Bryant Preferred Series, 581J 04 Series, 581J 06 Series, 581J 05 Series Installation Instructions Manual

Preferred™ Series 581J 04-06 Single Package Rooftop Gas Heating/Electric Cooling Unit with Puron® (R-410A) Refrigerant
Installation Instructions
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
Model Number Nomenclature and Dimensions . . . . . . . . . 3
Rated Indoor Airflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Step 1 — Plan for Unit Location . . . . . . . . . . . . . . . . . . . . 10
• ROOF MOUNT
Step 2 — Plan for Sequence of Unit Installation . . . . . . . 10
• CURB-MOUNTED INSTALLATION
• PAD-MOUNTED INSTALLATION
• FRAME-MOUNTED INSTALLATION
Step 3 — Inspect Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Step 4 — Provide Unit Support . . . . . . . . . . . . . . . . . . . . . 10
• ROOF CURB MOUNT
• SLAB MOUNT (HORIZONTAL UNITS ONLY)
• ALTERNATE UNIT SUPPORT (IN LIEU OF CURB OR SLAB MOUNT)
Step 5 — Field Fabricate Ductwork. . . . . . . . . . . . . . . . . . 12
Step 6 — Rig and Place Unit. . . . . . . . . . . . . . . . . . . . . . . . 12
• POSITIONING ON CURB
Step 7 — Convert to Horizontal and Connect Ductwork
(When Required). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Step 8 — Install Outside Air Hood . . . . . . . . . . . . . . . . . . 14
• ECONOMIZER AND TWO POSITION DAMPER HOOD PACKAGE REMOVAL AND SETUP (FACTORY OPTION)
• ECONOMIZER AND TWO-POSITION HOOD
Step 9 — Units with Hinged Panels Only . . . . . . . . . . . . . 15
Step 10 — Install Flue Hood. . . . . . . . . . . . . . . . . . . . . . . . 15
Step 11 — Install Gas Piping . . . . . . . . . . . . . . . . . . . . . . . 16
• FACTORY-OPTION THRU-BASE CONNECTIONS (GAS CONNECTIONS)
Step 12 — Install External Condensate Trap and
Line. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Step 13 — Make Electrical Connections . . . . . . . . . . . . . . 19
• FIELD POWER SUPPLY
• UNITS WITH FACTORY-INSTALLED NON-FUSED DISCONNECT
• UNITS WITHOUT FACTORY-INSTALLED NON­FUSED DISCONNECT
• ALL UNITS
• CONVENIENCE OUTLETS
• FACTORY-OPTION THRU-BASE CONNECTIONS (ELECTRICAL CONNECTIONS)
• UNITS WITHOUT THRU-BASE CONNECTIONS (ELECTRICAL CONNECTIONS)
• FIELD CONTROL WIRING
• THERMOSTAT
• HEAT ANTICIPATOR SETTINGS
• PERFECT HUMIDITY™ CONTROL CONNECTIONS
• LOW AMBIENT CONTROL (FACTORY OPTION)
• INTEGRATED GAS CONTROLLER
Economi$er® X (Factory Option) . . . . . . . . . . . . . . . . . . . 27
• SYSTEM COMPONENTS
• SPECIFICATIONS
•INPUTS
•OUTPUTS
• ENVIRONMENTAL
• ECONOMIZER MODULE WIRING DETAILS
• INTERFACE OVERVIEW
• SETUP AND CONFIGURATION
• ENTHALPY SETTINGS
• CHECKOUT
• TROUBLESHOOTING
RTU OPEN CONTROL SYSTEM . . . . . . . . . . . . . . . . . . 37
Smoke Detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
• COMPLETING RETURN-AIR SMOKE SENSOR INSTALLATION
• ADDITIONAL APPLICATION DATA
Step 14 — Adjust Factory-Installed Options . . . . . . . . . . 39
• SMOKE DETECTORS
• ECONOMI$ER IV OCCUPANCY SWITCH
Step 15 — Install Accessories. . . . . . . . . . . . . . . . . . . . . . . 39
Step 16 — Check Belt Tension. . . . . . . . . . . . . . . . . . . . . . 39
• BELT FORCE — DEFLECTION METHOD
• BELT TENSION METHOD
Pre-Start and Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . .CL-1

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes, including ANSI (American National Standards Institute) Z223.1. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.
It is important to recognize safety information. This is the safety-alert symbol . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety­alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
Catalog No. 04-53581010-01 Printed in U.S.A. Form II581J-4-6-02 Pg 1 4-19 Replaces: II581J-4-6-01
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
WARNING
GAS VALVE
INLET PRESSURE
TAP SET SCREW
Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation. There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed.
WARNING
WARNING
CARBON-MONOXIDE POISONING HAZARD Failure to follow instructions could result in severe personal
injury or death due to carbon-monoxide poisoning, if com­bustion products infiltrate into the building.
Check that all openings in the outside wall around the vent (and air intake) pipe(s) are sealed to prevent infiltration of combustion products into the building.
Check that furnace vent (and air intake) terminal(s) are not obstructed in any way during all seasons.
FIRE, EXPLOSION HAZARD Failure to follow this warning could result in death, serious
personal injury and/or property damage. Disconnect gas piping from unit when pressure testing at
pressure greater than 0.5 psig (3450 Pa). Pressures greater than 0.5 psig will cause gas valve damage resulting in haz­ardous condition. If gas valve is subjected to pressure great­er than 0.5 psig, it must be replaced before use. When pres­sure testing field-supplied gas piping at pressures of
0.5 psig or less, a unit connected to such piping must be isolated by closing the manual gas valve(s).
WARNING
UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could cause personal injury,
death and/or equipment damage.
®
Puron
(R-410A) refrigerant systems operate at higher pres­sures than standard R-22 systems. Do not use R-22 service equipment or components on Puron refrigerant equipment.
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could cause personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal.
Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refriger­ants and oils.
AVERTISSEMENT
RISQUE D’INTOXICATION AU MONOXYDE DE CARBONE
Si ces directives ne sont pas suivies, cela peut entraîner des blessures graves ou une intoxication au monoxyde de carbone pouvant causer la mort, si des produits de combustion s’infiltrent dans le bâtiment.
Vérifier que toutes les ouvertures pratiquées dans le mur extérieur autour du ou des tuyaux d’évent (et de la prise d’air) sont scellées de manière à empêcher l’infiltration de produits de combustion dans le bâtiment.
Veiller à ce que la ou les sorties de l’évent de l’appareil de chauffage (et la prise d’air) ne soient, en aucune façon, obstruées, quelle que soit la saison.
WARNING
FIRE HAZARD Failure to follow this warning could result in personal inju-
ry, death, and/or property damage. Inlet pressure tap set screw must be tightened and
NPT pipe plug must be installed to prevent gas leaks.
1
/8-in.
CUT HAZARD Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing air conditioning equipment.
CAUTION
2
WARNING
MANIFOLD
GAS VALVE
MANIFOLD PRESSURE
TAP SET SCREW
FIRE HAZARD Failure to follow this warning could result in personal inju-
ry, death, and/or property damage. Manifold pressure tap set screw must be tightened and
in. NPT pipe plug must be installed to prevent gas leaks.
1
/8-
MODEL NUMBER NOMENCLATURE AND
DIMENSIONS
See Fig. 1 for 581J model number nomenclature. See Fig. 2 and 3 for unit dimensional drawings. See Fig. 4 for corner weights and clearance dimensions. See Fig. 5 for base rail de­tails. See Fig. 6 for thru-the-base charts.

Rated Indoor Airflow

Table 1 lists the rated indoor airflow used for the AHRI effi­ciency rating for the units covered in this document.
Table 1 — Rated Indoor Airflow
MODEL NUMBER FULL LOAD AIRFLOW (CFM)
581J*04 1050 581J*05 1400 581J*06 1625
3
Model
J - Puron
®
(R-410A) Refrigerant
Unit Type
581 - High Efficiency Gas Heat RTU
Packaging and 2-Speed Fan Motor
A = Standard Packaging, electro-mechanical controls that require W7212 EconoMi$er IV B = LTL Packaging, electro-mechanical controls that require W7212 EconoMi$er IV C = Standard Packaging, electro-mechanical controls that require W7220 EconoMi$er X F =
LTL Packaging,
electro-mechanical controls
that require W7212 EconoMi$er IV
Cooling Tons
04 - 3 tons 05 - 4 tons 06 - 5 tons
Heat Level Input
Standard/Stainless Steel 1 Phase Models 3 Phase Models 065 = 65,000 072 = 72,000 090 = 90,000 115 = 115,000 130 = 130,000 150 = 150,000
Low NOx 060 = 60,000 090 = 90,000 120 = 120,000
Indoor Fan Options
0 = Electric (Direct) Drive X13 Motor (not available with Perfect Humidity) 1 = Standard Static - Belt Drive 2 = Medium Static - Belt Drive 3 = High Static - Belt Drive
Refrig. System/Gas Heat Options
A = Standard one stage cooling models/Natural Gas heat B = Standard one stage cooling models/Low NO
x
heat C = Standard one stage cooling models/ Stainless Steel gas heat exchanger G = Standard one stage cooling models and Perfect Humidity™ H = Standard one stage cooling models/Low NO
x
heat and Perfect Humidity™ J = Standard one stage cooling models/Stainless Steel gas heat exchanger and Perfect Humidity™
Coil Options (RTPF) (Outdoor - Indoor - Hail Guard)
A = Al/Cu - Al/Cu B = Precoat Al/Cu - Al/Cu C = E-coat Al/Cu - Al/Cu D = E-coat Al/Cu - E-coat Al/Cu E = Cu/Cu - Al/Cu F = Cu/Cu - Cu/Cu M = Al/Cu - Al/Cu — Louvered Hail Guard N = Precoat Al/Cu - Al/Cu — Louvered Hail Guard P = E-coat Al/Cu - Al/Cu — Louvered Hail Guard Q = E-coat Al/Cu - E-coat Al/Cu — Louvered Hail Guard R = Cu/Cu - Al/Cu — Louvered Hail Guard S = Cu/Cu - Cu/Cu — Louvered Hail Guard
Voltage
E = 460-3-60 J = 208/230-1-60 P = 208/230-3-60 T = 575-3-60
Outdoor Air Options
A = None B = Temperature Economizer w/ Barometric Relief, Standard Leak (W7212 or W7220) E = Temperature Economizer w/ Barometric Relief, Standard Leak w/ CO
2
(W7212 or W7220)
H =
Enthalpy
Economizer w/ Barometric Relief, Standard Leak (W7212 or W7220) L =
Enthalpy
Economizer w/ Barometric Relief, Standard Leak w/ CO
2
(W7212 or W7220)
Q =
Motorized 2-Position Damper
U =
Temperature Economizer w/ Barometric Relief, Ultra Low Leak (W7220) W =
Enthalpy
Economizer w/ Barometric Relief,
Ultra Low Leak (W7220)
Example:
Position:
581JE0 6A072A1A0AA
1234567891011 12 13 14 15 16 17
Factory Installed Options
0A = None NOTE: See the 581J Price Pages for a complete list of factory installed options.
NOTE: On single phase (-J voltage code) models, the following are not available as factory installed options:
- Perfect Humidity
TM
- Coated Coils or Cu Fin Coils
- Louvered Hail Guards
- EconoMi$er
®
or 2 Position Damper
- Powered 115 Volt Convenience Outlet
Fig. 1 — 581J 04-06 Model Number Nomenclature (Example)
4
Fig. 2 — Dimensional Drawing for Units Built On or After 4/15/19
5
Fig. 3 — Dimensional Drawing for Units Built On or Prior to 4/14/19
6
Fig. 4 — Corner Weights and Clearances
7
Fig. 5 — Base Rail Details
8
Fig. 6 — Thru-the-Base Charts
9

INSTALLATION

Jobsite Survey

Complete the following checks before installation.
1. Consult local building codes and the NEC (National Elec­trical Code) ANSI/NFPA 70 for special installation requirements.
2. Determine unit location (from project plans) or select unit location.
3. Check for possible overhead obstructions which may interfere with unit lifting or rigging.

Step 1 — Plan for Unit Location

Select a location for the unit and its support system (curb or other) that provides for the minimum clearances required for safety. This includes the clearance to combustible surfaces, unit performance and service access below, around, and above unit as specified in unit drawings. See Fig. 4 for clearances.
NOTE: Consider also the effect of adjacent units. Be sure that unit is installed such that snow will not block the
combustion intake or flue outlet. Unit may be installed directly on wood flooring or on Class A,
B, or C roof-covering material when roof curb is used. Do not install unit in an indoor location. Do not locate air inlets
near exhaust vents or other sources of contaminated air. For proper unit operation, adequate combustion and ventilation air must be provided in accordance with Section 5.3 (Air for Combustion and Ventilation) of the National Fuel Gas Code, ANSI Z223.1 (Ameri­can National Standards Institute) and NFPA (National Fire Protec­tion Association) 54 TIA-54-84-1. In Canada, installation must be in accordance with the CAN1-B149 installation codes for gas burning appliances.
Although unit is weatherproof, avoid locations that permit wa­ter from higher level runoff and overhangs to fall onto the unit.
Locate mechanical draft system flue assembly at least 4 ft (1.2 m) from any opening through which combustion products could enter the building, and at least 4 ft (1.2 m) from any adja­cent building (or per local code). Locate the flue assembly at least 10 ft (3.05 m) from an adjacent unit’s fresh air intake hood if within 3 ft (0.91 m) of same elevation (or per local code). When unit is located adjacent to public walkways, flue assembly must be at least 7 ft (2.1 m) above grade.
Select a unit mounting system that provides adequate height to allow installation of condensate trap per requirements. Refer to Step 12 — Install External Condensate Trap and Line on page 18 for required trap dimensions.
ROOF MOUNT Check building codes for weight distribution requirements.
Unit operating weights are shown in Table 2.
Table 2 — Unit Operating Weights
581J
Base Unit 505 (229) 590 (268) 600 (272) Economizer Vertical 50 (23) 50 (23) 50 (23) Horizontal 80 (36) 80 (36) 80 (36) Perfect Humidity™
System Cu Fins 25 (11) 43 (20) 56 (25) Powered Outlet 32 (15) 32 (15) 32 (15) Curb 14-in. (356 mm) 110 (50) 110 (50) 110 (50) 24-in. (610 mm) 145 (66) 145 (66) 145 (66)
27 (10) 34 (13) 34 (13)
UNIT LB (KG)
04 05 06

Step 2 — Plan for Sequence of Unit Installation

The support method used for this unit will dictate different se­quences for the steps of unit installation. For example, on curb­mounted units, some accessories must be installed on the unit before the unit is placed on the curb. Review the following for recommended sequences for installation steps.

CURB-MOUNTED INSTALLATION

1. Install curb
2. Install field-fabricated ductwork inside curb
3. Install accessory thru-base service connection package (affects curb and unit) (refer to accessory installation instructions for details)
4. Prepare bottom condensate drain connection to suit planned condensate line routing (refer to Step 12 on page 18 for details)
5. Rig and place unit
6. Install outdoor air hood
7. Install flue hood
8. Install gas piping
9. Install condensate line trap and piping
10. Make electrical connections
11. Install other accessories

PAD-MOUNTED INSTALLATION

1. Prepare pad and unit supports
2. Check and tighten the bottom condensate drain connection plug
3. Rig and place unit
4. Convert unit to side duct connection arrangement
5. Install field-fabricated ductwork at unit duct openings
6. Install outdoor air hood
7. Install flue hood
8. Install gas piping
9. Install condensate line trap and piping
10. Make electrical connections
11. Install other accessories
FRAME-MOUNTED INSTALLATION Frame-mounted applications generally follow the sequence for
a curb installation. Adapt the sequence as required to suit spe­cific installation plan.

Step 3 — Inspect Unit

Inspect unit for transportation damage. File any claim with transportation agency.
Confirm before installation of unit that voltage, amperage and circuit protection requirements listed on unit data plate agree with power supply provided.
On units with hinged panel option, check to be sure all latches are snug and in closed position.
Locate the carton containing the outside air hood parts. Do not remove carton until unit has been rigged and located in final position.

Step 4 — Provide Unit Support

ROOF CURB MOUNT Accessory roof curb details and dimensions are shown in
Fig. 7. Assemble and install accessory roof curb in accordance with instructions shipped with the curb.
The gasketing of the unit to the roof curb is critical for a water­tight seal. Install gasket supplied with the roof curb as shown in Fig. 7. Improperly applied gasket can also result in air leaks and poor unit performance.
10
ACCESSORY CONVENIENCE
OUTLET WIRING CONNECTOR
FITTING
1/2" [12.7] NPT 1/2" [12.7] NPT
CONTROL WIRING
FITTING
3/4" [19] NPT
POWER WIRING
1/2" [12.7] NPTCRRFCURB002A01
THRU THE CURB
CRBTMPWR003A01 THRU THE BOTTOM
CRBTMPWR001A01 3/4" [19] NPT
CONNECTOR PKG. ACC. GAS CONNECTION TYPE GAS FITTING
1-3/4"
[44.5]
11 3/4"[298.5] WIDE
INSULATED DECK PANELS
1.00"
[25.4]
"A"
SEE NOTE #2
2-3/8"
[61]
1' 4-13/16"
[427] INSIDE
8 9/16"[217.5] WIDE
INSULATED DECK PANEL
GAS SERVICE PLATE
THRU THE CURB
1-3/4"
[44.4]
E-ESECTION
SCALE 0.250
DRILL HOLE
2" [50.8] @
ASSEMBLY (IF
REQUIRED)
(SEE NOTE #8)
1-3/4"
[44.4]
RETURN AIR
1-3/4"
SUPPLY AIR
[44.5]
"A"
UNIT
[1711.3]
5' 7-3/8"
[944.6]
3'-1 3/16"
COUNTER FLASHING
NAIL (FIELD SUPPLIED)
(FIELD SUPPLIED)
TYPICAL (4) SIDES
7/16"
[11]
SYRACUSE, NY.
INDIANAPOLIS, IN.
THIS DOCUMENT AND THE INFORMATION CONTAINED THEREIN
IS PROPRIETARY TO CARRIER CORPORATION AND SHALL NOT
BE USED OR DISCLOSED TO OTHERS, IN WHOLE OR IN PART,
WITHOUT THE WRITTEN AUTHORIZATION OF CARRIER CORPORATION.
TOLERANCES ON:
DIMENSIONS ARE IN INCHES
- - - -
UNLESS OTHERWISE SPECIFIED
1 DEC 2 DEC 3 DEC ANG
PRODUCTION
CERTIFIED DRAWING
MATERIAL
DRAWING RELEASE LEVEL:
THIRD ANGLE
PROJECTION
SEE VIEW "B"
ROOFING MATERIAL
(FIELD SUPPLIED)
CANT STRIP
(FIELD SUPPLIED)
ROOFING FELT
(FIELD SUPPLIED)
B
(004-007)
SHEET 5 OF 5
48TC400427
CURB ASY, ROOF
SIZE DRAWING NUMBER REV
D
-
-
-
1041738
AUTHORIZATION NUMBER TITLE
DRAFTER CHECKER
ENGINEERING MANUFACTURING
MMC 06/17/11 - -
-
---
-
T-005, Y-002
WEIGHT:
ENGINEERING REQUIREMENTS
SURFACE FINISH MFG/PURCH MODEL (INTERNAL USE ONLY) NEXT DRAWING SCALE DISTRIBUTION
1067898--MMC04/22/13
RIGID INSULATION
(FIELD SUPPLIED)
- PURCH - N/A MMC
ECN NO.APP'DCHK'DBYDATEREVISION RECORDREV
NOTES:
1. ROOFCURB ACCESSORY IS SHIPPED DISASSEMBLED.
2. INSULATED PANELS: 25.4 [1"] THK. POLYURETHANE FOAM, 44.5 [1-3/4] # DENSITY.
3. DIMENSIONS IN [ ] ARE IN MILLIMETERS.
4. ROOFCURB: 18 GAGE STEEL.
5. ATTACH DUCTWORK TO CURB. (FLANGES OF DUCT REST ON CURB).
6. SERVICE CLEARANCE 4 FEET ON EACH SIDE.
7. DIRECTION OF AIR FLOW.
8. CONNECTOR PACKAGE CRBTMPWR001A01 IS FOR THRU-THE-CURB GAS TYPE
PACKAGE CRBTMPWR003A01 IS FOR THRU-THE-BOTTOM TYPE GAS CONNECTIONS.
A
14"
ROOF CURB
ACCESSORY #
CRRFCURB001A01
[356]
24"
[610]
11.96"
5.42"
[303.8]
[137.7]
21.74" [552.2]
Fig. 7 — Roof Curb Details
4.96"
70.87"
[126.0]
[1800.2]
E
E
RETURN AIR
OPENING
21.84"
1/3/4"[44.5]
3.00"
15.19" [385.8]
32.19"
[554.7]
[76.2]
VIEW "B"
CORNER DETAIL
[817.6]
16.03"
SUPPLY AIR
14.00"
[407.2]
OPENING
[355.6]
DUCT
GASKET
(FIELD SUPPLIED)
(SUPPLIED WITH CURB)
13.78" [350.0]
3.00"
[76.2]
40.69" [1033.5]
20.41" [518.3]
1.75" [44.5]
OVERALL DIM. 5'-7 3/8" WAS 5'-7 7/8; 18GA
MATERIAL WA 16 GA.; NAIL FIELD SUPPLIED WAS
WITH CURB
A
SUPPLY AIR RETURN AIR
1/4"
[7.0]
[115.5]
4 9/16"
11
Curb should be level. This is necessary for unit drain to func-
A
MAXIMUM ALLOWABLE
DIFFERENCE IN. (MM)
A-B B-C A-C
0.5 (13) 1.0 (25) 1.0 (25)
tion properly. Unit leveling tolerances are shown in Fig. 8. Re­fer to Accessory Roof Curb Installation Instructions for addi­tional information as required.
Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb and not to the unit. The accessory thru-the-base power and gas connection package must be installed before the unit is set on the roof curb. If field-installed thru-the-roof curb gas connections are desired, use factory-supplied
1
/2-in. pipe coupling and gas plate assembly to mount the thru-the-roof curb connection to the roof curb. Gas connections and power connections to the unit must be field-installed after the unit is installed on the roof curb.
If electric and control wiring is to be routed through the basepan, attach the accessory thru-the-base service connections to the base­pan in accordance with the accessory installation instructions.
C
B
Fig. 8 — Unit Leveling Tolerances
SLAB MOUNT (HORIZONTAL UNITS ONLY) Provide a level concrete slab that extends a minimum of 6-in.
(150 mm) beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from ob­structing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.

ALTERNATE UNIT SUPPORT (IN LIEU OF CURB OR SLAB MOUNT)

A non-combustible sleeper rail can be used in the unit curb support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4-in. x 4-in. (102 mm x 102 mm) pads on each side.

Step 5 — Field Fabricate Ductwork

Cabinet return-air static pressure (a negative condition) shall not exceed 0.35 in. wg (87 Pa) with economizer or 0.45 in. wg (112 Pa) without economizer.
For vertical ducted applications, secure all ducts to roof curb and building structure. Do not connect ductwork to unit.
Fabricate supply ductwork so that the cross sectional dimen­sions are equal to or greater than the unit supply duct opening dimensions for the first 18-in. (458 mm) of duct length from the unit basepan.
Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through unconditioned spaces must be insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.
A minimum clearance is not required around ductwork.

Step 6 — Rig and Place Unit

CAUTION
PROPERTY DAMAGE HAZARD Failure to follow this caution may result in damage to roof-
ing materials. Membrane roofs can be cut by sharp sheet metal edges. Be
careful when placing any sheet metal parts on such roof.
Keep unit upright and do not drop. Spreader bars are required. Rollers may be used to move unit across a roof. Rigging materi­als under unit (cardboard or wood) must be removed PRIOR to placing the unit on the roof curb. Level by using unit frame as a reference. See Table 2 and Fig. 9 for additional information.
Lifting holes are provided in base rails as shown in Fig. 9. Re­fer to rigging instructions on unit.
Rigging materials under unit (cardboard to prevent base pan damage) must be removed PRIOR to placing the unit on the roof curb.
When using the standard side drain connection, ensure the red plug in the alternate bottom connection is tight. Do this before setting the unit in place. The red drain plug an be tightened
1
with a
/2-in. square socket drive extension. For further details, see “Step 12 — Install External Condensate Trap and Line” on page 18.
Before setting the unit onto the curb, recheck gasketing on curb.
CAUTION
UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage. All panels must be in place when rigging. Unit is not de-
signed for handling by fork truck when packaging is re­moved.
If using top crate as spreader bar, once unit is set, carefully lower wooden crate off building roof top to ground. Ensure that no people or obstructions are below prior to lowering the crate.
12

POSITIONING ON CURB

DETAIL "A"
PLACE ALL SEAL STRIP IN PLACE BEFORE PLACING UNIT ON ROOF CURB.
DUCT END
SEE DETAIL "A"
"A"
(914-1371)
36"- 54"
"C"
"B"
SPREADER
BARS
REQUIRED
UNIT
MAX WEIGHT
DIMENSIONS
ABC
lb kg in. mm in. mm in. mm
581J*04 760 345 74.5 1890 38.0 965 33.5 850 581J*05 895 407 74.5 1890 38.0 965 41.5 1055 581J*06 930 423 74.5 1890 37.5 955 41.5 1055
NOTES:
1. SPREADER BARS ARE REQUIRED. Top damage will occur if spreader bars are not used.
2. Dimensions in () are in millimeters.
3. Hook rigging shackles through holes in base rail, as shown in Detail A. Holes in base rails are centered around the unit center of gravity. Use wooden top to prevent rigging straps from damaging unit.
REMOVABLE HORIZONTAL SUPPLY DUCT OPENING COVER
REMOVABLE HORIZONTAL RETURN DUCT OPENING COVER
Position unit on roof curb so that the following clearances are maintained: and the base rail inside the front and rear, 0.0-in. clearance be­tween the roof curb and the base rail inside on the duct end of the unit. This will result in the distance between the roof curb and the base rail inside on the condenser end of the unit being approximately
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage. All panels must be in place when rigging. Unit is not de-
signed for handling by fork truck when packaging is re­moved.
If using top crate as spreader bar, once unit is set, carefully lower wooden crate off building roof top to ground. Ensure that no people or obstructions are below prior to lowering the crate.
Flue vent discharge must have a minimum horizontal clearance of 4 ft (1220 mm) from electric and gas meters, gas regulators, and gas relief equipment. Minimum distance between unit and other electrically live parts is 48-in. (1220 mm).
Flue gas can deteriorate building materials. Orient unit such that flue gas will not affect building materials. Locate mechan­ical draft system flue assembly at least 48-in. (1220 mm) from an adjacent building or combustible material.
NOTE: Installation of accessory flue discharge deflector kit will reduce the minimum clearance to combustible material to 18-in. (460 mm).
After unit is in position, remove rigging skids and shipping materials.
Fig. 9 — Rigging Details
1
/4-in. (6.4 mm) clearance between the roof curb
1
/4-in. (6.4 mm).
CAUTION

Step 7 — Convert to Horizontal and Connect Ductwork (When Required)

Unit is shipped in the vertical duct configuration. Unit without factory-installed economizer or return-air smoke detector option may be field-converted to horizontal ducted configuration. To convert to horizontal configuration, remove screws from side duct opening covers (see Fig. 10) and remove covers. Use the screws to install the covers on vertical duct openings with the insulation-side down. The panels must be inserted into the notches on the basepan to properly seal. The notches are covered by the tape used to secure the insulation to the basepan and are not easily seen. See Fig. 11 for position of the notches in the basepan. Seals around duct openings must be tight. Secure with screws as shown in Fig. 12. Cover seams with foil duct tape.
Field-supplied flanges should be attached to horizontal duct openings and all ductwork should be secured to the flanges. In­sulate and weatherproof all external ductwork, joints, and roof or building openings with counter flashing and mastic in accor­dance with applicable codes.
Do not cover or obscure visibility to the unit’s informative data plate when insulating horizontal ductwork.
13
Fig. 10 — Horizontal Conversion Panels
NOTCHES
SCREWS
DUCT COVERS SHEET METAL FACE UP
BASEPAN
FILTER ACCESS PANEL
OUTDOOR-AIR OPENING AND INDOOR COIL ACCESS PANEL
COMPRESSOR ACCESS PANEL
HOOD PARTS
PLASTIC TIE WRAP QTY (2)
SCREWS FOR METAL TRAY QTY (2)
BASEPAN
NOTCHES
Fig. 12 — Horizontal Duct Panels In Place

Step 8 — Install Outside Air Hood

ECONOMIZER AND TWO POSITION DAMPER HOOD PACKAGE REMOVAL AND SETUP (FACTORY OPTION)

NOTE: Economizer and two position damper are not available as factory-installed options for single phase (-J voltage code) models.
1. The hood is shipped in knock-down form and must be field assembled. The indoor coil access panel is used as the hood top while the hood sides, divider and filter are packaged together, attached to a metal support tray using plastic stretch wrap, and shipped in the return air compart­ment behind the indoor coil access panel. The hood assem­bly’s metal tray is attached to the basepan and also attached to the damper using two plastic tie-wraps.
2. To gain access to the hood, remove the filter access panel. See Fig. 13.
Fig. 11 — Location of Notches
Fig. 13 — Typical Access Panel Locations
3. Locate the (2) screws holding the metal tray to the basepan and remove. Locate and cut the (2) plastic tie-wraps secur­ing the assembly to the damper. See Fig. 14. Be careful to not damage any wiring or cut tie-wraps securing any wiring.
Fig. 14 — Economizer and Two-Position Damper Hood
Parts Location
4. Carefully lift the hood assembly (with metal tray) through the filter access opening and assemble per the steps outlined in the Economizer Hood and Two-Position Hood section.
ECONOMIZER AND TWO-POSITION HOOD NOTE: If the power exhaust accessory is to be installed on the
unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter for use in the power exhaust hood assembly.
1. The indoor coil access panel will be used as the top of the hood. Remove the screws along the sides and bottom of the indoor coil access panel. See Fig. 15.
14
Loading...
+ 30 hidden pages