Burnham 4S Power Flame Low NOx Data Sheet

SERIES LN4S
Power Flame 30 PPM
Motor
Burner Model Sequence
Boiler Size Gas and Gas/#2 Oil Blower Oil Pump A/C
LN4S-100 LN4S-125 LN4S-150 LN4S-175 LN4S-200 LN4S-250 LN4S-300 LN4S-350 LN4S-400 LN4S-500 LN4S-600 LN4S-700 LN4S-800
LNIC4-G(O)-25 LNIC4-G(O)-30 LNIC5-G(O)-30 LNIC6-G(O)-30
LNIC6-G(O)-30 LNICM9A-G(O)-30 LNICM9B-G(O)-30 LNICM9B-G(O)-30 LNICM10-G(O)-30
LNICM10B-G(O)-30 LNICM10C-G(O)-30 LNICM10C-G(O)-30
LNICM11-G(O)-30
7
7
Horsepower
3 1/2 N/A Full Mod RM7840L/UV 7.3" w.c. 14" w.c. 2" 8" 5 1/2 N/A Full Mod RM7840L/UV 9.9" w.c. 28" w.c. 2-1/2" 8"
1/2
1/2 N/A Full Mod RM7840L/UV 13.2" w.c. 28" w.c. 2-1/2" 8" 10 1/2 N/A Full Mod RM7840L/UV 9.9" w.c. 28" w.c. 3" 10" 10 1/2 N/A Full Mod RM7840L/UV 12.8" w.c. 28" w.c. 3" 10"
5 1/2 5 Full Mod RM7840L/UV 25.7" w.c. 10 psig 3" 10" 5 1/2 5 Full Mod RM7840L/UV 32.7" w.c. 10 psig 3" 10"
1/2
1/2 5 Full Mod RM7840L/UV 40.9" w.c. 10 psig 3" 12" 10 3/4 5 Full Mod RM7840L/UV 63.0" w.c. 10 psig 3" 12" 15 3/4 7 20 3/4 7 20 3/4 7 25 2 15 Full Mod RM7840L/UV 74.8" w.c. 10 psig 3"HF 16"
[2]
[1]
Low Nox Burner Information
Firing
1/2
1/2
1/2
Gas and
Gas/#2 Oil
Full Mod RM7840L/UV 91.0" w.c. 10 psig 3" 12" Full Mod RM7840L/UV 90.0" w.c. 10 psig 3" 16" Full Mod RM7840L/UV 94.0" w.c. 10 psig 3"/4" (1) 16"
Safeguard
Minimum Gas
Pressure
Gas Train
Maximum Gas
Pressure
Size
Gas and Gas/#2Oil Firing Sequence
ALL MODELS: FULL MODULATION WITH PROVEN LOW FIRE START, SYNCHRONIZED FUEL/AIR CONTROL WITH MODULATING MOTOR.
NOTES:
[1]
EXPECTED EMISSIONS ARE 30 PPMVD OR LESS NOx (CORRECTED TO 3.0% O2) AND 400 PPMVD OR LESS CO (CORRECTED TO 3.0% O2) WHEN FIRING NATURAL GAS
[2]
ALL BLOWER AND AIR COMPRESSOR MOTORS AVAILABLE 208-230-460/60/3, INDICATE JOBSITE ON ORDER. OIL PUMP MOTORS ARE 230/60/1; CONSULT FACTORY
FOR OTHER VOLTAGES
[3]
DUAL SIZE GAS TRAINS: LEAK TEST COCK, MAIN GAS VALVE AND AUXILIARY GAS VALVE ARE INDICATED BY THE FIRST NUMBER. GAS REGULATOR AND MAIN
SHUTOFF COCK ARE INDICATED BY THE SECOND NUMBER.
FGR Line Size
LN-3 7/9/2013
Equipment Fuel Description
Control Cabinet Gas, Gas/#2 Oil Control Voltage Transformer Gas, Gas/#2 Oil Motor Starter Gas, Gas/#2 Oil Fusing Gas, Gas/#2 Oil Ignition Gas, Gas/#2 Oil Signal Lights Gas, Gas/#2 Oil Air Flow Safety Switch Gas, Gas/#2 Oil Gas Train Gas, Gas/#2 Oil
Oil Pump Gas/#2 Oil
Oil Firing Type Gas/#2 Oil
Pilot Gas Controls Gas, Gas/#2 Oil
Fuel Changeover Gas/#2 Oil Flue Gas Recirculation Gas, Gas/#2 Oil
SERIES LN4S
Burner Equipment
NEMA 1A with hinged door Included Magnetic starter with overload protection Control circuit only Gas/Electric pilot (4) - power on, fuel valve open, call for heat, flame failure All Models UL gas train for minimum inlet pressure indicated on Burner Information table. Assembled, wired and mounted on unit consisting of the following: Manual shut off valve Gas pressure Regulator Manual leak test valve 100 & 125: Single Motorized Gas Valve with Proof of closure 150 & Larger: 2 Gas Valves Main Gas Valve: Motorized type Auxillary gas valve: Solenoid type High and Low gas pressure switches Remote oil pump set with motor and accessories mounted on boiler skid 100 - 200: Pressure Atomizing 250 and larger: Air Atomizing All models have gas/electric pilot, manual pilot shut-off valve, pilot gas pressure regulator and solenoid gas valve Manual switch Induced flue gas recirculation, no external fan is required
LN-4 7/9/2013