1. Read and become familiar with these installation
instructions before installing this unit (Fig. 1).
2. Be sure the installation conforms to all applicable
local and national codes.
3. These instructions contai n importa nt inform ation for
the proper maintenance and repair of this equipment.
Retain these instructions for future u se.
alteration, service, maintenance, or use can cause
explosion, fire, electric shock, or other occurrences
which may injure you or damage your property. Consult a qualified installer or service agency for information or assistance. The qualified installer or agency
must use only factory-authorized kits or accessories
when repairing th is pro duc t .
569C
576B
Cancels: II 569C-72-4II 569C-72-5
8/15/00
Fig. 1 — Typical Unit (569C072 Shown)
Recognize safety information. This is the safety-alert symbol. () When you see this symbol on the unit and in
instructions or manuals, be alert to the potential for personal injury.
Understand the signal words — DANGER, WARNING, and
CAUTION. These words are used with the safety-alert symbol. Danger id entifies the most serious h azards which will
result in severe perso nal injury or death. Warning indicates
a condition that could result in pers onal injury. Caution is
used to identify unsafe practices whic h would res ult in minor
personal injury or product and property damage.
WARNING: Before performing service or maintenance operations on unit, turn off main power switch
to unit. Electrical shock could cause personal injury.
1. The power supply (volts, hertz, and phase) must correspond to that specified on unit rating plate.
2. The electric al supply provi ded by the utili ty must be
sufficient to handle load imposed by this unit.
3. Refer to the Locate the Unit section on page 2 and
Fig. 2 and 3 for locations of electrical inlets, required
clearances, and weight distributio n based on recommended support points before setting unit in place.
4. This installation must conform with local building
codes. Refer to local plumbing or wastewater codes
and other applicable local codes.
INSTALLATION
NOTE: When installing any accessory item, see the manufac-
turer’s installation instructions packaged with the accessory.
A qualified agenc y must us e f ac tor y - au th or iz e d kits or accessories when modif ying this unit.
The 569C072,090, and 120 units use hermetic compressors.
The 576B090,102, and 120 units use semi-hermetic compre ssors. Refer to Table 1.
NOTE: If vibration isolators are required for a particular
installation, use corner weight information in Fig. 2 to make
proper selection.
I. LOCATE THE UNIT
A. Clearance
Maintain cleara nce around and abo ve unit to provide mi nimum distance from combustible materials, proper airflow,
and service access. Refer to Fig. 2.
Minimum clearance (local codes or jurisdiction may prevail):
a. Bottom to combustible sur fac e s 0 inches.
b. Condenser coil, for proper airflow, 36 in. one side, 12 in.
the other. The left or rear side receiving the greater clearance is optional.
c. Overhead, 60 in. to ensure proper condenser fan
operation.
d. Between units, control box side, 42 in. per NEC (National
Electrical Code).
e. Between unit and ungrounded surfaces, control box side,
36 in. per NEC.
f. Between unit and block or concrete walls and other
grounded surfaces, control box side, 42 in. per NEC.
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
Slab-mounted units sho uld be a t least 4 in. abo ve the hig hest
expected water level (flood and runoff). Do not use the unit if
it has been under water.
II. RIG AND PLACE UNIT
Inspect unit for transportation damage. File any claim with
transportation agency. Keep unit upright and do not drop.
Spreader bars are not required if top crating is left on unit.
Rollers may be used to move unit across a roof. Level by
using unit frame as a reference. See Table 1 and Fig. 3
for additional information. Operating weight is shown in
Table 1.
These units are d esigned for o verhead rigg ing only. Rig with
packaging assembly and wood bumper strips in place to prevent unit damage by rigging cab le. As further protection for
coil faces, plywood sheets may be placed against sides of
unit, behind cables. Run cables to a central suspension point
so that angle from the horizontal is not less than 45 degrees.
Raise and set unit down carefully.
If it is necessary to roll unit into position, mount unit on longitudinal rails, using a minimum of 3 rollers. Apply force torails, not unit. If unit is to be skidded into position, place it
on a large pad and drag it by the pad. Do not apply any force
to unit.
Raise from above to lift unit from rails or pad when unit is in
final position.
Lifting holes are provided in base rails as shown in Fig. 3.
Refer to rigging instructions on unit.
IMPORTANT: If unit has forklift protection skids, be sure to
remove forklift protection skids from under unit before setting unit in place.
After unit is in position, remove shipping materials and rigging skids.
III. COMPRESSOR MOUNTING
Semi-hermetic compressors are shipped from the factory
held down by 4 bolts. After unit is installed, loosen each bolt
until the snubber washer can be moved with finger pressure
(576B units only). See Fig. 4.
IV. UNIT REFRIGERANT PIPING CONNECTIONS
Suction connections and liquid connection are sweat fittings.
Refer to Table 2 for refrigerant piping sizes. Follow standard
piping practices.
A. Size Refrigerant Lines
Consider length of piping required between condensing unit
and evaporator, amount of liquid lift, and compressor oil
return. See Table 3 for design details and line sizing. Refer
to evaporator installation instructions for additional
information.
Rows...Fins/in.
Face Area (sq ft)
Storage Capacity (lb)**
CONNECTIONS (sweat)
Suction (in.)
Liquid (in.)
12.2418.020.5018.018.018.0
11.2616.5618.8716.5616.5616.56
1
1
/
8
1
/
2
CONTROLS
Pressurestat Settings (psig)
High Cutout
Cut-in
Low Cutout
Cut-in
LEGEND
NEMA —
*Unit is factory supplied with holding charge only.
†Typical operating charge with 25 ft of interconnecting piping.
National Electrical Manufacturers Association
1
/
2
1071/
2
81/
2
R-22
Scroll, HermeticReciprocating, Semi-Hermetic
Propeller; Direct Drive
3
/
4
3
/
4
3
/
4
3
/
4
Enhanced Copper Tubes, Aluminum Lanced Fins
2...17
11/
1
8
/
2
11/
5
8
/
8
320 ± 20
426 ± 7
11/
8
1
/
2
11/
8
5
/
8
7 ± 3
22 ± 5
**Storage capacity of condenser coil with coil 80% full of liquid R-22 at
124 F.
NOTE:
Unit 576B120 has one step of unloading. Full load is 100% of
capacity, and one step of unloading is 67% capacity. Unit 576B120 has
the following unloader settings: load is 70 ± 1 psig and unload is 60
± 2 psig.
10
1...06DH824
(See Note)
3
/
4
11/
8
5
/
8
—3—
DIMENSIONS (ft-in.)
UNITABCDEF
ELECTRICAL CONNECTIONS
With Aluminum Coils (Standard)
569C072
569C090
569C120
576B090
576B102
576B120
1
1-6
/21-23/
1-81-6
1
—1-21/41-45/162-95/
4
/22-913/
1-32-5/163-57/
16
1-91-82-01-32-
1-61-4
1-71-52-9
1-71-52-9
3
/42-913/
1-32-5/163-57/
16
13
/
1-32-5/163-57/
16
13
/
1-32-5/163-57/
16
5
/163-57/
With Copper Coils (Optional)
569C072
569C090
569C120
576B090
576B102
576B120
1-81-3—1-2
1
1-9
/
1-62-913/
2
16
1-101-72-01-32-
1
1-7
/21-41/22-913/
1
1-7
/
1-42-913/
2
1
1-7
/
1-42-913/
2
16
16
16
1
/41-45/162-95/
1-32-5/163-57/
5
/163-57/
1-32-5/163-57/
1-32-5/163-57/
1-32-5/163-57/
CONNECTION SIZES
3
AA
16
16
16
16
16
16
BB
CC
DD
SERVICE VALVE CONNECTIONS
UNITSUCTIONLIQUID
569C072
569C090
569C120
16
16
16
16
16
16
576B090
576B102
576B120
WEIGHT CHART (lb)
UNIT
569C072
569C090
569C120
576B090
576B102
576B120
UNIT
569C072
569C090
569C120
576B090
576B102
576B120
NOTE:
Al indicates weight with aluminum-fin coil (standard);
Cu indicates weight with copper-fin coil (optional).
NOTES:
1. Dimensions in [ ] are in millimeters.
2.Center of Gravity. See chart for dimensions.
3.Direction of airflow.
4. Minimum clearance (local codes or jurisdiction may prevail):
a. Bottom to combustible surfaces, 0 inches.
b. Either left or rear side of condensing unit must have 36-in. clearance for proper airflow;
the remaining side(s) must have 12-in. clearance each.
c. Overhead, 60 in., to assure proper condenser fan operation.
d. Between units, control box side, 42 in. per NEC (National Electrical Code).
e. Between unit and ungrounded surfaces, control box side, 36 in. per NEC.
f. Between unit and block or concrete walls and other grounded surfaces, control box side,
42 in. per NEC.
5. With the exception of the clearance for the condenser coil as stated in Note 4b, a removable
fence or barricade requires no clearance.
6. Units may be installed on combustible floors made from wood or Class A, B, or C roof covering material.
7. Certified dimension drawings available on request.
″
Dia Field Power Supply Hole
/
1
8
2″ Dia Power Supply Knockout
1
″
Dia Power Supply Knockout
/
2
2
7
″
Dia Field Control Wiring Hole
/
8
1
″
/
1
8
1
″
/
1
8
1
″
1
/
8
1
″
/
1
8
1
″
/
1
8
1
″
1
/
8
1
″
/
2
1
″
/
2
5
″
/
8
1
″
/
2
5
″
/
8
5
″
/
8
Fig. 2 — Base Unit Dimensions
—4—
HOOK RIGGING SHACKLES THROUGH HOLES IN BA SE RAIL, ON ALL FOUR SIDES.
HOLES IN BASE RAILS ARE CENTERED AROUND THE UNIT CEN TER OF GRAVITY. USE
WOODEN TOP SKID, WHEN RIGGING, TO PREVENT RIGGING STRAPS FROM DAMAGING
UNIT.
The filter drier is factory installed. Moisture indicator is a
field-installed accessory and should be installed just after
liquid line shu toff valve at th e evaporator coil. Do not use areceiver. A receiver is not supplied with the unit and should
not be used.
NOTE: Unit is shipped with R-22 holding charge. System
pressure must be relieved before removing caps. Recover
refrigerant prior to brazing.
Pass nitrogen or other inert gas through piping while brazing to prevent formation of copper oxide.
Install field-supplied thermostatic expansion valve(s) in
evaporator section. It is recommended that a field supplied
liquid line solenoid be positioned in the main liquid line
(near the evapor ator coil). It should be wired to close wh en
compressor stops to m inimize refrigerant migration during
the ‘‘OFF’’ cycle.
Table 2 — Refrigerant Piping Sizes
LINEAR LENGTH OF PIPING — FT (M)
UNIT
0-25
(0-7.6)
25-50
(7.6-15.2)
Line Size (in. OD)
50-75
(15.2-22.9)
75-100
(22.9-30.5)
LSLSLSLS
569C072
569C090
569C120
576B090
576B102
576B120
1
/211/
1
/211/
5
/811/
1
/211/
5
/811/
5
/811/
8
8
8
8
8
8
1
/211/
1
/211/
5
/813/
1
/211/
5
/811/
5
/811/
1
/
8
8
8
8
8
8
11/
2
5
/
11/
8
5
/
13/
8
5
/
11/
8
5
/
13/
8
5
/
13/
8
8
8
8
8
8
8
1
/211/
5
/813/
5
/813/
5
/813/
5
/813/
5
/813/
LEGEND
L—
Liquid Line
S—
Suction Line
NOTES:
1. Pipe sizes are based on a 2° F (1° C) loss for liquid and suction
lines.
2. Pipe sizes are based on the maximum linear length shown for
each column, plus a 50% allowance for fittings.
3. Charge units with R-22 in accordance with unit installation
instructions.
Values shown are for units operating at 45 F (7.2 C) saturated
suction and 95 F (35 C) entering air.
LIQUID LINE
Max Allowable
Temp Loss
V. ELECTRICAL CONNECTIONS
WARNING: The unit cabinet must have an
uninterrupted, unbroken electrical ground to minimize
the possibility of perso nal injury if an electrical fault
should occur. This ground may co nsist of electrical wire
connected to the unit ground lug in the control
compartment or conduit approved for electrical ground
when installed in accordance with the NEC and local
electrical codes. Failure to adhere to this warning could
result in personal injury.
CAUTION: Failure to follow these precautions
could result in damage to the unit being installed:
A. Field Power Supply (Fig. 5-7)
1. Make all electrical connections in accordance with
NEC ANSI/NFPA (American National Standards
Institute/ National Fire Protection Association) 70,
latest edition, and local electrical codes governing
such wiring. Refer to unit wiring diagram.
2. Use only copper or copper-clad conductor fa n con nections between field-supplied electrical disconnect
switch and unit. DO NOT USE ALUMINUM WIRE.
Maximum wire size is no. 2 AWG (American Wire
Gage).
3. Voltage to compressor terminals during operation
must be within v ol tag e r ange indicated on unit nameplate (also see Table 4). On 3-phase units, voltages
between phases must be balanced within 2% and
8
8
8
8
8
8
—5—
the current within 10%. Use the formula shown in
Table 4, Note 2, to determine the percent voltage
imbalance. Operation on improper line voltage or
excessive phase imbalance constitutes abuse and may
cause damage to electrical components. Such operation would invalidate any applicable warranty.
4. Insulate low-voltage wires for highest voltage contained within conduit when low-voltage control wires
are run in same conduit as high-voltage wires.
5. Do not damage internal components when drilling
through any panel to mount electrical hardware, conduit, etc.
All units except 208/230-v units are factory wired for the
voltage shown on the nameplate. If the 208/230-v unit is to
be connecte d to a 208-v p ower sup ply, the tr ansfor mer must
be rewired by moving the black wire from the 230 -v term ina l
on the transforme r and connecting it to the 200-v terminal
on the transformer.
Refer to unit label diagram for additional information.
Pigtails are provi ded for field w ire conne ctions. Use factorysupplied splices or UL (Underwriters’ Laboratories)
approved copper/aluminum connector.
When installing units, provide a disconnect per NEC. All
field wiring must comply with NEC and local requirements.
Install field wiring as foll ows:
1. Install conduit through side panel openings.
2. Install power lines to terminal connections as shown
in Fig. 5.
B. Control Voltage Connections
Install an accessory ther mostat ass embly accordi ng to installation instructions included with the accessory. Locate thermostat assembly on a solid wall in the conditioned space to
sense average temperature in accordance with thermostat
installation instructions.
Route thermostat cable or equivalent single leads of colored
wire from subbase terminals to low-voltage connections on
unit (shown in Fig. 6) as described in Steps 1 through 4 below.
NOTE: For wire runs up to 50 ft, use no. 18 AWG insulated
wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG
C—
NEC —
LEGEND
Contactor
National Electrical Code
Field Wiring
Factory Wiring
Splice Connection (Factory Supplied)
Fig. 5 — Power Wiring Connections
insulated wire (35 C minimum). For over 75 ft, use no. 14
AWG insulated wire (35 C minimum). All wi re larger than
no. 18 AWG cannot be directly connected to the thermost at
and will require a junction box and splice at the thermostat.
1. Connect thermosta t wires to screw terminals of low
voltage connection boar d.
2. Pass the control wires through th e hole provided in
the corner post. See Fig. 7.
3. Feed wire through raceway built into the corner post
and into the 24-v thermostat connection board. The
24-v thermostat connection is located on the left side
of the low voltage connection comp artment. The raceway provides the UL required clea rance between the
high- and low-voltage wiring.
4. Total combined amperage draw of the field-in stalled
liquid line solenoid valve and indoor fan contactor
must not exceed 22 va. If the specified va must be
exceeded, use a remo te relay to switch the load.
Canadian Standards Association
Full Load Amps
Heating, Air Conditioning and Refrigeration
Locked Rotor Amps
Minimum Circuit Amps
Maximum Overcurrent Protection
National Electrical Code
Outdoor (Condenser) Fan Motor
Rated Load Amps
Underwriters’ Laboratories
VOLTAGE RANGECOMPRESSOROFMPOWER SUPPLY
MinMaxRLALRAFLAMCAMOCP
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage=
452 + 464 + 455
1371
=
3
=457
3
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.
The Canadian units may be fuse or circuit breaker.
Unbalanced 3-Phase Supply Voltage
2.
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%.
of voltage imbalance.
% of Voltage Imbalance =
100 x
max voltage deviation from average voltage
Use the following formula to determine the percent
average voltage
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance:
% Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT:
contact your local electric utility company immediately.
3. The 575-v units are CSA only.
4. The 380-v units are
If the supply voltage phase imbalance is more than 2%,
not
UL or CSA listed.
7
457
—7—
Fig. 7 — Field Control Wiring Raceway
(576B Unit Shown)
VI. ACCESSORY INSTALLATION
At this time any required accessories should be installed on
the unit. Refer to Table 5 for available accessories. Control
wiring information is provided in the unit wiring book.
Table 5 — Accessory List
PRE-START-UP
WARNING: Failure to observe the following warn-
ings could result in serious personal injury:
1. Follow recognized safety practices and wear
protective goggles when checking or servicing
refrigerant system.
2. Do not operate compressor or provide any electric power to unit unless compressor terminal
cover is in place and secured.
3. Do not remove compres sor term inal cover until
all electrical sources have been disconnected.
4. If refrigerant le ak is susp ected a roun d co mpre ssor terminals, recover refrigerant whenever
possible and relieve all pressure from system
before touching or disturbing anything inside
terminal box.
5. Never attempt to repair soldered connection
while refrigerant system is under pressure.
6. Do not use torch to remove any component.
System contains oil and refrigerant under
pressure. To remove a component, wear prote ctive goggles and proceed as follows :
a. Shut off electrical power to unit.
b. Recover refrigerant. Relieve all pressure
from system.
c. Cut component-connecting tubing with tub-
ing cutter and remove component from unit.
d. Carefully unsweat remaining tubing stubs
when necessary . Oil can ignite when exposed
to torch flame.
Proceed as follows to i nspect and pr epare the unit f or initial
start-up:
1. Field electrical power source must agree with unit
nameplate rating.
2. Check voltage imba la nc e as sho w n in Table 4, Note 2.
3. Check that all in ternal wiring connections are tight
and that all barriers, covers, and panels are in place.
4. Ensure al l s er vice valves are ope n. On 57 6 B un i ts, be
sure all compressor service valves are backseated.
5. Verify that compressor holddown bolts have been
loosened and that flat/snubber washers can be
rotated by applying finger pressure (snug, but not
tight).
6. On 569C and 576B units, verify compressor crankcase heater is securely in place. Crankcase heater
must operate for a least 24 hours before start-up.
7. Note that compressor oil level is visible in the sight
glass (576B units only).
8. Check for leaks in refrigerant system by using soap
bubbles and/or electronic leak detector.
9. Check that liquid line solenoid valve is located at
evaporator coil as shown in Filter Drier and Moisture
Indicator section, page 5.
10. Check that both outdoor and indoor units are properly mounted in a ccorda nc e with in st all ation in stru ctions and applicable codes.
—8—
START-UP
I. START-UP AND ADJUSTMENTS
CAUTION: Complete the required procedures
given in the Pre-Start-Up section and unit start-up
checklist at the end of this publication before starting
the unit. Do not jumper any safety devices when operating the unit.
Do not operate the com pressor when th e outdoor temperature is below 25 F (24 C) (unless accessory low
ambient ki t i s in stalled).
A. Checking Cooling Control Operation
Start and check the unit f or prope r cool ing con trol o perati on
as follows :
1. Place room thermostat SYSTEM switch in OFF position. Observe that blower motor starts when FAN
switch is placed in ON position and shuts down when
FAN switch is placed in AUTO. position.
2. Place SYSTEM switch in COOL position and FAN
switch in AUTO. position. Set cool ing control below
room temperature. Observe that compressor and condenser- and evaporator-fan motors start. Observe
that cooling cycle shuts down when control setting is
satisfied.
B. Unit Controls
All units have the following internal-protection controls:
Compressor Overload
This overload interrupts power to the compressor when
either the current or internal motor winding temperature
become excessive, and automatically resets when the internal temperature drops to a safe level. This overload may
require up to 60 minutes (or longer) to reset. If the internal
overload is sus pect ed of be ing op en, di sconn ect the elect ric al
power to the unit and check the circuit through the overload
with an ohmmeter or continuity tester.
Time Guard® II Device
The unit is equipped with accessory Ti me Guard II recycle
timer. The device will cause a 5-minute del ay between compressor starts.
Cycle-LOC™ Device
When high-pressure or low-pressure fault occurs, the Cycle LOC device will protect the system by not allowi ng the com pressor to start.
Low-Pressure Switch/(LPS)
When the suction line pressure drops below 7 psig (48 kPa),
the LPS opens 24-v power to the c ompressor contactor and
stops the compressor. When the pressure reaches 22 psig
(152 kPa), the switch resets and the compressor is allowe d to
restart.
High-Pressure Switch
When the refrigerant high-side pressure reaches 426 psig
(2937 kP a), the HPS opens 24-v po wer to the compresso r contactor and stops the compressor. When the pressure drops to
320 psig (2206 kPa), the switch resets and the compressor is
allowed to restart.
C. Sequence of Operation
At start-up, the thermostat calls for cooling. When all
safety devices are satisfied, the compressor contactor (fan
contactor) will en ergize caus ing the compressor and outdoo r
(condenser) fan motor to operate. Terminal “G” at the
(HPS)
thermostat is also energized, allowing the field-supplied
and -installed (24v) indoor (evaporator) fan contactor to function. A field-supplied and -installed liquid line valve (connected between Terminals G and C at the outdoor unit), will
also open. This allows the system to f unction in cooling; the
LPS will not open if compressor is not running. As cooling
demand is satisfied, the thermostat c ontacts break, deenergizing the contactor causing the system to shut off. The liquid line solenoid (LLS) v alve closes, minimizing the pote ntia l
for refrig erant migratio n at this time. Th e compressor do es
not restart until the thermostat again calls for cooling. If a
demand for cooling occurs within 5 minutes after the thermostat is satisfied, the system will not restart due to the feature of Time Guard II device. After the 5-minute time period,
the system will res tart as normal upon thermostat demand.
The system is protected with a Cycle-LOC devi ce s o that the
compressor will not start if a high-pressure or low-pressure
fault occurs. To reset the Cycle-LOC device, set the thermostat to eliminate the cooling demand then return to the original set point . This should b e done only on ce, and if system
shuts down due to the same fault, determine the problem
before attempting to reset the Cycle-LOC device.
The crankcase heaters must be energize d for a minimum of
24 hours before starting a 569C and 576B unit.
D. Oil Charge
576B Units
Allow unit to run for about 20 minutes. Stop unit and check
compressor oi l level . Ad d oil on ly if ne cess ary t o br ing oi l int o
view in sight glass. Use only approved compressor oil.
Approved oils are:
Suniso 3GS
WF32-150
If oil is added, run unit for an additional 10 minutes. Stop
unit and check oil level. If level is still low, add oil only after
determining that piping system is designed for proper oil
return and that system is not leaking oil.
569C Units
The 569C units do not have a sight glass and are factory
charged with the correct amount of oil.
All Units
Do not reuse drained oil or use any oil that has b een expo sed
to the atmosphere. Procedures for adding or removing oil are
given in the Standard Service Techniques Manual, Chapter
1, Refrigerants.
CARE AND MAINTENANCE
To ensure continuing high performance and to minimize the
possibility of premature equipment failure, periodic maintenance must be performed on this equipment. This cooling
unit should be inspected at least once each year by a qualified service person.
NOTE TO EQUIPMENT OWNER: Consult your local dealer
about the availability of a maintenance contract.
WARNING: The ability to properly perform maintenance on this equipment req uires certain expertise,
mechanical sk ills, tools, and equipment . If you do not
possess these, do not attempt to perform any maint enance on this equipment other than those procedures
recommended in the User’s Manual. FAILURE TO
HEED THIS WARNING COULD RESULT IN SERIOUS PERSONAL INJURY AND POSSIBLE DAMAGE TO THIS EQUIPMENT.
—9—
SERVICE
WARNING: When servicing unit, shut off all elec-
trical power to unit to avoid shock hazard or injury
from rotating parts.
I. CLEANING
Inspect unit interior at the beginning of each cooling season
and as operating conditions require.
A. Condenser Coil
Inspect coil monthly. Clean condenser coil annually, or as
required by location and outdoor-air conditions.
Clean coil as follows:
1. Turn off unit power and tag disconnect.
2. Remove and save top panel screws on condensing
unit.
3. Remove condenser coil corner post. See Fig. 8. To hold
top panel open, place coil corner post between top
panel and side panel. See Fig. 9.
4. Remove bracket holding coil sections together at
return end of condenser coil. Carefull y separate the
outer coil section 3 to 4 in. from the inner coil section.
See Fig. 10.
5. Use a wate r hos e o r other suitable equipment t o flu s h
down between the 2 coil se ctions to remove dirt and
debris. Clean the outer surfaces with a stiff brush in
the normal manner.
6. Reposition the outer coil section, attach the bracket
removed in Step 4, and remove the coil corner post
from between the top panel and side panel. Secure
the sections together. Install the coil corner post and
replace all screws (r emoved in Step 2).
II. LUBRICATION
A. Compressors
Each compressor is charged with the correct amount of oil at
the factory. Refer to the Oil Charge section on page 9 for
additional information.
B. Fan Motor Bearings
Fan moto r bearings are of the pe rmanently lubrica ted type.
No further lubrication is required.
Fig. 9 — Propping Up Top Panel
Fig. 10 — Separating Coil Sections
III. CONDENSER-FAN ADJUSTMENT (Fig. 11)
1. Shut off unit power supply, and tag disconnect.
2. Remove condenser-fan assembly (grille, motor, motor
cover, and fan).
3. Loosen fan hub setscrews.
4. Adjust fan height as shown in Fig. 11.
5. Tighten set screws.
6. Replace condenser-fan assembly.
Fig. 8 — Cleaning Condenser Coil
—10—
NOTE:
Fan height adjustments are as follows:
UNITin.mm
569C072
All Units
(except 569C072)
4.50114
6.42163
Fig. 11 — Outdoor (Condenser) Fan Adjustment
IV. CAPACITY CONTROL (576B120 Only)
A suction pressure-actuated unloader controls 2 cylinders
and provides capacity control . Unloaders are factory s et (see
Table 1), but may be field adjusted:
A. Control Set Point
The control set po int (cyl inde r loa d poin t) is ad jus tabl e from
0 to 85 psig. To adjust, turn control set point adjustment nut
(Fig. 12) clockwise to its bottom stop. In this position, set
point is 85 psig. Then, turn a djustment counterclockwi se to
desired control set point. Every full turn counterclockwise
decreases set point by 7.5 psig.
B. Pressure Differential
The pressure differential (difference between cylinder load
and unload points) is adjustable from 6 to 22 psig. To adjust,
turn pressure differential adjustment screw (Fig. 12) counterclockwise to its back stop position. In this position, differential is 6 psig. Then, turn adjustment screw clockwise to
desired pressure differential. Every full turn clockwise
increases differential by 1.5 psig.
Fig. 12 — Compressor Capacity Control Unloader
V. COMPRESSOR REMOVAL
See Table 1 for compressor information.
Follow safety codes and wear safety glasses and work gloves.
1. Shut off power to unit and install lockout. Remove
unit access panel (front of unit).
2. Remove refrigerant from system using refrigerant
removal methods described in GTAC II, Module 5,
Charging, Recovery, Recycling, and Reclamation.
3. Disconnect compressor wiring at compressor terminal box.
4. Remove bolts from suction flange and discharge service valve (576B units).
CAUTION: Excessive movement of copper lines at
compressor may cause higher le vels of vibration when
unit is restored to service.
5. Remove crankcase heater from compressor base
(576B units only).
6. Remove compressor ho lddown bolts.
7. Remove compressor from unit.
8. Clean system. Add new liquid line filter drier.
9. Install new compressor in unit.
10. Connect suction and discharge lines to compressor.
Ensure that compressor holddown bolts are in place.
11. Install crankcase heater.
12. Connect wiring.
13. Evacuate and recharge unit, per Step VII.
14. Restore unit power.
VI. CRANKCASE HEATER
The crankcase heater prevents refrigerant migration and
compressor oil diluti on during shutdown when compressor is
not operating.
Close both compressor service valves if applicable when
crankcase heater is deenergized for more than 6 hours.
VII. REFRIGERANT CHARGE
Unit panels must be in place when unit is operating during
charging procedure. Unit is shipped with a holding charge
only. Weigh in 7 lbs of R-22 to start unit. Refer to GTAC II,
Module 5, Charging, Recovery, Recycling, and Reclamation
for additional information.
See Troubleshooting Guide on page 13 for additional
information.
A. Low Charge Cooling
Using Cooling Charging Charts, Fig. 13 and 14, vary refrigerant until the condit ions of the appropria te chart are met.
Note the charging charts are different from type normally
used. The charts are based on charging the units to the correct sub-cooling for the various operating conditions. Accurate pressure gage and temperature sensing device are
required.
Connect the pressure ga ge to the service port on the liquid
line service valve. Mount the temperature sensing device on
the liquid line, close the liquid line service valve, and insulate it so that outdoor ambient temperature does not affect
the reading. Indoor-air cfm must be wi thin the norm al operating range of the unit.
Operate unit a minimum of 1 5 mi nute s. Ensure that temperature and pressure have stabilized. Plot liquid pressure and
temperature on chart and add or reduce charge as required.
Do not vent refrigerant to the atmosphere. Recover any
excess charge. Operate the unit until the system stabilizes.
Adjust charge to conform w ith charging chart, using liquid
pressure and temperature to read chart.
B. Refrigerant Leaks
Proceed as follows to repair a refrigerant leak and to charge
the unit:
1. Locate the leak and ensure that refrigerant system
pressure has been relieved.
2. Repair leak following accepted practices.
NOTE: Install a new filter drier in the liquid line whenever
the system has been opened for repair.
3. Add a small charge of R-22 refrigerant vapor to system and leak-test unit.
4. Evacuate refrigerant system up to 500 micons. If
additional leaks are not found.
5. Charge unit with R-22 refrigerant.
NOTE: Do not vent refrigerant to the atmosphere. Recover
any excess charge.
—11—
VIII. REFRIGERANT SERVICE PORTS
Each unit has 3 service ports: one on the suction line, one on
the liquid line, and one on the com press or dis charge line. Be
sure caps on the ports are tight.
IX. HIGH FLOW VALVES
Located on the compressor hot gas and suction tubes are
High Flow Valves. Large black plastic caps distinguish these
valves with O-rings located inside the caps. These valves can
not be accessed for service in the field. Ensure the plastic
caps are in place and tight or the possibility of refrigerant
leakage could occur.
Fig. 13 — Cooling Charging Chart — 569C072
Fig. 14 — Cooling Charging Chart — 569C090, 120
and 576B090,102,120
—12—
SYMPTOMCAUSEREMEDY
Compressor does not run —
Contactor open
Compressor does not run —
Contactor closed
Compressor cycles on highpressure switch —
Condenser fan on
Compressor cycles on highpressure switch —
Condenser fan off
Compressor cycles on lowpressure switch —
Evaporator fan running
Airflow restricted —
Low suction pressure
Indoor (evaporator) fan stopped —
Low suction pressure
Compressor runs but
cooling insufficient —
Suction pressure low
Compressor runs but
cooling insufficient —
Suction pressure high
NOTE:
See Fig. 15 and 16 for component arrangements.
TROUBLESHOOTING GUIDE
Power off.Restore power.
Fuses blown.
Transformer open/shorted.
Thermostat circuit open.Check thermostat setting.
Low-pressure switch open.
High-pressure switch open.
Connections loose.Tighten all connections.
Compressor motor thermostat open.Check for excessive motor temperature.
Compressor leads loose, broken.Check connections with power off.
Single phasing.Replace blown fuse.
Fan slips on shaft.Tighten fan hub screws.
Motor not running.Check power and capacitor
Motor bearings seized.Replace motor.
Motor overload open.Check overload rating. Check for fan blade obstruction.
Motor burned out, windings open.Replace motor.
Filter drier plugged.Replace filter drier.
Expansion valve power head
defective.
Low refrigerant charge.Find leak, repair, evacuate system, and recharge.
Expansion valve restricted/plugged.Remove and replace expansion valve.
Evaporator coil iced up.Check refrigerant charge.
Evaporator coil dirty.Clean coil fins.
Indoor-air filter dirty.Clean or replace filters.
Indoor-air dampers closed.Check damper operation and position.
Electrical connections loose.Tighten all connections.
Fan relay defective.Replace relay.
Motor overload open.Check power supply.
Motor defective.Replace motor.
Fan belt broken or slipping.Replace or tighten belt.
Refrigerant charge low.Add charge.
Head pressure low.Check refrigerant charge.
Indoor-air filters dirty.Clean or replace filters.
Expansion valve power head
WILL THIS DAMAGE PREVENT UNIT START-UP? (Y/N) _______
CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT? (Y/N) _______
HAS THE GROUND WIRE BEEN CONNECTED? (Y/N) _______
HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY? (Y/N) _______
ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? (Y/N) _______
HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED, WHERE APPLICABLE (Snubber washers are snug, but not tight)?
(Y/N) _______
CONTROLS
ARE THERMOSTAT AND INDOOR-FAN CONTROL WIRING
CONNECTIONS MADE AND CHECKED? (Y/N) _______
ARE ALL WIRING TERMINALS (including main power supply) TIGHT? (Y/N) _______
HAS CRANKCASE HEATER BEEN ENERGIZED FOR 24 HOURS? (Y/N) _______
INDOOR UNIT
HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE? (Y/N) _______
ARE PROPER AIR FILTERS IN PLACE? (Y/N) _______
HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT? (Y/N) _______
DO THE FAN BELTS HAVE PROPER TENSION? (Y/N) _______
HAS CORRECT FAN ROTATION BEEN CONFIRMED? (Y/N) _______
PIPING
IS LIQUID LINE SOLENOID VALVE LOCATED AT THE EVAPORATOR COIL AS REQUIRED? (Y/N) _______
HAVE LEAK CHECKS BEEN MADE AT COMPRESSOR, CONDENSER, EVAPORATOR,
TXVs (Thermostatic Expansion Valves), SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS
WITH A LEAK DETECTOR? (Y/N) _______
LOCATE, REPAIR, AND REPORT ANY LEAKS. ________________________________________________________________
ARE ALL 576B COMPRESSOR SERVICE VALVES FULLY OPENED (BACKSEATED)?
(Y/N) _______
HAVE LIQUID LINE SERVICE VALVE AND SUCTION LINE SERVICE VALVE BEEN OPENED? (Y/N) _______
IS THE OIL LEVEL IN COMPRESSOR CRANKCASE ON 576B UNIT IN VIEW IN THE COMPRESSOR SIGHT GLASS?
(Y/N) _______
CHECK VOLTAGE IMBALANCE
LINE-TO-LINE VOLTS: AB _______ V AC _______ V BC _______ V
(AB + AC + BC)/3 = AVERAGE VOLTAGE =V
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = __________ V
VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) = __________ %
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!
CALL LOCAL POWER COMPANY FOR ASSISTANCE.
CL-1
III. START-UP
CHECK EVAPORATOR-FAN SPEED AND RECORD. _______
CHECK CONDENSER-FAN SPEED AND RECORD. _______
AFTER AT LEAST 15 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:
OIL PRESSURE (576B only)
SUCTION PRESSURE
SUCTION LINE TEMP
DISCHARGE PRESSURE
DISCHARGE LINE TEMP
ENTERING CONDENSER-AIR TEMP
LEAVING CONDENSER-AIR TEMP
EVAP ENTERING-AIR DB (dry bulb) TEMP
EVAP ENTERING-AIR WB (wet bulb) TEMP
EVAP LEAVING-AIR DB TEMP
EVAP LEAVING-AIR WB TEMP
COMPRESSOR AMPS (L1/L2/L3) _____ / _____ / _____
HAS REFRIGERANT CHARGE BEEN ADJUSTED PER UNIT CHARGING CHART? _______________