains only to the Fireye products and not to any oth er equipment or to the combined system or its overall performance.
FIREYE guarantees for one year from the date of installation or 18 months from date of manufacture of its products to replace, or, at its option, to repair any product or part thereof (except lamps, elec­tronic tubes and photocells) which is found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order. THE FOREGOING
IS IN LIEU OF ALL OTHER WARRANTIES AND FIREYE MAKES NO WARRANTY OF MERCHANTABILITY OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED. Except as
specifically stated in these general terms and conditions of sale, remedies with respect to any product or part number manufactured or sold by Fireye shall be limited exclusively to the right to replace­ment or repair as above provided. In no event shall Fireye be liable for consequential or special dam­ages of any nature that may arise in connection with such product or part.
12
FIREYE M-4000
®
3 Manchester Road JANUARY 29, 2007 Derry, New Hampshire 03038 Supersedes Jan. 18, 2007 www.fireye.com
Loading...