Installation and servicing of air-conditioning equ ipment can
be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should
install, repair , or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained se rvice personnel. When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to the
unit, and other safety pre c au ti ons th at ma y a ppl y.
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.
WARNING: Before performing service or maintenance operations on unit, turn off main power switch to
unit and install lockout tag to disconnect switch. Electrical shock could cause personal injury.
580F
Dura
Cancels: II 580F-180-2II 580F-180-3
WAR NING:
1. Improper installation, adjustment, alteration, service, or maintenance can cause property damage,
personal injury, or loss of life. Refer to the User’s
Information Manual provided with this unit for
more details.
2. Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance.
What to do if you smell gas:
1. DO NOT try to light any appliance.
2. DO NOT touch any electrical switch, or use any
phone in your building.
3. IMMEDIATELY call your gas supplier from
a neighbor’s phone. Follow the gas supplier’s
instructions.
4. If you cannot reach your gas sup plier, call the fire
department.
WAR NING: Disconnect gas piping from unit when
pressure testing at p ressure greater than 0.5 psig. Pressures greater than 0.5 psig will cause gas valve damage
resulting in hazardous condition. If gas valve is subjected
to pressure greater than 0.5 psig, it must be replaced
before use. When pressure testing field-supplied gas piping at pressures of 0.5 psig or less, a unit connected to
such piping must be isolated by closing th e manual gas
valve(s).
IMPORTANT: Units have high ambient operating limits. If
limits are exceeded, the units will au tomatically lock the compressor out of operation. Manual reset will be required to
restart the compressor.
INSTALLATION
I. STEP 1 — PROVIDE UNIT SUPPORT
A. Roof Curb
Assemble or install accessory roof curb or horizontal adapter
roof curb in accordance with instructions shipped with this
accessory. See Fig. 1A, 1B, and 2. Install insulation, cant
strips, roofing, and counter flashing as shown. Ductwork can
be installed to roof curb or horizontal adapter roof curb before
unit is set in place. Curb or adapter roof curb shoul d be level.
This is necessary to permit unit drain to function properly.
Unit leveling tolerance is ±
tion. Refer to Accessory Roof Curb or Horizontal Adapter Roof
Curb Installation Instructions for additional information as
required. When accessory roof curb or horizontal adapter roof
curb is used, unit may be installed on class A, B, or C roof covering material.
1
/16 in. per linear ft in any direc-
Instructions continued on page 4.
Pac
Series
Sizes 180-300
15 to 25 Tons
3/15/06
DESCRIPTION
CURB
HEIGHT
Fig. 1A — Roof Curb Details — 580F180-240
PKG. NO. REF.
CRRFCURB012A002′-0″ (610) Side Supply and Return Curb for High Installation
CRRFCURB010A001′− 2″ (305) Standard Curb 14″ High
CRRFCURB011A002′-0″ (610) Standard Curb for Units Requiring High Installation
NOTE: CRRFCURB013A00 is a fully factory preassembled horizontal
adapter and includes an insulated transition duct. The pressure drop
through the adapter curb is negligible.
For horizontal return applications: The power exhaust and barometric
relief dampers must be installed in the return air duct.
IMPORTANT: The gasketing of the unit to the roof curb or
adapter roof curb is critical for a watertight seal. Install
gasket with the roof curb or adapter as shown in Fig. 1A and
1B. Improperly applied gasket can also result in air leaks
and poor unit performance.
B. Alternate Unit Support
When the curb or ada pter cannot be used, install unit on a
noncombustible surface. Support unit with sleepers, using
unit curb support area. If sleepers cannot be used, support
long sides of unit with a minimum of 3 equally spaced 4-in. x
4-in. pads on each side.
II. STEP 2 — RIG AND PLACE UNIT
Inspect unit for transportation damage. File any claim with
transportation agency.
Do not drop unit; keep upr ight. Use sprea der bars over unit
to prevent sling or cable damage. Rollers may be used to
move unit across a roof. Level by using unit frame a s a reference; leveling tolerance is ±
1
/16 in. per linear ft in any direction. See Fig. 3 for additional information. Unit operating
weight is shown in Table 1.
Four lifting holes are provided in ends of unit base rails as
shown in Fig. 3. Refer to rigging instructions on unit.
NOTE: On 58 0F300 unit s, the lower forklift braces mus t be
removed prior to setting unit on roof curb.
14 3/4"
6"
ACCESSORY
PACKAGE NO.
CRRFCURB013A00
12" WIDE STANDING
SEAM PANELS
CURB
HEIGHT
1′-11″
(584)
DESCRIPTION
Pre-Assembled, Roof Curb,
Horizontal Adapter
23"
A. Positioning
Maintain clearance, per Fig. 4-6, around and above unit to
provide minimum distance from combustible materials,
proper airflow, and service access.
Do not install unit in an indoor location. Do not locate air
inlets near exhaust vents or other sources of contaminated air .
For proper unit operation, adequate combustion and ventilation air must be provided in accordance with Section 5.3 (Air
for Combustion and Ventilation) of the National Fuel Gas
Code, ANSI Z223.1 (American National Standards Institute).
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
Locate mechanical draft system flue assembly at least 4 ft
from any opening through which combustion products could
enter the buil ding, and at le ast 4 ft fr om any adj acen t buil ding. When unit is located adjacent t o public walkways, flue
assembly must be at least 7 ft above grade.
B. Roof Mount
Check building codes for weight distribution requirements.
Unit operating weight is shown in Table 1.
Instructions continued on page 11.
—4—
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Refer to Fig. 4-6 for unit operating weights.
3. Remove boards at ends of unit and runners prior to rigging.
4. Rig by inserting hooks into unit base rails as shown. Use corner
post from packaging to protect coil from damage. Use bumper
boards for spreader bars on all units.
5. Weights do not include optional EconoMi$erIV. Add 90 lb (41 kg)
for EconoMi$erIV weight.
6. Weights given are for aluminum evaporator and condenser coil
plate fins.
CAUTION: All panels must be in place when rigging.
Rows...Fins/in.4...154...154...153...15 (2 coils)
Total Face Area (sq ft)21.721.721.743.4
CONDENSER FANPropeller Type
Nominal Cfm10,50010,50014,20021,000
Quantity...Diameter (in.)3...223...222...306...22
Motor Hp...Rpm
Watts Input (Total)1100110034002200
EVAPORATOR COILCross-Hatched
Rows...Fins/in.4...154...154...154...15
Total Face Area (sq ft)17.517.517.517.5
EVAPORATOR FANCentrifugal Type
Quantity...Size (in.)2...12 x 122...12 x 122...12 x 122...12 x 12
Type D riv eBeltBeltBeltBelt
Nominal Cfm60007200800010,000
Motor Hp557.510
Motor Nominal Rpm1745174517451740
Maximum Continuous Bhp6.135.90
Motor Frame Size184T184T213T215T
Nominal Rpm High/Low——— —
Fan Rpm RangeLow-Medium Static873-1021910-10951002-11511066-1283
Motor Bearing TypeBallBallBallBall
High Static1025-12001069-12871193-13691332-1550
Maximum Allowable Rpm1550155015501550
Motor Pulley Pitch DiameterLow-Medium Static4.9/5.94.9/5.95.4/6.64.9/5.9
Min/Max (in.)High Static4.9/5.94.9/5.95.4/6.64.9/5.9
Nominal Motor Shaft Diameter (in.)1
Fan Pulley Pitch Diameter (in.)Low-Medium Static9.49.49.48.0
High Static8.08.07.96.4
Nominal Fan Shaft Diameter (in.)1
Belt, Quantity...Type...Length (in.)Low-Medium Static1...BX...501...BX...501...BX...532...BX...50
High Static1...BX...481...BX...481...BX...502...BX...47
Pulley Center Line Distance (in.)13.3-14.813.3-14.814.6-15.414.6-15.4
Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Low-Medium Static37373736
High Static44344445
Movable Pulley Maximum Full Turns
*The ZRU140KC compressor is a tandem compressor, consisting of a ZR72KC (25% total capac-
ity) and a ZR68KC (24% total capacity).
†Circuit 1 uses the lower portion of the condenser coil and lower portion of the evaporator coils;
and Circuit 2 uses the upper portion of both coils.
**Pulley has 6 turns. Due to belt and pulley size, movable pulley cannot be set to 0 to 1
open.
††Pulley has 6 turns. Due to belt and pulley size, movable pulley cannot be set to 0 to
1
/2 turns
1
/2 turns
open.
***Rollout switch is manual reset.
†††A Liquid Propane kit is available as an accessory.
¶The 580F300 unit requires 2-in. industrial-grade filters capable of handling face velocities up to
625 ft/min (such as American Air Filter no. 5700 or equivalent).
NOTE: The 580F units have a low-pressure switch (standard) located on the suction side.
—10—
III. STEP 3 — FIELD FABRICATE DUCTWORK
Secure all ducts to building structure. Use flexible duct connectors between unit and ducts as required. Insulate and
weatherproof all external ductwork, joints, and roof openings
with counter flashing and m asti c i n acc ordance with applicable codes.
Ducts passing through an unconditioned space must be
insulated and covered with a vapor barrier.
IV. STEP 4 — MAKE UNIT DUCT CONNECTIONS
Unit is shipped for thru-the-bottom duct connections. Ductwork openings are shown in Fig. 1 and 4-6. Duct connections
are shown in Fig. 7. Field-fabricated concentric ductwork
may be connected as shown in Fig. 8 and 9. Attach all ductwork to roof curb and roof curb basepans.
V. STEP 5 — INSTALL FLUE HOOD AND WIND BAFFLE
Flue hood and wind baffle are shipped secured under main
control box. To install, secure flue hood to access panel. See
Fig. 10. The wind baffle is then installed over the flue hood.
NOTE: Whe n properly insta lled, flue hoo d will line up with
combustion fan housing. See Fig. 11.
VI. STEP 6 — TRAP CONDENSATE DRAIN
See Fig. 12 for drain location. One
3
/4-in. half coupling is provided inside unit evaporator section for condensate drain
connection. An 8
diameter pipe nipple, coupled to standard
1
/2-in. x 3/4-in. diameter and 2-in. x 3/4-in.
3
/4-in. diameter
elbows, provide a straight path down through hole in unit
base rails (see Fig. 13). A trap at least 4-in. de ep must be
used.
NOTE: Do not drill in this area; damage to basepan may result in water
leak.
Fig. 7 — Air Distribution — Thru-the-Bottom
NOTE: Dimensions A, A′, B, and B′ are obtained from field-supplied
ceiling diffuser.
Shaded areas indicate block-off panels.
Fig. 9 — Concentric Duct Details
WIND
BAFFLE
NOTE: Do not drill in this area; damage to basepan may result in water
leak.
Fig. 8 — Concentric Duct Air Distribution
Fig. 10 — Flue Hood Location
—11—
INDUCED DRAFT
MOTOR
VII. STEP 7 — ORIFICE CHANGE
This unit is factory assembled for heating operation using
natural gas at an elevation from sea level to 2000 ft. This
unit uses orifice type LH32RFn nn, wher e “nnn” i ndicates th e
orifice size based on drill size diameter in thousands of an
inch.
A. High Elevation (Above 2000 ft)
Use accessory high altitude kit when installing this unit at
an elevation of 2000 to 7000 ft. For elevations above 7000 ft,
refer to Table 2 to identify the correct orifice size for the
elevation. See Table 3 for the nu mber of orifi ces re quired for
each unit size. Purc hase the se orifi ces f rom your lo cal Bryant
dealer. Fo llow in structions in acc essory I nstallati on Ins tructions to install the correct orif ices.
580F240 Low Heat,
580F300 Low Heat,
580F180 High Heat
580F210 High Heat,
580F240 High Heat,
580F300 High Heat
6
7
B. Conversion To LP (Liquid Propane) Gas
Use accessory LP gas conversion kit when converting this unit
for use with LP fuel usage for elevations up to 7000 ft. For
elevations above 7000 ft, refer to Table 4 to identify the correct
orifice size for the elevation. See Table 3 for the number of
orifices required for each unit size. Purchase these orifices
from your local Bryant deale r. Follow instructions in acce ssory
Installation Instructions to install the corre ct orific es.
*As the height above sea level increases, there is less oxygen per
cubic foot of air. Therefore, heat input rate should be reduced at higher
altitudes. Includes a 4% input reduction per each 1000 ft.
†Orifices available through your Bryant dealer.
—12—
VIII. STEP 8 — INSTALL GAS PIPING
Unit is equipped for use with natural gas. Installation must
conform with local bu ilding codes or, in the absence of local
codes, with the National Fuel Gas Code, ANSI Z223.1.
Install field-supplied manual gas shutoff valve with a
1
/8-in.
NPT pressure tap for test gage co nnection at unit. Field gas
piping must include sediment trap and union. See Fig. 14.
WARNING: Do not pressure test gas supply while
connected to unit. Always disconnect union before
servicing.
IMPORTANT: Natural gas pressure at unit gas connection
must not be less than 5.5 in. wg or greater than 13.5 in. wg.
Size gas-supply piping for 0.5-in. wg maximum pressure
drop. Do not use supply pipe smaller than unit gas
connection.
Fig. 14 — Field Gas Piping
IX. STEP 9 — MAKE ELECTRICAL CONNECTIONS
A. Field Power Supply
Unit is factory wired for voltage shown on unit nameplate.
When installing units, provide a disconnect per NEC
(National Electrical Code) requirements of adequate size
(Table 5).
All field wiring must comply with NEC and local
requirements.
Route power and ground lines through control box end
panel or unit basepan (see Fig. 4-6) to connections as shown
on unit wiring diagram and Fig. 15.
CAUTION: The correct power phasing is critical in
the operation of the scroll compressors. An incorrect
phasing will cause the compressor to rotate in the
wrong direction. This may lead to premature compressor failure.
WARNING: The unit must be electrically grounded
in accordance with local codes and NEC ANSI/ NF PA 70
(National Fire Protection Association).
Field wiring must conform to temperature limitations for
type ‘‘T’’ wire. All field wiring must comply with NEC and
local require ments.
Transformer no. 1 is wi r ed for 230 -v unit. If 2 08/230-v unit is
to be run with 208-v power supply, the transfo rmer must be
rewired as follows:
1. Remove cap from red (208 v) wire.
2. Remove cap from orange (230 v) spliced wire.
3. Replace orange wire with red wire.
4. Recap both wires.
IMPORTANT: BE CERTAIN UNUSED WIRES ARE
CAPPED. Failure to do so may damage the transformers.
Operating voltage to compressor must be within voltage
range indicated on unit nameplate. On 3-phase units, voltages between phases must be balanced within 2%.
Unit failure as a res ult of ope ra tio n o n imp ro per line volt age
or excessive phase imbalance constitutes abuse and may
cause damage to electrical components.
B. Field Control Wiring
Install a Bryant-approv ed acces sory ther mosta t assemb ly (or
light commercial Thermidistat™ device for units equipped
with Perfect Humidity™ option) according to the installation
instructions included with accessory. Locate thermostat
assembly on a solid interior wall in the conditioned space to
sense average temperature.
Route thermostat cable or equivalent single leads of colored
wire from subbase terminals through conduit in uni t to lowvoltage connections as shown on unit label wiring diagram
and in Fig. 16.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American
Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft,
use no. 16 AWG insulated wire (35 C minimum). For over
75 ft, use no. 14 AWG insulated wire (35 C minimum). All
wire larger than no. 18 AWG cannot be directly connected a t
the thermos tat and wi ll req uire a j unction box and s plice a t
the thermostat.
Set heat anticipator settings as follows:
VOLTAGEW1W2
208/2300.980.44
4600.800.44
Settings may be changed slightly to provide a greater degree
of comfort for a particular installation.
C. Optional Non-Fused Disconnect
On units with the optional non-fused disconnect, incoming
power will be wired into the disconnect switch. Refer to
Fig. 17 for wiring for 100 and 200 amp disconnect switches.
Units with an MOCP (maximum overcurrent protection)
under 100 will use the 100 amp disconnect switch. Units
with an MOCP over 100 will use the 200 amp disconnect
switch. Refer to the applicable disconnect wiring diagram.
To prevent breakage during shipping, the disconnect handle
and shaft are shipped and packaged inside the unit control
box. Install the disconnec t handle before unit operation. To
install the handle and shaft, perform the following procedure:
1. Open the co nt ro l b ox do or and r e mo ve t he handle and
shaft from shipping location.
2. Loosen the Allen bolt located on the disconnect
switch. The bolt is locat ed on the sq uare hole a nd is
used to hold the shaft in place. The shaft cannot be
inserted until the Allen bo lt is moved.
3. Insert the disconnect shaft into the square hole on
the disconnect switch. The end of the shaft is specially cut and the shaft can only be inserted in the
correct orientation.
—13—
D. Optional Convenience Outlet
On units with optional convenience outlet, a 115-v GFI
(ground fault interrupt) convenience outl et rece ptacle is pr ovided for field wiring. Field wiring should be run thro ugh th e
7
/8-in. knockout provided in the basepan near the return air
opening.
THERMOSTAT ASSEMBLY
REMOVABLE JUMPER
RC
RH
Y1Y2
W1
W2
GC
L
X
LEGEND
EQUIP — Equipment
GND— Ground
NEC— National Electrical Code
TB— Te rm i n al B o a r d
NOTE: The maximum wire size for TB1 is 2/0.
Fig. 15 — Field Power Wiring Connections
4. Tighten the Allen bolt to lock the shaft into position.
5. Close the control box door.
6. Attach the handle to the external access door with
the two screws provided. When the handle is in the
ON position, the handle will be vertical. When
the handle is in the OFF position, the handle will be
horizontal.
7. Turn the handle to the OFF position and close the
door. The handle should fit over the end of the sha ft
when the door is closed.
8. The handle must be in the OFF position to open the
control box door.
R
RED
Y1
BLU
PNK
W1Y2
ORN
W2
VIO
C
BRN
X
WHT
G
BLK
Fig. 16 — Field Control Thermostat Wiring
6T3 4T2 2T1 LOAD
5L3 3L2 1L1 LINE
NOTE: The disconnect takes the place of TB-1 as shown on the unit
wiring diagram label and the component arrangement label.
Fig. 17 — Optional Non-Fused Disconnect Wiring
—14—
Table 5 — Electrical Data
UNIT
580F
LEGEND
FLA— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM— Indoor (Evaporator) Fan Motor
LRA— Locked Rotor Amps
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC— National Electrical Code
OFM — Outdoor (Condenser) Fan Motor
RLA— Rated Load Amps
*Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load
equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker. Canadian units may be
fuse or circuit breaker.
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%.
Min Max RLA LRA RLA LRA RLA LRA Qty Hp FLA (ea) HpFLAFLA LRAFLAMCAMOCP*
Use the following formula to determine the percent voltage
COMPRESSOR
No. 1No. 1ANo. 2
OFMIFM
% Voltage Imbalance
= 100 x
EXAMPLE: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
Maximum deviation is 7 v.
Determine percent voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
max voltage deviation from average voltage
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
POWER
EXHAUST
——0.5782/82110/110
4.618.80.5786/86110/110
——0.304150
2.36.00.304350
——0.5787/87110/110
4.618.80.5792/92110/110
——0.304450
2.36.00.304760
——0.57124/124 150/150
4.618.80.57129/129 150/150
——0.306180
2.36.00.306380
——0.57138/138 175/175
4.618.80.57143/143 150/175
——0.306480
2.360.306680
average voltage
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
= 1.53%
=
= 457
7
457
COMBUSTION
FAN MOTOR
452 + 464 + 455
3
1371
3
POWER
SUPPLY
X. STEP 10 — MAKE OUTDOOR-AIR INLET ADJUSTMENTS
A. Manual Outdoor-Air Damper
All units (except those equipped with a factory-installed
EconoMi$erIV ) h ave a ma nual out door-air damper to provide
ventilation air.
Damper can be preset to admit up to 25% outdoor air into
return-air compartment. To adjust, loosen securing screws
and move damper to desired setting, then retighten screws
to secure damper (Fig. 18).
XI. STEP 11 — INSTALL OUTDOOR-AIR HOOD
The outdoor-air hood is common to 25% air ventilation and
EconoMi$erIV. If EconoMi$erIV is factory installed, all
electrical connections have been made and adjusted at the
factory. Assemble and install hood in the field.
Fig. 18 — Standard 25% Outdoor-Air Section Details
—15—
IMPORTANT: If the unit is equipped with the optional
EconoMi$erIV component, move the outdoor-air temperature sensor prior to installing the outdoor-air hood. See the
Optional EconoMi$erIV section for more inform ation.
NOTE: The hood top panel, upper and lower filter retainers,
hood drain pan, baffle (size 300), and filter support bracket
are secured opposite the condenser end of the unit. The
screens, hood side panels, remaining section of filter support
bracket, seal strip, and hardware are in a package located
inside the return-air filter access panel (Fig. 19).
1. Attach seal strip to upper filter retainer. See Fig. 20.
2. Assemble hood top panel, side panels, upper filter
retainer, and drain pan (see Fig. 21).
3. Secure lower filter retainer and support bracket to
unit. See Fig. 21. Leave screws loose on size 300 units.
5. Loosen sheet metal screws for top pa nel of base unit
located above o utdoor-air inlet opening, and remove
screws for hood side panels located on the sides of the
outdoor-air inlet opening.
6. Match notches in hood top panel to unit top panel
screws. Inser t hood flange betw een top panel flan ge
and unit. Tighten screws.
7. Hold hood side panel flanges flat against unit, and
install screws removed in Step 5.
8. Insert outdoor-air inlet screens and spacer in channel
created by lower filter retainer and filter support
bracket.
9. Attach remaining section of filter support bracket.
XII. STEP 12 — INSTALL ALL ACCESSORIES
After all the factory-installed options have been adjusted,
install all field-installed accessories. Refer to the accessory
installation instructions included with each accessory.
A. Motormaster® I Control (–20 F) Installation (580F180
and 210 Only)
Install Field-Fabricated Wind Baffles
Wind baffles must be field-fabricated for all units to ensure
proper cooling cycle operation at low ambient temperatures.
See Fig. 22 for baffle details. Use 20-gage, galvanized sheet
metal, or similar corrosion-resistant metal for baffles. Use
field-supplied screws to attach baffles to uni t. Scre ws shou ld
1
be
/4-in. diameter and 5/8-in. long. Drill required screw holes
for mounting baffles.
Fig. 19 — Outdoor-Air Hood Component Location
Fig. 20 — Seal Strip Location
BAFFLE
LOWER FILTER
RETAINER
FILTER SUPPORT
BRACKET
CAUTION: To avoid damage to the refrigerant
coils and electrical components, use recommended
screw sizes only. Use care when drilling holes.
Install Motormaster I Controls
One Motormaster I control is required on size 180 and 210
units. The Motormaster I control must be used in conjunction
with the accessory fan motor sequencing kit and winter start
kit (purchased separately). The Motormaster I device controls
outdoor fan no. 1 while outdoor fans no. 2 and 3 are sequenced
off by the accessory fan motor sequencing kit.
Accessory Fan Motor Sequencing Kit — Install the access ory
fan motor sequencing kit per instruction supplied with accessory (purchased separately).
Winter Start Time Delay Relay Kit — Install the kit per
the instructions supplied with the accessory (purchased
separately).
Sensor Assembl y — Install the sensor assembly in the location shown in Fig. 23.
HOOD SIDE
HOOD TOP
PANEL
HOOD DRAIN PAN
UPPER FILTER RETAINER
NOTE: The outdoor-air hood comes with a baffle which is used on
size 300 units only, discard baffle for size 180-240 units.
PANELS (2)
FILTER SUPPORT
BRACKET
Fig. 21 — Outdoor-Air Hood Details
—16—
BAFFLE
(300 ONLY)
LOWER
FILTER
RETAINER
Loading...
+ 36 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.