Bryant 581A User Manual

Bryant
Air Conditioning
COMMERCIAL SINGLE PACKAGE ROOFTOP GAS HEATING/ELECTRIC COOLING UNITS
Model 581A
Sizes 155-240
13 to 20 Tons
Model 581A155,180
DESCRIPTION
The 581A gas heating/electric cooling rooftop units are de­signed to deliver optimum performance and reliability in a com­mercial rooftop unit.
The 13 to 20 ton units are one-piece gas heating, electric cool­ing units that are prewired and precharged with R-22 at the fac­tory, making jobsite installation easy. Every unit is factory run­tested prior to shipment to ensure reliable installation.
The 581A units are designed to be field-convertible from vertical supply/return to horizontal supply/return (using an accessory horizontal supply curb or adapter), making them easily adapt­able to a wide variety of new construction and replacement ap­plications. For vertical supply/return jobs, ductwork can be connected directly to the roof curb, allowing ductwork to be completed before unit is available for installation. All units in­clude easily replaceable internal filters.
The 581A units are available in a range of heating sizes and voltage options to meet most job requirements. Low-voltage ter­minal blocks make wiring connections quick and simple.
STANDARD FEATURES
INDUSTRY-LEADING COOLING EERS (Energy Efficiency Ra-
SEMI-HERMETIC COMPRESSORS are fully serviceable. They are highly regarded and preferred by owners and users, and are offered exclusively on the high-efficiency 13 to 20 ton 581A units.
Two 06D semi-hermetic compressors on independent refrigera­tion circuits are offered on the 180 and 240 units for 2 steps of capacity control and redundancy. A single 06D semi-hermetic compressor with unloading capability is offered on the 155 units. All compressors have service valves and a full complement of
Model 581A240
safety devices, including high- and low-pressure switches, over­temperature protection, an electronic compressor lockout de­vice, and crankcase heaters.
HIGH STATIC OVERSIZED FAN MOTORS AND VARIABLE­PITCH BELT DRIVES are supplied standard from the factory to
provide up to 2 in. wg of external static pressure at 400 cfm per ton with wet coils and clean filters installed. A 5 hp motor is pro­vided standard on the 581A180 (15-ton unit), and a 10 hp motor is standard on the 581A240 (20-ton unit).
The new 581Aunitscanbeeasily converted to horizontal supply and return with the new fan-performance-boosting horizontal high-static regain adapter (part no. 389210-201 or 389211-201). These vertical-to-horizontal supply/return adapters are not only fully factory assembled with a built-in insulated transition duct, they improve fan performance by as much as 0.6 in. wg of static.
INTERNAL RETURN-AIR FILTERS are provided. Two-in. throwaway filters are provided standard on all units, and can be easily accessed. There is no need to field-fabricate filter racks or install external filter accessories.
COMPRESSOR PROTECTION is assured. The 581A units have high- and low-pressure protection external to the compres­sor. These protections prohibit operation under abnormal unit conditions.
DUAL COMPRESSORS AND DUAL REFRIGERATION CIR­CUITS (180,240 units) are provided. Two compressors, each
POWER, CONTROL, AND GAS CONNECTIONS are made on the same side of the unit to simplify installation.
Form No. PDS 581A.155.2B
INDUCED-DRAFT COMBUSTION provides the exact amount of combustion air for the most efficient operation. Induced-draft combustion also eliminates the flue stack, giving the unit a low profile appearance. The draw-through design ensures safe op­eration under any conditions.
INTERMITTENT SPARK IGNITION eliminates the standing pi­lot flame that consumes gas when the furnace is shut down. The pilot is ignited only when the thermostat calls for heat.
TUBULAR U-SHAPED CELL design of the heat exchanger provides high-efficiency heating operation. The hot gases make 2 passes over the supply-air path to enhance efficiency.
is unaffected by adverse wind conditions. FURNACE SAFETY CONTROLS shut off gas if there is a pilot
outage, combustion-air failure, overheating of heat exchangers, or flame rollout.
TWO-STAGE HEATING WITH 2 INDEPENDENT GAS CON­TROL SYSTEMS (180,240 units) minimizes heating costs.
COMMERCIAL STRENGTH BASE RAILS with built-in rigging capability allow easy rigging of unit.
WEATHER-RESISTANT CABINET is built for durability in any climate. The cabinet is made of pre-painted, galvanized steel for long life and high-quality appearance.
LOW-AMBIENT OPERATION is provided standard. The units operate in cooling down to 35 F as shipped from the factory. Low-ambient kits are not required for most applications.
CRANKCASE HEATERS keep the oil free of refrigerant during the off cycle for added compressor life and reliability.
BELT-DRIVEN EVAPORATOR-FAN MOTORS are standard on all units and allow adjustment of the available static pressure to meet the job requirements of even the most demanding applications.
Manual Outdoor-Air Dampers — Package consists of a damper which can be set at 25% outdoor air. The package in­cludes a rainhood and birdscreen.
SUGGESTED USE
• To allow a fixed percentage of outdoor air for ventilation under all conditions.
• The damper may be used on either vertical or horizontal applications.
NOTE: The 25% manual outdoor-air damper will be factory installed whenever the factory-installed economizer is not chosen.
FIELD-INSTALLED ACCESSORY
DESCRIPTION AND USAGE
Roof Curbs (Horizontal and Vertical) — Full-perimeter galva-
nized steel support frame in 14- and 24-in. high designs pro­vides wood nailer to attach roof counter flashing. Insulated basepans in curb are provided to prevent condensation. Duct­work attaches to rails provided in the roof curb. A gasket is pro­vided to form an air- and watertight seal between unit and curb. The gasket meets the standards of the NRCA (National Roofing Contractors’ Association).
SUGGESTED USE:
• Rooftop application for vertical or horizontal discharge.
• Slab-mounted applications when elevation of the unit is necessary.
SUGGESTED USE:
• Rooftop applications for horizontal discharge where high air delivery cfms are required.
Two-Position Damper — Package consists of a low-leak damper assembly for easy installation. The damper will allow ei­ther 0 or 25% outdoor air into the unit any time the evaporator fan is running. When the evaporator fan is off or when there is a loss of power, the damper will be closed.
SUGGESTED USE:
• Allows a fixed percentage of outdoor air any time the evapo­rator fan is on, but closes when the evaporator fan is off to prevent cold backdrafts and wasted energy.
• The damper may be used on either vertical or horizontal air­flow applications.
Economizer — See description listed under Factory-Installed Options Description and Usage section above.
FACTORY-INSTALLED OPTIONS DESCRIPTION
AND USAGE
Economizer — The economizer will allow a fixed percentage
(between 0 and 100%) outdoor ventilation air into the unit any time the evaporator fan is running. A dry-bulb thermostat placed outdoors will bring in 100% outdoor air whenever the tempera­ture of the outdoor air alone will adequately provide cooling. If the economizer alone cannot provide enough cooling, then si­multaneous economizer and compressor operation will provide the most economical operation.
SUGGESTED USE:
• To allow a fixed percentage of outdoor air any time the evapo­rator fan is on, or operates in economizer mode if outdoor air can provide cooling, but closes when the evaporator fan is off to prevent cold backdrafts and wasted energy.
• To reduce energy usage. Use whenever the number of hours of operation at below 55 F is significant.
• The damper may be used on either vertical or horizontal applications.
CONTENTS
Page
Model Description .................................3
Heating Capacities and Efficiencies ...................4
Capacity Ratings ..................................4
Dimensional Drawings ............................5-8
Specifications ...................................9,10
Selection Procedure ..............................11
Gross Cooling Capacities ........................12-14
Air Delivery ....................................15-17
Electrical Data ...................................19
Operating Sequence ..............................20
Typical Wiring Schematic .........................20,21
Typical Installation ................................22
Application Data ................................23,24
Engineers’ Specification Guide ......................25
2
FIELD-INSTALLED ACCESSORY DESCRIPTION AND USAGE (cont)
Thermostats and Subbases — Provide staged cooling and
heating, automatic (or manual) changeover, fan control, and in­dicator light.
SUGGESTED USE:
• To control unit operations. Enthalpy Control Sensor — Package consists of a solid-state
sensor to be paired with a second enthalpy sensor for differen­tial enthalpy control. This sensor is mounted on the economizer assembly so that it can sense building return-air temperature. The 2 sensors will determine which combination of outdoor and return air will provide the greatest energy savings.
SUGGESTED USE:
• To enhance economizer operation for maximum energy savings.
NOTE: A single sensor may be used for single-sensor, outdoor­air, enthalpy control if desired.
Time GuardT II Device — Package consists of a control to be field wired into the unit controls, and provides a 5-minute delay in compressor operation between cooling cycles.
SUGGESTED USE:
• Prevents compressor short cycling when rapid compressor cycles may be a problem.
Head Pressure Control Device — Kit consists of an outdoor­air thermostat that permits adequate head pressure control dur­ing cooling operation at low outdoor-ambient temperatures. Refer to Trade Prices for more details or contact your local representative.
SUGGESTED USE:
• When cooling at low-ambient outdoor temperatures is desired.
Low-Ambient Kit — Kit consists of a solid-state control and condenser coil temperature sensor to modulate the condenser­fan motors in order to maintain condenser-coil head pressure
for proper cooling operation. Refer to Trade Prices for more de­tails or contact your local representative.
SUGGESTED USE:
• Whenever cooling is required at low outdoor ambient tem­peratures (as low as –20 F).
• Low-ambient kit is not usually required when economizer is used.
Barometric Relief Package — This package is useful when it is necessary to remove excess pressure from the conditioned space.
NOTE: Optional economizer is required. SUGGESTED USE:
• When the job requires the ability to relieve internal building pressure.
Power Exhaust Package — This package is useful when it is necessary to remove excess pressure from the conditioned space.
NOTE: Optional economizer is required. SUGGESTED USE:
• When the job requires the ability to relieve internal building pressure and pressure losses through the return-air ductwork are greater than 0.20 in. wg.
• When the job requires the ability to move large quantities of air to relieve pressure in the conditioned space.
Winter Start Time Delay Relay — Used in conjunction with ac­cessory low-ambient kit or head pressure control device, per­mits operation in cooling at lower outdoor ambient tempera­tures. See Trade Prices for more details or contact your local representative.
SUGGESTED USE:
LEGEND
ODS — Order Distribution System
MODEL DESCRIPTION
(ODS Model Number)
3
HEATING CAPACITIES AND EFFICIENCIES
UNIT 581A
155 154 —/154,000 123,000 15-45 80 2485 155 231 231,000/115,500 185,000 25-55 80 3057 180 270 270,000/115,500 216,000 15-45 80 4364 240 270 270,000/115,500 216,000 15-45 80 4364 240 485 485,000/242,500 388,000 35-65 80 5427
HEATING INPUT
(Btuh)
Stage 2/Stage 1
OUTPUT CAPACITY
(Btuh)
TEMPERATURE
RISE (F)
STEADY-STATE
EFFICIENCY
(%)
MINIMUM HEATING
CFM
CAPACITY RATINGS
UNIT 581A
155 13 146,000 13.91 10.5 12.8 180 15 186,000 18.05 10.3 10.5 240 20 234,000 25.29 9.3 9.3
ARI — Air Conditioning and Refrigeration Institute EER — Energy Efficiency Ratio IPLV — Integrated Part-Load Values
NOTE:
Rated in accordance with ARI Standards 360-86. Ratings are net values, reflecting the effects of circulating fan heat. Ratings are based on:
NOMINAL
TONS
LEGEND
NET COOLING
(Btuh)
TOTAL
kW
EER IPLVCAPACITY
Cooling Standard: 80 F db, 67 F wb indoor entering-air temperature and 95 F db air entering out-
door unit. IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and 80 F db outdoor entering-air
temperature.
4
DIMENSIONAL DRAWING — 581A155,180
UNIT
MAXIMUM SHIPPING
581A
WEIGHT
155 154 1920 871 155 231 1940 880 180 270 2310 1048
UNIT 581A
WEIGHT OF CORNER* DIMENSIONS
ABCD X Y Z
Lb Kg Lb Kg Lb Kg Lb Kg Ft-in. mm Ft-in. mm Ft-in. mm
155 154 365 166 360 163 373 169 540 245 3-2 965 3-1 155 231 372 169 363 165 377 171 547 248 3-2 965 3-1 180 270 509 231 506 230 475 216 519 235 3-7
3
⁄81102 3-43⁄81035 1- 8 508
*Weights are for unit only and do not include options or crating.
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Center of gravity.
3. Direction of airflow.
4. Ductwork to be attached to accessory roof curb only.
5. Minimum clearance: a. Rear: 78-09 (2134) for coil removal. This dimension can be reduced to
48-09 (1219) if conditions permit coil removal from the top. b. Left side: 48-09 (1219) for proper condenser coil airflow. c. Front: 48-09 (1219) for control box access. d. Rightside: 48-09 (1219) for proper operation of damper and power ex-
haust (if so equipped). e. Top: 68-09 (1829) to assure proper condenser fan operation. f. Local codes or jurisdiction may prevail.
6. With the exception of clearance for the condenser coil and the damper/ power exhaust as stated in Note No. 5, a removable fence or barricade requires no clearance.
7. Dimensions are from outside of corner post. Allow 08­side for top cover drip edge.
3
⁄8949 1-10 559
1
⁄4946 1-10 559
5
⁄169 (8) on each
5
DIMENSIONAL DRAWING — 581A240
UNIT 581A
ABCD A B C D E
Lb Kg Lb Kg Lb Kg Lb Kg Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm
240 270 523 237 541 245 574 260 596 270 3-4 1016 3-7 1092 0-3 76 6-11 240 485 465 211 486 220 725 329 737 334 4-2 1270 3-5 1041 0-4
CORNER WEIGHT* DIMENSIONS
1
⁄2114 8- 71⁄42623 3-35⁄81006
*Weights are for unit only and do not include options or crating.
UNIT 581A
240 270 2514 1140 240 485 2793 1267
1
⁄22121 1-713⁄16504
MAXIMUM SHIPPING
WEIGHT
Lb Kg
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Center of gravity.
3. Direction of airflow.
4. Ductwork to be attached to accessory roof curb only.
5. Minimum clearance: a. Rear: 7809 (2134) for coil removal. This dimension
can be reduced to 4809 (1219) if conditions permit coil removal from the top.
b. 4809 (1219) to combustible surfaces, all four sides
(includes between units).
c. Left side: 4809 (1219) for proper condenser coil
airflow. d. Front: 4809 (1219) for control box access. e. Right side: 4809 (1219) for proper operation of
damper and power exhaust (if so equipped). f. Top: 6809 (1829) to assure proper condenser fan
operation. g. Bottom: 149 (356) to combustible surfaces (whennot
using curb). h. Control box side: 3809 (914) to ungrounded surfaces
(non-combustible). i. Control box side: 3869 (1067) to block or concrete
walls, or other grounded surfaces. j. Local codes or jurisdiction may prevail.
6. With the exception of clearance for the condenser coil and the damper/power exhaust as stated in Note No. 5, a removable fence or barricade requires no clearance.
7. Dimensions are from outside of corner post. Allow
5
⁄169 (8) on each side for top cover drip edge.
08-
6
DIMENSIONAL DRAWING — HORIZONTAL AND VERTICAL ROOF CURBS AND HORIZONTAL ADAPTER
NOTE: To prevent the hazard of stagnant water build-up in the drain pan
of the indoor-air section, unit can only be pitched as shown.
ACCESSORY
PACKAGE
NO.
308450-201
308450-202
308450-203
389210-201
389171-201*
389171-202*
389171-203*
389211-201*
CURB
HEIGHT
18-29 Standard Curb — 58-7
(355) 149 High (1703) (503)
28-09
(610)
28-09
(610)
18-119
(584)
18-29 Standard Curb — 78-2
(355) 149 High (2205) (1006)
28-09
(610)
28-09
(610)
18-119
(584)
DESCRIPTION ‘‘A’’ ‘‘B’’ ‘‘C’’ ‘‘D’’ ‘‘E’’
Standard Curb for
High Installation
Horizontal Supply and 58-7
Pre-Assembled, High-Static,
Horizontal Adapter
Standard Curb
High Installation
Horizontal Supply 78-2
Pre-Assembled, High-Static,
Horizontal Adapter
*For 581A240 high-heat applications.
COMPR SECT. — Compressor Section
LEGEND
NOTES:
1. Roof curb accessory is shipped unassembled.
2. Insulated panels,
3. Dimensions in ( ) are in millimeters.
1
⁄2-in. thick neoprene-coated, 2 lb density.
4. Direction of airflow.
5. Roof curb: 18 gage steel.
6. Attach all ductwork to roof curb.
7. Field installation of sidewall insulation is mandatory.
1
⁄169 18-713⁄
1
16
58-7
(1703)
1
16
(1703)
1
16
58-7
(1703)
13
⁄169 38-35⁄
13
16
78-2
(2205)
13
16
(2205)
13
16
78-2
(2205)
9
9
9
9
9
9
18-713⁄
(503)
18-713⁄
(503)
18-713⁄
(503)
38-35⁄ (1006)
38-35⁄ (1006)
38-35⁄ (1006)
16
9
———
16
9
———Units Requiring
16
9
58-69
(1676)
16
9
68-29
(1880)
8
9
8
9
8
9
58-69
(1676)
8
9
68-29
(1880)
08-21⁄
2
(64)
08-61⁄
4
(159)
———
———for Units Requiring
08-21⁄
2
(64)
08-61⁄
4
(159)
9
18-69
(457)Return Curb
9
18-25⁄
8
9
(371)
9
18-69
(457)and Return Curb
9
18-25⁄
8
9
(371)
7
DIMENSIONAL DRAWING — HORIZONTAL ADAPTER INSTALLATION
NOTES:
1. The 389210-201 and 389211-201 are fully factory-preassembled hori­zontal adapters which include an insulated high-static regain transition duct to substantially improve fan static performance.
2. Power exhaust and barometric relief accessories cannot be used with factory pre-assembled, high-static, horizontal adapters.
8
Loading...
+ 18 hidden pages