Bryant 580F User Manual

Page 1
installation, start-up and service instructions
Dura
SINGLE PACKAGE ROOFTOP GAS HEATING/ELECTRIC COOLING UNITS
Cancels: II 580F-36-4 II 580F-36-5
580F
Pac
Series
Sizes 036-073
3 to 6 Tons
10/1/05
IMPORTANT — READ BEFORE INSTALLING
1. Read and become familiar with these installation instructions before installing this unit (Fig. 1A and 1B).
2. Be sure the installation conforms to all applicable lo­cal and national codes.
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 -34
I. Step 1 — Provide Unit Support. . . . . . . . . . . . . . . . . 1
II. Step 2 — Field Fabricate Ductwork . . . . . . . . . . . . . 4
III. Step 3 — Install External Trap for
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
IV. Step 4 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . 4
V. Step 5 — Install Flue Hood . . . . . . . . . . . . . . . . . . . . 6
VI. Step 6 — Install Gas Piping . . . . . . . . . . . . . . . . . . . 6
VII. Step 7 — Make Electrical Connections . . . . . . . . . 10
VIII. Step 8 — Adjust Factory-Installed Options. . . . . . 14
IX. Step 9 — Adjust Evaporator-Fan Speed . . . . . . . . 22
PRE-START-UP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35-37
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37-43
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . .43-48
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install, repair, or servic e air-conditioning equipment.
Untrained personnel can perform basic maintenance func­tions of cleaning coils and filters and replacing filters. All other operations sh o uld be perfor me d by trai ne d se rvi ce per­sonnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing opera tions.
WARNING: Disconnect gas piping from unit when leak testing at pressure greater than 1/2 psig. Pres­sures greater tha n resulting in hazardous condition. If gas valve is sub­jected to pressure greater than replaced before use. When pressure testing field­supplied gas piping at pressures of unit connected to such piping must be isolated by man­ually closing the gas valve.
WARNING: Before performing service or mainte­nance operations on unit, turn off main power switch to unit and install a lockout tag. Electrical shock could cause personal injury.
CAUTION: Ensure voltage listed on unit data plate agrees with electrical supply p r ov ided fo r t he unit .
Unit is ship ped in t he ve rti cal d uc t con figu rat ion . To convert t o horizontal configuration, remove screws from side duct open­ing covers and remove covers. Using the same screws, install covers on vertical duct openings with the insulation-side down. Seals around duct openings must be tight. See Fig. 2.
Confirm before installation of unit that voltage, amperage and circuit protection requirements listed on unit data plate agree with power supply provided.
I. STEP 1 — PROVIDE UNIT SUPPORT
A. Roof Curb
Assemble and install accessory roof curb in accordance with instructions shipped with curb. See Fig. 3. Install insulation, cant strips, roofing felt, and counter flashing as shown. Duct-
work must be attached to curb, not to the unit. The accessory thru-the-bottom power and gas connection package must be installed before the unit is set on the roof curb. If field-
installed (thru-the-roof curb) gas connections are desired, use factory-supplied to mount the thru-the-roof curb connection to the roof curb. Gas connections and power connections to the unit must be field installed after the unit is installed on the roo f curb.
If electric and control wiring is to be routed through the basepan, attach the accessory thru-the-bottom service con­nections to the basepan in accordance with the accessory installation instructions.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 3. Improperly applied gasket can result in air leaks and poor unit performance.
Curb should be level. Unit leveling tolerances are shown in Fig. 4. This is necessary for unit drain to function properly. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
1
/2 psig will cause g as valve damage
1
/2 psig, it must be
1
/2 psig or less, a
INSTALLATION
3
/4-in. pipe coupling and gas plate assembly
Page 2
2
Fig. 1A — Base Unit Dimensions — 580F036-072
Page 3
3
Fig. 1B — Base Unit Dimensions — 580F073
Page 4
Fig. 2 — Horizontal Conversion Panels
B. Slab Mount (Horizontal Units Only)
Provide a level concrete slab tha t extends a minimum of 6 in. beyond unit cabi ne t. I nsta ll a grav el apr on in f ron t of con dens er coil air inlet to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.
C. Alternate Unit Support
A non-combustible sleepe r rail can be used in the unit curb support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side.
II. STEP 2 — FIELD FABRICATE DUCTWORK
Secure all ducts to roof curb and building s tructure on verti ­cal ducted units. Do not connect ductwork to unit. For h or i­zontal applications, fiel d-supplie d flanges sh ould b e attach ed to horizontal duct openings and all ductwork should be secured to the flanges. Insulate and weatherproof all exter­nal ductwork, joints , and roo f openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through a n unc ondit i one d spa ce must be insu­lated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with appli­cable fire codes.
A minimum clearance is not required around ductwork. Cab­inet return air static pressure (a negative condition) should not exceed 0.35 in. wg with economizer or 0.45 in. wg with­out economizer.
These units are designed for a minimum continuous heating return-air temperature of 50 F (dry bulb), or an intermittent operation down to 45 F (dry bulb), such as when used with a night set-back thermostat.
To operate at lower return-air temperatures, a field-supplied outdoor air temperature control must be used to initiate both stages of heat when the temperature is below 45 F. Indoor comfort may be compromised when these lower air tempera­tures are used with insufficient heating temperature rise.
III. STEP 3 — INSTALL EXTERNAL TRAP FOR CONDEN­SATE DRAIN
The unit’s
3
/4-in. condensate drain connections are located on the bottom and side of the unit. Unit discharge connec­tions do not determine the use of drain connections; either drain connection can be used with vertical or horizontal applications.
When using the standard side drain connection, make sure the plug (Red) in the alternate bottom connection is tight before installing the unit.
To use the bottom drain connection for a roof curb installation, relocate the factory-i nstalle d plug (Re d) from t he bott om con­nection to the side connection. The center dr ain plug l ooks like a star connection, however it can be removed with a
1
/2-in. socket drive. See Fig. 5A. The piping for the condensate drain and external trap can be completed after the unit is in place.
All units must have an external trap for condensate drainage. Install a trap at least 4-in. deep and protect against freeze-up. If drain line is installed downstream from the external trap, pitch the line away fr om the unit at 1 in. per 10 ft of r un. Do not use a pipe size smaller than the unit connection (
3
/4 in.). See Fig. 5B.
IV. STEP 4 — RIG AND PLACE UNIT
Inspect unit for transportation damage. File any claim with transportation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by using unit frame as a ref erence. See Table 1 and Fi g. 6 for additional information.
Lifting holes are provided in base rails as shown in Fig. 1A and 1B. Refer to rigging instructions on unit.
CAUTION: All panels must be in place when rigging. Unit is not designed for handling by a fork truck. Damage to unit may result.
4
Page 5
ROOF CURB
ACCESSORY
CRRFCURB001A01
CRRFCURB002A01
A UNIT SIZE
1-2 [356]
2-0 [610]
580F
036-073
1-4 [406]
D ALT
DRAIN
HOLE
13/4″
[44.5]
GAS POWER CONTROL
3
/4″ [19] NPT
1
/2″ [12.7] NPT3/4″ [19] NPT
3
/4″ [19] NPT 11/4″ [31.7]
NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels.
3. Dimensions in [ ] are in millimeters.
4. Roof curb, galvanized steel.
5. Attach ductwork to curb (flanges of duct rest on curb).
6. Service clearance: 4 ft on each side.
CONNECTOR
PKG. ACCY.
BC
CRBTMPWR001A01 CRBTMPWR002A01 1 CRBTMPWR003A01
1-9
11
[551]
/16″
CRBTMPWR004A01
7. Direction of airflow.
8. Connector packages CRBTMPWR001A01 and 2A01 are for thru-the-curb type gas. Packages CRBTMPWR003A01 and 4A01 are for thru-the-bottom type gas connections.
3
/4″ [19] NPT
1
/4″ [31.7]
1
/2″
[12.7]
NPT
ACCESSORY
POWER
1
/2″
[12.7]
NPT
Fig. 3 — Roof Curb
5
Page 6
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-B B-C A-C
0.5 1.0 1.0
Fig. 4 — Unit Leveling Tolerances
DRAIN PLUG
NOTE: Drain plug is shown in factory-installed position.
DRAIN PLUGHORIZONTAL
Fig. 5A — Condensate Drain Pan
NOTE: Trap should be deep enough to offset maximum unit static dif-
ference. A 4-in. trap is recommended.
Fig. 5B — Condensate Drain Piping Details
A. Positioning
Maintain cleara nce around and abov e unit to provide mini ­mum distance from combustible materials, proper airflow, and service access. See Fi g. 1A and 1B. A properly positioned unit will have the fol lo wing c l ea ranc es be twe en uni t and r o of
1
curb:
/4-in. clearance between roof curb and base rails on each side and duct end of unit; 1/4-in. clearance between roof curb and condenser coil end of unit . (See Fig. 3, section C-C.)
Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of contami­nated air.
Be sure that unit is installed such that snow will not block the combustion intake or flue outlet.
Unit may be installed directly on wood flooring or on Class A, B, or C roof-covering material when roof curb is used.
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
Flue vent discharge must have a minimum horizontal clear­ance of 4 ft from electric and gas meters, gas regulators, and gas relief equipment.
Minimum distance between unit and other electrically live parts is 48 inches.
Flue gas can deteriorate building materials . Orie nt unit suc h that flue gas will not affect building materials.
Adequate combustion-air space must be provided for proper operation of this equipment. Be sure that installation complies with all local codes and Section 5.3, Air for Combus­tion and Ventilation, NFGC (National Fuel Gas Code), and ANSI (American National Standards Institute) Z223.1, and NFPA (National Fire Protectio n As so ci atio n) 5 4 TI A -54 -84- 1. In Canada, installation must be in accordance with the CAN1-B149 installation codes for gas burning appliances.
After unit is in position, remove rigging skids and shipping materials.
V. STEP 5 — INSTALL FLUE HOOD
Flue hood is shipped screwed to the basepan beside the burner compartment access panel. Remove from shipping location and using screws provided, install flue hood and screen in location shown in Fig. 7.
VI. STEP 6 — INSTALL GAS PIPING
Unit is equipped for use wi th type of gas shown on name­plate. Refer to local building codes, or in the absence of local codes, to ANSI Z223.1 entitled National Fuel Gas Code. In Canada, installation must be in accordance with the CAN1.B149.1 and CAN1.B149.2 installation codes for gas burning appliances.
For natural gas applications, gas pressure at unit gas con­nection must not be less than 4 in. wg or greater than
13.0 in. wg while unit is oper atin g. On 580F04 8,0 60,072 high heat units, the gas pressure at unit gas connection must not be less than 5 in. wg or greater than 13 in. wg while the unit is operating. For propane applications, the gas pressure must not be less than 5 in. wg or greater than 13 in. wg at the unit connection.
Size gas supply piping for 0.5 in. wg maximum pressure drop. Do not use supply pipe smaller than unit gas connec­tion. Support gas pipi ng as shown in the ta ble in Fig. 8. For example, a
3
/4-in. gas pipe must have one field-fabricated support beam every 8 ft. Therefore, an 18-ft long gas pipe would have a minimum of 2 support beams, a 48-ft long pipe would have a minimum of 6 support beams.
See Fig. 8 for typical pipe guide and locations of external manual main shutoff valve.
CAUTION: When connecting the gas line to the unit gas valve, the installer MUST use a backup wrench to prevent valve damage.
6
Page 7
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit.
3. Unit weights do not include economizer. See Table 1 for econo­mizer weights.
CAUTION: All panels must be in place when rigging. Unit
is not designed for handling with a fork truck. Damage to unit may result.
580F UNIT SIZE
036 510 231 048 520 236 060 540 245 072 615 279 073 665 302
Fig. 6 — Rigging Details
MAX WEIGHT “A” “B” “C” Lb Kg in. mm in. mm in. mm
73.69 1872 37.50 953 33.35 845
7
Page 8
Table 1 — Physical Data
580F UNIT SIZE 036 048 060 072 073 NOMINAL CAPACITY (tons) 34566 OPERATING WEIGHT (lb)
Unit
Al/Al* 460 470 490 565 615 Al/Cu* 465 476 497 576 Cu/Cu* 468 482 505 587
Economizer
EconoMi$er IV 50 50 50 50
Roof Curb† 115 115 115 115 115
COMPRESSOR Reciprocating Scroll
Quantity 11111 No. Cylinders (per Circuit) 22222 Oil (oz) 50 50 50 54 60
REFRIGERANT TYPE R-22
Expansion Device Fixed Orifice Metering Device Operating Charge (lb-oz)
Circuit 1 4-4 6-6 6-14 9-0 11-0 Circuit 2 —————
CONDENSER COIL Enhanced Copper Tubes, Aluminum Lanced Fins
Rows...Fins/in. 1...17 2...17 2...17 2...17 2...17 Total Face Area (sq ft) 8.36 8.36 10.42 10.42 16.5
CONDENSER FAN Propeller Type
Nominal Cfm 3500 4000 4000 4000 4100 Quantity...Diameter (in.) 1...22.0 1...22.0 1...22.0 1...22.0 1...22.0 Motor Hp...Rpm Watts Input (Total) 325 325 325 325 320
EVAPORATOR COIL Enhanced Copper Tubes, Aluminum Double-Wavy Fins
Rows...Fins/in. 2...15 2...15 3...15 4...15 4...15 Total Face Area (sq ft) 4.17 5.5 5.5 5.5 5.5
EVAPORATOR FAN Centrifugal Type
Quantity...Size (in.) Std 1...10 x 10 1...10 x 10 1...11 x 10 1...10 x 10 1...10 x 10
Type Drive Std Direct Direct Direct Belt Belt
Nominal Cfm 1200 1600 2000 2100 2100 Maximum Continuous Bhp Std .34 .75 1.20 2.40 2.40
Motor Frame Size Std 48 48 48 56 56
Nominal Rpm High/Low (Direct Drive) Std 860/800 1075/970 1075/970
Fan Rpm Range Std 1070-1460 1070-1460
Motor Bearing Type Ball Ball Ball Ball Ball Maximum Allowable Rpm 2100 2100 2100 2100 2100 Motor Pulley Pitch Diameter Min/Max (in.) Std 2.8/3.8 2.8/3.8
Nominal Motor Shaft Diameter (in.) Std
Fan Pulley Pitch Diameter (in.) Std ———4.54.5
Belt, Quantity...Type...Length (in.) Std 1...A...40 1...A...40
Pulley Center Line Distance (in.) Std 14.7-15.5 14.7-15.5
Speed Change per Full Turn of Std —— — 8080
Movable Pulley Flange (rpm) Alt 48 70 80
Movable Pulley Maximum Full Turns Std ——— 55
From Closed Position Alt 556——
Factory Setting Std —— — 33
Factory Speed Setting (rpm) Std 1226 1226
Fan Shaft Diameter at Pulley (in.)
Alt 1...10 x 10 1...10 x 10 1...10 x 10 High-Static 1...10 x 10 1...10 x 10 1...11 x 10 1...10 x 10 1...10 x 10
Alt Belt Belt Belt High-Static Belt Belt Belt Belt Belt
Alt 1.20 1.20 1.30/2.40** High-Static 2.40 2.40 2.90 2.90 2.90
Alt 48 48 56 High-Static 56 56 56 56 56
Alt ————— High-Static —————
Alt 685-1045 770-1175 878-1192 High-Static 1075-1455 1075-1455 1300-1685 1300-1685 1300-1685
Alt 1.9/2.9 1.9/2.9 2.4/3.4 High-Static 2.8/3.8 2.8/3.8 3.4/4.4 3.4/4.4 3.4/4.4
Alt High-Static
Alt 4.5 4.0 4.5 High-Static 4.5 4.5 4.5 4.5 4.5
Alt 1...A...34 1...A...34 1...A...39 High-Static 1...A...39 1...A...39 1...A...40 1...A...40 1...A...40
Alt 10.0-12.4 10.0-12.4 14.7-15.5 High-Static 10.0-12.4 10.0-12.4 14.7-15.5 14.7-15.5 14.7-15.5
High-Static 65 65 60 60 60
High-Static 66555
Alt 33 3—— High-Static 3
Alt 829 932 1035 High-Static 1233 1233 1416 1416 1416
LEGEND Al Aluminum
Bhp — Brake Horsepower Cu — Copper
*Evaporator coil fin material/condenser coil fin material. Contact your local
Bryant representative for details about coated fins.
†Weight of 14-in. roof curb.
**Single phase/three-phase.
1
/4...1100
1
/
2
1
/
2
5
/
8
1
/
2
5
/
8
††Rollout switch lockout is manually reset by interrupting power to unit or reset-
ting thermostat.
||California rated three-phase high heat models.
***Three phase standard high-heat models have heating input values as shown.
Single phase standard high heat models have one-stage heating with heating input values as follows: 580FJV036115 — 115,000 Btuh 580FJV048150 — 150,000 Btuh 580FJV060150 — 150,000 Btuh
†††California SCAQMD compliant Low NO
that are controlled to 40 nanograms per joule or less.
1
/4...1100
1
/
1
/
5
/
31/
5
/
1
/4...1100
1
31/
/
2
5
/
8
5
/
8
2
5
/
8
2 2 8
2
8
1
/4...1100
5
/
8
——
5
/
8
31/
2
5
/
8
models have combustion products
x
50
1
/4...1100
5
/
7
/
31/
5
/
8
8
2
8
8
Page 9
Table 1 — Physical Data (cont)
580F UNIT SIZE 036 048 060 072 AND 073 FURNACE SECTION
Rollout Switch Cutout Temp (F)†† 195 195 195 195 Burner Orifice Diameter
(in. ...drill size)
Natural Gas Std 074 .113...33 .113...33 .113...33 .113...33
Liquid Propane Alt 074 .089...43 .089...43 .089...43 .089...43
Thermostat Heat Anticipator Setting (amps)
208/230 v and 575 Stage 1 .14 .14 .14 .14
460 v Stage 1 .14 .14 .14 .14
Gas Input (Btuh) CA High Output 3-Phase Units
Stage 2 .14 .14 .14 .14
Stage 2 .14 .14 .14 .14
Standard Units 074 74,000/— 74,000/— 74,000/— 74,000/— (Stage 2/ Stage 1) 115*** 115,000/82,000 115,000/— 115,000/— 115,000/—
Low NOx Units 060N††† 60,000 60,000 60,000
Efficiency (Steady
State) (%) 80 80 80 80
Temperature Rise Range 074 25-55 25-55 25-55 25-55
Manifold Pressure (in. wg)
Natural Gas Std 3.5 3.5 3.5 3.5
Liquid Propane Alt 3.5 3.5 3.5 3.5 Gas Valve Quantity 1111 Gas Valve Pressure Range
Psig 0.180-0.487 0.180-0.487 0.180-0.487 0.180-0.487
in. wg 5.0-13.5 5.0-13.5 5.0-13.5 5.0-13.5 Field Gas Connection Size (in.)
HIGH-PRESSURE SWITCH (psig)
Standard Compressor 450 ± 50 500 ± 50 Internal Relief (Differential) Cutout 428 428 Reset (Auto.) 320 320
LOSS-OF-CHARGE (LOW-PRESSURE SWITCH) (psig)
Cutout 7 ± 3 Reset (Auto.) 22 ± 7
FREEZE PROTECTION THERMOSTAT (F)
Opens 30 ± 5 Closes 45 ± 5
OUTDOOR-AIR INLET SCREENS Cleanable. Screen size and quantity varies with option selected. RETURN-AIR FILTERS Throwaway
Quantity...Size (in.) 2...16 x 25 x 2
LEGEND Al Aluminum
Bhp — Brake Horsepower Cu — Copper
*Evaporator coil fin material/condenser coil fin material. Contact your local rep-
resentative for details about coated fins.
†Weight of 14-in. roof curb.
**Single phase/three-phase.
114/115 .113...33 .113...33 .113...33 .113...33 149/150 .129...30 .129...30 .129...30
060N .102...38 .102...38 .102...38 090N .102...38 .102...38 .102...38 120N .116...32 .116...32
114/115 .089...43 .089...43 .089...43 .089...43 149/150 .104...37 .104...37 .104...37
060N .082...45 .082...45 .082...45 090N .082...45 .082...45 .082...45 120N .094...42 .094...42
114|| 115,000 149|| 150,000 150,000
150*** 150,000/120,000 150,000/120,000 150,000/120,000
090N††† 90,000 90,000 90,000 120N††† 120,000 120,000
114/115 55-85 35-65 35-65 35-65 149/150 50-80 50-80 50-80 060N 20-50 20-50 20-50 090N 30-60 30-60 30-60 120N 40-70 40-70
1
/
2
††Rollout switch lockout is manually reset by interrupting power to unit or reset-
ting thermostat.
||California rated three-phase high heat models.
***Three phase standard high-heat models have heating input values as shown.
Single phase standard high heat models have one-stage heating with heating input values as follows: 580FJV036115 — 115,000 Btuh 580FJV048150 — 150,000 Btuh 580FJV060150 — 150,000 Btuh
†††California SCAQMD compliant Low NO
that are controlled to 40 nanograms per joule or less.
1
/
2
1
/
2
models have combustion products
x
1
/
2
9
Page 10
VII. STEP 7 — MAKE ELECTRICAL CONNECTIONS
WARNING: Unit cabinet must have an uninter-
rupted, unbroken electrical ground to minimize the possi­bility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accor­dance with NEC (N a tio n al Electrical Code), ANSI/N FPA, latest edition, and local electrical codes. Do not use gas piping as an electrical ground. Failure to follow this warning could result in the installer being liable for p er­sonal injury of others.
BLOWER ACCESS PANEL
A. Field Power Supply
All units except 208/230-v units are factory wired for the voltage shown on the na meplate. If the 208/230-v u nit is to be connected to a 208-v power supply, the transformer must be rewired by m oving the blac k wire with th e
1
/4-in. female space connector from the 230-volt connection and moving to the 208-volt
1
/4-in. male terminal on the primary side of the
transformer. Refer to unit label diagram for additional information.
Pigtails are provided for fie ld wire connectio ns. Use factory­supplied splices or UL (Underwriters’ Laboratories) approved copper/aluminum connector.
When installing units, provide a disconnect per the NEC. All field wiring must comply with NEC and local require-
ments. Install field wiring as foll ows:
1. Install conduit through side panel openings. Install conduit between disconnect and control box.
2. Install power lines to terminal connections as shown in Fig. 9.
Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate (see Tables 2A and 2B). On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in the legend for Tables 2A and 2B, Note 2 to determine the percent of voltage imbalance. Operation on impr op er lin e volta ge or excess ive phase imbal­ance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Bryant warranty.
B. Field Control Wiring
Install a Bryant-approved accessory thermostat assembly according to installation instructions included with the accessory. Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature in accor­dance with thermostat installation instructions. Connect thermostat wires to terminal board.
Route thermostat cable or equivalent single leads of colored wire from subbase terminals through connector on unit to low-voltage connections (shown in Fig. 10).
NOTE: For wire runs up 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over
Fig. 7 — Flue Hood Details
LEGEND
NFGC — National Fuel Gas Code
*Field supplied. NOTE: Follow all local codes.
SPACING OF SUPPORTS
STEEL PIPE
NOMINAL DIAMETER
(in.)
1
/
2
3
/4 or 1 8
1
1
/4 or larger 10
X
DIMENSION
(feet)
6
Fig. 8 — Gas Piping Guide (With Accessory
Thru-the-Curb Service Connections)
75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than n o. 18 AWG cannot be dir ectly con nect ed to the thermos tat and wi ll req uire a j unction box and s plice a t the thermostat.
Pass the control wires thro ugh the hole provided i n the cor­ner post; then feed w ires throug h the raceway buil t into the corner post to the 24-v barri er located on the le ft side of the control box. See Fig. 11. The raceway provides the UL required clearance between high-voltage and low-voltage wiring.
C. Heat Anticipator Settings
Set heat anticipator settings at 0.14 amp for the first stage and 0.14 amp for second- stage heating, when available.
10
Page 11
208/230-1-60
208/230-3-60
460-3-60
(SIZES 072 AND 073)
575-3-60
(SIZES 072 AND 073)
LEGEND
C—Contactor COMP — Compressor IFC Indoor-Fan Contactor NEC National Electrical Code TB Terminal Block
COOL STAGE 1
FAN
HEAT STAGE 1
COOL STAGE 2
HEAT STAGE 2
24 VAC HOT
24 VAC COM
N/A
OUTDOOR AIR
SENSOR
Y1/W2
G
W/W1
Y/Y2
O/W2
R
C
S1
S2
Fig. 9 — Power Wiring Connections
R
G
Y1
Y2
W1
W2
C
IPD/X
WIRE CONNECTIONS TO LOW-VOLTAGE SECTION (CONNECTION BOARD)
208/230-3-60
575-3-60, 460-3-60
(SIZES 036-060)
RACEWAY LOW VOLTAGE
CONNECTIONS
INTEGRATED GAS UNIT CONTROLLER (IGC)
THERMOSTAT DIPSWITCH SETTINGS ON
OFF
B
A
D
C
LEGEND
Field Wiring
NOTE: Underlined letter indicates active thermostat output when con­figured for A/C operation.
Fig. 10 — Low-Voltage Connections
HOLE IN END PANEL (HIDDEN)
Fig. 11 — Field Control Wiring Raceway
11
Page 12
Table 2A — Electrical Data (Without Convenience Outlet)
580F UNIT SIZE
036
(3 Tons)
048
(4 Tons)
060
(5 Tons)
072
(6 Tons)
073
(6 Tons)
NOMINAL VO LTAGE
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
TYPE
High 5.2 19.4/19.4 25/25 19/19 109/109
High 2.6 8.9 15 9 57
High 2.6 6.3 15 7 56
High 5.2 25.9/25.9 30/30 25/25 124/124
High 2.6 13.8 20 13 62
High 2.6 9.7 15 10 49
High 7.5 28.9/28.9 35/35 29/29 174/174
High 3.4 13.5 20 13 93
High 3.4 9.9 15 11 76
High 7.5 34.7/34.7 40/40 34/34 205/205
High 3.4 16.2 20 16 103
High 3.4 11.9 15 13 86
High 7.5 34.7/34.7 40/40 34/34 205/205
High 3.4 16.2 20 16 103
High 3.4 11.9 15 13 86
VO LTAGE
IFM
Std
Alt 4.9 26.6/26.6 35/35 26/26 111/111
Std
Alt 4.9 19.1/19.1 25/25 19/19 90/ 90
Std
Alt 2.1 8.4 15 8 48
Std
Alt 2.1 6.0 15 7 37
Std
Alt 4.9 35.4/35.4 45/45 34/34 133/133
Std
Alt 4.9 25.6/25.6 30/30 25/25 105/105
Std
Alt 2.1 13.3 20 13 53
Std
Alt 2.1 9.3 15 10 42
Std
Alt 6.6 44.0/44.0 60/60 42/42 184/184
Std
Alt 5.2 26.6/26.6 35/35 26/26 148/148
Std
Alt 2.6 13.5 20 13 81
Std
Alt 2.6 9.9 15 11 65
Std
Std
Std
Std
Std
Std
RANGE
Min Max RLA LRA Hp FLA FLA MCA MOCP† FLA LRA
187 254 16.2 96.01/41.4
187 254 10.2 75.01/41.4
414 508 4.4 40.01/40.8
518 632 3.7 31.01/40.8
187 254 23.3 118.01/41.4
187 254 15.4 90.01/41.4
414 508 8.3 45.01/40.8
518 632 6.4 36.01/40.8
187 254 28.8 147.01/41.4
187 254 16.0 114.01/41.4
414 508 7.4 64.01/40.8
518 632 6.2 52.01/40.8
187 254 20.6 146.01/41.4
414 508 9.5 73.01/40.9
518 632 7.6 58.41/40.6
187 254 20.6 146.01/41.4
414 508 9.5 73.01/40.9
518 632 7.6 58.41/40.6
LEGEND
FLA Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM Indoor (Evaporator) Fan Motor LRA Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC — National Electrical Code OFM — Outdoor (Condenser) Fan Motor RLA — Rated Load Amps
*Used to determine minimum disconnect per NEC.
†Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
the following formula to determine the percent of voltage imbalance. % Voltage Imbalance
= 100 x
Example: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v
max voltage deviation from average voltage
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
average voltage
452 + 464 + 455
1371
=
3
= 457
3
COMPR
(ea)
Use
OFM
(ea)
Maximum deviation is 7 v. Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
3. For units with power exhaust: If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the unit (must be in accordance with NEC and/or local codes). Determine the new MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust For example, using a 580F060 unit with MCA = 28.9 and MOCP = 35, with
CRPWREXH030A01 power exhaust. MCA New = 28.9 amps + 1.6 amps = 30.5 amps If the new MCA does not exceed the published MOCP, then MOCP would not change. The
MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.
COMBUSTION
IFM
3.5
3.5
1.3
1.3
3.5
3.5
1.8
1.8
5.9
5.9
3.1
3.1
5.2
2.6
2.6
5.2
2.6
2.6
FAN MOTOR
FLA
.6
.6
.3
.3
.6
.6
.3
.3
.6
.6
.3
.3
.6
.3
.3
.6
.3
.3
= 1.53%
POWER EXHAUST
PAR T N O.
CRPWREXH030A01 1.6 N/A 0.64 15 CRPWREXH021A01 N/A 0.9 N/A 15 CRPWREXH022A01 3.3 N/A 1.32 15 CRPWREXH023A01 N/A 1.8 N/A 15 CRPWREXH028A01 1.7 N/A 0.68 15 CRPWREXH029A01 N/A 1.0 N/A 15
POWER SUPPLY
25.2/25.2 30/30 24/24 106/106
17.7/17.7 25/25 17/17 85/ 85
7.6 15 7 44
5.5 15 6 35
34.0/34.0 40/40 32/32 129/129
24.2/24.2 30/30 23/23 101/101
13.0 20 13 51
9.2 15 10 41
43.3/43.3 60/60 42/42 161/161
27.3/27.3 35/35 27/27 128/128
13.2 20 13 71
9.7 15 11 58
32.4/32.4 40/40 31/31 180/180
15.4 20 15 90
11.4 15 12 75
32.4/32.4 40/40 31/31 180/180
15.4 20 15 90
11.4 15 12 79
7
457
MCA
(230 v)
MCA
(460 v)
MCA
(575 v)
DISCONNECT
SIZE*
(for separate
power source)
MOCP
12
Page 13
Table 2B — Electrical Data (With Convenience Outlet)
580F UNIT SIZE
036
(3 Tons)
048
(4 Tons)
060
(5 Tons)
072
(6 Tons)
073
(6 Tons)
NOMINAL VO LTAGE
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
IFM
TYPE
Std
Std
High 5.2 24.2/24.2 30/30 25/25 114/114
Std
High 2.6 11. 1 15 11 59
Std
High 2.6 8.0 15 9 58
Std
Std
High 5.2 30.7/30.7 35/35 31/31 129/129
Std
High 2.6 16. 0 20 16 64
Std
High 2.6 11. 4 15 12 51
Std
Std
High 7.5 33.7/33.7 40/40 34/34 179/179
Std
High 3.4 15. 6 20 16 96
Std
High 3.4 11. 7 15 13 77
Std
High 7.5 39.5/39.5 45/45 39/39 210/210
Std
High 3.4 18.4 25 18 105
Std
High 3.4 13. 7 20 15 90
Std
High 7.5 39.5/39.5 45/45 39/39 210/210
Std
High 3.4 18.4 25 18 105
Std
High 3.4 13. 7 20 15 90
VO LTAGE
RANGE
Min Max RLA LRA Hp FLA FLA MCA MOCP† FLA LRA
187 254 16.2 96.01/41.4
Alt 4.9 32.6/32.6 40/40 31/31 116/116
187 254 10.2 75.01/41.4
Alt 4.9 23.9/23.9 30/30 25/25 95/ 95
414 508 4.4 40.01/40.8
Alt 2.1 10.6 15 11 50
518 632 3.7 31.01/40.8
Alt 2.1 7.7 15 9 39
187 254 23.3 118.01/41.4
Alt 4.9 41.4/41.4 50/50 40/40 138/138
187 254 15.4 90.01/41.4
Alt 4.9 30.4/30.4 35/35 30/30 110/110
414 508 8.3 45.01/40.8
Alt 2.1 15.5 20 15 55
518 632 6.4 36.01/40.8
Alt 2.1 11.1 15 12 44
187 254 28.8 147.01/41.4
Alt 6.6 50.0/50.0 60/60 48/48 188/188
187 254 16.0 114.01/41.4
Alt 5.2 31.4/31.4 40/40 32/32 153/153
414 508 7.4 64.01/40.8
Alt 2.6 15.6 20 15 83
518 632 6.2 52.01/40.8
Alt 2.6 11.7 15 12 67
187 254 20.6 146.01/41.4
414 508 9.5 73.01/40.6
518 632 7.6 58.41/40.6
187 254 20.6 146.01/41.4
414 508 9.5 73.01/40.6
518 632 7.6 58.41/40.6
LEGEND
FLA Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM Indoor (Evaporator) Fan Motor LRA Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC — National Electrical Code OFM — Outdoor (Condenser) Fan Motor RLA — Rated Load Amps
*Used to determine minimum disconnect per NEC.
†Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
the following formula to determine the percent of voltage imbalance. % Voltage Imbalance
= 100 x
Example: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v
max voltage deviation from average voltage
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
average voltage
452 + 464 + 455
1371
=
3
= 457
3
COMPR
(ea)
Use
OFM
(ea)
IFM
Maximum deviation is 7 v. Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
3. For units with power exhaust: If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the unit (must be in accordance with NEC and/or local codes). Determine the new MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust For example, using a 580F060 unit with MCA = 28.9 and MOCP = 35, with
CRPWREXH030A01 power exhaust. MCA New = 28.9 amps + 1.6 amps = 30.5 amps If the new MCA does not exceed the published MOCP, then MOCP would not change. The
MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.
COMBUSTION
FAN MOTOR
FLA
3.5
3.5
1.3
1.3
3.5
3.5
1.8
1.8
5.9
5.9
3.1
3.1
5.2
2.6
2.6
5.2
2.6
2.6
POWER EXHAUST
CRPWREXH030A01 1.6 N/A 0.64 15 CRPWREXH021A01 N/A 0.9 N/A 15 CRPWREXH022A01 3.3 N/A 1.32 15 CRPWREXH023A01 N/A 1.8 N/A 15 CRPWREXH028A01 1.7 N/A 0.68 15 CRPWREXH029A01 N/A 1.0 N/A 15
.6
.6
.3
.3
.6
.6
.3
.3
.6
.6
.3
.3
.6
.3
.3
.6
.3
.3
= 1.53%
PAR T N O.
POWER SUPPLY
31.2/31.2 35/35 30/30 111/111
22.5/22.5 25/25 23/23 90/ 90
9.8 15 10 47
7.2 15 8 36
40.0/40.0 45/45 38/38 134/134
29.0/29.0 35/35 29/29 106/106
15.2 20 15 53
10.9 15 12 42
49.3/49.3 60/60 47/47 166/166
32.1/32.1 40/40 32/32 133/133
15.3 20 15 74
11.5 15 13 60
37.2/37.2 45/45 37/37 184/184
17.6 20 17 92
13.1 20 14 77
37.2/37.2 45/45 37/37 184/184
17.6 20 17 92
13.1 20 14 77
7
457
MCA
(230 v)
MCA
(460 v)
MCA
(575 v)
DISCONNECT
SIZE*
(for separate
power source)
MOCP
13
Page 14
VIII. STEP 8 — ADJUST FACTORY-INSTALLED OPTIONS
A. Manual Outdoor-Air Damper
The outdoor-air hood and screen are attached to the basepan at the bottom of the unit for shipping.
Assembly:
1. Determine quantity of ventilation required for build­ing. Record amount for use in Step 8.
2. Remove and save outdoor air opening panel and screws. See Fig. 12.
3. Separate hood and screen from basepan by removing the 4 screws securing them. Save al l screws.
4. Replace evaporator coil access panel.
5. Place hood o n front of outdo or air open ing panel. See Fig. 13 for hood details. Secure top of hood with the 4 screws removed in Step 3. See Fig. 14.
OUTDOOR AIR OPENING PANEL
3 SCREWS (SIDE)
6. Remove and save 6 screws (3 on each side) from sides of the manual outdoor-air damper.
7. Align screw holes on hood with screw holes on side of manual outdoor-air da mper. See Fig. 13 and 14. Se­cure hood with 6 screws from Step 6.
8. Adjust minimum positio n setti ng of the dampe r bla d e by adjusting the manual outdoor-air adjustment screws on the front of th e damper bla de. See Fig. 12. Slide blade vertically until it is in the appropriate po­sition determined by Fig. 15. Tighten screws.
9. Remove and save scr ews currently on sides of hood. Insert screen. Secure screen to hood using the screws. See Fig. 14.
Fig. 12 — Damper Panel with Manual Outdoor-Air
Damper Installed
Fig. 14 — Outdoor-Air Damper with
Hood Attached
Fig. 13 — Outdoor-Air Hood Details
Fig. 15 — Outdoor-Air Damper Position Setting
14
Page 15
B. Optional EconoMi$er IV
See Fig. 16 for EconoMi$er IV component locations. NOTE: These instructions are for installing the optional
EconoMi$er IV only. Refer to the accessory EconoM i$er IV installation instructions when field installing an EconoMi$er IV accessory.
1. To remove the existing unit filter access panel, raise the panel and swing the bottom outward. The panel is now disengaged from the track and can be removed. See Fig. 17.
2. The box with the economizer hood components is shipped in the compartment behind the economizer. The EconoMi$er IV controller is mounted on top of the EconoMi$er I V in the position shown in Fig. 16. The optional EconoMi$er2 with 4 to 20 mA actuator signal control does not include the EconoMi$er IV controller. To remove the component box from its shipping position, remove the screw holding the hood box bracket to the top of the economizer. Slide the hood box out of the unit. See Fig. 18.
IMPORTANT: If the power exhaust accessory is to be installed on the unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter
for use in the power exhaust hood assembly.
3. The indoor coil access panel will be used as the top of the hood. Remove the screws along the sides an d bot­tom of the indoor coil access panel. See Fig. 19.
4. Swing out indoor coil access panel and insert the hood sides under the panel (hood top). Use the screws provided to attach the hood sides to the hood top. Use screws provided to attach the hoo d sides to the unit. See Fig. 20.
5. Remove the shipping tape holding the economizer barometric relief damper in place.
6. Insert the ho od divider between the hood s ides. See Fig. 20 and 21. Secure hood divider with 2 screws on each hood side. The hood divider is also used as the bottom filter rack for the aluminum filter.
7. Open the filter clips which are located underneath the hood top. Insert the aluminum filter into the bot­tom filter rack (hood divider). Push the filter into po­sition past the op en filter clips. Close the fi lter clips to lock the filter into place. See Fig. 21.
8. Caulk the ends of the joint between the unit top panel and the hood top. See Fig. 19.
9. Replace the filter access panel.
10. Install all EconoMi$er IV accessories. EconoMi$er IV wiring is shown in Fig. 22.
Barometric flow capacity is shown in Fig. 23. Outdoor air leakage is shown in Fig. 24. Return air pressure drop is shown in Fig. 25.
x
o
B
H
d
o
o
HOOD BOX BRACKET
ECONOMI$ER IV CONTROLLER
WIRING HARNESS
ACTUATOR
OUTSIDE AIR TEMPERATURE SENSOR
LOW AMBIENT SENSOR
Fig. 16 — EconoMi$er IV Component Locations
FILTER ACCESS PANEL
COMPRESSOR ACCESS PANEL
OUTDOOR-AIR OPENING AND INDOOR COIL ACCESS PANEL
Fig. 17 — Typical Access Panel Locations
Fig. 18 — Hood Box Removal
SIDE PANEL
TOP SIDE PANEL
INDOOR COIL ACCESS PANEL
INDOOR COIL ACCESS PANEL
CAULK HERE
Fig. 19 — Indoor Coil Access Panel Relocation
15
Page 16
TOP PANEL
INDOOR COIL ACCESS PANEL
17 1/4”
LEFT HOOD SIDE
B
19 1/16”
HOOD DIVIDER
SCREW
Fig. 20 — Outdoor-Air Hood Construction
33 3/8”
BAROMETRIC RELIEF
FOR OCCUPANCY CONTROL REPLACE JUMPER WITH FIELD-SUPPLIED TIME CLOCK
DIVIDER
OUTSIDE AIR
CLEANABLE ALUMINUM FILTER
FILTER
Fig. 21 — Filter Installation
HOOD
FILTER CLIP
LEGEND
DCV — Demand Controlled Ventilation IAQ — Indoor Air Quality LA — Low Ambient Lockout Device OAT — Outdoor-Air Temperature POT — Potentiometer RAT — Return-Air Temperature
Potentiometer Defaults Settings: Power Exhaust Middle Minimum Pos. Fully Closed DCV Max. Middle DCV Set Middle Enthalpy C Setting
Fig. 22 — EconoMi$er IV Wiring
NOTES:
1. 620 ohm, 1 watt 5% resistor should be removed only when using differential enthalpy or dry bulb.
2. If a separate field-supplied 24 v transformer is used for the IAQ sensor power supply, it cannot have the secondary of the transformer grounded.
3. For field-installed remote minimum position POT, remove black wire jumper between P and P1 and set control minimum position POT to the minimum position.
16
Page 17
2500
2000
1500
1000
500
0
FLOW IN CUBIC FEET PER MINUTE (cfm)
0.05
STATIC PRESSURE (in. wg)
0.15
Fig. 23 — Barometric Flow Capacity
30
25
20
15
10
5
0
0.13 0.2 0 0.22 0. 25 0.30 0.35 0 .40 0 .45 0.50
FLOW IN CUBIC FEET PER MINUTE (cfm)
STATIC PRESSURE (in. wg)
Fig. 24 — Outdoor-Air Damper Leakage
0.25
Outdoor Air Lockout Sensor The EconoMi$er I V is equipped with an ambi ent tempera-
ture lockout switch located i n the outdoor air stream which is used to lockout the co mpresso rs belo w a 42 F ambie nt te m­perature. See Fig. 16.
Table 3 — Supply Air Sensor
Temperature/Resistance Values
TEMPERATURE (F) RESISTANCE (ohms)
–58 200,250 –40 100,680 –22 53,010
–4 29,091 14 16,590 32 9,795 50 5,970 68 3,747 77 3,000
86 2,416 104 1,597 122 1,080 140 746 158 525 176 376 185 321 194 274 212 203 230 153 248 116 257 102 266 89 284 70 302 55
6000
5000
4000
3000
2000
1000
0
0.05 0.10 0.15 0. 20 0.25 0.30 0. 35
FLOW IN CUBIC FEET PER MINUTE (cfm)
STATIC PRESSURE (in. wg)
Fig. 25 — Return-Air Pressure Drop
C. EconoMi$er IV Standard Sensors
Outdoor Air Temperature (OAT) Sensor The outdoor air temperature sensor (HH57AC074) is a 10 to
20 mA device used to measure the outdoo r-air temperature. The outdoor-air temperature is used to determine when the EconoMi$ er IV ca n be used for free cooling. The sensor is factory-installed on the EconoMi$er IV in the outdoor airstream. See Fig. 16. The ope rating range of temperatu re measurement is 40 to 100 F.
Supply Air Temperature (SAT) Sensor The supply air temperature sensor is a 3 K thermistor
located at the inlet of the indoor fan. See Fig. 26. This sensor is factory installed. The operating range of tempera­ture measurement is 0° to 158 F. See Table 3 for sensor temperature/resistance values.
The temperature sensor l ooks like an eyelet terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture.
D. EconoMi$er IV Control Modes
Determine the EconoMi$er IV control mode before set up of the control. Some modes of operation may require different sensors. Refer to Table 4. The EconoMi$er IV is supplied fr om the f ac­tory with a supply air temperature sensor and an outdoor air temperature sensor. This allows for operation of the EconoMi$er IV with outdoor air dry bulb changeover control. Additional accessories can be added to allow for different types of changeover con tro l and op era ti on of the Econ oMi $e r IV and unit.
Outdoor Dry Bulb Changeover The standard controller is shippe d from the factory config-
ured for outdoor dry bulb changeover control. The outdoor air and supply air temperature sensors are included as standard. For this control mode, the outdoor temperature is compared to an adjustable set point selected on the control. If the outdoor-air temperature is above the set point, the EconoMi$er IV will adjust the outdoor air dampers to mini­mum position. If the outdoor-air temperature is below the set point, the position of the outdoor air dampers will be controlled to pr ovide fr ee cooli ng using o utdoor ai r. When in this mode, the LED next to the free cooling set point potenti­ometer will be on. T he changeover temperat ure set point is controlled by the free cooling set poi nt pote ntiometer locat ed on the control. Se e Fig. 27. Th e s cale on the pote n tio me ter is A, B, C, and D . See Fig. 28 for the corresponding temperature changeover values.
Differential Dry Bulb Control For differential dry bulb control the standard outdoor dry
bulb sensor is used in conjunction with an additional acces­sory dry bulb sensor (part number CRTEMPSN002A00). The accessory senso r must be mounted in the return airstream. See Fig. 29. Wiring is provided in th e EconoMi$e r IV wiring harness. See Fig. 22.
17
Page 18
In this mode of operation, the outdoor air temperature is compared to the return air temperature and the lower tem­perature air stream is used for cooling. When using this mode of changeover control, turn the enthalpy setpoint potentiometer fully clockwise to the D setting. See Fig. 27.
Outdoor Enthalpy Changeover For enthalpy control, accessory enthalpy sensor (part num-
ber HH57AC078) is required. Replace the standard outdoor dry bulb temperature sensor with the accessory enthalpy sensor in the same mou nt ing lo ca tio n . Se e Fig. 16. When the outdoor air enthalpy rises above the outdoor enthalpy changeover set point, the outdoor-air damper moves to its minimum position. The outdoor enthalpy changeover set point is set with the outdoo r enthalpy set point potentiome­ter on the EconoMi$er IV controller. The set points are A, B, C, and D. See Fig. 30. The factory-installed 620-ohm jumper must be in place across terminals SR and SR+ on the EconoMi$er IV controller. See Fig. 16 and 31.
Differential Enthalpy Control For differential enthalpy control, the EconoMi$er IV con-
troller uses two enthalpy sensors (HH57AC078 and CRENTDIF004A00), one in the outside air and one in the return air duct. The EconoMi$er IV controller compares the outdoor air enthalpy to the return air enthalpy to determine EconoMi$er IV use. The contro ll er selects the lowe r en thalpy air (return or outdoor) for cooling. For example, when the outdoor air has a lower enthalpy than the return air, the EconoMi$er IV opens to b r ing in outdoor air for free cooling.
19
LED ON
18
17
16
15
mA
14
13
12
11
10
9
40
LED OFF
45
D
50
60
55
DEGREES FAHRENHEIT
LED ON
C
LED OFF
65
70
LED ON
LED OFF
75
Fig. 28 — Outdoor Air Temperature
Changeover Set Points
ECONOMI$ER IV
B
85
80
ECONOMI$ER IV CONTROLLER
RETURN AIR SENSOR
LED ON
LED OFF
90
A
100
95
GROMMET
SUPPLY AIR TEMPERATURE SENSOR MOUNTING LOCATION
SUPPLY AIR TEMPERATURE SENSOR
Fig. 26 — Supply Air Sensor Location
Fig. 27 — EconoMi$er IV Controller Potentiometer
and LED Locations
RETURN DUCT (FIELD-PROVIDED)
Fig. 29 — Return Air Temperature or Enthalpy
Sensor Mounting Location
Replace the standard outside air d ry bulb temperatu re sensor with the accessory enthalpy sensor in the same mounting loca­tion. See Fig. 16. Mount the return air enthalpy sensor in the return air duct. See Fig. 29. Wiring is provided in the EconoMi$er IV wiring harness. See Fig. 22. The outdoor enthalpy changeover set point is set with the outdoor enthalpy set point potentiometer on the EconoMi$er IV controller. When using this mode of chan geover control, turn the enthalpy s et point potentiometer fully clockwise to the D setting.
Table 4 — EconoMi$er IV Sensor Usage
ECONOMI$ER IV WITH OUTDOOR AIR
APPLICATION
Outdoor Air
Dry Bulb
Differential
Dry Bulb
Single Enthalpy HH57AC078
Differential
Enthalpy
CO
for DCV
2
Control using a
Wall-Mounted
CO
Sensor
2
CO
for DCV
2
Control using a
Duct-Mounted
CO
Sensor
2
*CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on many
different base units. As such, these kits may contain parts that will not be needed for installation.
†33ZCSENCO2 is an accessory CO
**33ZCASPCO2 is an accessory aspirator box required for duct-mounted
applications.
††CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2 and
33ZCASPCO2 accessories.
33ZCSENCO2†
33ZCASPCO2**
DRY BULB SENSOR
Accessories Required
None. The outdoor air dry bulb sensor
is factory installed.
CRTEMPSN002A00*
HH57AC078
and
CRENTDIF004A00*
33ZCSENCO2
and
sensor.
2
CRCBDIOX005A00††
OR
18
Page 19
CONTROL
CURVE
4
1
2
1
A B C D
1
6
1
CONTROL POINT
APPROX. °F (°C)
AT 50% RH
73 (23) 70 (21) 67 (19) 63 (17)
HA
NT
E
4
2
2
2
0
2
8
35
(2)
LPY
40
(4)
85
(29)90(32)95(35)
46
4
4
42
40
IR
8
3
Y A
6
DR
3
D
N
U
4
3
PO
R
32
E
P
TU
30
B
28
26
(16)
55
(13)
B
50
C
(10)
45
D
(7)
70
(21)
0
1
65
(18)
60
A
80
(27)
75
(24)
0
0
9
80
70
0
6
50
40
3
RELA
0
IVE HUM
T
100
(38)
IDITY
20
105
110
(41)
(43)
)
%
(
0
1
35
40
45
50
55
60
65
(2)
(4)
(7)
(10)
(13)
(16)
(18)
(21)
70
APPROXIMATE DRY BULB TEMPERATURE— °F (°C)
Fig. 30 — Enthalpy Changeover Settings
TR1
N1
P1
T1
AQ1
SO+
SR+
EXH
2V 10V
EXH
Open
2V 10V
DCV
2V 10V
Free Cool
B
A
Min Pos
DCV
Max
DCV
C
D
Set
Set
N
P
T
AQ
SO
SR
TR
24
24 Vac
Vac
COM
HOT
_
+
12
5
4
3
EF1
EF
Fig. 31 — EconoMi$er IV Control
Indoor Air Quality (IAQ) Sensor Input The IAQ input can be used for demand control ventilation
control based on the level of CO
measured in the spa ce or
2
return air duct. Mount the accessory IAQ sensor according to manufacturer
specifications. The IAQ sensor should be wired to the AQ and AQ1 terminals of the controller. Adjust the DCV potentiome­ters to correspond to the DCV voltage output of the indoor air quality sensor at the user-determined set point. See Fig. 32.
A
B
C
D
75
(24)
80
(27)
(29)90(32)95(35)
105
85
100 (38)
(41)
110 (43)
HIGH LIMIT CURVE
If a separate field-supplied transformer is used to power the IAQ sensor, the sensor must not be grounded or the EconoMi$er IV control board will be damaged.
Exhaust Set Point Adjustment The exhaust set point will determine when the exhaust fan
runs based on d am p er p o sit i on ( if ac ce ss or y pow e r ex ha ust i s installed). The set point is modified with the Exhaust Fan Set Point (EXH SET) potentiometer. See Fig. 27. The set point represents the damper position above which the exhaust fans will be turned on. When there is a call for exhaust, the EconoMi$er IV controller provides a 45 ± 15 second delay before exhaust fan activation to allow the dampers to open. This delay allows the damper to reach the appropriate position to avoid unnecessary fan overload.
Minimum Position C o ntrol There is a minimum damper position potentiometer on the
EconoMi$er IV c o nt ro ll er. See Fig. 27. The mini mum damper position maintains the minimum airflow into the building during the occupied period.
When using demand ventilation, the minimum damper posi­tion represents the minimum ventilation position for VOC (volatile organic compound) ventilation requirements. The maximum demand ventilation position is used for fully occu­pied ventilation.
When demand ventilation control is not being used, the min­imum position potentiometer should be used to set the occu­pied ventilation position. The maximum demand ventilation position should be turned fully clock wi se.
Adjust the minimum position potentiometer to allow the minimum amount of outdoor air, as required by local codes,
19
Page 20
CO SENSOR MAX RANGE SETTING
2
6000
5000
4000
3000
2000
1000
RANGE CONFIGURATION (ppm)
0
2345678
DAMPER VOLTAGE FOR MAX VENTILATION RATE
800 ppm 900 ppm 1000 ppm 1100 ppm
Fig. 32 — CO2 Sensor Maximum Range Setting
to enter the building. Make minimum position adjustments with at least 10 F temperature difference between the out­door and return-air temperatures.
To determine the minimum position setting, perform the following proced ur e :
1. Calculate the appropriate mixed air temperature using the following formula:
OA
(T
x
)+ (TR x
100 100
= Outdoor-Air Temperature
T
O
O
RA
) = T
M
OA = Percent of Outdoor Air TR = Return-Air Temperature RA = Percent of Return Air TM = Mixed-Air Temperature As an example, if local codes require 10% outdoor air
during occupied conditions, outdoor-air temperature is 60 F, and return-air temperature is 75 F.
(60 x .10) + (75 x .90) = 73.5 F
2. Disconnect the supply air sensor from terminals T and T1.
3. Ensure that the factory-installed jumper is in place across terminals P and P1. If remote damper posi­tioning is being used, make sure that the terminals are wired accor din g to Fig. 22 and that t he mi nimu m position potentiometer is turned fully clockwise.
4. Connect 24 vac across terminals TR and TR1.
5. Carefully adjust th e minim um positi on potent iomet er until the measured mixed-air temperature matches the calculated va lue.
6. Reconnect the supply air sensor to terminals T and T1.
Remote control of the EconoMi$er IV damper is desirable when requiring additional temporary ventilation. If a field-supplied remote potentiometer (Honeywell part num­ber S963B1128) is wired to the E co no Mi$er IV controller, th e minimum position of the damper can be controlled from a remote location.
To control the minimum damper position remotely, remove the factory-insta lled jumper on the P and P1 terminals on the EconoMi$er IV controller. Wire the field-supplied poten­tiometer to the P and P1 termina ls on the EconoMi$er IV controller. See Fig. 31.
Damper Movement Damper movement from full open to full closed (or vice
versa) takes 2
1
/2 minutes. Thermostats The EconoMi$er IV control works with conventional thermo-
stats that have a Y1 (cool stage 1), Y2 (cool stage 2), W1 (heat stage 1), W2 (heat stage 2), and G (fan). The EconoMi$er IV control do es not support space temperature sensors. Connections are made at the thermostat terminal connection board located in the main control box.
Occupancy Control The factory default configuration for the Econo Mi$er IV con -
trol is occupied mode. Occupied status is provided by the black jumper from terminal TR to terminal N. When unoccu­pied mode is desired, install a field-supplied timeclock func­tion in place of th e jumper between TR an d N. See Fig. 22. When the timeclock contacts are closed, the EconoMi$er I V control will be in occupied mode. When the timeclock con­tacts are open (removin g the 24-v signal from terminal N), the EconoMi$er IV will be in unoccupied mode.
Demand Controlled V enti lation (DCV) When using the EconoMi$er IV for demand controlled venti-
lation, there are some equipment selection criteria which should be considered. When selecting the heat capacity and cool capacity of the equipment, the maximum ventilation rate must be evaluated for design conditio ns. The maximum damper position must be calculated to provide the desired fresh air.
Typically the maximum ventilation rate will be ab out 5 to 10% more than the typical cfm required per person, using normal outside air design criteria.
A proportional anticipatory strategy should be taken with the following conditions: a zone with a large area, varied occupancy, and equipm ent that cannot exceed the req uired ventilation rate at design con dition s. Exceeding th e requ ired ventilation rate means the equipment can co ndition air a t a maximum ventilation rate that is gre ater than the requ ired ventilation rate for maximum occupancy. A proportional­anticipatory strategy will cause the fresh air supplied to increase as the room CO
level increases even though the
2
CO2 set point has not been reached. By the time the CO level reaches the set point, the damper will be at maximum ventilation and should maintain the set point.
In order to have the CO
sensor control the economizer
2
damper in this manner, first determine the damper voltage output for minimum or base ventilat ion. Base v entilatio n is the ventilation required to remove contaminants during unoccupied periods. The following equation may be used to determine the percent of outside-air entering the building for a given damper position. For best results there should be at least a 10 degree difference in outside and return-air temperatures.
OA
(TO x T
O
)+ (TR x
100 100
= Outdoor-Air Temperature
RA
) = T
M
OA = Percent of Outdoor Air TR = Return-Air Temperature RA = Percent of Return Air TM = Mixed-Air Temperature Once base ventilation has been determined, set the mini-
mum damper position potentiometer to the correct position. The same equation can be used to determine the occupied or
maximum ventilation rate to the building. For example, an
2
20
Page 21
output of 3.6 volts t o the ac tuat o r pro vide s a ba se ve ntil at io n rate of 5% and an output of 6.7 volts provides the maximum ventilation rate of 20% (or bas e plu s 15 cfm pe r pers on). Use Fig. 32 to determine the maximum setting of the CO
sensor.
2
For example, a 1100 ppm set point relates to a 15 cfm per person design. Use the 1100 ppm curve on Fig. 32 to find the point when the CO
sensor output will be 6.7 volts. Line up
2
the point on the graph with the left side of the chart to deter­mine that the range configuration for the CO
sensor should
2
be 1800 ppm. The EconoMi$er IV controller will output the
6.7 volts f rom th e CO
sensor to the actuator when the CO
2
concentration in the spac e is a t 1100 ppm . The D CV set point may be left at 2 volts since the CO
sensor voltage will be
2
ignored by the Econ oMi$er IV co ntroller u ntil it rises above the 3.6 volt setting of the minimum position potentiometer.
Once the fully occupied damper position has been deter­mined, set the maximu m da mpe r de ma nd con t ro l ve nt il atio n potentiometer to this position. Do not set to the maximum position as this can result in over-ventilation to the space and potential high-humidity levels.
CO
Sensor Configuration
2
The CO2 sensor has preset standard voltage settings that can be selected anytime afte r the sensor is powere d up. See Table 5.
Use setting 1 or 2 f or Bryant equipment. See Table 5.
1. Press Clear and Mode buttons. Hold at least 5 sec­onds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to select the preset number. See Table 5.
4. Press Enter to lock in the selection.
5. Press Mode to exit and resume normal operation.
The custom settings of the CO
sensor can be changed any-
2
time after the s ensor is energiz ed. Follow the s teps belo w to change the non-standard settings:
1. Press Clear and Mode buttons. Hold at least 5 sec­onds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
2
3. Use the Up/Down button to toggle to the NONSTD menu and press Enter.
4. Use the Up/Down button to toggle through each of the nine variables, starting with Altitude, until the desired setting is reached.
5. Press Mode to move through the variables.
6. Press Enter to lock in the selection, then press Mode to continue to the next variable.
Dehumidification of Fresh Air with DCV Control Information from ASHRAE indicates that the largest humid-
ity load on any zone is the fresh air introduced. For some applications, an energy recove ry unit is added t o reduce the moisture content of the fresh air being brought into the building when the enthalpy is hi gh. In most cases, the no r­mal heating and co oling proc esse s are m ore tha n ade quate to remove the humidity loads for most commercial applications.
If normal roof top heating and cooling operation is not ade­quate for the outdoor humidity level, an energy recovery unit and/or a dehumidification option should be con sidered.
Table 5 — C O
SETTING EQUIPMENT OUTPUT
1
Interface w/Standard
2 Proportional Any
Building Control System
3 Exponential Any
4
5 Proportional 20
Economizer
6 Exponential 15
7 Exponential 20
8 Health & Safety Proportional
Parking/Air Intakes/
9
Loading Docks
LEGEND
ppm — Parts Per Million
Proportional Any
Proportional 15
Proportional
Sensor Standard Settings
2
VENTILATION
RATE
(cfm/Person)
ANALOG
OUTPUT
0-10V
4-20 mA
2-10V
7-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
CO
CONTROL RANGE
2
(ppm)
0-2000 1000 50
0-2000 1000 50
0-2000 1100 50
0-1100 1100 50
0- 900 900 50
0-1100 1100 50
0- 900 900 50
0-9999 5000 500
0-2000 700 50
OPTIONAL
RELAY SETPOINT
(ppm)
RELAY
HYSTERESIS
(ppm)
21
Page 22
IX. STEP 9 — ADJUST EVAPORATOR-FAN SPEED
Adjust evaporator-fan speed to meet jobsite requirements. Table 6 shows fan rpm at motor pulley settings. Table 7 shows motor performance. Table 8 provides accessory static pressure drop information. Refer to Tables 9-32 to determine fan speed settings.
A. Direct-Drive Motors
The evaporator-fan motor factory speed setting is shown on label diagram affixed to base unit. If other than factory set­ting is desired, refer to label diagram for motor reconnection. See Fig. 33 for direct drive motor location.
B. Belt-Drive Motors
Fan motor pulleys are factory set for speed shown in Table 1. See Fig. 34 for belt drive motor location.
NOTE: Before adjusting fan speed, make sure the new fan speed will provi de an air temperature rise range as sho w n in Table 1.
To change fan speed:
1. Shut off unit power supply and tag disconnect.
2. Loosen belt by loosening fan motor mounting nuts. See Fig. 34.
3. Loosen movable pulley flange setscrew (see Fig. 35).
4. Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed. Increasing fan speed incr eases lo ad on motor. Do not exceed maximum speed specified in Table 1.
5. Set movable flange at nearest keyway of pulley hub and tighten setscrew. (See Table 1 for speed change for each full turn of pulley flange.)
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from mounting.
To adjust belt tension:
1. Loosen fan motor mounting nuts.
2. Slide m otor mounting plate away from fa n scroll fo r proper belt tension (
1
/2-in. deflection with 8 to 10 lb of
force).
3. Tighten motor mounting nuts.
4. Adjust bolt and tighten nut to secure motor in fixed position.
MOTOR MOUNTING PLATE NUTS
Fig. 34 — Belt Drive Motor Mounting
Fig. 33 — Direct-Drive Motor Mounting
Fig. 35 — Evaporator-Fan Pulley Adjustment
22
Page 23
Table 6 — Fan Rpm at Motor Pulley Settings*
UNIT 580F
0
036† 1045 1009 973 937 901 865 829 793 757 721 685
1
/
2
11
1
/
2
036** 1455 1423 1392 1360 1328 1297 1265 1233 1202 1170 1138 1107 1075 048† 1175 1135 1094 1054 1013 973 932 892 851 811 770 048** 1455 1423 1392 1360 1328 1297 1265 1233 1202 1170 1138 1107 1075 060† 1192 1166 1140 1114 1087 1061 1035 1009 983 957 930 904 878 060** 1685 1647 1608 1570 1531 1493 1454 1416 1377 1339 1300 072, 073†† 1460 1421 1382 1343 1304 1265 1226 1187 1148 1109 1070 072, 073** 1685 1647 1608 1570 1531 1493 1454 1416 1377 1339 1300
*Approximate fan rpm shown.
†Indicates alternate motor and drive package.
MOTOR PULLEY TURNS OPEN
22
1
/
††Indicates standard motor and drive package.
33
2
**Indicates high-static motor and drive package.
1
/
2
44
1
/
2
55
Table 7 — Motor Data
UNIT
580F
036
048
060
072, 073
LEGEND
BHP — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horse-
power range of the motors can be utilized with confidence. Using fan motors up to the horsepower ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
†Single phase/three-phase.
EVAPORATOR-FAN
MOTOR
Standard
Alternate
High Static
Standard
Alternate
High Static
Standard
Alternate
High Static
Standard
High Static
UNIT
VOLTAGE
MAXIMUM ACCEPTABLE
CONTINUOUS BHP*
MAXIMUM ACCEPTABLE
OPERATING WATTS
208/230
460 1.3
0.34 440
575 1.3
208/230
460 2.1
1.20 1000
575 2.1
208/230
460 3.0
2.40 2120
575 3.0
208/230
460 1.8
0.75 850
575 1.8
208/230
460 2.1
1.20 1000
575 2.1
208/230
460 3.0
2.40 2120
575 3.0
208/230
460 3.2
1.20 1340
575 3.2
208/230
460 3.0
1.30/2.40† 2120
575 3.0
208/230
460 3.9
2.90 2562
575 3.9
208/230
460 3.0
2.40 2120
575 3.0
208/230
460 3.9
2.90 2562
575 3.9
NOTES:
1. All indoor-fan motors 5 hp and larger meet the minimum efficiency require­ments as established by the Energy Policy Act of 1992 (EPACT) effective October 24, 1997.
2. High-static motor not available on single-phase units.
1
/
2
MAXIMUM
AMP DRAW
2.8
4.9
6.0
3.5
4.9
6.0
5.9
10.1/6.7†
8.6
6.7
8.6
6
COMPONENT
Vertical EconoMi$er IV Horizontal EconoMi$er IV
LEGEND
FIOP — Factory-Installed Option
Table 8 — Accessory/FIOP Static Pressure* (in. wg)
2250 2500 3000 3500 4000 4500 5000
0.06 0.075 0.115 0.15 0.195 0.25 0.325 — 0.10 0.15 0.21 0.275 0.34
*The static pressure must be added to external static pressure. The sum and the
evaporator entering-air cfm should then be used in conjunction with the Fan Performance tables to determine blower rpm and watts.
CFM
23
Page 24
Table 9 — Fan Performance 580F036 — Vertical Discharge Units, Standard Motor
Airflow
(Cfm)
900 0.49 0.21 253 0.50 0.23 277 0.51 0.26 307 0.55 0.31 363 1000 0.42 0.23 270 0.43 0.25 292 0.43 0.27 321 0.51 0.32 374 1100 0.37 0.24 287 0.38 0.26 307 0.39 0.28 335 0.46 0.33 385 1200 0.33 0.26 304 0.33 0.27 323 0.34 0.29 349 0.40 0.34 397 1300 0.27 0.27 321 0.28 0.29 338 0.28 0.31 364 0.34 0.34 408 1400 0.20 0.29 338 0.23 0.30 354 0.25 0.32 378 1500 0.16 0.30 355 0.18 0.31 369 0.20 0.33 392
LEGEND See page 34 for general fan performance notes. Bhp — Brake Horsepower Input to Fan
ESP — External Static Pressure (in. wg)
ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts
208 V 230, 460, 575 V 208 V 230, 460, 575 V
Low Speed High Speed
STANDARD MOTOR (DIRECT DRIVE)
Table 10 — Fan Performance 580F036 — Vertical Discharge Units, Alternate Motor (Belt Drive)*
AIRFLOW
(Cfm)
900 643 0.15 152 768 0.22 222 870 0.30 296 958 0.37 373 1037 0.46 454 1000 683 0.19 191 804 0.27 268 904 0.35 348 991 0.43 430 1069 0.52 517 1100 725 0.24 237 842 0.32 321 939 0.41 407 1025 0.50 496 1102 0.59 588 1200 767 0.29 291 880 0.38 382 976 0.48 474 1060 0.57 570 1136 0.67 668 1300 811 0.35 352 920 0.45 451 1013 0.55 550 1095 0.66 652 1170 0.76 756 1400 855 0.43 423 960 0.53 529 1051 0.64 636 1132 0.75 744 1205 0.86 855 1500 900 0.51 504 1002 0.62 617 1090 0.74 731 1169 0.85 846 1242 0.97 963
AIRFLOW
(Cfm)
900 1110 0.54 538 1177 0.63 627 1239 0.72 718 1298 0.82 813 1355 0.92 911 1000 1141 0.61 607 1207 0.70 700 1269 0.80 796 1328 0.90 895 1384 1.00 998 1100 1173 0.69 683 1238 0.79 781 1300 0.89 883 1358 0.99 987 1414 1.10 1094 1200 1205 0.77 768 1270 0.88 872 1332 0.98 979 1389 1.09 1088 —— — 1300 1239 0.87 863 1303 0.98 972 1364 1.09 1084 —— — —— — 1400 1273 0.97 967 1337 1.09 1082 —— — —— — —— — 1500 1309 1.09 1082 —— — —— — —— — —— —
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
LEGEND Bhp Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 685 to 1045 rpm. All other rpms require a field-
supplied drive.
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
3. See page 34 for general fan performance notes.
Table 11 — Fan Performance 580F036 — Vertical Discharge Units, High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
900 643 0.15 152 768 0.22 222 870 0.30 296 958 0.37 373 1037 0.46 454 1000 683 0.19 191 804 0.27 268 904 0.35 348 991 0.43 430 1069 0.52 517 1100 725 0.24 237 842 0.32 321 939 0.41 407 1025 0.50 496 1102 0.59 588 1200 767 0.29 291 880 0.38 382 976 0.48 474 1060 0.57 570 1136 0.67 668 1300 811 0.35 352 920 0.45 451 1013 0.55 550 1095 0.66 652 1170 0.76 756 1400 855 0.43 423 960 0.53 529 1051 0.64 636 1132 0.75 744 1205 0.86 855 1500 900 0.51 504 1002 0.62 617 1090 0.74 731 1169 0.85 846 1242 0.97 963
AIRFLOW
(Cfm)
900 1110 0.54 538 1177 0.63 627 1239 0.72 718 1298 0.82 813 1355 0.92 911 1000 1141 0.61 607 1207 0.70 700 1269 0.80 796 1328 0.90 895 1384 1.00 998 1100 1173 0.69 683 1238 0.79 781 1300 0.89 883 1358 0.99 987 1414 1.10 1094 1200 1205 0.77 768 1270 0.88 872 1332 0.98 979 1389 1.09 1088 1444 1.21 1200 1300 1239 0.87 863 1303 0.98 972 1364 1.09 1084 1421 1.21 1199 1475 1.32 1316 1400 1273 0.97 967 1337 1.09 1082 1397 1.21 1200 1453 1.33 1320 1507 1.45 1443 1500 1309 1.09 1082 1371 1.21 1204 1430 1.33 1327 1486 1.46 1453 1540 1.59 1581
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
LEGEND Bhp Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 1075 to 1455 rpm. All other rpms require a field-supplied
drive.
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 34 for general fan performance notes.
24
Page 25
Table 12 — Fan Performance 580F048 — Vertical Discharge Units, Standard Motor
Airflow
(Cfm)
1200 0.68 0.41 458 0.74 0.45 506 0.74 0.51 572 0.85 0.56 632 1300 0.61 0.42 471 0.67 0.46 521 0.66 0.52 589 0.78 0.58 651 1400 0.53 0.45 503 0.59 0.49 556 0.59 0.54 616 0.70 0.60 681 1500 0.45 0.47 536 0.51 0.52 593 0.52 0.56 631 0.63 0.62 698 1600 0.36 0.49 557 0.42 0.54 616 0.45 0.58 654 0.56 0.64 723 1700 0.26 0.52 584 0.32 0.57 646 0.37 0.60 678 0.48 0.66 750 1800 0.15 0.54 610 0.22 0.60 674 0.30 0.62 698 0.41 0.68 772 1900 0.04 0.56 629 0.11 0.62 696 0.23 0.64 720 0.34 0.70 796 2000 0.16 0.66 744 0.26 0.73 823
ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts
208 V 230, 460, 575 V 208 V 230, 460, 575 V
Low Speed High Speed
LEGEND See page 34 for general fan performance notes. Bhp Brake Horsepower Input to Fan
ESP External Static Pressure (in. wg)
STANDARD MOTOR (DIRECT DRIVE)
Table 13 — Fan Performance 580F048 — Vertical Discharge Units, Alternate Motor (Belt Drive)*
AIRFLOW
(Cfm)
1200 666 0.26 257 778 0.37 367 871 0.47 471 952 0.57 572 1025 0.67 670 1300 701 0.31 306 810 0.43 426 901 0.54 540 981 0.65 651 1053 0.76 760 1400 737 0.36 361 842 0.49 491 931 0.62 616 1010 0.74 738 1081 0.86 856 1500 773 0.42 422 875 0.57 564 963 0.70 699 1040 0.84 831 1110 0.96 960 1600 810 0.49 491 909 0.65 643 994 0.79 790 1070 0.94 932 1140 1.08 1070 1700 847 0.57 567 943 0.73 730 1027 0.89 888 1101 1.05 1040 1170 1.20 1189 1800 885 0.66 652 978 0.83 826 1060 1.00 994 1133 1.16 1157 1900 923 0.75 745 1014 0.94 930 1093 1.11 1109 2000 962 0.85 847 1049 1.05 1043
AIRFLOW
(Cfm)
1200 1093 0.77 767 1155 0.87 861 1213 0.96 955 1268 1.05 1047 1321 1.14 1137 1300 1119 0.87 866 1181 0.98 970 1239 1.08 1073 1294 1.18 1175 —— — 1400 1147 0.98 972 1208 1.09 1086 —— — —— — —— — 1500 1175 1.09 1086 1600 —— — —— — —— — —— — —— — 1700 —— — —— — —— — —— — —— — 1800 —— — —— — —— — —— — —— — 1900 —— — —— — —— — —— — —— — 2000 —— — —— — —— — —— — —— —
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
0.20.40.60.81.0
1.21.41.61.82.0
LEGEND
Bhp Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 770 to 1175 rpm. All other rpms require a field-supplied drive.
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
3. See page 34 for general fan performance notes.
Table 14 — Fan Performance 580F048 — Vertical Discharge Units, High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
1200 666 0.26 257 778 0.37 367 871 0.47 471 952 0.57 572 1025 0.67 670 1300 701 0.31 306 810 0.43 426 901 0.54 540 981 0.65 651 1053 0.76 760 1400 737 0.36 361 842 0.49 491 931 0.62 616 1010 0.74 738 1081 0.86 856 1500 773 0.42 422 875 0.57 564 963 0.70 699 1040 0.84 831 1110 0.96 960 1600 810 0.49 491 909 0.65 643 994 0.79 790 1070 0.94 932 1140 1.08 1070 1700 847 0.57 567 943 0.73 730 1027 0.89 888 1101 1.05 1040 1170 1.20 1189 1800 885 0.66 652 978 0.83 826 1060 1.00 994 1133 1.16 1157 1200 1.32 1316 1900 923 0.75 745 1014 0.94 930 1093 1.11 1109 1165 1.29 1283 1231 1.46 1453 2000 962 0.85 847 1049 1.05 1043 1127 1.24 1233 1198 1.42 1417 1263 1.61 1598
AIRFLOW
(Cfm)
1200 1093 0.77 767 1155 0.87 861 1213 0.96 955 1268 1.05 1047 1321 1.14 1137 1300 1119 0.87 866 1181 0.98 970 1239 1.08 1073 1294 1.18 1175 1346 1.28 1275 1400 1147 0.98 972 1208 1.09 1086 1265 1.21 1199 1320 1.32 1310 1371 1.43 1419 1500 1175 1.09 1086 1235 1.22 1209 1292 1.34 1332 1346 1.46 1452 1397 1.58 1572 1600 1204 1.21 1207 1263 1.35 1340 1320 1.48 1472 1373 1.61 1603 1424 1.74 1732 1700 1233 1.34 1336 1292 1.49 1480 1348 1.63 1622 1401 1.77 1762 1451 1.91 1901 1800 1262 1.48 1473 1321 1.64 1627 1376 1.79 1779 1428 1.94 1930 1479 2.09 2078 1900 1293 1.63 1620 1350 1.79 1784 1405 1.96 1946 1457 2.12 2106 1506 2.28 2265 2000 1323 1.79 1776 1380 1.96 1950 1434 2.13 2123 1486 2.31 2293 —— —
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
0.20.40.60.81.0
1.21.41.61.82.0
LEGEND Bhp Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 1075 to 1455 rpm. All other rpms require a field-supplied
drive.
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 34 for general fan performance notes.
25
Page 26
Table 15 — Fan Performance 580F060 — Vertical Discharge Units, Standard Motor
STANDARD MOTOR (DIRECT DRIVE)
Airflow
(Cfm)
1500 0.69 0.67 750 1.01 0.71 791 1.00 0.70 782 1.20 0.76 845 1.22 0.79 875 1.28 0.85 949 1600 0.49 0.70 780 0.85 0.74 824 0.85 0.74 821 1.06 0.79 883 1.09 0.82 913 1.17 0.89 988 1700 0.29 0.73 810 0.70 0.77 857 0.70 0.77 861 0.93 0.83 921 0.97 0.85 950 1.06 0.92 1027 1800 0.09 0.75 839 0.54 0.80 891 0.55 0.81 900 0.80 0.86 959 0.84 0.89 988 0.95 0.96 1066 1900 0.39 0.83 924 0.40 0.84 940 0.67 0.90 997 0.72 0.92 1025 0.84 0.99 1105 2000 0.23 0.86 957 0.25 0.88 979 0.54 0.93 1035 0.59 0.95 1063 0.73 1.03 1144 2100 0.08 0.89 990 0.10 0.91 1018 0.41 0.96 1073 0.46 0.99 1101 0.62 1.06 1183 2200 0.28 1.00 1111 0.34 1.02 1138 0.51 1.10 1222 2300 0.15 1.03 1149 0.21 1.06 1176 0.40 1.13 1261 2400 0.02 1.07 1187 0.09 1.09 1213 0.29 1.17 1300 2500 0.18 1.20 1340
LEGEND See page 34 for general fan performance notes. Bhp Brake Horsepower Input to Fan
ESP External Static Pressure (in. wg)
208 V 230,460,575 V 208 V 230,460,575 V 208 V 230,460,575 V
ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts
Low Speed Medium Speed High Speed
Table 16 — Fan Performance 580F060 — Single-Phase, Vertical Discharge Unit,
Alternate Motor (Belt Drive)*
AIRFLOW
(Cfm)
1500 802 0.42 370 912 0.55 489 1006 0.70 624 1088 0.87 773 1163 1.05 935 1600 840 0.49 432 947 0.63 557 1038 0.78 696 1119 0.95 848 1193 1.14 1013 1700 878 0.57 502 982 0.71 632 1071 0.87 776 1151 1.05 932 1224 1.24 1100 1800 917 0.65 581 1017 0.81 716 1105 0.97 864 1183 1.15 1024 1900 956 0.75 668 1053 0.91 808 1139 1.08 961 1216 1.27 1126 —— — 2000 995 0.86 764 1090 1.02 910 1173 1.20 1067 2100 1035 0.98 869 1127 1.15 1021 2200 1075 1.11 984 1164 1.29 1141 2300 1115 1.25 1110 2400 —————— ——— ——— ——— 2500 —————— ——— ——— ———
AIRFLOW
(Cfm)
1500 1232 1.25 1109 —— — —— — —— — —— — 1600 —————— ——— ——— ——— 1700 —————— ——— ——— ——— 1800 —————— ——— ——— ——— 1900 —————— ——— ——— ——— 2000 —————— ——— ——— ——— 2100 —————— ——— ——— ——— 2200 —————— ——— ——— ——— 2300 —————— ——— ——— ——— 2400 —————— ——— ——— ——— 2500 —————— ——— ——— ———
LEGEND Bhp Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 878 to 1192 rpm. All other rpms require a field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.30.
3. See page 34 for general fan performance notes.
26
Page 27
Table 17 — Fan Performance 580F060 — Three-Phase, Vertical Discharge Units,
Alternate Motor (Belt Drive)*
AIRFLOW
(Cfm)
1500 802 0.42 370 912 0.55 489 1006 0.70 624 1088 0.87 773 1163 1.05 935 1600 840 0.49 432 947 0.63 557 1038 0.78 696 1119 0.95 848 1193 1.14 1013 1700 878 0.57 502 982 0.71 632 1071 0.87 776 1151 1.05 932 1224 1.24 1100 1800 917 0.65 581 1017 0.81 716 1105 0.97 864 1183 1.15 1024 1255 1.35 1197 1900 956 0.75 668 1053 0.91 808 1139 1.08 961 1216 1.27 1126 1287 1.47 1302 2000 995 0.86 764 1090 1.02 910 1173 1.20 1067 1249 1.39 1236 1319 1.59 1416 2100 1035 0.98 869 1127 1.15 1021 1209 1.33 1183 1283 1.53 1357 1351 1.74 1541 2200 1075 1.11 984 1164 1.29 1141 1244 1.47 1309 1317 1.68 1488 1385 1.89 1676 2300 1115 1.25 1110 1202 1.43 1273 1280 1.63 1446 1352 1.83 1629 1418 2.05 1822 2400 1155 1.40 1246 1240 1.59 1415 1316 1.79 1594 1387 2.01 1782 1452 2.23 1980 2500 1196 1.57 1394 1278 1.77 1569 1353 1.97 1753 1422 2.19 1946 —— —
AIRFLOW
(Cfm)
1500 1232 1.25 1109 1297 1.46 1295 1357 1.68 1492 1415 1.91 1700 1469 2.16 1917 1600 1262 1.34 1190 1325 1.55 1379 1385 1.78 1579 1442 2.01 1788 1496 2.26 2009 1700 1291 1.44 1281 1354 1.66 1472 1414 1.89 1674 1470 2.12 1887 1524 2.37 2109 1800 1322 1.55 1380 1384 1.77 1575 1443 2.00 1779 1499 2.25 1994 —— — 1900 1352 1.68 1489 1414 1.90 1687 1472 2.13 1894 1528 2.38 2112 —— — 2000 1384 1.81 1607 1445 2.04 1808 1502 2.27 2019 —— — —— — 2100 1415 1.95 1736 1476 2.18 1940 —— — —— — —— — 2200 1448 2.11 1875 1507 2.35 2083 —— — —— — —— — 2300 1480 2.28 2025 —— — —— — —— — —— — 2400 —————— ——— ——— ——— 2500 —————— ——— ——— ———
LEGEND Bhp Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 878 to 1192 rpm. All other rpms require a field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 34 for general fan performance notes.
Table 18 — Fan Performance 580F060 — Vertical Discharge Units, High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
1500 802 0.42 370 912 0.55 489 1006 0.70 624 1088 0.87 773 1163 1.05 935 1600 840 0.49 432 947 0.63 557 1038 0.78 696 1119 0.95 848 1193 1.14 1013 1700 878 0.57 502 982 0.71 632 1071 0.87 776 1151 1.05 932 1224 1.24 1100 1800 917 0.65 581 1017 0.81 716 1105 0.97 864 1183 1.15 1024 1255 1.35 1197 1900 956 0.75 668 1053 0.91 808 1139 1.08 961 1216 1.27 1126 1287 1.47 1302 2000 995 0.86 764 1090 1.02 910 1173 1.20 1067 1249 1.39 1236 1319 1.59 1416 2100 1035 0.98 869 1127 1.15 1021 1209 1.33 1183 1283 1.53 1357 1351 1.74 1541 2200 1075 1.11 984 1164 1.29 1141 1244 1.47 1309 1317 1.68 1488 1385 1.89 1676 2300 1115 1.25 1110 1202 1.43 1273 1280 1.63 1446 1352 1.83 1629 1418 2.05 1822 2400 1155 1.40 1246 1240 1.59 1415 1316 1.79 1594 1387 2.01 1782 1452 2.23 1980 2500 1196 1.57 1394 1278 1.77 1569 1353 1.97 1753 1422 2.19 1946 1486 2.42 2149
AIRFLOW
(Cfm)
1500 1232 1.25 1109 1297 1.46 1295 1357 1.68 1492 1415 1.91 1700 1469 2.16 1917 1600 1262 1.34 1190 1325 1.55 1379 1385 1.78 1579 1442 2.01 1788 1496 2.26 2009 1700 1291 1.44 1281 1354 1.66 1472 1414 1.89 1674 1470 2.12 1887 1524 2.37 2109 1800 1322 1.55 1380 1384 1.77 1575 1443 2.00 1779 1499 2.25 1994 1552 2.50 2219 1900 1352 1.68 1489 1414 1.90 1687 1472 2.13 1894 1528 2.38 2112 1580 2.63 2339 2000 1384 1.81 1607 1445 2.04 1808 1502 2.27 2019 1557 2.52 2240 1609 2.78 2470 2100 1415 1.95 1736 1476 2.18 1940 1533 2.43 2155 1587 2.68 2378 2200 1448 2.11 1875 1507 2.35 2083 1563 2.59 2301 1617 2.85 2528 2300 1480 2.28 2025 1539 2.52 2237 1595 2.77 2459 2400 1513 2.46 2187 1571 2.71 2403 2500 1547 2.66 2360
LEGEND Bhp Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require a field-supplied
drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See page 34 for general fan performance notes.
27
Page 28
Table 19 — Fan Performance 580F072,073 — Vertical Discharge Units, Standard Motor (Belt Drive)*
AIRFLOW
(Cfm)
1800 967 0.65 579 1077 0.81 718 1172 0.96 856 1257 1.12 993 1334 1.27 1130 1900 1007 0.75 663 1115 0.91 811 1208 1.08 957 1291 1.24 1101 1368 1.40 1246 2000 1048 0.85 757 1153 1.03 913 1244 1.20 1066 1326 1.37 1219 1401 1.54 1371 2100 1090 0.97 859 1191 1.15 1023 1281 1.33 1185 1361 1.51 1345 1435 1.69 1505 2200 1131 1.09 970 1230 1.29 1143 1318 1.48 1313 1397 1.67 1481 1470 1.86 1649 2300 1173 1.23 1091 1269 1.43 1273 1355 1.63 1451 1433 1.83 1627 1505 2.03 1803 2400 1215 1.38 1223 1309 1.59 1413 1393 1.80 1600 1470 2.01 1784 1540 2.21 1967 2500 1258 1.54 1365 1349 1.76 1564 1431 1.98 1759 1506 2.20 1951 —— — 2600 1300 1.71 1518 1389 1.94 1726 1470 2.17 1929 1544 2.40 2130 —— — 2700 1343 1.90 1683 1430 2.14 1899 1509 2.38 2111 —— — —— — 2800 1386 2.09 1860 1471 2.35 2085 —— — —— — —— — 2900 1429 2.31 2050 3000 —————— ——— ——— ———
AIRFLOW
(Cfm)
1800 1406 1.43 1268 1473 1.58 1407 1535 1.74 1548 1595 1.90 1690 1652 2.06 1833 1900 1438 1.57 1391 1504 1.73 1537 1567 1.90 1685 1626 2.06 1833 1682 2.23 1983 2000 1471 1.72 1523 1536 1.89 1677 1598 2.06 1831 1657 2.24 1986 —— — 2100 1504 1.87 1665 1569 2.06 1825 1630 2.24 1986 —— — —— — 2200 1538 2.04 1816 1602 2.23 1984 —— — —— — —— — 2300 1572 2.23 1978 —— — —— — —— — —— — 2400 —————— ——— ——— ——— 2500 —————— ——— ——— ——— 2600 —————— ——— ——— ——— 2700 —————— ——— ——— ——— 2800 —————— ——— ——— ——— 2900 —————— ——— ——— ——— 3000 —————— ——— ——— ———
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
LEGEND Bhp Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 1070 to 1460 rpm. All other rpms require a field-supplied
drive.
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 34 for general fan performance notes.
Table 20 — Fan Performance 580F072,073 — Vertical Discharge Units, High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
1800 967 0.65 579 1077 0.81 718 1172 0.96 856 1257 1.12 993 1334 1.27 1130 1900 1007 0.75 663 1115 0.91 811 1208 1.08 957 1291 1.24 1101 1368 1.40 1246 2000 1048 0.85 757 1153 1.03 913 1244 1.20 1066 1326 1.37 1219 1401 1.54 1371 2100 1090 0.97 859 1191 1.15 1023 1281 1.33 1185 1361 1.51 1345 1435 1.69 1505 2200 1131 1.09 970 1230 1.29 1143 1318 1.48 1313 1397 1.67 1481 1470 1.86 1649 2300 1173 1.23 1091 1269 1.43 1273 1355 1.63 1451 1433 1.83 1627 1505 2.03 1803 2400 1215 1.38 1223 1309 1.59 1413 1393 1.80 1600 1470 2.01 1784 1540 2.21 1967 2500 1258 1.54 1365 1349 1.76 1564 1431 1.98 1759 1506 2.20 1951 1576 2.41 2142 2600 1300 1.71 1518 1389 1.94 1726 1470 2.17 1929 1544 2.40 2130 1613 2.62 2329 2700 1343 1.90 1683 1430 2.14 1899 1509 2.38 2111 1581 2.61 2320 1649 2.85 2527 2800 1386 2.09 1860 1471 2.35 2085 1548 2.60 2305 1619 2.84 2522 2900 1429 2.31 2050 1512 2.57 2283 1588 2.83 2512 3000 1473 2.54 2252 1553 2.81 2494
AIRFLOW
(Cfm)
1800 1406 1.43 1268 1473 1.58 1407 1535 1.74 1548 1595 1.90 1690 1652 2.06 1833 1900 1438 1.57 1391 1504 1.73 1537 1567 1.90 1685 1626 2.06 1833 1682 2.23 1983 2000 1471 1.72 1523 1536 1.89 1677 1598 2.06 1831 1657 2.24 1986 1713 2.41 2142 2100 1504 1.87 1665 1569 2.06 1825 1630 2.24 1986 1688 2.42 2149 1744 2.60 2312 2200 1538 2.04 1816 1602 2.23 1984 1663 2.42 2152 1720 2.61 2321 1775 2.81 2491 2300 1572 2.23 1978 1635 2.42 2153 1695 2.62 2328 1753 2.82 2504 —— — 2400 1607 2.42 2150 1669 2.63 2332 1729 2.83 2515 —— — —— — 2500 1642 2.63 2333 1704 2.84 2523 —— — —— — —— — 2600 1677 2.85 2527 2700 —————— ——— ——— ——— 2800 —————— ——— ——— ——— 2900 —————— ——— ——— ——— 3000 —————— ——— ——— ———
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
LEGEND Bhp Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require a field-supplied
drive.
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See page 34 for general fan performance notes.
28
Page 29
Table 21 — Fan Performance 580F036 — Horizontal Discharge Units, Standard Motor
STANDARD MOTOR (DIRECT DRIVE)
Airflow
(Cfm)
900 0.54 0.21 253 0.57 0.23 277 0.55 0.26 307 0.60 0.31 363 1000 0.49 0.23 270 0.51 0.25 292 0.52 0.27 321 0.53 0.32 374 1100 0.43 0.24 287 0.45 0.26 307 0.46 0.28 335 0.49 0.33 385 1200 0.39 0.26 304 0.40 0.27 323 0.38 0.29 349 0.43 0.34 397 1300 0.33 0.27 321 0.35 0.29 338 0.35 0.31 364 0.36 0.34 408 1400 0.26 0.29 338 0.28 0.30 354 0.29 0.32 378 1500 0.21 0.30 355 0.23 0.31 369 0.24 0.33 392
ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts
208 V 230, 460, 575 V 208 V 230, 460, 575 V
Low Speed High Speed
LEGEND See page 34 for general fan performance notes. Bhp — Brake Horsepower Input to Fan
ESP — External Static Pressure (in. wg)
Table 22 — Fan Performance 580F036 — Horizontal Discharge Units, Alternate Motor (Belt Drive)*
AIRFLOW
(Cfm)
900 607 0.14 142 745 0.22 221 856 0.31 304 952 0.39 393 1037 0.49 485 1000 640 0.18 174 775 0.26 261 884 0.35 351 978 0.45 446 1062 0.55 545 1100 674 0.21 212 805 0.31 307 912 0.41 404 1005 0.51 506 1089 0.61 611 1200 708 0.26 256 836 0.36 359 941 0.47 464 1033 0.57 572 1116 0.69 683 1300 743 0.31 307 868 0.42 417 971 0.53 530 1062 0.65 645 1143 0.77 764 1400 780 0.37 364 900 0.49 483 1002 0.61 603 1091 0.73 726 1172 0.86 851 1500 816 0.43 428 934 0.56 556 1033 0.69 685 1121 0.82 815 1201 0.95 947
AIRFLOW
(Cfm)
900 1114 0.59 582 1186 0.69 684 1253 0.79 789 1316 0.90 898 1375 1.02 1010 1000 1139 0.65 648 1210 0.76 754 1277 0.87 865 1340 0.98 979 1399 1.10 1097 1100 1165 0.72 720 1236 0.84 832 1302 0.95 948 1364 1.07 1068 1423 1.20 1191 1200 1191 0.80 799 1261 0.92 917 1327 1.04 1039 1389 1.17 1165 —— — 1300 1218 0.89 885 1288 1.02 1010 1353 1.14 1138 —— — —— — 1400 1246 0.99 980 1315 1.12 1111 —— — —— — —— — 1500 1274 1.09 1083 —— — —— — —— — —— —
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
LEGEND Bhp Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 685 to 1045 rpm. All other rpms require a field-
supplied drive.
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
3. See page 34 for general fan performance notes.
Table 23 — Fan Performance 580F036 — Horizontal Discharge Units, High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
900 607 0.14 142 745 0.22 221 856 0.31 304 952 0.39 393 1037 0.49 485 1000 640 0.18 174 775 0.26 261 884 0.35 351 978 0.45 446 1062 0.55 545 1100 674 0.21 212 805 0.31 307 912 0.41 404 1005 0.51 506 1089 0.61 611 1200 708 0.26 256 836 0.36 359 941 0.47 464 1033 0.57 572 1116 0.69 683 1300 743 0.31 307 868 0.42 417 971 0.53 530 1062 0.65 645 1143 0.77 764 1400 780 0.37 364 900 0.49 483 1002 0.61 603 1091 0.73 726 1172 0.86 851 1500 816 0.43 428 934 0.56 556 1033 0.69 685 1121 0.82 815 1201 0.95 947
AIRFLOW
(Cfm)
900 1114 0.59 582 1186 0.69 684 1253 0.79 789 1316 0.90 898 1375 1.02 1010 1000 1139 0.65 648 1210 0.76 754 1277 0.87 865 1340 0.98 979 1399 1.10 1097 1100 1165 0.72 720 1236 0.84 832 1302 0.95 948 1364 1.07 1068 1423 1.20 1191 1200 1191 0.80 799 1261 0.92 917 1327 1.04 1039 1389 1.17 1165 1448 1.30 1293 1300 1218 0.89 885 1288 1.02 1010 1353 1.14 1138 1414 1.28 1270 1473 1.41 1404 1400 1246 0.99 980 1315 1.12 1111 1379 1.25 1246 1440 1.39 1383 1499 1.53 1523 1500 1274 1.09 1083 1342 1.23 1221 1406 1.37 1362 1467 1.51 1505 1525 1.66 1652
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
LEGEND Bhp Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 1075 to 1455 rpm. All other rpms require a field-supplied
drive.
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 34 for general fan performance notes.
29
Page 30
Table 24 — Fan Performance 580F048 — Horizontal Discharge Units, Standard Motor
STANDARD MOTOR (DIRECT DRIVE)
Airflow
(Cfm)
1200 0.75 0.41 458 0.81 0.45 506 0.87 0.51 572 0.92 0.56 632 1300 0.68 0.42 471 0.74 0.46 521 0.79 0.52 589 0.85 0.58 651 1400 0.60 0.45 503 0.66 0.49 556 0.71 0.54 616 0.77 0.60 681 1500 0.51 0.47 536 0.58 0.52 593 0.64 0.56 631 0.70 0.62 698 1600 0.42 0.49 557 0.49 0.54 616 0.56 0.58 654 0.63 0.64 723 1700 0.32 0.52 584 0.39 0.57 646 0.48 0.60 678 0.55 0.66 750 1800 0.21 0.54 610 0.29 0.60 674 0.41 0.62 698 0.48 0.68 772 1900 0.09 0.56 629 0.18 0.62 696 0.33 0.64 720 0.41 0.70 796 2000 0.06 0.65 731 0.26 0.66 744 0.33 0.73 823
LEGEND See page 34 for general fan performance notes. Bhp — Brake Horsepower Input to Fan
ESP — External Static Pressure (in. wg)
ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts
208 V 230, 460, 575 V 208 V 230, 460, 575 V
Low Speed High Speed
Table 25 — Fan Performance 580F048 — Horizontal Discharge Units, Alternate Motor (Belt Drive)*
AIRFLOW
(Cfm)
1200 643 0.23 234 762 0.34 343 859 0.46 458 944 0.58 579 1020 0.71 705 1300 675 0.28 277 790 0.40 394 886 0.52 517 969 0.65 644 1044 0.78 777 1400 707 0.33 326 819 0.45 452 913 0.58 581 996 0.72 716 1070 0.86 855 1500 740 0.38 382 849 0.52 515 941 0.66 653 1023 0.80 795 1096 0.95 941 1600 773 0.45 444 879 0.59 586 970 0.73 731 1050 0.88 880 1123 1.04 1034 1700 807 0.52 513 910 0.67 663 999 0.82 817 1078 0.98 973 1150 1.14 1134 1800 841 0.59 589 942 0.75 749 1029 0.91 910 1106 1.08 1074 1900 875 0.68 674 974 0.85 842 1059 1.02 1012 1135 1.19 1184 2000 910 0.77 767 1006 0.95 944 1090 1.13 1122
AIRFLOW
(Cfm)
1200 1089 0.84 837 1153 0.98 974 1213 1.12 1115 —— — —— — 1300 1113 0.92 915 1177 1.06 1058 —— — —— — —— — 1400 1138 1.01 1000 1201 1.15 1149 —— — —— — —— — 1500 1163 1.10 1092 1600 1189 1.20 1191 —— — —— — —— — —— — 1700 —————— ——— ——— ——— 1800 —————— ——— ——— ——— 1900 —————— ——— ——— ——— 2000 —————— ——— ——— ———
LEGEND Bhp Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 770 to 1175 rpm. All other rpms require a field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
3. See page 34 for general fan performance notes.
30
Page 31
Table 26 — Fan Performance 580F048 — Horizontal Discharge Units, High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
1200 643 0.23 234 762 0.34 343 859 0.46 458 944 0.58 579 1020 0.71 705 1300 675 0.28 277 790 0.40 394 886 0.52 517 969 0.65 644 1044 0.78 777 1400 707 0.33 326 819 0.45 452 913 0.58 581 996 0.72 716 1070 0.86 855 1500 740 0.38 382 849 0.52 515 941 0.66 653 1023 0.80 795 1096 0.95 941 1600 773 0.45 444 879 0.59 586 970 0.73 731 1050 0.88 880 1123 1.04 1034 1700 807 0.52 513 910 0.67 663 999 0.82 817 1078 0.98 973 1150 1.14 1134 1800 841 0.59 589 942 0.75 749 1029 0.91 910 1106 1.08 1074 1177 1.25 1242 1900 875 0.68 674 974 0.85 842 1059 1.02 1012 1135 1.19 1184 1205 1.37 1360 2000 910 0.77 767 1006 0.95 944 1090 1.13 1122 1165 1.31 1302 1234 1.49 1485
AIRFLOW
(Cfm)
1200 1089 0.84 837 1153 0.98 974 1213 1.12 1115 1270 1.27 1262 1324 1.42 1413 1300 1113 0.92 915 1177 1.06 1058 1237 1.21 1205 1293 1.36 1358 1347 1.52 1514 1400 1138 1.01 1000 1201 1.15 1149 1261 1.31 1303 1317 1.47 1461 1370 1.63 1623 1500 1163 1.10 1092 1226 1.25 1247 1285 1.41 1407 1341 1.58 1571 1394 1.75 1740 1600 1189 1.20 1191 1252 1.36 1353 1310 1.53 1520 1365 1.70 1690 1418 1.87 1865 1700 1216 1.31 1299 1277 1.48 1468 1335 1.65 1640 1390 1.83 1817 1442 2.01 1998 1800 1242 1.42 1414 1303 1.60 1590 1361 1.78 1770 1415 1.96 1953 1467 2.15 2140 1900 1270 1.55 1538 1330 1.73 1721 1387 1.92 1908 1441 2.11 2098 1493 2.30 2292 2000 1297 1.68 1672 1357 1.87 1862 1414 2.07 2055 1467 2.26 2252 —— —
LEGEND Bhp Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 1075 to 1455 rpm. All other rpms require a field-supplied
drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 34 for general fan performance notes.
Table 27 — Fan Performance 580F060 — Horizontal Discharge Units, Standard Motor
STANDARD MOTOR (DIRECT DRIVE)
Airflow
(Cfm)
1500 0.74 0.67 750 1.06 0.71 791 1.07 0.70 782 1.27 0.76 845 1.26 0.79 875 1.33 0.85 949 1600 0.54 0.70 780 0.90 0.74 824 0.92 0.74 821 1.13 0.79 883 1.14 0.82 913 1.22 0.89 988 1700 0.34 0.73 810 0.75 0.77 857 0.77 0.77 861 1.00 0.83 921 1.01 0.85 950 1.11 0.92 1027 1800 0.14 0.75 839 0.59 0.80 891 0.62 0.81 900 0.87 0.86 959 0.89 0.88 988 1.00 0.96 1066 1900 0.44 0.83 924 0.47 0.84 940 0.74 0.90 997 0.77 0.92 1025 0.89 0.99 1105 2000 0.28 0.86 957 0.32 0.88 979 0.61 0.93 1035 0.64 0.95 1063 0.78 1.03 1144 2100 0.13 0.89 990 0.17 0.91 1018 0.48 0.96 1073 0.51 0.99 1101 0.67 1.06 1183 2200 0.02 0.95 1058 0.35 1.00 1111 0.39 1.02 1138 0.56 1.10 1222 2300 0.22 1.03 1149 0.26 1.06 1176 0.45 1.13 1261 2400 0.09 1.07 1187 0.14 1.09 1213 0.34 1.17 1300 2500 ———————————————0.231.201340
LEGEND See page 34 for general fan performance notes. Bhp — Brake Horsepower Input to Fan
ESP — External Static Pressure (in. wg)
ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts
Low Speed Medium Speed High Speed
208V 230, 460, 575 V 208 V 230, 460, 575 V 208 V 230, 460, 575 V
31
Page 32
Table 28 — Fan Performance 580F060 — Single-Phase, Horizontal Discharge Units,
Alternate Motor (Belt Drive)*
AIRFLOW
(Cfm)
1500 790 0.40 353 896 0.53 470 990 0.67 599 1074 0.83 738 1151 1.00 886 1600 828 0.46 413 930 0.60 535 1021 0.75 669 1103 0.91 812 1179 1.09 965 1700 866 0.54 479 964 0.68 607 1053 0.84 746 1133 1.01 894 1207 1.18 1051 1800 905 0.62 553 1000 0.77 687 1085 0.94 831 1164 1.11 984 1236 1.29 1146 1900 944 0.71 635 1036 0.87 775 1119 1.04 924 1195 1.22 1082 —— — 2000 984 0.82 725 1072 0.98 871 1153 1.15 1025 2100 1024 0.93 824 1109 1.10 976 1188 1.28 1136 2200 1064 1.05 932 1147 1.23 1090 2300 1105 1.18 1050 2400 —————— ——— ——— ——— 2500 —————— ——— ——— ———
AIRFLOW
(Cfm)
1500 1223 1.18 1045 —— — —— — —— — —— — 1600 1249 1.27 1127 —— — —— — —— — —— — 1700 —————— ——— ——— ——— 1800 —————— ——— ——— ——— 1900 —————— ——— ——— ——— 2000 —————— ——— ——— ——— 2100 —————— ——— ——— ——— 2200 —————— ——— ——— ——— 2300 —————— ——— ——— ——— 2400 —————— ——— ——— ——— 2500 —————— ——— ——— ———
LEGEND Bhp Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 878 to 1192 rpm. All other rpms require a field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.30.
3. See page 34 for general fan performance notes.
Table 29 — Fan Performance 580F060 — Three-Phase, Horizontal Discharge Units,
Alternate Motor (Belt Drive)*
AIRFLOW
(Cfm)
1500 790 0.40 353 896 0.53 470 990 0.67 599 1074 0.83 738 1151 1.00 886 1600 828 0.46 413 930 0.60 535 1021 0.75 669 1103 0.91 812 1179 1.09 965 1700 866 0.54 479 964 0.68 607 1053 0.84 746 1133 1.01 894 1207 1.18 1051 1800 905 0.62 553 1000 0.77 687 1085 0.94 831 1164 1.11 984 1236 1.29 1146 1900 944 0.71 635 1036 0.87 775 1119 1.04 924 1195 1.22 1082 1266 1.41 1248 2000 984 0.82 725 1072 0.98 871 1153 1.15 1025 1227 1.34 1189 1297 1.53 1360 2100 1024 0.93 824 1109 1.10 976 1188 1.28 1136 1260 1.47 1305 1328 1.67 1481 2200 1064 1.05 932 1147 1.23 1090 1223 1.41 1256 1294 1.61 1430 1360 1.81 1612 2300 1105 1.18 1050 1185 1.37 1215 1259 1.56 1386 1328 1.76 1566 1393 1.97 1752 2400 1146 1.33 1179 1223 1.52 1349 1295 1.72 1527 1362 1.93 1711 1426 2.14 1903 2500 1187 1.48 1317 1262 1.68 1494 1332 1.89 1677 1398 2.10 1868 1460 2.33 2065
AIRFLOW
(Cfm)
1500 1223 1.18 1045 1291 1.36 1212 1355 1.56 1388 1415 1.77 1573 1473 1.99 1765 1600 1249 1.27 1127 1316 1.46 1298 1379 1.66 1478 1439 1.87 1665 1496 2.09 1860 1700 1277 1.37 1217 1342 1.57 1392 1404 1.77 1575 1463 1.99 1766 1520 2.21 1965 1800 1305 1.48 1316 1369 1.68 1495 1430 1.89 1681 1489 2.11 1876 1545 2.34 2078 1900 1333 1.60 1423 1397 1.81 1606 1457 2.02 1797 1514 2.25 1995 —— — 2000 1363 1.73 1540 1425 1.94 1727 1484 2.16 1922 1541 2.39 2124 —— — 2100 1393 1.87 1665 1454 2.09 1857 1512 2.31 2056 —— — —— — 2200 1424 2.03 1801 1484 2.25 1997 —— — —— — —— — 2300 1455 2.19 1946 —— — —— — —— — —— — 2400 1487 2.37 2103 —— — —— — —— — —— — 2500 —————— ——— ——— ———
LEGEND Bhp Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 878 to 1192 rpm. All other rpms require a field-
supplied drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 34 for general fan performance notes.
32
Page 33
Table 30 — Fan Performance 580F060 — Horizontal Discharge Units, High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
1500 790 0.40 353 896 0.53 470 990 0.67 599 1074 0.83 738 1151 1.00 886 1600 828 0.46 413 930 0.60 535 1021 0.75 669 1103 0.91 812 1179 1.09 965 1700 866 0.54 479 964 0.68 607 1053 0.84 746 1133 1.01 894 1207 1.18 1051 1800 905 0.62 553 1000 0.77 687 1085 0.94 831 1164 1.11 984 1236 1.29 1146 1900 944 0.71 635 1036 0.87 775 1119 1.04 924 1195 1.22 1082 1266 1.41 1248 2000 984 0.82 725 1072 0.98 871 1153 1.15 1025 1227 1.34 1189 1297 1.53 1360 2100 1024 0.93 824 1109 1.10 976 1188 1.28 1136 1260 1.47 1305 1328 1.67 1481 2200 1064 1.05 932 1147 1.23 1090 1223 1.41 1256 1294 1.61 1430 1360 1.81 1612 2300 1105 1.18 1050 1185 1.37 1215 1259 1.56 1386 1328 1.76 1566 1393 1.97 1752 2400 1146 1.33 1179 1223 1.52 1349 1295 1.72 1527 1362 1.93 1711 1426 2.14 1903 2500 1187 1.48 1317 1262 1.68 1494 1332 1.89 1677 1398 2.10 1868 1460 2.33 2065
AIRFLOW
(Cfm)
1500 1223 1.18 1045 1291 1.36 1212 1355 1.56 1388 1415 1.77 1573 1473 1.99 1765 1600 1249 1.27 1127 1316 1.46 1298 1379 1.66 1478 1439 1.87 1665 1496 2.09 1860 1700 1277 1.37 1217 1342 1.57 1392 1404 1.77 1575 1463 1.99 1766 1520 2.21 1965 1800 1305 1.48 1316 1369 1.68 1495 1430 1.89 1681 1489 2.11 1876 1545 2.34 2078 1900 1333 1.60 1423 1397 1.81 1606 1457 2.02 1797 1514 2.25 1995 1570 2.48 2200 2000 1363 1.73 1540 1425 1.94 1727 1484 2.16 1922 1541 2.39 2124 1596 2.63 2333 2100 1393 1.87 1665 1454 2.09 1857 1512 2.31 2056 1568 2.55 2262 1622 2.79 2475 2200 1424 2.03 1801 1484 2.25 1997 1541 2.48 2200 1596 2.71 2411 2300 1455 2.19 1946 1514 2.42 2147 1571 2.65 2355 1625 2.89 2570 2400 1487 2.37 2103 1545 2.60 2308 1601 2.84 2521 2500 1520 2.56 2269 1577 2.79 2480
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
LEGEND
Bhp Brake Horsepower Input to Fan Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require a field-supplied
drive.
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See page 34 for general fan performance notes.
Table 31 — Fan Performance 580F072,073 — Horizontal Discharge Units, Standard Motor (Belt Drive)*
AIRFLOW
(Cfm)
1800 919 0.63 561 1010 0.75 663 1095 0.87 771 1174 1.00 886 1250 1.14 1008 1900 960 0.73 648 1047 0.85 754 1129 0.98 867 1206 1.11 986 1279 1.25 1111 2000 1001 0.84 744 1085 0.96 855 1163 1.09 972 1238 1.23 1095 1309 1.38 1224 2100 1043 0.96 850 1123 1.09 965 1199 1.22 1086 1271 1.37 1213 1340 1.52 1346 2200 1085 1.09 966 1162 1.22 1086 1235 1.36 1211 1305 1.51 1342 1372 1.67 1479 2300 1127 1.23 1092 1201 1.37 1217 1272 1.52 1347 1340 1.67 1482 1405 1.83 1623 2400 1169 1.38 1229 1241 1.53 1359 1310 1.68 1493 1375 1.84 1633 1439 2.00 1778 2500 1212 1.55 1378 1281 1.70 1513 1348 1.86 1652 1412 2.02 1796 1473 2.19 1945 2600 1255 1.73 1539 1322 1.89 1678 1386 2.05 1822 1448 2.22 1970 1508 2.39 2124 2700 1298 1.93 1713 1363 2.09 1857 1425 2.26 2005 2800 1341 2.14 1899 1404 2.31 2048 2900 1384 2.36 2099 3000 —————— ——— ——— ———
AIRFLOW
(Cfm)
1800 1321 1.28 1137 1390 1.43 1273 1455 1.59 1415 1518 1.76 1563 1579 1.93 1718 1900 1348 1.40 1243 1415 1.56 1381 1479 1.72 1526 1541 1.89 1677 1601 2.06 1834 2000 1377 1.53 1359 1442 1.69 1500 1505 1.86 1648 1565 2.03 1801 1624 2.21 1961 2100 1406 1.67 1485 1470 1.83 1629 1531 2.00 1780 1591 2.18 1936 1648 2.36 2098 2200 1437 1.83 1621 1499 1.99 1769 1559 2.16 1923 1617 2.34 2082 —— — 2300 1468 1.99 1769 1529 2.16 1920 1587 2.34 2077 —— — —— — 2400 1500 2.17 1928 1559 2.35 2083 —— — —— — —— — 2500 1533 2.36 2098 —— — —— — —— — —— — 2600 —————— ——— ——— ——— 2700 —————— ——— ——— ——— 2800 —————— ——— ——— ——— 2900 —————— ——— ——— ——— 3000 —————— ——— ——— ———
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
LEGEND Bhp Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 1070 to 1460 rpm. All other rpms require a field-supplied
drive.
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 34 for general fan performance notes.
33
Page 34
Table 32 — Fan Performance 580F072,073 — Horizontal Discharge Units, High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
1800 919 0.63 561 1010 0.75 663 1095 0.87 771 1174 1.00 886 1250 1.14 1008 1900 960 0.73 648 1047 0.85 754 1129 0.98 867 1206 1.11 986 1279 1.25 1111 2000 1001 0.84 744 1085 0.96 855 1163 1.09 972 1238 1.23 1095 1309 1.38 1224 2100 1043 0.96 850 1123 1.09 965 1199 1.22 1086 1271 1.37 1213 1340 1.52 1346 2200 1085 1.09 966 1162 1.22 1086 1235 1.36 1211 1305 1.51 1342 1372 1.67 1479 2300 1127 1.23 1092 1201 1.37 1217 1272 1.52 1347 1340 1.67 1482 1405 1.83 1623 2400 1169 1.38 1229 1241 1.53 1359 1310 1.68 1493 1375 1.84 1633 1439 2.00 1778 2500 1212 1.55 1378 1281 1.70 1513 1348 1.86 1652 1412 2.02 1796 1473 2.19 1945 2600 1255 1.73 1539 1322 1.89 1678 1386 2.05 1822 1448 2.22 1970 1508 2.39 2124 2700 1298 1.93 1713 1363 2.09 1857 1425 2.26 2005 1485 2.43 2158 1544 2.61 2315 2800 1341 2.14 1899 1404 2.31 2048 1464 2.48 2201 1523 2.66 2358 1580 2.84 2520 2900 1384 2.36 2099 1445 2.54 2253 1504 2.71 2410 1561 2.90 2572 3000 1428 2.60 2313 1487 2.78 2471
AIRFLOW
(Cfm)
1800 1321 1.28 1137 1390 1.43 1273 1455 1.59 1415 1518 1.76 1563 1579 1.93 1718 1900 1348 1.40 1243 1415 1.56 1381 1479 1.72 1526 1541 1.89 1677 1601 2.06 1834 2000 1377 1.53 1359 1442 1.69 1500 1505 1.86 1648 1565 2.03 1801 1624 2.21 1961 2100 1406 1.67 1485 1470 1.83 1629 1531 2.00 1780 1591 2.18 1936 1648 2.36 2098 2200 1437 1.83 1621 1499 1.99 1769 1559 2.16 1923 1617 2.34 2082 1673 2.53 2246 2300 1468 1.99 1769 1529 2.16 1920 1587 2.34 2077 1644 2.52 2239 1699 2.71 2406 2400 1500 2.17 1928 1559 2.35 2083 1616 2.53 2243 1672 2.71 2408 1726 2.90 2579 2500 1533 2.36 2098 1591 2.54 2257 1647 2.73 2421 2600 1566 2.57 2281 1623 2.75 2444 2700 1600 2.79 2477 2800 —————— ——— ——— ——— 2900 —————— ——— ——— ——— 3000 —————— ——— ——— ———
LEGEND Bhp Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require a field-supplied
drive.
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
0.2 0.4 0.6 0.8 1.0
1.2 1.4 1.6 1.8 2.0
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See below for general fan performance notes.
GENERAL FAN PERFORMANCE NOTES
1. Values include losses for filters, unit casing, and wet coils. See Table 8 for accessory/FIOP static pressure information.
2. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using fan motors up to the wattage ratings shown will not result in nui­sance tripping or premature motor failure. Unit warranty will not be affected. See Table 7 — Motor Data for additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative for details.
4. Interpolation is permissible. Do not extrapolate.
34
Page 35
PRE-START-UP
WARNING: Failure to observe the following warnings
could result in serious personal injury .
1. Follow recognized safety practices and wear protective goggles when checking or the servicing refrigerant system.
2. Do not o perate the compr essor or provi de any electric power to the unit unless the compres sor termina l cov­er is in place and secured.
3. Do not remo ve the com pre ssor termi nal cove r unti l all electrical sources are disconn ected.
4. Relieve all pressure from the system before touching or disturbing anything in side the c omp ress or term ina l box if refrigerant leak is suspected around the com­pressor terminals.
5. Never attempt to repair a soldered connection while the refrigerant system is under pressure.
6. Do not use to rch to remove any component. The sys ­tem contains oil and refrigerant under pressure. To re­move a component, wear protective goggles and proceed as follows: a. Shut off gas and then electrical power to the unit.
Install lockout tag.
b. Relieve all pressure from the system using both
high-pressure and low-pressure ports.
c. Cut the component connection tubing with a tubing
cutter, and remove the component from the unit.
d. Carefully unsweat the remaining tubing stubs when
necessary. Oil can ignite when exposed to torch flame.
Proceed as follows to ins pect and prep are the unit f or initial start-up:
1. Remove all access panels.
2. Read and follow instructions on all WARNING, CAUTION, and INFORMATION labels attached to, or shipped with, the unit.
3. Make the following inspections: a. Inspect for shipping and handling damages such
as broken lines, loose p arts, or discon nec ted wires, etc.
b. Inspect for oil at all refrigerant tubing connections
and on unit base. Detecting oil generally indicates a refrigerant leak. Leak-test all refrigerant tubing connections using an electronic leak detector, halide torch, or liquid-soap solution.
c. Inspect all field- and factory-wiring connections.
Be sure that connections are completed and tight.
d. Inspect coil fins. If damaged during shipping and
handling, carefully straighten the fins with a fin comb.
4. Verify the following conditions: a. Make sure that condenser fan blade is correctly
positioned in the fan orifice. See Condenser-Fan
Adjustment section on page 39 for more details. b. Make sure that air filter(s) is in place. c. Make sure that condensate drain trap is filled
with water to ensure proper drainage. d. Make sure that all tools and miscellaneous loose
parts have been removed.
START-UP
I. UNIT PREPARATION
Make sure that unit has bee n installed in accordance with these installation instructions and applicable codes. Make
sure Start-Up Checklist on back page is filled out and completed.
II. RETURN-AIR FILTERS
Make sure correct filters are installed in filter tracks. See Table 1. Do not operate unit without return-air filters.
III. COMPRESSOR MOUNTING
Compressors are internally spring mounted. Do not loosen or remove compressor holddown bolts.
IV INTERNAL WIRING
Check all electrical connections in unit control boxes. Tighten as required. Ensure wiring does not come in contact with refrigerant tubing.
V. GAS PIPING
Check gas piping for leaks.
WARNING: Disconnect gas piping from unit when
leak testing at pressure greater than
1
sures greater tha n
/2 psig will cause g as valve damage
1
/2 psig. Pres-
resulting in hazardous condition. If gas valve is sub­jected to pressure greater than
1
/2 psig, it must be replaced before use. When pressure testing field­supplied gas piping at pressures of
1
/2 psig or less, a unit connected to such piping must be isolated by man­ually closing the gas valve.
VI. REFRIGERANT SERVICE PORTS
To service refrigerant service ports, remove compressor access panel. Each unit system has 4 Schrader-type service gage ports: one on the suction line, one on the liquid line, and two on the compressor discharge line. Be sure that caps on the ports are tight. One of the Schrader-type valves on the compressor discharge line is located under the low-pressure switch.
The Schrader valve on the compr essor di scharge li ne that is located under the high pressure switch does not contain a Schrader core in the valve.
VII. HIGH FLOW VALVES
Located on the compressor hot gas and suction tubes are high flow valves. Large black plastic caps distinguis h these valves with o- r in gs located inside the ca ps. These valv es ca n­not be accessed for service in the field. Ensure the plastic caps are in place and tight or the possibility of refrigerant leakage could occur.
VIII. COMPRESSOR ROTATION
On 3-phase units with scroll compressors, it is important to be certain compressor is rotating i n the proper direc tion. To determine whether or not compressor is rotating in the proper direction:
1. Connect service gage s to suction and discharge pres­sure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge pressure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge pres­sure does not rise to normal levels:
1. Note that the evaporator fan is probably also rotating in the wrong direction.
2. Turn off power to the unit and tag disconnect.
3. Reverse any two of the unit power leads.
4. Reapply power to the unit.
35
Page 36
The suction and discharge pressure levels should now move to their normal start-up levels.
NOTE: When the compres sor is rotating in th e wrong direc­tion, the unit makes an elevated level of noise and does not provide cooling.
IX. COOLING
Set space thermostat to OFF position. To start unit, turn on main power supply. Set system selector switch at COOL posi­tion and fan switch at AUTO. position. Adjust thermostat to a setting below room temperature. Compressor, outdoor fan and evaporator motor start on closure of contactor.
Check unit charge. Refer to Refrigerant Charge section, page 39.
Reset thermostat at a position above room temperature. Compressor will shut off. Evaporator fan will shut off after 30-second delay.
To Shut Off Unit
Set system selector switch at OFF position. Resetting ther­mostat at a position ab ove room temperature shu ts unit off temporarily until space temperature exceeds thermostat setting.
X. MAIN BURNERS
Main burners are factory set and should require no adjustment.
TO CHECK ignition of main burners and heating controls, move thermostat set p oint abov e room tem perature a nd ver­ify that the burners light and evaporator fan is energized. After ensuring that the unit continues to heat the building, lower the thermostat setting below room temperature and verify that the burners and evaporator fan turn off. (Fan will turn off only if fan selector switch is in the AUTO. position.)
Refer to Table 33A and 33B for the correct orifice to use at high altitudes.
XI. HEATING
1. Purge gas supply line of air by opening union ahead of gas valve. If gas odor is detected, tighten union and wait 5 minutes before proceeding.
2. Turn on electrical supply and manual gas val ve .
3. Set system switch selector at HEAT position and fan switch at AUTO. or ON position. Set heating temper­ature lever above room temperature.
4. The induced-draft motor will start.
5. After a call for heating, the main burners should light within 5 seconds. If the burner does not light, then there is a 22-second delay before another 5-second try. If the burner still does not light, the time delay is repeated. If the burner does not light within 15 min­utes, there is a lockout. To reset the control, break the 24-v power to W1.
6. The evaporator-fan motor wil l turn on 45 seconds af­ter the burners are ignited.
7. The evaporator-fan motor will turn off 45 seconds af­ter thermo st a t te m p e r at u r e i s sa t isfied.
8. Adjust airflow to obtain a temperature rise within the range specified on the unit nameplate.
NOTE: The default value for the evaporator-fan motor ON/ OFF delay is 45 seconds. The Integrated Gas Unit Controller (IGC) modifies this value when abnormal limit switch cycles occur . Based upon unit operating conditions, the ON delay can be reduced to 0 seconds and the OFF delay can be extended
to 180 seconds. When one flash of the LED is observed, t he evaporator-fan ON/OFF delay has been modified.
If the limit switch trips at the start of the heating cycle dur­ing the evap or ator ON delay, t he ti me period of the ON de lay for the next cycle will be 5 seconds less than the time at which the swit ch trip ped. (Exa mple: If th e l imit switch trip s at 30 seconds, t he ev aporator-fan ON delay for the next cycle will occur at 25 seconds.) To prevent short-cycling, a 5-second reduction will only occur if a minimum of 10 minutes has elapsed since the last call for heating.
The evaporator-fan OFF delay can also be modified. Once the call for heating has ended, there is a 10-minute period dur­ing which the modification can occur. If the limit switch trips during this period, the evaporator-fan OFF delay will increase by 15 seconds. A maximum of 9 trips can occur, extending the evaporator-fan OFF delay to 180 seconds.
To restore the original default value, reset the power to the unit.
To Shut Off Unit
Set system selector switch at OFF position. Resetting heat­ing selector lever bel ow room temperature will temporar ily shut unit off until space temperature falls be low therm ostat setting.
Table 33A — Altitude Compensation* — Standard Units
74,000 AND 115,000 BTUH
ELEVATION
(ft)
0-2,000 33 43 30 37
2,000 36 44 31 39 3,000 36 45 31 40 4,000 37 45 32 41 5,000 38 46 32 42 6,000 40 47 34 43 7,000 41 48 35 43 8,000 42 49 36 44
9,000 43 50 37 45 10,000 44 50 39 46 11,000 45 51 41 47 12,000 46 52 42 48 13,000 47 52 43 49 14,000 48 53 44 50
*As the height above sea level increases, there is less oxygen per cubic foot of air.
Therefore, heat input rate should be reduced at higher altitudes.
†Orifices available through your Br yant distributor.
NOMINAL INPUT
Natural
Gas
Orifice
Size†
Liquid
Propane
Orifice
Size†
150,000 BTUH
NOMINAL INPUT
Natural
Gas
Orifice
Size†
Liquid
Propane
Orifice Size†
Table 33B — Altitude Compensation* — Low NOx Units
60,000 AND 90,000 BTUH
ELEVATION
(ft)
0-2,000 38 45 32 42
2,000 40 47 33 43 3,000 41 48 35 43 4,000 42 49 36 44 5,000 43 49 37 45 6,000 43 50 38 45 7,000 44 50 39 46 8,000 45 51 41 47
9,000 46 52 42 48 10,000 47 52 43 49 11,000 48 53 44 50 12,000 49 53 44 51 13,000 50 54 46 52 14,000 51 54 47 52
*As the height above sea level increases, there is less oxygen per cubic foot of
air. Therefore, the input rate should be reduced at higher altitudes.
†Orifices are available through your local Bryant distributor.
NOMINAL INPUT
Natural
Gas
Orifice
Size†
Liquid
Propane
Orifice
Size†
120,000 BTUH
NOMINAL INPUT
Natural
Gas
Orifice
Size
Liquid
Propane
Orifice
Size†
36
Page 37
XII. SAFETY RELIEF
A soft solder joint at the suction service Schrader port pro­vides pressure relief under abnormal temperature and pres­sure conditions (i.e., fire in building).
XIII. VENTILATION (CONTINUOUS FAN)
Set fan and system selector switches at ON and OFF posi­tions, respectively. Evaporator fan operates continuous ly to provide constant air circulation. When the evaporator-fan selector switch is turned to the OFF position, there is a 30-second del a y be f or e th e f an tur ns off.
XIV. OPERATING SEQUENCE
A. Cooling, Units without EconoMi$er IV
When thermostat calls for cooling, terminals G and Y1 and the compressor contactor (C) are energized. The indoor (evaporator) fan motor (IFM), compressor, and outdoor (con­denser) fan motor (OFM) start. The OFM runs continuously while the unit is in cooling. When the thermostat is satisfied, C is deenergized and the compressor and OFM shut off. After a 30-second delay, the (IFM) shuts off. If the thermostat fan selector switch is in the ON position, the evaporator motor will run continuously.
B. Heating, Units without EconoMi$er IV
When the thermostat call s for heatin g, terminal W1 is ener­gized. The induced-draft motor is energized and the burner ignition seque nce begins. The indoor (evaporator) f an motor (IFM) is energized 45 seconds after a flame is ignited. When additional he at is n eeded, W 2 is en ergized and t he high- fire solenoid on the main gas valve (MGV) is energized. When the thermostat is satis fied and W1 is deenergized, the IFM stops after a 45-second time-off delay.
C. Cooling, Units with EconoMi$er IV
When free cooling is not avail able, the compressors will be controlled b y th e zone ther mosta t. Wh en f ree co oling is a vai l­able, the outdoor-air damper is modulated by the EconoMi$er IV control to provide a 50 to 55 F supply-air temperature into the zone. As the supply-air temperature fluctuates above 55 or be lo w 50 F, the dampers will be modu­lated (open or close) to bring the supply-air temperature back within set point limits.
Integrated EconoMi$er IV operation on single-stage units requires a 2-stage thermostat (Y1 and Y2).
For EconoMi$er IV operation, there must be a thermostat call for the fan (G). This will move the damper to its mini­mum position during the occupied mode.
Above 50 F supply-air temperature, the dampers will modu­late from 100% o pen to the minimum open po sition. From 50 F to 45 F supply-air temperature, the dampers will main­tain at the minimum open position. Below 45 F the dampers will be completely shut. As the supply-air temperature rises, the dampers will com e ba ck ope n to the mini mu m ope n posi ­tion once the supply-air temperature rises to 48 F.
If optional power exhaust is installed, as the outdoor-air damper opens and closes, the power exhaust fans will be energized and deenergized.
If field-installed accessory CO
sensors are connected to the
2
EconoMi$er IV control, a demand controlled ventilation
strategy will begin to o perate. As the CO
level in the zone
2
increases above the CO2 set point, the minimum position of the damper wi ll be i ncr eased pro port ional ly. As the CO
level
2
decreases because of the increase in fresh air, the outdoor-air damper will be proportionally closed. Damper position will follow the higher demand condition from DCV mode or free cooling mode.
On the initial power to the EconoMi$er IV control, it will take the damper up to 2
1
/2 minutes before it begins to position itself. Any change in damper position will take up to 30 sec­onds to initiate. Damper movement from full closed to full open (or vice versa) will take bet we en 1
1
/2 and 21/2 minutes.
If free cooling can be used as determined from the appropri­ate changeover com mand (switch, dr y bulb, enthalpy curve, differential dry bulb, or differential enthalpy), a call for cool­ing (Y1 closes at the thermostat) will cause the control to modulate the dampers open to maintain the supply a ir tem­perature set point at 50 to 55 F.
As the supply air temperature drops belo w the set point range of 50 to 55 F, the control will modulate the outdoor-air damp­ers closed to maintain the proper supply-air temperatur e .
D. Heating, Units with EconoMi$er IV
When the room temperature calls for heat, the heating controls are energized as described in the Heating, Units Without Economizer section. When the thermostat is satis­fied, the economizer damper moves to the minimum position.
SERVICE
CAUTION: When servicing unit, shut off all electri-
cal power to unit and install lockout tag to avoid shock hazard or injury f rom rotat i ng p a rts.
I. CLEANING
Inspect unit interior at the beginning of heating and cooling season and as operating conditions require.
A. Evaporator Coil
1. Turn unit power off and install lockout tag. Remove evaporator coil access panel.
2. If economizer or two-position damper is installed, remove economizer by disconnecting Molex plug and removing mounting screws.
3. Slide filters out of unit.
5. Reinstall economizer and filters.
6. Reconnect wiring.
7. Replace access panels.
B. Condenser Coil
Inspect coil month ly. Clean condenser coil annually, and as required by location and outdoor air conditio ns.
One-Row Coils (Size 036) Wash coil wi th comme rci al c oil clea ner. It is not necessary to
remove top panel.
37
Page 38
2-Row Coils (Sizes 048-073) Clean coil as follows:
1. Turn off unit power and install lockout tag.
2. Remove top panel screws on condenser end of unit.
3. Remove condenser coil corner post. See Fig. 36. To hold top panel open, place coil corner post between top panel and center post. See Fig. 37.
4. Remove screws securing coil to compressor plate and compressor access panel.
5. Remove fast ener holdi ng coil sect ions togethe r at re­turn end of condenser coil. Carefully separate the outer coil section 3 to 4 in. from the inner coil section. See Fig. 38.
6. Use a wate r hose or other suitabl e equ ip m ent t o flu s h down between the 2 coil se ctions to remove dirt and debris. Clean the outer surfaces with a stiff brush in the normal manner.
7. Secure inner and o uter co il row s to ge the r wi th a f iel d­supplied fastener.
8. Reposition the outer coil section and re move the coil corner post from between the top panel and center post. Reinstall the coil corner post and replace all screws.
Fig. 36 — Cleaning Condenser Coil
Fig. 37 — Propping Up Top Panel
Fig. 38 — Separating Coil Sections
C. Condensate Drain
Check and clean each year at start of cooling season. In win­ter, protect condensate drain against freeze-up.
D. Filters
Clean or rep lace at s tar t of e ach h eatin g an d co oling seas on, or more often if operating conditions require it. Replacement filters must be same dimensions as original filters.
E. Outdoor-Air Inlet Screen
Clean screen with stea m or hot water and a mild deter gent. Do not use disposable filters in place of screen.
II. LUBRICATION
A. Compressors
Each compressor is charged w ith the correct amount of oil at the factory.
B. Fan Motor Bearings
Fan motor bearings are of the permanently lubricated type. No further lubrication is required. No lubrication of con­denser or evaporator fan motors is required.
III. BLOWER BELT ADJUSTMENT
Inspect blower b elt for wear, proper belt tension, a nd pulley alignment as conditions require or at the beginning of each heating and air conditioning season.
Refer to Step 9 — Adjust Evaporator-Fan Speed on page 22 for adjustment and alignment procedures.
Check belt tension a t least once each heat ing or cooli ng sea­son or as conditions require. Adjust as required.
IV. MANUAL OUTDOOR-AIR DAMPER
If outdoor-air damper blade adjustment is required, see Manual Outdoor-Air Damper section on page 14.
38
Page 39
V. ECONOMI$ER IV ADJUSTMENT
Refer to Optional EconoMi$er IV section on page 15.
VI. CONDENSER-FAN ADJUSTMENT (Fig. 39)
Shut off unit power supply. Remove condenser-fan assembly (grille, motor, and fan) and loosen fan hub setscrews. Adjust fan height as shown in Fig. 39. Tighten setscrews and replace condenser-fan assembly.
Fig. 39 — Condenser-Fan Adjustment
VII. REFRIGERANT CHARGE
Amount of refrigerant charge is listed on unit nameplate (also refer to Table 1). Compressor must run a minimum of 10 minutes before adjus ting or checki ng charge.
Unit panels must be in place when unit is operating during charging procedure.
A. No Charge
Use standard evacuating techniques. After evacuating sys­tem, to 500 microns, weigh in the specified amount of refrig­erant. (Refer to Table 1.)
B. Low-Charge Cooling
Using Cooling Charging Charts, Fig. 40-43, vary refrigerant until the conditions of the appropriate chart are met. Note the charging charts a re different from type normall y used. Charts are based on charging the units t o the correct super­heat for the var ious op erating c onditio ns. Accurate pr essure gage and temperature sensing device are required. Do not use pocket type thermometers for measuring surface temper­atures as they are not designed for this type of measure­ment. Connect the pressure gage to the service port on the suction line. Mount the temperature sensing device on the suction line and insula te it so that ou tdoor am bient temper a­ture does not affect the reading. Indoor-air cfm must be within the normal operating range of the unit.
C. To Use Cooling Charging Chart
Take the outdoor ambient temperature and read the suction pressure gage. Refer to chart to determine what suction tem­perature should be. If suction temperature is high, add refrigerant. If suction temp erature is low, carefully recover some of the charge. Recheck the suction pressure as charge is adjusted .
EXAMPLE: (Fig. 42)
Outdoor Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 F
Suction Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80 psig
Suction Temperature should be . . . . . . . . . . . . . . . . . . . 76 F
(Suction Temperature may vary 5 F.)
VIII. FLUE GAS PASSAGEWAYS
To inspect the flue collector box and upper areas of the heat exchanger:
1. Remove the combustion blower wheel and motor assembly according to directions in Combustion-Air Blower section on pa ge 39.
2. Remove the flue cover to inspect the heat exchanger.
3. Clean all surfaces as required using a wire brush.
IX. COMBUSTION-AIR BLOWER
Clean periodically to assure proper airflow and heating effi­ciency. Inspect blower whee l every f all and p eri od ical ly du ri ng heating season. For the first heating season, inspect blower wheel bimonthly to determine proper cleaning frequency.
To access burner section, slide the sliding burner partition out of the unit.
To inspect blower wheel, shine a flashlight in to draft hood opening. If cleaning is required, remove m otor and wheel as follows:
1. Slide burner access panel out.
2. Remove the 7 screws that attach induced-draft motor housing to vestibule plate (Fig. 44).
3. The blower wheel can be cleaned at this point. If ad­ditional cleaning is required, continue with Steps 4 and 5.
4. To remove blower from the motor shaft, remove 2 setscrews.
5. To remove motor, remove the 4 screws that hold the motor to mounting plate. Remove the motor cooling fan by removing one setscrew. Then remove nuts that hold motor to mounting plate.
6. To reinstall, reverse the procedure outlined above.
X. LIMIT SWITCH
Remove blower access panel (Fig. 7). Limit switch is located on the fan deck.
XI. BURNER IGNITION
Unit is equipped with a direct spark ignition 100% lockout system. Integrated Gas Unit Controller (IGC ) is loc ated in the control box (Fig. 11). The IGC contains a self-diagnostic LED (light-emitting diode). A single LED on the IGC provides a visual display of operational or sequential problems when the power supply is uninterrupted. Whe n a break in power o ccurs , the IGC will be reset (resulting in a loss of fault history) and the indoor (evaporator) fan ON/OFF times will be reset. The LED error code can be ob served through the viewport. During servicing refer to the labe l o n th e cont ro l b ox co ver o r Table 34 for an explanation of LED error code d escriptions.
If lockout occurs, unit may be reset by interrupting power supply to unit for at least 5 seconds.
39
Page 40
3 TON UNIT CHARGING CHART
SUCTION LINE TEMPERATURE (DEG. C)
-7 -1 4 10 16 21 27
100
90
80
70
689
621
552
483
OUTDOOR TEMP
F C 125 52
115 46
105 41
95 35
85 29
75 24
65 18
55 13
45 7
60
50
SUCTION LINE PRESSURE (PSIG)
40
30
20 30 40 50 60 70 80
SUCTION LINE TEMPERATURE (DEG. F)
Fig. 40 — Cooling Charging Chart, 580F036
4 TON UNIT CHARGING CHART
SUCTION LINE TEMPERATURE (DEG. C)
-7 -1 4 10 16 21 27
100
90
414
345
276
207
689
621
SUCTION LINE PRESSURE (KILOPASCALS)
OUTDOOR TEMP
F C 125 115
105 41
95 35 85 29
52 46
80
70
60
50
SUCTION LINE PRESSURE (PSIG)
40
30
20 30 40 50 60 70 80
SUCTION LINE TEMPERATURE (DEG. F)
Fig. 41 — Cooling Charging Chart, 580F048
40
552
483
414
345
276
207
75
65
55
45 7
SUCTION LINE PRESSURE (KILOPASCALS)
24
18
13
Page 41
5 TON UNIT CHARGING CHART
SUCTION LINE TEMPERATURE (DEG. C)
-7 -1 4 10 16 21 27
100
90
80
70
689
621
552
483
OUTDOOR
TEMP
F C 125 52
115 46
105 41
95 35
85 29
75 24
65 18
55 13 45 7
60
50
SUCTION LINE PRESSURE (PSIG)
40
30
20 30 40 50 60 70 80
SUCTION LINE TEMPERATURE (DEG. F)
Fig. 42 — Cooling Charging Chart, 580F060
6 TON UNIT (60 Hz) CHARGING CHART
SUCTION LINE TEMPERATURE (DEG. C)
-7 -1 4 10 16 21 27
100
90
80
70
414
345
276
207
SUCTION LINE PRESSURE (KILOPASCALS)
689
621
552
483
OUTDOOR TEMP
F C 125 52 115 46 105 41 95 35 85 29 75 24 65 18 55 13 45 7
60
50
SUCTION LINE PRESSURE (PSIG)
40
30
20 30 40 50 60 70 80
SUCTION LINE TEMPERATURE (DEG. F)
Fig. 43 — Cooling Charging Chart, 580F072, 073
41
414
345
SUCTION LINE PRESSURE (KILOPASCALS)
276
207
Page 42
Table 34 — LED Error Code Description*
LED INDICATION ERROR CODE DESCRIPTION
ON Normal Operation
OFF Hardware Failure
1 Flash† Evaporator Fan On/Off Delay Modified 2 Flashes Limit Switch Fault 3 Flashes Flame Sense Fault 4 Flashes 4 Consecutive Limit Switch Faults 5 Flashes Ignition Lockout Fault 6 Flashes Induced-Draft Motor Fault 7 Flashes Rollout Switch Fault 8 Flashes Internal Control Fault 9 Flashes Internal Software Processor Fault
LED — Light-Emitting Diode
†Indicates a code that is not an error. The unit will continue to operate
IMPORTANT: Refer to Troubleshooting Tables 35-37 for additional infor­mation.
LEGEND
*A 3-second pause exists between LED error code flashes. If more than one error code exists, all applicable codes will be displayed in numerical sequence.
when this code is displayed.
XII. MAIN BURNERS
To access burners, remove burner access pan el and s lide out burner partition. At the beginning of each heating season, inspect for deterioration or blockage due to corrosion or other causes. Observe the main burner flames and adjust, if necessary.
CAUTION: When working on gas train, do not hit or
plug orifice spuds.
A. Removal and Replacement of Gas Train (Fig. 44-46)
1. Shut off manual gas valve.
2. Shut off power to unit and tag disconnect.
3. Slide out burner partition.
4. Disconnect gas piping at unit gas valve.
5. Remove wires connected to gas valve. Mark each wire.
6. Remove ignitor wires and sensor wires at the Inte­grated Gas Unit Controller (IGC) (see Fig. 11).
7. Remove the 2 screws that attach the burner rack to the vestibule pl ate (Fig. 44).
8. Slide the burner tray out of the unit (Fig. 45).
9. To reinstall, reverse the procedure outlined above.
B. Cleaning and Adjustment
1. Remove burner rack from unit as described in Removal and Replacement of Gas Train section, abo ve.
2. Inspect burners; if dirty, remove burners from rack.
3. Using a soft brush clean burners and cross-over port as required.
4. Adjust spark gap. See Fig. 46.
5. Reinstall burners on rack.
6. Reinstall burner rack as described in Removal and Replacement of Gas Train section, above.
XIII. HIGH-PRESSURE SWITCH
Located on the compressor hot gas line is a high-pressure switch containing a Schrader core depressor. This switch opens at 428 psig and closes at 320 psig. No adjustment is necessary. Refer to Table 1.
XIV. LOSS OF CHARGE SWITCH
Located on the cond enser liquid line is a low-pressure switch which functions as a loss-of-charge switch. This switch con­tains a Schrader core depressor. This switch opens at 7 psig and closes at 22 psig. No adjustment is necessary. Refer to Table 1.
XV. FREEZESTAT
Located on the “hair pin” end of the evaporator coil is a bimetal temperature sensing switch. This switch protects the evaporator coi l from f reeze -up due to lack of ai rflow. The switch opens at 30 F and closes at 45 F. No adjustment is necessary. Refer to Table 1.
XVI. REPLACEMENT PARTS
A complete list of repl acement parts may be obtained from any Bryant distributor upon request.
INDUCED­DRAFT MOTOR MOUNTING PLATE
BURNER SECTION
INDUCED­DRAFT MOTOR
MANIFOLD PRESSURE TAP
Fig. 44 — Burner Section Details
ROLLOUT SWITCH
FLUE EXHAUST
VESTIBULE PLATE
BLOWER HOUSING
GAS VALV E
Fig. 45 — Burner Tray Details
42
Page 43
580F036-073 — 74,000 BTUH INPUT
580F036-060 (Low NO
580F036-073 — 115,000 BTUH INPUT 580F048-073 — 150,000 BTUH INPUT
580F036-060 (Low NO
580F048-060 (Low NO
LOW HEAT
) — 60,000 BTUH INPUT
x
MEDIUM AND HIGH HEAT
) — 90,000 BTUH INPUT
x
) — 120,000 BTUH INPUT
x
Fig. 46 — Spark Adjustment
TROUBLESHOOTING
I. UNIT TROUBLESHOOTING
Refer to Tables 35-37 and Fig. 47 for unit troubleshooting information.
II. ECONOMI$ER IV TROUBLESHOOTING
See Table 38 for EconoMi$er IV logic. A functional vi ew of the Econ oMi$er IV is shown in Fig. 48.
Typical settings, sensor ranges, and jumper positions are also shown. An EconoMi$er IV simulator program is avail­able from Bryant to help with EconoMi$er IV training and troubleshooting.
A. EconoMi$er IV Preparation
This procedure is used to prepare the EconoMi$er IV for troubleshooting. No troubleshooting or testing is done by performing the following procedure.
NOTE: This procedure requires a 9-v battery, 1.2 kilo-ohm resistor, and a 5.6 kilo-ohm resistor which are not supplied with the EconoMi$er IV.
IMPORTANT: Be sure to record the positio ns of all potenti­ometers befo re starting troubleshooting.
1. Disconnect power at TR and TR1. All LEDs should be off. Exhaust fan contacts should be open.
2. Disconnect device at P and P1.
43
Page 44
3. Jumper P to P1.
4. Disconnect wires at T and T1. Place 5.6 kilo-ohm re­sistor across T and T1.
5. Jumper TR to 1.
6. Jumper TR to N.
7. If connected, remove sensor from terminals SO and +. Connect 1.2 kilo-ohm 4074EJM checkout resistor across terminals S
8. Put 620-ohm resistor across terminals S
and +.
O
and +.
R
9. Set minimum position, DCV set point, and exhaust potentiometers fully CCW (counterclockwise).
10. Set DCV maximum position potentiometer fully CW (clockwise).
11. Set enthalpy potentiometer to D.
12. Apply power (24 vac) to terminals TR and TR1.
B. Differential Enthalpy
To check differential enthalpy:
1. Make sure Econo Mi $ er IV prep a rat io n p ro ce dur e h as been performed.
2. Place 620-ohm resistor across SO and +.
3. Place 1.2 kilo-ohm resistor across S
and +. The Free
R
Cool LED should be lit.
4. Remove 620-ohm resistor across S
and +. The Free
O
Cool LED should turn off.
5. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.
C. Single Enthalpy
To check single enthalpy:
1. Make sure Econo Mi $ er IV prep a rat io n p ro ce dur e h as been performed.
2. Set the enthalpy potentiometer to A (fully CCW). The Free Cool LED should be lit .
3. Set the enthalpy potentiometer to D (fully CW ). The Free Cool LED should turn off.
4. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.
D. DCV (Demand Controlled Ventilation) and Power Exhaust
To check DCV and Power Exhaust:
1. Make sure Econo Mi $ er IV prep a rat io n p ro ce dur e h as been performed.
2. Ensure terminals AQ and AQ 1 ar e o pen . The LE D for both DCV and Exhaust should be off. The actuator should be fully closed.
3. Connect a 9-v battery to AQ (positive node) and AQ1 (negative node). The LED for both DCV and Exhaust should turn on. Th e actu a tor sh oul d d riv e to betwe en 90 and 95% open.
4. Turn the Exhaust potentiometer CW until the Ex­haust LED turns off. The LED shou ld turn off when the potentiometer is approximately 90% . The actua­tor should remain in position.
5. Turn the DCV set point potenti ometer CW until the DCV LED turns off. The DCV LED should turn off when the potentiom eter i s ap prox im at el y 9-v. The ac­tuator should drive fully closed.
6. Turn the DCV and Exhaust potentiometers CCW un­til the Exhaust LED turns on. The exhaust contacts will close 30 to 120 seconds afte r the Exhaust LED turns on.
7. Return EconoMi$er IV settings and wiring to norm al after completing troubleshooting.
E. DCV Minimum and Maximum Position
To check the DCV minimum and maximum position:
1. Make sure Econ o Mi$ er I V pr epa ra tio n proce d ur e has been performed.
2. Connect a 9-v battery to AQ (positive node) and AQ1 (negative node). Th e DCV LED should turn on. The actuator should drive to between 90 and 95% open.
3. Turn the DCV Maximum Position potentiometer to midpoint. The actuator should drive to between 20 and 80% open.
4. Turn the DCV Maximum Position potentiometer to fully CCW. The actuator should drive fully closed.
5. Turn the Minimum Position potentiometer to mid­point. The actua tor should drive to betwee n 20 and 80% open.
6. Turn the Minimum Position Potentiometer fully CW. The actuator should drive fully open.
7. Remove the jumper from TR and N. The actuator should drive fully closed.
8. Return EconoMi$er IV settings and wiring to norm al after completing troubleshooting.
F. Supply-Air Input
To check supply-air input:
1. Make sure Econ o Mi$ er I V pr epa ra tio n proce d ur e has been performed.
2. Set the Enthalpy potentiometer to A. The Free Cool LED turns on. The actuator should drive to between 20 and 80% open.
3. Remove the 5.6 kilo-ohm resistor and jumper T to T1. The actuator should drive fully open.
4. Remove the jumper across T and T1. The actuator should drive fully closed.
5. Return EconoMi$er IV settings and wiring to norm al after completing troubleshooting.
G. EconoMi$er IV Troubleshooting Completion
This procedure is used to return the EconoMi$er IV to opera­tion. No trouble shooting or testi ng is done by performing the following procedure.
1. Disconnect power at TR and TR1.
2. Set enthalpy potentiometer to previous setting.
3. Set DCV maximum position po tentiometer to previ­ous setting.
4. Set minimum position, DCV set point, and exhaust potentiometers to previous settings.
5. Remove 620-ohm resistor from terminals S
and +.
R
6. Remove 1.2 kilo-ohm checkout resistor from termi­nals S nals S
and +. If used, reconnect sensor from termi-
O
and +.
O
7. Remove jumper from TR to N.
8. Remove jumper from TR to 1.
9. Remove 5.6 kilo-ohm resistor from T and T1. Recon­nect wires at T and T1.
10. Remov e jumper from P to P1. Reconn ect device at P and P1.
11. Apply power (24 vac) to terminals TR and TR1.
44
Page 45
Table 35 — LED Error Code Service Analysis
SYMPTOM CAUSE REMEDY
Hardware Failure. (LED OFF)
Fan ON/OFF Delay Modified (LED/FLASH)
Limit Switch Fault. (LED 2 flashes)
Flame Sense Fault. (LED 3 flashes)
4 Consecutive Limit Switch Faults. (LED 4 flashes)
Ignition Lockout. (LED 5 flashes)
Induced-Draft Motor Fault. (LED 6 flashes)
Rollout Switch Fault. (LED 7 flashes)
Internal Control Fault. (LED 8 flashes)
Internal Software Fault. (LED 9 flashes)
CAUTION: If the IGC must be replaced, be sure to ground
yourself to dissipate any electrical charge that may be present before handling new control board. The IGC is sensitive to static electricity and may be damaged if the necessary precautions are not taken.
Loss of power to control module (IGC). Check 5 amp fuse on IGC, power to unit, 24-v circuit breaker, and
High limit switch opens during heat exchanger warm-up period before fan-on delay expires. Limit switch opens within three minutes after blower-off delay timing in Heating mode.
High temperature limit switch is open. Check the operation of the indoor (evaporator) fan motor.
The IGC sensed flame that should not be present.
Inadequate airflow to unit. Check operation of indoor (evaporator) fan motor and that supply-air
Unit unsuccessfully attempted ignition for 15 minutes.
IGC does not sense that induced-draft motor is operating.
Rollout switch has opened. Rollout switch will automatically reset, but IGC will continue to lockout unit.
Microprocessor has sensed an error in the software or hardware.
Internal Software Processor fault. Fault code will automatically reset after one hour. Can be immediately
transformer. Units without a 24-v circuit breaker have an internal overload in the 24-v transformer. If the overload trips, allow 10 minutes for automatic reset.
Ensure unit is fired on rate and temperature rise is correct.
Ensure unit’s external static pressure is within application guidelines.
Ensure that the supply-air temperature rise is in accordance with the range on the unit nameplate.
Reset unit. If problem persists, replace control board.
temperature rise agrees with range on unit nameplate information.
Check ignitor and flame sensor electrode spacing, gaps, etc. Ensure that flame sense and ignition wires are properly terminated. Verify that unit is obtaining proper amount of gas.
Check for proper voltage. If motor is operating, check the speed sensor plug/IGC Terminal J2 connection. Proper connection: PIN 1 — White, PIN 2 — Red, PIN 3 — Black.
Check gas valve operation. Ensure that induced-draft blower wheel is prop­erly secured to motor shaft. Reset unit at unit disconnect.
If error code is not cleared by resetting unit power, replace the IGC.
reset by resetting unit power supply.
IMPORTANT:
troubleshooting analysis.
IGC Integrated Gas Unit Controller LED — Light-Emitting Diode
Refer to Table 36 — Heating Service Analysis for additional
LEGEND
Table 36 — Heating Service Analysis
PROBLEM CAUSE REMEDY
Burners Will Not Ignite. Misaligned spark electrodes. Check flame ignition and sensor electrode positioning. Adjust as needed.
No gas at main burners. Check gas line for air, purge as necessary. After purging gas line of air, allow
Water in gas line. Drain water and install drip leg to trap water. No power to furnace. Check power supply, fuses, wiring, and circuit breaker. No 24 v power supply to control circuit. Check transformer. Transformers with internal overcurrent protection require a
Miswired or loose connections. Check all wiring and wire nut connections. Burned-out heat anticipator in thermostat. Replace thermostat. Broken thermostat wires. Run continuity check. Replace wires, if necessary.
Inadequate Heating. Dirty air filter. Clean or replace filter as necessary.
Gas input to unit too low. Check gas pressure at manifold. Clock gas meter for input. If too low, increase
Unit undersized for application. Replace with proper unit or add additional unit. Restricted airflow. Clean filter, replace filter, or remove any restrictions. Blower speed too low. Use high speed tap, increase fan speed, or install optional blower, as suitable
Limit switch cycles main burners. Check rotation of blower, thermostat heat anticipator settings, and temperature
Too much outdoor air. Adjust minimum position.
Poor Flame Characteristics. Incomplete combustion (lack of combustion
Burners Will Not Turn Off. Unit is locked into Heating mode for a one
air) results in: Aldehyde odors, CO, sooting flame, or floating flame.
minute minimum.
gas to dissipate for at least 5 minutes before attempting to relight unit. Check gas valve.
cool down period before resetting.
manifold pressure, or replace with correct orifices.
for individual units.
rise of unit. Adjust as needed.
Check economizer operation. Check all screws around flue outlets and burner compartment. Tighten as nec-
essary. Cracked heat exchanger. Overfired unit — reduce input, change orifices, or adjust gas line or manifold
pressure. Check vent for restriction. Clean as necessary. Check orifice to burner alignment. Wait until mandatory one minute time period has elapsed or re-
set power to unit.
45
Page 46
Table 37 — Cooling Service Analysis
PROBLEM CAUSE REMEDY
Compressor and Condenser Fan Will Not Start.
Compressor Will Not Start But Condenser Fan Runs.
Compressor Cycles (Other Than Normally Satisfying Thermostat).
Compressor Operates Continuously.
Excessive Head Pressure. Dir ty air filter. Replace filter.
Head Pressure Too Low. Low refrigerant charge. Check for leaks; repair and recharge.
Excessive Suction Pressure. High head load. Check for source and eliminate.
Suction Pressure Too Low. Dir ty air filter. Replace filter.
Evaporator Fan Will Not Shut Off. Time off delay not finished. Wait for 30-second off delay. Compressor Makes Excessive
Noise (580F072 and 073 Scroll Only).
Power failure. Call power company. Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker. Defective thermostat, contactor, transformer, or
control relay. Insufficient line voltage. Determine cause and correct. Incorrect or faulty wiring. Check wiring diagram and rewire correctly. Thermostat setting too high. Lower thermostat setting below room temperature. Faulty wiring or loose connections in compressor
circuit. Compressor motor burned out, seized, or internal
overload open. Defective run/start capacitor, overload, start relay. Determine cause and replace. One leg of three-phase power dead. Replace fuse or reset circuit breaker. Determine cause. Refrigerant overcharge or undercharge. Recover refrigerant, evacuate system, and recharge to
Defective compressor. Replace and determine cause. Insufficient line voltage. Determine cause and correct. Blocked condenser. Determine cause and correct. Defective run/start capacitor, overload, or start relay. Determine cause and replace. Defective thermostat. Replace thermostat. Faulty condenser-fan motor or capacitor. Replace. Restriction in refrigerant system. Locate restriction and remove. Dirty air filter. Replace filter. Unit undersized for load. Decrease load or increase unit size. Thermostat set too low. Reset thermostat. Low refrigerant charge. Locate leak; repair and recharge. Leaking valves in compressor. Replace compressor. Air in system. Recover refrigerant, evacuate system, and recharge. Condenser coil dirty or restricted. Clean coil or remove restriction.
Dirty condenser coil. Clean coil. Refrigerant overcharged. Recover excess refrigerant. Air in system. Recover refrigerant, evacuate system, and recharge. Condenser air restricted or air short-cycling. Determine cause and correct.
Compressor valves leaking. Replace compressor. Restriction in liquid tube. Remove restriction.
Compressor valves leaking. Replace compressor. Refrigerant overcharged. Recover excess refrigerant.
Low refrigerant charge. Check for leaks; repair and recharge. Metering device or low side restricted. Remove source of restriction. Insufficient evaporator airflow. Increase air quantity. Check filter and replace if
Temperature too low in conditioned area. Reset thermostat. Outdoor ambient below 25 F. Install low-ambient kit.
Compressor rotating in wrong direction. Reverse the 3-phase power leads as described in the
Replace component.
Check wiring and repair or replace.
Determine cause. Replace compressor.
nameplate.
necessary.
Start-Up section on page 35.
46
Page 47
NOTES:
1. If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent.
2. Three phase motors are protected under primary single phasing conditions.
4. Use copper conductors only.
6. TRAN is wired for 230 v unit. If unit is to be run with 208 v power supply, disconnect BLK wire from 230 v tap (ORN) and connect to 208 v tap (RED). Insulate end of 230 v tap.
C—Contactor, Compressor CAP Capacitor COMP — Compressor Motor EQUIP — Equipment FPT Freeze Up Protection Thermostat FU Fuse GND Ground GVR Gas Valve Relay HPS High-Pressure Switch HS Hall-Effect Sensor I—Ignitor IDM Induced-Draft Motor IFC Indoor Fan Contactor IFM Indoor (Evaporator) Fan Motor IGC Integrated Gas Unit Controller LPS Low-Pressure Switch LS Limit Switch MGV Main Gas Valve
LEGEND
OFM Outdoor (Condenser) Fan Motor OLR Overload Relay P—Plug PL Plug Assembly QT Quadruple Terminal RS Rollout Switch SAT Supply Air Temperature Sensor TRAN — Transformer
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Fig. 47 — Typical Unit Wiring Diagram
47
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring To indicate common potential only;
not to represent wiring.
Page 48
Table 38 — EconoMi$er IV Input/Output Logic
INPUTS OUTPUTS
Demand Control
Ventilation (DCV)
Below set (DCV LED Off)
Above set (DCV LED On)
*For single enthalpy control, the module compares outdoor enthalpy
to the ABCD set point.
†Power at N terminal determines Occupied/Unoccupied setting:
24 vac (Occupied), no power (Unoccupied).
**Modulation is based on the supply air sensor signal.
††Modulation is based on the DCV signal.
High (Free Cooling LED Off)
Low (Free Cooling LED On)
High (Free Cooling LED Off)
Low (Free Cooling LED On)
Enthalpy*
Outdoor Return
Low On On On On Minimum position Closed
High On On On Off Modulating** (between min.
Low On On On On Modulating†† (between min.
High On On On Off Modulating*** Modulating†††
Y1 Y2
On Off On Off Off Off Off Off
On Off Off Off Off Off Off Off Minimum position Closed
On Off On Off Off Off Off Off
On Off Off Off Off Off Off Off
Compressor N Terminal†
Stage1Stage
2
position and full-open)
position and DCV maximum)
***Modulation is based on the greater of DCV and supply air sensor
signals, between minimum position and either maximum position (DCV) or fully open (supply air signal).
†††Modulation is based on the greater of DCV and supply air sensor
signals, between closed and either maximum position (DCV) or fully open (supply air signal).
Occupied Unoccupied
Damper
Modulating** (between closed and full-open)
Modulating†† (between closed and DCV maximum)
Fig. 48 — EconoMi$er IV Functional View
48
Page 49
Access panels
15
Altitude compensation 36 Barometric flow capacity 17 Burner ignition 39 Burner rack 42 Burner section 42 Burner spark gap 43 Charging chart, refrigerant 40, 41 Clearance 2, 3 CO2 sensor Configuration 20 Settings 21 Combustion blower wheel 39 Compressor Lubrication 38 Mounting 35 Rotation 35 Condensate drain Cleaning 38 Location 4, 6 Condenser coil 8 Cleaning 37 Condenser fan 8 Adjustment 39 Control circuit Wiring 10 Wiring raceway 11 Demand control ventilation 20 Dimensions 2, 3, 5 Ductwork 4 EconoMi$er IV 15-21 Adjustment 39 Components 15 Damper movement 20 Inputs and Outputs 48 Troubleshooting 43, 44 Wiring 16 Electrical connections 10 Electrical data 12, 13 Enthalpy changeover set points 19 Evaporator coil 8 Cleaning 37 Evaporator fan motor Lubrication 38 Motor data 23 Mounting 22 Performance 24-34 Pulley adjustment 22 Pulley setting 8, 23 Speed 8 Factory-installed options 14-21 EconoMi$er IV 15-21 Manual outdoor air damper 14 Filter Cleaning
38
Installation 16 Size 9 Flue gas passageways 39 Flue hood 6, 10 Freeze protection thermostat 9, 42 Gas connection 9 Gas input 9 Gas piping 6, 10, 35 Gas pressure 1, 6, 9 Heat anticipator settings 9, 10 Heat exchanger 9 High flow valves 35 High pressure switch 9, 42 Horizontal units 1, 4 Indoor air quality sensor 19 Integrated gas controller 39 Error codes 42, 45 Leak test 35 Limit switch 39 Liquid propane 9 Low pressure switch 9, 42 Main burners 36 Manual outdoor air damper 14
INDEX
Mounting Compressor 35 Unit 4 Natural gas 9 Operating limits 4 Operating sequence 37 Cooling 37 EconoMi$er IV 37 Heating 37 Outdoor air hood 14, 16 Outdoor air inlet screens Cleaning 38 Outdoor air temperature sensor 17 Physical data 8, 9 Power supply 10 Wiring 11 Pressure switches High pressure 9, 42 Low pressure 9, 42 Pre-Start-Up 35 Refrigerant Charge 8, 39 Type 8 Refrigerant service ports 35 Replacement parts 42 Return air filter 9, 35 Return air temperature sensor 18 Rigging unit 4, 7 Roof curb Assembly 1 Dimensions 5 Connector package 5 Leveling tolerances 6 Weight 8 Safety considerations 1 Safety relief 37 Service 37-43 Service ports 35 Slab mount 4 Start-up 35-37 Start-up checklist CL-1 Thermostat 10 Troubleshooting 43-48 Ventilation 37 Weight Corner 2, 3 EconoMi$er IV 2, 3, 8 Maximum 7 Unit 2, 3, 7, 8 Wiring EconoMi$er IV 16 Power connections 11 Thermostat 11 Unit 47
49
Page 50
SERVICE TRAINING
Packaged Service Training programs are an excellent way to increase you r knowledge of the equipment discussed in this manual, including:
• Unit Familiarizat ion • Maintenanc e
• Installation Overview • Operating Sequence
A large selection of product, theory, and skills programs are available, using popular video-based formats and materials. All include video and/or slides, plus companion book.
Classroom Service Training which includes “hands-on” experience with the products in our labs can mean increased confidence that rea lly pays divi dends in faster tro ubl esh ootin g and few er call­backs. Course descriptions and schedules are in our catalog.
CALL FOR FREE CATALOG 1-800-644-5544
[ ] Packaged Service Training [ ] C lassroom Service Training
Copyright 2005 Bryant Heating & Cooling Systems Printed in U.S.A. CATALOG NO. 04-53580001-01
Page 51
Page 52
START-UP CHECKLIST
(Remove and Use in Job File)
I. PRELIMINARY INFORMATION:
MODEL NO.: _______________________________________ SERIAL NO.:_______ _______________________________________ DATE: _____________________________________________ TECHNICIAN: ____________________________________________
BUILDING LOCATION: ___________________________________
II. PRE-START-UP (insert checkmark in box as each item is completed)
VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS
VERIFY THAT FLUE HOOD IS INSTALLED
CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
CHECK TO ENSURE NO WIRES ARE TOUCHING REFRIGERANT TUBING OR SHARP EDGES
CHECK GAS PIPING FOR LEAKS
CHECK THAT RETURN-AIR FILTER IS CLEAN AND IN PLACE
VERIFY THAT UNIT INSTALLATION IS LEVEL
CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS
VERIFY PULLEY ALIGNMENT AND BELT TENSION ARE CORRECT
CUT ALONG DOTTED LINE
III. START-UP:
ELECTRICAL
SUPPLY VOLTAGE L1-L2 ____________ L2-L3 ____________ L3-L1 ____________ COMPRESSOR AMPS L1 ____________ L2 ____________ L3 ____________ INDOOR-FAN AMP L1 ____________ L2 ____________ L3 ____________
TEMPERATURES
OUTDOOR-AIR TEMPERATURE _____________ DB _____________ WB ____________ RETURN-AIR TEMPERATURE _____________ DB _____________ WB ____________ COOLING SUPPLY AIR _____________ DB _____________ WB ____________ GAS HEAT SUPPLY AIR _____________ DB
PRESSURES
GAS INLET PRESSURE ____________ IN. WG GAS MANIFOLD PRESSURE ____________ IN. WG (LOW FIRE) ____________ IN. WG (HI FIRE) REFRIGERANT SUCTION ____________ PSIG ____________ TEMP F REFRIGERANT DISCHARGE ____________ PSIG ____________ TEMP F
VERIFY REFRIGERANT CHARGE USING CHARGING TABLES
VERIFY THAT 3-PHASE SCROLL COMPRESSOR IS ROTATING IN CORRECT DIRECTION (580F072 AND 073 ONLY)
CUT ALONG DOTTED LINE
Copyright 2005 Bryant Heating & Cooling Systems Printed in U.S.A. CL-1 CATALOG NO. 04-53580001-01
Loading...