Bryant 580F036-150 User Manual

HEATING & COOLING SUBMITTAL
Dura
Pac
Series
Unit 580F036-150
1
3 to 12
COMMERCIAL SINGLE-PACKAGE
ROOFTOP GAS HEATING/
ELECTRIC COOLING UNITS
/2 NOMINAL TONS
580F units are a single piece, gas heating/electric cooling unit, with a low profile, pre-wired, tested and charged at the factory. The units have the capability for convertible supply and return open­ings and are intended for installation on an acces­sory curb (ordered separately), or for slab mounting (for horizontal duct connections). Units are designed to accept a field-installed economizer, enthalpy control, manual or 2-position outside air damper, roof curb, as well as up to 3 choices of gas heat. Refer to accessory chart for full listing.
FEATURES
• Standard one-year full product warranty.
• Five-year protection plan for the motor­compressor.
• Five-year protection plan on heat exchangers.
• Outdoor ambient cooling operation from 25 F (–4 C) to 115 F (46 C).
• Units are tested and certified by ARI and certi­fied by UL and CSA. Factory-run test printout included in each rooftop.
• 24-volt control circuit, with resettable breaker.
• Two-inch disposable-type return air filters in ded­icated rack.
• Hermetic compressor on independent circuit with internal line break and overload protection, self­lubricating with internal discharge muffler.
• Refrigeration circuit contains a filter drier to trap dirt and particles.
• Two-speed direct-drive evaporator fan on sizes 036-060. All other sizes are belt driven. Adjustable belt-drive fans are optional on 036­060 sizes.
• Non-corrosive condensate pan with self-draining design with both bottom and side drain connections.
• Thru-the-bottom power, control and gas entry capability.
• Indoor and outdoor coils constructed of alumi­num fins mechanically bonded to seamless copper tubes.
• Single point electrical and gas connections.
• Direct-drive propeller condenser fan totally enclosed with permanently lubricated bearings.
• Pre-painted, insulated cabinet with primed inner panels, certified 500-hr salt spray test and non­corrosive screws.
• Large, easily removable panels provide ready access to unit components for rapid removal or maintenance.
S U B M I T TA L D ATA
Job Name ______________________________________
Architect _______________________________________
Engineer _______________________________________
Contractor _____________________________________
Unit Designation _________________________________
PERFORMANCE DATA
Cooling
Net Total Cap. ________________________________Btuh
Net Sensible Cap. _____________________________Btuh
Compressor Power Input _________________________kW
_______________________________ F Outdoor Air Temp.
Indoor Entering Air db_________ F wb _________ F
CFM ____________ Ext. Static Pressure ____ (in. wg)
Fan RPM ____________________________________ Bhp
SEER/EER______________________________________
Heating
Input: Stage 1 ______________ Total ___________Btuh
Output: Stage 1 ______________ Total ___________Btuh
AFUE _________________________________________%
Steady State ___________________________________%
Operating Weight ________ lbs. (unit) _______ lbs. (curb)
ELECTRICAL DATA
Power Supply to Unit ______ Volts _____ Phase _____ Hz
Minimum Circuit Amps ______________
Maximum Overcurrent Protection (Fuse Only) ___________
• Filter access door for filter access and maintenance that requires no tools.
• Induced draft (negative pressure) combustion sys­tem with Hall effect sensor to detect proper opera­tion of induced-draft motor.
• 3 to 6-ton units have one stage of cooling and 7
1
to 121/2-ton units have two stages of cooling. Units will have either one stage or two stages of gas heat­ing depending on unit size, voltage, and heating capacity.
• Heavy Alumagard™ coated heat exchangers, with aluminized steel burners.
• Heating controls with direct spark ignition and redundant gas valve. Fan switch, high temperature limit switch and flame rollout switch standard.
• Fixed orifice metering device precisely controls refrigerant flow to each circuit individually.
• Reliable accurate control circuit with color coded wires and easily accessible terminal board.
• Integrated gas control board with built-in diagnostics to determine error codes and control indoor fan on/ off delays.
• Integrated gas control board provides anti-cycle pro­tection for gas heat operation.
• Loss of charge (low pressure), freeze protection, and high pressure switches standard.
FACTORY-INSTALLED OPTIONS
EconoMi$er — Fully Modulating, Gear Driven
Copper/Copper Coils — Evaporator, Condenser, Both
/
2
Pre-Coated Condenser Coil
E-Coat (Post-Coated) Condenser Coil
Unit-Mounted Non-Fused Disconnect Switch
115-Volt Convenience Outlet
Alternate Motor and Drive (except 072 and 102 size)
High-Static Motor (except 150 size)
25% Manual Air Damper
FIELD-INSTALLED ACCESSORIES
EconoMi$er — Fully Modulating, Gear Driven
EconoMi$er with 4 to 20 mA Actuator — Fully Modulating,
Gear Driven
Power Exhaust for EconoMi$er
EconoMi$er/Power Exhaust
25% Open Two-Position Damper
25% Open Manual Air Damper
100% Open Two-Position Damper
Durablade Economizer
Solid-State Enthalpy Control
Differential Enthalpy Control
Roof Curb (14- or 24-in. Height)
Thru-the-Bottom/Roof Curb Electrical and
Gas Connection Kit
Time Guard® II Compressor Anti-Cycle Control
Condenser Coil Hail Guard
Condenser Coil Protector
–20 F Motormaster® Low Ambient Control Kit
Programmable Set-Back Thermostat
Liquid Propane (LP) Gas Kit
Flue Hood Protector Kit
Flue Discharge Deflector
Indoor Fan/Filter Status Indicator
Other ____________________