TEM, RELEASETHEOPERATORANDDONOTUSEITUNTIL
SAFETYCONDITIONSHAVEBEENRESTORED • CUTOFF
THEPOWERSUPPLYBEFORERELEASINGTHEOPERATOR
FORMANUALOPENINGSANDBEFOREANYOTHEROPERA-
TION, TOPREVENTPOTENTIALLYHAZARDOUSSITUATIONS.
EADTHEINSTRUCTIONS IFTHEPOWERSUPPLYCABLE
R
ISDAMAGED, ITMUSTBEREPLACEDBYTHEMANUFAC-
TURERORAUTHORIZEDTECHNICALASSISTANCESERVICE,
ORINANYCASE, BYSIMILARLYQUALIFIEDPERSONS, TO
PREVENTANYRISK • ITIS FORBIDDEN FORUS-
ERSTOPERFORMANY OPERATIONS THAT ARE
NOT EXPRESSLY REQUIRED OF THEM AND
WHICH ARE NOT LISTED
This symbol shows which parts to read carefully.
This symbol shows the parts which describe safety issues.
⚠
This symbol indicates what should be communicated to users.
☞
All measurements, unless otherwise stated, are expressed in millimeters.
REFERENCE REGULATIONS
CAME S.p.A. is certified for its ISO 9001 quality and ISO 14001 environmental management systems.
This product complies with the current regulations mentioned in the declaration of conformity.
DESCRIPTION
This product has been designed and built by CAME S.p.A. in compliance with current legal safety standards.
The operator is composed of a part made of cast aluminium inside of which works the irreversible gearmotor plus an
aluminium casing.
The Sipario
The operators:
001VLR01DX
001VLR01SX
001VLR02 Irreversible operator for controlling two-leaf swing shutters, complete with control board and transmission-
The transmission arms:
001VLR07DX RIGHT-HAND curved transmission arm for single-panel shutters.
001VLR07SX LEFT-HAND curved transmission arm for single-panel shutters.
001VLR08DX Adjustable RIGHT-HAND curved transmission arm for shutters with single- or double-jointed panels.
001VLR08SX Adjustable LEFT-HAND curved transmission arm for shutters with single- or double-jointed panels.
001VLR09DX Adjustable RIGHT-HAND augmented curved transmission arm for shutters with double-jointed panels.
001VLR09SX Adjustable LEFT-HAND augmented curved transmission arm for shutters with double-jointed panels.
001VLR10DX RIGHT-HAND augmented curved transmission arm for single-panel shutters.
001VLR10SX LEFT-HAND augmented curved transmission arm for single-panel shutters.
The optional accessories:
001VLR04 Covering cross-piece for the VLR02 with light bays greater than 970 mm.
001VLR05 Emergency operation device, complete with 12 V batteries and battery-charging card.
RIGHT-HAND irreversible OPERATOR for controlling one-leaf swing shutters, complete with control board
and transmission-arm guide.
LEFT-HAND irreversible OPERATOR for controlling one-leaf swing shutters, complete with control board and
transmission-arm guide.
arm guides.
Intended use
The VOILA operator is designed for opening and closing one or two-leaf swing leaves.
By shutters we mean
Any installation and use other than that specified in this manual is forbidden.
must always exceed 90°; install a simple strike plate for this.
shutter
90 / 110130165
500 / 1050
750 / 1050
720 / 2100
970 / 2100
500 / 1050
750 / 1050
820 / 2100
970 / 2100
500 / 1050
750 / 1050
720 / 2100
970 / 2100
FA00135-EN - vers.
7 - Manual code
Page
8
FA00135-EN
2
One or two-leaved jointed double-paneled shutter
Unfoldable type of transmission armVLR08VLR09
A - Minimum space between the inner fi xture and the
shutter
130160
B - Bay width (min./max.)
One leaf, without VLR01xx batteries
One leaf, with VLR01xx+VLR05 batteries
Two leaves, without VLR02 batteries
Two leaves with VLR02+VLR05 batteries
500 / 1050
750 / 1050
820 / 2100
970 / 2100
500 / 1050
750 / 1050
900 / 2100
970 / 2100
F - Width of internal panel (min./max.)140 / 170170 / 240
The angle
For this application, fi t a corner protection
must always exceed 90°; install a simple strike plate for this.
for the arm.
GENERAL INSTRUCTIONS FOR INSTALLING
Installation must be carried out by expert qualified personnel and in full compliance with the regulations in force.
⚠
Preliminary checks
• Check that the operator fixing point is protected from possible knocks, and that the fixing surface is solid. Also check that
appropriate screws, plugs, etc. are used to fix the panel;
• Set up suitable conduits and tubes to safely run the electrical cables through and to protect them from mechanical damage.
• Remove the shutter opening stops and replace them with strike plates.
• Make sure the angles between the two leaves always exceeds 90°.
Tools and materials
Make sure you have all the tools and materials you will need for installing in total
safety and in compliance with applicable regulations. The figure shows some of the
equipment installers will need.
Cable types and minimum thicknesses
ConnectionCable typeCable length
1 < 10 m10 < 20 m 20 < 30 m
Power supply to control panel 230 V
Accessories powered at 24 V2 x 0.5 mm
Command and safety device2 x 0.5 mm
Home & building automation connections CAT5 - U/UTP - AWG24max 1200 m
If the cable lengths differ from that specified in the table, then you must determine the cable diameter based on the actual
☞
power draw from the connected devices and according to the CEI EN 60204-1 standard.
For multiple, sequential loads along the same line, the dimensions on the table need to be recalculated according to the actual
power draw and distances. For connecting products that are not contemplated in this manual, see the literature accompanying
said products
8 - Manual code
Page
9
FA00135-EN
2
INSTALLING
The following illustrations are examples. It is up to the installer to find the most suitable solution.
The template features the indications for use on both the right and left.
Tracing the holes
Rest the template against the shutters and the bay side
panel of the bay and mark the holes using a pencil; finish
marking out the holes ❶ on the metal anchoring base of the
Voilà unit.
So, drill for using suitable fasteners.
For laying the cables, see details on page 14; zone
shows the cable entry point, in option 1.
Cut the slide rails to the required length, leaving a minimum clearance at the ends.
One or two-leaf single-panel shutterOne or two-leaved jointed double-paneled shutter
Fit the arm skid into the slide rail
(see ).
Fit the guide to the shutter and
check that it is level and that the
skid slides smoothly.
Use the premarked holes and
use flat countersunk screws (not
issued).
performed with the transmission
arm fixed to the motor shaft.
FA00135-EN - vers.
The VLR08/VLR09 adjustable arms, allow you to adjust the leaf opening more accurately, by changing the joining holes of the
two semi-arms (see page 10, figure ).
11 - Manual code
Page
1÷2
0
12
FA00135-EN
2
VLR02 operator Master and Slave connection
Attach the cable clips ❻.
Connect the Slave gearmotor to the Master operator using the wired cable❼ on the MOTOR1 terminal.
In this way, the right-hand leaf will open first.
If you need the left-hand leaf to open first while keeping the Master to the right, swap the MOTOR1 and
MOTOR2 connectors.
Manual release of the operator
Activating the manual release could result in the shutter moving inadvertently due to possible mechanical failures or
Terminals for powering 24 V AC accessories.
Maximum allowed power: 15 W.
CX 3
R22 R23
B A GND
M6
R3
R6
C17
C11 C12
⑫
⑯
14
FA00135-EN
2
There are two possible points to pass the power-supply and accessory-control cables through: either on the anchoring base
through the existing slots (option 1), or on the end cap which features pre-shaped apertures (option 2).
Connect the ground to both gearmotors.
Option 1Option 2
Command and control devices
The AF and RSE cards must be fitted
into the control board AFTER CUTTING
OFF THE MAINS POWER.
N.B.: the basic control board recognises
them only when it is powered up.
LEFT-HANDMOTOR
RSE card
RIGHT-HANDMOTOR
GND
B
A
CX3
2104
11
CRP - Came Remote Protocoll.
Connection to the home-automation
system.
AF card
B A GND
M6
OPEN-STOP function (NO contact)
LINE 1A-F
CLOSE-STOP function (NO contact)
⚠ If the PARTIAL OPENING function is activated via a dip-switch on the button connected to 2-3, then the button connected
to 2-4 will automatically operate as a sequential OPEN-STOP-CLOSE-STOP command.
⚠ If MAINTAINED ACTION is activated via dip-switches, the two buttons will operate as automatically OPEN and CLOSE,
respectively.
⚠When the MAINTAINED ACTION function is active, the PARTIAL OPENING function cannot be set.
OFFONONOFFDeleting memorized transmitters and weather units
OFFONOFFONIncreasing the maneuvering speed
ONONOFFONReducing the slow-down speed
OFFOFFONONAdjusting the sensitivity
ONOFFONONSlowed-down start when closing
OFFONONONImmediate closing in case of a power outage
ONONONONResetting parameters
Self-learning of the gate-leaf travel
Select the DIPs as shown and press the PROG key on the
board.
To calibrate the travel the leaves must be closed.
The leaves will perform a series of maneuvers to establish the
limit switch points.
During calibration the red LED flashes. Once the calibration is
To disable the function: with the DIP switches set as shown,
press again the PROG key on the control boar.
Button-activated maintained action
Select the DIP switches as shown or press PROG on the
control board.
Once memorized the buzzer sounds off for one second.
done the buzzer sounds off for one second.
To restore the default parameters press
If calibration was not successful, the LED flashes quickly and
the buzzer sounds 4 times.
The self-learning procedure can be interrupted
by pressing the PROG key .
To configure for one swing-leaf, connect the operator to
⚠
MOTOR2.
Partial opening from button
Use the buttons to move the leaves to the desired position
Only consider the first leaf's opening angle. During the first
maneuver, the second leaf will memorize the opening angle
PROG again. The LED flashes and the buzzer sounds off
twice.
The opening button connected to 2-3 (NO contact) is
⚠
default set to the OPEN-STOP function.
If I enable maintained action from a button, I cannot enable
partial opening from a button and neither from a transmitter.
You can memorize up to a maximum of ten different
radio codes.
Partial opening using transmitter (only if already saved to
a button).
of the first leaf.
Select the DIP switches as shown or press PROG on the
Select the DIP switches as shown or press PROG on the
control board.
Once memorized the buzzer sounds off for one second.
control board. The red LED flashes. Within ten seconds press
the button on the transmitter you wish to memorize. Once
memorized the buzzer sounds off for one second.
If the partial opening angle does not come within the
minimum and maximum default-set limits (fro 10% to 50%
of the travel), upon sending the next command the opening
angle will automatically set to the closest level.
If the key has already been memorized, the LED will flash
quickly and buzzer will flash four times.
16 - Manual code
Page
17
FA00135-EN
2
OPEN-STOP from transmitter
Select the DIP switches as shown or press PROG on the
control board. The red LED flashes. Within ten seconds press
the button on the transmitter you wish to memorize.
control board. The LED stays on and the buzzer sounds off
for 1 s.
To return to the default settings, press the PROG key again.
The LED flashes and the buzzer sounds off twice.
Once memorized the buzzer sounds off for one second.
If the key has already been memorized, the LED will flash
quickly and buzzer will flash four times.
CLOSE-STOP from transmitter
Select the DIP switches as shown or press PROG on the
control board. The red LED flashes. Within ten seconds press
the button on the transmitter you wish to memorize.
Once memorized the buzzer sounds off for one second.
If the key has already been memorized, the LED will flash
quickly and buzzer will flash four times.
Transmitter activated OPEN-STOP-CLOSE-STOP
Select the DIP switches as shown or press PROG on the
control board. The red LED flashes. Within ten seconds press
the button on the transmitter you wish to memorize.
Once memorized the buzzer sounds off for one second.
If the key has already been memorized, the LED will flash
quickly and buzzer will flash four times.
Weather unit
The weather unit occupies 3 radio codes.
⚠
Select the DIP switches as shown or press PROG on the
control board. The red LED flashes. Within ten seconds press
the P2 key on the weather unit. Once memorized the buzzer
sounds off for one second.
If the weather unit has already been memorized, the LED will
flash quickly and the buzzer will sound off four times.
Deleting memorized transmitters and weather units
Select the DIP-switches as shown and press PROG on the
control board for five seconds.
After deleting, the red LED flashes and the buzzer sounds off
for one second.
Adjusting the sensitivity
The default obstruction-intervention time is one second.
To increase the intervention time to two seconds:
Select the DIP switches as shown or press PROG on the
control board. The LED stays on and the buzzer sounds off
for 1 s.
To return to the default parameters, press PROG again. The
LED flashes and the buzzer sounds off twice.
Slowed-down start when closing
The slow-down is disabled by default.
To enable it:
Select the DIP switches as shown or press PROG on the
control board. The LED stays on and the buzzer sounds off
for 1 s.
To return to the default parameters, press PROG again. The
LED flashes and the buzzer sounds off twice.
Immediate closing in case of a power outage
This function can be used only where there are batteries.
⚠
To enable it:
Select the DIP switches as shown or press PROG on the
control board. The LED stays on and the buzzer sounds off
for 1 s.
To return to the default parameters, press PROG again. The
LED flashes and the buzzer sounds off twice.
Resetting parameters
Once reset, the LED flashes and the buzzer sounds off twice.
With this function the transmitters and weather unit are not
deleted.
Increasing the maneuvering speed
The default maneuvering speed is set to 70%.
To increase the maneuvering speed by 20%:
Select the DIP switches as shown or press PROG on the
control board. The red LED stays lit and buzzer sounds off
for one second.
To return to the default settings, press the PROG key again.
The LED flashes and the buzzer sounds off twice.
Reducing the slow-down speed
FA00135-EN - vers.
The default maneuvering speed is set to 50%.
To reduce the slow-down speed by 10%:
Select the DIP switches as shown or press PROG on the
17 - Manual code
Page
18
FA00135-EN
2
FINAL OPERATIONS
Fasten the end caps using the supplied screws.
Fit the snap-in casing onto the gearmotor and secure it using the
supplied screws.
With two-leaved installations like with the Voilà VLR02, whose window-bay width exceeds 970 mm, we suggest also fitting
the VLR04 covering cross-piece so that it also covers the Master/Slave connection.
After reducing it to the right size (L1 = L - 14 mm), snap it into the guides and cover the joints using suitably modified strips
with the end caps removed.
CAME S.p.A. applies a certified Environmental Management System at its premises, which is compliant with the UNI EN
☞
ISO 14001 standard to ensure environmental protection.
Please continue safeguarding the environment. At CAME we consider it one of the fundamentals of our operating and market
strategies. Simply follow these brief disposal guidelines:
DISPOSING OF THE PACKAGING
The packaging materials (cardboard, plastic, and so on) should be disposed of as solid household waste, and simply
separated from other waste for recycling.
Always make sure you comply with local laws before dismantling and disposing of the product.
DISPOSE OF RESPONSIBLY!
DISPOSING OF THE PRODUCT
Our products are made of various materials. Most of these (aluminium, plastic, iron, electrical cables) are classified as solid
household waste. They can be recycled by separating them before dumping at authorized city plants.
Whereas other components (control boards, batteries, transmitters, and so on) may contain hazardous pollutants.
These must therefore be disposed of by authorized, certified professional services.
Before disposing, it is always advisable to check with the specific laws that apply in your area.
DISPOSE OF RESPONSIBLY!