Bryant 580F User Manual

installation, start-up and service instructions
SINGLE PACKAGE ROOFTOP GAS HEATING/ELECTRIC COOLING UNITS
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-25
I. Step 1 — Provide Unit Support. . . . . . . . . . . . . . . . . 1
II. Step 2 — Rig and Place Unit. . . . . . . . . . . . . . . . . . . 4
III. Step 3 — Field Fabricate Ductwork . . . . . . . . . . . . 11
IV. Step 4 — Make Unit Duct Connections . . . . . . . . . 11
V. Step 5 — Install Flue Hood and Wind Baffle . . . . . 11
VI. Step 6 — Trap Condensate Drain . . . . . . . . . . . . . . 11
VII. Step 7 — Orifice Change. . . . . . . . . . . . . . . . . . . . . 12
VIII. Step 8 — Install Gas Piping . . . . . . . . . . . . . . . . . . 13
IX. Step 9 — Make Electrical Connections . . . . . . . . . 13
X. Step 10 — Make Outdoor-Air Inlet Adjustments . . 15
XI. Step 11 — Install Outdoor-Air Hood. . . . . . . . . . . . 15
XII. Step 12 — Install All Accessories . . . . . . . . . . . . . 16
XIII. Step 13 — Adjust Factory-Installed Options. . . . . 18
XIV. Step 14 — Install Control Accessory for Optional
Perfect Humidity™ Dehumidification Package . . 24
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26-34
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34-42
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . .43-47
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equ ipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install, repair , or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func­tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained se rvice per­sonnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety pre c au ti ons th at ma y a ppl y.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extin­guishers available for all brazing operations.
WARNING: Before performing service or mainte­nance operations on unit, turn off main power switch to unit and install lockout tag to disconnect switch. Elec­trical shock could cause personal injury.
580F
Dura
Cancels: II 580F-180-2 II 580F-180-3
WAR NING:
1. Improper installation, adjustment, alteration, ser­vice, or maintenance can cause property damage, personal injury, or loss of life. Refer to the User’s Information Manual provided with this unit for more details.
2. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
What to do if you smell gas:
1. DO NOT try to light any appliance.
2. DO NOT touch any electrical switch, or use any phone in your building.
3. IMMEDIATELY call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
4. If you cannot reach your gas sup plier, call the fire department.
WAR NING: Disconnect gas piping from unit when pressure testing at p ressure greater than 0.5 psig. Pres­sures greater than 0.5 psig will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than 0.5 psig, it must be replaced before use. When pressure testing field-supplied gas pip­ing at pressures of 0.5 psig or less, a unit connected to such piping must be isolated by closing th e manual gas valve(s).
IMPORTANT: Units have high ambient operating limits. If limits are exceeded, the units will au tomatically lock the com­pressor out of operation. Manual reset will be required to restart the compressor.
INSTALLATION
I. STEP 1 — PROVIDE UNIT SUPPORT
A. Roof Curb
Assemble or install accessory roof curb or horizontal adapter roof curb in accordance with instructions shipped with this accessory. See Fig. 1A, 1B, and 2. Install insulation, cant strips, roofing, and counter flashing as shown. Ductwork can be installed to roof curb or horizontal adapter roof curb before unit is set in place. Curb or adapter roof curb shoul d be level. This is necessary to permit unit drain to function properly. Unit leveling tolerance is ± tion. Refer to Accessory Roof Curb or Horizontal Adapter Roof Curb Installation Instructions for additional information as required. When accessory roof curb or horizontal adapter roof curb is used, unit may be installed on class A, B, or C roof cov­ering material.
1
/16 in. per linear ft in any direc-
Instructions continued on page 4.
Series
Sizes 180-300
15 to 25 Tons
3/15/06
DESCRIPTION
CURB
HEIGHT
Fig. 1A — Roof Curb Details — 580F180-240
PKG. NO. REF.
CRRFCURB012A00 2-0 (610) Side Supply and Return Curb for High Installation
CRRFCURB010A00 1′− 2 (305) Standard Curb 14 High
CRRFCURB011A00 2-0 (610) Standard Curb for Units Requiring High Installation
2
A
A
Fig. 1B — Roof Curb Details — 580F300
3
3 1/2"
2" X 1/4 SUPPORT TYP. STITCH WELDED
FULLY INSULATED SUPPLY PLENUM 1" INSULATION 1 1/2 # DENSITY, STICK PINNED & GLUED
NOTE: CRRFCURB013A00 is a fully factory preassembled horizontal adapter and includes an insulated transition duct. The pressure drop through the adapter curb is negligible.
For horizontal return applications: The power exhaust and barometric
relief dampers must be installed in the return air duct.
Fig. 2 — Horizontal Supply/Return Adapter Installation (580F180-240)
IMPORTANT: The gasketing of the unit to the roof curb or
adapter roof curb is critical for a watertight seal. Install gasket with the roof curb or adapter as shown in Fig. 1A and 1B. Improperly applied gasket can also result in air leaks and poor unit performance.
B. Alternate Unit Support
When the curb or ada pter cannot be used, install unit on a noncombustible surface. Support unit with sleepers, using unit curb support area. If sleepers cannot be used, support long sides of unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side.
II. STEP 2 — RIG AND PLACE UNIT
Inspect unit for transportation damage. File any claim with transportation agency.
Do not drop unit; keep upr ight. Use sprea der bars over unit to prevent sling or cable damage. Rollers may be used to move unit across a roof. Level by using unit frame a s a refer­ence; leveling tolerance is ±
1
/16 in. per linear ft in any direc­tion. See Fig. 3 for additional information. Unit operating weight is shown in Table 1.
Four lifting holes are provided in ends of unit base rails as shown in Fig. 3. Refer to rigging instructions on unit.
NOTE: On 58 0F300 unit s, the lower forklift braces mus t be removed prior to setting unit on roof curb.
14 3/4"
6"
ACCESSORY
PACKAGE NO.
CRRFCURB013A00
12" WIDE STANDING SEAM PANELS
CURB
HEIGHT
1-11
(584)
DESCRIPTION
Pre-Assembled, Roof Curb,
Horizontal Adapter
23"
A. Positioning
Maintain clearance, per Fig. 4-6, around and above unit to provide minimum distance from combustible materials, proper airflow, and service access.
Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air . For proper unit operation, adequate combustion and ventila­tion air must be provided in accordance with Section 5.3 (Air for Combustion and Ventilation) of the National Fuel Gas Code, ANSI Z223.1 (American National Standards Institute).
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
Locate mechanical draft system flue assembly at least 4 ft from any opening through which combustion products could enter the buil ding, and at le ast 4 ft fr om any adj acen t buil d­ing. When unit is located adjacent t o public walkways, flue assembly must be at least 7 ft above grade.
B. Roof Mount
Check building codes for weight distribution requirements. Unit operating weight is shown in Table 1.
Instructions continued on page 11.
4
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Refer to Fig. 4-6 for unit operating weights.
3. Remove boards at ends of unit and runners prior to rigging.
4. Rig by inserting hooks into unit base rails as shown. Use corner post from packaging to protect coil from damage. Use bumper boards for spreader bars on all units.
5. Weights do not include optional EconoMi$erIV. Add 90 lb (41 kg) for EconoMi$erIV weight.
6. Weights given are for aluminum evaporator and condenser coil plate fins.
CAUTION: All panels must be in place when rigging.
UNIT 580F
MAXIMUM
SHIPPING WEIGHT
lb kg ft-in. mm ft-in. mm 180 1875 850 6-11 210 1925 873 6-11 240 2085 923 6-11 300 2445 1109 6-11
Fig. 3 — Rigging Details
DIMENSIONS
AB
1
/22121 4-0 1219
1
/22121 3-2 964
1
/22121 3-4 1016
1
/22121 3-4 1016
5
(8) on each side for
16
/
5
so equipped.
Top: 6′-0(1829) to assure proper condenser fan operation.
surfaces.
Bottom: 14″ (356) to combustible surfaces (when not using curb).
Control box side: 3′-0″ (914) to ungrounded surfaces, non-combustible.
Control box side: 3′-6 (1067) to block or concrete walls, or other grounded
Local codes or jurisdiction may prevail.
exhaust as stated in Note #6, a removable fence or barricade requires no clear-
ance.
top cover drip edge.
7. With the exception of clearance for the condenser coil and the damper/power
8. Dimensions are from outside of corner post. Allow 0′-
(1219) if conditions permit coil removal from the top.
Rear: 7′-0″ (2134) for coil removal. This dimension can be reduced to 4′-0
4-0 (1219) to combustible surfaces, all four sides (includes between units).
Left side: 4-0(1219) for proper condenser coil airflow.
Front: 4′-0″ (1219) for control box access.
1. Refer to print for roof curb accessory dimensions.
2. Dimensions in [ ] are in millimeters.
3. Center of gravity.
4. Direction of airflow.
5. Ductwork to be attached to accessory roof curb only.
NOTES:
6. Minimum clearance:
Right side: 4-0(1219) for proper operation of damper and power exhaust if
Fig. 4 — Base Unit Dimensions — 580F180, 210
6
(8) on each side for
16
/
5
NOTES:
so equipped.
Top : 6-0(1829) to assure proper condenser fan operation.
surfaces.
Bottom: 14″ (356) to combustible surfaces (when not using curb).
Control box side: 3′-0″ (914) to ungrounded surfaces, non-combustible.
Control box side: 3′-6″ (1067) to block or concrete walls, or other grounded
Local codes or jurisdiction may prevail.
exhaust as stated in Note #6, a removable fence or barricade requires no clear-
ance.
top cover drip edge.
7. With the exception of clearance for the condenser coil and the damper/power
8. Dimensions are from outside of corner post. Allow 0′-
(1219) if conditions permit coil removal from the top.
Rear: 7-0 (2134) for coil removal. This dimension can be reduced to 4′-0
4-0 (1219) to combustible surfaces, all four sides (includes between units).
Left side: 4-0(1219) for proper condenser coil airflow.
Front: 4′-0″ (1219) for control box access.
1. Refer to print for roof curb accessory dimensions.
2. Dimensions in [ ] are in millimeters.
3. Center of gravity.
4. Direction of airflow.
5. Ductwork to be attached to accessory roof curb only.
6. Minimum clearance:
Right side: 4′-0(1219) for proper operation of damper and power exhaust if
Fig. 5 — Base Unit Dimensions — 580F240
7
(8) on eac h side for top cover
16
/
5
ditions permit coil removal from the top.
•Rear: 7′-0″ (2134) for coil re moval. This dimension can be reduced t o 4′-0″ (1219) if con-
•4′-0″ (1219) to combustible surfaces, all four sides (includes between units).
•Left side: 4′-0″ (1219) for proper condenser coil airflow.
• Right side: 4′-0″ (1219) for proper operation of damper and power exhaust if so eq uipped.
•Top: 6′-0″ (182 9) to assure proper condenser fan operation.
•Front: 4′-0″ (1219) for control box access.
• Bottom: 14(356) to combustible surfaces (when not using curb).
1. Refer to print for roof curb accessory dimensions.
2. Dim ensions in ( ) are in millimeters.
3. Center of Gravity.
4. Direction of airflow.
5. Ductwork to be attached to accessory roof curb only.
NOTES:
6. Minimum clearance:
• Con trol box side: 3′-0″ (914) to ungrounded surfaces, non-c ombustible.
drip edge.
• Con trol box side: 3′-6″ (1067) t o block or concrete walls, or other gro unded surfaces.
• Local codes or jurisdiction may prevail.
stated in Note #6, a removable fence or barricade requ ires no clearance.
9. The lower forklift brace must be removed prior to setting unit on roof curb.
7. With the exception of clearance for the condenser coil and the damper/power exhaust as
8. Dimensions are from outside of corner post. Allow 0′-
Fig. 6 — Base Unit Dimensions — 580F300
8
Table 1 — Physical Data
UNIT 580F 180 210 240 300
NOMINAL CAPACITY (tons) 15 18 20 25 OPERATING WEIGHT 1800 1850 1900 2270
EconoMi$erIV 90 90 90 90 Perfect Humidity™ Dehumidification Package 40 40 40 40
COMPRESSOR/MANUFACTURER Scroll, Copeland
Quantity...Model (Ckt 1, Ckt 2) Capacity Stages (%) 60, 40 55, 45 55, 45 50, 50
Number of Refrigerant Circuits 222 2 Oil (oz) (Ckt 1, Ckt 2) 85, 60 106, 81 106,106 136, 106
REFRIGERANT TYPE R-22
Expansion Device TXV Operating Charge (lb-oz) Circuit 1† 19-8 19-8 19-11 26-13 Circuit 2 13-8 19-2 13-14 25-10
CONDENSER COIL Cross-Hatched
Rows...Fins/in. 4...15 4...15 4...15 3...15 (2 coils) Total Face Area (sq ft) 21.7 21.7 21.7 43.4
CONDENSER FAN Propeller Type
Nominal Cfm 10,500 10,500 14,200 21,000 Quantity...Diameter (in.) 3...22 3...22 2...30 6...22 Motor Hp...Rpm Watts Input (Total) 1100 1100 3400 2200
EVAPORATOR COIL Cross-Hatched
Rows...Fins/in. 4...15 4...15 4...15 4...15 Total Face Area (sq ft) 17.5 17.5 17.5 17.5
EVAPORATOR FAN Centrifugal Type
Quantity...Size (in.) 2...12 x 12 2...12 x 12 2...12 x 12 2...12 x 12 Type D riv e Belt Belt Belt Belt Nominal Cfm 6000 7200 8000 10,000 Motor Hp 557.510 Motor Nominal Rpm 1745 1745 1745 1740
Maximum Continuous Bhp 6.13 5.90 Motor Frame Size 184T 184T 213T 215T
Nominal Rpm High/Low ——— — Fan Rpm Range Low-Medium Static 873-1021 910-1095 1002-1151 1066-1283
Motor Bearing Type Ball Ball Ball Ball
High Static 1025-1200 1069-1287 1193-1369 1332-1550
Maximum Allowable Rpm 1550 1550 1550 1550 Motor Pulley Pitch Diameter Low-Medium Static 4.9/5.9 4.9/5.9 5.4/6.6 4.9/5.9
Min/Max (in.) High Static 4.9/5.9 4.9/5.9 5.4/6.6 4.9/5.9 Nominal Motor Shaft Diameter (in.) 1 Fan Pulley Pitch Diameter (in.) Low-Medium Static 9.4 9.4 9.4 8.0
High Static 8.0 8.0 7.9 6.4 Nominal Fan Shaft Diameter (in.) 1 Belt, Quantity...Type...Length (in.) Low-Medium Static 1...BX...50 1...BX...50 1...BX...53 2...BX...50
High Static 1...BX...48 1...BX...48 1...BX...50 2...BX...47 Pulley Center Line Distance (in.) 13.3-14.8 13.3-14.8 14.6-15.4 14.6-15.4 Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Low-Medium Static 37 37 37 36
High Static 44 34 44 45 Movable Pulley Maximum Full Turns
From Closed Position 6** 6†† 6** 6†† Factory Pulley Setting 3.5 3.5 3.5 3.5 Factory Speed Setting (rpm) Low-Medium Static 965 1002 1120 1182
Fan Shaft Diameter at Pulley (in.) 1
High Static 1134 1178 1328 1470
LEGEND
Bhp — Brake Horsepower TXV — Thermostatic Expansion Valve
*The ZRU140KC compressor is a tandem compressor, consisting of a ZR72KC (25% total
capacity) and a ZR68KC (24% total capacity).
†Circuit 1 uses the lower portion of the condenser coil and lower portion of the evaporator coils;
and Circuit 2 uses the upper portion of both coils.
**Pulley has 6 turns. Due to belt and pulley size, movable pulley cannot be set to 0 to 1
open.
††Pulley has 6 turns. Due to belt and pulley size, movable pulley cannot be set to 0 to
open.
***Rollout switch is manual reset.
†††A Liquid Propane kit is available as an accessory.
¶The 580F300 unit requires 2-in. industrial-grade filters capable of handling face velocities up to
625 ft/min (such as American Air Filter no. 5700 or equivalent).
NOTE: The 580F units have a low-pressure switch (standard) located on the suction side.
1...ZR94KC,
1...ZR72KC
1
/2...1050
1
/
8
7
/
16
7
/
16
1...ZR108KC,
1...ZR94KC
3
Aluminum Pre-Coated, or Copper Plate Fins
/8-in. Copper Tubes, Aluminum Lanced,
1
/2...1050 1...1075
3
/8-in. Copper Tubes, Aluminum Lanced or
Copper Plate Fins, Face Split
1...ZR125KC,
1...ZR108KC
8.7 [208/230 v]
9.5 [460 v]
1
/2 turns
1
/2 turns
17/
17/
11/
8
16
16
13/
17/
17/
8
16
16
1...ZRU140KC,*
1...ZR144KC
1
/2...1050
10.2 [208/230 v]
11.8 [460 v]
13/
8
17/
16
17/
16
9
Table 1 — Physical Data (cont)
UNIT 580F
FURNACE SECTION
Rollout Switch Cutout Temp (F)*** 190 190 190 190
(Low Heat/High Heat)
180
(Low Heat/High Heat)
210
(Low Heat/High Heat)
240
(Low Heat/High Heat)
300
Burner Orifice Diameter (in. ...drill size)
Natural Gas Std 0.1285...30/0.136...29 0.1285...30/0.136...29 0.1285...30/0.136...29 0.1285...30/0.136...29
Thermostat Heat Anticipator Setting (amps)
208/230 v Stage 1 0.98 0.98 0.98 0.98
460 v Stage 1 0.80 0.80 0.80 0.80
Stage 2 0.44 0.44 0.44 0.44
Stage 2 0.44 0.44 0.44 0.44
Gas Input Stage 1 206,000/270,000 206,000/270,000 206,000/270,000 206,000/270,000
Stage 2 275,000/360,000 275,000/360,000 275,000/360,000 275,000/360,000 Efficiency (Steady-State) (%) 81 81 81 81 Temperature Rise Range 15-45/20-50 15-45/20-50 15-45/20-50 15-45/20-50 Manifold Pressure (in. wg)
Natural Gas Std 3.3 3.3 3.3 3.3
Liquid Propane††† Alt 3.3 3.3 3.3 3.3 Gas Valve Quantity 1111 Gas Valve Pressure Range
in. wg 5.5-13.5 5.5-13.5 5.5-13.5 5.5-13.5
psig 0.235-0.487 0.235-0.487 0.235-0.487 0.235-0.487 Field Gas Connection Size (in.-FPT)
3
/
4
3
/
4
3
/
4
3
/
4
HIGH-PRESSURE SWITCH (psig)
Cutout 426 Reset (Auto) 320
LOW-PRESSURE SWITCH (psig)
Cutout 27 Reset (Auto) 44
FREEZE PROTECTION THERMOSTAT (F)
Opens 30 ± 5 Closes 45 ± 5
OUTDOOR-AIR INLET SCREENS Cleanable
Quantity...Size (in.) 2...20 x 25 x 1
1...20 x 20 x 1
RETURN-AIR FILTERS Throwaway¶
Quantity...Size (in.) 4...20 x 20 x 2
1
POWER EXHAUST
/2 Hp, 208/230-460 v Motor Direct Drive, Propeller-Fan (Factory-Wired for 460 v)
4...16 x 20 x 2
LEGEND
Bhp — Brake Horsepower TXV — Thermostatic Expansion Valve
*The ZRU140KC compressor is a tandem compressor, consisting of a ZR72KC (25% total capac-
ity) and a ZR68KC (24% total capacity).
†Circuit 1 uses the lower portion of the condenser coil and lower portion of the evaporator coils;
and Circuit 2 uses the upper portion of both coils.
**Pulley has 6 turns. Due to belt and pulley size, movable pulley cannot be set to 0 to 1
open.
††Pulley has 6 turns. Due to belt and pulley size, movable pulley cannot be set to 0 to
1
/2 turns
1
/2 turns
open.
***Rollout switch is manual reset.
†††A Liquid Propane kit is available as an accessory.
¶The 580F300 unit requires 2-in. industrial-grade filters capable of handling face velocities up to
625 ft/min (such as American Air Filter no. 5700 or equivalent).
NOTE: The 580F units have a low-pressure switch (standard) located on the suction side.
10
III. STEP 3 — FIELD FABRICATE DUCTWORK
Secure all ducts to building structure. Use flexible duct con­nectors between unit and ducts as required. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and m asti c i n acc ordance with applica­ble codes.
Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier.
IV. STEP 4 — MAKE UNIT DUCT CONNECTIONS
Unit is shipped for thru-the-bottom duct connections. Duct­work openings are shown in Fig. 1 and 4-6. Duct connections are shown in Fig. 7. Field-fabricated concentric ductwork may be connected as shown in Fig. 8 and 9. Attach all duct­work to roof curb and roof curb basepans.
V. STEP 5 — INSTALL FLUE HOOD AND WIND BAFFLE
Flue hood and wind baffle are shipped secured under main control box. To install, secure flue hood to access panel. See Fig. 10. The wind baffle is then installed over the flue hood.
NOTE: Whe n properly insta lled, flue hoo d will line up with combustion fan housing. See Fig. 11.
VI. STEP 6 — TRAP CONDENSATE DRAIN
See Fig. 12 for drain location. One
3
/4-in. half coupling is pro­vided inside unit evaporator section for condensate drain connection. An 8 diameter pipe nipple, coupled to standard
1
/2-in. x 3/4-in. diameter and 2-in. x 3/4-in.
3
/4-in. diameter elbows, provide a straight path down through hole in unit base rails (see Fig. 13). A trap at least 4-in. de ep must be used.
NOTE: Do not drill in this area; damage to basepan may result in water leak.
Fig. 7 — Air Distribution — Thru-the-Bottom
NOTE: Dimensions A, A, B, and Bare obtained from field-supplied
ceiling diffuser.
Shaded areas indicate block-off panels.
Fig. 9 — Concentric Duct Details
WIND BAFFLE
NOTE: Do not drill in this area; damage to basepan may result in water leak.
Fig. 8 — Concentric Duct Air Distribution
Fig. 10 — Flue Hood Location
11
INDUCED DRAFT MOTOR
VII. STEP 7 — ORIFICE CHANGE
This unit is factory assembled for heating operation using natural gas at an elevation from sea level to 2000 ft. This unit uses orifice type LH32RFn nn, wher e “nnn” i ndicates th e orifice size based on drill size diameter in thousands of an inch.
A. High Elevation (Above 2000 ft)
Use accessory high altitude kit when installing this unit at an elevation of 2000 to 7000 ft. For elevations above 7000 ft, refer to Table 2 to identify the correct orifice size for the elevation. See Table 3 for the nu mber of orifi ces re quired for each unit size. Purc hase the se orifi ces f rom your lo cal Bryant dealer. Fo llow in structions in acc essory I nstallati on Ins truc­tions to install the correct orif ices.
Table 2 — Altitude Compensation*
COMBUSTION FAN HOUSING
MAIN BURNER SECTION
HEAT EXCHANGER SECTION
Fig. 11 — Combustion Fan Housing Location
3/4" FPT DRAIN CONNECTION
1-3/8" DRAIN HOLE
Fig. 12 — Condensate Drain Details (580F180 Shown)
ELEVATION (ft)
0-1,999 30 29
2,000 30 29 3,000 31 30 4,000 31 30 5,000 31 30 6,000 31 30 7,000 32 31 8,000 32 31 9,000 33 31
10,000 35 32
*As the height above sea level increases, there is less oxygen per cubic
foot of air. Therefore, heat input rate should be reduced at higher alti­tudes. Includes a 4% input reduction per each 1000 ft.
†Orifices available through your Bryant dealer.
NATURAL GAS ORIFICE†
Low Heat High Heat
Table 3 — Orifice Quantity
UNIT ORIFICE QUANTITY 580F180 Low Heat 5 580F210 Low Heat,
580F240 Low Heat, 580F300 Low Heat, 580F180 High Heat
580F210 High Heat, 580F240 High Heat, 580F300 High Heat
6
7
B. Conversion To LP (Liquid Propane) Gas
Use accessory LP gas conversion kit when converting this unit for use with LP fuel usage for elevations up to 7000 ft. For elevations above 7000 ft, refer to Table 4 to identify the correct orifice size for the elevation. See Table 3 for the number of orifices required for each unit size. Purchase these orifices from your local Bryant deale r. Follow instructions in acce ssory Installation Instructions to install the corre ct orific es.
Table 4 — LP Gas Conversion*
Fig. 13 — Condensate Drain Piping Details
ELEVATION (ft) LP GAS ORIFICE†
0-1,999 36
2,000 37 3,000 38 4,000 38 5,000 39 6,000 40 7,000 41 8,000 41 9,000 42
10,000 43
*As the height above sea level increases, there is less oxygen per
cubic foot of air. Therefore, heat input rate should be reduced at higher altitudes. Includes a 4% input reduction per each 1000 ft.
†Orifices available through your Bryant dealer.
12
VIII. STEP 8 — INSTALL GAS PIPING
Unit is equipped for use with natural gas. Installation must conform with local bu ilding codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1.
Install field-supplied manual gas shutoff valve with a
1
/8-in. NPT pressure tap for test gage co nnection at unit. Field gas piping must include sediment trap and union. See Fig. 14.
WARNING: Do not pressure test gas supply while connected to unit. Always disconnect union before servicing.
IMPORTANT: Natural gas pressure at unit gas connection must not be less than 5.5 in. wg or greater than 13.5 in. wg.
Size gas-supply piping for 0.5-in. wg maximum pressure drop. Do not use supply pipe smaller than unit gas connection.
Fig. 14 — Field Gas Piping
IX. STEP 9 — MAKE ELECTRICAL CONNECTIONS
A. Field Power Supply
Unit is factory wired for voltage shown on unit nameplate. When installing units, provide a disconnect per NEC
(National Electrical Code) requirements of adequate size (Table 5).
All field wiring must comply with NEC and local requirements.
Route power and ground lines through control box end panel or unit basepan (see Fig. 4-6) to connections as shown on unit wiring diagram and Fig. 15.
CAUTION: The correct power phasing is critical in the operation of the scroll compressors. An incorrect phasing will cause the compressor to rotate in the wrong direction. This may lead to premature compres­sor failure.
WARNING: The unit must be electrically grounded in accordance with local codes and NEC ANSI/ NF PA 70 (National Fire Protection Association).
Field wiring must conform to temperature limitations for type ‘‘T’’ wire. All field wiring must comply with NEC and local require ments.
Transformer no. 1 is wi r ed for 230 -v unit. If 2 08/230-v unit is to be run with 208-v power supply, the transfo rmer must be rewired as follows:
1. Remove cap from red (208 v) wire.
2. Remove cap from orange (230 v) spliced wire.
3. Replace orange wire with red wire.
4. Recap both wires.
IMPORTANT: BE CERTAIN UNUSED WIRES ARE CAPPED. Failure to do so may damage the transformers.
Operating voltage to compressor must be within voltage range indicated on unit nameplate. On 3-phase units, volt­ages between phases must be balanced within 2%.
Unit failure as a res ult of ope ra tio n o n imp ro per line volt age or excessive phase imbalance constitutes abuse and may cause damage to electrical components.
B. Field Control Wiring
Install a Bryant-approv ed acces sory ther mosta t assemb ly (or light commercial Thermidistat™ device for units equipped with Perfect Humidity™ option) according to the installation instructions included with accessory. Locate thermostat assembly on a solid interior wall in the conditioned space to sense average temperature.
Route thermostat cable or equivalent single leads of colored wire from subbase terminals through conduit in uni t to low­voltage connections as shown on unit label wiring diagram and in Fig. 16.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected a t the thermos tat and wi ll req uire a j unction box and s plice a t the thermostat.
Set heat anticipator settings as follows:
VOLTAGE W1 W2
208/230 0.98 0.44
460 0.80 0.44
Settings may be changed slightly to provide a greater degree of comfort for a particular installation.
C. Optional Non-Fused Disconnect
On units with the optional non-fused disconnect, incoming power will be wired into the disconnect switch. Refer to Fig. 17 for wiring for 100 and 200 amp disconnect switches. Units with an MOCP (maximum overcurrent protection) under 100 will use the 100 amp disconnect switch. Units with an MOCP over 100 will use the 200 amp disconnect switch. Refer to the applicable disconnect wiring diagram.
To prevent breakage during shipping, the disconnect handle and shaft are shipped and packaged inside the unit control box. Install the disconnec t handle before unit operation. To install the handle and shaft, perform the following procedure:
1. Open the co nt ro l b ox do or and r e mo ve t he handle and shaft from shipping location.
2. Loosen the Allen bolt located on the disconnect switch. The bolt is locat ed on the sq uare hole a nd is used to hold the shaft in place. The shaft cannot be inserted until the Allen bo lt is moved.
3. Insert the disconnect shaft into the square hole on the disconnect switch. The end of the shaft is spe­cially cut and the shaft can only be inserted in the correct orientation.
13
D. Optional Convenience Outlet
On units with optional convenience outlet, a 115-v GFI (ground fault interrupt) convenience outl et rece ptacle is pr o­vided for field wiring. Field wiring should be run thro ugh th e
7
/8-in. knockout provided in the basepan near the return air
opening.
THERMOSTAT ASSEMBLY
REMOVABLE JUMPER
RC
RH
Y1 Y2
W1
W2
GC
L
X
LEGEND
EQUIP — Equipment GND Ground NEC National Electrical Code TB Te rm i n al B o a r d
NOTE: The maximum wire size for TB1 is 2/0.
Fig. 15 — Field Power Wiring Connections
4. Tighten the Allen bolt to lock the shaft into position.
5. Close the control box door.
6. Attach the handle to the external access door with the two screws provided. When the handle is in the ON position, the handle will be vertical. When the handle is in the OFF position, the handle will be horizontal.
7. Turn the handle to the OFF position and close the door. The handle should fit over the end of the sha ft when the door is closed.
8. The handle must be in the OFF position to open the control box door.
R
RED
Y1
BLU
PNK
W1Y2
ORN
W2
VIO
C
BRN
X
WHT
G
BLK
Fig. 16 — Field Control Thermostat Wiring
6T3 4T2 2T1 LOAD
5L3 3L2 1L1 LINE
NOTE: The disconnect takes the place of TB-1 as shown on the unit wiring diagram label and the component arrangement label.
Fig. 17 — Optional Non-Fused Disconnect Wiring
14
Table 5 — Electrical Data
UNIT 580F
LEGEND FLA Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration IFM Indoor (Evaporator) Fan Motor LRA Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC National Electrical Code OFM — Outdoor (Condenser) Fan Motor RLA Rated Load Amps
*Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load
2. Unbalanced 3-Phase Supply Voltage
NOMINAL VOLTAGE
(3 Ph, 60 Hz)
208/230 187 253 32.1 195 20.7 156 3 0.5 1.7 5.0 15.8/15.8
180
210
240
300
equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
imbalance.
460 414 508 16.4 95 10 70 3 0.5 0.8 5.0 7.9
208/230 187 253 30.1 225 28.8 195 3 0.5 1.7 5.0 15.8/15.8
460 414 508 15.5 114 14.7 95 3 0.5 0.8 5.0 7.9
208/230 187 253 42 239 33.6 225 2 1 6.6 7.5 25.0/25.0
460 414 508 19.2 125 17.3 114 2 1 3.3 7.5 13.0
208/230 187.2 253 20.7 156 20.7 156 47.1 245 6 0.5 1.7 10.0 28.0/28.0
460 414 508 10 75 10 75 19.6 125 6 0.5 0.8 10.0 14.6
VO LTAG E
RANGE
Min Max RLA LRA RLA LRA RLA LRA Qty Hp FLA (ea) Hp FLA FLA LRA FLA MCA MOCP*
Use the following formula to determine the percent voltage
COMPRESSOR
No. 1 No. 1A No. 2
OFM IFM
% Voltage Imbalance
= 100 x
EXAMPLE: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
Maximum deviation is 7 v. Determine percent voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, con­tact your local electric utility company immediately.
max voltage deviation from average voltage
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v
POWER
EXHAUST
0.57 82/82 110/110
4.6 18.8 0.57 86/86 110/110 — 0.30 41 50
2.3 6.0 0.30 43 50 — 0.57 87/87 110/110
4.6 18.8 0.57 92/92 110/110 — 0.30 44 50
2.3 6.0 0.30 47 60 — 0.57 124/124 150/150
4.6 18.8 0.57 129/129 150/150 — 0.30 61 80
2.3 6.0 0.30 63 80 — 0.57 138/138 175/175
4.6 18.8 0.57 143/143 150/175 — 0.30 64 80
2.3 6 0.30 66 80
average voltage
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
= 1.53%
=
= 457
7
457
COMBUSTION
FAN MOTOR
452 + 464 + 455
3
1371
3
POWER SUPPLY
X. STEP 10 — MAKE OUTDOOR-AIR INLET ADJUST­MENTS
A. Manual Outdoor-Air Damper
All units (except those equipped with a factory-installed EconoMi$erIV ) h ave a ma nual out door-air damper to provide ventilation air.
Damper can be preset to admit up to 25% outdoor air into return-air compartment. To adjust, loosen securing screws and move damper to desired setting, then retighten screws to secure damper (Fig. 18).
XI. STEP 11 — INSTALL OUTDOOR-AIR HOOD
The outdoor-air hood is common to 25% air ventilation and EconoMi$erIV. If EconoMi$erIV is factory installed, all electrical connections have been made and adjusted at the factory. Assemble and install hood in the field.
Fig. 18 — Standard 25% Outdoor-Air Section Details
15
IMPORTANT: If the unit is equipped with the optional EconoMi$erIV component, move the outdoor-air tempera­ture sensor prior to installing the outdoor-air hood. See the Optional EconoMi$erIV section for more inform ation.
NOTE: The hood top panel, upper and lower filter retainers, hood drain pan, baffle (size 300), and filter support bracket are secured opposite the condenser end of the unit. The screens, hood side panels, remaining section of filter support bracket, seal strip, and hardware are in a package located inside the return-air filter access panel (Fig. 19).
1. Attach seal strip to upper filter retainer. See Fig. 20.
2. Assemble hood top panel, side panels, upper filter retainer, and drain pan (see Fig. 21).
3. Secure lower filter retainer and support bracket to unit. See Fig. 21. Leave screws loose on size 300 units.
4. Slide baffle (size 300) behind lower filter retainer and tighten screws.
5. Loosen sheet metal screws for top pa nel of base unit located above o utdoor-air inlet opening, and remove screws for hood side panels located on the sides of the outdoor-air inlet opening.
6. Match notches in hood top panel to unit top panel screws. Inser t hood flange betw een top panel flan ge and unit. Tighten screws.
7. Hold hood side panel flanges flat against unit, and install screws removed in Step 5.
8. Insert outdoor-air inlet screens and spacer in channel created by lower filter retainer and filter support bracket.
9. Attach remaining section of filter support bracket.
XII. STEP 12 — INSTALL ALL ACCESSORIES
After all the factory-installed options have been adjusted, install all field-installed accessories. Refer to the accessory installation instructions included with each accessory.
A. Motormaster® I Control (–20 F) Installation (580F180 and 210 Only)
Install Field-Fabricated Wind Baffles Wind baffles must be field-fabricated for all units to ensure
proper cooling cycle operation at low ambient temperatures. See Fig. 22 for baffle details. Use 20-gage, galvanized sheet metal, or similar corrosion-resistant metal for baffles. Use field-supplied screws to attach baffles to uni t. Scre ws shou ld
1
be
/4-in. diameter and 5/8-in. long. Drill required screw holes
for mounting baffles.
Fig. 19 — Outdoor-Air Hood Component Location
Fig. 20 — Seal Strip Location
BAFFLE
LOWER FILTER RETAINER
FILTER SUPPORT BRACKET
CAUTION: To avoid damage to the refrigerant coils and electrical components, use recommended screw sizes only. Use care when drilling holes.
Install Motormaster I Controls One Motormaster I control is required on size 180 and 210
units. The Motormaster I control must be used in conjunction with the accessory fan motor sequencing kit and winter start kit (purchased separately). The Motormaster I device controls outdoor fan no. 1 while outdoor fans no. 2 and 3 are sequenced off by the accessory fan motor sequencing kit.
Accessory Fan Motor Sequencing Kit — Install the access ory fan motor sequencing kit per instruction supplied with acces­sory (purchased separately).
Winter Start Time Delay Relay Kit — Install the kit per the instructions supplied with the accessory (purchased separately).
Sensor Assembl y — Install the sensor assembly in the loca­tion shown in Fig. 23.
HOOD SIDE
HOOD TOP PANEL
HOOD DRAIN PAN
UPPER FILTER RETAINER
NOTE: The outdoor-air hood comes with a baffle which is used on size 300 units only, discard baffle for size 180-240 units.
PANELS (2)
FILTER SUPPORT BRACKET
Fig. 21 — Outdoor-Air Hood Details
16
BAFFLE (300 ONLY)
LOWER FILTER RETAINER
Loading...
+ 36 hidden pages