WARNING:IMPROPER INSTALLING MAY RESULT IN SERIOUS DAMAGE. FOLLOW ALL INSTALLATION INSTRUCTIONS
THIS MANUAL IS EXCLUSIVELY INTENDED FOR PROFESSIONAL FITTERS OR SKILLED TECHNICIANS
IMPORTANT SAFETY INSTRUCTIONS FOR INSTALLING
LEGEND
ENGLISH
This symbol shows which parts to read carefully.
This symbol shows which parts describe safety issues
This symbol shows which parts to tell users about.
REFERENCE REGULATIONS
Came Cancelli Automatici S.p.A. is certified for the: ISO 9001 quality and ISO 14001 environmental management systems.
This product complies with the current regulations mentioned in the declaration of conformity.
DESCRIPTION
Multi-feature control panel for swing gates, with manageable
limit-switches and slow-down speed adjusting.
The control devices and accessories run on 24 V.
The overall draw of the accessories must not exceed
20 W.
All connections are quick-fuse protected. See table.
The control board provides and controls the following
functions:
- automatic closing after and opening command;
- pre-flashing of the movement indicator;
- obstruction detection when gate is stopped at any point;
- torque adjusting of the connected operator;
- opening ram-jolt;
- fixed ten second slow-down with adjustable speed;
- manageable limit-switches:
The definable control modes are:
- opening/closign;
- opening/closing in maintained action;
- partial opening;
- total stop.
The photocells, after detecting an obstruction, may trigger:
- a reopening if the gate is closing;
- reclosing or partial stop if gate is opening;
- partial stop if gate is opening.
Dedicated trimmers adjust:
- the automatic closing time;
- gearmotor M2 delayed closign;
- the working time.
You can also connect:
- gate open warning lights; - cycle lights;
- electrolock.
Intended use
The ZA3P control panel is designed for controlling ATI, FERNI, KRONO, FAST and FROG 230 V swing-gate operators.
Any installation and/or use other than that specified in this manual is forbidden.
Limits to use
The overall power of the connected motors must never exceed 600 W.
Technical data
TypeZA3P
Protection rating (IP)54
Power supply (V - 50/60 Hz)230 AC
Power draw when idle (mA)60
Maximum power ( W)600
Casing materialABS
Operating temperature (°C)-20 ÷ +55
Insulation class
* Contained in the 230 V FROG gearmotor box. Connect them to the black cables (motor M1) and red ones (motor M2),
10 11 S 1 2 3 3P 4 5 7 2 C1 CX B1 B2TS 10
which are set up on the control board; if pairing ATI, FAST, FERNI and KRONO gearmotors, these will stay unused (the
condensers are connected inside).
Transformer and condenser cable colors:
- Manual code:
p.
white; red; black; orange; purple; light blue.
Page 4
4
319W86
2
Dimensions
ENGLISH
(mm)
GENERAL INSTRUCTIONS FOR INSTALLING
Only skilled, qualified staff must install this product.
Warning! Before working on the control panel, cut off the main current supply and, if present, remove any batteries.
Preliminary checks
Before beginning the installation, do the following:
• make sure you have set up a suitable dual pole cut off device along the power supply that is compliant with the installation
rules. It should completely cut off the power supply according to category III surcharge conditions (that is, with minimum
contact openings of 3 mm); make sure that any connections inside the container (ones that ensure continuity to the
protection circuit) are fitted with additional insulation with respect to those of other electrical parts inside:
set up suitable tubes and conduits for the electric cables to pass through, making sure they are protected from any mechanical
damage
Cable types and minimum thicknesses
ConnectionCable type
Control panel power supply 230 V AC
Motor/encoder power supply 24 V DC3 x 1 mm
Flashing light2 x 0.5 mm
Photocell transmitters2 x 0.5 mm
Photocell receivers4 x 0.5 mm
FROR CEI
20-22
CEI EN
50267-2-1
Cable length
1 < 10 m
3G x 1.5 mm
Command and safety device2 x 0.5 mm
AntennaRG58max 10 m
If cable lengths differ from those specified in the table, establish the cable sections depending on the actual power draw
of the connected devices and according to the provisions of regulation CEI EN 60204-1.
For multiple, sequential loads along the same line, the dimensions on the table need to be recalculated according to the actual
power draw and distances. If connecting products that are not contemplated in this manual, see the literature accompanying
said products
319W86 v.
- Manual code:
p.
Page 5
5
319W86
2
Tools and materials
Make sure you have all the tools and materials you will need for installing in total safety and in compliance with applicable
regulations. The figure shows some of the equipment installers will need.
INSTALLATION
Fastening the control panel
Fasten the control panel base in a
protected area; use rounded cross head
screws with maximum 6 mm diameter.
Perforate the pre-drilled holes.
The holes have different diameters:
23, 29 and 37 mm.
Be careful not to damage the control
board inside the control panel.
Enter the cable gland with the
corrugated tubes for threading the
electrical cables.
Gate open warning light (Contact rated at: 24V - 3W max.). - Warns when the
gate is open, and turns o when the gate is closed.
Movement fl ashing light (Contact rated at: 230V A.C.
- 25W max.). - Flashes when the gate is opening and
closing.
Courtesy light (230V-60W). -It stays on
for a fi xed time of 5 minutes from the
moment in which the gate-leaves start
their maneuver.
ENGLISH
UVWXYEE3
Command and control devices
Stop button (contact N.C.). - For commanding the gate stop while
excluding the automatic closing cycle. To resume movement, press
the command button or the transmitter button. If unused, short-circuit
terminals 1-2.
Key-switch selector and/or button (contact N.O.). - For commanding
gate opening and closing. By pressing the button or turning the key-switch
selector, the gate inverts its movement or stops depending on the selection
319W86 v.
made on the DIP-switches (see functions selecting, DIP-switches 2 and 3).
10 11 S 1 2 3 3P 4 5 7 2
- Manual code:
p.
10 11 S 1 2 3 3P 4 5 7 2 C1 CX B1 B2
Page 8
8
319W86
2
Safety devices
DeltaDir/DeltaS
ENGLISH
<- C1 ->
Reopening during closing connection (contact NC). With safety devices such as photocells, sensitive safety-
edges and other EN 12978 regulation compliant devices. When closing, the contact triggers the inversion of
movement until opening is complete.
If unused, short-circuit 2-C1.
<- CX ->
with DIP-switch 8 OFF - DIP-switch 2 OFF
(Selector )
Connection for reopening during closing (contact
NC). - With safety devices such as photocells, sensitive
safety-edges and other EN 12978 regulation compliant
devices. When opening, the contact triggers the
inversion of movement until closing is completed.
If unused, disable input CX with DIP-switch 8 set to ON.
with DIP-switch 8 OFF - DIP-switch 2 ON
(Selector )
Partial stop connection (contact NC). - With safety
devices such as photocells, sensitive safety-edges and
other EN 12978 regulation compliant devices. Stops
movement and then triggers automatic closing.
<- TS ->
with DIP-switch 10 ON
Safety test function connection - With each opening and closing command, the board checks the efficiency of
the photocells. Any malfunction of the photocells is warned by the flashing LED
cancels any command from the radio transmitter or button.
IMPORTANT: When activating the safety test feature, at least one pair of photocells must be connected in
"reopening during closing" (C1).
1 ON Automatic closing activated (1 OFF - deactivated);
2 ON "Open-stop-close-stop" with button (2-7) and radio-control
(AF card fi tted) activated;
2 OFF "Open-close" with button (2-7) and radio-control (AF card
fi tted) activated; 3 ON "Open only" with radio-control
(AF card fi tted) activated (3 OFF-deactivated);
4 ON Pre-fl ashing while opening and closing activated (4 OFF-
deactivated)
5 ON Obstruction detection activated (5 OFF-deactivated);
6 OFF "Maintained action" (excludes functioning of the radio
control) deactivated (6 ON-activated);
7 ON Ram-jolt activated; with each opening command, the
gate-leaves at fi nal closing point press for one second,
thus facilitating the releasing of the electrolock which
is connected to terminals 11-S. It is active only if the
gate-leaves are closed and the end of the working time,
or at the 1st maneuver after powering up the system (7
OFF-deactivated);
8 OFF Terminal CX activated (8 ON-deactivated);
9 OFF Ten-second slow-down deactivated (9 OFF.-activated);
10 ON Photocells test activated (10 OFF deactivated).
L2T L1T1234
12 24
0
CT 012 24
L1T
L2T
FC1FA2FC2
2
FA1
1011 S 1 2 3 3P 4 5 7 2 C1CX B1 B2TS10
UVWXYEE3
LN
Selector
1 ON Limit switches enabled (1 OFF -
2 OFF CX with reclosing during opening
2 ON CX with partial stop feature.
disabled);
feature.
ENGLISH
Trimmer adjusting
Adjusting working time from a minimum of 10 seconds to a
maximum of 120 seconds.
Adjusting the automatic closing time from a minimum of 1
second, to a maximum of 120 seconds.
Adjusting delayed closing of 2nd motor (min. 0”, max. 15”)
and simultaneously partial opening (min. 0”, max. 30”).
Adjusting slow-down speed
To adjust the slow-down speed (operation to be done with gate stopped):
• by pressing CH1 again it shifts to the next speed;
319W86 v.
• confirm the choice by pressing CH2;
• reset DIP-switch 6 to OFF.
- Manual code:
p.
will show the set slow-down speed
Flashing in quick
succession
minimum2
medium3
maximum
L2T L1T1234
12 24
0
CT 012 24
L1T
L2T
UVWXYEE3
LN
Slow-down
speed 1
FC1FA2FC2
2
FA1
1011 S 1 2 3 3P 4 5 7 2 C1CX B1 B2TS10
Page 10
L2TL1T1234
10
319W86
2
Adjusting the motor torque
To vary the motor torque, move the show
faston to one of the four positions:
1 min., 4 max..
ENGLISH
ACTIVATING THE RADIO CONTROL
Antenna and AF radiofrequency card
Connect the antenna's RG58 cable to the
corresponding terminals.
Fit the radio frequency card into the control board
AFTER CUTTING OFF THE MAIN POWER SUPPLY
N.B.: The control board recognizes the radiofrequency
card only when it is powered up.
C1 FA2 FC2
L2T L1T1234
12 24
0
CT 012 24
L1T
L2T
FC1FA2FC2
2
FA1
1011 S 1 2 3 3P 4 5 7 2 C1CX B1 B2TS10
UVWXYEE3
LN
2C1CXB1B2
Possible connection of a second operator, that can
be activated by the second channel of
the radio circuit (contact NO). Contact rated for:
5A-24 V DC
Memorization (max. 25 different transmitters)
CH1 = Channel for direct commands to a functions of the gearmotor's control board
("open only / " open-close-invert" command or "open-stop-close-stop",
depending on the selection made on DIP-switches 2 and 3).
CH2 = Channel for direct command to an accessory device connected to B1-B2.
Keep button CH1 pressed on the control board (the warning LED will fl ash),
with a transmitter button send the code , the LED will stay on to tell you that
memorization has been successful.
Perform the same procedure with button CH2, associating it to another button
on the transmitter.
Simultaneously keep pressed buttons CH1 and CH2 for over fi ve seconds; when the LED stays lit, all of the
radio control will be cancelled.
>5”
FINAL OPERATIONS
Fastening the cover
Once the electrical connections and set up are done, fit the
cover and fasten it using the supplied screws.
DISMANTLING AND DISPOSAL
CAME CANCELLI AUTOMATICI S.p.A. employs an Environmental Management System at its premises. This
system is certified and compliant with the UNI EN ISO 14001 regulation standard to ensure that the environment is
respected and safeguarded.
Please continue protecting the environment. At CAME we consider it fundamental in our strategic market policies. Just
follow these simple dismantling instructions:
Before disposing, it is always advisable to check with the specific laws that apply in your area.
DO NOT DISPOSE OF IN NATURE!
DISPOSING OF THE PACKAGING The packaging materials (cardboard, plastic, and so on) should be disposed of as
solid urban waste, and simply separated from other waste for recycling.
DISMANTLING AND DISPOSAL Our products are made with different materials. Most of these (aluminum, plastic,
iron, electrical cables) are classified as solid urban waste. They can be recycled by separating them before dumping
at authorized city dumps. Whereas other components (control boards, batteries, transmitters, and so on) may contain
hazardous pollutants. These must therefore be disposed of by authorized, certified professional services.
Declaration Came Cancelli Automatici S.p.A.declares that this product conforms to the essential, pertinent
requirements provided by directives 2006/95/CE and 2014/30/UE. An
original copy of the declaration of conformity is available on request.
11- Manual code:
p.
Page 12
IT • Per ogni ulteriore informazione su azienda, prodotti e assistenza nella vostra lingua:
CAM E Cance ll i Au tomat ic i S. p. a.
Do ss on D i Casie r
Ass is te nza Tecnica /N um er o Verd e 80 0 29 58 30
www. came.com
Engl ish
319 W86
2
EN • For any further information on company, products and assistance in your language:
FR • Pour toute autre information sur la société, les produits et l’assistance dans votre langue :
DE • Weitere Infos über Unternehmen, Produkte und Kundendienst bei:
ES • Para cualquier información sobre la empresa, los productos y asistencia en su idioma:
NL • Voor meer informatie over het bedrijf, de producten en hulp in uw eigen taal:
PT • Para toda e qualquer informação acerca da empresa, de produtos e assistência técnica, em sua língua:
PL •
Wszystkie inne informacje dotyczące fi rmy, produktów oraz usług i pomocy technicznej w Waszym języku znajdują się na stronie:
RU •
Для получения дополнительной информации о компании, продукции и сервисной поддержке на вашем языке:
HU • A vállalatra, termékeire és a műszaki szervizre vonatkozó minden további információért az Ön nyelvén:
HR • Za sve dodatne informacije o poduzeću, proizvodima i tehničkoj podršci:
UK • Для отримання будь-якої іншої інформації про компанію, продукцію та технічну підтримку: