Bryant 577D-A User Manual

577D----A EVOLUTIONR 15 SEER SINGLE--PACKAGED AIR CONDITIONER AND GAS FURNACE SYSTEM WITH PURONR (R--410A) REFRIGERANT SINGLE PHASE 2--5 NOMINAL TONS (SIZES 24--60)
Installation Instructions
!
CAUTION
Failure to follow this caution may result in improper unit operation. OAT sensor must be field installed. See Accessory Installation for more details.
!
CAUTION
Failure to follow this caution may result in improper unit operation. This Evolutionr unit is designed for use with an Evolution User Interface.
NOTE: Read the entire instruction manual before starting the installation.
TABLE OF CONTENTS
PAGE
SAFETY CONSIDERATIONS 2.........................
INTRODUCTION 2...................................
RECEIVING AND INSTALLATION 2--13.................
Check Equipment 2..................................
Identify Unit 2....................................
Inspect Shipment 2.................................
Provide Unit Support 2...............................
Roof Curb 2......................................
Slab Mount 3.....................................
Provide Clearances 3.................................
Rig and Place Unit 3.................................
Inspection 3......................................
Rigging/Lifting of Unit 9............................
Select and Install Ductwork 9...........................
Configuring Units for Downflow (Vertical) Discharge 10...
Provide for Condensate Disposal 10.....................
Install Flue Hood 11..................................
Install Gas Piping 11.................................
Install Electrical Connections 12........................
High--Voltage Connections 12........................
Routing Power Leads Into Unit 12.....................
Connecting Ground Lead to Ground Screw 12...........
Routing Control Power Wires 13.....................
Accessory Installation 13............................
Special Procedures for 208 -- v Operation 13..............
PRE-- START--UP 16...................................
START--UP 16--29.....................................
Unit Start--Up and Troubleshooting 16...................
Sequence of Operation 23.............................
Check for Refrigerant Leaks 28.........................
Start--Up Adjustments 28..............................
A09032
Fig. 1 -- Unit 577D----A
Checking Cooling and Heating Control Operation 28......
Checking and Adjusting Refrigerant Charge 28...........
Refrigerant Charge 29..............................
No Charge 29.....................................
Low Charge Cooling 29.............................
To Use Cooling Charging Charts 29....................
Non--Communicating Emergency Cooling/Heating Mode 29..
MAINTENANCE 31--34................................
Air Filter 31........................................
Indoor Fan and Motor 31..............................
Inducer Blower 31...................................
Limit Switch 31.....................................
Burner Ignition 31...................................
Main B urners 31....................................
Inducer Pressure Switch 32............................
Outdoor Coil, Indoor Coil, and Condensate Drain Pan 32.....
Outdoor Fan 32.....................................
Electrical Controls and Wiring 32.......................
Refrigerant Circuit 33.................................
Indoor Airflow 33...................................
Pressure Switches 33.................................
L o s s -- o f -- C h a r g e S w i t c h 3 3............................
High--Pressure Switches 33............................
Copeland Scroll Compressor (Puron
Refrigerant System 33................................
Refrigerant 33....................................
Compressor Oil 33.................................
Servicing Systems on Roofs with Synthetic Materials 33....
Liquid-- Line Filter Drier 34..........................
Puron (R--410A) Refrigerant Charging 34...............
TROUBLESHOOTING 34..............................
FINAL CHECKS 35...................................
CARE AND MAINTENANCE 35........................
START--UP CHECKLIST 39............................
®
Refrigerant) 33........
1
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing. Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. consult local building codes, the current editions of the National Fuel Gas Code (NFGC) NFPA 54/ANSI Z223.1, and the National Electrical Code (NEC) NFPA 70. In Canada refer to the current editions of the National Standards of Canada CAN/CSA--B149.1 and .2 Natural Gas and Propane Installation codes, and Canadian Electrical Code CSA C22.1
Recognize safety information. This is the safety--alert symbol When you see this symbol on the unit and in instructions or manu­als, be alert to the potential for personal injury. Understand these
577D-- --A
signal words: DANGER, WARNING, and CAUTION. Th ese words are u sed with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in per­sonal injury or death. CAUTION is used to identify unsafe practic­es which may result in minor personal injury or product and prop­erty damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing system, always turn off main power to system and install lockout tag. There may be more than one disconnect switch. Turn off accessory heater power switch if applicable.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal injury or equipment damage.
Puron (R--410A) systems operate at higher pressures than standard R-- 22 systems. DO NOT use R--22 service equipment or components on Puron (R--410A) equipment. Ensure service equipment is rated for Puron (R--410A).
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
When removing access panels or performing maintenance functions inside your unit, be aware of sharp sheet metal parts and screws. Although special care is taken to reduce sharp edges to a minimum, be extremely careful when handling parts or reaching into the unit.
INTRODUCTION
The 577D----A packaged unit is a fully self--contained combination Category I gas heating/electric air conditioner designed for outdoor installation (See Fig. 1). Standard units are shipped in a horizontal--discharge configuration for installation on a rooftop, or on cement slab (See Fig. 4 for roof curb dimensions). Standard
units can be converted to downflow (vertical) discharge configurations for rooftop applications. Models with an N in the thirteenth position of the model number are dedicated Low NOx units designed for California installations. These models meet the California maximum oxides of nitrogen (NOx) emissions requirements of 40 nanograms/joule or less as shipped from the factory and must be installed in California Air Quality Management Districts or any other regions in North America where a Low NOx rule exists. In gas heating mode, this unit is designed for a minimum continuous return--air temperature of 55_F(13_C) db and a maximum continuous return--air temperature of 80_F(27_C) db. Failure to follow these return--air temperature limits may affect reliability of heat exchangers, motors, and other components. NOTE: Low NOx requirements apply only to natural gas installations.
RECEIVING AND INSTALLATION
Check Equipment
IDENTIFY UNIT The unit model number and serial number are printed on the unit
.
informative plate. Check this information against shipping papers. INSPECT SHIPMENT Inspect for shipping damage before removing packaging material. If unit appears to be damaged or is torn loose from its anchorage, have it examined by transportation inspectors before removal. Forward claim papers directly to transportation company. Manufacturer is not responsible for any damage incurred in transit. Check all items against shipping list. Immediately notify the nearest distributor office if any item is missing. To prevent loss or damage, leave all parts in original packages until installation.
If the unit is to be mounted on a curb in a downflow application, review “Configuring Units for Downflow Discharge” to determine which method is to be used to remove the downflow panels before rigging and lifting into place. The panel removal process may require the unit to be on the ground.
Provide Unit Support
IMPORTANT: The unit must be secured to the curb by installing
screws through the bottom of the curb flange and into the unit base rails. When installing large base units onto the common curb, the screws must be installed before allowing the full weight of the unit to rest on the curb. A minimum of six screws are required for large base units. Failure to secure unit properly could result in an unstable unit. See Warning near Rigging/Lifting information and accessory curb instructions for more details. For hurricane tie downs, contact distributor for details and PE (Professional Engineering) Certificate, if required. ROOF CURB Install accessory roof curb in accordance with instructions shipped with curb (See Fig. 4). Install insulation, cant strips, roofing, and flashing. Ductwork must be attached to curb. IMPORTANT: The gasketing of the unit to the roof curb is critical for a water tight seal. Install gasketing material supplied with the roof curb. Improperly applied gasketing also can result in air leaks and poor unit performance. Curb should be level to within 1/4 in. (6.35 m) (See Fig. 2). This is necessary for unit drain to function properly. Refer to accessory roof curb installation instructions for additional information as required.
2
A
C
MAXIMUM ALLOWABLE
B
A-B
(6.35)
1/4
Fig. 2 -- Unit Leveling Tolerances
Installation on older “G” series roof curbs.
Two accessory kits are available to aid in installing a new “G” series unit on an old “G” roof curb.
1. Accessory kit number CPADCURB001A00, (small chassis) and accessory kit number CPADCURB002A00, (large chassis) includes roof curb adapter and gaskets for the perimeter seal and duct openings. No additional modifications to the curb are required when using this kit.
2. An alternative to the adapter curb is to modify the existing curb by removing the outer horizontal flange and use accessory kit number CPGSKTKIT001A00 which includes spacer blocks (for easy alignment to existing curb) and gaskets for the perimeter seal and duct openings. This kit is used when existing curb is modified by removing outer horizontal flange.
!
UNIT/STRUCTURAL DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Ensure there is sufficient clearance for saw blade when cutting the outer horizontal flange of the roof curb so there is no damage to the roof or flashing.
CAUTION
OPTIONAL
RETURN
AIR
OPENING
DIFFERENCE in. (mm)
1/4
B-C
(6.35)
A-C
1/4
OPTIONAL
SUPPLY
AIR
OPENING
(6.35)
A07925
Provide Clearances
The required minimum service clearances are shown in Fig. 5 and
6. Adequate ventilation and outdoor air must be provided. The outdoor fan draws air through the outdoor coil and discharges it through the top fan grille. Be sure that the fan discharge does not recirculate to the outdoor coil. Do not locate the unit in either a corner or under an overhead obstruction. The minimum clearance under a partial overhang (such as a normal house overhang) is 48 in. (1219 mm) above the unit top. The maximum horizontal extension of a partial overhang must not exceed 48 in. (1219 mm).
IMPORTANT: Do not restrict outdoor airflow. An air restriction at either the outdoor--air inlet or the fan discharge may be detrimental to compressor life.
Do not place the unit where water, ice, or snow from an overhang or roof will damage or flood the unit. Do not install the unit on carpeting or other combustible materials. Slab-- mounted units should be at least 4 in. (102 mm) above the highest expected water and runoff levels. Do not use unit if it has been under water.
Rig and Place Unit
Rigging and handling of this equipment can be hazardous for many reasons due to the installation location (roofs, elevated structures, etc.).
Only trained, qualified crane operators and ground support staff should handle and install this equipment.
When working with this equipment, observe precautions in the literature, on tags, stickers, and labels attached to the equipment, and any other safety precautions that might apply.
Training for operators of the lifting equipment should include, but not be limited to, the following:
1. Application of the lifter to the load, and adjustment of the lifts to adapt to various sizes or kinds of loads.
2. Instruction in any special operation or precaution.
3. Condition of the load as it relates to operation of the lifting kit, such as balance, temperature, etc.
Follow all applicable safety codes. Wear safety shoes and work gloves.
Inspection
Prior to initial use, and at monthly intervals, all rigging shackles, clevis pins, and straps should be visually inspected for any damage, evidence of wear, structural deformation, or cracks. Particular attention should be paid to excessive wear at hoist hooking points and load support areas. Materials showing any kind of wear in these areas must not be used and should be discarded.
577D-- --A
!
WARNING
(50.8mm)
EVAP. COIL COND. COIL
A07926
Fig. 3 -- Slab Mounting Detail
SLAB MOUNT Place the unit on a solid, level concrete pad that is a minimum of 4
in. (102 mm) thick with 2 in. (51 mm) above grade. The slab should extend approximately 2 in. (51 mm) beyond the casing on all 4 sides of the unit (See Fig. 3). Do not secure the unit to the slab except when required by local codes.
UNIT FALLING HAZARD
Failure to follow this warning could result in personal injury or death.
Never stand beneath rigged units or lift over people.
!
WARNING
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal injury/death or property damage.
When straps are taut, the clevis should be a minimum of 36 in. (914 mm) above the unit top cover.
3
HVAC unit base rails
Anchor screw
Flashing field supplied
Roofing material field supplied
Cant strip field supplied
HVAC unit basepan
Sealing Gasket
Roofcurb
Wood nailer*
Roofcurb*
Insulation (field supplied)
B
G
C
F
A
H
D
Dashed lines show cross support location for large basepan units.
E
A09413
*Provided with roofcurb
SMALL/COMMON CURB
A09090
ROOF CURB DETAIL
577D-- --A
B
C
G
SUPPLY
AIR
SMALL BASE UNIT
H
A
F
RETURN
E
AIR
LARGE BASE UNIT
D
UNIT PLACEMENT ON
LARGE CURB
A09415
COMMON CURB
SMALL OR LARGE BASE UNIT
A09094
A
UNIT SIZE
Small
or
Large
Large
NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Roof curb is made of 16--gauge steel.
4. Attach ductwork to curb (flanges of duct rest on curb).
5. Insulated panels: 1--in. (25.4 mm) thick fiberglass 1 lb. density.
CATALOG
NUMBER
CPRFCURB010A00
CPRFCURB011A00
CPRFCURB012A00
CPRFCURB013A00
(mm)
(279)
(356)
(279)
(356)
B (small / common
IN.
11
14
11
14
base)
IN. (mm)*
B(large
base)
IN. (mm)*
10 (254)
14 (356)
14 (356)
Fig. 4 -- Roof Curb Dimensions
A09414
C
IN.
(mm)
16
(406)
D
IN.
(mm)
47.8
(1214)
E
IN.
(mm)
32.4
(822)
43.9
(1116)
F
IN.
(mm)
2.7 (69)
G
IN. (mm)HIN. (mm)
30.6 (778)
46.1 (1170)
42.2 (1072)
4
577D-- --A
Fig. 5 -- 577D----A24--30 Unit Dimensions
5
A09556
577D-- --A
Fig. 6 -- 577D----A36--60 Unit Dimensions
6
A09557
Table 1 – Physical Data -- Unit 577D----A
UNIT SIZE 24040 24060 30040 30060 36060 36090 42060 42090
NOMINAL COOLING CAPACITY (ton) 2 2 2 --- 1 / 2 2 --- 1 / 2 3 3 3 --- 1 / 2 3 --- 1 / 2
NOMINAL HEATING CAPACITY (Btu) 40,000 60,000 40,000 60,000 60,000 90,000 60,000 90,000
SHIPPING WEIGHT (lb)
COMPRESSORS
Quantity
REFRIGERANT : PURON (R --- 410A)
Quantity (lb)
REFRIGERANT METERING DEVICE TXV
OUTDOOR COIL
Rows...Fins/in. Face Area (sq ft )
OUTDOOR FAN
Nominal Cfm Diameter (in.)
Motor Hp (Rpm)
INDOOR COIL
Rows...Fins/in. Face Area (sq ft )
(kg)
Size 2Ton 2Ton 3Ton 3Ton 3Ton 3Ton 4Ton 4Ton
(mm)
(kg)
INDOOR FAN
Nominal Airflow (Cfm) Comfort Variable based on Comfort Roll back (see User Interface instructions for more information). Efficiency 700 700 875 875 1050 1050 1225 1225 Max 800 800 1000 1000 1200 1200 1400 1400
Furnace (gas ht.) airflow ---Low Stage 475 727 475 727 745 875 745 875 Furnace (gas ht.) airflow ---High Stage 844 1120 844 1120 1120 1410 1120 1410
Size (in.)
(mm)
Motor HP 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4
FURNACE SECTION* Burner Orifice No. (Qty...Drill Size)
Natural Gas (Factory Installed) Propane Gas
HIGH--- PRESSURE SWITCH (psig)
C u t --- o u t
Reset (Auto)
HIGH--- PRESSURE SWITCH 2 (psig)
(Compressor Solenoid) C u t --- o u t Reset (Auto)
L O S S --- O F --- C H A R G E / LOW---PRESSURE SWITCH
(Liquid Line) (psig) C u t --- o u t
Reset (auto)
RETURN-- -AIR FILTERS Throwaway
(in.)
(mm)
Continued next page.
426 193
10.1
4.6
2...21
13.6
2700
22
559
1/8 (825)
3...17
3.7
10x10
254x254
2...44
2...55
431 196
10.1
4.6
2...21
13.6
2700
22
559
1/8 (825)
3...17
3.7
10x10
254x254
3...44
3...55
20x24x1
508x610x25
433 196
11.3
5.1
2...21
15.3
2700
22
559
1/8 (825)
3...17
3.7
10x10
254x254
2...44
2...55
438 199
2 --- S t a g e S c r o l l
11.3
5.1
2...21
15.3
2700
22
559
1/8 (825)
3...17
3.7
10x10
254x254
3...44
3...55
1
670 ±10
470 ± 25
565 ± 15 455 ± 15
23 ± 5 55 ± 5
522 237
9.5
4.3
2...21
17.5
2800
22
559
1/8 (825)
3...17
4.7
11x10
279x254
3...44
3...55
24x30x1
610x762x25
530 240
9.5
4.3
2...21
17.5
2800
22
559
1/8 (825)
3...17
4.7
11x10
279x254
3...38
3...53
544 247
13.8
6.3
2...21
19.4
2800
22
559
1/8 (825)
3...17
4.7
11x10
279x254
3...44
3...55
24x36x1
610x914x25
552 250
13.8
6.3
2...21
19.4
2800
22
559
1/8 (825)
3...17
4.7
11x10
279x254
3...38
3...53
577D-- --A
7
UNIT SIZE 48090 48115 48130 60090 60115 60130
Table 1—Physical Data (Con’t) -- Unit 577D----A
NOMINAL COOLING CAPACITY (ton) 4 4 4 5 5 5
NOMINAL HEATING CAPACITY (Btu) 90,000 115,000 130,000 90,000 115,000 130,000
SHIPPING WEIGHT (lb)
COMPRESSORS
Quantity
REFRIGERANT : PURON (R --- 410A)
Quantity (lb)
REFRIGERANT METERING DEVICE TXV
Size 4Ton 4Ton 4Ton 5Ton 5Ton 5Ton
OUTDOOR FAN
Nominal Cfm Diameter (in.)
Motor Hp (Rpm)
OUTDOOR COIL
Rows...Fins/in. Face Area (sq ft )
INDOOR COIL
Rows...Fins/in. Face Area (sq ft )
INDOOR FAN
Nominal Airflow (Cfm)
Comfort Variable based on Comfort Roll back (see User Interface instructions for more information).
577D-- --A
Efficiency 1400 1400 1400 1750 1750 1750
Max 1600 1600 1600 2000 2000 2000
Furnace (gas ht.) airflow--- Low Stage 815 1215 1255 845 1215 1255
Furnace (gas ht.) airflow--- High Stage 1385 1885 1875 1300 1910 1920
Size (in.)
Motor HP (RPM) 3/4 3/4 3/4 1 1 1
FURNACE SECTION* Burner Orifice No. (Qty...Drill Size)
Natural Gas (Factory Installed)
Propane Gas
HIGH--- PRESSURE SWITCH (psig)
C u t --- o u t
Reset (Auto)
HIGH--- PRESSURE SWITCH 2 (psig)
(Compressor Solenoid)
C u t --- o u t
Reset (Auto)
L O S S --- O F --- C H A R G E / LOW---PRESSURE SWITCH
(Liquid Line) (psig) C u t --- o u t Reset (auto)
RETURN-- -AIR FILTERS Throwaway†(in.) (mm)
(kg)
(mm)
(mm)
(kg)
*Based on altitude of 0 to 2000 ft (0 to 610 m). {Recommended filter sizes for field---installed air filter grilles mounted on the wall or ceiling of the conditioned structure. Required filter sizes shown are based on
the larger of the AHRI (Air Conditioning, Heating and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft/minute for throwaway type or 450 ft/minute for high ---capacity type. Air filter pressure drop for non ---standard filters must not exceed 0.08 IN. W.C.
558 253
15.3
6.9
3300
22
559
1/4 (1100)
2...21
19.4
3...17
5.7
11x10
279x254
3...38
3...53
558 253
15.3
6.9
3300
22
559
1/4 (1100)
2...21
19.4
3...17
5.7
11x10
279x254
3...33
3...51
558 253
15.3
6.9
3300
22
559
1/4 (1100)
2...21
19.4
3...17
5.7
11x10
279x254
3...31
3...49
2 --- S t a g e S c r o l l
1
670 ± 10 470 ± 25
565 ± 15 455 ± 15
23 ± 5 55
± 5
24x36x1
610x914x25
609 276
15.8
7.2
3300
22
559
1/3 (1110)
2...21
23.3
4...17
5.7
11x10
279x254
3...38
3...53
609 276
15.8
7.2
3300
22
559
1/3 (1110)
2...21
23.3
4...17
5.7
11x10
279x254
3...33
3...51
609 276
15.8
7.2
3300
22
559
1/3 (1110)
2...21
23.3
4...17
5.7
11x10
279x254
3...31
3...49
8
CAUTION - NOTICE TO RIGGERS PRUDENCE - AVIS AUX MANIPULATEUR
PANNEAUX D'ACCES DOIT ÊTRE EN PLACE POUR MANIPULATION.
Use top skid as spreader bar. / Utiliser la palette du haut comme barre de répartition
ACCESS PANELS MUST BE IN PLACE WHEN RIGGING.
DUCTS
MINIMUM HEIGHT: 36" (914.4 mm) HAUTEUR MINIMUM
UNIT HEIGHT HAUTEUR D'UNITÉ
SEE DETAIL A VOIR DÉTAIL A
CABINET MODEL
Small 577D------A24 426 193 Small 577D------A30 433 196
Large
NOTE: See dimensional drawing for corner weight distribution.
Rigging/Lifting of Unit (See Fig. 7)
!
WARNING
UNIT FALLING HAZARD
Failure to follow this warning could result in personal injury or death.
Large base units must be secured to common curb before allowing full weight of unit to rest on curb. Install screws through curb into unit base rails while rigging crane is still supporting unit.
DETAIL A
VOIR DÉTAIL A
577D------A36 522 237 577D------A42 544 247 577D------A48 558 253 577D------A60 609 276
Fig. 7 -- Suggested Rigging
Select and Install Ductwork
The design and installation of the duct system must be in accordance with the standards of the NFPA for installation of non--residence type air conditioning and ventilating systems, NFPA 90A or residence type, NFPA 90B and/or local codes and ordinances.
Select and size ductwork, supply-- air registers, and return air grilles according to ASHRAE (American Society of Heating, Refrigeration, and Air Conditioning Engineers) recommendations.
The unit has duct flanges on the supply-- and return-- air openings on the side of the unit.
SEAL STRIP MUST BE IN PLACE BEFORE PLACING UNIT ON ROOF CURB
BANDE SCELLANT DOIT ÊTRE EN PLACE AVANT DE PLACER L'UNITÉ SUR LA BASE DE TOIT
50CY502286 2.0
RIGGING WEIGHT
lb kg
577D-- --A
A09079
Lifting holes are provided in base rails as shown in Fig. 5 and 6.
1. Leave top shipping skid on the unit for use as a spreader bar to prevent the rigging straps from damaging the unit. If the skid is not available, use a spreader bar of sufficient length to protect the unit from damage.
2. Attach shackles, clevis pins, and straps to the base rails of the unit. Be sure materials are rated to hold the weight of the unit (See Fig. 7).
3. Attach a clevis of sufficient strength in the middle of the straps. Adjust the clevis location to ensure unit is lifted level with the ground.
After the unit is placed on the roof curb or mounting pad, remove the top skid.
!
WARNING
PERSONAL INJURY HAZARD
Failure to follow this warning could result in personal injury or death.
For vertical supply and return units, tools or parts could drop into ductwork, therefore, install a 90 degree turn in the return ductwork between the unit and the conditioned space. If a 90 degree elbow cannot be installed, then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditioned space.
When designing and installing ductwork, consider the following:
1. All units should have field--supplied filters or accessory filter rack installed in the return-- air side of the unit. Recommended sizes for filters are shown in Table 1.
9
2. Avoid abrupt duct size increases and reductions. Abrupt change in duct size adversely affects air performance.
IMPORTANT: Use flexible connectors between ductwork and unit to prevent transmission of vibration. Use suitable gaskets to ensure weather tight and airtight seal. When electric heat is installed, use fireproof canvas (or similar heat resistant material) connector between ductwork and unit discharge connection. If flexible duct is used, insert a sheet metal sleeve inside duct. Heat resistant duct connector (or sheet metal sleeve) must extend 24 -- in. (610 mm) from electric heater element.
3. Size ductwork for max possible air flow (See Table 1).
4. Seal, insulate, and weatherproof all external ductwork. Seal, insulate and cover with a vapor barrier all ductwork passing through conditioned spaces. Follow latest Sheet Metal and Air Conditioning Contractors National Association (SMACNA) and Air Conditioning Contractors Association (ACCA) minimum installation standards for residential heating and air conditioning systems.
5. Secure all ducts to building structure. Flash, weatherproof, and vibration--isolate duct openings in wall or roof according to good construction practices.
577D-- --A
6. Read unit rating plate for any required clearances around ductwork.
Configuring Units for Downflow (Vertical) Discharge
!
WARNING
Basepan Downflow (Vertical) Supply Knockout
Horizontal Duct Covers
A09076
Basepan Downflow (Vertical) Return Knockout
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing system, always turn off main power to system and install lockout tag. There may be more than one disconnect switch.
1. Open all electrical disconnects before starting any service work.
2. Remove horizontal (metal) duct covers to access vertical (downflow) discharge duct knockouts in unit basepan. (See Fig. 8.)
!
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Collect ALL screws that were removed. Do not leave screws on rooftop as permanent damage to the roof may occur.
To remove downflow return and supply knockout covers, break front and right side connecting tabs with a screwdriver and hammer. Push cover down to break rear and left side tabs.
NOTE: These panels are held in place with tabs similar to an electrical knockout. Reinstall horizontal duct covers (see Fig. 8) shipped on unit from factory. Insure openings are air and watertight.
The design and installation of the duct system must be in accordance with the standards of the NFPA for installation of nonresidence--type air conditioning and ventilating systems, NFPA 90A or residence-- type, NFPA 90B; and/or local codes and ordinances.
Adhere to the following criteria when selecting, sizing, and installing the duct system:
1. Units are shipped for horizontal duct installation (by removing duct covers).
A09077
Fig. 8 -- Supply and Return Duct Opening
2. Select and size ductwork, supply--air registers, and return--air grilles according to American Society of Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) recommendations.
3. Use flexible transition between rigid ductwork and unit to prevent transmission of vibration. The transition may be screwed or bolted to duct flanges. Use suitable gaskets to ensure weather--tight and airtight seal.
4. All units must have field--supplied filters or accessory filter rack installed in the return--air side of the unit. Recommended sizes for filters are shown in Table 1.
5. Size all ductwork for maximum required airflow (either heating or cooling) for unit being installed. Avoid abrupt duct size increases or decreases or performance may be affected.
6. Adequately insulate and weatherproof all ductwork located outdoors. Insulate ducts passing through unconditioned space, and use vapor barrier in accordance with latest issue of Sheet Metal and Air Conditioning Contractors National Association (SMACNA) and Air Conditioning Contractors of America (ACCA) minimum installation standards for heating and air conditioning systems. Secure all ducts to building structure.
7. Flash, weatherproof, and vibration isolate all openings in building structure in accordance with local codes and good building practices.
Provide for Condensate Disposal
NOTE: Ensure that condensate--water disposal methods comply
with local codes, restrictions, and practices. The units dispose of condensate through a 3/4 --in. NPT female
fitting that exits on the compressor end of the unit. Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground level installations. Install a field-- supplied condensate trap at end of condensate connection to ensure proper drainage. Make sure that
10
the outlet of the trap is at least 1 in. (25 mm) lower than the drain--pan condensate connection to prevent the pan from overflowing. Prime the trap with water. When using a gravel apron, make sure it slopes away from the unit.
If the installation requires draining the condensate water away from the unit, install a field--supplied 2--in. (51 mm) trap at the condensate connection to ensure proper drainage. Condensate trap is available as an accessory or is field--supplied. Make sure that the outlet of the trap is at least 1 in. (25 mm) lower than the unit drain--pan condensate connection to prevent the pan from overflowing. Connect a drain tube using a minimum of field-- supplied 3/4 --in. PVC or field--supplied 3/4 --in. copper pipe at outlet end of the 2 --in. (51 mm) trap (See Fig. 9). Do not undersize the tube. Pitch the drain tube downward at a slope of at least 1 in. for every 10 ft. (3 m) of horizontal run. Be sure to check the drain trough for leaks. Prime the trap at the beginning of the cooling season start--up.
Install Flue Hood
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
The venting system is designed to ensure proper venting. The flue hood assembly must be installed as indicated in this section of the unit installation instructions.
Install the flue hood as follows:
1. This installation must conform with local building codes and with the National Fuel Gas Code (NFGC), NFPA 54/ANSI Z223.1 (in Canada, CAN/CSA B149.1, and B149.2) or latest revision. Refer to provincial and local plumbing or wastewater codes and other applicable local codes.
2. Remove flue hood from shipping location (inside the return section of the blower compartment--See Fig. 8). Remove the return duct cover to locate the flue hood. Remove two screws on flue panel. Place flue hood assembly over flue panel. Orient screw holes in flue hood with holes in the flue panel.
3. Secure flue hood to flue panel by inserting a single screw on the top and the bottom of the hood.
TRAP OUTLET
1-in. (25 mm) min.
2-in. (51 mm) min.
A09052
Fig. 9 -- Condensate Trap
Install Gas Piping
The gas supply pipe enters the unit through the access hole provided. The gas connection to the unit is made to the 1/2--in. FPT gas inlet on the gas valve.
Install a gas supply line that runs to the heating section. Refer to Table 2 and the current edition of NFGC in the U.S. and the current
NSCNGPIC in Canada. Do not use cast--iron pipe. It is recommended that a black iron pipe is used. Check the local utility for recommendations concerning existing lines. Size gas supply piping for 0.5 IN. W.C. maximum pressure drop. Never use pipe smaller than the 1/2-- in. FPT gas inlet on the unit gas valve.
For natural gas applications, the gas pressure at unit gas connection must not be less than 4.0 IN. W.C. or greater than 13 IN. W.C. while the unit is operating. For propane applications, refer to propane conversion kit instructions.
A 1/8-- in. (3.2 mm) NPT plugged tapping, accessible for test gauge connection, must be installed immediately upstream of the gas supply connection to the gas valve and downstream of manual equipment shutoff valve.
When installing the gas supply line, observe local codes pertaining to gas pipe installations. Refer to the NFPA 54/ANSI Z223.1--2009 (in Canada, CAN/CSA B149.1).
NOTE: In the state of Massachusetts:
1. Gas supply connections MUST be performed by a licensed plumber or gas fitter.
2. When flexible connectors are used, the maximum length shall not exceed 36 in. (915 mm).
3. When lever handle type manual equipment shutoff valves are used, they shall be T-- handle valves.
4. The use of copper tubing for gas piping is NOT approved by the state of Massachusetts.
In the absence of local building codes, adhere to the following pertinent recommendations:
1. Avoid low spots in long runs of pipe. Grade all pipe 1/4 in. (6.35 mm) for every 15 ft (4.6 m) of length to prevent traps. Grade all horizontal runs downward to risers. Use risers to connect to heating section and to meter.
2. Protect all segments of piping system against physical and thermal damage. Support all piping with appropriate straps, hangers, etc. Use a minimum of one hanger every 6 ft. (1.8 m). For pipe sizes larger than 1/2 in., follow recommendations of national codes.
3. Apply joint compound (pipe dope) sparingly and only to male threads of joint when making pipe connections. Use only pipe dope that is resistant to action of liquefied petroleum gases as specified by local and/or national codes. Never use Teflon tape.
4. Install sediment trap in riser leading to heating section (See Fig. 10). This drip leg functions as a trap for dirt and condensate.
5. Install an accessible, external, manual main shutoff valve in gas supply pipe within 6 ft (1.8 m) of heating section.
6. Install ground--joint union close to heating section between unit manual shutoff and external manual main shut off valve.
7. Pressure test all gas piping in accordance with local and national plumbing and gas codes before connecting piping to unit.
NOTE: Pressure test the gas supply system after the gas supply piping is connected to the gas valve. The supply piping must be disconnected from the gas valve during the testing of the piping systems when test pressure is in excess of 0.5 psig. Pressure test the gas supply piping system at pressures equal to or less than 0.5 psig. The unit heating section must be isolated from the gas piping system by closing the external main manual shutoff valve and slightly opening the ground--joint union.
577D-- --A
11
OUT
IN
TEE
NIPPLE
Install Electrical Connections
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
The unit cabinet must have an uninterrupted, unbroken electrical ground. This ground may consist of an electrical wire connected to the unit ground screw in the control compartment, or conduit approved for electrical ground when installed in accordance with NEC, NFPA 70 National Fire Protection Association (latest edition) (in Canada, Canadian Electrical Code CSA C22.1) and local electrical codes.
CAP
C99020
Fig. 10 -- Sediment Trap
577D-- --A
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in fire, explosion, personal injury, death and/or property damage.
S Connect gas pipe to unit using a backup wrench to avoid
S Never purge a gas line into a combustion chamber. Never
S Use proper length of pipe to avoid stress on gas control
S If a flexible connector is required or allowed by authority
S If codes allow a flexible connector, always use a new
8. Check for gas leaks at the field--installed and
!
WARNING
damaging gas controls.
test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection
of leaks to check all connections.
manifold.
having jurisdiction, black iron pipe shall be installed at
furnace gas valve and extend a minimum of 2 in. (51 mm)
outside furnace casing.
connector. Do not use a connector which has previously
serviced another gas appliance.
factory--installed gas lines after all piping connections have been completed. Use a commercially available soap solution made specifically for the detection of leaks (or method specified by local codes and/or regulations).
HIGH--VOLTAGE CONNECTIONS The unit must have a separate electrical service with a
field-- supplied, waterproof disconnect switch mounted at, or within sight from, the unit. Refer to the unit rating plate, NEC and local codes for maximum fuse/circuit breaker size and minimum circuit amps (ampacity) for wire sizing.
The field--supplied disconnect may be mounted on the unit over the high--voltage inlet hole (See Fig. 5 and 6).
NOTE: Field supplied disconnect switch box should be positioned so that it does not cover up any of the unit gas combustion supply air louvers.
Operation of unit on improper line voltage constitutes abuse and may cause unit damage that could affect warranty.
!
UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the unit being installed.
1. Make all electrical connections in accordance with NEC NFPA 70 (latest edition) and local electrical codes governing such wiring. In Canada, all electrical connections must be in accordance with CSA standard C22.1 Canadian Electrical Code Part 1 and applicable local codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between field-- supplied electrical disconnect switch and unit. DO NOT USE ALUMINUM WIRE.
3. Be sure that high--voltage power to unit is within operating voltage range indicated on unit rating plate.
4. Insulate low--voltage wires for highest voltage contained within conduit when low--voltage control wires are in same conduit as high--voltage wires.
5. Do not damage internal components when drilling through any panel to mount electrical hardware, conduit, etc.
CAUTION
ROUTING POWER LEADS INTO UNIT Use only copper wire between disconnect and unit. The high
voltage leads should be in a conduit until they enter the duct panel; conduit termination at the duct panel must be watertight. Run the high--voltage leads through the power entry knockout on the power entry side panel. See Fig. 5 and 6 for location and size. For single-- phase units, connect leads to the black and yellow wires.
CONNECTING GROUND LEAD TO GROUND SCREW Connect the ground lead to the chassis using the ground screw on
the control plate near the inducer switch (See Fig. 12).
12
Table 2 – Maximum Gas Flow Capacity*
NOMINAL
IRON PIPE
SIZE (IN.)
1/2 .622 175 120 97 82 73 66 61 57 53 50 44 40 3/4 .824 360 250 200 170 151 138 125 118 110 103 93 84 77 72
1 1.049 680 465 375 320 285 260 240 220 205 195 175 160 145 135 1 --- 1 / 4 1.380 1400 950 770 600 580 530 490 460 430 400 360 325 300 280 1 --- 1 / 2 1.610 2100 1460 1180 990 900 810 750 690 650 620 550 500 460 430
*Capacity of pipe in cu ft of gas per h r for gas pressure of 0.5 psig or less. Pressure drop of 0.5 ---IN. W.C. (based on a 0.60 specific gravity gas). Refer toTable2 and NFPA 54/ANSI Z223.1.
{ This length includes an ordinary number of fittings.
INTERNAL
DIAMETER
(IN.)
10
(3.0)20(6.1)30(9.1)40(12.1)50(15.2)60(18.3)70(21.3)80(24.4)90(27.4)
ROUTING CONTROL POWER WIRES
For detailed instruction on the low voltage connections to the User Interface (UI), refer to the UI installation guide.
Form a drip--loop with the control leads before routing them into the unit. Route the low voltage control leads through grommeted, low--voltage hole provided into unit (See Fig. 5 and 6). Connect user interface leads to unit control power leads as shown in Fig. 14.
The unit transformer supplies 24--v power for complete system including accessory electrical heater. Transformer is factory wired for 230--v operation. If supply voltage is 208--v, rewire transformer primary as described in Special Procedures for 208--v Operation section.
The furnace board is fused by a board--mounted automotive fuse placed in series with transformer SEC1 and R circuit. The C circuit of transformer circuit is referenced to chassis ground through a printed circuit run at SEC2 and gas valve grounding wire. Check to be sure control board is mounted securely using both factory--installed screws.
ACCESSORY INSTALLATION
A. Outdoor Air Temperature Sensor (OAT)
LENGTH OF PIPE ft (m)†
100
(30.5)
125
(38.1)
150
(45.7)
175
(53.3)
The OAT input is used to supply outdoor temperature data for system level functions and for temperature display on User Interface (UI). Using two wires of the field--supplied thermostat wire cable, wire the ends of the two black OAT pigtails. Wire the opposite ends of these two wires to the OAT provided with the UI. There is no polarity to be observed.
NOTE: Mis--wiring OAT inputs will not cause damage to either Evolution control or thermistor. If the thermistor is wired incorrectly, no reading will appear at UI. Re-- wire thermistor correctly for normal operation.
B. Humidifier Connections
The furnace control board terminal marked HUM is provided for low voltage (24--vac) control of a humidifier. No humidistat is required as UI monitors indoor humidity.
When commanded to operate humidifier, the unit control will energize the HUM output to turn humidifier on and de--energize HUM output to turn humidifier off. Wire HUM and COM terminals directly to humidifier as shown in Fig. 14.
C. Electronic Air Cleaner
Electronic Air Cleaner terminals are provided on the Evolution Control Board (EAC--1 and EAC --2). While these terminals can be
!
CAUTION
EQUIPMENT OPERATION HAZARD
The installation of an outdoor air temperature sensor (OAT) using the Evolution control board OAT terminals is required. Many Evolution features (auto humidity control, comfort rollback, etc.) will be lost if the OAT is not connected.
For detailed mounting instructions for the OAT sensor, please refer installation instructions shipped with the OAT.
used to power a 230V EAC, it is recommended that any EAC be installed per the EAC installation instructions and connected separately to a standard 115V or 230V outlet with an airflow sensor to control operation of the EAC.
SPECIAL PROCEDURES FOR 208--V OPERATION Be sure unit disconnect switch is open.
Disconnect the black primary lead from the transformer. See unit wiring label (See Fig. 16 and 17).
Connect the black primary lead to the transformer terminal labeled 208--v.
200
(61.0)
577D-- --A
13
577D-- --A
A09075
Fig. 11 -- Typical Installation
GROUND SCREW
(IN SPLICE BOX)
GROUND
LEAD
SINGLE-PHASE
L1 CONNECTIONS TO DISCONNECT PER NEC
LEGEND
L2
NOTE: Use copper wire only.
NEC – National Electrical Code
Field Wiring Splice Connections
Fig. 12 -- Line Power Connections
BLK
YEL
A06299
14
HP/AC BOARD
FURNACE BOARD
Fig. 13 -- Control Plate
A09108
577D-- --A
Fig. 14 -- Control Voltage Wiring Connections
15
A06357
PRE--START--UP
!
WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK AND ENVIRONMENTAL HAZARD
Failure to follow this warning could result in personal injury or death and/or property damage.
1. Follow recognized safety practices and wear protective goggles when checking or servicing refrigerant system.
2. Do not operate compressor or provide any electric power to unit unless compressor terminal cover is in place and secured.
3. Do not remove compressor terminal cover until all electrical sources are disconnected and tagged.
4. Relieve and recover all refrigerant from system before touching or disturbing anything inside terminal box if refrigerant leak is suspected around compressor terminals.
5. Never attempt to repair soldered connection while
577D-- --A
refrigerant system is under pressure.
6. Do not use torch to remove any component. System contains oil and refrigerant under pressure.
7. To remove a component, wear protective goggles and proceed as follows:
a. Shut off gas supply to unit.
b. Shut off electrical power to unit and install
lockout tag.
c. Relieve and reclaim all refrigerant from system
using both high-- and low--pressure ports.
d. Cut component connecting tubing with tubing
cutter and remove component from unit.
e. Carefully unsweat remaining tubing stubs when
necessary. Oil can ignite when exposed to flame.
Use the Start--Up Checklist supplied at the end of this book and proceed as follows to inspect and prepare the unit for initial start--up:
1. Remove all access panels. (See Fig. 24.)
2. Read and follow instructions on all DANGER, WARNING, CAUTION, and INFORMATION labels attached to, or shipped with unit.
3. Make the following inspections:
a. Inspect for shipping and handling damages, such as
broken lines, loose parts, disconnected wires, etc.
b. Inspect for oil at all refrigerant tubing connections and
on unit base. Detecting oil generally indicates a refrigerant leak. Leak test all refrigerant tubing connections using electronic leak detector, or liquid--soap solution. If a refrigerant leak is detected, see following Check for Refrigerant Leaks section.
c. Inspect all field-- and factory --wiring connections. Be
sure that connections are completed and tight.
d. Ensure wires do not touch refrigerant tubing or sharp
sheet metal edges.
e. Inspect coil fins. If damaged during shipping and
handling, carefully straighten fins with a fin comb.
4. Verify the following conditions:
a. Make sure gas line is free of air. Before lighting the unit
for the first time, perform the following tasks with the gas valve in the OFF position.
NOTE: If the gas supply pipe was not purged before connecting the unit, it will be full of air. It is recommended that the ground
joint union be loosened, and the supply line be allowed to purge until the odor of gas is detected. Never purge gas lines into a combustion chamber. Immediately upon detection of gas odor, retighten the union. Allow 5 minutes to elapse, then light unit.
b. Make sure that condenser--fan blade is correctly
positioned in fan orifice. Top 1/3 of condenser fan blade should be within fan orifice venturi.
c. Ensure fan hub is positioned correctly with respect to
motor housing (See Fig. 27).
d. Make sure that air filter(s) is in place.
e. Make sure that condensate drain trap is filled with water
to ensure proper drainage.
f. Make sure that all tools and miscellaneous loose parts
have been removed.
5. Compressors are internally spring mounted. Do not loosen or remove compressor holddown bolts.
6. Each unit system has two Schrader-- type ports, one low--side Schrader fitting located on the suction line, and one high--side Schrader fitting located on the compressor discharge line. Be sure that caps on the ports are tight.
START--UP
Unit Start--Up and Troubleshooting
NOTE: Always check high-- and low--voltage supply to the unit components. Check the integrity of the plug receptacle connections and unit wiring harness prior to assuming a component failure.
A. LED Description
LEDs built into Evolution control boards provide installer or service person information concerning operation and/or fault condition of the unit controls and ECM motor. This information is also available at the system UI in text with basic troubleshooting instructions. Careful use of information displayed will reduce the need for extensive manual troubleshooting.
Both the furnace and heat pump (HP)/air conditioner (AC) boards have an amber LED and a green LED. On the HP/AC board, these are located near the System Communications connector (ABCD) (lower right corner of the HP/AC board as installed in the unit). On the furnace board, these are located at the upper right side, adjacent to the fuse, above the terminal block. The amber LED is the System Status LED, labeled STATUS. The green LED, labeled COMM, is used as an indicator of system communications status (See Fig. 15 and 18).
Status Codes will be displayed on the STATUS LED using the following protocol:
1. The number of short flashes indicates first digit of code.
2. The number of long flashes indicates second digit of code.
3. A short flash is 0.25 seconds on. A long flash is 1 second on.
4. The time between flashes is 0.25 seconds.
5. The time between last short flash and first long flash is 1 second.
6. The LEDs will be off for 2.5 seconds before repeating code.
7. If multiple status codes are active concurrently, the highest priority status code is displayed.
B. Control Start--Up and System Communications
Troubleshooting
On power up, green COMM LEDs will be turned off until successful system communications are established (this should happen within 10 seconds). Once communications with UI are successful, both COMM LEDs will be lit and held on. At the same time, amber STATUS LEDs will be lit and held continuously on until a request for operating mode is received. The STATUS LED will be on any time unit is in idle mode.
If, at any time, communications are not successful for a period exceeding 2 minutes, the Evolution control will only allow
16
emergency heating or cooling operation using a common thermostat and the terminal strip connections on the two control boards (See Non--Communicating Emergency Cooling/Heating Mode) and will display Status Code 16, System Communication Fault, on amber STATUS LED. No further troubleshooting information will be available at UI until communications are re--established.
If either COMM LED does not light within proper time period and status codes are not displayed;
1. Check system transformer high-- and low--voltage to be sure the system is powered.
2. Check ABCD connection on both boards.
3. Check fuse on furnace board to be sure it is not blown. If fuse is open, check system wiring before replacing it to be sure a short does not cause a failure of replacement fuse.
If COMM LED does not light within proper time period and status code is displayed:
1. Check system wiring to be sure UI is powered and connections are made A to A, B to B, etc. and wiring is not shorted. Miswiring or shorting of the ABCD communications wiring will not allow successful communications.
NOTE: Shorting or miswiring low--voltage system wiring will not cause damage to unit control or UI but may cause low voltage fuse to open.
C. Indoor Fan Motor Troubleshooting
The indoor fan is driven by an ECM motor consisting of two parts: the control module and the motor winding section. Do not assume motor or module is defective if it will not start. Use the designed--in LED information aids and follow troubleshooting steps described below before replacing motor control module or entire motor. Motor control module is available as a replacement part.
VERIFY MOTOR WINDING SECTION
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
After disconnecting power from the ECM motor, wait at least 5 minutes before removing the control section. Internal capacitors require time to discharge.
operate electric heaters while a fault condition exists. The control communicates with the motor at least once every five seconds, even when the motor is idle. If, during operation, the control does not communicate with the motor for more than 25 seconds, the motor will shut itself down and wait for communications to be reestablished.
D. Furnace Control Troubleshooting
Furnace control faults indicated by flashing codes on the amber system STATUS LED can be resolved using troubleshooting information provided below. Codes are listed in order of their priority, highest to lowest. Though multiple faults can exist at any time, only the highest priority code will be displayed on STATUS LED. Clearing the indicated fault when multiple faults exist will cause the next highest priority Status Code to be flashed. All existing faults, as well as a fault history, can be viewed at UI.
STATUS CODE CONTINUOUS OFF Check for 230 VAC at L1 and L2, and 24 VAC at SEC --1 and SEC--2 .
STATUS CODE CONTINUOUS ON Control has 24 VAC power.
STATUS CODE 11 -- NO PREVIOUS CODE Stored status codes are erased automatically after 72 hours.
STATUS CODE 12 -- BLOWER ON AFTER POWER UP (230 VAC or 24 VAC) Blower runs for 90 seconds if unit is powered up during a call for heat (R--W/W1 closed) or (R--W/W1 opens) during blower on--delay period.
STATUS CODE 1 3 -- LIMIT CIRCUIT LOCKOUT Lockout occurs if a limit or flame rollout switch is open longer than 3 minutes or 10 successive limit trips occurred during high heat. Control will auto reset after three hours. Refer to status code
33.
STATUS CODE 1 4 -- IGNITION LOCKOUT Control will auto reset after three hours. Refer to status code 34.
STATUS CODE 1 5 -- BLOWER MOTOR LOCKOUT Indicates the blower failed to reach 250 RPM or the blower failed to communicate within 30 seconds after being turned ON in two successive heating cycles. Control will auto reset after 3 hours. Refer to status code 41.
577D-- --A
Before proceeding to replace a motor control module:
1. Check motor winding section to be sure it is functional.
2. Remove motor control module section and unplug winding plug. Motor shaft should turn freely, resistance between any two motor leads should be similar and resistance between any motor lead and unpainted motor end should exceed 100,000 ohms.
3. Failing any of these tests, entire ECM motor must be replaced.
4. Passing all of the tests, motor control module alone can be replaced.
MOTOR TURNS SLOWLY
1. Low static pressure loading of blower while access panel is removed will cause blower to run slowly. Particularly at low airflow requests. This is normal, do not assume a fault exists.
2. Recheck airflow and system static pressure using UI service screens with access panel in place.
NOTE: Blower motor faults will not cause a lockout of blower operation. The fan coil control will attempt to run the blower motor as long as UI maintains a demand for airflow. The control will not
A06026
Fig. 15 -- Detail of Furnace Board
17
577D-- --A
Fig. 16 -- Connection Wiring Schematic--577D-- -- A Single Phase Gas Inputs 040, 060, 090 kBtu/hr
18
A10217C
577D-- --A
Fig. 16 Cont. -- Ladder Wiring Schematic--577D----A Single Phase Gas Inputs 040, 060, 090 kBtu/hr
19
A10217L
577D-- --A
Fig. 17 -- Connection Wiring Schematic--577D-- -- A Single Phase Gas Inputs 115, 130 kBtu/hr
20
A10219C
577D-- --A
Fig. 17 Cont. -- Ladder Wiring Schematic--577D---- A Single Phase Gas Inputs 115, 130 kBtu/hr
21
A10219L
577D-- --A
UTILITY RELAY
UTILITY SIGNAL
OPEN RELAY
*
SUPPLIED BY UTILITY PROVIDER
STATUS CODE 2 1 -- GAS HEATING LOCKOUT Control will NOT auto reset. Check for mis--wired gas valve or defective control (valve relay).
STATUS CODE 22 -- ABNORMAL FLAME-- PROVING SIGNAL Flame is proved while gas valve is de--energized. Inducer will run until fault is cleared. Check for leaky gas valve or stuck--open gas valve.
STATUS CODE 23 -- PRESSURE SWITCH DID NOT OPEN Check for obstructed pressure tubing or pressure switch stuck closed.
STATUS CODE 24 -- SECONDARY VOLTAGE FUSE IS OPEN Check for short circuit in secondary voltage (24VAC) wiring.
STATUS CODE 25 -- INVALID MODEL SELECTION OR SETUP ERROR Indicates either the model plug is missing or incorrect. If code flashes 4 times on power--up, control is defaulting to model selection stored in memory. Check for proper model plug number and resistance values per wiring diagram.
STATUS CODE 31, 32 -- PRESSURE SWITCH OR RELAY DID NOT CLOSE OR REOPENED Control relay may be defective. If open longer than five minutes, inducer shuts off for 15 minutes before retry. If open during blower on--delay period, blower will come on for the selected blower off--delay. Check for excessive wind, restricted vent, defective inducer motor, defective pressure switch, lower inducer voltage (230VAC), inadequate combustion air supply, disconnected or obstructed pressure tubing, or low inlet gas pressure (if LGPS used).
STATUS CODE 3 3 -- LIMIT C IRCUIT FAULT Indicates a limit or flame rollout switch is open. Blower will run for 4 minutes or until open switch remakes, whichever is longer. If open longer than 3 minutes, code changes to lockout 13. If open less than 3 minutes status code 33 continues to flash until blower
*
Fig. 18 -- 2-- Stage HP/AC Control Board
LLS
Liquid Line Solenoid
A05247
shuts off. Check for loose blower wheel, restricted vent, excessive wind, dirty filter or restricted duct system, defective switch or connections, or inadequate combustion air supply (flame roll--out switch open).
STATUS CODE 3 4 -- IGNITION PROVING FAILURE Control will try three more times before lockout 14 occurs. If flame signal lost during blower on-- delay period, blower will come on for the selected blower off--delay. Check for oxide buildup on flame sensor (clean with fine steel wool), proper flame sense microamps (.5 microamps D.C. min., 4.0--6.0 nominal), manual valve shutoff, low inlet gas pressure, control ground continuity, gas valve defective or turned off, flame sensor must not be grounded, inadequate flame carryover or rough ignition, or green/yellow wire must be connected to unit sheet metal.
STATUS CODE 4 1 -- BLOWER MOTOR FAULT Indicates the blower failed to reach 250 RPM or the blower failed to communicate within the prescribed time limits. Thirty seconds after being turned ON or ten seconds during steady--state operation.
STATUS CODE 4 2 -- INDUCER MOTOR FAULT Indicates inducer motor hasn’t started within a prescribed time limit. Check inducer motor and wiring.
STATUS CODE 4 5 -- CONTROL CIRCUITRY LOCKOUT Auto reset after one hour lockout due to gas valve relay stuck open, flame sense circuit failure, or software check error. Reset power to clear lockout. Replace control if status code repeats.
E. HP/AC Control Troubleshooting
See Table 4 for HP/AC control board status codes and troubleshooting information.
STATUS CODE 5 3, OUTDOOR AIR TEMPERATURE SENSOR FAULT -- DETAILED DESCRIPTION
If an OAT sensor is found at power--up, input is constantly checked to be within a valid temperature range. If sensor is found to be
22
open or shorted at any time after initial validation, Status Code 53 will be displayed at amber STATUS LED.
Check for faults in wiring connecting sensor to OAT terminals. Using an Ohm meter, check resistance of thermistor for a short or open condition.
If thermistor is shorted or open, replace it to return the system to normal operation. If fault is in the wiring connections, correcting the fault will clear the code and return the system to normal operation.
NOTE: If fault condition is an open thermistor or a wiring problem that appears to be an open thermistor and the power to the unit is cycled off, the fault code will be cleared on the next power--up but the fault will remain and system operation will not be as expected.
This is because on power-- up, the unit control cannot discern the difference between an open sensor or if a sensor is not installed.
Sequence of Operation
The 577D---- A packaged unit is designed for installation with a communicating UI. This unit will not respond to commands provided by a common thermostat except under certain emergency situations described in Step 1—Start--Up and Troubleshooting.
The UI uses temperature, humidity and other data supplied from indoor and outdoor system components to control heating or cooling system for optimum comfort. The unit will be commanded by UI to supply airflow. The unit will operate the indoor blower at requested airflow for most modes.
INDOOR AIRFLOW ADJUSTMENTS The nominal requested airflow for air conditioner operations will
be 350 cfm per ton of nominal cooling capacity as defined by unit size. Actual airflow request will be adjusted from nominal using indoor and outdoor temperature and indoor humidity data to optimize the system operation for occupant comfort and system efficiency. Refer to UI literature for further system control details.
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in unit damage.
For cooling operation, the recommended airflow is 350 to 450 cfm for each 12,000 Btuh of rated cooling capacity. For heating operation, the airflow must produce a temperature rise that falls within the range stamped on the unit rating plate.
For gas heat operations, Table 3 shows the temperature rise in each gas heating mode. Refer to these tables to determine the desired heating airflow for the system being installed.
NOTE: Be sure that all supply-- and return-- air grilles are open, free from obstructions, and adjusted properly. Airflow can be changed using the UI. See UI installation instructions for more detail.
NOTE: Once the compressor has started and then has stopped, it should not be started again until 4 minutes have elapsed. The cooling cycle remains “on” until the room temperature drops to point that is slightly below the cooling control setting of the UI.
AIR CONDITIONER SEQUENCE OF OPERATION
COOLING OPERATION With a call for first stage cooling, the outdoor fan, and low stage
compressor are energized. If low--stage cannot satisfy cooling demand, high-- stage cooling is energized by the UI. After second stage is satisfied, the unit returns to low--stage operation until first stage is satisfied or until second stage is required again. When both first stage and second stage cooling are satisfied, the compressor will shut off.
NOTE: When two--stage unit is operating at low--stage, system vapor (suction) pressure will be higher than a standard single-- stage system or high-- stage operation.
NOTE: Outdoor fan motor will continue to operate for one minute after compressor shuts off, when outdoor ambient is greater than or equal to 100°F(38°C).
UTILITY INTERFACE WITH Evolution CONTROL
The utility curtailment relay should be connected to factory supplied pigtails (PINK, connected to R, VIOLET connected to Y2 on the control board) located in the low voltage splice box (See Fig. 16, 18 and 18). This input allows a power utility device to interrupt compressor operation during peak load periods. When the utility sends a signal to shut the system down, the UI will display “Curtailment Active”.
COMPRESSOR OPERATION When the compressor is operating in low stage, the modulating
ring is deactivated, allowing two internal bypass ports to close off 33% of the scroll compression area so the system operates at part load capacity. The 24--volt solenoid coil is de--energized in low--stage operation.
When the compressor is operating at high stage, the modulating ring is activated, sealing the bypass ports, which allows the compressor to operate at full load capacity. The 24--volt solenoid coil is energized in high stage operation.
CRANKCASE HEATER OPERATION (IF APPLICABLE) The crankcase heater is energized during off cycle below 65_F
(18_C) outdoor air temperature.
OUTDOOR FAN MOTOR OPERATION The outdoor unit control energizes the outdoor fan any time the
compressor is operating. The outdoor fan remains energized if a pressure switch or compressor overload should open. Outdoor fan motor will continue to operate for one minute after the compressor shuts off when the outdoor ambient is greater than or equal to 100_F(38°C).
TIME DELAYS--AIR CONDITIONER OPERATIONS The unit time delays include:
S Five minute time delay to start cooling operation when there is a
call from the thermostat or user interface. To bypass this feature,
momentarily short and release Forced Defrost pins.
S Five minute compressor recycle delay on return from a
brown--out condition.
S Two minute time delay to return to standby operation from last
valid communication (with Evolution only).
S One minute time delay of outdoor fan at termination of cooling
mode when outdoor ambient is greater than or equal to 100_F
(38°C).
S There is no time delay between air conditioner staging from low
to high and from high to low capacity; the compressor will change
from low to high and from high to low capacity as demand
dictates.
577D-- --A
23
Table 3 – Air Delivery and Temperature Rise at Rated Heating Input
Unit
577DNWA24040 577DNWA30040
577DNWA30060 577DNWA36060 577DNWA42060
577DNWA36090 577DNWA42090 577DNWA48090 577DNWA60090
577DNWA48115 577DNWA60115
577DNWA48130 577DNWA60130
Airflow delivery values for external static pressure values of up to 1 IN. W.C.
Rated Heating Input (Btu/hr) Heating Rise RangeoF(oC) He ating Rise Either Stage, °F(oC)
High Stage Low Stage High Stage Low Stage
40,000 26,000
60,000 39,000
90,000 58,500
115,000 75,000
130,000 84,500
20 --- 50
( 1 1 --- 2 8 )
25 --- 55 ( 1 4 --- 3 1 )
35 --- 65 ( 1 9 --- 3 6 )
30 --- 60 ( 1 7 --- 3 3 )
35 --- 65 ( 1 9 --- 3 6 )
Table 4 – Heat Pump/Air Conditioner Board Status Codes
OPERATION FAULT
Standby – no call for unit operation None
577D-- --A
Emergency Mode
Low Stage Cool/Heat Operation None 1, pause Normal operation. High Stage C ool /Heat Operation None 2, pause Normal operation.
Standard Thermo­stat Contr ol
System Communica­tions Failure
Invalid Model Plug 25
H i g h --- P r e s s u r e Switch Open
L o w --- P r e s s u r e Switch Open
Control Fault 45 Outdoor unit control board has failed. Control board needs to be replaced.
Brown Out (230 v) 46
No 230v at Unit 47
Outdoor Air Temp Sensor Fault
Outdoor Coil Sensor Faul t
Thermistors Out of Range
Low Stage Thermal Cutout
High Stage Thermal Cutout
Contactor Shorted 73
No 230V at Com­pressor
Low Stage Thermal Lockout
High Stage Thermal Lockout
Low--- Pressure Lock­out
H i g h --- P r e s s u r e Lockout
AMBER LED
FLASH
CODE
On solid, no
flash
Rapid, con-
tinuous
flashing
16
31
32 L ow ---pressure switch trip. Ch eck refrigerant charge and indoor air flow.
53
55 Coil sensor not reading or out of range. Ohm out sensor and check wiring.
56
71
72
74
81
82
83
84
“Efficiency” “Comfort”
High Stage Low Stage High Stage Low Stage
15---45
( 8 --- 2 5 )
25 --- 55 ( 1 4 --- 3 1 )
35 --- 65 ( 1 9 --- 3 6 )
30 --- 60 ( 1 7 --- 3 3 )
35 --- 65 ( 1 9 --- 3 6 )
Normal operation.
Unit being controlled by standard thermostat inputs instead of Evolution Control. Only h igh stage operation is available. This operating mode should be used in emergency situations only.
Communication with UI lost. Check wiring to UI, indoor and outdoor units.
Control does not detect a model plug or detects an invalid model plug. Unit will not operate without correct model plug.
High ---pressure switch trip. Check refrigerant charge, outdoor fan operation and coils for airflow restrictions.
Line voltage < 187v for at least 4 seconds. Compressor and fan operation not allowed until voltage>
There is no 230v at the contactor when indoor unit is powered and cooling/ heating demand exists. Verify the disconnect is closed and 230v wiring is connected to the unit.
Outdoor air sensor not reading or out of range. Ohm out sensor and check wiring.
Improper relationship between coil sensor and outdoor air sensor. Ohm out sensors and check wiring.
Compressor voltage sensed, then disappears while cooling or heating de­mand exists. Possible causes are internal compressor overload trip or start relay not releasing (if installed).
Compressor voltage sensed, then disappears while cooling or heating de­mand exists. Possible causes are internal compressor overload trip or start relay not releasing (if installed).
Compressor voltage sensed when no demand for compressor operation exists. Contactor may be stuck closed or there is a wiring er ror.
Compressor voltage not sensed when compressor should be starting. Con­tactor may be stuck open or there is a wiring error.
Thermal cutout occurs in three consecutive low/ high stage cycl es. Low stage locked out for 4 hours or until 24v power recycled.
Thermal cutou t occurs in thr ee consecutive high/low stage cycles. High stage locked out for 4 hours or until 24v power recycled.
Low ---pressure switch trip has occurred during 3 con secutive cycles. Unit operation locked out for 4 hours or until 24v power recycled.
High ---pressure switch trip has occurred du ring 3 consecutive cycles. Unit operation locked out for 4 hours or until 24v power recycled.
35
(19)
POSSIBLE CAUSE AND ACTION
190v. Verify line voltage.
30
(17)
40
(22)
50
(28)
45
(25)
50
(28)
40
(22)
35
(19)
50
(28)
55
(31)
50
(28)
55
(31)
24
EVOLUTION CONTROLLED LOW AMBIENT COOLING NOTE: When this unit is operating below 55_F(13°C) outdoor
temperature, provisions must be made for low ambient operation. This unit is capable of low ambient cooling down to 0_F(--18°C). ONLY when using the Evolution control. A low ambient kit is not required, and the outdoor fan motor does not need to be replaced for Evolution controlled low ambient operation. Low ambient cooling must be enabled in the UI set--up. Fan may not begin to cycle until about 40_F(4°C).OAT. Fan will cycle based on coil and outdoor air temperature. Evolution controlled low ambient mode operates as follows:
S In high stage, fan is off when outdoor coil temp is <outdoor air
temperature plus 3_F(1.7_C) or outdoor fan has been ON for 30
minutes. (Fan is turned off to allow refrigerant system to
stabilize.)
S In low stage, fan is off when outdoor coil temp is <outdoor air
temperature plus 1_F(.6_C) or outdoor fan has been ON for 30
minutes. (Fan is turned off to allow refrigerant system to
stabilize.)
S In high stage and low stage, fan is on when outdoor coil temp >
outdoor air temperature plus 25_F (13.8_C) or outdoor coil temp >80_F(27_C) or if outdoor fan has been OFF for 30 minutes.
(Fan is turned on to allow refrigerant system to stabilize.)
S Low--pressure switch is ignored for first 3 minutes during low
ambient start up. After 3 minutes, if LPS trips, then outdoor fan
motor is turned off for 10 minutes with the compressor running. If
LPS closes within 10 minutes then cooling continues with the
outdoor fan cycling per the coil temperature routine listed above
for the remainder of the cooling cycle. If the LPS does not close
within 10 minutes, then the normal LPS trip response (shut down
cooling operation and generate LPS trip error) will occur.
DEHUMIDIFICATION MODE This Evolution system can be used to dehumidify the living space.
See UI Installation Instructions for more details.
SEQUENCE OF OPERATION--GAS HEAT NOTE: Evolution control must be grounded for proper operation
or control will lock out.
NOTE: If a power interruption occurs during a call for heat, the control will start a 90--second blower only ON period two seconds after power is restored, if the UI is still calling for gas heating. The amber LED light will flash code 12 during the 90-- second period, after which the LED will be ON continuously, as long as no faults are detected. After the 90--second period, the unit will respond to the UI normally.
GAS HEAT MODE AND ADJUSTMENTS
When the UI calls for gas heat, the Evolution furnace board performs a self--check, verifies the pressure switch is open, and starts the inducer on high speed.
1. Inducer Pre-- purge Period: When the inducer motor comes up on high speed, the pressure switch closes, and the Evolution ignition control on the furnace board begins a 15 second pre--purge period. If the pressure switch fails to remain closed, the inducer will remain running. After the pressure switch re--closes, the Evolution ignition control will begin a 15 second pre--purge period.
2. Trial-- For-- Ignition Sequence: The spark igniter will spark for 3 seconds. The main gas valve relay contact closes to energize the gas valve on low stage. After 5 seconds, the igniter is de--energized and a 2--second flame--proving
period begins. NOTE: The unit always lights on high speed inducer and low stage gas valve operation.
3. Flame--Proving: When the burner flame is proved at the flame--proving sensor, the furnace control determines what heating stage to run based on feedback from the UI. If the UI is asking for low stage gas heat, the ignition control will change the inducer speed to low speed and keep the gas valve energized on low stage. If the UI is asking for high stage gas heat, the ignition control will maintain running the inducer on high speed and energize the gas valve’s high stage relay to increase gas flow.
If the burner flame is not proved within 2 seconds, the control will close the gas valve and repeat the ignition sequence up to 3 more Trials--For--Ignition before going to Ignition--Lockout. Lockout will reset automatically after 3 hours, by momentarily interrupting 230 VAC power, or by interrupting 24 VAC power at SEC1 or SEC2 to the furnace board.
If flame is proved when there should be no flame present, control will lock out of Gas--Heating mode and operate the inducer motor until flame is no longer proved.
4. Blower--On Delay: If the burner flame is proven, approximately 37 seconds after the gas valve is opened the Indoor Blower is turned on to the appropriate speed for the gas heating stage.
Simultaneously, the humidifier terminal HUM and electronic air cleaner terminal EAC-- 1 are energized throughout the heating cycle.
NOTE: EAC-- 2 terminal is common with L2 and will have 115VAC--to--ground when unit is powered.
5. Blower--Off Delay: When the call for gas heat is satisfied, the gas valve is de-- energized, stopping the flow of gas to the burners, and de--energizing the HUM terminal. The inducer motor will remain on for a 4-- second post--purge period. The indoor blower and air cleaner terminal EAC--1 will remain energized for 90, 120, 150, or 180 seconds (depending on selection of blower--off delay selected in the UI). The factory--set default is 120-- second blower--OFF delay.
CHECK GAS INPUT (NATURAL GAS)
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in component damage.
Do not redrill an orifice. Improper drilling (burrs, out--of--round holes, etc.) can cause excessive burner noise and misdirection of burner flame. If orifice hole appears damaged or it is suspected to have been redrilled, check orifice hole with a numbered drill bit of correct size.
!
FIRE HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
DO NOT bottom out gas valve regulator adjusting screws. This can result in unregulated manifold pressure and result in excess overfire and heat exchanger failures.
CAUTION
WARNING
577D-- --A
25
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury and/or death.
If the manifold pressure and/or gas rate is not properly adjusted on HI and LO stages, excess carbon monoxide can be produced.
!
WARNING
FIRE AND UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death and/or property damage.
Unsafe operation of the unit may result if manifold pressure is outside of the ranges listed in Table 6.
Gas input rates on rating plate are for installations at altitudes up to 2000 ft (610 m). Input rate must be within ± 2% of rating plate input.
577D-- --A
1. Determine the correct gas input rate. a. The rated gas inputs shown in Table 6 are for altitudes
from sea level to 2000 ft (610 m) above sea level. These inputs are based on natural gas with a heating value of 1025 Btu/ft3 at .60 specific gravity.
IN THE U.S.A.: The input rating for altitudes above 2,000 ft (610 m) must be
reduced by 4 percent for each 1,000 ft (305 m) above sea level.
For installations below 2,000 ft, (610 m) refer to the unit rating plate.
For installations above 2,000 ft, (610 m) multiply the input by on the rating plate by the derate multiplier in Table 5 for the correct input rate.
Table 5 – Altitude Derate Multiplier for U.S.A*.
Altitude ft (m) Percent of Derate
0--2000
(0--610)
2001--3000*
(610--914)
3001--4000
(915--1219)
4001--5000
(1220--1524)
5001--6000
(1524--1829)
6001--7000
(1829--2134)
7001--8000
(2134--2438)
8001--9000
(2139--2743)
9001--10,000 (2744--3048)
* In Canada see Canadian Altitude Adjustment. {Derate multiplier factors are based on midpoint altitude for altitude range.
0 1.00
8--12 0.90
12--16 0.86
16--20 0.82
20--24 0.78
24--28 0.74
28--32 0.70
32--36 0.66
36--40 0.62
Derate Multiplier
Factor{
IN CANADA: The input rating for altitudes from 2,000 (610 m) to 4,500 ft (1372
m) above sea level must be derated 10 percent by an authorized Gas Conversion Station or Dealer.
EXAMPLE: 90,000 Btuh Input Furnace Installed at 4300 ft (1372 m).
Furnace Input Rate Derate Multiplier Furnace Input Rate
at Sea Level X Factor = at Installation
Altitude
90,000 X 0.90 = 81,000
b. When the gas supply being used has a different heating
value or specific gravity, refer to national and local codes, or contact your distributor to determine the required orifice size.
2. Adjust manifold pressure to obtain low stage input rate (See Fig. 19).
a. Turn off gas supply to unit.
b. Remove pipe plug on manifold (See Fig. 20 and
connect manometer). Turn on gas supply to unit.
c. Turn gas valve switch to ON.
d. Set unit to run for 20 minutes in low--stage gas heat
operation using the ”INSTALLER CHECKOUT” menu on the User Interface.
e. Remove regulator adjustment cap from low stage gas
valve pressure regulator (See Fig. 19) and turn low--stage adjusting screw (3/16 or smaller flat--tipped screwdriver) counterclockwise (out) to decrease rate and clockwise (in) to increase input rate.
REGULATOR COVER SCREW
ON/OFF SWITCH
INLET PRESSURE TAP
PLASTIC ADJUST SCREW
REGULATOR SPRING
HIGH STAGE GAS PRESSURE REGULATOR ADJUSTMENT
LOW STAGE GAS PRESSURE REGULATOR ADJUSTMENT
MANIFOLD PRESSURE TAP
A04167
Fig. 19 -- Redundant Automatic Gas Control Valve
NOTE: DO NOT set low stage manifold pressure less than 1.4
IN. W.C. or more than 2.0 IN. W.C. for natural gas. If manifold pressure is outside this range, change main burner orifices.
f. Re-- install low stage regulator adjustment cap.
g. Leave manometer connected.
NOTE: If orifice hole appears damaged or it is suspected to have been re--drilled, check orifice hole with a numbered drill bit of the correct size. Never re--drill an orifice. A burr--free and squarely aligned orifice hole is essential for proper flame characteristics.
3. Verify natural gas low stage input rate.
a. Turn off all other gas appliances and pilots served by
the gas meter.
b. If unit is not running, set unit to run for 20 minutes in
low--stage gas heat operation using the ”INSTALLER CHECKOUT” menu on the UI.
c. Record number of seconds for gas meter to complete
one revolution.
d. Divide number of seconds in step c. into 3600 (number
of seconds in 1 hour).
e. Multiply result of step d. by the number of cubic feet
shown for one revolution of test dial to obtain cubic feet of gas flow per hour.
f. Multiply result of step f. by Btu heating value of the gas
to obtain total measured input shown in Table 6. (Consult the local gas supplier if the heating value of gas is not known).
EXAMPLE: Assume a 90,000 high stage input unit is being installed. Assume that the size of the dial is 2 cubic ft., one revolution takes 129 sec., and the heating value of the gas is 1025 Btu/ft3. Proceed as follows:
26
a. 129 sec. to complete one revolution
b. 3600/129 = 27.9
c. 27.9x2=55.8ft3of gas flow/hr.
d. 55.8 x 1050 = 58,590 Btuh input.
In this example, the nominal input rate for low stage is 58,500 Btu/hr, so the low stage manifold pressure is correctly set.
If the measured low stage rate is too low, increase the manifold pressure to increase rate. If the measured low stage rate is too high, decrease the manifold pressure to decrease rate.
NOTE: Double--check that UI is running on low stage gas heat while clocking the low stage firing rate.
4. Verify proper low stage gas heat temperature rise.
a. Furnace must operate within rise range listed on rating
plate.
b. Select ”COMFORT” or ”EFFICIENCY” mode on UI.
”COMFORT” mode will provide a warmer supply air temperature, while ”EFFICIENCY” will provide lower gas consumption.
c. Make sure access panel is re--installed on the unit.
d. Measure supply and return temperatures as close to the
unit as possible. Subtract the return temperature from the supply temperature to determine rise. Rise should fall within the range specified on the rating plate.
5. Adjust manifold pressure to obtain high stage input rate (See Fig. 19).
a. Set unit to run for 20 minutes in high--stage gas heat
operation using the ”INSTALLER CHECKOUT” menu on the UI.
b. Remove regulator adjustment cap from high stage gas
valve pressure regulator (See Fig. 19) and turn high--stage adjusting screw (3/16 or smaller flat--tipped screwdriver) counterclockwise (out) to decrease rate and clockwise (in) to increase input rate.
NOTE: DO NOT set high stage manifold pressure less than 3.2 IN. W.C. or more than 3.8 IN. W.C. for natural gas. If manifold pressure is outside this range, change main burner orifices.
c. Re-- install high stage regulator adjustment cap.
d. Leave manometer connected.
6. Verify natural gas high stage input rate.
a. Turn off all other gas appliances and pilots served by
the gas meter.
b. If unit is not running, set unit to run for 20 minutes in
high stage gas heat operation using the ”INSTALLER CHECKOUT” menu on the UI.
c. Record number of seconds for gas meter to complete 1
revolution.
d. Divide number of seconds in step c. into 3600 (number
of seconds in 1 hour).
e. Multiply result of step d. by the number of cubic feet
shown for one revolution of test dial to obtain cubic feet of gas flow per hour.
f. Multiply result of step f. by Btu heating value of the gas
to obtain total measured input shown in Table 6. (Consult the local gas supplier if the heating value of gas is not known).
EXAMPLE: Assume a 90,000 high stage input unit is being installed. Assume that the size of the dial is 2 cubic ft., one revolution takes 84 sec., and the heating value of the gas is 1025 Btu/ft3. Proceed as follows:
a. 84 sec. to complete one revolution
b. 3600/84 = 42.9
c. 42.9x2=85.8ft3ofgasflow/hr.
d. 85.8 x 1050 = 90,090 Btuh input.
In this example, the nominal input rate for high stage is 90,000 Btu/hr, so the high stage manifold pressure is correctly set.
If the measured high stage rate is too low, increase the manifold pressure to increase rate. If the measured high stage rate is too high, decrease the manifold pressure to decrease rate.
NOTE: Double--check that User Interface is running on high stage gas heat while clocking the low stage firing rate.
7. Verify proper high stage gas heat temperature rise. a. Furnace must operate within rise range listed on rating
plate.
b. Make sure access panel is re--installed on the unit.
c. Measure supply and return temperatures as close to the
unit as possible. Subtract the return temperature from the supply temperature to determine rise. Rise should fall within the range specified on the rating plate.
NOTE: If the temperature rise is outside the rating plate range, first check:
a. Gas input for low and high stage gas heat operation.
b. Derate for altitude, if applicable.
c. Return and supply ducts for excessive restrictions
causing static pressures in excess of .5 IN. W.C.
d. Make sure model plug is installed.
8. Final Check a. Turn off gas to unit
b. Remove manometer from pressure tap.
c. Replace pipe plug on manifold (See Fig. 20).
d. Turn on gas to unit.
e. Check for leaks.
CHECK GAS INPUT (PROPANE GAS)
Refer to propane kit installation instructions for properly checking gas input.
NOTE: For installations below 2,000 ft (610 m), refer to the unit rating plate for proper propane conversion kit. For installations above 2,000 ft (610 m), contact your distributor for proper propane conversion kit.
CHECK BURNER FLAME With control access panel removed (See Fig. 24), observe the unit
heating operation. Watch the burner flames to see if they are light blue and soft in appearance, and that the flames are approximately the same for each burner. Propane will have blue flame (See Fig.
21). Refer to the Maintenance section for information on burner removal.
Pipe Plug
Manifold
A09082
Fig. 20 -- Burner Assembly
577D-- --A
27
BURNER FLAME
BURNER
Fig. 21 -- Monoport Burner
LIMIT SWITCHES
Normally closed limit switch (LS) completes the control circuit. Should the leaving--air temperature rise above the maximum allowable temperature, the limit switch opens and the control circuit “breaks.” Any interruption in the control circuit instantly
577D-- --A
closes the gas valve and stops gas flow to the burners. The blower motor continues to run until LS resets. The furnace board STATUS LED will display STATUS CODE 33.
When the air temperature at the limit switch drops to the low--temperature setting of the limit switch, the switch closes and completes the control circuit. The direct-- spark ignition system cycles and the unit returns to normal heating operation.
ROLLOUT SWITCH
The function of the rollout switch is to close the main gas valve in the event of flame rollout. The switch is located above the main burners. When the temperature at the rollout switch reaches the maximum allowable temperature, the control circuit trips, closing the gas valve and stopping gas flow to the burners. The indoor fan motor (IFM) continues to run until switch is reset. The furnace board STATUS LED will display STATUS CODE 33.
CONTINUOUS FAN MODE When continuous fan operation is requested by the UI indoor fan
motor will operate at continuous blower airflow. Continuous fan operation is programmable. See the UI Owner’s Manual for detailed instructions. Terminal EAC--1 is energized as long as the indoor fan motor is energized.
During a call for gas heat, the Evolution control will transition the indoor fan motor to continuous blower airflow or gas heat airflow, whichever is lowest. The indoor fan motor will remain ON until the burners ignite, then shut OFF and remain OFF for the blower--ON delay allowing the heat exchangers to heat up more quickly, then restarts at the end of the blower--ON delay period.
The indoor fan motor will revert to continuous--blower airflow after the gas heating cycle is completed.
When the UI “calls for cooling”, the indoor fan motor will switch to operate at cooling airflow. When the call for cooling is satisfied, the indoor fan motor will operate an additional 90 seconds at cooling airflow before transitioning back to continuous-- blower airflow.
When the call for continuous fan is removed, the indoor blower will continue operating for an additional 5 seconds before shutting down, if no other function requires blower motor operation.
MANIFOLD
C99021
COMPONENT TEST
The Evolution Furnace Board features a gas component test system to help diagnose a system problem in the case of a gas component failure. To initiate the component test procedure, ensure that there are no UI inputs to the control (the ABCD connector can be removed from the Evolution control board for this operation) and all time delays have expired. Turn on setup switch SW1--6.
NOTE: The component test feature will not operate if the control is receiving any UI signals or until all time delays have expired.
The component test sequence is as follows:
1. The control turns the inducer motor ON and keeps it ON
through step 3.
2. After waiting 10 seconds, the control turns the igniter ON
for 15 seconds, then OFF.
3. The control then turns the indoor fan motor on for 15
seconds, then OFF.
4. After shutting the blower motor OFF, the control runs the
inducer for 10 seconds, then turns it OFF.
NOTE: The EAC terminals are energized when the blower is operating.
After the component test is completed, one or more status codes (11, 25, or 41) will flash. See component test section or Status Code Label for explanation of status codes.
NOTE: To repeat component test, turn setup switch SW1--6 to OFF and then back ON.
Check for Refrigerant Leaks
Locate and repair refrigerant leaks and charge the unit as follows:
1. Use both high-- and low--pressure ports to relieve system
pressure and reclaim remaining refrigerant.
2. Repair leak following accepted practices.
NOTE: Install a filter drier whenever the system has been opened for repair.
3. Check system for leaks using an approved method.
4. Evacuate refrigerant system and reclaim refrigerant if no
additional leaks are found.
5. Charge unit with Puron (R--410A) refrigerant, using an
accurate scale. Refer to unit rating plate for required charge.
Start--Up Adjustments
Complete the required procedures given in the Pre--Start--Up section before starting the unit. Do not jumper any safety devices when operating the unit. Do not operate the unit in cooling mode when the outdoor temperature is below 40°F(4°C) (unless low--ambient operation is enabled in the UI). Do not rapid cycle the compressor. Allow 5 min. between “on” cycles to prevent compressor damage.
CHECKING COOLING AND HEATING CONTROL OPERATION
See UI Installation Instructions for detailed system CHECKOUT. CHECKING AND ADJUSTING REFRIGERANT CHARGE The refrigerant system is fully charged with Puron (R-- 410A)
refrigerant and is tested and factory sealed. NOTE: Any adjustment to refrigerant charge must be done with
unit operating in HIGH stage.
NOTE: Adjustment of the refrigerant charge is not required unless the unit is suspected of not having the proper R--410A charge. The charging label and the tables shown refer to system temperatures and pressures in cooling mode only. A refrigerant charging label is attached to the outside of the unit.
28
Table 6 – Heating Inputs
ORIFICES
HEATING INPUT (BT U/HR)*
High Stage Low Stage
40,000 26,000 2 4.0 13.0 3.23.8 1.4 ∼ 2.0 60,000 39,000 3 4.0 13.0 3.23.8 1.4 ∼ 2.0
90,000 58,500 3 4.0 13.0 3.23.8 1.4 ∼ 2.0 115,000 75,000 3 4.0 13.0 3.23.8 1.4 ∼ 2.0 130,000 84,500 3 4.0 13.0 3.23.8 1.4 ∼ 2.0
*Cubic ft of n atural gas per hour for gas pressures of .5 psig (14 IN. W.C.) or l ess and a pressure drop of .5 IN. W.C. (based on a .60 specific gravity gas). Ref: Table 6.2 (b) NPFA 54 / ANSI Z223.1 --- 2009.
NUMBER OF
GAS SUPPLY PRESSURE (IN. W.C.) MANIFOLD PRESSURE (IN. W.C.)
Natural Natural
Min Max High Stage Low Stage
Table 7 – ECM Wet Co il Pressure Drop (IN. W.C.)
UNIT SIZE
600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100
24 0.005 0.007 0.010 0.012 0.015
30 0.007 0.010 0.012 0.015 0.018 0.021 0.024
36 0.019 0.023 0.027 0.032 0.037 0.042 0.047
42 0.014 0.017 0.020 0.024 0.027 0.031 0.035 0.039 0.043
48 0.027 0.032 0.036 0.041 0.046 0.052 0.057 0.063 0.068
60 0.029 0.032 0.036 0.040 0.045 0.049 0.053
STANDARD CFM (SCFM)
Table 8 – Filter Pressure Drop Table (IN. W.C.)
FILTER SIZE
in. (mm)
20X20X1
(508x508x25)
24X30X1
(610x762x25)
24X36X1
(610x914x25)
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300
0.05 0.07 0.08 0.1 0.12 0.13 0.14 0.15
0.05 0.6 0.07 0.07 0.08 0.09 0.1
0.06 0.07 0.07 0.08 0.09 0.09 0.10 0.11 0.12 0.13 0.14 0.14
CFM
577D-- --A
IMPORTANT: When evaluating the refrigerant charge, an indicated adjustment to the specified factory charge must always be very minimal. If a substantial adjustment is indicated, an abnormal condition exists somewhere in the cooling system, such as insufficient airflow across either coil or both coils.
REFRIGERANT CHARGE The amount of refrigerant charge is listed on the unit rating plate
and/or the physical data table. Refer to the Refrigeration Service Techniques Manual, Refrigerants Section.
NO CHARGE
Check for leak. Use standard evacuating techniques. After evacuating system, weigh in the specified amount of refrigerant (refer to system rating plate).
LOW CHARGE COOLING Use Cooling Charging Chart (Fig. 23). Vary refrigerant until the
conditions of the chart are met. Note that charging charts are different from type normally used. Charts are based on charging the units to correct subcooling for the various operating conditions. Accurate pressure gauge and temperature sensing devices are required. Connect the pressure gauge to the service port on the suction line. Mount the temperature sensing device on the suction line and insulate it so that the outdoor ambient does not affect the reading. Indoor air CFM must be within the normal operating range of the unit.
TO USE COOLING CHARGING CHARTS
Take the liquid line temperature and read the manifold pressure gauges.
Refer to the chart to determine what the liquid line temperature should be.
NOTE: If the problem causing the inaccurate readings is a refrigerant leak, refer to Check for Refrigerant Leaks section.
NON-- COMMUNICATING EMERGENCY COOLING / HEATING MODE: 4--WIRE THERMOSTAT
This mode of operation is provided only in the case where the UI has failed or is otherwise unavailable. If communications cannot be established with the UI, the Evolution furnace board will enable the standard thermostat input terminals to allow simple thermostatic control of the 577D-- -- A unit.
For control with a standard thermostat, disconnect the ABCD connectors from both control boards and using No. 18 AWG color--coded, insulated type 90°C minimum or equivalent wire, make the connections between the standard thermostat, the furnace board, and the HP/AC board per Fig. 22. Recommend the use of interconnecting wire with 105C, 600V, 2/64” insulation.
The Evolution control will respond to cooling and heating demands with the maximum safe airflow based on gas furnace output and unit cooling capacity.
29
577D-- --A
A06360
Fig. 22 -- Non-- Communicating Emergency Cooling/Heating Wiring Connections
Fig. 23 -- Cooling Charging Table--Subcooling
30
A09109
MAINTENANCE
To ensure continuing high performance, and to minimize the possibility of premature equipment failure, periodic maintenance must be performed on this equipment. This packaged unit should be inspected at least once each year by a qualified service person. To troubleshoot unit, refer to Table 9 and 10, Troubleshooting Chart.
NOTE TO EQUIPMENT OWNER: Consult your local dealer about the availability of a maintenance contract.
!
WARNING
PERSONAL INJURY AND UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death and possible unit component damage.
The ability to properly perform maintenance on this equipment requires certain expertise, mechanical skills, tools and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment, other than those procedures recommended in the Owner’s Manual.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow these warnings could result in personal injury or death:
1. Turn off electrical power to the unit and install lockout tag before performing any maintenance or service on this unit.
2. Use extreme caution when removing panels and parts.
3. Never place anything combustible either on or in contact with the unit.
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Errors made when reconnecting wires may cause improper and dangerous operation. Label all wires prior to disconnecting when servicing.
The minimum maintenance requirements for this equipment are as follows:
1. Inspect air filter(s) each month. Clean or replace when necessary.
2. Inspect indoor coil, drain pan, and condensate drain each cooling season for cleanliness. Clean when necessary.
3. Inspect indoor fan motor and wheel for cleanliness each cooling season. Clean when necessary.
4. Check electrical connections for tightness and controls for proper operation each cooling season. Service when necessary.
5. Check for restrictions on inducer outlet. Clean flue hood.
6. Inspect burner compartment before each heating season for rust, corrosion, soot or excessive dust.
7. Inspect all accessories. Perform any service or maintenance to the accessories as recommended in the accessory instructions.
Air Filter
IMPORTANT: Never operate the unit without a suitable air filter
in the return--air duct system. Always replace the filter with the same dimensional size and type as originally installed. See Table 1 for recommended filter sizes.
Inspect air filter(s) at least once each month and replace (throwaway--type) or clean (cleanable--type) at least twice during each cooling season and twice during the heating season, or whenever the filter becomes clogged with dust and lint.
Indoor Fan and Motor
NOTE: All motors are pre--lubricated. Do not attempt to lubricate
these motors.
For longer life, operating economy, and continuing efficiency, clean accumulated dirt and grease from the blower wheel and motor annually.
Inducer Blower
NOTE: All motors are pre--lubricated. Do not attempt to lubricate
these motors.
Clean periodically to assure proper airflow and heating efficiency. Inspect blower wheel every fall and periodically during the heating season. For the first heating season, inspect blower wheel bi--monthly to determine proper cleaning frequency.
Limit Switch
Remove unit access panel to gain access to the limit switch. The limit switch is located above the indoor blower housing.
NOTE: On small chassis units, a second limit switch is located beside the indoor blower housing.
Burner Ignition
Unit is equipped with a direct spark ignition 100 percent lockout system. Ignition module is located in the control box. Refer to additional information in the Start--Up & Troubleshooting section for Status Code information.
Main Burners
At the beginning of each heating season, inspect for deterioration or blockage due to corrosion or other causes. Observe the main burner flames and adjust, if necessary.
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
When servicing gas train, do not hit or plug orifice spuds.
Removal of Gas Train To remove the gas train for servicing:
1. Shut off main gas valve.
2. Shut off power to unit and install lockout tag.
3. Remove control access panel (See Fig. 24).
4. Disconnect gas piping at unit gas valve.
5. Remove fan partition mounting bracket (2 screws located on the left side of control compartment on the fan partition panel). Slide bracket forward, bottom first, to remove. (See Fig. 25.)
6. Remove wires connected to gas valve. Mark each wire.
7. Remove the mounting screw that attaches the burner rack to the unit base (See Fig. 25).
CAUTION
577D-- --A
31
8. Partially slide the burner rack out of the unit (see Fig. 25 and 26). Remove ignitor and sensor wires at the burner as­sembly. Remove wires to rollout switch.
9. Slide the burner rack out of the unit (See Fig. 25 and 26).
10. To reinstall, reverse the procedure outlined above.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
!
WARNING
injury or death.
Disconnect and install lockout tag on electrical power to the unit before cleaning and lubricating the blower motor and wheel.
Outdoor Coil, Indoor Coil, and Condensate Drain Pan
Inspect the condenser coil, evaporator coil, and condensate drain pan at least once each year.
The coils are easily cleaned when dry; therefore, inspect and clean the coils either before or after each cooling season. Remove all obstructions, including weeds and shrubs, that interfere with the airflow through the condenser coil. Straighten bent fins with a fin comb. If coated with dirt or lint, clean the coils with a vacuum cleaner, using the soft brush attachment. Be careful not to bend the fins. If coated with oil or grease, clean the coils with a mild
577D-- --A
Compressor Access Panel
Blower Access Panel
Control Access Panel
A09479
Fig. 24 -- Unit Access Panels
Integrated Gas Unit Controller (IGC)
Auto Transformer fuses used on 460 volt units only. (Hidden)
Interface Fan Board (IFB)
Induced Draft Motor
Fan Partition Mounting Bracket
Flue Collector Box
Inducer Blower Housing
Burner Rack
Mounting Screw
Rollout Switch
A09480
Fig. 25 -- Blower Housing and Flue Collector Box
detergent and water solution. Rinse coils with clear water, using a garden hose. Be careful not to splash water on motors, insulation, wiring, or air filter(s). For best results, spray condenser coil fins from inside to outside the unit. On units with an outer and inner condenser coil, be sure to clean between the coils. Be sure to flush all dirt and debris from the unit base.
Inspect the drain pan and condensate drain line when inspecting the coils. Clean the drain pan and condensate drain by removing all foreign matter from the pan. Flush the pan and drain trough with clear water. Do not splash water on the insulation, motor, wiring, or air filter(s). If the drain trough is restricted, clear it with a “plumbers snake” or similar probe device.
Outdoor Fan
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in damage to unit components.
Keep the outdoor fan free from all obstructions to ensure proper cooling operation. Never place articles on top of the unit.
A07680
Fig. 26 -- Burner Rack Removed
Inducer Pressure Switch
Inspect pressure switch connections. Inspect pressure switch tube for cracks or restrictions. Replace if needed.
1. Remove 4 screws holding outdoor grille and motor to top cover.
2. Turn motor/grille assembly upside down on top cover to expose fan blade.
3. Inspect the fan blades for cracks or bends.
4. If fan needs to be removed, loosen setscrew and slide fan off motor shaft.
5. When replacing fan blade, position blade according to the table shown in Fig. 27.
6. Ensure that set screw engages the flat area on the motor shaft when tightening.
7. Replace grille.
Electrical Controls and Wiring
Inspect and check the electrical controls and wiring annually. Be sure to turn off the electrical power to the unit.
Remove access panel to locate all the electrical controls and wiring. Check all electrical connections for tightness. Tighten all screw connections. If any smoky or burned connections are noticed, disassemble the connection, clean all the parts, re--strip the wire end and reassemble the connection properly and securely.
32
After inspecting the electrical controls and wiring, replace all the panels. Start the unit, and observe at least one complete cooling cycle to ensure proper operation. If discrepancies are observed in operating cycle, or if a suspected malfunction has occurred, check each electrical component with the proper electrical instrumentation. Refer to the unit wiring label when making these checks.
A06132
UNIT SIZE “A” DIM. IN. (MM)
24 1 (26) 30 1 (26) 36 1 (26) 42 1 (26) 48 11/32 (9) 60 9/16 (14)
Fig. 27 -- Outdoor Fan Blade Clearance
Refrigerant Circuit
Inspect all refrigerant tubing connections and the unit base for oil accumulation annually. Detecting oil generally indicates a refrigerant leak.
If oil is detected or if low performance is suspected, leak test all refrigerant tubing using an electronic leak detector, or liquid--soap solution. If a refrigerant leak is detected, refer to Check for Refrigerant Leaks section.
If no refrigerant leaks are found and low performance is suspected, refer to Checking and Adjusting Refrigerant Charge section.
Indoor Airflow
The heating and/or cooling airflow does not require checking unless improper performance is suspected. If a problem exists, be sure that all supply-- and return--air grilles are open and free from obstructions, and that the air filter is clean.
Pressure Switches -- Refrigerant Circuit
Pressure switches are protective devices integrated into the control circuit (low voltage). They shut off compressor if abnormally high or low pressures are present in the refrigeration circuit. These pressure switches are specifically designed to operate with Puron (R--410A) systems. R--22 pressure switches must not be used as replacements for the Puron (R--410A) system.
Loss--of--Charge (Low Pressure)
This switch is located on the liquid line and protects against low suction pressures caused by such events as loss of charge, low airflow across indoor coil, dirty filters, etc. It opens if the system pressure drops to about 20 psig. If system pressure is above this, switch should be closed.
High--Pressure Switches (HPS & The high--pressure switches are located on the discharge line and
protects against excessive condenser coil pressure. HPS opens at 670 psig shutting down the compressor, while HPS2 opens at 565, limiting the compressor to low--stage operation only.
High pressure may be caused by a dirty outdoor coil, failed fan motor, or outdoor air recirculation.
To check switches:
1. Turn off all power to unit.
2. Disconnect leads on switch.
Switch
HPS2)
3. Apply ohm meter leads across switch. You should have continuity on a good switch.
NOTE: Because these switches are attached to refrigeration system under pressure, it is not advisable to remove this device for troubleshooting unless you are reasonably certain that a problem exists. If switch must be removed, remove and recover all system charge so that pressure gauges read 0 psi. Never open system without breaking vacuum with dry nitrogen.
Copeland Scroll Compressor (Puron Refrigerant)
The compressor used in this product is specifically designed to operate with Puron (R-- 410A) refrigerant and cannot be interchanged.
The compressor is an electrical, as well as mechanical, device. Exercise extreme caution when working near compressors. Power should be shut off, if possible, for most troubleshooting techniques. Refrigerants present additional safety hazards.
!
WARNING
EXPLOSION, FIRE HAZARD
Failure to follow this warning could result in personal injury or death and/or property damage.
Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils.
The scroll compressor pumps refrigerant throughout the system by the interaction of a stationary and an orbiting scroll. The scroll compressor has no dynamic suction or discharge valves, and it is more tolerant of stresses caused by debris, liquid slugging, and flooded starts. The compressor is equipped with noise reducing shutdown device and an internal pressure-- relief port. The pressure--relief port is a safety device, designed to protect against extreme high pressure. The relief port has an operating range between 550 and 625 psi differential pressure.
Refrigerant System
This step covers the refrigerant system of the 577D----A, including the compressor oil needed, servicing systems on roofs containing synthetic materials, the filter drier, and refrigerant charging.
REFRIGERANT
!
WARNING
UNIT OPERATION, SAFETY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could result in personal injury or equipment damage.
This system uses Puron (R--410A) refrigerant which has higher operating pressures than R--22 and other refrigerants. No other refrigerant may be used in this system. Gauge set, hoses, and recovery system must be designed to handle Puron. If you are unsure, consult the equipment manufacturer.
COMPRESSOR OIL
If additional oil is needed use Uniqema RL32--3MAF. If this oil is not available, use Copeland Ultra 32CC or Mobil Artic EAL22CC. This oil is extremely hygroscopic, meaning it absorbs water readily. POE oils can absorb 15 times as much water as other oils designed for HCFC and CFC refrigerants. Take all necessary precautions to avoid exposure of the oil to the atmosphere.
SERVICING SYSTEMS ON ROOFS WITH S YNTHETIC MATERIALS
POE (polyolester) compressor lubricants are known to cause long term damage to some synthetic roofing materials.
577D-- --A
33
Exposure, even if immediately clean ed up, may cause embrittlement (leading to cracking) to occur in one year or more. When performing any service that may risk exposure of compressor oil to the roof, take appropriate precautions to protect roofing. Procedures which risk oil leakage include, but are not limited to, compressor replacement, repairing refrigerant leaks, and replacing refrigerant components such as filter drier, pressure switch, metering device, coil, accumulator, or reversing valve.
Synthetic Roof Precautionary
1. Cover extended roof working area with an impermeable polyethylene (plastic) drip cloth or tarp. Cover an approximate 10 X 10 ft (3x3 m) area.
2. Cover area in front of the unit service panel with a terry cloth shop towel to absorb lubricant spills and prevent run--offs, and protect drop cloth from tears caused by tools or components.
3. Place terry cloth shop towel inside unit immediately under component(s) to be serviced and prevent lubricant run --offs through the louvered openings in the unit base.
4. Perform required service.
5. Remove and dispose of any oil--contaminated material per
577D-- --A
local codes.
LIQUID--LINE FILTER DRIER The filter drier is specifically designed to operate with Puron. Use
only factory--authorized components. Filter drier must be replaced whenever the refrigerant system is opened. When removing a filter drier, use a tubing cutter to cut the drier from the system. Do not unsweat a filter drier from the system. Heat from unsweating will release moisture and contaminants from drier into system.
PURON (R-- 410A) REFRIGERANT CHARGING Refer to unit information p late and charging chart. Some R --410A
refrigerant cylinders contain a dip tube to allow liquid refrigerant to flow from cylinder in upright position. For
cylinders equipped with a dip tube, charge Puron units with cylinder in upright position and a commercial metering device in manifold hose. Charge refrigerant into suction line.
Procedure
TROUBLESHOOTING
LED DESCRIPTION LEDs built into Evolution control boards provide installer or
service person information concerning operation and/or fault condition of the unit controls and ECM motor. This information is also available at the system UI in text with basic troubleshooting instructions. Careful use of information displayed will reduce the need for extensive manual troubleshooting. See section B in Start-- Up & Troubleshooting and Table 4, as well as the UI instructions, for additional information. Additional Troubleshooting information can be found in Table 9 and 10.
MAJOR COMPONENTS 2--STAGE HP/AC BOARD The two--stage HP/AC control board controls the following
functions:
-- Low-- and high-- stage compressor operation
-- Outdoor fan motor operation
-- Reversing valve operation
-- Defrost operation
-- Low ambient cooling
-- Crankcase heater operation
-- Compressor external protection
-- Pressure switch monitoring (refrigerant)
-- Time delays FURNACE BOARD The furnace board controls the following functions:
-- Indoor blower operation
-- G a s v a l v e
-- Inducer motor
-- Remote sparker module
-- Pressure switch monitoring (gas) SYSTEMS COMMUNICATION FAILURE If communication with the Evolution Control is lost with the UI,
the controls will flash the appropriate fault codes. Check the wiring to the UI, indoor and outdoor units.
MODEL PLUG The HP/AC control board must have a valid model plug to operate.
If a valid model plug is not detected, it will not operate and the control will flash the appropriate fault code, shown in Table 4.
PRESSURE SWITCH PROTECTION--REFRIGERANT
The unit is equipped with high-- and low--pressure switches. If the control senses the opening of a high-- or low--pressure switch, it will respond as follows:
1. De--energize the compressor contactor (HPS1 & LPS) or the compressor solenoid contactor (HPS2).
2. Keep the outdoor fan operating for 15 minutes.
3. Display the appropriate fault codes.
4. After a 15 minute delay, if there is still a call for cooling and the LPS or HPS is reset, the compressor contactor is energized.
5. If LPS or HPS has not closed after a 15 minute delay, the outdoor fan is turned off. If the open switch closes anytime after the 15--minute delay, then resume operation with a call for cooling.
6. If LPS or HPS trips 3 consecutive cycles, the unit operation is locked out for 4 hours.
7. In the event of a high--pressure switch trip or high pressure lockout, check the refrigerant charge, outdoor fan operation and outdoor coil for airflow restrictions.
8. In the event of a low--pressure switch trip or low pressure lockout, check the refrigerant charge and indoor airflow.
CONTROL FAULT
If the HP/AC control board has failed, the control will flash the appropriate fault code (See Table 4). The control board should be replaced.
BROWN OUT PROTECTION
If the line voltage is less than 187v for at least 4 seconds, the appropriate compressor contactor and fan relay are de--energized. Compressor and fan operation are not allowed until voltage is a minimum of 190v. The control will flash the appropriate fault code (See Table 4).
230V LINE (POWER DISCONNECT) DETECTION If there is no 230v at the compressor contactor when the unit is
powered and cooling demand exists, the appropriate error code is displayed. Verify that the disconnect is closed and 230v wiring is connected to the unit.
COMPRESSOR VOLTAGE SENSING The control board input terminals VS and L2 (See Fig. 18) are
used to detect compressor voltage status, and alert the user of potential problems. The control continuously monitors the high voltage on the run capacitor of the compressor motor. Voltage should be present any time the compressor contactor is energized, and voltage should not be present when the contactor is de--energized.
CONTACTOR SHORTED DETECTION If there is compressor voltage sensed when there is no demand for
compressor operation, the contactor may be stuck closed or there is a wiring error. The control will flash the appropriate fault code.
COMPRESSOR THERMAL CUTOUT If the control senses the compressor voltage after start-- up, and is
then absent for 10 consecutive seconds while cooling demand
34
exists, the thermal protector is open. The control de--energizes the compressor contactor for 15 minutes, but continues to operate the outdoor fan. The control Status LED will flash the appropriate code shown in Table 4. After 15 minutes, with a call for low or high stage cooling, the compressor contactor is energized. If the thermal protector has not re--set, the outdoor fan is turned off. If the call for cooling continues, the control will energize the compressor contactor every 15 minutes. If the thermal protector closes (at the next 15 minute interval), check the unit will resume operation.
If the thermal cutout trips for three consecutive cycles, then unit operation is locked out for 4 hours and the appropriate fault code is displayed.
NO 230V AT COMPRESSOR If the compressor voltage is not sensed when the compressor
should be starting, the contactor may be stuck open or there is a wiring error. The control will flash the appropriate fault code. Check the contactor and control box wiring.
TROUBLESHOOTING UNIT FOR PROPER SWITCHING BETWEEN LOW & HIGH STAGES
Check the suction pressures at the service valves. Suction pressure should be reduced by 3--10% when switching from low to high capacity.
NOTE: The liquid pressures are very similar between low and high stage operation, so liquid pressure should not be used for troubleshooting.
Compressor current should increase 20--45% when switching from low to high stage. The compressor solenoid, when energized in high stage, should measure 24vac.
COMPRESSOR INTERNAL RELIEF The compressor is protected by an internal pressure relief (IPR)
which relieves discharge gas into compressor shell when differential between suction and discharge pressures exceeds 550 -­625 psi. The compressor is also protected by an internal overload attached to motor windings.
TEMPERATURE THERMISTORS
Thermistors are electronic devices which sense temperature. As the temperature increases, the resistance decreases. Thermistors are used to sense outdoor ambient (OAT) and coil temperature (OCT). Refer to Fig. 28 for resistance values versus temperature. See Fig. 29 for OCT location.
If the outdoor ambient or coil thermistor should fail, the HP/AC control will flash the appropriate fault code (See Table 4).
IMPORTANT: Coil thermistor is factory mounted. Check to insure thermistor is mounted properly. Outdoor air thermistor (OAT) is field mounted and connected. Verify that the OAT has been properly installed.
THERMISTOR SENSOR COMPARISON
The control continuously monitors and compares the outdoor air temperature sensor and outdoor coil temperature sensor to ensure proper operating conditions. The comparison is:
S In cooling mode, if the outdoor air sensor indicates 10 _F
(5.5_C) warmer than the coil sensor (or) the outdoor air sensor indicates 20_F(11.0_C) cooler than the coil sensor, the sensors
are out of range.
S In heating if the outdoor air sensor indicates 35_F (19.3_C)
warmer than the coil sensor (or) the outdoor air sensor indicates 10_F(5.5_C) cooler than the coil sensor, the sensors are out of
range.
If the sensors are out of range, the control will flash the appropriate fault code as shown in Table 4.
The thermistor comparison is not performed during low ambient cooling operation.
FAILED THERMISTOR DEFAULT OPERATION
Factory defaults have been provided in the event of failure of outdoor air thermistor and/or coil thermistor.
If the OAT sensor should fail, low ambient cooling will not be allowed and the one-- minute outdoor fan off delay will not occur. Defrost will be initiated based on coil temperature and time.
If the OCT sensor should fail, low ambient cooling will not be allowed. Defrost will occur at each time interval during heating operation, but will terminate after 5 minutes.
If there is a thermistor out of range error, defrost will occur at each time interval during heating operation, but will terminate after 5 minutes.
Refer to the Troubleshooting Chart (Table 9 and 10) for additional troubleshooting information.
577D-- --A
THERMISTOR CURVE
90 80
70
60
50
40 30 20
RESISTANCE (KOHMS)
10
0
0 20 40 60 80 100 120
TEMPERATURE (DEG. F)
Fig. 28 -- Resistance Values Versus Temperature
A91431
A06311
Fig. 29 -- Outdoor Coil Thermistor (OCT) Attachment
FINAL CHECKS
IMPORTANT: Before leaving job, be sure to do the following:
1. Ensure that all wiring is routed away from tubing and sheet metal edges to prevent rub--through or wire pinching.
2. Ensure that all wiring and tubing is secure in unit before adding panels and covers. Securely fasten all panels and covers.
3. Tighten service valve stem caps to 1/2--turn past finger tight.
4. Leave Users Manual with owner. Explain system operation and periodic maintenance requirements outlined in manual.
5. Fill out Start--Up Checklist located at the back of this manual and place in customer file.
35
CARE AND MAINTENANCE
For continuing high performance and to minimize possible equipment failure, periodic maintenance must be performed on this equipment.
Frequency of maintenance may vary depending upon geographic areas, such as coastal applications. See Users Manual for information.
577D-- --A
36
AIR CONDITIONER WITH PURON
REFRIGERATION SECTION QUICK--REFERENCE GUIDE
Puron refrigerant operates at 50-- 70 percent higher pressures than R-- 22. Be sure that servicing equipment and replacement components are designed to operate with Puron. Puron refrigerant cylinders are rose colored.
S Puron refrigerant cylinders manufactured prior to March 1, 1999, have a dip tube that allows liquid to flow out of cylinder in upright
position. Cylinders manufactured March 1, 1999 and later DO NOT have a dip tube and MUST be positioned upside down to allow liquid
to flow.
S Recovery cylinder service pressure rating must be 400 psig. DOT 4BA400 or DOT BW400. S Puron systems should be charged with liquid refrigerant. Use a commercial--type metering device in the manifold hose. S Manifold sets should be minimum 700 psig high side and 180 psig low side with 550 psig low side retard. S Use hoses with minimum 700 psig service pressure rating. S Leak detectors should be designed to detect HFC refrigerant. S Puron, as with other HFCs, is only compatible with POE oils. S Vacuum pumps will not remove moisture from oil. S Only use factory--specified liquid--line filter driers with rated working pressures no less than 600 psig. S Do not install a suction--line filter drier in liquid line. S POE oils absorb moisture rapidly. Do not expose oil to atmosphere. S POE oils may cause damage to certain plastics and roofing materials. S Wrap all filter driers and service valves with wet cloth when brazing. S A Puron liquid-- line filter drier is required on every unit. S Do not use an R --22 TXV. S Never open system to atmosphere while it is under a vacuum. S When system must be opened for service, break vacuum with dry nitrogen and replace filter driers. S Do not vent Puron into the atmosphere. S Observe all warnings, cautions, and bold text. S Do not leave Puron suction line driers in place for more than 72 hrs.
577D-- --A
37
Table 9 – Troubleshooting Chart -- Cooling
SYMPTOM CAUSE REMEDY
Compressor and outdoor fan will not start
Compressor will not start but condenser fan runs
577D-- --A
Compressor cycles (other than normally sat­isfying) cooling/heating calls
Compressor operates continuously
Excessive head pressure
Head pressure too low
Excessive suction pressure
Suction pressure too low
IFM does not run
IFM operation is intermittent
Power failure Call power company Fuse blown or circuit breaker tripped Replace fuse or reset circuit breaker
Defective contactor, transformer, control relay, or high-­pressure, loss--of--charge or low-- pressure switch
Insufficient line voltage Determine cause and correct
Incorrect or faulty wiring Check wiring diagram and rewire correctly
UI setting too low/too high ResetUIsetting
Units have a 5--minute time delay
Faulty wiring or circuit Loose connections in compressor
Compressor motor burned out, seized, or Determine cause internal overload open Replace compressor Defective run capacitor, overload, or PTC (positive
temperature coefficient) thermistor Low input voltage (20 percent low) Determine cause and correct
Refrigerant overcharge or undercharge
Defective compressor Replace and determine cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run/start capacitor, overload or start relay Determine cause and replace Faulty outdoor fan motor or capacitor Replace Restriction in refrigerant system Locate restriction and remove Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size UI temperature set too low ResetUIsetting Low refrigerant charge Locate leak, repair, and recharge
Air in system
Outdoor coil dirty or restricted Clean coil or remove restriction Dirty air filter Replace filter Dirty indoor or outdoor coil Clean coil Refrigerant overcharged Recover excess refrigerant
Air in system
Indoor or outdoor air restricted or air short--cycling Determine cause and correct Low refrigerant charge Check for leaks, repair and recharge Restriction in liquid tube Remove restriction High heat load Check for source and eliminate Reversing valve hung up or leaking internally Replace valve Refrigerant overcharged Recover excess refrigerant Dirty air filter Replace filter Low refrigerant charge Check for leaks, repair and recharge Metering device or low side restricted Remove source of restriction Insufficient c oil airflow Check filter–replace if necessary Temperature too low in conditioned area ResetUIsetting Outdoor ambient below 55°F(13°C) Verify low--ambient cooling enabled in UI Filter drier r estricted Replace Blower wheel not secured to shaft Properly tighten blower wheel to shaft Insufficient voltage at motor Determine cause and correct Power connectors not properly sealed Connectors should snap easily; do not force Water dripping into motor Verify proper drip loops in connector wires
Connectors not firmly sealed
Replace component
DO NOT bypass this compressor time delay–wait for 5 minutes until time--delay relay is de--energized
Check wiring and repair or replace
Determine cause and replace
Recover refrigerant, evacuate system, and re­charge to capacities shown on rating plate
Recover refrigerant, evacuate system, and re­charge
Recover refrigerant, evacuate system, and re­charge
Gently pull wires individually to be sure they are crimped into the housing
38
SYMPTOM CAUSE REMEDY
Burners w ill not ignite
Inadequate heating
Poor flame characteristics
Table 10 – Troubleshooting Chart -- Gas Furnace Operation
Water in gas line Drain. Install drip leg.
No power to unit
No 24--v power supply to control circuit
Mis-- wired or loose connections Check all wiring and wire nut connections
Misaligned spark electrodes
No gas at main burners
Inducer pressure switch not closing
Dirty air filter Clean or replace filter as necessary
Gas input to unit too low
Unit undersized for application Replace with proper unit or add additional unit Restricted airflow Clean or replace filter. Remove any restriction.
Limit switch cycles main burners
Incomplete combustion results in: Aldehyde odors, carbon monoxide, sooting flame, floating flame
Check power supply fuses, wiring or circuit breaker.
Check transformer. NOTE: Some transformers have internal over-­current protection that requires a cool--down peri­od to reset.
Check flame ignition and sense electrode posi­tioning. Adjust as necessary.
1. Check gas line for air. Purge as necessary. NOTE: After purging gas line of air, wait at least 5 minutes for any gas to dissipate before attempt­ing to light unit.
2. Check gas valve.
1. Check pressure switch wires, connections, and tubing. Repair or replace if necessary.
Check gas pressure at manifold match with that on unit nameplate
Check rotation of blower, temperature rise of unit. Adjust as necessary.
1. Tighten all screws around burner compartment
2. Cracked heat exchanger. Replace.
3. Unit over--fired. Reduce input (change orifices or adjust gas line or manifold pressure).
4. Check burner alignment.
5. Inspect heat exchanger for blockage. Clean as necessary.
577D-- --A
39
START--UP CHECKLIST
(Remove and Store in Job Files)
I. PRELIMINARY INFORMATION
MODEL NO.:
SERIAL NO.: DATE:
TECHNICIAN:
II. PRESTART-- UP (Insert check mark in box as each item is completed)
( ) VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
( ) REMOVE ALL SHIPPING HOLD DOWN BOLTS AND BRACKETS PER INSTALLATION INSTRUCTIONS ( ) CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS ( ) CHECK GAS PIPING FOR LEAKS (WHERE APPLICABLE)
( ) CHECK THAT INDOOR (EVAPORATOR) AIR FILTER IS CLEAN AND IN PLACE ( ) VERIFY THAT UNIT INSTALLATION IS LEVEL
( ) CHECK FAN WHEEL, AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS ( ) MAKE SURE THAT -- (If Applicable) ON A60 SIZE PURON HEAT PUMP ONLY, THE TWO WIRE TIRES FASTEN TO THE
OUTDOOR COILS AND REVERSING VALVE/ACCUMULATOR HAVE BEEN REMOVED
III. START--UP
577D-- --A
ELECTRICAL
SUPPLY VOLTAGE
COMPRESSOR AMPS INDOOR (EVAPORATOR) FAN AMPS
TEMPERATURES
OUTDOOR (CONDENSER) AIR TEMPERATURE DB RETURN-- AIR TEMPERATURE DB WB
COOLING SUPPLY AIR DB WB GAS HEAT SUPPLY AIR
PRESSURES
GAS INLET PRESSURE IN. W.C. GAS MANIFOLD PRESSURE IN. W.C.
REFRIGERANT SUCTION PSIG, SUCTION LINE TEMP* REFRIGERANT DISCHARGE PSIG, LIQUID TEMP{ ( ) VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS
GAS HEAT TEMPERATURE RISE TEMPERATURE RISE (See Literature) RANGE
MEASURED TEMPERATURE RISE ( ) VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PROPERLY
( ) VERIFY THAT OUTDOOR AIR THERMISTOR (OAT) IS PROPERLY INSTALLED & CONNECTED
* Measured at suction inlet to compressor
{ Measured at liquid line leaving condenser.
E2010 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231 Edition Date: 04/ 10
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
40
Catalog No. II577D---06
Replaces: II577D--- 05
Loading...