Burkert 2732 User Manual [en, de, fr]

Type 2702, 2712, 2730,
2731, 2731 K, 2732
Additional information for use in the hazardous area
If Bürkert devices of type:
• 2702, 2712, 2730, 2731, 2731 K and 2732 are used in the potentially explosive area:
Zone (gas) 1 and 2; Zone (dust) 21 and 22 follow the instructions in this additional information as well as the respective operating instructions (see page 2).
Zusatzinformation für den Einsatz im Ex-Bereich
Für Bürkert Geräte des Typs:
• 2702, 2712, 2730, 2731, 2731 K und 2732 müssen beim Einsatz im explosionsgefährdeten Bereich:
Zone (Gas) 1 und 2; Zone (Staub) 21 und 22 zusätzlich zur jeweiligen Bedienungsanleitung die Hinweise dieser Zusatzinformation beachtet werden (siehe Seite 3).
Information supplémentaire concernant l'utilisation dans une zone à risque d'explosion
Pour les appareils Bürkert des types :
• 2702, 2712, 2730, 2731, 2731 K et 2732 utilisés dans des zones présentant des risques d'explosion, telles que les :
zones (gas) 1 et 2; ainsi que les zones (poussière) 21 et 22, il convient de respecter les instructions de service correspondantes mais également les consignes de cette information supplémentaire (voir page 4).
Type label / Typenschild / Plaque signalétique
Warnung: In EX-Bereichen darf die Oberfläche
ACHTUNG: In Ex-Bereichen darf die Oberfläche nur mit einem feuchten Tuch gereinigt werden
II 2G c T4 IP65/67 II 2D c T135°C
© 2011 Bürker t Werke GmbH Supplement 1107/01_EU-ML_00809542 / Original: DE
nur mit einem feuchten Tuch gereinigt werden
Warning: In Hazardous Areas the surface
CAUTION: In Hazardous Areas the surface
may only be cleaned with a wet towel
may only be cleaned with a wet towel
deutsch englishfrançais
1
Type 2702, 2712, 2730,
2731, 2731 K, 2732
Basic Safety Instructions
Danger!
Danger of explosion caused by electrostatic charge!
If there is a sudden discharge from electrostatically charged devices or persons, there is a danger of explosion in the EX area.
• Take appropriate measures to prevent electrostatic charges in the EX area.
• Clean the device surface by gently wiping it with a damp or antistatic cloth.
Media in the EX area:
If explosive media are used, this may create an additional risk of explosions!
Contol unit in the EX area:
The control unit may restrict use in an explosive atmosphere. Follow operating instructions for controller.
Cleaning in the EX area:
Test cleaning agent for approval in explosive atmosphere.
Temperature ranges in the EX area
Max. T
Environment
DN 25 > DN 25
Medium
T6 85 °C -10 ... +45 °C -10 ... +55 °C
T5 100 °C -10 ... +60 °C -10 ... +70 °C
T4 135 °C -10 ... +95 °C -10 ... +105 °C
140
130 120 110
Temperature class T5
100
Temperature class T6
90 80 70 60 50 40 30 20
Ambiente temperature [°C]
10
2
Temperature class T4
10 20 30 40 50 60 70 80 90 100 110 120 1300
Medium temperature [°C]
english
Valves DN 25 Valves > DN 25
Loading...