COMMERCIAL
SINGLE PACKAGE ROOFTOP
GAS HEATING/ELECTRIC COOLING UNITS
Model 581A
Sizes 155-240
13 to 20 Tons
Model 581A155,180
DESCRIPTION
The 581A gas heating/electric cooling rooftop units are designed to deliver optimum performance and reliability in a commercial rooftop unit.
The 13 to 20 ton units are one-piece gas heating, electric cooling units that are prewired and precharged with R-22 at the factory, making jobsite installation easy. Every unit is factory runtested prior to shipment to ensure reliable installation.
The 581A units are designed to be field-convertible from vertical
supply/return to horizontal supply/return (using an accessory
horizontal supply curb or adapter), making them easily adaptable to a wide variety of new construction and replacement applications. For vertical supply/return jobs, ductwork can be
connected directly to the roof curb, allowing ductwork to be
completed before unit is available for installation. All units include easily replaceable internal filters.
The 581A units are available in a range of heating sizes and
voltage options to meet most job requirements. Low-voltage terminal blocks make wiring connections quick and simple.
All units are listed with ETL (ETL Testing Laboratory) and ETLC
(ETL Testing Laboratory for Canadian certification). All units are
ARI (Air-Conditioning & Refrigeration Institute) approved and
comply with ASHRAE Standard 62 (American Society of Heating, Refrigeration, and Air Conditioning Engineers).
STANDARD FEATURES
INDUSTRY-LEADING COOLING EERS (Energy Efficiency Ra-
tios) assure minimum operating costs and will qualify for attractive utility rebates in many areas.
SEMI-HERMETIC COMPRESSORS are fully serviceable. They
are highly regarded and preferred by owners and users, and are
offered exclusively on the high-efficiency 13 to 20 ton 581A
units.
Two 06D semi-hermetic compressors on independent refrigeration circuits are offered on the 180 and 240 units for 2 steps of
capacity control and redundancy. A single 06D semi-hermetic
compressor with unloading capability is offered on the 155 units.
All compressors have service valves and a full complement of
Model 581A240
safety devices, including high- and low-pressure switches, overtemperature protection, an electronic compressor lockout device, and crankcase heaters.
HIGH STATIC OVERSIZED FAN MOTORS AND VARIABLEPITCH BELT DRIVES are supplied standard from the factory to
provide up to 2 in. wg of external static pressure at 400 cfm per
ton with wet coils and clean filters installed. A 5 hp motor is provided standard on the 581A180 (15-ton unit), and a 10 hp motor
is standard on the 581A240 (20-ton unit).
EASY INSTALLATION makes these units perfect for vertical
supply and return roof curb mount applications on new construction, retrofit, and replacement applications. The unique
industry-leading compact size and weight are favored by designers, contractors, owners, and users, and are significant advantages in terms of minimizing required roof structures on new
construction and retrofit jobs.
The new 581Aunitscanbeeasily converted to horizontal supply
and return with the new fan-performance-boosting horizontal
high-static regain adapter (part no. 389210-201 or 389211-201).
These vertical-to-horizontal supply/return adapters are not only
fully factory assembled with a built-in insulated transition duct,
they improve fan performance by as much as 0.6 in. wg of
static.
THE FACTORY-ASSEMBLED PACKAGE is a compact, fully
self-contained electric cooling/gas heating unit that is prewired,
prepiped, and precharged for minimum installation expense.
INTERNAL RETURN-AIR FILTERS are provided. Two-in.
throwaway filters are provided standard on all units, and can be
easily accessed. There is no need to field-fabricate filter racks
or install external filter accessories.
COMPRESSOR PROTECTION is assured. The 581A units
have high- and low-pressure protection external to the compressor. These protections prohibit operation under abnormal unit
conditions.
DUAL COMPRESSORS AND DUAL REFRIGERATION CIRCUITS (180,240 units) are provided. Two compressors, each
on its own independent circuit, provide standby reliability and
high operating efficiency.
POWER, CONTROL, AND GAS CONNECTIONS are made on
the same side of the unit to simplify installation.
Form No. PDS 581A.155.2B
INDUCED-DRAFT COMBUSTION provides the exact amount
of combustion air for the most efficient operation. Induced-draft
combustion also eliminates the flue stack, giving the unit a low
profile appearance. The draw-through design ensures safe operation under any conditions.
INTERMITTENT SPARK IGNITION eliminates the standing pilot flame that consumes gas when the furnace is shut down. The
pilot is ignited only when the thermostat calls for heat.
TUBULAR U-SHAPED CELL design of the heat exchanger
provides high-efficiency heating operation. The hot gases make
2 passes over the supply-air path to enhance efficiency.
POSITIVE-PRESSURE MECHANICAL FLUE GAS VENTING
is unaffected by adverse wind conditions.
FURNACE SAFETY CONTROLS shut off gas if there is a pilot
outage, combustion-air failure, overheating of heat exchangers,
or flame rollout.
TWO-STAGE HEATING WITH 2 INDEPENDENT GAS CONTROL SYSTEMS (180,240 units) minimizes heating costs.
These independent gas control systems make single-stage
heating possible if one stage fails.
ADVANCED DESIGN of evaporator and condenser coils provides optimum heat transfer and cooling efficiency. Coils are
computer-designed with advanced heat transfer surfaces, and
are fabricated of copper tubing with aluminum fins.
COMMERCIAL STRENGTH BASE RAILS with built-in rigging
capability allow easy rigging of unit.
WEATHER-RESISTANT CABINET is built for durability in any
climate. The cabinet is made of pre-painted, galvanized steel for
long life and high-quality appearance.
LOW-AMBIENT OPERATION is provided standard. The units
operate in cooling down to 35 F as shipped from the factory.
Low-ambient kits are not required for most applications.
COMPRESSOR VIBRATION ISOLATION MOUNTING on all
units eliminates noise-causing vibration transmission into the
conditioned space.
CRANKCASE HEATERS keep the oil free of refrigerant during
the off cycle for added compressor life and reliability.
STANDARD WARRANTIES include 1 year on parts (no labor),
with an additional 4 years on compressors (155 units) and
heat exchangers (all units). Additional extended warranties are
available.
BELT-DRIVEN EVAPORATOR-FAN MOTORS are standard on
all units and allow adjustment of the available static pressure to
meet the job requirements of even the most demanding
applications.
Manual Outdoor-Air Dampers — Package consists of a
damper which can be set at 25% outdoor air. The package includes a rainhood and birdscreen.
SUGGESTED USE
• To allow a fixed percentage of outdoor air for ventilation under
all conditions.
• The damper may be used on either vertical or horizontal
applications.
NOTE: The 25% manual outdoor-air damper will be factory
installed whenever the factory-installed economizer is not
chosen.
FIELD-INSTALLED ACCESSORY
DESCRIPTION AND USAGE
Roof Curbs (Horizontal and Vertical) — Full-perimeter galva-
nized steel support frame in 14- and 24-in. high designs provides wood nailer to attach roof counter flashing. Insulated
basepans in curb are provided to prevent condensation. Ductwork attaches to rails provided in the roof curb. A gasket is provided to form an air- and watertight seal between unit and curb.
The gasket meets the standards of the NRCA (National Roofing
Contractors’ Association).
SUGGESTED USE:
• Rooftop application for vertical or horizontal discharge.
• Slab-mounted applications when elevation of the unit is
necessary.
Horizontal Adapter — The adapter is prefabricated, factoryassembled with built-in insulated duct, and permits full perimeter mounting.
SUGGESTED USE:
• Rooftop applications for horizontal discharge where high air
delivery cfms are required.
Two-Position Damper — Package consists of a low-leak
damper assembly for easy installation. The damper will allow either 0 or 25% outdoor air into the unit any time the evaporator
fan is running. When the evaporator fan is off or when there is a
loss of power, the damper will be closed.
SUGGESTED USE:
• Allows a fixed percentage of outdoor air any time the evaporator fan is on, but closes when the evaporator fan is off to
prevent cold backdrafts and wasted energy.
• The damper may be used on either vertical or horizontal airflow applications.
Economizer — See description listed under Factory-Installed
Options Description and Usage section above.
FACTORY-INSTALLED OPTIONS DESCRIPTION
AND USAGE
Economizer — The economizer will allow a fixed percentage
(between 0 and 100%) outdoor ventilation air into the unit any
time the evaporator fan is running. A dry-bulb thermostat placed
outdoors will bring in 100% outdoor air whenever the temperature of the outdoor air alone will adequately provide cooling. If
the economizer alone cannot provide enough cooling, then simultaneous economizer and compressor operation will provide
the most economical operation.
SUGGESTED USE:
• To allow a fixed percentage of outdoor air any time the evaporator fan is on, or operates in economizer mode if outdoor air
can provide cooling, but closes when the evaporator fan is off
to prevent cold backdrafts and wasted energy.
• To reduce energy usage. Use whenever the number of hours
of operation at below 55 F is significant.
• The damper may be used on either vertical or horizontal
applications.
CONTENTS
Page
Model Description .................................3
Heating Capacities and Efficiencies ...................4
FIELD-INSTALLED ACCESSORY DESCRIPTION AND USAGE (cont)
Thermostats and Subbases — Provide staged cooling and
heating, automatic (or manual) changeover, fan control, and indicator light.
SUGGESTED USE:
• To control unit operations.
Enthalpy Control Sensor — Package consists of a solid-state
sensor to be paired with a second enthalpy sensor for differential enthalpy control. This sensor is mounted on the economizer
assembly so that it can sense building return-air temperature.
The 2 sensors will determine which combination of outdoor and
return air will provide the greatest energy savings.
SUGGESTED USE:
• To enhance economizer operation for maximum energy
savings.
NOTE: A single sensor may be used for single-sensor, outdoorair, enthalpy control if desired.
Time GuardT II Device — Package consists of a control to be
field wired into the unit controls, and provides a 5-minute delay
in compressor operation between cooling cycles.
SUGGESTED USE:
• Prevents compressor short cycling when rapid compressor
cycles may be a problem.
Head Pressure Control Device — Kit consists of an outdoorair thermostat that permits adequate head pressure control during cooling operation at low outdoor-ambient temperatures.
Refer to Trade Prices for more details or contact your local
representative.
SUGGESTED USE:
• When cooling at low-ambient outdoor temperatures is
desired.
Low-Ambient Kit — Kit consists of a solid-state control and
condenser coil temperature sensor to modulate the condenserfan motors in order to maintain condenser-coil head pressure
for proper cooling operation. Refer to Trade Prices for more details or contact your local representative.
SUGGESTED USE:
• Whenever cooling is required at low outdoor ambient temperatures (as low as –20 F).
• Low-ambient kit is not usually required when economizer is
used.
Barometric Relief Package — This package is useful when it
is necessary to remove excess pressure from the conditioned
space.
NOTE: Optional economizer is required.
SUGGESTED USE:
• When the job requires the ability to relieve internal building
pressure.
Power Exhaust Package — This package is useful when it is
necessary to remove excess pressure from the conditioned
space.
NOTE: Optional economizer is required.
SUGGESTED USE:
• When the job requires the ability to relieve internal building
pressure and pressure losses through the return-air ductwork
are greater than 0.20 in. wg.
• When the job requires the ability to move large quantities of
air to relieve pressure in the conditioned space.
Winter Start Time Delay Relay — Used in conjunction with accessory low-ambient kit or head pressure control device, permits operation in cooling at lower outdoor ambient temperatures. See Trade Prices for more details or contact your local
representative.
SUGGESTED USE:
• When job requires the ability to operate in cooling at low
outdoor-ambient temperatures.
*Weights are for unit only and do not include options or crating.
NOTES:
1. Dimensions in ( ) are in millimeters.
2.Center of gravity.
3.Direction of airflow.
4. Ductwork to be attached to accessory roof curb only.
5. Minimum clearance:
a. Rear: 78-09 (2134) for coil removal. This dimension can be reduced to
48-09 (1219) if conditions permit coil removal from the top.
b. Left side: 48-09 (1219) for proper condenser coil airflow.
c. Front: 48-09 (1219) for control box access.
d. Rightside: 48-09 (1219) for proper operation of damper and power ex-
haust (if so equipped).
e. Top: 68-09 (1829) to assure proper condenser fan operation.
f. Local codes or jurisdiction may prevail.
6. With the exception of clearance for the condenser coil and the damper/
power exhaust as stated in Note No. 5, a removable fence or barricade
requires no clearance.
7. Dimensions are from outside of corner post. Allow 08side for top cover drip edge.
*Weights are for unit only and do not include options or crating.
UNIT
581A
240 27025141140
240 48527931267
1
⁄22121 1-713⁄16504
MAXIMUM SHIPPING
WEIGHT
LbKg
NOTES:
1. Dimensions in ( ) are in millimeters.
2.Center of gravity.
3.Direction of airflow.
4. Ductwork to be attached to accessory roof curb only.
5. Minimum clearance:
a. Rear: 7809 (2134) for coil removal. This dimension
can be reduced to 4809 (1219) if conditions permit
coil removal from the top.
b. 4809 (1219) to combustible surfaces, all four sides
(includes between units).
c. Left side: 4809 (1219) for proper condenser coil
airflow.
d. Front: 4809 (1219) for control box access.
e. Right side: 4809 (1219) for proper operation of
damper and power exhaust (if so equipped).
f. Top: 6809 (1829) to assure proper condenser fan
operation.
g. Bottom: 149 (356) to combustible surfaces (whennot
using curb).
h. Control box side: 3809 (914) to ungrounded surfaces
(non-combustible).
i. Control box side: 3869 (1067) to block or concrete
walls, or other grounded surfaces.
j. Local codes or jurisdiction may prevail.
6. With the exception of clearance for the condenser coil
and the damper/power exhaust as stated in Note No. 5,
a removable fence or barricade requires no clearance.
7. Dimensions are from outside of corner post. Allow
5
⁄169 (8) on each side for top cover drip edge.
08-
6
DIMENSIONAL DRAWING — HORIZONTAL AND VERTICAL ROOF CURBS AND HORIZONTAL ADAPTER
NOTE: To prevent the hazard of stagnant water build-up in the drain pan
of the indoor-air section, unit can only be pitched as shown.
ACCESSORY
PACKAGE
NO.
308450-201
308450-202
308450-203
389210-201
389171-201*
389171-202*
389171-203*
389211-201*
CURB
HEIGHT
18-29Standard Curb —58-7
(355)149 High(1703)(503)
28-09
(610)
28-09
(610)
18-119
(584)
18-29Standard Curb —78-2
(355)149 High(2205)(1006)
28-09
(610)
28-09
(610)
18-119
(584)
DESCRIPTION‘‘A’’‘‘B’’‘‘C’’‘‘D’’‘‘E’’
Standard Curb for
High Installation
Horizontal Supply and58-7
Pre-Assembled, High-Static,
Horizontal Adapter
Standard Curb
High Installation
Horizontal Supply78-2
Pre-Assembled, High-Static,
Horizontal Adapter
*For 581A240 high-heat applications.
COMPR SECT. — Compressor Section
LEGEND
NOTES:
1. Roof curb accessory is shipped unassembled.
2. Insulated panels,
3. Dimensions in ( ) are in millimeters.
1
⁄2-in. thick neoprene-coated, 2 lb density.
4.Direction of airflow.
5. Roof curb: 18 gage steel.
6. Attach all ductwork to roof curb.
7. Field installation of sidewall insulation is mandatory.
1. The 389210-201 and 389211-201 are fully factory-preassembled horizontal adapters which include an insulated high-static regain transition
duct to substantially improve fan static performance.
2. Power exhaust and barometric relief accessories cannot be used with
factory pre-assembled, high-static, horizontal adapters.
CONDENSER COILEnhanced Copper Tubes, Aluminum Lanced Fins
Rows...Fins/in.3...154...154...15
Total Face Area (sq ft)22.222.222.2
CONDENSER FANPropeller Type
Nominal Cfm10,50014,200
Quantity...Diameter (in.)3...222...30
Motor Hp...Rpm
Watts Input (Total)10903550
EVAPORATOR COILCopper Tubes, Aluminum or Copper Plate Fins
Rows...Fins/in.2...173...154...15
Total Face Area (sq ft)17.917.917.9
EVAPORATOR FANCentrifugal Type
Quantity...Size (in.)2...10 x 102...12 x 122...12 x 12
Type DriveBeltBeltBelt
Nominal Cfm500060008000
Motor Hp3.7510
Maximum Continuous Bhp4.255.90
Motor Frame Size56H184T215T
Fan Rpm Range1194-15261238-14941323-1579
Motor Bearing TypeBallBallBall
Maximum Allowable Rpm155015501550
Motor Pulley Pitch Diameter Min/Max (in.)3.4/4.45.4/6.65.8/7.0
Nominal Motor Shaft Diameter (in.)
Fan Pulley Pitch Diameter (in.)5.27.97.9
Nominal Fan Shaft Diameter (in.)13⁄
Belt, Quantity...Type...Length (in.)1...AX...421...BX...501...BX...51
Pulley Center Line Distance (in.)13.5-15.513.3-14.814.6-15.4
Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Movable Pulley Maximum Full Turns
From Closed Position
Factory Setting3.533
Factory Speed Setting (rpm)129313661451
Fan Shaft Diameter at Pulley (in.)1
Condenser Entering Air Temperature ............95F
Evaporator Entering Air Temperature ........80FEdb/
67 F Ewb
Evaporator Air Quantity ...................8000 cfm
External Static Pressure .................1.30 in. wg
Power Supply (V-Ph-Hz) ..................460-3-60
edb — Entering dry bulb
ewb — Entering wet bulb
II DETERMINE UNIT SIZE:
Select unit based on cooling requirements.
Enter Gross Cooling Capacities tables on pages 12-14 at
condenser entering temperature of 95 F,evaporator air entering at 8000 cfm and 80 F db and 67 F wb. The 581A240
270 unit will provide a gross cooling capacity of
254,000 Btuh and a sensible heat capacity of 193,800
Btuh. For evaporator air temperatures other than 80 F, calculate sensible heat capacity correction, using the formula
found in Note 3 following the Gross Cooling Capacities
tables.
NOTE: Unit ratings are gross capacities and do not include
the effect of evaporator-fan motor heat. To calculate net
capacities, see Step V.
III SELECT HEATING CAPACITY OF UNIT TO PROVIDE
DESIGN CONDITION REQUIREMENTS:
In the Heating Capacities table on page 4, note that unit
581A240 270 will provide output capacity of 216,000 Btuh,
which is adequate for the given application.
IV DETERMINE FAN SPEED AND POWER REQUIRE-
MENTS AT DESIGN CONDITIONS:
Before entering the Air Delivery tables on pages 15-17,
calculate the total static pressure required based on unit
components. From the given and the Pressure Drop table
on page 18, find:
External static pressure1.30 in. wg
Economizer0.10 in. wg
Total Static Pressure1.40 in. wg
Enter the Air Delivery table for standard 581A240 270
460-v unit at 8000 cfm and 1.40 in. wg external static pressure. Find that the rpm is 1409 and the bhp is 6.84. The
factory-installed standard motor will suffice.
V DETERMINE NET COOLING CAPACITY:
Cooling capacities are gross capacities and do not include
indoor (evaporator) fan motor (IFM) heat. Use the watts input power to the motor from the Air Delivery table.
IFM Watts = 6297
Determine net capacity using the following formula:
Net capacity = gross capacity – IFM heat
= 254,000 Btuh – 6297 Watts (3.412)
= 254,000 Btuh – 21,485 Btuh
Net capacity = 232,515 Btuh
Net sensible capacity = 193,800 – 21,485 Btuh
Net sensible capacity = 172,315 Btuh
The 581A240 270 is the correct selection for the given
conditions.
Btuh
Watt
11
GROSS COOLING CAPACITIES
581A155 (13 TON)
Air Entering
Evaporator
CfmBF
37500.06
43750.07
50000.08
56250.09
62500.10
581A155 (13 TON) (cont)
Air Entering
Evaporator
CfmBF
37500.06
43750.07
50000.08
56250.09
62500.10
BF— Bypass Factor
Edb— Entering Dry Bulb
Ewb— Entering Wet Bulb
kW— Compressor Motor Power Input
MBtuh — Btuh in thousands
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
t=t –
ldbedb
t= Wet-bulb temperature corresponding to enthalpy of air
Bhp— Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates standard operating range.
2.Indicates field-supplied motor and drive required.
3. All other numbers indicate field-supplied drive required.
4.
5. Factory shipped motor drive range is 1194 to 1526 rpm. Other rpms
indicates maximum bhp/watts of standard motor and drive.
require a field-supplied drive.
0.20.40.60.81.0
1.21.41.61.82.0
External Static Pressure (in. wg)
Standard Belt-Drive Motor
External Static Pressure (in. wg)
6. Static pressure losses (i.e., economizer) must be added to external
static pressure before entering Air Delivery table. See page 18 for
accessory/FIOP static pressure information.
7. Interpolation is permissible. Do not extrapolate.
8. Maximum continuous bhp is 4.25 and the maximum continuous
watts are 3775. Extensive motor and drive testing on these units ensures that the full horsepower range of the motor can be utilized with
confidence. Using your fan motors up to the wattage ratings shown
will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected.
Bhp— Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates standard operating range.
2.Indicates field-supplied motor and drive required.
3. All other numbers indicate field-supplied drive required.
4.
5. Factory shipped motor drive range is 1194 to 1526 rpm. Other rpms
indicates maximum bhp/watts of standard motor and drive.
require a field-supplied drive.
0.20.40.60.81.0
1.21.41.61.82.0
External Static Pressure (in. wg)
Standard Belt-Drive Motor
External Static Pressure (in. wg)
6. Static pressure losses (i.e., economizer) must be added to external
static pressure before entering Air Delivery table. See page 18 for
accessory/FIOP static pressure information.
7. Interpolation is permissible. Do not extrapolate.
8. Maximum continuous bhp is 5.9, and the maximum continuous watts
are 5180. Extensive motor and drive testing on these units ensures
that the full horsepower range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will
not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
Bhp— Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates standard operating range.
2. All other numbers indicate field-supplied drive required.
3.
4. Factory shipped motor drive range is 1323 to 1579 rpm. Other rpms
indicates maximum bhp/watts of standard motor and drive.
require a field-supplied drive.
0.20.40.60.81.0
1.21.41.61.82.0
External Static Pressure (in. wg)
Standard Belt-Drive Motor
External Static Pressure (in. wg)
5. Static pressure losses (i.e., economizer) must be added to external
static pressure before entering Air Delivery table. See page 18 for
accessory/FIOP static pressure information.
6. Interpolation is permissible. Do not extrapolate.
7. Maximum continuous bhp is 10.2 for 208/230-v units and 11.8 for
460-v units. The maximum continuous watts are 9510 for the 208/
230-v units and 11,000 for the 460-v unit. Extensive motor and drive
testing on these units ensures that the full horsepower range of the
motor can be utilized with confidence. Using your fan motors up to
the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
NOTE: The 389210-201, 389211-201 high static regain
adapter accessories may be used to provide horizontal
supply/return.
Horizontal Supply/Return Fan Performance
With 389210-201 or 389211-201 High Static Regain Adapter
17
NOTE: The 389210-201, 389211-201 horizontal supply/
return adapter accessories improve 581A fan performance by increasing external static pressure by amount
shown above.
1. The factory-assembled horizontal adapter substantially improves fan performance. See graph on
page 17.
2. The static pressure must be added to external static pressure. The sum and the evaporator
entering-air cfm should then be used in conjunction with the Air Delivery table to determine blower
rpm, bhp, and watts.
FLA— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM— Indoor (Evaporator) Fan Motor
LRA— Locked Rotor Amps
MCA— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC— National Electrical Code
OFM— Outdoor (Condenser) Fan Motor
RLA— Rated Load Amps
*This is the maximum size permissible; smaller fuse size may be used where con-
NOTES: In compliance with NEC requirements for multimotor and combination
load equipment (refer to NECArticles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The Canadian units may be fuse
or circuit breaker.
6
SIZE
19
OPERATING SEQUENCE
COOLING, UNITS WITHOUT ECONOMIZER — When thermo-
stat calls for cooling, terminals G and Y1 are energized. The indoor (evaporator) fan contactor (IFC) and compressor contactor
no. 1 (C1) are energized, and evaporator-fan motor, compressor no. 1 (581A180,240) or unloaded compressor (581A155),
and condenser fan start. The condenser-fan motor runs continuously while unit is cooling. For units with 2 stages of cooling, if
the thermostat calls for a second stage of cooling by energizing
Y2, compressor contactor no. 2 (C2) is energized and compressor no. 2 starts (581A180,240) or compressor no. 1 runs fully
loaded (581A155).
HEATING, UNITS WITHOUT ECONOMIZER
NOTE: The 581A155 (High Heat), 180,240 units have 2 stages
of heat.
Set thermostat system switch at HEAT or AUTO. position and
set fan switch to AUTO. position for heating.
When first-stage thermostat calls for heat, time-delay relay for
evaporator fan begins timer sequence. Induced-draft relay
closes, and induced-draft motor starts.
Pressure switch closes and pilot valve no. 1 opens, allowing gas
to flow to the first-stage pilot. Spark ignitor ignites pilot flame.
Sensor detects flame and the main gas valve no. 1 opens. Gas
flows to main burners and first-stage burners ignite. Spark ignitor turns off.
When sequence is complete, time-delay relay closes and
evaporator fans start.
Second Stage — 581A155 High-Heat and 581A180,240
Units — With an additional heating call, the second-stage ther-
mostat closes. (The control relay closes during the first stage of
operation.) Pilot valve no. 2 opens, and the spark ignitor ignites
pilot. The sensor detects a flame and energizes main gas valve
coil no. 2, opening main gas valve no. 2. Gas flows to the main
burners, and the second stage burners ignite. The spark ignitor
turns off.
When the second-stage thermostat is satisfied, the secondstage gas valve closes.
When the first-stage thermostat is satisfied, the first-stage gas
valve closes. The induced-draft motor turns off, the time relay
opens, and the timer sequence begins. When the sequence is
complete, the evaporator-fan motor turns off.
COOLING, UNITS WITH ECONOMIZER — Upon a call for
cooling, when outdoor ambient is above the enthalpy control
setting, the economizer damper moves to VENT position. The
compressor(s) and evaporator and condenser fans energize.
Upon a first call for cooling, when outdoor ambient is below the
enthalpy control setting, the evaporator fan starts and the
economizer is fully open. The compressor(s) remains off.
Upon a second-stage call for cooling, compressor no. 1 is energized and mechanical cooling is integrated with economizer
cooling. If the outdoor-air temperature drops below 50 F, a cooling lockout switch prevents the compressors from running.
When supply-air temperature drops below a fixed set point, the
economizer damper modulates to maintain the temperature at
the fixed set point.
A freeze protection thermostat (FPT) is located on the evaporator coil. It detects frost build-up and turns off the compressors,
allowing the coil to clear. Once frost has melted, the compressors can be reenergized.
HEATING,UNITS WITH ECONOMIZER — Outdoor-air damper
stays at VENT position while evaporator fan is operating. Refer
to Heating, Units Without Economizer section above for remainder of operating sequence.
LEGEND FOR TYPICAL WIRING SCHEMATIC
BRK W/AT — Breaks with Amp Turns
C—Contactor, Compressor
CLO— Compressor Lockout
COM— Common
CR— Control Relay
CT— Current Transformer
DM— Damper Motor
FPT— Freeze Protection Thermostat
GND— Ground
HPS— High-Pressure Switch
HR— Heat Relay
HV— High Voltage
IP— Ignitor Pilot
ICP— Ignitor Control Pack
IDR— Induced Draft Relay
IFR— Indoor (Evaporator) Fan Relay
LOR— Lockout Relay
LPS— Low-Pressure Switch/Loss of Charge
LS— Limit Switch
MAT— Mixed Air Thermostat
MGV— Main Gas Valve
MV— Main Valve
OAT— Outdoor-Air Thermostat
OFC— Outdoor (Condenser) Fan Contactor
PGV— Pilot Gas Valve
PL— Plug Assembly
PRI— Primary
PV— Pilot Valve
SN— Sensor
TB— Terminal Block
TDR— Time-Delay Relay
TR— Timer Relay
TRAN — Transformer
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To indicate common potential only; not to represent wiring.
20
TYPICAL WIRING SCHEMATIC (581A240 270 SHOWN)
21
TYPICAL INSTALLATION
NEC — National Electrical Code
22
APPLICATION DATA
1. Ductwork — Ductwork should be attached to the curb on all
units. Interior installation may proceed before unit is set in
place on roof. If ductwork will be attached to the unit, do not
drill in condensate drain pan area — leaks may result. See
figures on page 24 for information on field-installed concentric ductwork when applicable.
2. Thru-The-Curb Service Connections — Roof curb connections allow field power wires, control wires, and gas supply
to enter through the roof curb opening.
3. Thermostat — Use of 2-stage cooling thermostat is
required.
4. Heating-to-Cooling Changeover — All units are automatic
changeover from heating to cooling when automatic
changeover thermostat and subbase are used.
5. Airflow — Units are draw-thru on cooling and blow-thru on
heating.
6. Maximum Airflow — To minimize the possibility of condensate blow-off from evaporator, airflow through units should
not exceed 500 cfm/ton.
7. Minimum Airflow — The minimum airflow for cooling is
300 cfm/ton.
8. Minimum Ambient Cooling Operation Temperature — Units
are designed to operate at outdoor temperatures down to
35 F. To operate at lower outdoor-air temperatures, see
Trade Prices for appropriate accessories, or contact your
local representative.
9. Maximum Operating Outdoor-Air Temperature — For cooling, this temperature is 120 F (180) or 125 F (155, 240).
10. HighAltitude —A change to the gas orifice may be required
at high altitudes. Refer to Altitude Compensation chart
below.
11. Minimum Temperature— Air entering the heat exchanger in
heating is 50 F continuous and 45 F intermittent.
12. Internal Unit Design — Due to the internal design (drawthru over the motor), air path, and specially designed motors, the full horsepower (maximum continuous bhp) listed
in the Specifications table and the notes following each Air
Delivery table can be utilized with extreme confidence.
Using the motors with the values listed in the Specifications
table
will not
result in nuisance tripping or premature motor
failure. The unit warranty will not be affected.
OPTION AND ACCESSORY LIST
ITEM
Integrated EconomizerXX
Manual Outdoor-Air DamperX
Two-Position DamperX
Barometric Relief DamperX
Roof Curbs (Horizontal and Vertical)X
Horizontal AdapterX
Thermostats and SubbasesX
Power ExhaustX
Head Pressure Control DeviceX
Low-Ambient KitX
Time GuardT II Control CircuitX
Enthalpy Control SensorX
Winter Start Time-Delay
*Derating of the unit is not required unless the heating value of the gas
exceeds the values listed in the table above, or if the elevation exceeds
6000 ft. Derating conditions must be 4% per thousand ft above sea
level. For example, at 4000 ft, if the heating value of the gas exceeds
1000 Btu/ft
6000 ft, the same formula applies. For example, at 7000 ft, the unit will
require a 28% derating of the maximum heating value per the National
Fuel Gas Code.
3
, the unit will require a 16% derating. For elevations above
MAXIMUM HEATING VALUE
(Btu/ft3)
23
APPLICATION DATA (cont)
EVAPORATOR-FAN MOTOR PERFORMANCE
UNIT
581A
155
180
240
LEGEND
Bhp — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the
full horsepower range of the motors can be utilized with confidence.
UNIT
VOLTAGE
208/230
4604.8
208/230
4607.9
208/23010.20951028.0
46011.8011,00014.6
MAXIMUM
ACCEPTABLE
CONTINUOUS
BHP*
4.253775
5.905180
MAXIMUM
ACCEPTABLE
OPERATING
WATTS
Using your fan motors up to the horsepower ratings shown in this table
will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
MAXIMUM
AMP DRAW
10.5
15.8
NOTE: Do not drill in this area; damage to basepan may result in
water leak.
Concentric Duct Air Distribution
NOTE: Dimensions A, A8 and B, B8 are obtained from field-
supplied ceiling diffuser.
Shaded area indicates block-off panels.
Concentric Duct Details
24
ENGINEERS’ SPECIFICATION GUIDE
GENERAL: Furnish and install single-package, outdoor rooftopmounted, electrically controlled, heating and cooling unit utilizing reciprocating compressor(s) for cooling and gas combustion
for heating duty. Unit shall discharge supply air vertically or horizontally as shown on the contract drawings.
Nominal unit electrical characteristics shall be
3 ph, 60 Hz. The unit shall be capable of satisfactory operation
within voltage limits of
COOLING CAPACITY: Total cooling capacity of the unit shall be
or greater at conditions of
at unit at
denser entering air of
tions shall be a minimum of
HEATINGCAPACITY: Total heating capacity of the unit shall be
CABINET: The cabinet shall be constructed of galvanized steel,
bonderized and coated with a prepainted, baked enamel finish.
COMPRESSOR: Compressor(s) shall be of the semi-hermetic
type with crankcase heaters and suitable vibration isolators and
dual independent refrigeration circuits shall be supplied
(180,240).
CONDENSER SECTION: The condenser coils shall have aluminum plate fins mechanically bonded to seamless copper
tubes with all joints brazed. Condenser fan shall be of the directdriven propeller type and shall discharge air vertically. Fan shall
have permanently lubricated bearings.
EVAPORATOR SECTION: Evaporator coils shall have aluminum plate fins mechanically bonded to seamless copper tubes
with all joints brazed. Evaporator fan shall be belt driven as
shown on the equipment drawings. Bearings shall be sealed,
permanently lubricated, ball-bearing type.
HEATING SECTION: The unit shall be equipped with an
induced-draft combustion system with energy saving intermittent spark ignition and redundant main gas valve. The heat exchanger shall be of the tubular section type constructed of a
minimum of 20-gage steel coated with a nominal 1.2 mil
aluminum-silicone alloy for corrosion resistance. Burners shall
be of the in-shot type constructed of aluminum coated steel.
Btuh or greater, and sensible capacity shall be Btuh
F dry bulb,F wet bulb and con-
Btuh or greater with a gas input ofBtuh.
vtov.
cfm evaporator air entering
F dry bulb. Total design condi-
Btuh/Watt.
REFRIGERANT SYSTEM: Refrigerant system shall include filter drier, fixed orifice feed system, and service gage connections on suction line, liquid line, and compressor discharge line,
as well as low-pressure and high-pressure protection.
FILTER SECTION: Filter section shall consist of factory-
v,
installed low velocity, 2-in. thick fiberglass throwaway filters of
commercially available sizes. Filter access panel shall be easy
access.
CONTROLS: Unit shall be complete with self-contained lowvoltage control circuit. Safeties shall include compressor overtemperature and overcurrent.
Heating section shall be provided with the following minimum
protection: High temperature limit switch, induced-draft pressure switch, manual reset flame rollout switch and flame proving
controls.
OPTIONS: Factory-installed integrated economizer shall include all hardware and controls to provide cooling using outdoor
air alone or in conjunction with mechanical cooling. Dampers
shall be low leakage type, not to exceed 2% leakage at 1.0 in.
wg pressure differential. Economizer shall be capable of introducing up to 100% outdoor air and shall be equipped with a
gravity relief damper. Economizer controls shall be dry-bulb
type.
On all units where the factory-installed economizer is not chosen, the factory-installed manual outdoor-air damper shall be
included.
APPROVALS: The unit shall be ETL, Canada design certified
and ETL tested and certified. All wiring shall be in accordance
with NEC and units shall meet ASHRAE Standard 62. The unit
shall be rated in accordance with ARI Standard 360. Units shall
be designed to conform to NRCA standards. Insulation and adhesive shall meet NFPA90A requirements for flame spread and
smoke generation.
ACCESSORIES: Field-installed accessories shall include: Horizontal and vertical roof curbs (14 in. or 24 in.), horizontal
adapter, economizer, two-position damper, low-ambient kit,
Time GuardT II short-cycle circuit protection, thermostat and
subbase, barometric relief damper, power exhaust, head pressure control device, winter start time-delay relay, and enthalpy
control sensor.
25
Bryant
Air Conditioning
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
UNIT MUST BE INSTALLED IN ACCORDANCE
WITH INSTALLATION INSTRUCTIONS
Copyright 1995 Carrier Corporation
Printed in U.S.A.6/95CATALOG NO. BY-3258-105
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.