Operating Instructions Type 0330/0331
Voltage 12V or 24V
UL / UR valid with
class 2 power supply only
Design:
2-way solenoid valve, direct acting, normally closed (Circuit function A), normally open (Circuit function B).
3-way solenoid valve, direct acting, normally closed (Circuit function C), normally open (Circuit function D), mixer function (Circuit
function E) or diverter function (Circuit function F).
Seal Materials and Fluids handled:
See Table1.
Fluid and Ambient Temperature:
For Hazardous Locations Div. 1 (T4 rated)
Max. Ambient Temperature 104 °F (40 °C)
Max. Fluid Temperature 194 °F (90 °C)
For Hazardous Locations Div. 2 and Ordinary Locations:
See Table1.
Pressure Range:
Maximum inlet pressure see label on valve.
Type 0330: PTFE tape is recommended for sealing ports.
Mounting is accomplished by means of four M4 x 8 mm tapped
holes located on the valve underside.
Type 0331: Ports A (B) are coded on side of body. For common
pressure, align "A(B)" markings on valve and manifold. Valve operation C an D valves can be mounted on the same manifold but the
manual override buttons will point in opposite directions.
To remove valve from manifold loosen only the two unsealed
screws. Manifolds can be connected together with nipples.
Blanking plugs, Order No. 0315-1016, should be screwed into
the unused ports. Manifolds can be fixed in position using M5
screws.
Marking (example):
Body Material
BR = Brass
SS = Stainless Steel
Seal Material
EPDM = EPDM
NBR = NBR
FKM = FKM
Circuit Function
A = 2-way - Normally Closed
B = 2-way - Normally Open
C = 3-way - Normally Closed
D = 3-way - Normally Open
E = Mixer Function
F = Diverter Function
Recorder No.
Voltage / Frequency / Power Consumption
Manual override:
The manual override can be retained in position if, after depressing
the button, it is turned in a clockwise direction.
Assembly instructions:
The conduit connector on the coil (4) must be supported against
torque during the assembly using appropriate tools (1) (i.e. pliers,
gripper...) (for example a gripper).
While tightening for example a fitting (3) into the conduit connector attention must be paid to the fact that a max. torque of 20Nm
(177lbf in) is not exceeded.
Seal materials
Fluid Temperatures [°F] NBR EPDM FKM
Air
Water
Neutral gas
Light oil
LP-gas
Operating Instructions 1103/13_EU-EN_00893144
Fluid
Ambient
Fluid
Ambient
Fluid
Ambient
Fluid
Ambient
Fluid
Ambient
+ 32 to + 176
+ 32 to + 131
+ 41 to + 176
+ 32 to + 131
+ 32 to + 176
+ 32 to + 131
+ 32 to + 140
+ 32 to + 131
+ 32 to + 140
+ 32 to + 131
Maximum Pressure
Approvals
The valve is FM/CSA approved as
Explosion Proof valve for Hazardous Locations
Class I, Division 1, Group A, B, C, D
Class II, Division 1, Group E, F, G
Class III, Division 1 and 2
Operating Temperature T 4
or FM approved as
Nonincendive for Hazardous Locations
Class I, Division 2, Group A, B, C, D
Class II, Division 2, Group F, G
Class III, Division 1 and 2
Operating Temperature T 4A
CSA approved for Ordinary Locations
UL Recognized and UL Listed for General
Purpose and Fire Protection Services.
See label on the valve.
- 22 to + 194
+ 14 to + 131
+ 41 to + 194
+ 14 to + 131
- 22 to + 194
+ 14 to + 131
+ 32 to + 194
+ 32 to + 131
+ 41 to + 194
+ 32 to + 131
+ 32 to + 194
+ 32 to + 131
+ 32 to + 140
+ 32 to + 131
+ 32 to + 140
+ 32 to + 131
Operating Instructions
Bürkert Company Locations
Wiring Diagram
Electrical Connection Type 2509
Power*
Ground (green dot)
Power*
* Orientation is not important
Electrical Connection:
Ensure supply voltage/frequency corresponds with that on label.
Voltage tolerance is ± 10 %.
Available Electrical Connections see “Marking”.
Wiring diagram see above.
For this product to be considered UL-listed and CSA approved
for General Purpose and FM approved for Hazardous Locations
Division 2, it must be in conjunction with the type 2509 cable plug
connector (Electrically Operated Valves Parts, YSYI2).
The connector and gasket must be assembled to the valve with the
screw provided after the connection of the wire leads. This valve
and connector assembly is delivered together and is to be used as
one unit.
For valves to be used in Intrinsically Safe Applications the positive
pole is identified by a “+” on the pin or wire No. 1 has to be connected to the “+”.
See Control Drawing for the Rules of Interconnection.
Warning:
All valves to be used in Intrinsically Safe Applications must be
clearly marked as Intrinsically Safe Apparatus.
Trouble-Shooting:
Check port connections, minimum operating pressure differential
if required and supply voltage. Ensure pilot hole in piston is clear
and pilot bore in the valve outlet is not abstracted. If core does not
pull in, check for short circuit, coil burn-out or foreign matter impeding core movement. A jammed or missing core causes the coil
to overheat in the case of AC supply.
Warning:
These products are designed to operate in a wide variety of applications, it is the user’s responsibility to select a model that is
appropriate for the application. This product is designed to be
installed only by suitably qualified and trained personnel.
Specifications should not be exceeded under any circumstances.
The torque for the terminal screw on type 2509 is 0,5 Nm
(4,4 lbf-in.).
Germany
Contact address:
Bürkert Fluid Control Systems
Sales Center
Chr.-Bürkert-Str. 13-17
D-74653 Ingelfingen
Tel. + 49 (0) 7940 - 10 91 111
Fax + 49 (0) 7940 - 10 91 448
E-mail: info@de.buerkert.com
International
Contact addresses can be found on the Internet at:
Changes made to this product will render any applicable warranty
null and avoid.
Specifications subject to change without notice.
Any questions? Please call Bürkert Contromatic Technical Service
at (949) 223 31 00.
www.burkert.com