Burnham Boilers C Brochure

Page 1
HIGH
EffIcIEncy
HEAVY
CONSTRUCTION
DURABLE
20  200 BHP
ASME SECTION IV
C Series
COMPACT PACKAGE BOILER
Page 2
C Series COMPACT PACKAGE BOILER
2
Pag e
America’s Boiler Company
The Burnham Commercial C Series compact packaged boiler was
designed with extensive manufacturing experience and is sold and
serviced through the largest and most experienced network of sales
representatives in the country. With a complete commercial product
oering an unmatched sales and technical support, it’s no wonder
why Burnham Commercial is America’s Boiler Company!
Packaged Boilers That Can Actually Fit Through A Door!
The C Series Firetube boiler is fully packaged and designed to provide
maximum cost and energy eciency. The C Series boiler ts through
any standard 36" x 80" doorway, up to 100HP. It eliminates the need
for any costly building alterations or dicult site assemblies. This
convenient size allows for easier and less expensive retrot or upgrade
of an existing boiler room.
A forced-draft unit, the C Series avoids the expense of a tall stack
and is much more economical to operate and install than atmospheric-
red boilers. The forced draft creates a more controlled combustion,
and a more thorough mixture of fuel and air is achieved resulting in
optimum eciency.
Other design features help maintain this durability and economy
over the years. While the original eciency of some other boilers can
decrease when outer wrappers develop air leaks and tubes cannot be
cleaned thoroughly, the C Series overcomes these problems. Built to
ASME standards, its outer shell of heavy welded steel boilerplate and
extra heavy tube sheets assure the continued airtight conditions
necessary for ecient combustion. Its heavy construction materials and
welded design assure durability and longevity that throw away designs
can’t oer. Opening the front ue door allows convenient access to the
retubes. By brushing out all of the retubes, the original eciency of
the boiler is restored in a matter of minutes. All tube ends are rolled in
accordance with the ASME code and are inspected for hydraulic tightness
by an independent insurance inspector, prior to shipping.
FRONT
REAR
These installation, operation and maintenance features add up to real
savings for you. Factory testing assures you that the boiler will deliver
clean, quiet and reliable heat from the day it’s installed.
Page 3
3
Pag e
Boiler HP
20 30 40 50 60 70 80
90 100 125 150 175 200
Boiler HP
20
30
40
50
60
70
80
90 100 125 150 175 200
10 psig
83.2
83.7
83.9
84.1
84.3
84.4
84.4
84.6
84.7
84.3
84.7
84.9
85.1
10 psig
86.0
86.7
86.8
87.2
87.4
87.5
87.5
87.8
88.0
87.2
87.8
88.0
88.3
EFFICIENCIES AND FEATURES
C Series Anticipated Eciencies
natural Gas
25% 50% 75% 100%
180°F Water
85.3
85.7
85.8
86.0
86.1
86.1
86.2
86.3
86.4
86.2
86.5
86.7
86.8
10 psig
83.5
83.8
83.9
84.1
84.3
84.3
84.3
84.6
84.8
84.1
84.6
84.8
85.0
180°F Water
85.3
85.4
85.5
85.7
85.9
85.8
85.9
86.1
86.3
85.7
86.1
86.3
86.6
#2 oIl
25% 50% 75% 100%
180°F Water
88.2
88.6
88.7
89.0
89.2
89.2
89.3
89.5
89.7
89.1
89.6
89.8
89.9
10 psig
86.2
86.7
86.8
87.1
87.4
87.3
87.4
87.8
88.0
87.0
87.6
87.9
88.2
180°F Water
87.9
88.3
88.3
88.6
88.9
88.9
88.9
89.3
89.6
88.6
89.2
89.4
89.7
10 psig
83.2
83.4
83.4
83.7
84.0
83.9
83.9
84.3
84.6
83.4
84.1
84.3
84.6
10 psig
86.0
86.4
86.4
86.8
87.1
87.1
87.1
87.6
87.9
86.4
87.2
87.4
87.8
180°F Water
84.8
84.9
84.9
85.1
85.4
85.3
85.4
85.7
86.0
84.9
85.5
85.7
86.0
180°F Water
87.5
87.8
87.9
88.2
88.6
88.5
88.5
89.0
89.3
87.9
88.7
88.9
89.2
10 psig
82.6
82.7
82.7
83.0
83.4
83.3
83.3
83.8
84.2
82.6
83.5
83.7
84.1
10 psig
85.4
85.8
85.9
86.3
86.7
86.6
86.7
87.2
87.6
85.9
86.7
87.0
87.4
180°F Water
84.1
84.1
84.1
84.4
84.8
84.7
84.7
85.2
85.6
84.1
84.9
85.1
85.5
180°F Water
86.9
87.2
87.3
87.7
88.1
88.0
88.0
88.6
89.0
87.3
88.2
88.4
88.8
Standard Features*
3-Pass retube construction
ASME Section IV construction
Water-cooled side walls
Rolled and ared tube ends
Front and rear ue doors
Oversized combustion chamber
Washout openings
Top/Vertical smokebox discharge
Lifting lugs
Enameled steel jacket
Fiberglass insulation
Structural steel base with extended skid to protect burner during shipment
* Burnham Commercial oers a wide array of optional equipment on the boiler and the burner.
Contact your local representative for options not shown here.
Optional Equipment*
Locking quadrant damper
Combustion relief door
Read/Horizontal smokebox discharge in lieu of top
Stack thermometer
Bolt-on front smokebox
Flue brush with handle
Beaded tubes
Drain valve
Fork-lift base
Pre-piped and wired gas train
Oversized gauges
Steam & water trim connections
Steam
Gauge glass set
Steam pressure gauge
Operating control
Manual-reset high limit
Firing rate control
Low re hold aquastat (when required)
Manual-reset probe-type low water cut-o
Pump control/low water cut-o
Water
Manual-reset low water cut-o
Pressure/Temperature gauge
Operating control
Manual-reset high limit
Firing rate control
Low re hold aquastat (when required)
Page 4
4
Pag e
C SERIES RATINGS AND DIMENSIONS
C Series Ratings
GROSS OUTPUT NET RATING SQ FT NET FIRING RATE
Boiler HP
20 30 40 50 60 70 80
90 100 125 150 175 200
A
30
30 34-1/2 34-1/2 34-1/2 34-1/2 34-1/2 34-1/2 34-1/2 50-3/4 50-3/4 50-3/4 50-3/4
B
66-3/8 66-3/8 73-7/8 75-3/8 75-3/8 78-1/2 78-1/2 78-1/2 78-1/2 94-3/4 94-3/4 94-3/4 94-3/4
C
75-5/8 82-5/8
90-1/8 100-5/8 113-1/8 114-5/8 125-1/8 135-1/8 145-1/8
138 154-1/2 170-3/4
187
MBH
670 1,004 1,339 1,674 2,009 2,343 2,678 3,013 3,348 4,184 5,021 5,858 6,695
Lbs/Hr
690 1,035 1,380 1,725 2,070 2,415 2,760 3,105 3,450 4,312 5,175 6,037 6,900
Water - MBH
582
873 1,164 1,455 1,747 2,038 2,329 2,620 2,911 3,638 4,366 5,094 5,822
Steam - MBH
520
780 1,040 1,299 1,559 1,819 2,079 2,339 2,599 3,248 3,898 4,548 5,198
Steam
2,166 3,249 4,332 5,415 6,497 7,580 8,663
9,746 10,829 13,533 16,242 18,950 21,658
Firing rates are nominal catalog rates based on 82% eciency ring natural gas and 84% ring #2 oil.
Higher eciencies can be expected as shown on page 3.
C Series Dimensions
A
OVERALL
WIDTH
Gas - MBH
816 1,225 1,633 2,041 2,449 2,858 3,266 3,674 4,082 5,102 6,123 7,144 8,165
#2 Oil - GPH
5.7
8.5
11.4
14.2
17.1
19.9
22.8
25.6
28.5
35.6
42.7
49.8
56.9
FRONT VIEW
Specications subject to change without notice.
All connections are threaded unless otherwise specied.
C
OVER SKID
PLAN VIEW
B
MAX. HEIGHT
SIDE VIEW
©2011 Burnham Commercial
Lancaster, PA 17604
Phone: 888.791.3790
www.burnhamcommercial.com
Form No. PL81465512000-8/11
Printed in the U.S.A.
Loading...