Bryant 581Jx14 series Installation Instructions Manual

581J*14
SINGLE PACKAGE ROOFTOP, GAS HEATING/ELECTRIC COOLING WITH PURON SIZE 14
R
(R--410A) REFRIGERANT
Installation Instructions
NOTE: Read the entire instruction manual before starting
TABLE OF CONTENTS
SAFETY CONSIDERATIONS 2....................
Rated Indoor Airflow (cfm) 3.....................
INSTALLATION 6...............................
Jobsite Survey 6................................
Step 1 -- Plan for Unit Location 6..................
Roof Mount 6...............................
Step 2 -- Plan for Sequence of Unit Installation 7......
Curb--Mount Installation 7.....................
Pad--Mount Installation 7......................
Frame--Mount Installation 7....................
Step 3 -- Inspect Unit 7...........................
Step 4 -- Provide Unit Support 7...................
Roof Curb Mount 7..........................
Slab Mount (Horizontal Units Only) 9...........
Alternate Unit Support 9......................
Step 5 -- Field Fabricate Ductwork 9................
Step 6 -- Rig and Place Unit 9.....................
Positioning on Curb 10.......................
Step 7 -- Convert to Horizontal and Connect Ductwork 11
Step 8 -- Install Outside Air Hood 11...............
Economizer Hood Removal and Setup —
Factory Option 11...........................
Two Position Damper Hood Removal and Setup —
Factory Option 11...........................
Economizer Hood and Two--Position Hood 12.....
Step 9 -- Install Flue Hood 13.....................
Step 10 -- Install Gas Piping 13....................
Factory--Option Thru--Base Connections
(Gas Connections) 14.........................
Step 11 -- Install External Condensate Trap and Line 16..
Step 12 -- Make Electrical Connections 16...........
Field Power Supply 16........................
All Units 18................................
Units without Factory--Installed
Non--Fused Disconnect 18.....................
Units with Factory--Installed
Non--Fused Disconnect 18.....................
Convenience Outlets 19.......................
Factory--Option Thru--Base Connections
(Electrical Connections) 21....................
Units without Thru--Base Connections 21.........
Field Control Wiring 21.......................
Thermostat 21...............................
Unit without Thru--Base Connection Kit 22.......
Heat Anticipator Settings 22...................
Low Ambient Control (Factory Option) 22...........
Variable Frequency Drive (VFD) 2--Speed Indoor Fan Motor System (Factory Option) 22.
EconoMi$er X -- Ultra Low Leak Economizer
(Factory Option) 22.............................
Perfect Humidityt Control Connections 23........
Perfect Humidity -- Space RH Controller 23.......
RTU Open Control System 25.....................
Supply Air Temperature (SAT) Sensor 28.........
Outdoor Air Temperature (OAT) Sensor 29.......
EconoMi$er2 29.............................
Field Connections 29..........................
Space Temperature (SPT) Sensors 29............
Economizer Controls 30........................
Indoor Air Quality (CO
Outdoor Air Quality Sensor 31.................
Space Humidity Sensor or Humidistat 31.........
Smoke Detector/Fire Shutdown (FSD) 32.........
Connecting Discrete Inputs 32..................
Communication Wiring -- Protocols 33............
General 33.................................
Local Access 34.............................
RTU Open Troubleshooting 34.................
Outdoor Air Enthalpy Control 35.................
Differential Enthalpy Control 35................
Return Air Enthalpy Sensor 35.................
Smoke Detectors 36...........................
Step 13 -- Adjust Factory--Installed Options 42........
Step 14 -- Install Accessories 42...................
)Sensor 30.............
2
START--UP CHECKLIST 43.......................
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloths for brazing operations and have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and appropriate national electrical codes (in USA, ANSI/NFPA70, National Electrical Code (NEC); in Canada, CSA C22.1) for special requirements.
581J*14
It is important to recognize safety information. This is the safety--alert symbol
unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
. When you see this symbol on the
!
WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect gas piping from unit when leak testing at pressure greater than 0.5 psig (3450 Pa). Pressures greater than 0.5 psig (3450 Pa) will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than 0.5 psig (3450 Pa), it must be replaced before use. When pressure testing field--supplied gas piping at pressures of 0.5 psig (3450 Pa) or less, a unit connected to such piping must be isolated by closing the manual gas valve.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury or death.
Before performing service or maintenance operations on unit, always turn off main power switch to unit and install lock(s) and lockout tag(s). Unit may have more than one power switch.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury, death and/or equipment damage.
Puronr (R--410A) refrigerant systems operate at higher pressures than standard R--22 systems. Do not use R--22 service equipment or components on Puron refrigerant equipment.
!
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could cause personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal.
Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing air conditioning equipment.
2
Rated Indoor Airflow (cfm)
The table to the right lists the rated indoor airflow used for the AHRI efficiency rating for the units covered in this document.
Model Number Full Load Airflow (cfm)
581J*14D/F/K/M 4375
1234567891011 12
581JE14D240A3A0AA
Model
581J = High Efficiency Gas Heat Packaged Rooftop Unit
Voltage
E = 460-3-60 P = 208/230-3-60 T = 575-3-60
Cooling Tons
14 - 12.5 ton
Refirg. System/Gas Heat Options
D = Two Stage Cooling Models F = Two Stage Cooling Models and Stainless Steel Gas Heat Exchanger K = Two Stage Cooling Models and Perfect Humidity M = Two Stage Cooling Models/SS HX Heat and Perfect Humidity
Heat Level
Standard/Stainless Steel 150 = 150,000 180 = 180,000 240 = 240,000
Coil Options (Outdoor – Indoor – Hail Guard)
A = Al/Cu – Al/Cu B = Precoat Al/Cu – Al/Cu C = E-coat Al/Cu – Al/Cu D = E-coat Al/Cu – E-Coat Al/Cu E = Cu/Cu – Al/Cu F = Cu/Cu – Cu/Cu M = Al/Cu – Al/Cu – Louvered Hail Guards N = Precoat Al/Cu – Al/Cu – Louvered Hail Guards P = E-coat Al/Cu – Al/Cu – Louvered Hail Guards Q = E-coat Al/Cu – E-coat Al/Cu – Louvered Hail Guards R = Cu/Cu – Al/Cu – Louvered Hail Guards S = Cu/Cu – Cu/Cu – Louvered Hail Guards
TM
Fig. 1 -- 581J 14 Model Number Nomenclature (Example)
13
14 15 16 17
Packaging and 2-Speed Indoor Fan Motor
A = Standard Packaging, electro mech. controls that require W7212 EconoMi$er IV B = LTL Packaging, electro mech. controls that require W7212 EconoMi$er IV C = Standard Packaging, electro mech. controls that require W7220 EconoMi$er X D = Standard Packaging and 2-speed Indoor Fan Motor (VFD) Controller E = LTL Packaging and 2-speed Indoor Fan Motor (VFD) Controller F = LTL Packaging, electro mech. controls that require W7220 EconoMi$er X
Factory Installed Options
0A = None NOTE: See the 581J 3 to 15 ton Price Pages for a complete list of factory installed options.
Outdoor Air Options
A = None B = Temperature Econo w/ Barometric Relief and W7212 Econo Controller E = Temperature Econo w/ Barometric Relief, CO2 and W7212 Econo Controller H = Enthalpy Econo w/ Barometric Relief and W7212 Econo Controller L = Enthalpy Econo w/ Barometric Relief, CO2 and W7212 Econo Controller Q = Motorized 2 Position Damper w/ Barometric Relief U = Temperature Ultra Low Leak Econo w/ Barometric Relief W = Enthalpy Ultra Low Leak Econo w/ Barometric Relief
Indoor Fan Options
1 = Standard Static Option – Belt Drive 2 = Medium Static Option – Belt Drive 3 = High Static Option – Belt Drive C = High Static Option with High Efficiency Motor – Belt Drive
581J*14
C150074
3
581J*14
Fig. 2 -- Unit Dimensional Drawing – 14 Size Unit
C11338
4
581J*14
Fig. 2 -- Unit Dimensional Drawing – 14 Size Unit (cont.)
C11339
5
C
D
B
A
581J*14
LOCATION DIMENSION CONDITION
48---in (1219 mm)
A
B
C
D
NOTE: Unit not designed to have overhead obstruction. Contact Application Engineering for guidance on any application
18---in (457 mm) 18---in (457) mm 12---in (305 mm)
42---in (1067 mm) 36---in (914 mm) Special
36---in (914 mm) 18---in (457 mm)
48---in (1219 mm) 42---in (1067 mm) 36---in (914 mm) Special
planning overhead obstruction or for vertical clearances.
Unit disconnect is mounted on panel No disconnect, convenience outlet option Recommended service clearance Minimum clearance
Surface behind servicer is grounded (e.g., metal, masonry wall) Surface behind servicer is electrically non---conductive (e.g., wood, fiberglass) Check sources of flue products within 10---ft of unit fresh air intake hood
Side condensate drain is used Minimum clearance
No flue discharge accessory installed, surface is combustible material Surface behind servicer is grounded (e.g., metal, masonry wall, another unit) Surface behind servicer is electrically non---conductive (e.g., wood, fiberglass) Check for adjacent uni ts or building fresh air intakes within 10- --ft (3 m ) of this unit’s flue outlet
Fig. 3 -- Service Clearance Dimensional Drawing
INSTALLATION
Jobsite Survey
Complete the following checks before installation.
1. Consult local building codes and the NEC (National Electrical Code) ANSI/NFPA 70 for special installa­tion requirements.
2. Determine unit location (from project plans) or select unit location.
3. Check for possible overhead obstructions which may interfere with unit lifting or rigging.
Step 1 — Plan for Unit Location
Select a location for the unit and its support system (curb or other) that provides for at least the minimum clearances required for safety. This includes the clearance to combustible surfaces, unit performance and service access below, around and above unit as specified in unit drawings. See Fig. 3.
NOTE: Consider also the effect of adjacent units.
C12322
Unit may be installed directly on wood flooring or on Class A, B, or C roof--covering material when roof curb is used
Do not install unit in an indoor location. Do not locate air inlets near exhaust vents, relief valves, or other sources of contaminated air.
Although unit is weatherproof, avoid locations that permit water from higher level runoff and overhangs to fall onto the unit.
Select a unit mounting system that provides adequate height to allow installation of condensate trap per requirements. Refer to Step 11 — Install External Condensate Trap and Line – for required trap dimensions.
Roof Mount —
Check building codes for weight distribution requirements. Unit operating weight is shown in Table 1.
6
Table 1 – Operating Weights
581J*14
COMPONENT UNITS LB (KG)
Base Unit 1430 (649)
Economizer
Vertical 100 (45)
Horizontal 115 (52)
Perfect Humidity™ System 62 (28)
Powered Outlet 32 (15)
Curb
14---in/356 mm 180 (82)
24---in/610 mm 235 (107)
Step 2 — Plan for Sequence of Unit Installation
The support method used for this unit will dictate different sequences for the steps of unit installation. For example, on curb--mounted units, some accessories must be installed on the unit before the unit is placed on the curb. Review the following for recommended sequences for installation steps.
Curb--mounted installation —
Install curb Install field--fabricated ductwork inside curb Install accessory thru--base service connection package
(affects curb and unit) (refer to accessory installation instructions for details)
Prepare bottom condensate drain connection to suit planned condensate line routing (refer to Step 9 for details)
Rig and place unit Install outdoor air hood Install condensate line trap and piping Make electrical connections Install other accessories
Pad--mounted installation —
Prepare pad and unit supports Check and tighten the bottom condensate drain
connection plug Rig and place unit Convert unit to side duct connection arrangement Install field--fabricated ductwork at unit duct openings Install outdoor air hood Install condensate line trap and piping Make electrical connections Install other accessories
Frame--mounted installation —
Frame--mounted applications generally follow the sequence for a curb installation. Adapt as required to suit specific installation plan.
Step 3 — Inspect Unit
Inspect unit for transportation damage. File any claim with transportation agency.
Confirm before installation of unit that voltage, amperage and circuit protection requirements listed on unit data plate agree with power supply provided.
On units with hinged panel option, check to be sure all latches are snug and in closed position.
Locate the carton containing the outside air hood parts; see Figs. 11 & 12. Do not remove carton until unit has been rigged and located in final position.
Step 4 — Provide Unit Support
Roof Curb Mount —
Accessory roof curb details and dimensions are shown in Fig. 4. Assemble and install accessory roof curb in accordance with instructions shipped with the curb.
NOTE: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 4. Improperly applied gasket can also result in air leaks and poor unit performance.
581J*14
7
581J*14
Fig. 4 -- Roof Curb Details
C10772
8
Curb should be level. This is necessary for unit drain to function properly. Unit leveling tolerances are show in Fig. 5. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
C
A
B
MAXIMUM ALLOWABLE
DIFFERENCE IN. (MM)
A-B
0.5” (13)
B-C
1.0” (25)
A-C
1.0” (25)
C10001
Fig. 5 -- Unit Leveling Tolerances
Step 5 — Field Fabricate Ductwork
NOTE: Cabinet return-air static pressure (a negative
condition) shall not exceed 0.35 in. wg (87 Pa) with economizer or 0.45 in. wg (112 Pa) without economizer.
For vertical ducted applications, secure all ducts to roof curb and building structure. Do not connect ductwork to unit.
Fabricate supply ductwork so that the cross sectional dimensions are equal to or greater than the unit supply duct opening dimensions for the first 18 in. (458 mm) of duct length from the unit basepan.
Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through unconditioned spaces must be insulated and covered with a vapor barrier.
Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb and
not to the unit.
IMPORTANT: If the unit’s gas connection and/or electric and control
wiring is to be routed through the basepan and the unit is equipped with the factory--installed Thru--the--Base service option see the following sections:
S Factory--Option Thru--Base Connections
(Gas Connection) on page 11
S Factory--Option Thru--Base Connections
(Electrical Connections) on page 18
If using the field--installed Thru--the--Base accessory follow the instructions provided with the accessory kit.
NOTE: If gas and/or electrical connections are not going to occur at this time, tape or otherwise cover the fittings so that moisture does not get into the building or conduit in the interim.
Slab Mount (Horizontal Units Only) —
Provide a level concrete slab that extends a minimum of 6 in. (150 mm) beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.
Alternate Unit Support (InLieuofCurborSlabMount)—
A non--combustible sleeper rail can be used in the unit curb support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4--in. x 4--in. (102 mm x 102 mm) pads on each side.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.
!
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in damage to roofing materials.
Membrane roofs can be cut by sharp sheet metal edges. Be careful when placing any sheet metal parts on such roof.
Step 6 — Rig and Place Unit
When the unit is ready to be rigged and no longer will be lifted by a fork truck, the wood protector under the basepan must be removed. Remove 4 screws from each base rail. Wood protector will drop to the ground. See instructions on the unit base rails.
Keep unit upright and do not drop. Spreader bars are required. Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Table 1 and Fig. 6 for additional information.
Lifting holes are provided in base rails as shown in Fig. 6. Refer to rigging instructions on unit.
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
All panels must be in place when rigging. Unit is not designed for handling by fork truck.
CAUTION
581J*14
Before setting the unit onto the curb, recheck gasketing on curb.
9
“B”
914 - 1371
( 36” - 54” )
“C”
PLACE ALL SEAL STRIP IN PLACE BEFORE PLACING UNIT ON ROOF CURB.
“A”
SEE DETAIL “A”
MAX WEIGHT
LB KG IN MM IN MM IN MM
581J*14
UNIT
581J*14 2215 1009 116.0 2945 62.5 1590 59.5 1510
NOTES:
1. SPREADER BARS REQUIRED — Top damage will occur if spreader bars are not used.
2. Dimensions in ( ) are in millimeters.
3. Hook rigging shackles through holes in base rail, as shown in detail “ A.” Holes in base rails are centered around the unit center of gravity. Use wooden top to prevent rigging s traps from damaging unit .
PositioningonCurb—
For full perimeter curbs CRRFCURB074A00 and 075A00, the clearance between the roof curb and the front and rear
1
base rails should be the curb and the end base rails should be
/4in (6.4 mm). The clearance between
1
/2in (13 mm). For retrofit applications with curbs CRRFCURB003A01 and 4A01, the unit should be position as shown in Fig. 7.
5
Maintain the 15.5 in (394 mm) and 8
5
clearances and allow the 22
/16in (567 mm) dimension to
/8in (220 mm)
float if necessary.
DUCT END
A B C
Fig. 6 -- Rigging Details
DIMENSIONS
Original Position
DETAIL “A”
C10774
New Position (moved 12.5 in.)
Fig. 7 -- Retrofit Installation Dimensions
If the alternative condensate drain location through the bottom of the unit is used in conjunction with a retrofit curb, the hole in the curb must be moved 12.5 in (320 mm) towards the end of the unit. (See Fig. 8.)
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
Remove all shipping materials and top skid. Remove extra center post from the condenser end of the unit so that the condenser end of the unit matches Figs. 27 and 28. Recycle or dispose of all shipping materials.
C10003
C10904
Fig. 8 -- Alternative Condensate Drain Hole Positions
IMPORTANT:
If the unit has the factory--installed Thru--the--Base option, make sure to complete installation of the option before placing the unit on the roof curb.
See the following sections:
S Factory--Option Thru--Base Connections
(Gas Connection) on page 11
S Factory--Option Thru--Base Connections
(Electrical Connections) on page 18
NOTE: If gas and/or electrical connections are not
going to occur at this time, tape or otherwise cover the fittings so that moisture does not get into the building or conduit in the interim.
10
Step 7 — Convert to Horizontal and Connect Ductwork (when required)
Unit is shipped in the vertical duct configuration. Unit without factory--installed economizer or return air smoke detector option may be field--converted to horizontal ducted configuration using accessory CRDUCTCV002A00. To convert to horizontal configuration, remove screws from side duct opening covers and remove covers.
Discard the supply duct cover. Install accessory CRDUCTCV002A00 to cover the vertical supply duct opening. Use the return duct cover removed from the end panel to cover the vertical return duct opening.
Field--supplied flanges should be attached to horizontal duct openings and all ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof or building openings with counter flashing and mastic in accordance with applicable codes.
Do not cover or obscure visibility to the unit’s informative data plate when insulating horizontal ductwork.
FILTER ACCESS PANEL
INDOOR COIL ACCESS PANEL
Fig. 10 -- Typical Access Panel Locations
Remove Hood Parts
Cut Plastic Ties (2) Places
Economizer
C10004
581J*14
Fig. 9 -- Horizontal Conversion Panels
Step 8 — Install Outside Air Hood
Economizer Hood Removal and Setup -­Factory Option —
1. The hood is shipped in knock--down form and located in the return air compartment. It is attached to the economizer using two plastic tie--wraps.
2. To gain access to the hood, remove the filter access panel. (See Fig. 10.)
3. Locate and cut the (2) plastic tie--wraps, being careful to not damage any wiring. (See Fig. 11.)
4. Carefully lift the hood assembly through the filter access opening and assemble per the steps outlined in Economizer Hood and Two–Position Hood on page 10.
C06108
C10005
Fig. 11 -- Economizer Hood Package Location
Two Position Damper Hood Removal and Setup -­Factory Option —
1. The hood is shipped in knock--down form and assembled to a metal support tray using plastic stretch wrap. Located in the return air compartment, the assembly’s metal tray is attached to the basepan and also attached to the damper using two plastic tie--wraps.
2. To gain access to the hood, remove the filter access panel. (See Fig. 10.)
3. Locate the (2) screws holding the metal tray to the basepan and remove. In order to remove the screws, it may be necessary to remove the panel underneath the two--position damper. Remove the two screws. Locate and cut the (2) plastic tie--wraps securing the assembly to the damper. (See Fig. 12.) Be careful to not damage any wiring or cut tie--wraps securing any wiring.
11
4. Carefully lift the hood assembly (with metal tray) through the filter access opening and assemble per the steps outlined in Economizer Hood and Two–Position Hood on page 10.
5. If removed, reattach the panel under the damper.
Hood Parts
LEFT HOOD SIDE
SCREW
TOP PAN EL
INDOOR COIL ACCESS PANEL
Plastic Tie Wrap Qty (2)
581J*14
Screws for Metal Tray Qty (2)
Fig. 12 -- Two--Position Damper Hood Package Location
Economizer Hood and Two--Position Hood — NOTE: If the power exhaust accessory is to be installed
on the unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter for use in the power exhaust hood assembly.
1. The indoor coil access panel will be used as the top of the hood. If the panel is still attached to the unit, re­move the screws along the sides and bottom of the panel. See Fig. 13.
SIDE PAN EL
C10006
HOOD DIVIDER
C10008
Fig. 14 -- Economizer Hood Construction
3. Remove the shipping tape holding the economizer barometric relief damper in place.
4. Insert the hood divider between the hood sides. See Fig. 14 and 15. Secure hood divider with 3 screws on each hood side. The hood divider is also used as the bottom filter rack for the aluminum filter.
5. Attach the post that separates the filters with the screws provided.
6. Open the filter clips which are located underneath the hood top. Insert the aluminum filters into the bottom filter rack (hood divider). Push the filter into position past the open filter clips. Close the filter clips to lock the filters into place. See Fig. 15.
7. Install the two rain deflectors on the edge of the hood topasshowninFig.13.
RAIN DEFLECTORS
CAULK
INDOOR COIL ACCESS PAN EL
HERE
Fig. 13 -- Indoor Coil Access Panel Relocation
2. Swing out indoor coil access panel and insert the
hood sides under the panel (hood top). Be careful not to lift the panel too far as it might fall out. Use the screws provided to attach the hood sides to the hood top. Use screws provided to attach the hood sides to the unit. See Fig. 14.
TOP PAN EL
INDOOR COIL ACCESS PAN EL
C10007
BAROMETRIC RELIEF
DIVIDER
CLEANABLE ALUMINUM FILTER
FILTER
OUTSIDE AIR
HOOD
Fig. 15 -- Economizer Filter Installation
8. Caulk the ends of the joint between the unit top panel and the hood top as shown in Fig. 13.
9. Replace the filter access panel.
12
FILTER CLIP
C10009
Step 9 — Install Flue Hood
R
The flue hood is shipped screwed to the basepan beside the burner compartment access panel. Remove the panel below the control box access panel to access the flue hood shipping location. Using screws provided, install flue hood and screen in location shown in Fig. 16.
Table 3 – Liquid Propane Supply Line Pressure Ranges
UNIT MIN MAX
581J*14 11.0 in. wg (2740 Pa) 13.0 in. wg (3240 Pa)
The gas supply pipe enters the unit at the burner access panel on the front side of the unit, through the long slot at the bottom of the access panel. The gas connection to the
3
unit is made to the
/4--in. FPT gas inlet port on the unit gas
valve.
CONTROL BOX ACCESS PANEL
FLUE HOOD
C10804
Fig. 16 -- Flue Hood Details
Step 10 — Install Gas Piping
Installation of the gas piping must be accordance with local building codes and with applicable national codes. In U.S.A., refer to NFPA 54/ANSI Z223.1 National Fuel Gas Code (NFGC). In Canada, installation must be accordance with the CAN/CSA B149.1 and CAN/CSA B149.2 installation codes for gas burning appliances.
This unit is factory equipped for use with Natural Gas fuel at elevations up to 2000 ft (610 m) above sea level. Unit may be field converted for operation at elevations above 2000 ft (610 m) and/or for use with liquefied petroleum fuel. See accessory kit installation instructions regarding these accessories.
NOTE: In U.S.A. the input rating for altitudes above 2000 ft (610 m) must be derated by 4% for each 1000 ft (305 m) above sea level. In Canada the input rating must be derated by 10% for altitudes of 2000 ft (610 m) to 4500 ft. (1372 m) above sea level.
For natural gas applications, gas pressure at unit gas connection must not be less than 5 in. wg (1250 Pa) or greater than 13 in. wg (3240 Pa) while the unit is operating. For liquified petroleum applications, the gas pressure must not be less than 11 in. wg (2740 Pa) or greater than 13 in. wg (3240 Pa) at the unit connection.
Table 2 – Natural Gas Supply Line Pressure Ranges
UNIT MIN MAX
581J*14 5.0 in. wg (1250 Pa) 13.0 in. wg (3240 Pa)
!
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in damage to equipment.
When connecting the gas line to the unit gas valve, the installer MUST use a backup wrench to prevent damage to the valve.
Install a gas supply line that runs to the unit heating section. Refer to the NFPA 54/NFGC or equivalent code for gas pipe sizing data. Size the gas supply line to allow for a maximum pressure drop of 0.5--in wg (124 Pa) between gas regulator source and unit gas valve connection when unit is operating at high--fire flow rate.
The gas supply line can approach the unit in three ways: horizontally from outside the unit (across the roof), thru--curb/under unit basepan (accessory kit required) or through unit basepan (factory--option or accessory kit required). Consult accessory kit installation instructions for details on these installation methods. Observe clearance to gas line components per Fig. 17.
X
9” MINIMUM CLEARANCE
BASE UNIT
BASE RAIL
FOR PANEL REMOVAL
MANUAL GAS SHUTOFF VALVE
48” MINIMUM
ROOF CURB
NFGC – National Fuel Gas Code
Field supplied.
*
NOTE: Follow all local codes.
STEEL PIPE
NOMINAL DIAMETER
(in.)
1
/
2
3
/
or 1
4
1
1
/
or larger
4
LEGEND
GAS REGULATOR
*
DRIP LEG
PER NFGC
FABRICATED
SPACINGOFSUPPORTS
X DIMENSION
(ft)
6 8
10
*
*
FIELD-
SUPPORT
FROM GAS METE
*
C11121
Fig. 17 -- Gas Piping Guide
581J*14
13
Factory--Option Thru--Base Connections (Gas Connection) —
3
This serviceconnection kit consists of a
1
fitting (stainless steel), a
1
and a 1
/2--in electrical bulkhead connector, connected to an
/2--in electrical bulkhead connector
/4--in NPTgasadapter
“L” bracket covering the embossed (raised) section of the unit basepan in the condenser section. See Fig. 18.
1
/2” ELECTRICAL BULKHEAD CONNECTOR
3
/4” NPT GAS ADAPTER FITTING
11/2” ELECTRICAL BULKHEAD CONNECTOR
581J*14
Fig. 18 -- Thru--the--Base Option, Shipping Position
C10905
CONNECTOR PLATE ASSEMBLY
GASKET
C10906
Fig. 19 -- Completing Installation of Thru--the--Base
Option
1. Remove the “L” bracket assembly from the unit (see Fig. 18).
2. Cut and discard the wire tie on the gas fitting. Hand tighten the fitting if it has loosened in transit.
3. Remove connector plate assembly from the “L” bracket and discard the “L” bracket, but retain the washer head screws and the gasket (located between the “L” bracket and the connector plate assembly
NOTE: Take care not to damage the gasket, as it is reused in the following step.
4. Place the gasket over the embossed area in the basepan, aligning the holes in the gasket to the holes in the basepan. See Fig. 19.
5. Install the connector plate assembly to the basepan using 8 of the washer head screws.
NOTE: If gas and/or electrical connections are not going to occur at this time, tape or otherwise cover the fittings so that moisture doesnot get into the building or conduit in theinterim.
The thru--base gas connector has male and female threads. The male threads protrude above the basepan of the unit; the female threads protrude below the basepan.
Check tightness of connector lock nuts before connecting gas piping.
3
Install a fitting. Attach a
/4--in NPT street elbow on the thru--base gas
3
/4--in pipe nipple with minimum length of 16--in (406 mm) (field--supplied) to the street elbow and extend it through the access panel at the gas support bracket. (See Fig. 20.)
THRU-BASE GAS FITTING
3
/4-in NPT STREET ELBOW
GAS SUPPORT BRACKET
C10806
Fig. 20 -- Gas Line Piping
Other hardware required to complete the installation of the gas supply line will include a manual shutoff valve, a sediment trap (drip leg) and a ground--joint union. A pressure regulator valve may also be required (to convert gas pressure from pounds to inches of pressure). The manual shutoff valve must be located within 6--ft (1.83 m) of the unit. The union, located in the final leg entering the unit, must be located at least 9--in (230 mm) away from the access panel to permit the panel to be removed for service. If a regulator valve is installed, it must be located a minimum of 4--ft (1220 mm) away from the unit’s flue outlet. Some municipal codes require that the manual shutoff valve be located upstream of the sediment trap. See Fig. 21 and 22 for typical piping arrangements for gas piping that has been routed through the sidewall of the curb. See Fig. 23 for typical piping arrangement when thru--base is used. Ensure that all piping does not block access to the unit’s main control box or limit the required working space in front of the control box.
14
Loading...
+ 30 hidden pages