Burnham Care-Free E4 Installation, Operating And Service Instructions

Page 1
nonoitamrofnignikeesnehW.rotcartnocgnitaehruoyllac,reliobotsriaperroecivresroF
.lebaLgnitaRnonwohssarebmuNlaireSdnarebmuNledoMrelioBedivorp,reliob
rebmuNledoMrelioB rebmuNlaireSrelioB etaDnoitallatsnI
4E
rotcartnoCgnitaeH rebmuNenohP
sserddA
8143606R9-2/10 Price - $3.00
Page 2
IMPORTANT: READ THESE INSTRUCTIONS CAREFULLY BEFORE PROCEEDING WITH THE INSTALLATION OF BOILER. POST INSTRUCTIONS NEAR BOILER FOR REFERENCE BY OWNER AND SERVICE TECHNICIAN. MAINTAIN INSTRUCTIONS IN LEGIBLE CONDITION.
NOTE: — The equipment shall be installed in accordance with those installation regulations in force in the area where the installation is to be made. These shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made.
All wiring shall be made in accordance with the National Electrical Code and/or local regulations.
SECTION I - INSTALLATION INSTRUCTIONS ...........................................................Page 3
SECTION II - OPERATING AND SERVICE INSTRUCTIONS .....................................Page 5
CLEARANCE REQUIREMENTS
For Service Accessibility
LEFT SIDE 18" 18"
RIGHT SIDE 6" 0"
TOP 9" 9"
BOTTOM 9" 15"
REAR 0" 0"
FRONT For Door Removal - 24"
* Closet Installation Requires Two Ventilation Openings, one located at top and one at bottom, each opening to have 25 sq. in. net free area.
Approved for Closet & Alcove Installation with minimum
clearance to combustible material*
2" Closet
18" Alcove
Water Flow Rate -
Recommended Power
Supply to Boiler
Min.*
Wire Size
#4 AWG 80 155 5.5 4.6 4.2
Max. Fuse Size-Amps
Appx.
Wt. Full
(Lb.)
Water
Contents
(Gal.)
Boiler
Model
DOE HEATING
CAPACITY, BTU/HR
AFUE
KW
Amps
Rating
%
(240V)
(240V)
No. and Size
of Elements
240V 220V 208V
412 41,000 35,000 31,000 100 12 50 4-3KW #6 AWG 60 155 4.1 3.5 3.1
416 55,000 46,000 41,000 100 16 70
420 68,000 58,000 52,000 100 20 85 4-5KW #2 AWG 90 155 6.8 5.8 5.2
DOE Heating Capacities are shown. Where the boiler and piping are in the heated space, the boiler may be selected on the basis of the DOE Heating Capacity. Where a piping loss and/or a pickup loss will exist, add this loss to the building loss to determine the total heating requirements. Where a piping loss only will exist but cannot be calculated, multiply the calculated building loss by a 1.15 factor to determine the total heating requirement.
*For runs in excess of 50 ft. consult local or national electrical code.
Maximum Allowable Working Pressure: 30 PSI (Water Only)
2-3KW (top)
2-5KW (bottom)
(GPM) Based on 20°F Temp. Rise and Boiler
Capacity At
240V 220V 208V
Figure 1: Dimensions and Specications
2
Page 3
SECTION I: INSTALLATION INSTRUCTIONS
A. Inspect Shipment carefully for any signs of damage.
1. All equipment is carefully manufactured, inspected and packed. Our responsibility ceases upon delivery of Boiler to the carrier in good condition.
2. Any claims for damage or shortage in shipment
must be led immediately against the carrier by
the consignee. No claims for variances from, or shortage in orders, will be allowed by Boiler Manufacturer, unless presented within sixty (60) days after receipt of goods.
B. Read These Instructions Carefully before proceeding
with installation and operation of the “CARE-FREE” Electric Boiler.
1. The “CARE-FREE” is U.L. listed, constructed and tested in accordance with the requirements of the ASME Boiler and Pressure Vessel Code and designed for use in any conventional hydronic system except steam and gravity hot water.
2. The “CARE-FREE” Electric Boilers are shipped completely assembled less circulator. All electrical controls are mounted and wired in a compartment immediately behind the Front Door of the Boiler Jacket, see Figure 1.
C. Locate Boiler in or adjacent to the space to be heated
with consideration given to the location of the electrical service. Although its compactness will allow the “CARE-FREE” Electric Boiler to be mounted almost anywhere – closet, alcove, or other small area, see CLEARANCE REQUIREMENTS on Page 2.
D. Mount Boiler to wall using four 3/8" lag screws
or anchor bolts (depending upon wall construction)
passing through the holes provided in the wall mounting channels. Figure 1 shows bolt center dimensions. It is recommended that 1/2" plywood be used as a base for mounting the boiler so that the structure is adequate to carry the weight imposed upon it – see Figure 1 for weight of boiler when full of water. Boiler should be level for proper operation of BUILT­IN AIR SEPARATOR.
E. Connect Supply and Return Piping to Heating
System using standard recognized practices. See Figure
2. Install an appropriate size expansion tank in system as per Figure 2. Do not connect into the 3/4" tee on top
of the boiler; instead install an automatic oat type air
vent at this point. Water content of the boiler is given in Figure 1.
The relief valve outlet should be piped full size to a
drain or near the oor.
The heating elements are NOT compatible with
ethylene glycol based antifreeze.
If a low water cut-off is required, it must be mounted in
the system piping above the boiler.
The minimum safe water level of a hot water boiler is
just above the highest water containing cavity of the boiler; that is, a hot water boiler must be full of water to operate safely.
If it is required to perform a long term pressure test of
the hydronic system, the boiler should rst e isolated to
avoid a pressure test including the boiler, ALL trapped
air must rst be removed from the boiler.
A loss of pressure during such a test, with no visible
water leakage, is an indication that the boiler contained trapped air.
Figure 2: Recommended Boiler Piping
3
Page 4
F. Install Electric Wiring in accordance with
NATIONAL ELECTRICAL CODE and Local Regulations. The Burnham “CARE-FREE” Electric Boilers may be used with 208 and 240 volt, 60 cycle, single phase power and one 3 wire power supply. Since the heaters are rated at 240 volts, however, any input voltage less than this affects boiler capacity, see Figure
3.
To remove Front Door for access to terminal blocks and
controls:
1. CAUTION – make sure Electrical Service to Boiler is disconnected.
2. Remove retaining screw at top of door.
3. Lower Door as far as possible, then push forward until Hinge Pins in lower corners slide out of the slots.
4. Raise one side of Door until Door will clear opening – pull forward for removal.
Repeat above in reverse for replacing Door.
Provisions are provided in the right side of the boiler
jacket for power input, circulator, and thermostat wiring, see Figure 1.
The power input legs are connected to the L1 and
L2 terminals on the terminal board on the control compartment of the boiler. The neutral leg is connected to the terminal marked N. Minimum recommended wire sizes are shown in Figure 1. A separate grounding conductor of at least #6AWG copper must be run to the
eld grounding lug on the control panel.
The Circulator is to be connected from its housing to
the terminals marked N and M on the Main Terminal Block using Flexible Conduit, see Figures 2 and 4. If the “QUICK CONNECT CIRCULATOR-PAK” is ordered as Optional Equipment from the Boiler Manufacturer, the Flexible Conduit for connecting the circulator will be furnished.
G. A Prewired Low Voltage Control System is furnished
with every “CARE-FREE” boiler.
1. All controls are furnished in a compartment at the front of the boiler for easy accessibility. In addition to the Transformer used to power the system, are the following: Circulator Relay, Heating Element Sequencers (one per Heating Element), Dual High Limit Control, Circulator Operation Selector Switch, Circulator Fuse and Heating Element Relays.
2. If the Circulator Fuse is blown, power is interrupted to the Transformer and hence, the control system de-energized. This action prevents the Heating Elements from coming on while the Circulator is inoperative.
A Circulator Operation Selector Switch provides for
either Continuous or Intermittent Circulator operation. With the switch in the “CONT.” position the Circulator Delay Control will be bypassed and the Circulator will operate continuously. The room Thermostat regulates only the operation of the Heating Elements in the boiler.
With the Circulator Switch in the “INT.” position, the
Thermostat will operate both the Circulator and the Heating Elements. Timing and wiring of the bimetal heaters in the Circulator Relay and Sequencers assures Circulator operation before and after Heating Elements are energized and de-energized, respectively. The Sequencers permit only one Heating Element at a time (from bottom to top) to be energized thus preventing a sudden inrush of electrical current. More detailed operation is described in subsequent pages.
Wiring of a one zone system is shown in Figure 4.
Figures 5 and 6 show wiring for zoned systems, the former when Zone Valves are used and the latter when multiple Circulators are used.
Figure 3: Boiler Capacity at Various Voltages
4
Page 5
SECTION II: OPERATING AND SERVICE INSTRUCTIONS
A. Intermittent Circulator Operation
1. ROOM TH ERMOSTAT CLOSES
2. CIRCULA TOR MOTOR ENERGIZE D
a. As the thermostat closes its contacts, a low
voltage circuit (24V.) is completed to the bimetal heater in the circulator relay (24A51). After a time delay of 15 seconds, the main contacts (120V.) of the circulator relay close to start the circulator.
3. HEA TING ELEM ENT #1 EN ERGIZED
a. Simultaneous with the completing of the circuit
for the circulator relay, two additional circuits are completed.
b. The rst circuit is for the Heating Element
Relays which pull in immediately and the second is for the bimetal heater in the #1 Heating Element Sequencer (24A54).
c. These two circuits will be energized only if the
boiler is not “OFF” on limit.
d. After a time delay of 45 seconds (30 seconds
after the circulator has started) the main and auxiliary contacts of the #1 Sequencer close; the main contacts (240V.) energizing heating element #1 and its pilot light (located at the bottom of the side panel), the auxiliary contacts (24V.) energizing the bimetal heater in the #2 Heating Element Sequencer.
4. HEA TING ELEM ENT #2 EN ERGIZED
a. 45 seconds after bimetal heater in #2 Heating
Element Sequencer is energized, its main contacts (240V.) and auxiliary contacts close; the main contacts energizing heating element #2 and its pilot light (3rd lowest in the boiler), the auxiliary contacts (24V.) energizing the bimetal heater in the #3 Heating Element Sequencer.
5. HEA TING ELEM ENT #3 EN ERGIZED
a. 45 seconds after bimetal heater in the #3 Heating
Element Sequencer is energized, its main contacts and auxiliary contacts close; the main contacts (240V.) energizing heating element #3 and its pilot light (2nd lowest in the boiler), the auxiliary contacts (24V.) energizing the bimetal heater in the #4 Heating Element Sequencer.
6. HEA TING ELEM ENT #4 EN ERGIZED
a. 45 seconds after bimetal heater in #4 Heating
Element Sequencer is energized, its main contacts and auxiliary contacts close, the main contacts (240V.) energizing heating element #4 and its pilot light (highest in the boiler) – nothing is connected to the auxiliary contacts.
7. ROOM TH ERMOSTAT OPENS
8. HEATING ELEMENTS DE-ENERG IZED
When the thermostat is satised and opens its
contacts, the low voltage circuits to the Heating Element Relay and the Heating Element Sequencers are broken. The Heating Element Relays “drop-out” immediately and totally de-energize the Heating Elements and pilot lights. After a time delay of 45 seconds, the main contacts of all the Sequencers “break” thus resetting the Heating Element Relays.
9. CIRCULA TOR MOTOR DE-ENERG IZED
Simultaneous with the breaking of the low voltage
circuit to the Heating Element Sequencers is the breaking of the low voltage circuit to the Circulator Relay by the opening of the thermostat contact. After a time delay of 90 seconds after all Heating Elements are “off” the bimetal heater opens the main contacts in the Circulator Relay thus stopping the circulator. When the boiler is zoned with circulator and switching relays as illustrated in Figure 6 on Page 8 the circulator switch must be in the “constant” position; therefore the circulator will not have any delay when the thermostat(s) closes or opens its contacts.
B. Continuous Circulator Operation
If the Circulator Switch (located in the control portion
of the Boiler Jacket) is placed in the “CONT.” position, the Circulator will run continuously and the Heating Elements will sequence as in steps 3-6 and 8 above.
C. Dual Limit Operation
The Dual Limit Control consists of two independently
adjustable temperature limits. The left hand adjustment is for the safety limit and should be set initially for 220°F. The lower right hand adjustment is for the operating limit and should be set for 210°F with a differential setting (upper right hand adjustment) of 10º. These adjustments may be varied to suit the individual installation, with minimum of 10° difference between the limit settings. If the setting of the operating Limit or the safety limit is reached, the Heating Elements only will be de-energized; the Circulator will continue to run. If the Circulator Switch is in the “INT.” position,
the Circulator runs until the thermostat is satised and
the main contacts on the Circulator Relay open.
WARNING
Before installation of the boiler is considered complete, the operation of the boiler controls should be checked, particularly the Operating & Safety Limit Controls.
5
Page 6
Figure 4: Wiring Diagram - Model E-4 Boilers
6
Page 7
D. Indicator Lights
There is an indicator light for each heating element.
If an indicator light is “on” it indicates its respective heating element is energized. If the light is “off” it indicates:
1. The heating element has not been energized.
2. The heating element sequencer is malfunctioning.
E. Built-In Air Eliminator
An air eliminator has been built into the top of the
electric boiler and a 3/4" tapping is provided with
nipple and tee for connection of Relief Valve and a oat
type Air Vent. See Figure 1.
Figure 5: Wiring Diagram - 3 Zone System
White-Rodgers 2 Wire Zone Valves
Figure 6: Wiring Diagram - 2 Zone System
Multiple Circulators
7
Page 8
LLiim
miitteedd
W
Waarrrraannttyy
FFoorrRReessiiddeennttiiaallGGrraaddeeWWaatteerraannddSStteeaammBBooiilleerrs
s
Using Cast Iron, Carbon Steel, Cast Aluminum,
or Stainless Steel Heat Exchangers
aannddPPaarrttss//AAcccceessssoorriiees
s
Subject to the terms and conditions set forth below, U.S. Boiler Company, Inc. Lancaster, Pennsylvania hereby extends the following limited warranties to the original owner of a residential grade water or steam boiler or U.S. Boiler Company, Inc. supplied parts and/or accessories manufactured and shipped on or after July 1, 2008:
ONE YEAR LIMITED WARRANTY ON RESIDENTIAL GRADE BOILERS AND PARTS / ACCESSORIES SUPPLIED BY U.S. BOILER COMPANY, INC.
U.S. Boiler Company, Inc. warrants to the original owner that its residential grade water and steam boilers and parts/accessories comply at the time of manufacture with recognized hydronic industry standards and requirements then in effect and will be free of defects in material and workmanship under normal usage for a period of one year from the date of original installation. If any part of a residential grade boiler or any part or accessory provided by U.S. Boiler Company, Inc. is found to be defective in material or workmanship during this one year period, U.S. Boiler Company, Inc. will, at its option, repair or replace the defective part.
HEAT EXCHANGER WARRANTIES
U.S. Boiler Company, Inc. warrants to the original owner that the heat exchanger of its residential grade boilers will remain free from defects in material and workmanship under normal usage for time period specified in the chart below of the original owner at the original place of installation. If a claim is made under this warranty during the “No
Charge” period from the date of original installation, U.S. Boiler Company, Inc. will, at its
option, repair or replace the heat exchanger. If a claim is made under this warranty after the expiration of the “No Charge” period from the date of original installation, U.S. Boiler Company, Inc. will, at its option and upon payment of the pro-rated service charge set forth below, repair or replace the heat exchanger. The service charge applicable to a heat exchanger warranty claim is based upon the number of years the heat exchanger has been in service and will be determined as a percentage of the retail price of the heat exchanger model involved at the time the warranty claim is made as follows:
NOTE: If the heat exchanger involved is no longer available due to product obsolescence or redesign, the value used to establish the retail price will be the published price as shown in the Burnham
Repair Parts Pricing where the heat exchanger last
appeared or the current retail price of the then nearest equivalent heat exchanger.
*MegaSteam Waterside Corrosion Warranty: U.S. Boiler Company, Inc. warrants the cast iron sections of the MegaSteam boiler to resist Temperature Induced Chloride Activated Graphitic Corrosion for a period of five years from the date of original installation. In the event that any cast iron section of a Mega Steam boiler fails due to this corrosion mechanism during this period, U.S. Boiler Company, Inc. will repair or replace, at its option, the cast iron section assembly.
LIFETIME NIPPLE LEAKAGE WARRANTY
U.S. Boiler Company, Inc. warrants the cast iron and steel nipples that join the cast iron boiler sections to be free of defects in material and workmanship for the lifetime of the original owner at the original place of installation. In the event that such nipples are found to be defective in material and workmanship during this period, U.S. Boiler Company, Inc. will repair or replace at its option, the cast iron section assembly.
ADDITIONAL TERMS AND CONDITIONS
1. Applicability: The limited warranties set forth above are extended only to the original owner at the original place of installation within the United States and Canada. These warranties are applicable only to boilers, parts, or accessories designated as residential grade by U.S. Boiler Company, Inc. and installed in a single or two-family residence and do not apply to commercial grade products.
2. Components Manufactured by Others: Upon expiration of the one year limited warranty on residential grade boilers, all boiler components manufactured by others but furnished by U.S. Boiler Company, Inc. (such as oil burner, circulator and controls) will be subject only to the manufacturer’s warranty, if any.
3. Proper Installation: The warranties extended by U.S. Boiler Company, Inc. are conditioned upon the installation of the residential grade boiler, parts, and accessories in strict compliance with U.S. Boiler Co., Inc. installation instructions. U.S. Boiler Company, Inc. specifically disclaims liability of any kind caused by or relating to improper installation.
4. Proper Use and Maintenance: The warranties extended by U.S. Boiler Company, Inc. conditioned upon the use of the residential grade boiler, parts, and accessories for its intended purposes and its maintenance accordance with U. S. Boiler Company, Inc. recommendations and hydronics industry standards. For proper installation, use, and maintenance, see all applicable sections of the
Installation and Operating, and Service Instructions Manual furnished with the unit.
5. This warranty does not cover the following: a. Expenses for removal or reinstallation. The homeowner will be responsible
for the cost of removing and reinstalling the alleged defective part or its replacement and all labor and material connected therewith, and transportation to and from U.S. Boiler Company, Inc.
b. Components that are part of the heating system but were not furnished by
U.S. Boiler Company, Inc. as part of the residential boiler.
c. Improper burner adjustment, control settings, care or maintenance.
d. This warranty cannot be considered as a guarantee of workmanship of an
installer connected with the installation of the U.S. Boiler Company, Inc. boiler, or as imposing on U.S. Boiler Company, Inc. liability of any nature for unsatisfactory performance as a result of faulty workmanship in the installation, which liability is expressly disclaimed.
e. Boilers, parts, or accessories installed outside the 48 contiguous United
States, the State of Alaska and Canada.
f. Damage to the boiler and/or property due to installation or operation of the
boiler that is not in accordance with the boiler installation and operating instruction manual.
g. Any damage or failure of the boiler resulting from hard water or scale
buildup in the heat exchanger.
h. Any damage caused by improper fuels, fuel additives or contaminated
combustion air that may cause fireside corrosion and/or clogging of the burner or heat exchanger.
i. Any damage resulting from combustion air contaminated with particulate
which cause clogging of the burner or combustion chamber including but not limited to sheetrock or plasterboard particles, dirt, and dust particulate.
j. Any damage, defects or malfunctions resulting from improper operation,
maintenance, misuse, abuse, accident, negligence including but not limited to operation with insufficient water flow, improper water level, improper water chemistry, or damage from freezing.
k. Any damage caused by water side clogging due to dirty systems or
corrosion products from the system. l. Any damage resulting from natural disaster. m. Damage or malfunction due to the lack of required maintenance outlined in
the Installation and Operating Manual furnished with the unit.
6. Exclusive Remedy: U.S. Boiler Company, Inc. obligation for any breach of these warranties is limited to the repair or replacement of its parts in accordance with the terms and conditions of these warranties.
7. Limitation of Damages: Under no circumstances shall U.S. Boiler Company, Inc. be liable for incidental, indirect, special or consequential damages of any kind whatsoever under these warranties, including, but not limited to, injury or damage to persons or property and damages for loss of use, inconvenience or loss of time. U.S. Boiler Company, Inc. liability under these warranties shall under no circumstances exceed the purchase price paid by the owner for the residential grade boiler involved. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you.
8. Limitation of Warranties: These warranties set forth the entire obligation of U.S. Boiler Company, Inc. with respect to any defect in a residential grade boiler, parts, or accessories and U.S. Boiler Company, Inc. shall have no express obligations, responsibilities or liabilities of any kind whatsoever other than those set forth herein. These warranties are given in lieu of all other express warranties.
ALL APPLICABLE IMPLIED WARRANTIES, IF ANY, INCLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ARE EXPRESSLY LIMITED IN DURATION TO A PERIOD OF ONE YEAR EXCEPT THAT IMPLIED WARRANTIES, IF ANY, APPLICABLE TO THE HEAT EXCHANGER IN A RESIDENTIAL GRADE BOILER SHALL EXTEND TO THE ORIGINAL OWNER FOR THE TIME SPECIFIED IN THE HEAT EXCHANGER SECTION SHOWN ABOVE AT THE ORIGINAL PLACE OF INSTALLATION. SOME STATES DO NOT ALLOW LIMITATION ON HOW LONG AN IMPLIED WARRANTY LASTS, SO THE ABOVE LIMITATION MAY NOT APPLY TO YOU.
PROCEDURE FOR OBTAINING WARRANTY SERVICE
In order to assure prompt warranty service, the owner is requested to complete and mail the Warranty Card provided with the product or register product online at www.burnham.com within ten days after the installation of the boiler, although
failure to comply with this request will not void the owner’s rights under these
warranties. Upon discovery of a condition believed to be related to a defect in material or workmanship covered by these warranties, the owner should notify the installer, who will in turn notify the distributor. If this action is not possible or does not produce a prompt response, the owner should write to U.S. Boiler Company, Inc.,
C/O Burnham, P.O. Box 3079, Lancaster, PA 17604, giving
full particulars in support of the claim. The owner is required to make available for inspection by U.S. Boiler Company, Inc. or its representative the parts claimed to be defective and, if requested by U.S. Boiler Company, Inc. to ship these parts prepaid to U.S. Boiler Company, Inc. at the above address for inspection or repair. In addition, the owner agrees to make all reasonable efforts to settle any disagreement arising in connection with a claim before resorting to legal remedies in the courts.
THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS AND YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE.
Years in Service 1-5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25+
Cast Iron Water 5 15 20 25 30 40 45 50 55 60 65 70 75
Cast Iron Steam*
Carbon Steel 5 15 20 25 30 40 45 50 55 60 65 70 75
Cast Aluminum 30 40 50 60 70 Stainless Steel 30 40 50 60 70
Service Charge as a % of Retail Price
No Charge 10
No Charge 10
No Charge 100
No Charge 100
No Charge 100
Loading...