Burnham 4S Webster Low NOx Data Sheet

SERIES LN4S
Webster 30 PPM
Motor
Burner Model Sequence
Boiler Size Gas and Gas/#2 Oil Blower Oil Pump A/C
LN4S-100 LN4S-125 LN4S-150
JBX2-*-50 JBX3-*-50 JBX3-*-75 7.5 NA N/A Full Mod RM7840L/UV 1 psi 1 psi 3" 6"
Horsepower
5 NA N/A Full Mod RM7840L/UV 1 psi 1 psi 2.5 6" 5 NA N/A Full Mod RM7840L/UV 1 psi 1 psi 2.5 6"
[1]
Low Nox Burner Information
[2]
Firing
Gas and
Gas/#2 Oil
Safeguard
Minimum Gas
Pressure
Gas Train
Maximum
Gas Pressure
Size
FGR Line Size
LN4S-175 JBX3-*-75 7.5 NA N/A Full Mod RM7840L/UV 1 psi 1 psi 3" 6" LN4S-200 JBX3-*-100 10 NA N/A Full Mod RM7840L/UV 2 psi 5 psi 3" 6" LN4S-250 LN4S-300 LN4S-350
HDSX5-*-75A 7.5 NA N/A Full Mod RM7840L/UV 2 psi 5 psi 3" 8" HDSX7-*-150A 15 1/3 2 Full Mod RM7840L/UV 3 psi 7 psi 3" 8" HDSX7-*-200A 20 1/2 3 Full Mod RM7840L/UV 3 psi 7 psi 3" 8"
LN4S-400 HDSX7-*-200B 20 1/2 3 Full Mod RM7840L/UV 3 psi 7 psi 3" 8" LN4S-500 HDSX7-*-300B 30 1/2 5 Full Mod RM7840L/UV 3 psi 7 psi 3" 10" LN4S-600
HDSX9-*-400B 40 1/2 5 Full Mod RM7840L/UV 4 psi 7 psi 3" 10"
LN4S-700 HDSX9-*-500B 50 1/2 5 Full Mod RM7840L/UV 5 psi 7 psi 3" 10" LN4S-800 HDSX9-*-600B 60 1/2 7.5 Full Mod RM7840L/UV 5 psi 7 psi 3" 12"
Gas and Gas/#2Oil Firing Sequence
ALL MODELS: FULL MODULATION WITH PROVEN LOW FIRE START, SYNCHRONIZED FUEL/AIR CONTROL WITH MODULATING MOTOR.
NOTES:
[1]
EXPECTED EMISSIONS ARE 30 PPMVD OR LESS NOx (CORRECTED TO 3.0% O2) AND 400 PPMVD OR LESS CO (CORRECTED TO 3.0% O2) WHEN FIRING NATURAL GAS
[2]
ALL BLOWER AND AIR COMPRESSOR MOTORS AVAILABLE 208-230-460/60/3, INDICATE JOBSITE ON ORDER. OIL PUMP MOTORS ARE 230/60/1; CONSULT FACTORY
FOR OTHER VOLTAGES
15-Mar
SERIES LN4S
Burner Equipment
Equipment Fuel Description
Control Cabinet Gas, Gas/#2 Oil NEMA 1A with hinged door Control Voltage Transformer Gas, Gas/#2 Oil Included Motor Starter Gas, Gas/#2 Oil Magnetic starter with overload protection Fusing Gas, Gas/#2 Oil Control circuit only Ignition Gas, Gas/#2 Oil Gas/Electric pilot Signal Lights Gas, Gas/#2 Oil (4) - power on, fuel valve open, call for heat, flame failure Air Flow Safety Switch Gas, Gas/#2 Oil All Models Gas Train Gas, Gas/#2 Oil UL gas train for minimum inlet pressure indicated on Burner
Information table. Assembled, wired and mounted on unit consisting of the following: Manual shut off valve Gas pressure Regulator Manual leak test valve 100 & 125: Single Motorized Gas Valve with Proof of closure 150 & Larger: 2 Gas Valves Main Gas Valve: Motorized type Auxillary gas valve: Solenoid type High and Low gas pressure switches
Oil Pump Gas/#2 Oil Remote oil pump set with motor and accessories mounted on
boiler skid
Oil Firing Type Gas/#2 Oil 100 - 200: Pressure Atomizing
250 and larger: Air Atomizing
Pilot Gas Controls Gas, Gas/#2 Oil All models have gas/electric pilot, manual pilot shut-off valve, pilot
gas pressure regulator and solenoid gas valve Fuel Changeover Gas/#2 Oil Manual switch Flue Gas Recirculation Gas, Gas/#2 Oil Induced flue gas recirculation, no external fan is required
Loading...