COMMERCIAL
SINGLE PACKAGE ROOFTOP UNITS
GAS HEATING/ELECTRIC COOLING UNITS
580F, 579F, 581A/B
DuraPac and
DuraPac Plus Series
Sizes 036-300
3 to 25 Tons
48-910df
581A210-300
Standard efficiency units (580F072, 090, 120, 150 and
579F180-300) are available. Standard efficiency units
(580F036-060, 073, 091,103,121,151, and 180-300) that meet
ASHRAE 90.1-04 minimum energy efficiency requirements are
also available. High efficiency units (581B036-150 and
581A155-300) well exceed ASHRAE 90.1-04 energy efficiency
requirements and must comply with Energy Star high efficiency
requirements. Gas heating with electric cooling rooftops offer:
• Pre-painted galvanized steel cabinet for long life and quality
appearance
• Commercial strength base rails with built-in rigging capability
• Convertible design for vertical or horizontal supply/return
(036-151 and 210-300 only)
• A wide assortment of factory-installed options available,
including high-static drives that provide additional performance range
• Factory-installed optional gear driven EconoMi$er IV (vertical
return for sizes 036-151 only) for use with standard rooftop
unit controls (includes CO
• Factory-installed optional gear driven EconoMi$er2 (vertical
return only) for use with third party DDC controls (includes
4 to 20 mA actuator for demand control ventilation)
• Hot gas reheat dehumidification package (581A181-300 only)
Heat Options
• Exclusive integrated gas control board with diagnostics
• Alumagard™ heat exchanger coating
• Induced-draft fan for gas combustion
SIZES 036-073
a48-8207
sensor control capability)
2
580F240
579F240-300
50-1242f
SIZES 090-151
50-1214df
a48-5997
48-831df
• Tubular, dimpled heat exchangers
579F180-216
581A155,180
580F180,210
580F300
• Natural gas
• LP conversion kits
•Low NO
• Optional stainless steel heat exchangers.
(size 036-060 only)
X
FEATURES/BENEFITS
Every compact one-piece unit arrives fully assembled,
charged, tested, and ready to run.
GAS HEAT MODELS — All ignition components are contained
in the compact IGC (integrated gas controller) which is easily
accessible for servicing. The IGC control board, designed and
manufactured exclusively for Bryant rooftop units, provides
built-in diagnostic capability. An LED (light-emitting diode) simplifies troubleshooting by providing visual fault notification and
system status confirmation.
The IGC also contains an exclusive anti-cycle protection for
gas heat operation. After 4 continuous cycles on the unit hightemperature limit switch, the gas heat operation is disabled,
and an error code is issued. This feature greatly improves reliability of the rooftop unit.
The IGC also contains burner control logic for accurate and
dependable gas ignition. The LED is visible without removing
the unit control box access panel. This LED fault-notification
system reduces service person troubleshooting time and minimizes service costs. The IGC also maximizes heating efficiency by controlling evaporator-fan on and off delays.
Tubular, dimpled gas heat exchangers optimize heat transfer
for improved efficiency. The tubular design permits hot gases
to make multiple passes across the path of the supply air. The
dimpled design creates a turbulent gas flow to maximize heating efficiency.
The efficient in-shot burners and all ignition components are
contained in an easily removable, compact assembly.
The California Air Quality Management Districts NO
ment of 40 nanograms/joule or less is met on 036-060 size Low
NO
models.
x
The extra thick Alumagard™ heat exchanger coating provides
corrosion resistance and ensures long life (optional stainless
steel heat exchangers are available).
require-
x
The unsightly appearance of flue stacks is eliminated and the
effects of wind on heating operations are diminished by the
induced draft combustion system. The inducer fan draws hot
combustion gas through the heat exchanger at the optimum
rate for the most effective heat transfer. The heat exchanger
operates under negative pressure, preventing flue gas leakage
into the indoor supply air.
During the heating mode, the evaporator-fan relay automatically
starts the evaporator fan after the heat exchanger warms up to
a suitable temperature. The 30-second fan delay prevents cold
air from entering the supply duct system when the conditioned
space is calling for heat to maximize efficiency.
The direct-spark ignition system saves operating expense when
compared to pilot ignition systems. No crossover tube is
required, therefore no sooting or pilot fouling problems can
occur.
All standard units are designed for natural gas, but an accessory LP (liquid propane) conversion kit is available.
All units have a flame rectification sensor to quickly sense the
burner flame and ignite burners almost immediately. Fast shutdown is a certainty since the sensor reacts quickly to any flame
outage or system failure. In the event of a shutdown, an error
code is issued at the IGC board.
Safety is also assured due to the heating safety controls which
will shut down the unit if there is a problem. If excessive temperatures develop, limit switches shut off the gas valve. After
4 continuous short cycles of the high-temperature limit switch,
the IGC board locks out the gas heat cycle to prevent any further short cycles. This safety feature is provided exclusively on
Bryant rooftop units. The rollout switch also deenergizes the
gas valve in the event of a flame rollout.
QUIET, EFFICIENT OPERATION AND DEPENDABLE PERFORMANCE — Compressors have vibration isolators for quiet
operation. Efficient fan and motor design permits operation at
low sound levels.
Unit sizes 090-300 offer lower utility costs through part-load
operation using 2 or 3 stages of cooling.
Quiet and efficient operation is provided by belt-driven evaporator fans (standard on all units over 5 tons). The belt-driven
evaporator-fan is equipped with variable-pitch pulleys which
allow adjustment within the rpm ranges of the factory-supplied
pulleys.
Increased operating efficiency is achieved through computerdesigned coils featuring staggered internally enhanced copper
tubes. Fins are ripple-edged for strength, lanced, and double
waved for higher heat transfer.
DURABLE, DEPENDABLE CONSTRUCTION — Designed for
durability in any climate, the weather-resistant cabinets are constructed of galvanized steel and bonderized, and all exterior
panels are coated with a prepainted baked enamel finish. The
paint finish is non-chalking, and is capable of withstanding
ASTM (American Society for Testing and Materials) B117
500-hour Salt Spray Test. All internal cabinet panels are primed,
permitting longer life and a more attractive appearance for the
entire unit.
In addition, all size 036-151 units are designed with a single,
continuous top piece to eliminate any possible leaks at seams
or gasketing. Totally enclosed condenser-fan motors and
permanently lubricated bearings provide additional unit
dependability.
EASY INSTALLATION AND CONVERSION
All Units are Shipped in the Vertical Duct Configuration for
fit-up to standard roof curbs. The contractor can order and
install the roof curb early in the construction stage, before decisions on size requirements are made.
All units feature a base rail design with forklift slots and rigging
holes for easier maneuvering. Durable packaging protects all
units during shipment and storage.
2
FEATURES/BENEFITS (cont)
The units can be easily converted from a vertical to a horizontal
duct configuration by relocating the panels supplied with the
unit (size 036-150 only).
To Convert 036-151 Units from vertical to horizontal discharge,
simply relocate 2 panels. The same basic unit can be used for a
variety of applications and can be quickly modified at the jobsite.
To Convert 155-300 Units from vertical to horizontal discharge,
use the optional horizontal supply/return adapter roof curb
(581A155,180 and 579F/580F180-300) or accessory conversion
kit (581A210-300). Please note that 581A210-300 units are
available from the factory configured for horizontal supply/return.
Convenient Duct Openings in the unit basepans permit sideby-side or concentric duct connections (see Application data
section) without requiring internal unit modification.
NOTE: On units using horizontal supply and return, the accessory barometric relief or power exhaust MUST be installed on
the return ductwork.
Thru-The-Bottom Service Connection Capability comes
standard with the rooftop unit to allow power and control wiring
and gas connections to be routed through the unit’s basepan,
thereby minimizing roof penetrations (to prevent water leaks).
(Thru-the-bottom gas connection requires thru-the-bottom
accessory kit.) Power, gas and control connections are made
on the same side of the unit to simplify installation.
The Non-Corrosive Sloped Condensate Drain Pan
(Size 036-150) permits either an external horizontal side con-
densate drain (outside the roof curb) or an internal vertical
bottom drain (inside the roof curb). Both options require an
external, field-supplied P-trap.
Standard 2-in. Throwaway Filters are easily accessed
through a removable panel located above the air intake hood.
No tools are required to change unit filters.
Belt-Driven Evaporator-Fan Motors (optional on 580F units
under 6 tons) allow maximum on-site flexibility without changing
motors or drives.
Low Voltage Wiring Connections are easily made thanks to
the large terminal board which is located for quick, convenient
access.
In addition, color-coded wires permit easy tracing and
diagnostics.
PROVEN COMPRESSOR RELIABILITY — Design techniques
feature computer-programmed balance between compressor,
condenser, and evaporator. Bryant-specified hermetic compressors are equipped with compressor overcurrent and overtemperature protection to ensure dependability.
All units have Bryant’s exclusive Acutrol™ (036-150) or TXV
(thermostatic expansion valve) metering device (155-300)
which precisely controls refrigerant flow, preventing slugging
and flood-back, while maintaining optimum unit performance.
Refrigerant filter driers are standard.
INTEGRATED ECONOMIZERS AND OUTDOOR-AIR DAMPERS — Available as options or accessories, economizers and
manual outdoor-air dampers introduce outdoor air which mixes
with the conditioned air, improving indoor-air quality and often
reducing energy consumption.
During a first stage call for cooling, if the outdoor-air temperature is below the economizer control changeover set point, the
mixed-air sensor modulates the economizer outdoor-air damper
open to take advantage of free cooling provided by the outside
air. When second-stage cooling is called for, the compressor is
energized in addition to the economizer. If the outdoor-air temperature is above the changeover set point, the first stage of
compression is activated and the economizer damper stays at
minimum position.
Accessory upgrade kits allow for control by differential dry-bulb
temperature (outdoor vs return), outdoor air enthalpy
changeover, or more precise differential enthalpy control.
Units can be equipped with different economizer options to
meet specific controls applications. The factory-installed or
field-installed EconoMi$er IV and EconoMi$er2 are available.
The EconoMi$er IV is used with the standard rooftop unit controls and includes an industry standard, stand-alone, solid-state
controller. The control can be used with a CO
(demand control ventilation) operation. For direct digital control
sensor for DCV
2
(DDC) applications, the EconoMi$er2 can be operated using a
third party control system. The EconoMi$er2 includes 4 to
20 mA actuator capability for demand control ventilation
applications.
All economizers incorporate a parallel blade, gear-driven
damper system for efficient air mixing and reliable control. In
addition, the standard damper actuator includes a spring return
to provide reliable closure on power loss. The economizers for
sizes 036-151 are equipped with up to 100% barometric relief
capability for high outdoor airflow operations. Economizers for
unit sizes 036-151 are available, factory-installed, for vertical
return only. Economizers for unit sizes 155-300 are compatible
for vertical or horizontal return. An optional field-installed barometric relief package is available for size 155-300 units.
In addition, single-stage power exhaust is available as a fieldinstalled accessory for EconoMi$er IV to help maintain proper
building pressure.
For units without economizer, year-round ventilation is
enhanced by an optional manual outdoor-air damper. On 036150 units, a 25% or 50% manual damper is available as a fieldinstalled accessory. Unit sizes 155-300 are equipped with a
manual 25% damper.
SERVICE OPTIONS (581B and 581A Units Only) — Servicing
a rooftop unit has never been easier with the factory-installed
service options for these rooftop units. These options include
the following:
• Hinged access panels are provided for the filter/indoor-fan
motor, compressors, evaporator fan, and control box areas.
Quick access to major components is accomplished by simply
unlatching and swinging open the various panels. Each
hinged panel is permanently mounted to the unit, thereby
eliminating the concern of a dropped or wind-blown panel
puncturing delicate roof materials. The 4 extended access
panels are also equipped with ‘‘tie back’’ retaining devices to
hold the door in the open position while servicing the unit.
• An external, covered, 115-v Ground Fault Interrupt (GFI)
receptacle is provided as a convenient power source for drills,
lights, refrigerant recovery units, or other electrical service
tools. A factory-supplied step down transformer is connected
to the “load” side of the unit main power connection (size 036-
150). For sizes 155-300, connect the outlet to a field-supplied
and properly fused branch circuit power supply.
• Slide out “motor-drive-blower” reduces service time (only on
581A210-300).
• An integral non-fused disconnect switch within the rooftop unit
reduces installation time, labor and material costs. Safety is
assured by an interlock which prevents access to the control
box unless the switch is in the OFF position. In addition, the
externally mounted handle incorporates power lockout capability to further protect service personnel.
3
FEATURES/BENEFITS (cont)
INDOOR-AIR QUALITY (IAQ) BEGINS WITH BRYANT ROOFTOPS — Sloped condensate pans minimize biological growth in
rooftop units in accordance with ASHRAE (American Society of
Heating, Refrigeration and Air Conditioning Engineers)
Standard 62. Two-inch filters with optional dirty filter indicator
switch provide for greater particle reduction in the return air.
The face-split evaporator coils improve the dehumidification
capability of standard units, maximize building humidity control.
Optional proportional reacting CO
EconoMi$er IV outdoor air damper option/accessory to aid the
IAQ benefits.
adaptive dehumidification system is an all-inclusive factoryinstalled option that can be ordered with any 581B rooftop unit
to meet the demand for providing a flexible and high performing
solution to accommodate all of these design related issues.
This system expands the envelope of operation of 581B rooftop
products to provide unprecedented flexibility to meet year-round
comfort conditions. The Perfect Humidity adaptive dehumidification system has the industry’s only dual dehumidification mode
setting. The Perfect Humidity system includes two new modes
of operation. The 581B rooftop coupled with the Perfect Humidity system is capable of operating in normal design cooling
mode, subcooling mode, and hot gas reheat mode. Normal
Design Cooling mode is when the unit will operate under its normal sequence of operation by cycling compressors to maintain
comfort conditions. Subcooling mode will operate to satisfy part
load type conditions when the space requires combined sensible and a higher proportion of latent load control. Hot Gas
sensor is available with the
2
Reheat mode will operate when outdoor temperatures diminish
and the need for latent capacity is required for sole humidity
control. Hot Gas Reheat mode will provide neutral air for maximum dehumidification operation.
EXCLUSIVE HOT GAS REHEAT DEHUMIDIFICATION PACKAGE (581A181-300) — The hot gas reheat dehumidification
package is a result of recent advances by Bryant in controlling
comfort levels. This factory-installed option significantly
improves the dehumidification capability of the rooftop unit and
helps control humidity levels in the building.
This option provides increased dehumidification by cooling the
hot liquid refrigerant leaving the condenser coil. The hot gas
reheat package consists of a subcooling coil located on the
leaving-air side of the evaporator coil. The location of this coil in
the indoor airstream enhances the latent capacity of the units
by as much as 40%. Many buildings suffer from humidity damage or poor indoor air quality due to humid conditions. The
improved latent capacity provided by the hot gas reheat option
reduces the building’s humidity, eliminating potential property
damage and making the space more comfortable.
The hot gas reheat option is the ideal IAQ option for hot and
humid regions. The operation of the hot gas reheat package
can be controlled by a field-installed, wall mounted humidistat
or Thermidistat™ device. The circuit activates only when
needed (using the accessory humidistat) as opposed to some
dehumidification systems that operate continuously. The humidistat can be set for any humidity level between 20% and 80%
relative humidity. The Thermidistat device can be set for any
humidity level between 50% and 90% relative humidity.
4
MODEL NUMBER NOMENCLATURE
580F036-150 (Standard and Medium Efficiency) 3 to 12
580F E V 060 120 N KB
1
/2 Tons
580F – Packaged Rooftop
NOTE: The example model number 580FEV060120NKB designates a 5-ton 460-3-60 volt Low NOx, gas/electric rooftop unit
with 120,000 Btuh natural gas heat, EconoMi$er2 and alternate drive. Low NOx units must show the “N” designation in the
model number.
Standard Efficiency
Voltage Designation
J–208/230-1-60
P–208/230-3-60
E–460-3-60
T–575-3-60
Fuel Control Type/Heat Exchanger
V– Natural Gas/Direct Spark Ignition
N – Low NOx Natural Gas/Direct Spark Ignition/Stainless
*Refer to the Trade Prices for ordering codes of factory-installed options.
The Example model number 581BEV060120NDA designates a high efficiency 5-ton 460-3-60 volt Low NOx gas/electric roof top unit with
120,000 Btuh natural gas heat and EconoMi$er IV. Low NOx units must show an “N” in the nomenclature.
1. All indoor-fan motors 5 hp and larger meet the minimum efficiency requirements as established
by the Energy Policy Act of 1992 (EPACT) effective October 24, 1997.
2. The example model number 580FEV180275--CB designates a 15-ton 460-3-60 volt gas/
electric rooftop unit with 275,000 Btuh natural gas heat input, EconoMi$er IV, and the standard low-medium fan drive static capability.
Fan Drive Position
(Standard Motor)
B–Standard Low-Medium
Fan Drive Static
Capability
D–Alternate High Fan
Drive Static Capability
Factory-Installed Outdoor-Air
and Other Upgrade Options
C– EconoMi$er IV
H– Manual Outdoor-Air Damper
Voltage Designation
E – 460-3-60
P – 208/230-3-60
T – 575-3-60
Fuel and Control Type
V–Natural Gas/Electric Relight Pilot
Nominal Tons
155 – 13 Tons
180
181––
*See pages 213 and 214 for cooling capacity tables for 5581A181 unit. For all other
data, contact application engineering.
NOTE: All indoor-fan motors 5 hp and larger meet the minimum efficiency requirements
as established by the Energy Policy Act of 1992 (EPACT) effective October 24, 1997.
The example model number: 581AEV180230--CB designates a 15 ton 460-3-60 high
efficiency gas/electric rooftop unit with 230,000 Btuh natural gas input, EconoMi$er IV
and standard, low-medium fan drive static capability.
High Efficiency Gas/Electric Unit
15 Tons
15 Tons with hot gas reheat*
Fan Drive Position
(Standard Motor)
B–Standard Low-Medium
Fan Drive Static
Capability
D–Alternate High Fan
Drive Static Capability
Factory-Installed Outdoor-Air
and Other Upgrade Options
C–EconoMi$er IV
H–Manual Outdoor-Air Damper
db— Dry Bulb
EER — Energy Efficiency Ratio
IPLV — Integrated Part-Load Values
SEER — Seasonal Energy Efficiency Ratio
wb— Wet Bulb
*Air Conditioning and Refrigeration Institute.
†Applies only to units with capacity of 65,000 Btuh or less.
**The IPLV applies only to two-stage cooling units.
NOTES:
1. Rated in accordance with ARI Standards 210/240 (for sizes 036-
120) or 360, (for size 150 and 151) and 270.
2. ARI ratings are net values, reflecting the effects of circulating fan
heat.
12
12
1
/
2
1
/
2
144,00016.09.0879.20
136,00014.39.5869.70
3.Ratings are based on:
Cooling Standard: 80 F db, 67 F wb indoor entering-air temperature and 95 F db air entering outdoor unit.
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature
and 80 F db outdoor entering-air temperature.
4.All 580F036, 048, 060, 073, 091, 103, 121, 151 units are in compliance with ASHRAE 90.1-1999 Energy Standard for minimum
SEER and EER requirements. Refer to state and local codes or
visit the following website: http://solstice.crest.org/efficiency/bcap
to determine if compliance with this standard pertains to a given
geographical area of the United States.
5.All 581B036-120 units are in compliance with Energy Star high
efficiency requirements.
IPLV
RATING
(dB)
HEATING CAPACITIES AND EFFICIENCIES (Standard-Efficiency Units) — 580F036-151
dB
036336,0003.2113.011.2076**
048446,0004.2513.011.0576**
060561,0005.5513.011.0080**
072673,0006.70—11.0080**
0907
1028
1
/
2
1
/
2
90,0008.18—11.008211.6
103,0008.90—11.608212.8
12010120,00010.91—11.008411.4
15012
1
/
2
138,00014.40—9.68610.3
LEGEND
EER— Energy Efficiency Ratio
IPLV— Integrated Part-Load Value
SEER — Seasonal Energy Efficiency Ratio
*Air-Conditioning & Refrigeration Institute.
†Applies only to units with capacity of 65,000 Btuh or less.
**The IPLV is not applicable to single-compressor units.
NOTES:
1. Rated in accordance with ARI Standard 210/240 (036-120 units) or
360 (150 units) and 270 (036-150 units).
2. Ratings are net values, reflecting the effects of circulating fan heat.
Ratings are based on:
Cooling Standard: 80 F db, 67 wb indoor entering-air temperature
and 95 F db outdoor entering-air temperature.
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature
and 80 F db outdoor entering-air temperature.
Sizes 036-120
Only
3. All 581B036-150 units are in compliance with ASHRAE 90.1-1999
Energy Standard for minimum SEER and EER requirements. Refer
to state and local codes or visit the following website: http://solstice.crest.org/efficiency/bcap to determine if compliance with this
standard pertains to a given geographical area of the United States.
4. All 581B036-120 units are Energy Star certified.
dB— Sound Levels (decibels)
db— Dry Bulb
EER — Energy Efficiency Ratio
IPLV — Integrated Part-Load Values
wb— Wet Bulb
*Air Conditioning and Refrigeration Institute.
NOTES:
1. Rated in accordance with ARI Standards 360 and 270.
2. The 579F300 is beyond the scope of the ARI Certification
Program.
3. ARI ratings are net values, reflecting the effects of circulating fan
heat.
NOMINAL
TONS
NOMINAL
TONS
LEGEND
NET COOLING
CAPACITY
(Btuh)
HIGH HEAT UNITS
NET COOLING
CAPACITY
(Btuh)
TOTAL
WATTS
TOTAL
WATTS
4. Ratings are based on:
Cooling Standard: 80 F db, 67 F wb indoor entering-air tempera-
ture and 95 F db air entering outdoor unit.
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature
and 80 F db outdoor entering-air temperature.
*All units are 2-stage heat.
NOTE: Minimum allowable temperature of mixed-air entering the heat exchanger during first-stage
heating is 45 F. There is no minimum mixed-air temperature limitation during second-stage heating.
For entering-air temperatures below 45 F both stages of heat must be energized together to minimize
condensation issues and ensure proper unit operation.
1. Rated in accordance with ARI Standards 360 and 270.
2. ARI ratings are net values, reflecting the effects of circulating fan
heat.
3. Ratings are based on:
Cooling Standard: 80 F db, 67 F wb indoor entering-air temperature and 95 F db air entering outdoor unit.
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature
and 80 F db outdoor entering-air temperature.
NOMINAL
TONS
NOMINAL
TONS
NET COOLING
CAPACITY (Btuh)
NET COOLING
CAPACITY (Btuh)
TOTAL
WATTS
TOTAL
WATTS
4. All 580F180-300 units are in compliance with ASHRAE 90.11999 Energy Standard for minimum SEER and EER requirements. Refer to state and local codes or visit the following website:
http://solstice.crest.org/efficiency/bcap
with this standard pertains to a given geographical area of the
United States.
*All units are 2-stage heat.
NOTE: Minimum allowable temperature of mixed-air entering the heat exchanger during first-stage
heating is 45 F. There is no minimum mixed-air temperature limitation during second-stage heating.
For entering-air temperatures below 45 F both stages of heat must be energized together to minimize
condensation issues and ensure proper unit operation.
dB— Sound Levels (decibels)
db— Dry Bulb
EER — Energy Efficiency Ratio
IPLV — Integrated Part-Load Values
wb— Wet Bulb
*Air Conditioning and Refrigeration Institute.
NOTES:
1. Rated in accordance with ARI Standards 360 and 270.
2. ARI ratings are net values, reflecting the effects of circulating fan
heat.
3. Ratings are based on:
Cooling Standard: 80 F db, 67 F wb indoor entering-air temperature and 95 F db air entering outdoor unit.
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature
and 80 F db outdoor entering-air temperature.
LEGEND
NOMINAL
TONS
NOMINAL
TONS
NET COOLING
CAPACITY
(Btuh)
NET COOLING
CAPACITY
(Btuh)
HIGH HEAT UNITS
TOTAL
WATTS
TOTAL
WATTS
4.All 581A155, 180 units are in compliance with ASHRAE 90.11999 Energy Standard for minimum EER requirements. Refer to
state and local codes or visit the following website: http://solstice.crest.org/efficiency/bcap to determine if compliance with this
standard pertains to a given geographical area of the United
States.
*All units are 2-stage heat.
†Minimum heating cfm must be maintained to ensure proper heating operation.
NOTE: Minimum allowable temperature of mixed air entering the heat exchanger during first stage
heating is 45 F. There is no minimum mixed-air limitation during second-stage heating. For entering
air temperatures below 45 F, both stages of heat must be energized together to minimize condensation issues and ensure proper unit operation.
db— Dry Bulb
EER — Energy Efficiency Ratio
IPLV — Integrated Part-Load Values
wb— Wet Bulb
*Air Conditioning and Refrigeration Institute.
†IPLV values are calculated based on control configuration T.CTL = 2
(2 Stage Y1).
**Size 300 unit is not listed with ARI, but is tested to ARI standards.
NOTES:
1. Rated in accordance with ARI Standards 360-93 and 270-95.
2. ARI ratings are net values, reflecting the effects of circulating fan heat.
LEGEND
NOMINAL
TONS
CFM
NET COOLING
CAPACITY (Btuh)
TOTAL
kW
3. Ratings are based on:
Cooling Standard: 80 F db, 67 F wb indoor entering-air temperature and
95 F db air entering outdoor unit.
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and 80 F
db outdoor entering-air temperature.
4. All 581A210-300 units are in compliance with ASHRAE 90.1 2001 Energy
Standard for minimum EER requirements. Refer to state and local codes or
visit the following website: http://solstice.crest.org/efficiency/bcap
mine if compliance with this standard pertains to a given geographical area
of the United States.
*7000 cfm minimum recommended above 1.0 in. wg external static pressure.
NOTE: All units are 2-stage gas heat.
HEATING INPUT
(Btuh) Stage 2/Stage 1
HEATING INPUT
(Btuh) Stage 2/Stage 1
HEATING INPUT
(Btuh) Stage 2/Stage 1
HEATING INPUT
(Btuh) Stage 2/Stage 1
OUTPUT CAPACITY
(Btuh)
TEMPERATURE
RISE (F)
HORIZONTAL SUPPLY — NATURAL GAS
OUTPUT CAPACITY
(Btuh)
TEMPERATURE
RISE (F)
VERTICAL SUPPLY — PROPANE
OUTPUT CAPACITY
(Btuh)
TEMPERATURE
RISE (F)
HORIZONTAL SUPPLY — PROPANE
OUTPUT CAPACITY
(Btuh)
TEMPERATURE
RISE (F)
STEADY-STATE
EFFICIENCY %
STEADY-STATE
EFFICIENCY %
STEADY-STATE
EFFICIENCY %
STEADY-STATE
EFFICIENCY %
MINIMUM
HEATING CFM
MINIMUM
HEATING CFM
MINIMUM
HEATING CFM
MINIMUM
HEATING CFM
IPLV†
to deter-
15
OPTIONS AND ACCESSORIES
581B036-150 AND 580F036-151
ITEMOPTION*ACCESSORY†
100% Open Two-Position Damper X
25% Open Two-Position DamperX
Condenser Coil GrilleX
Condenser Coil Hail Guard AssemblyX
Convenience Outlet (Load Side)X
Copper Fins Indoor and Outdoor CoilX
Copper Fins Outdoor CoilX
E-Coat Outdoor Coil (Aluminum)X
E-Coat Outdoor Coil (Copper)X
EconoMi$er IV with ControllerXX
EconoMi$er2 (without controller)XX
Electronic Programmable ThermostatX
Enthalpy or Differential Enthalpy SensorX
Fan/Filter StatusX
Flue Discharge Deflector X
Flue Shield X
High-Static Motor and DriveX
Hinged Access Panels (581B only)X
Hinged Panel Kit for EconomizerX
Perfect Humidity™ Dehumidification Package (581B only)X
HumidistatX
Indoor Air Quality (CO
Light Commercial Thermidistat™ DeviceX
Low NO
(036-060)X
X
Louvered Hail GuardXX
LP (Liquid Propane) Conversion KitX
Manual Outdoor-Air DamperX
Motormaster® I, II, IV Head Pressure Control Low Ambient Kit)X
Outdoor Air Enthalpy SensorX
Power Exhaust Transformer for 575 vX
Power Exhaust with Barometric Relief X
Pre-Coat Aluminum Fins on Outdoor CoilX
Return Air CO
Sensor (EconoMi$er IV)X
2
Return Air Enthalpy SensorX
Return Air Temperature SensorX
Roof Curbs (Vertical and Horizontal Discharge)X
Smoke Detectors, Supply/Return (Blanket Quote Control)X
Stainless Steel Heat ExchangerX
Thermostats and SubbasesX
Thru-the-Bottom Utility ConnectionsX
Time Guard II (Compressor Cycle Delay) Control CircuitX
Unit-Mounted Non-Fused DisconnectX
UVC Lights (Blanket Quote Control)XX
*Factory-installed.
†Field-installed.
NOTES:
1. Refer to unit price pages or contact your local representative for
accessory and option package information.
2. Some options may increase product lead times.
) SensorX
2
16
OPTIONS AND ACCESSORIES (cont)
579F180-300, 580F180-300, AND 581A155-181
ITEMOPTION*ACCESSORY†
25% Open Two-Position DamperX
Barometric Relief Damper (not for use with Horizontal Adapter Curb)X
Condenser Coil Hail Guard Assembly (180-240)X
Convenience Outlet (Load Side)X
Copper Fins Indoor and Outdoor CoilX
Copper Fins Outdoor CoilX
E-Coat Outdoor Coil (Aluminum)X
E-Coat Outdoor Coil (Copper)X
EconoMi$er IV with ControllerXX
EconoMi$er2 (without Controller)X
Electronic Programmable ThermostatX
Enthalpy or Differential Enthalpy SensorX
Fan/Filter StatusX
High-Static Motor and DriveX
Hinged Access PanelsX
Horizontal Adapter Curb (180-240)X
Hot Gas Reheat Dehumidification Package (581A181 only)X
HumidistatX
Indoor Air Quality (CO
Light Commercial Thermidistat™ DeviceX
LP (Liquid Propane) Conversion KitX
Manual Outdoor-Air DamperX
Motormaster® I, V Head Pressure Control (Low Ambient Kit)X
Outdoor Air Enthalpy SensorX
Power Exhaust without Barometric ReliefX
Pre-coat Aluminum Fins on Outdoor CoilX
Return Air CO
Return Air Enthalpy SensorX
Return Air Temperature SensorX
Roof Curbs (Vertical and Horizontal Discharge)X
Thermostats and SubbasesX
Time Guard II (Compressor Cycle Delay) Control CircuitX
Ultraviolet Germicidal LampsX
Unit-Mounted Non-Fused Disconnect X
Winter Start Time DelayX
*Factory-installed.
†Field-installed.
NOTES:
1. Refer to unit price pages or contact your local representative for
accessory and option package information.
2. Some options may increase product lead times.
3. No other options are available with hot gas reheat units.
SensorX
2
) SensorX
2
17
OPTIONS AND ACCESSORIES (cont)
581A210-300
ITEMOPTION*ACCESSORY†
EconoMi$er IVXX
Power ExhaustXX
Barometric ReliefXX
Hail GuardXX
Horizontal KitXX
Return Smoke DetectorXX
Supply Smoke DetectorX
Return and Supply Smoke DetectorX
Non-Fused DisconnectX
Non-Powered Convenience OutletX
Outdoor Air Enthalpy SensorX
Return Air Enthalpy SensorX
Return Air Temperature SensorX
Return Air CO
Indoor Air Quality (CO
Hot Gas ReheatX
Non-Powered Convenience OutletX
Pre-Coat CondenserX
E-Coat Condenser CoilX
Copper Condenser CoilX
Copper Evaporator CoilX
E-Coat Copper Evaporator CoilX
Low Range DriveX
Mid-Low Range DriveX
Mid-High Range DriveX
High Range DriveX
Roof Curb (14 in.)X
Roof Curb (24 in.)X
Low Heat GasX
High Heat GasX
Medium Heat GasX
Stainless Steel Heat ExchangersX
Propane KitX
Drip EdgeX
Two-Posit ion Da mperXX
Condensate Overflow SwitchX
Phase Loss DetectionX
Manual DamperXX
Thermostat and SubbaseX
Hinged Access PanelsX
*Factory-installed.
†Field-installed.
NOTES:
1. Refer to unit price pages or contact your local representative for
accessory and option package information.
2. Some options may increase product lead times.
SensorX
2
) Room SensorX
2
18
OPTIONS AND ACCESSORIES (cont)
Roof Curbs (Horizontal and Vertical) permit installation and
securing of ductwork to curb prior to mounting unit on the curb.
Both 14-in. and 24-in. roof curbs are available as field-installed
accessories.
EconoMi$er IV is available as a factory-installed option in
vertical supply/return configuration only for unit sizes 036-151.
Vertical or horizontal configuration is available for unit sizes
155-300. (The EconoMi$er IV is available as a field-installed
accessory for horizontal and/or vertical supply return configurations.) The EconoMi$er IV is provided with an industry standard, stand-alone, solid-state controller that is easy to configure
and troubleshoot. The EconoMi$er IV is compatible with nonDDC applications. The EconoMi$er IV is equipped with a
barometric relief damper capable of relieving up to 100% return
air (for unit sizes 036-151 only). Dry bulb outdoor-air temperature sensor is provided as standard. The return air sensor,
indoor enthalpy sensor, and outdoor enthalpy sensor are provided as field-installed accessories to provide enthalpy control,
differential enthalpy control, and differential dry bulb temperature control.
EconoMi$er IV on 579F and 581A units is used for both vertical
and horizontal return air configurations.
EconoMi$er2 is available as a blanket quote control or as a
field-installed accessory for horizontal and/or vertical supply
return configurations. The EconoMi$er2 is provided without a
controller for use with field-installed third-party controls. The
EconoMi$er2 is equipped with a barometric relief damper capable of relieving up to 100% return air. Dry bulb outdoor-air temperature sensor is provided as standard. The enthalpy,
differential temperature (adjustable), and differential enthalpy
control are provided as field-installed accessories. The
EconoMi$er2 is capable of control from a 4 to 20 mA signal
through optional 4 to 20 mA design without microprocessor
control (required for third party control interface).
Manual Outdoor-Air Damper can be preset to admit up to 50%
outdoor air for year round ventilation and is available as a fieldinstalled accessory.
Two-Position Damper package is available as an accessory.
Both 25% or 100% outdoor air dampers are available.
Head Pressure Control (Motormaster) accessory package
maintains condensing temperature between 90 F and 110 F at
outdoor ambient temperatures down to –20 F by condenser-fan
speed modulation or condenser-fan cycling and wind baffles.
Unit-Mounted, Non-Fused Disconnect Switch provides unit
power shutoff. The switch is accessible from outside the unit,
provides power off lockout capability and is available as a
factory-installed option.
Convenience Outlet is factory-installed and internally mounted
with easily accessible 115-v female receptacle.
Compressor Cycle Delay (Time Guard II) accessory prevents
unit from restarting for minimum of 5 minutes after shutdown.
Thru-The-Bottom Utility Connectors permit electrical connections to be brought to the unit through the basepan.
Connectors are available as field-installed accessories.
Fan/Filter Status Switch accessory provides status of indoor
(evaporator) fan (ON/OFF) or filter (CLEAN/DIRTY).
Power Exhaust accessory will provide system exhaust of up to
100% of return air (vertical only). The power exhaust is a fieldinstalled accessory (separate vertical and horizontal design).
Ultraviolet Germicidal Lamps eliminate odor causing mold
and fungus that may develop in the wet area of the evaporator
section of the unit. The high output, low temperature germicidal
lamps are field installed in the evaporator section of the unit,
aimed at the evaporator coil and condensate pan.
Hinged Panel Option provides hinged access panels for the filter, compressor, evaporator fan, and control box areas. Filter
hinged panels permit tool-less entry for changing filters. Each
hinged panel is permanently attached to the rooftop unit.
Hinged panels are a factory-installed option.
19
PHYSICAL DATA — 580F036-073
UNIT SIZE 580F036048060072073
NOMINAL CAPACITY (tons)34566
LEGEND*Evaporator coil fin material/condenser coil fin material. Contact your local repre-
Al— Aluminum
Bhp — Brake Horsepower
Cu— Copper
1
/
2
1
/4...1100
3
/8-in. OD Enhanced Copper Tubes, Aluminum Lanced Fins
5
/
8
5
/
8
7
/
8
3
/8-in. OD Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Face Split
sentative for details about coated fins.
†Weight of 14-in. roof curb.
**Rollout switch lockout is manually reset by interrupting power to unit or resetting
**Rollout switch lockout is manually reset by interrupting power to unit or resetting
thermostat.
1
/
2
3
/
4
3
/
4
3
/
4
3
/
4
3
/
4
3
/
4
3
/
4
—
580F036-151
25
BASE UNIT DIMENSIONS — 580F036-072
580F036-151
26
a48-8195
BASE UNIT DIMENSIONS — 580F073
580F036-151
27
a48-8196
BASE UNIT DIMENSIONS — 580F090,120,150
580F036-151
28
a48-8197
BASE UNIT DIMENSIONS — 580F091,103,121,151
580F036-151
29
a48-8198
ACCESSORY DIMENSIONS — 580F
ROOF CURB
ACCESSORY
CRRFCURB001A01
CRRFCURB002A01
580F036-151
AUNIT SIZE
1′ -2″
[356]
2′ -0″
[610]
580F
036-073
1′ -4″
[406]
D ALT
DRAIN
HOLE
13/4″
[44.5]
GASPOWERCONTROL
3
/4″ [19] NPT
1
/2″ [12.7] NPT3/4″ [19] NPT
3
/4″ [19] NPT11/4″ [31.7]
NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels.
3. Dimensions in [ ] are in millimeters.
4. Roof curb, galvanized steel.
5. Attach ductwork to curb (flanges of duct rest on curb).
6. Service clearance: 4 ft on each side.
CONNECTOR
PKG. ACCY.
BC
CRBTMPWR001A01
CRBTMPWR002A011
CRBTMPWR003A01
1′ -9
11
[551]
/16″
CRBTMPWR004A01
7. Direction of airflow.
8. Connector packages CRBTMPWR001A01 and 2A01 are for
thru-the-curb type gas. Packages CRBTMPWR003A01 and
4A01 are for thru-the-bottom type gas connections.
3
/4″ [19] NPT
1
/4″ [31.7]
1
/2″
[12.7]
NPT
ACCESSORY
POWER
1
/2″
[12.7]
NPT
Roof Curb
30
a48-7317
Loading...
+ 238 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.