Burkert 8025 UNIVERSAL Quick Start Manual

Type 8025
UNIVERSAL
Quickstart
English - Deutsch - Français
We reserve the right to make technical changes without notice. Technische Änderungen vorbehalten. Sous réserve de modifications techniques.
© Bürkert SAS, 2012 - 2019
Type 8025 UNIVERSAL
1 ABOUT THE QUICKSTART .....................................................................4
2 INTENDED USE .............................................................................................5
3 BASIC SAFETY INFORMATION ............................................................5
4 GENERAL INFORMATION ........................................................................6
5 DESCRIPTION OF THE RATING PLATE ............................................7
6 TECHNICAL DATA ........................................................................................7
7 INSTALLATION AND WIRING ..............................................................11
8 ADJUSTMENT AND COMMISSIONING ....................................................37
9 PACKAGING, TRANSPORT .................................................................. 46
10 STORAGE ......................................................................................................46
11 DISPOSAL OF THE DEVICE ................................................................ 46
English
3
Type 8025 UNIVERSAL
About the Quickstart

1 ABOUT THE QUICKSTART

The▶Quickstart▶describes▶the▶life▶cycle▶of▶the▶device.▶Please▶keep▶ this▶Quickstart▶in▶a▶safe▶place,▶accessible▶to▶all▶users▶and▶any▶new▶ owners.▶
The Quickstart contains important safety information.
Failure▶to▶comply▶with▶these▶instructions▶can▶lead▶to▶hazardous▶ situations.▶Pay▶attention▶in▶particular▶to▶the▶chapters▶"3▶Basic▶ safety▶information"▶and▶"2▶Intended▶use".▶
▶ Whatever▶the▶version▶of▶the▶device,▶this▶Quickstart▶must▶be▶
read▶and▶understood.▶
The▶Quickstart▶explains▶how▶to▶install,▶set,▶and▶start-up▶the▶device. A▶detailed▶description▶of▶the▶device▶can▶be▶found▶in▶the▶related▶
Operating▶Instructions▶available▶on▶the▶internet▶under:▶ ▶www.burkert.com
1.1 Symbols used
DANger
Warns against an imminent danger.
▶ Failure▶to▶observe▶this▶warning▶results▶in▶death▶or▶in▶serious▶injury.▶
WArNINg
Warns against a potentially dangerous situation.
▶ Failure▶to▶observe▶this▶warning▶can▶result▶in▶serious▶injury▶or▶
even▶death.▶
CAUTION
Warns against a possible risk.
▶ Failure▶to▶observe▶this▶warning▶can▶result▶in▶substantial▶or▶minor▶
injuries.▶
NOTICe
Warns against material damage.
Indicates▶additional▶information,▶advice▶or▶important▶ recommendations.▶
Refers▶to▶information▶contained▶in▶these▶Quickstart▶or▶in▶ other▶documents.▶
▶ Indicates▶an▶instruction▶to▶be▶carried▶out▶to▶avoid▶a▶danger,▶a▶
warning▶or▶a▶possible▶risk. ▶→ Indicates▶a▶procedure▶to▶be▶carried▶out.▶
1.2 Definition of the word "device"
The▶word▶"device"▶used▶within▶this▶Quickstart▶refers▶to▶the▶trans­mitter▶type▶8025▶UNIVERSAL▶with▶serial▶numbers▶higher▶or▶equal▶to▶ 20▶000.▶
4
English
Type 8025 UNIVERSAL
Intended use

2 INTENDED USE

Use of the device that does not comply with the instructions could present risks to people, nearby installations and the environment.
The▶transmitter▶8025▶UNIVERSAL▶has▶been▶designed▶to▶process▶ a▶frequency▶signal,▶received▶from▶a▶flow▶sensor▶connected▶to▶the▶ transmitter.▶
▶ Use▶the▶device▶in▶compliance▶with▶the▶characteristics▶and▶
commissioning▶and▶use▶conditions▶specified▶in▶the▶contractual▶
documents▶and▶in▶the▶Operating▶Instructions.▶ ▶▶ Never▶use▶the▶device▶for▶security▶applications.▶▶ Use▶the▶device▶only▶in▶combination▶with▶foreign▶devices▶or▶for-
eign▶components▶recommended▶or▶approved▶by▶Bürkert.▶ ▶▶ Protect▶the▶device▶against▶electromagnetic▶interference,▶ultra-
violet▶rays▶and,▶when▶installed▶outdoors,▶the▶effects▶of▶climatic▶
conditions.▶ ▶▶ Only▶operate▶a▶device▶in▶perfect▶working▶order.▶ Store,▶transport,▶install▶and▶operate▶the▶device▶properly.▶▶ Only▶use▶the▶device▶as▶intended.▶

3 BASIC SAFETY INFORMATION

This▶safety▶information▶does▶not▶take▶into▶account▶any▶contingencies▶ or▶occurrences▶that▶may▶arise▶during▶installation,▶use▶and▶mainte­nance▶of▶the▶device.▶
The▶operating▶company▶is▶responsible▶for▶the▶respect▶of▶the▶local▶ safety▶regulations▶including▶for▶the▶staff▶safety.▶
Danger due to electrical voltage.
▶ If▶a▶12...36▶V▶DC▶energized▶version▶is▶installed▶either▶in▶a▶wet▶
environment▶or▶outdoors,▶all▶the▶electrical▶voltages▶must▶be▶of▶ max.▶35▶V▶DC.▶
▶ Before▶carrying▶out▶work▶on▶the▶system,▶disconnect▶the▶electri-
cal▶power▶for▶all▶the▶conductors▶and▶isolate▶it.▶
▶ All▶equipment▶connected▶to▶the▶device▶must▶be▶double▶insu-
lated▶with▶respect▶to▶the▶mains▶according▶to▶the▶standard▶IEC▶ 61010-1:2010.▶
▶ Observe▶all▶applicable▶accident▶protection▶and▶safety▶regula-
tions▶for▶electrical▶equipment.▶
Various dangerous situations
To▶avoid▶injury:▶
▶ Do▶not▶use▶the▶device▶in▶explosive▶atmospheres.▶▶ Do▶not▶use▶the▶device▶in▶an▶environment▶incompatible▶with▶the▶
materials▶it▶is▶made▶of.▶
▶ ▶Do▶not▶subject▶the▶device▶to▶mechanical▶stress.▶
English
5
Type 8025 UNIVERSAL
General information

4 GENERAL INFORMATION

Various dangerous situations
To▶avoid▶injury:▶
▶ Do▶not▶make▶any▶modifications▶to▶the▶device.▶▶ Prevent▶any▶unintentional▶power▶supply▶switch-on.▶▶ Only▶qualified▶and▶skilled▶staff▶can▶carry▶out▶the▶installation▶and▶
maintenance▶work.▶ ▶▶ Guarantee▶a▶defined▶or▶controlled▶restarting▶of▶the▶process,▶
after▶a▶power▶supply▶interruption.▶ ▶▶ Observe▶the▶general▶technical▶rules.▶
NOTICe
Elements / Components sensitive to electrostatic discharges
The▶device▶contains▶electronic▶components▶sensitive▶to▶electro­static▶discharges.▶They▶may▶be▶damaged▶if▶they▶are▶touched▶by▶an▶ electrostatically▶charged▶person▶or▶object.▶In▶the▶worst▶case▶sce­nario,▶these▶components▶are▶instantly▶destroyed▶or▶go▶out▶of▶order▶ as▶soon▶as▶they▶are▶activated.▶
▶ To▶minimise▶or▶even▶avoid▶all▶damage▶due▶to▶an▶electrostatic▶
discharge,▶take▶all▶the▶precautions▶described▶in▶standard▶
EN▶61340-5-1.▶ ▶▶ Also▶ensure▶that▶you▶do▶not▶touch▶any▶of▶the▶live▶electrical▶
components.▶
4.1 Manufacturer's address and international contacts
To▶contact▶the▶mannufacturer▶of▶the▶device,▶use▶following▶address:▶ Bürkert▶SAS▶ Rue▶du▶Giessen▶ BP▶21▶ F-67220▶TRIEMBACH-AU-VAL▶ You▶may▶also▶contact▶your▶local▶Bürkert▶sales▶office.▶ The▶addresses▶of▶our▶international▶sales▶offices▶are▶available▶on▶the▶
internet▶at:▶www.burkert.com
4.2 Warranty conditions
The▶condition▶governing▶the▶legal▶warranty▶is▶the▶conforming▶use▶of▶ the▶device▶in▶observance▶of▶the▶operating▶conditions▶specified▶in▶the▶ Operating▶Instructions.▶
4.3 Information on the Internet
You▶can▶find▶the▶Operating▶Instructions▶and▶technical▶data▶sheets▶ regarding▶the▶type▶8025▶UNIVERSAL▶at:▶www.burkert.com
6
English
Type 8025 UNIVERSAL
1
11
7
8
1213
35
10
4
2
9
Description of the rating platE

5 DESCRIPTION OF THE RATING PLATE

LFLOW 8025 PANEL SUPPLY: 12-36V... 210 mA DO1: 5-36V... 100mA AO1:4-20mA DO2&3: 2xRelay 30V and 42V peak or 60V... max. IP20
S/N 20 000
Made in France
00564417 W46MA
1.▶ Measured▶value▶
2.▶ Type▶of▶the▶device,▶housing▶
3.▶ Specifications▶of▶the▶digital▶output▶DO1▶(transistor)▶
4.▶ Specifications▶of▶the▶analogue▶output▶AO1▶
5.▶ Supply▶voltage▶and▶max.▶current▶consumption▶
6.▶ Protection▶class▶of▶the▶device▶
7.▶ Manufacturing▶code▶
8.▶ Conformity▶marking▶
9.▶ Certification
10.▶Warning:▶Before▶using▶the▶device,▶take▶into▶account▶the▶tech­nical▶specifications▶described▶in▶this▶Quickstart.▶
11.▶Specifications▶of▶the▶relay▶outputs▶DO2▶and▶DO3▶
12.▶Serial▶number▶
13.▶Article▶number
Fig. 1 : Rating plate of the device (example)
6

6 TECHNICAL DATA

6.1 Conditions of use
Ambiant temperature
Air humidity Height above see level Operating conditions Equipment mobility Use
Installation category Degree of pollution
Protection rating according▶to▶IEC/EN▶60529
•▶ wall-mounted▶version •▶ IP65▶
•▶ panel▶version •▶ front▶side▶IP65▶
1)
▶not▶evaluated▶by▶UL
–10...+60▶°C▶
<▶80▶%,▶non▶condensated▶ max.▶2000▶m▶ Continuous▶operation Fixed▶device Indoor▶and▶outdoor▶▶
(Protect▶the▶device▶against▶electro­magnetic▶interference,▶ultraviolet▶rays▶ and,▶when▶installed▶outdoors,▶against▶ the▶effects▶of▶climatic▶conditions)
Category▶I▶according▶to▶UL/EN▶61010-1 Degree▶2▶according▶to▶UL/EN▶61010-1
1)
,▶device▶wired,▶cable▶glands▶ tightened,▶cover▶lid▶screwed▶tight▶ and▶entry▶item▶nuts▶of▶the▶cable▶ glands▶tightened▶at▶a▶screwing▶ torque▶of▶1.5▶N·m▶
1)
,▶rear▶side▶IP20▶1)▶
English
7
Type 8025 UNIVERSAL
Measuring Equipment EXXXXXX
®
Technical data
6.2 Conformity to standards and directives
The▶applied▶standards,▶which▶verify▶conformity▶with▶the▶EU▶direc­tives,▶can▶be▶found▶on▶the▶EU-type▶examination▶certificate▶and/or▶the▶ EU▶declaration▶of▶conformity▶(if▶applicable).▶
UL-Certification
Devices▶with▶variable▶key▶PU01▶or▶PU02▶are▶UL-certified▶devices▶ and▶comply▶also▶with▶the▶following▶standards:▶
•▶ UL▶61010-1▶
•▶ CAN/CSA-C22.2▶n°61010-1▶
Identification on▶the▶device Certification Variable key
UL-recognized▶ PU01▶
UL-listed▶ PU02▶
6.3 Mechanical data
Part Material
Housing▶and▶cover,▶wall-mounted▶version▶ ABS▶ Cable▶glands,▶wall-mounted▶version▶ PA▶ Open▶housing,▶panel▶version▶ PC▶ Foil▶ polyester▶ 4▶screws▶ Stainless▶steel▶ Cable▶clips▶ PA▶
8
English
6.4 Dimensions
→ Please▶refer▶to▶the▶technical▶data▶sheets▶related▶to▶the▶device▶at:▶
www.burkert.com
6.5 Electrical data
Power supply 12...36 V DC
Power source (not▶supplied)▶
115/230 V AC power supply
•▶ frequency▶ •▶ 50/60▶Hz▶
•▶ supplied▶voltage▶ •▶ 27▶V▶DC,▶regulated▶
•▶ maximum▶current▶ •▶ 250▶mA▶
•▶ integrated▶protection▶ •▶ 250▶mA▶time-delay▶fuse▶
•▶ power •▶ 6▶VA▶
•▶ filtered▶and▶regulated
•▶ max.▶tolerance▶12▶V▶DC:▶–5▶%▶ or▶+10▶%
•▶ max.▶tolerance▶36▶V▶DC:▶±10▶%
•▶ Connection▶to▶main▶supply:▶ permanent▶(through▶external▶ SELV▶(safety▶extra-low▶voltage)▶ and▶through▶LPS▶(limited▶power▶ source)
•▶ Limited▶power▶source▶according▶ to▶UL▶/▶EN▶60950-1▶standards
•▶ or▶limited▶energy▶circuit▶ according▶to▶UL▶/▶EN▶61010-1,▶ Paragraph▶9.4
Type 8025 UNIVERSAL
Technical data
Current consumption
(without▶the▶consumption▶of▶ the▶4...20▶mA▶output)
•▶ version▶without▶ relays,▶energized▶with▶
12...36▶V▶DC
•▶ version▶with▶relays,▶ener­gized▶with▶12...36▶V▶DC
•▶ version▶without▶ relays,▶energized▶with▶ 115/230▶V▶AC
•▶ version▶with▶relays,▶ener­gized▶with▶115/230▶V▶AC
▶ ▶
•▶ 50▶mA▶(at▶12▶V▶DC)▶▶ and▶30▶mA▶(at▶36▶V▶DC)▶▶
•▶ 70▶mA▶(at▶12▶V▶DC)▶▶ and▶45▶mA▶(at▶36▶V▶DC)▶
•▶ 35▶mA▶▶ ▶
•▶ 50▶mA▶
Digital output DO1 (transistor)
•▶ type▶▶
•▶ function▶▶
•▶ frequency▶(f)▶
•▶ Electrical▶data▶▶
•▶ duty▶cycle▶if▶
0.6▶<▶f▶<▶300▶Hz▶
•▶ duty▶cycle▶if▶ 300▶<▶f▶<▶1500▶Hz▶
•▶ duty▶cycle▶if▶ 1500▶<▶f▶<▶2200▶Hz▶
•▶ protection▶
polarized,▶potential-free▶▶
•▶ NPN▶/▶PNP▶(wiring▶dependent),▶ open▶collector
•▶ pulse▶output▶(by▶default),▶user▶ configurable
•▶ 0.6...2200▶Hz
•▶ 5...36▶V▶DC,▶100▶mA▶max.,▶voltage▶ drop▶2.7▶V▶DC▶at▶100▶mA▶
•▶ >▶0.45▶▶
•▶ >▶0.4▶▶
•▶ <▶0.4▶▶
•▶ galvanically▶isolated,▶and▶ protected▶against▶over­voltages,▶polarity▶reversals▶and▶ short-circuits▶
English
9
Type 8025 UNIVERSAL
Technical data
Digital outputs DO2 and DO3 (relays)
•▶ operating▶▶
•▶ electrical▶data▶of▶the▶load▶ (non▶UL▶devices)▶
•▶ electrical▶data▶of▶the▶load▶ (UL▶devices)▶
▶ ▶
•▶ max.▶breaking▶capacity▶
•▶ life▶span▶
Current output AO1
•▶ specification▶▶ ▶
•▶ max.▶loop▶impedance▶
•▶ hysteresis▶(by▶ default),▶user▶con­figurable,▶normally▶open
•▶ 230▶V▶AC▶/▶3▶A▶▶ or▶40▶V▶DC▶/▶3▶A▶
•▶ max.▶30▶V▶AC▶and▶42▶Vpeak,▶3▶A▶▶ or▶max.▶60▶V▶DC,▶1▶A
To▶use▶the▶relay▶outputs▶in▶a▶wet▶ location,▶observe▶the▶following▶ DANGER▶safety▶instruction.
•▶ 750▶VA▶(resistive▶load)▶
•▶ min.▶100000▶cycles▶
•▶ 4...20▶mA,▶sink▶or▶source▶(wiring▶ dependent),▶22▶mA▶to▶indicate▶a▶ fault▶(can▶be▶activated)
•▶ 1300W▶at▶36▶V▶DC,▶▶ 1000W▶at▶30▶V▶DC,▶▶ 750W▶at▶24▶V▶DC,▶▶ 300W▶at▶15▶V▶DC,▶▶ 200W▶at▶12▶V▶DC
•▶ 900W▶if▶the▶device▶is▶energized▶ with▶115/230▶V▶AC
DANger
Danger due to the operation of the relay outputs of a UL device in a wet location.
▶ If▶a▶UL▶device▶is▶used▶in▶a▶wet▶location:▶
▶- energize▶the▶relay▶outputs▶with▶an▶alternating▶voltage▶of▶max.▶
16▶Vrms▶and▶22.6▶Vpeak.▶
▶- or▶energize▶the▶relay▶outputs▶with▶a▶direct▶voltage▶of▶
max.▶35▶V▶DC.▶
6.6 Specifications of the connected flow sensor
Signal originating from the remote sensor
•▶ type▶▶ ▶ ▶
•▶ frequency
•▶ max.▶voltage
Input impedance
•▶ pulse,▶sine-wave▶(typical▶sensitivity▶ 50▶mV▶peak-to-peak▶at▶250▶Hz),▶ "on/off",▶or▶standard▶voltage▶
0...5▶V▶DC
•▶ 0.6▶Hz▶to▶2.2▶kHz,▶can▶be▶adjusted
•▶ 36▶V▶DC
depends▶on▶the▶position▶of▶selector▶ "LOAD"▶on▶the▶electronic▶board▶of▶the▶
8025.▶See▶chap.▶7.4.11
10
English
Type 8025 UNIVERSAL
Installation and wiring
Power supply
supplied▶by▶the▶transmitter▶depending▶ on▶the▶position▶of▶selector▶"SENSOR▶ SUPPLY"▶of▶the▶8025,▶either:
•▶ 5▶V▶DC,▶30▶mA▶max.
•▶ (L+)-12V:▶supply▶voltage▶(L+)▶of▶the▶ transmitter▶minus▶12▶V▶DC▶(minus▶
12.5▶V▶DC▶max.),▶80▶mA▶max.
•▶ L+:▶supply▶voltage▶(L+)▶of▶the▶ transmitter▶(minus▶1.5▶V▶DC▶max.),▶ 140▶mA▶max.▶(if▶the▶device▶is▶ener­gized▶with▶12...36▶V▶DC),▶▶ 80▶mA▶max.▶(if▶the▶device▶is▶ener­gized▶with▶115/230▶V▶AC)

7 INSTALLATION AND WIRING

7.1 Safety instructions
DANger
Risk of injury due to electrical voltage.
▶ If▶a▶12...36▶V▶DC▶energized▶version▶is▶installed▶either▶in▶a▶wet▶
environment▶or▶outdoors,▶all▶the▶electrical▶voltages▶must▶be▶of▶ max.▶35▶V▶DC.▶
▶ Disconnect▶the▶electrical▶power▶for▶all▶the▶conductors▶and▶iso-
late▶it▶before▶carrying▶out▶work▶on▶the▶system.▶
▶ All▶equipment▶ connected▶ to▶ the▶wall-mounted▶ or▶ panel▶ version▶
of▶the▶flow▶transmitter▶8025▶ UNIVERSAL▶must▶be▶double▶insu­lated▶in▶ relation▶ to▶ the▶mains▶ in▶ accordance▶ with▶IEC▶ standard▶ 61010-1:2010.▶
▶ Observe▶all▶applicable▶accident▶protection▶and▶safety▶regula-
tions▶for▶electrical▶equipment.▶
WArNINg
Risk of injury due to non-conforming installation.
▶ The▶electrical▶installation▶can▶only▶be▶carried▶out▶by▶qualified▶
and▶skilled▶staff▶with▶the▶appropriate▶tools.▶
▶ Fit▶a▶circuit▶breaker▶or▶a▶switch▶to▶the▶electrical▶installation▶in▶
which▶the▶device▶is▶installed.▶
▶ Install▶the▶circuit▶breaker▶or▶switch▶in▶a▶place▶which▶is▶easy▶to▶
reach.
▶ Identify▶the▶circuit▶breaker▶or▶switch▶as▶the▶electrical▶power▶cut-
off▶system▶for▶the▶device.▶
English
11
Type 8025 UNIVERSAL
95
95
Installation and wiring
WArNINg
Risk of injury due to non-conforming installation.
▶ Install▶appropriate▶overload▶safety▶devices.▶For▶a▶version▶ener-
gized▶by▶115/230▶V▶AC,▶insert▶overcurrent▶protective▶devices▶in▶ the▶live▶conductor▶and▶in▶the▶neutral▶conductor.
▶ Do▶not▶energize▶a▶device,▶version▶12...36▶V▶DC,▶with▶an▶alter-
nating▶voltage▶or▶with▶a▶direct▶voltage▶higher▶than▶36▶V▶DC.▶
▶ Observe▶the▶standard▶NF▶C▶15-100▶/▶IEC▶60364.▶
WArNINg
Risk of injury due to unintentional switch on of power supply or uncontrolled restarting of the installation.
▶ Take▶appropriate▶measures▶to▶avoid▶unintentional▶activation▶of▶
the▶installation.▶
▶ Guarantee▶a▶set▶or▶controlled▶restarting▶of▶the▶process▶subse-
quent▶to▶any▶intervention▶on▶the▶device.▶
NOTICe
Risk of damage to the device if the incorrect supply voltage is applied.
▶ Energize▶the▶device▶with▶a▶supply▶voltage▶in▶accordance▶with▶the▶
position▶of▶the▶selector.▶See▶Fig.▶11,▶chap.▶7.4.5.▶
Protect▶this▶device▶against▶electromagnetic▶interference,▶ ultraviolet▶rays▶and,▶when▶installed▶outdoors,▶the▶effects▶of▶ the▶climatic▶conditions.▶
7.2 Installation of a panel version
Install▶the▶panel▶version▶of▶the▶device▶in▶a▶cabinet▶with▶a▶ protection▶class▶at▶least▶IP54▶to▶ensure▶a▶degree▶of▶pol­lution▶2▶inside▶the▶cabinet.▶
→ To▶cut▶the▶opening▶in▶the▶cabinet▶door,▶use▶the▶supplied▶drilling▶
jig,▶respecting▶the▶dimensions▶indicated▶in▶Fig.▶2.▶
80 76 50
80
76
50
Fig. 2 : Dimensions of the drilling jig [mm]
→ Insert▶the▶4▶screws▶in▶the▶housing▶(from▶the▶front).▶→ Insert▶the▶seal▶on▶the▶external▶threads▶of▶the▶4▶screws▶(rear▶of▶
the▶housing).▶
→ Put▶the▶assembly▶on▶the▶cutout,▶electronics▶turned▶to▶the▶inside▶
of▶the▶cabinet.▶ ▶→ Put▶the▶4▶washers▶on▶the▶4▶screws.▶→ Put▶a▶nut▶on▶each▶of▶the▶4▶screws▶and▶tighten▶the▶nuts▶to▶secure▶
the▶device▶to▶the▶cabinet.▶
12
English
Type 8025 UNIVERSAL
Installation and wiring
Washer
Nut
Cable▶clip
Seal
Fig. 3 : Installation of a 8025, panel version
Screws
7.3 Installation of a wall-mounted version
NOTICe
Risk of material damage if the cable glands are not tightly screwed on the housing
▶ Before▶installing▶the▶wall-mounted▶housing▶on▶its▶support,▶
tighten▶the▶nuts▶of▶the▶entry▶item▶of▶the▶cables▶glands▶at▶a▶torque▶ of▶1.5▶N·m.▶
The▶flow▶transmitter▶in▶a▶wall-mounted▶version▶has▶4▶holes▶in▶the▶ bottom▶of▶the▶housing.▶
→ Remove▶the▶covering▶strips▶covering▶the▶screws.▶
FLOW
Covering▶strips
Nut▶of▶the▶entry▶item
Fig. 4 : Location of the fastening nuts and the covering strips
→ Loosen▶the▶4▶screws▶and▶open▶the▶cover▶to▶get▶access▶to▶the▶
holes▶[1].▶
ENTER
0....9
English
13
11
106 mm
SOURCE SINK
CURRENT
BINARY
Iout
L+ L- PE P- P+
Univ
(AO1)
PULSE
Supply
Batch
DO1
12..36Vdc
NC
PE ISOG DO4 DI4 DI3 DI2 DI1
INPUT
PULSE
FLOW
SENSOR
PE PEPE
SENSOR
+5V
L+
SENSOR TYPE
SUPPLY
(L+)-12V
COIL NPN/PNP
COIL/PNP
470
2.2K 39K
LOAD
SUPPLY
+-
NC
213PE
OFFON
NPN/PNP
DO2
COIL
DO3
1 1
T 250 mA
56789 10
230V
230V
230V
106 mm
LN
LN
Fig. 5 : Installation of a wall-mounted version
→ Secure▶the▶housing▶to▶the▶support▶respecting▶the▶dimensions▶
indicated▶in▶Fig.▶5.▶ ▶→ Wire▶according▶to▶instructions▶in▶chap.▶7.4.▶→ Close▶the▶housing▶and▶tighten▶the▶4▶screws▶of▶the▶cover.▶
7.4 Wiring
DANger
Risk of injury due to electrical voltage.
▶ If▶a▶12...36▶V▶DC▶energized▶version▶is▶installed▶either▶in▶a▶wet▶
environment▶or▶outdoors,▶all▶the▶electrical▶voltages▶must▶be▶of▶ max.▶35▶V▶DC.▶
▶ Disconnect▶the▶electrical▶power▶for▶all▶the▶conductors▶and▶iso-
late▶it▶before▶carrying▶out▶work▶on▶the▶system.▶
▶ All▶equipment▶connected▶to▶the▶device▶must▶be▶double▶insulated▶in▶
relation▶to▶the▶mains▶in▶accordance▶with▶IEC▶standard▶61010-1:2010.▶
Type 8025 UNIVERSAL
Installation and wiring
DANger
Risk of injury due to electrical voltage.
▶ Observe▶all▶applicable▶accident▶protection▶and▶safety▶regula-
tions▶for▶electrical▶equipment.▶
DANger
Danger due to the operation of the relay outputs of a UL device in a wet location.
▶ If▶a▶UL▶device▶is▶used▶in▶a▶wet▶location:
▶- energize▶the▶relay▶outputs▶with▶an▶alternating▶voltage▶of▶max.▶
16▶Vrms▶and▶22.6▶Vpeak.
▶- or▶energize▶the▶relay▶outputs▶with▶a▶direct▶voltage▶of▶
max.▶35▶V▶DC.
NOTICe
Risk of damage to the device if the incorrect supply voltage is applied.
▶ Energize▶the▶device▶with▶a▶supply▶voltage▶in▶accordance▶with▶the▶
position▶of▶the▶selector.▶See▶Fig.▶11,▶chap.▶7.4.5.▶
The▶device▶can▶be▶damaged▶if▶it▶is▶not▶tight.▶
•▶ Insert▶the▶supplied▶stopper▶gaskets▶into▶the▶unused▶cable▶ glands▶to▶ensure▶the▶tightness▶of▶the▶device.▶
14
English
Type 8025 UNIVERSAL
Installation and wiring
Only▶move▶the▶selectors▶when▶the▶power▶supply▶is▶off.▶
Protect▶this▶device▶against▶electromagnetic▶interference,▶ ultraviolet▶rays▶and,▶when▶installed▶outdoors,▶the▶effects▶of▶ the▶climatic▶conditions.▶
For▶a▶correct▶operation▶of▶the▶device,▶respect▶the▶following▶ recommendations▶during▶the▶electrical▶installation:
•▶ Make▶sure▶the▶installation▶is▶equipotential.▶See▶ chap.▶7.4.2.▶
•▶ Do▶not▶install▶the▶cables▶near▶high▶voltage▶or▶high▶ frequency▶cables;▶if▶a▶combined▶installation▶cannot▶ be▶avoided,▶a▶minimum▶clearance▶of▶30▶cm▶should▶be▶ respected.▶
For▶a▶device▶fed▶at▶12...36▶V▶DC,▶respect▶the▶following▶ recommendations▶for▶the▶electrical▶installation:
•▶ Use▶a▶filtered▶and▶regulated▶12...36▶V▶DC▶power▶supply.▶ The▶circuit▶has▶to▶be▶safety▶extra▶low▶voltage▶(SELV),▶with▶ a▶safe▶energy▶level.▶
The▶power▶supply▶of▶the▶device▶can▶be▶damaged▶if▶it▶is▶not▶ protected.
•▶ Protect▶the▶device▶power▶supply▶by▶means▶of▶a▶300▶mA▶ fuse▶and▶a▶switch.
The▶power▶supply▶of▶a▶transistor▶output▶can▶be▶damaged▶if▶ it▶is▶not▶protected.
•▶ Protect▶the▶power▶supply▶of▶each▶transistor▶output▶by▶ means▶of▶a▶125▶mA▶fuse.
The▶relays▶can▶be▶damaged▶if▶not▶protected.
•▶ Protect▶the▶relays▶by▶means▶of▶a▶max.▶3▶A▶fuse▶and▶a▶ circuit▶breaker▶(depending▶on▶the▶process).▶
•▶ Do▶not▶apply▶both▶a▶dangerous▶voltage▶and▶a▶safety▶extra­low▶voltage▶to▶the▶relays.▶
7.4.1 Specifications of the connection cables
Tab. 1 : Specifications of the cables and wires for the direct wiring to the
Specification of the cables and the con­ductors (not▶supplied)
terminal blocks of a panel-mounted version
Recommended value
Shielded▶cable yes Length▶of▶the▶cable max.▶50▶m Operating▶temperature,▶UL▶device min.▶90▶°C Operating▶temperature,▶non▶UL▶device min.▶80▶°C▶ Cross▶section▶of▶the▶conductors 0.2...1.5▶mm
2
English
15
Loading...
+ 33 hidden pages