Bryant 575C User Manual

installation, start-up and service instructions
AIR-COOLED SPLIT SYSTEM HEAT PUMP
Cancels: II 575B-72-3 II 575B-72-4
575B/575C/541A
Sizes 072-180
6 to 15 Tons
9/15/04
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-14
I. Complete Pre-Installation Checks . . . . . . . . . . . . . . 1
III. Complete Refrigerant Piping
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
IV. Complete Electrical Connections. . . . . . . . . . . . . . . 9
PRE-START-UP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15,16
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16-18
SEQUENCE OF OPERATION. . . . . . . . . . . . . . . . . . . . . .18-20
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20-24
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . .25,26
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . CL-1, CL-2
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equip­ment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated struc­tures, etc.).
Only trained, qualified installers and service mechanics should install, start-up, and service this equipment. Untrained personnel can perform basic maintenance func­tions such as cleaning coils. All other operat ions should be performed by trained service personnel.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep quenching cloth and fire extinguisher nearby when brazing. Use care in handling, rigging, and setting bulky equipment.
WARNING: Before installing or servicing system, always turn off main powe r to syst em a nd ins tall lock­out tag on disconnect. There may be more than one dis­connect switch. Electrical shock can cause personal injury.
GENERAL
The split system heat pump units described in this book are designed for use with the 524A-H indoor packaged air handler sections only.
INSTALLATION
I. COMPLETE PRE-INSTALLATION CHECKS
A. Uncrate Unit
Remove unit packaging except for the top skid assembly, which should be left in place until after the unit is rigged into its final location.
B. Inspect Shipment
File claim with shipping company if shipment is damaged or incomplete.
C. Consider System Requirements
• Consult local bui ldin g codes and Nati onal Electr ical C ode (NEC) for special installation requiremen ts.
• Allow sufficient space for airflow clearance, wiring, refrig­erant piping, and servicing unit. See Fig. 1-3 for unit dimensions. Figure 4 shows typical componen t locations for 541A180 units.
• Locate unit so that outdoor coi l airflow is unrestricte d on all sides and above.
• Unit may be mounted on a level pad directly on the base channels or mounted on raised pads at support points. See Table 1 for unit operating weights.
II. RIG AND MOUNT UNIT
CAUTION: Be sure unit panels are securely in
place prior to rigging. Be careful rigging, handling, and installing unit. Improper unit location can cause sys­tem malfunction and material damage. Inspect base rails for any shipping damage and make sure they are fastened securely to unit before rigging.
A. Rigging
These units are designed for over head rigging. Refer to rig­ging label for preferred ri gging method. Spreader bars are not required if top crating is left on unit. All panels must be in place when rigging. As further protection for coil faces, plywood sheets may be placed against sides of unit, behind cables. Run cables to a central suspension point so that angle from the horizontal is no t les s tha n 45 degr ee s. Raise and set unit down carefully.
If it is necessary to roll the unit into position, mount the unit on field-supplied rails placed lengthwise under the unit, using a minimum of 3 rollers. Apply force to the rails, not the unit. If the unit is to be skidded into position, place it on a large pad and drag it by the pad. Do not apply any force to the unit.
Raise from above to lift unit from the rails or pad when unit is in final position.
After unit in position, remove all shipping materials and top crating.
B. Locate Unit
For service access and unrestricted airflow, provide clearance on each end and side of unit. Position un it so that there is unrestricted airflow above unit.
NOTE: Be fore mounting unit, remov e holddown br acke ts and release skid.
If conditions or local codes requ ire unit to be fastene d t o pad, use the mounting ho les in the b ase rai ls.
C. Mount Unit
The unit may be mounted on a solid, level concrete pad, on accessory mounting legs, or on field-supplied raised supports at each mounting position. (Note that mounting hardware is field supplied.)
Bolt unit securely to pad or supports after unit is in position and is level. Be sure to mount unit level to ensure proper oil return to compressors. Mou nting ho les on unit can be used to secure unit to vibration isolators, if required.
19 3/8
10
24 1/2
4 7/8
D
CONTROL BOX
Line & Low Voltage Wiring Entrances
1-1/2
2-1/8
9-3/4
1-1/8
5-3/4
2-1/2
4-1/4
33
1-1/2
REAR
38-1/2
1-1/2
A
C
FRONT
7/8 4 PLACES
27
24
33
B
35
BOTTOM
35
33
1-1/2
TOP FRONT
NOTES:
1. All dimensions are in inches.
2. Recommended clearance for proper airflow (local codes or jurisdictions may prevail): Top — 60 in. Sides — 24 in. on 3 sides, one side may be 6 in. (Control box side should have 24-in. clearance for service access.)
3. Corner Weights (lb): A = 86
B = 84 C = 92 D = 90
Fig. 1 — 575B072 Unit Dimensions
2
38-1/2
1-1/2
Fig. 2 — 575C090,120 Unit Dimensions
3
WEIGHT DISTRIBUTION
UNIT 541A
180
WEIGHT — lb (kg)
Tot al
Operating
Weight
803
(364)
Support Point
12 34
158
243
244
(72)
(110)
(111)
158 (72)
Fig. 3 — 541A180 Unit Dimensions
4
NOTE: Recommended service clearances are as follows (local codes or jurisdictions may prevail): Side (compressor) — 3 Side (opposite compressor) — 3 ft (914 mm) Ends — 2 ft (616 mm) Top — 5 ft (1524 mm)
1
/2 ft (1067 mm)
12 3 45 6 78 9101112
13
14
15
28
27
26
19202122232425
LEGEND
1— Defrost Board/Time Guard II Control 11 — Power Terminal Block 20 — High-Pressure Switch 2— Fuse 12 — Control Terminal Block 21 — Compressor 3— Fan No. 1 13 — Compressor Lockout (CLO2 for 4— Compressor Lockout (CLO) Device 23 — Filter Drier
Crankcase Heater)
22 — Capacity Control Solenoid
5— Outdoor-Fan Relay 14 — Control Relay (CR3) 24 — Muffler 6— Outdoor-Fan Contactor 15 — Liquid Line Solenoid 25 — Oil Solenoid 7— Compressor Contactor 16 — Control Relay (CR2) 26 — Reversing Valve 8— Fan Motor Capacitors 17 — No Dump Relay (NDR) 27 — Accumulator 9— Circuit Breaker 18 — Oil Pressure Switch 28 — Coil
10 — Fan No. 2 19 — Fusible Plug (hidden)
Fig. 4 — Component Locations — 541A180 Shown
16
17
18
5
Table 1 — Physical Data — 575B072, 575C090,120 and 541A180 Units
UNIT 575B072 575C090 575C120 541A180 NOMINAL CAPACITY (tons) 6 7.5 10 15 OPERATING WEIGHTS (lb)
Aluminum-Fin Coils (standard) 345 464 506 803 Copper-Fin Coils (optional) N/A 565 607 945
REFRIGERANT* R-22
Operating Charge, Typical (lb)† 20 20 22 37 Shipping Charge (lb) 19 9 3
COMPRESSOR Scroll Semi-hermetic reciprocating
Qty...Model 1...SR_75 1...ZR_94 1...ZR125 1...06DF537†† Oil Charge (oz) 88 90 110 128 No. Cylinders N/A 6 Speed (rpm) 3500 1750
OUTDOOR FANS
Qty...Rpm 1…1100 2…1100 2…1075 Diameter (in.) 26 22 26 Nominal Hp Nominal Airflow (cfm total) 6300 6500 11,000 Watts (total) 750 570 1460
OUTDOOR COILS (Qty) 12 1
Face Area (sq ft total) 24 29.2 29.2 Rows...Fins/in. 2…18 2…17 3…15 Storage Capacity (lb)** 17.3 34.2 40.1
CONTROLS Pressurestat Settings (psig)
High Pressure
Open 420 428 ± 10 395 ± 20 Close 300 320 ± 20 295 ± 20
Low Pressure
Open 5 7 ± 3 7 ± 3 Close 20 22 ± 5 22 ± 5
PIPING CONNECTIONS (in. ODM)
Vapor 1 Liquid
*Unit is factory supplied with holding charge only.
†Typical operating charge with 25 ft of interconnecting pipe.
**Storage capacity of condenser coil with 80% full of liquid at 95 F.
††Equipped with an electric solenoid unloader, capacity steps are 100% and 67%.
3
/
4
1
/
8
5
/
8
11/
8
1
/
2
1
/
4
13/
8
1
/
2
15/
1
/
2
8
5
/
8
6
III. COMPLETE REFRIGERANT PIPING CONNECTIONS
Refrigerant lines mu st b e ca reful ly desig ne d a nd c onstr ucted to ensure equipment reliabili ty and efficiency. Line length, pressure drop, compressor oil return, and vertical separation are several of the design criteria that must be evaluated. See Table 2.
IMPORTANT: Do not bury refrigerant piping underground. IMPORTANT: Piping must be properly sized and installed for
the system to operate efficiently.
A. Check Vertical Separation
If there is any vertical separation between the indoo r and o ut­door units, check to ensure that the separation is within allowable limits. Relocate equipment if necessary. See Table 3.
B. Refrigerant Line Sizing
Consider the length of the piping required betwe en the out­door and indoor units. The maximum allowable line length is 100 ft. See Table 3. Refrigerant suction piping should be insulated.
IMPORTANT: A refrigerant receiver is not provided with the unit. Do not install a receiver.
IMPORTANT: For 575C090,120 applications with liquid lift greater than 20 ft, use
5
/8-in. liquid line. Maximum lift is
60 ft.
Table 2 — Refrigerant Piping Sizes
LENGTH OF PIPING ft
OUTDOOR
UNIT
575B072
575C090
575C120
541A180
*If there is a vertical separation between indoor and outdoor units, see
Table 3 — Maximum Vertical Separation.
LEGEND
L — Liquid Line V — Vapor Line NOTES:
1. Pipe sizes are based on a 2 F loss for liquid and vapor lines.
2. Pipe sizes are based on the maximum linear length, shown for each column, plus a 50% allowance for fittings.
3. Charge units with R-22 refrigerant in accordance with unit installation instructions.
4. Maximum line length must not exceed 100 ft.
5. Do not bury refrigerant piping.
0-25 26-60 61-100
Line Size (in. OD)
LVLVLV
1
/211/
3
/811/
1
/213/
5
/815/
8
8
8
8
5
/811/
1
/211/
1
/213/
3
/415/
8
8
8
8
5
/811/
1
/211/
1
/213/
3
/415/
8
8
8
8
MAXIMUM
LIQUID
LINE
(in. OD)*
5
/
8
5
/
8
5
/
8
3
/
4
Table 3 — Maximum Vertical Separation*
unit to outdoor unit before opening the liquid and vapor lines at the outdoor unit. For specific filter driers see Table 4.
D. Liquid Line Piping Procedure
Pipe the system liquid line as follows:
WARNING: Unit is pressurized with a holding charge of refrigerant. Recover R-22 holding charge before removing runaround liquid piping loop. Failure to recover holding charge before removing piping loop could result in equipment damage and personal injury.
1. Open service valves in sequence: a. Discharge service valve on compressor. b. Suction service valve on compress or.
c. Liquid line valve.
2. Remove
1
/4-in. flare cap from liquid valve Schrader
port.
3. Attach refri gerant recovery device and recover hold-
ing charge.
4. Remove runaround loop (581A180 only).
5. Connect system liquid line from liquid connection of
outdoor unit (575B,C, 541A) to indoor unit (524A-H) liquid line connections. Select proper field-supplied bi-flow filter driers and install in the liquid line. See Fig. 5. Install a field-supplied liquid moisture indica­tor between the filter drier(s) and the liquid connec­tions on the indoor un it. Braze or silver alloy so lder all connections. Pass nitrogen or other inert gas through piping while making connections to prevent formation of copper oxide. (Copper oxides are extremely active under high temperature and pres­sure. Failure to prevent collection of copper oxides may result in system component failures.)
E. Liquid Line Solenoid Valve
Addition of a li qui d so le noi d v alv e (LL SV ) is required (except for 541A180 units that already ha ve LLSV factory-i nstalle d). The LLSV must be a bi-f low type suited for use in heat pump systems. Refer to Table 4. Wire the solenoid valve in parallel with the compressor contactor coil.
The LLSV must be installed at the outdoor unit with the flow arrow pointed toward the outdoor unit (in-flow direction for the Heating mode).
OUTDOOR
UNIT
575B 072 090 50
575C
541A 180 180 80
*Vertical distance between indoor and outdoor units.
090 090 60 120 120 60
INDOOR UNIT
524A-H
DISTANCE FT
Outdoor Unit
Above 524A-H
C. Install Filter Drier(s) and Moisture Indicator(s)
Every unit should have a filter drier and liquid-moisture indicator (sight glass). In some applications, depending on space and convenience requirements, it may be desirable to install 2 filter driers and sight glasses. One filter drier and sight glass may be installed at A
locations in Fig. 5. If desired, 2 filter driers and sight glasses may be installed at B
locations in Fig. 5.
Select the filter drier for maximum unit capacity and minimum pressure drop. Complete the refrigerant piping from indoor
LEGEND
TXV — Thermostatic Expansion Valve
Fig. 5 — Location of Sight Glass(es)
and Filter Driers
7
Table 4 — Refrigerant Specialties Part Numbers
UNIT
575B072
575C090
575C120
541A180
*A filter drier is shipped loose with the 575B072 units.
†Bushings required.
**Factory Installed.
LIQUID LINE
SIZE
1
/2″ 200RB GS-1928 5T4 AMG-24/50-60 AMI1TT4 *
5
/8″ 200RB GS-1929 5T5 AMG-24/50-60 AMI1TT5 *
3
/8″ 200RB GS-1928 5T4† AMG-24/50-60 AMI1TT3 P504-8083S
1
/2″ 200RB GS-1928 5T4 AMG-24/50-60 AMI1TT4 P504-8084S
1
/2″ 200RB GS-1928 5T4 AMG-24/50-60 AMI1TT4 P504-8164S
5
/8″ ** ** AMI1TT5 P504-8085S Qty 2
3
/4″ ** ** AMI1TT5 P504-8085S Qty 2
LIQUID LINE
SOLENOID VALVE (LLSV)
F. Provide Safety Relief
A fusible plug is loca ted on the compressor crankcas e or in the liquid line. See Fig. 6. Do not cap this plug. If local code requires additi onal safety devices, insta ll them as directed.
Head Pressure Control (541A180 only) Fan cycling for head pressure control is a standa rd offering
but is functional on the cooling cycle only. Number 2 fan cycles as a function of liquid pressure. Fan cycling pressure switch cycles the fan off at 160 ± 10 psig as pressure decreases and cycles bac k on at 255 ± 10 psig. Switch is auto­matically bypassed in h ea ting c yc le. Table 5 s ho ws min im um outdoor air temperature for full cooling capacity.
G. Vapor Line Piping Procedure
Connect system vapor li ne to the vapor line s tub on the out­door unit and the vapor stubs on the indoor unit. At the indoor unit, construct vapor piping branches as shown in Fig. 7 for good mixi ng of the refri gerant leaving the ind oor coil during cooling. This will ensure proper TXV (thermo­static expansion valve) bulb sensing.
Where vapor line is expose d to outd oor ai r, line must be insu­lated. See Table 6 for insulation requirements.
Table 5 — Minimum Outdoor Air
Operating Temperature
LLSV COIL SIGHT GLASS FILTER DRIER
Fig. 6 — Location of Fusible Plug —
541A180 Unit
UNIT
COMPRESSOR
CAPACITY
575B 072
%
575C
090 35 –20 120 35 –20
541A 180
*Applies to Cooling mode of operation only.
†Wind baffles (field-supplied and field-installed) are recommended for
100
100
67
MINIMUM OUTDOOR TEMP — F*
Standard
Unit
Head Pressure
Control†
00
23 36
–20 –20
all units with low ambient head pressure control. Refer to Low Ambient Control Installation Instructions (shipped with accessory) for details.
Table 6 — Insulation for Vapor Line Exposed
to Outdoor Conditions
LENGTH OF EXPOSED
VAPOR LINE*
ft in.
10
25
35
50
*Recommended vapor line insulation for piping exposed to outdoor
conditions to prevent loss of heating during heating cycle. When vapor line goes through interior spaces, insulation should be selected to pre­vent condensation on cooling cycle. Heating capacity should be reduced 1000 Btuh if over 35 ft of vapor line with exposed to outdoor conditions.
†Closed cell foam insulation with a thermal conductivity of: 0.28 Btu
2
• in./ft
• h • °F.
INSULATION THICKNESS†
3
/
8
1
/
2
3
/
4
3
/
4
3
/4 in. insulation is
LEGEND
TXV — Thermostatic Expansion Valve
Fig. 7 — Vapor Line Branch Piping Details
8
IV. COMPLETE ELECTRICAL CONNECTIONS
7
A. Power Supply
Electrical characteristics of available power supply must agree with nameplate rating. Supply voltage must be within tolerances shown in Table 7. Phase imbalance must not exceed 2%. Operat ion of unit on improper supply voltage or
with excessive phase imbalance constitutes abuse and is not covered by Bryant warranty.
Per local code requirements, provide an adequate fused disconnect switch within sight of unit and out of reach of children. Provision the switch for locking open (off) to prevent power from being turned on while unit is being serviced. The disconnect switch, fuses, and field wiri ng mus t comply with local requirements. Refer to Table 7 for unit electrical data.
B. Power Wiring
All power wiring must comply with applicable local require­ments. Run power wires from disconnect switch through unit power opening and connect to terminal block inside the unit control box. Unit must be grounded.
C. Unbalanced 3-Phase Supply Voltage
Never operat e a motor where a phase imbala nce in supply voltage is greater than 2%. Use the following formula to determine the percentage of voltage im balance:
% Voltage Imbalance:
= 100 x
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
452 + 464 + 455
1371
=
3
3
= 457
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v
Maximum deviation is 7 v. Determine percent of voltage imbalance.
% Voltage Imbalance= 100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
WARNING: Unit cabinet must have an uninter­rupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code), ANSI/NFPA (American National Standards Institute/National Fire Protection Association), and local electrical codes. Failure to follow this warning could result in the installer being liable for personal injury of others.
IMPORTANT: Operation of unit on improper power supply voltage or with excessive phase imbalance constitutes abuse and is not covered by Bryant warranty.
D. General Wiring Notes (See Fig. 8-13)
1. A crankcase heater is wired in the c ontr ol ci rcuit so it is always operable as l ong as po wer su pply discon nect is on, even if any saf ety device is open or unit stop/ start switch is off.
2. The power-circuit field supply disconnect should never be open except when unit is being service d or is to be down for a prolonged period. When operation is resumed, crankcase heater should be energized for 24 hours before start-up. If system is to be shu t down
for a prolonged period, it is recommended that the suction and discharge valves be closed to prevent an excessive accumulation of refrige rant in the com­pressor oil.
3. Terminals for field power supply are suitable for cop­per, copper-clad aluminum, or aluminum conductors.
4. Bryant recommends an indoor airflow switch (field supplied) be installed and interlocked with the outdoor unit. This prevents the outdoor unit from operating if ind oor airflow fails (broken fan belt, etc.). Operation of the compressor in vacu um can damage bearing surfaces. Install indoor airflow switch in a convenient locati on at the indo or supply air d uct and wire per Fig. 14.
5. If the system is equipped with an accessory electri c heater, refer to the 524A-H inst allation instructions and tables.
E. Control Circuit Wiring
Control voltage is 24 v. See unit label diagram for field supplied wiring details. Route control wires through opening in unit to connection in unit control box.
Control Tran sf o r me r W iring On 208/230V units, check the transformer primary wiring
connections. See Fig. 8 or refer to unit label diagram. For 575B,C Unit — If unit will be operating at 208-3-60
power, remove black wire (BLK) from the transformer pri­mary connection labeled “230” and move it to the connection labeled “208”. See Fig. 8.
For 541A Unit — Transformers no. 1 and 2 are wired for a 230-v unit. If a 208/230-v unit is to be run with a 208-v power supply, the transformers must be rewired as follows:
1. Remov e ca p from red (208 v) wire.
2. Remove cap from orange (230 v) spliced wire.
3. Replace orange wire with red wire.
4. Recap both wires.
IMPORTANT: BE CERTAIN UNUSED WIRES ARE CAPPED. Failure to do so may result in damage to the transformer.
9
Duplex 575C120, 541A180 with 524A-H240 or 524A-H300 In order to properly connect two heat pump condensing
units to a single 524A-H packaged air handler, it is necessary to add field-supplied Fan Coil Relay Board(s), P/N 33ZCRLYBRD. Relay board(s) no. 1 and no. 2 should be installed in the control box of condensing unit.
IMPORTANT: The common (COM) terminals from the fan coil relay board(s) mu st be connected to the ‘C’ terminal in condensing unit ‘A’.
Route thermostat cable or equivalent single leads of no. 18 AWG (American Wire Gage) colored wire from sub­base terminals through conduit in unit to low-voltage con­nections as shown on unit wiring diagram and Fig. 12 and 13.
NOTE: For wire runs up to 50 ft, use no. 18 AWG insulated wire (35 C minimum). For 51 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junc­tion box and a splice at the thermostat.
Table 7 — Electrical Data
Fig. 8 — Wiring Diagram — 575C090,120 —
Control Transformer
UNIT
575B 072 NONE
090
575C
120
541A 180 NONE
LEGEND FLA Full Load Amps
LRA Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC National Electrical Code RLA Rated Load Amps
*Units are suitable for use on electrical systems where voltage supplied
to the unit terminals is not below or above the listed limits.
FAC TORY -
INSTALLED
OPTION
NONE OR DISCONNECT CONVENIENCE OUTLET 43.8 60 NONE OR DISCONNECT CONVENIENCE OUTLET 21.9 30 NONE OR DISCONNECT CONVENIENCE OUTLET 50.0 70 NONE OR DISCONNECT CONVENIENCE OUTLET 25.0 30 NONE OR DISCONNECT CONVENIENCE OUTLET 20.0 25
NOMINAL VOLTAGE
(V-Ph-Hz)
208/230-3-60 187 253 18.9 146 5.1 28.7 45
460-3-60 414 506 9.5 73 2.6 14.5 20 575-3-60 517 633 7.6 58 1.2 10.7 15
208/230-3-60 187 254 29.0 190 1.5
460-3-60 418 506 15.0 95 0.7
208/230-3-60 187 254 34.0 225 1.5
460-3-60 418 506 17.0 114 0.7
575-3-60 523 632 14.0 80 0.7
208/230-3-60 187 253 63.6 266 4.3 87.5 125
460-3-60 414 528 29.3 120 2.3 40.7 60 575-3-60 518 660 23.8 96 1.8 33.0 50
VOLTAGE RANGE* COMPRESSOR FAN MOTORS POWER SUPPLY
Min Max RLA LRA FLA MCA MOCP
39.0 60
19.8 30
45.0 60
23.0 30
18.0 25
NOTES:
1. The MCA and MOCP values are calculated in accordance with the NEC, Article 440.
2. Motor RLA and LRA values are established in accordance with Underwriters’ Laboratories (UL), Standard 1995.
3. The 575-v units are UL, Canada-listed only.
4. Convenience outlet is available as either a factory-installed option or a field-installed accessory and is 115-v, 1 ph, 60 Hz.
10
FAN
R-RV
DEFROST CONTROL
C
R
BL
O
Y-R V
RV
CC
PS2
PS1
DF
LEGEND
DF Defrost Relay LP/HP — Low or High-Pressure Switch (Optional)
RV
BK
COIL
BK
BL BL
Y
LP/HP
LP/HP
Y
BK
SEN
BK
Y
WR
PS Pressure Switch RV Reversing Valve SEN Outdoor Coil Temperature Sensor TSTAT — Thermostat
Line Voltage Factory Low Voltage Factory Low Voltage Field
COLOR CODE
BK Black BL Blue O Orange R Red W White Y Ye l l o w
W
Y
O
DEFROST HEAT
COMPRESSOR
HEAT/COOL
COMMON
24 VAC
FROM TS TAT
NOTES:
1. All electrical work must be done in conformance with the National Electrical Code (NFPA No. 70) and in conformance with local codes and authorities having jurisdiction.
2. For use with copper conductors only.
CAUTION: Not suitable for use on systems exceeding
150 volts to ground.
Fig. 9 — Wiring Diagram — 575B072; 208/230-3-60 Units
TO ELECTRIC HEATER ACCESSORY, IF EQUIPPED
THERMOSTAT
R
Y
O
E
W2
G
C
CONNECTION
BOARD (TB)
1
2
3
4
IFC
LLSV
5
6
7
8
NOTES:
1. For thermostat and subbase part no. see
2. Use copper conductors only.
Fig. 10 — Wiring Diagram — 575C090,120; 230-3-60 Units
LEGEND
IFC Indoor Fan Contactor LLSV — Liquid Line Solenoid Valve TB Terminal Block
Field Wiring
price pages.
11
LEGEND
EQUIP — Equipment GND Ground HC Heater Contactor IFC Indoor Fan Contactor IFM Indoor Fan Motor NEC National Electrical Code TB Terminal Block
Fig. 11 — Wiring Diagram — 541A180 Unit With Standard Thermostat and Electric Heat
12
DISCONNECT
3-Ph ONLY
524A-H240
TERMINAL BLOCK
TB1
R
Y1
Y2
W1
W2
G
C
X
FIELD
POWER
SUPPLY
EQUIP GND
FIELD POWER WIRING
C1
WHT
TB1
L1
L2
L3
524A-H
HEAT ACCESSORY
IFC
C2
WHT
HC1
HC1
CIRCUIT BREAKER
(5 HP AND LARGER)
W1
W2
C
R
Y1
Y2
W1
W2
G
C
O
TS TAT
HTR1
IFC
21
11
22
12
23
13
BLK BLK BLK
1 2 3
UNIT WIRING
IFM
HEAT PUMP “A”
TB2
R
Y1
Y2
W1
W2
G
CR
C
X
CR
G
G2/(W)
G3/(Y)
COM
RELAY BOARD
(33ZCRLYBRD)
(VALVE)
HI(COOL)
MED(HEAT)
LO
FAN
LEGEND
CR Control Relay (Field-Supplied) EQUIP — Equipment GND Ground HC Heating Contactor HTR Electric Heater IFC Indoor-Fan Contactor IFM Indoor-Fan Motor TB Terminal Block TSTAT — Thermostat
Factory Wiring
Field Control Wiring
NOTE: Use copper conductors only.
Fig. 12 — Wiring Diagram — Duplex 575C120 With 524A-H240 and Electric Heat
HEAT PUMP “B”
TB2
R
Y1
Y2
W1
W2
G
C
X
13
DISCONNECT
3-Ph ONLY
524A-H300
TERMINAL BLOCK
TB1
R
Y1
Y2
W1
W2
G
C
X
FIELD
POWER
SUPPLY
EQUIP GND
FIELD POWER WIRING
C1
WHT
TB1
L1
L2
L3
HEAT ACCESSORY
IFC
C2
WHT
CIRCUIT BREAKER
(5 HP AND LARGER)
524A-H
W1
W2
C
R
Y1
Y2
W1
W2
G
C
X
TS TAT*
HC1
HC1
HTR1
IFC
21
11
22
12
23
13
BLK BLK BLK
G
G2/(W)
G3/(Y)
COM
1 2 3
UNIT WIRING
RELAY BOARD (33ZCRLYBRD)
(VALVE)
HI(COOL)
MED(HEAT)
LO
IFM
FAN
HEAT PUMP A
541A180
TB2
R
B
W1
A2
Y1
Y2
Q
C
P
X
1
2
CR
G
G2/(W)
G3/(Y)
COM
RELAY BOARD (33ZCRLYBRD)
(VALVE)
HI(COOL)
MED(HEAT)
LO
FAN
LEGEND
HEAT PUMP B
575C120
CR Control Relay (Field-Supplied) EQUIP — Equipment GND Ground HC Heating Contactor HTR Electric Heater IFC Indoor-Fan Contactor IFM Indoor-Fan Motor TB Terminal Block TSTAT — Thermostat
Factory Wiring
Field Control Wiring
*Do not configure TSTAT for heat pump. NOTE: Use copper conductors only.
TB2
Y1
Y2
W1
W2
R
CR
G
C
X
Fig. 13 — Wiring Diagram — Duplex 575C120 and 541A180 With 524A-H300 and Electric Heat
CR
LEGEND
AFS — Airflow Switch (Sail Switch) CR Control Relay DB Defrost Board
Factory Wiring Field Control Wiring
NOTES:
1. Locate YEL wire between on DB and terminal 5 of CR3 and cut.
Y
2. Splice airflow switch (AFS) (field supplied) contact wires (field provided) to two ends of cut YEL wire as depicted.
Fig. 14 — Typical Field Wiring for Airflow Switch —
541A180/524A-H
14
PRE-START-UP
IMPORTANT: Before beginning Pre-Start-Up or Start-Up,
review Start-Up Checklist at the back of this book. The checklist assures proper start-up of the system and provides a record of unit condition, application requirements, system information, and operation at initial start-up.
CAUTION: Do not attempt to start the heat pump system, even momentarily, until the following steps have been completed. Compressor damage may result.
I. PRELIMINARY CHECKS
1. Check all air handler and other equipment auxiliary components. Consult manufacturer’s instructions re­garding any other equipment attached to unit. If unit has field-installed accessories, be sure all are properly installed and correctly wired. If used, airflow switch must be properly installed. See Fig. 14 for typical field wiring.
2. As shipped, compressor is held down by 4 bolts. After unit is installed, loosen each bolt and locknut until flat washer or snubber can be moved with finger pres­sure. Be sure compressor floats freely on the moun t­ing springs (541A units only). See Fig. 15A and 15B for compressor mountin g.
3. Check tightness of all electrical connections.
4. Electrical power source must agree with nameplate rating.
5. Turn on crankcase heater for 24 hours before starting the unit to be sure a ll refrigeran t is out of the oil . To energize crankcase heater, perform the following steps:
a. Set the space thermostat system switch to OFF, or
adjust the tem perature so t here is no dem and for
cooling. b. Close the field disconnect. c. Leave the compressor circuit breaker off. The
crankcase heater is now energized.
6. Leak test the field refrigerant piping, connections and joints, and indoor coil. To perform leak test, com­plete the following steps:
a. Pressurize refrigerant piping; do not exceed
150 psi.
b. Using soap bubbles and/or an electronic leak
detector, test refrigerant piping, connections and joints, and the indoor coil. See Fig. 16.
c. Check for leaks.
Evacuate and dehydrate entire refrigerant system.
7. 541A180 only — compressor oil le vel s hould be visibl e in sight glass. Adjust the oil level as required. No oil should be removed unless the crankcase heater has been energized for at least 24 hours. See Start-Up section, Preliminary Oil Charge.
NOTE: The 575B, 575C units do not have a compres­sor oil level sight glass. These units are factory charged with the required amount of oil. If required, use the followin g oil for repl acement: For 575B units use Zerol 150, part number P903-2001. For 575C units use RCD, part number P903-0101.
8. Backseat (open) compressor suction and discharge valves. Now close valves one turn to allow refrig erant pressure to reach test gages.
SELF-LOCKING BOLT
SNUBBER WASHER
NEOPRENE SNUBBER
COMPRESSOR FOOT
Fig. 15A — Compressor Mounting — 575B072 and
575C090,120 Units
Fig. 15B — Compressor Mounting — 541A180 Units
150 PSI MAX
DRY
OUTDOOR
UNIT
NITROGEN
SUCTION LINE
LIQUID LINE
LIQUID LINE SOLENOID VALVE
TXV
SOAP
Fig. 16 — Recommended Process for
Checking for Leaks
II. PRELIMINARY CHARGE
CAUTION: The 575C090 and 575C120 units contain a
9 lb charge of refrigerant. Add remainder of preliminary charge and allow pressure to equalize before starting compressor. Failure to do so WILL cause the compressor to overheat in a few minutes, possibly causing permanent compressor damage. The amount of refrigerant added
must be at least 80% of the operating charge listed in the Physical Data table (Table 1).
INDOOR
COIL
15
Before starting the unit, charge liquid refrigerant into the high side of the system through the liquid service valve. Allow high and low side pre ssu res t o equali ze be for e star ting compressor. If pressures do not equalize readily, charge vapor on low side of system to assure charge in the evapora­tor. Refer to GTAC II, Module 5, Charging, Recovery, Recy­cling, and Reclamation for liquid charging procedures.
III. LIQUID LINE SOLENOID
To minimize refrigerant migration to the compresso r during the heat pump OFF cycle, the 575B,C unit must have a bi-flow liquid line solenoid valve (field supplied). The valve opens when the compressor is energized, and closes when the compressor is deenergized. This reduces compressor flooded starts, thus significantly increasing compressor life.
IV. ACCUMULATOR
The unit accumulator controls the rate of l iquid refrigerant to the compressor during heat pump operation.
The 541A accumulator features a unique method for returning oil to the comp ress or. The oil return mechanism is external to the accumulator. The mixture of oil and refriger­ant is metered to the compressor by a brass orifice which is removable and cleanable. The oil return mechanism also contains a solen oid va lve th at op ens wh en the c ompres sor is ON and closes when the compressor is OFF. This keeps the liquid refrigerant stored in the accumulator from dra ining to the compressor during the heat pump OFF cycle, which further protects the compressor against flooded starts.
becomes excessive, and automatically resets when the internal temperature drops to a safe level. This overload usually resets within 60 minutes (or longer). If the internal overload is sus pected of bei ng open , disco nnec t the elect ric al power to the unit and check the circuit through the overload with an ohmmeter o r continuity tester.
III. ADVANCED SCROLL TEMPERATURE PROTECTION (ASTP)
Advanced Scroll Temperature Protectio n (ASTP) is a form of internal dischar ge temperature protection that unloads the scroll compressor when the internal temperature reaches approximately 300 F. At this temperature, an internal bi­metal disk valve opens and causes the scroll elements to sep­arate, which stops compression. Suction and discharge pres­sures balance while the motor continues to run. The longer the compressor runs unloaded, the longe r it must cool before the bi-metal disk re sets. See Fig. 17.
To manually reset ASTP, the compressor should be stopped and allowed to cool. If the compressor is not stopped, the motor will run un til the motor protector trips, which occu rs up to 90 minutes later. Advanced Scroll Temperature Protec­tion will reset automatically before the motor protector resets, which may take up to 2 hours. A label located above the terminal box identifies Copeland Scroll compressor models (ZR94, 108 and 125) that contai n this t ec hno lo gy. See Fig. 18.
START-UP
CAUTION: Compres sor crankcase heat er must be
on for 24 hours before start-u p. After the heater has been on for 24 hours, the unit can be started.
CAUTION: Prior to starting compressor, a preliminary
charge of refrigerant must be added to avoid possible compressor damage.
I. COMPRESSOR ROTATION (575B,C Units)
On 3-phase units with scroll compressors, it is important to be certain compressor is rotating i n the proper di rection. To determine whether or not compressor is rotating in the proper direction:
1. Connec t service gages to suctio n and discharge pres­sure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge pressure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge pressure does not rise to normal levels:
1. Note that the condenser fan is probably also rotating in the wrong direction.
2. Turn off power to the unit, tag disconnect.
3. Reverse any two of the unit power leads.
4. Reapply power to the compressor, verify correct pressures.
The suction and discharge pressure levels should now move to their normal start-up levels.
II. COMPRESSOR OVERLOAD
This overload interrupts power to the compressor when either the current or internal motor winding temperature
120
110
100
90
80
es)
70
nut
60
50
(Mi
40
30
20
Recommended Cooling Ti me
10
0
0 102030405060708090
*Times are approximate. NOTE: Various factors, including high humidity, high ambient tempera-
ture, and the presence of a sound blanket will increase cool-down times.
Compressor Unloaded Run Time (Minutes)
Fig. 17 — Recommended Minimum Cool-Down Time After
Compressor is Stopped*
Fig. 18 — Advanced Scroll Temperature Protection Label
16
IV. COMPRESSOR LOCKOUT DEVICE
The compressor lockout (CLO) device pre vents the compres­sor from starting or running in a high pressure, loss-of­charge or freezestat op en s it uati on. Reset t he CLO d evic e b y setting the thermostat to eliminate cooling demand and return it to the original set point. If the system shuts down again for the same fault, determine the possible cause before attempting to reset the CLO device.
V. PRELIMINARY OIL CHARGE (541A)
The compressor is factory charged with oil (see Table 1). When oil is chec ke d at sta rt-up , i t may be ne cessar y to a dd or remove oil to bring it to the proper level. Add oil only if necessary to bring oil into view in sight glass. Use only Bryant-approved compressor oil. One recommended oil level adjustment method is as follows:
A. Add Oil
Close suction service valve and pump down crankcase to 2 psig. Wait a few minutes and repeat until pressu re remains steady at 2 psig. Remove oil fill plug above the sight gla ss, add oil through plug hole, and replace plug. Run compressor for 20 minutes and check oil level.
NOTE: Use only Bryant-approved compre ssor oil. Approved sources are:
Petroleum Specialties, Inc.. . . . . . . . . . . . . . . . . . .Cryol 150A
Texaco, Inc. . . . . . . . . . . . . . . . . . . . . . . . . . . . .Capella WF-32
Witco Chemical Co.. . . . . . . . . . . . . . . . . . . . . . . . .Suniso 3GS
Do not use oil that has been drained out, or oil that has been exposed to atmosphere.
B. Remove Oil
Pump down compressor to 2 psig. Loosen the
1
/4-in. pipe plug at the compressor base and all ow t he oil to seep o ut past the threads of the plug. Retighten plug when level is correct.
NOTE: The crankcase is slightly pressurized. Do not remove the plug, or the entire oil charge will be lost.
Small amounts of oil can be removed through the oil pump discharge connection while the compressor is running.
VI. START UNIT
The field disconnect is closed, the fan circuit breaker is closed, and the s pace the rmos tat is se t abov e ambi ent so t hat there is no demand for cooling. Only the crankcase heater will be energized.
Next, close the compressor circuit breaker and then reset space thermostat below ambient so that a call for cooling is ensured.
NOTE: Do not use circu it breake r to start and stop the com­pressor except in an emergency.
After starting, there is a delay of at least 3 seconds before compressor starts.
VII. ADJUST REFRIGERANT CHARGE
CAUTION: Never charge liquid into the low-
pressure side of system. Do not overcharge. During charging or removal of refrigerant, be sure indoor-fan system is operating.
CAUTION: Charge unit on cooling cycle only. If unit is charged on heating cycle, overcharging may occur.
Refer to Charging Charts Fig. 19A-19C and Table 8. Do not exceed maximum refri gerant charge. Vary refrigerant until the conditions of the chart are met. Note that charging charts are different from type normally used. Charts are based on charging the un its to the corr ect subc ooling for the various operating conditions. Accurate pressure gage and temperature sensing device are required.
Connect the pressure ga ge to the service port on the liquid line service valve. Mount the temperature sensing device on the liquid line, close to the l iquid line servi ce valve and insulate it so that outdoor ambient temperature does not affect the reading. Indoor airflow mus t be withi n the norm al operating range of the unit. Operate unit a minimum of 15 minutes. Ens ur e press ur e and tem per atu re re adin gs h a v e stabilized. Plot liquid pressure and temperature on chart and add or reduce charge to meet curve. Adjust charge to conform with charging chart, using the liquid pressure and temperature to read chart.
If the sight glass is cloudy, check refrigerant charge again. Ensure all fans are operating. Also ensure maximum allo w­able liquid lift has not been exceeded. If charged per chart and if the sight glass is still cloudy, check for a plugged filter drier or a partially closed solenoid valve. Replace or repair, as needed.
VIII. CHECK HEATING CYCLE OPERATION
Place thermostat selector switch at HEAT and reset the space set point above ambient temperature so that a call for heating is ensured. Compressor will start wi thin 5 minutes. Observe system operation.
IX. CHECK COMPRESSOR OIL LEVEL (541A)
After adjusting the refrigerant charge, allow the system to run fully loaded for 20 minutes. Running oil level should be within view in the cran kcas e si ght g las s. Stop comp resso r a t the field power supply disconnect and check the crankcase oil level. Add oil o n l y if ne ce ssa r y to br ing the oil into view in the sight glass. If oil is added, run the system for an addi­tional 10 minu tes, then stop and check oil level . If the level remains low, check the piping system for proper design for oil return; also check the system for leaks.
If the initial check shows too much oil (too high in the sight glass) remove oil to proper level. See Preliminary Oil Charge section for proper procedure for adding and removing oil.
When the above checks are complete, repeat the procedure with the unit operating at minimum load conditions. Unload the compressor by disconnecti ng the field-control circuit lea d
at TB2 .
Y2
Reconnect the field-control circuit lead when checks are complete.
X. FINAL CHECKS
Ensure all safety controls are operating, control panel covers are on, and the service panels are in place.
Table 8 — Maximum Refrigerant Charge
UNIT
575B 072 27.0
575C
541A 180 62.0
090 34.2 120 34.2
R-22
(lb)
17
0
60
54
49
43
38
32
27
21
LIQUID TEMPERATURE AT LIQUID VALVE (C)
16
10
Fig. 19A — 575B072 Charging Chart
140
130
ADD CHARGE IF ABOVE CURVE
120
110
100
90
80
LIQUID TEMPERATURE AT LIQUID VALVE (F)
70
60
50
344
100
50
150 200 250 300 350 40
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
1034
689
LIQUID PRESSURE AT LIQUID VALVE (Kilopascals)
REDUCE CHARGE IF BELOW CURVE
1379
1724
Fig. 19B — 575C090,120 Charging Chart
Fig. 19C — 541A180 Charging Chart
2069
2414
SEQUENCE OF OPERATION
I. 575B072 UNITS
When power is supplied to unit, the transfor mer (TRAN) a nd crankcase heater (CCH) are energized.
A. Cooling
On a call for cooling, the thermostat completes the following circuits: R-G, R-Y , and R-O . If the compressor recycle delay of 3 minutes is complete, the compressor and outdoor fan start. The reversing valv e is energized for cool ing and the indoor­fan motor starts.
When the thermostat is satisfied, the circuits are opened, and the compressor, outdoor-fan motor, and indoor-fan motor stop. The reversing valve is deenergized.
B. Heating
On a call for heating, the thermostat completes the following circuits: R-G and R-Y. If the compressor recycle delay of 3 minutes is complete, the compressor and outdoor fan start. The indoor-fan motor will also start.
If room temperature continues to fall, the thermostat completes circuit R-W. If the optional electric heat package is used, the heat relay is energized, and the electric heaters are energized.
When the thermostat is satisfied, the circuits are opened, and the compressor, outdoor-fan motor, heaters, and indoor­fan motor stop.
C. Defrost
Defrost board (DB) is a time and temperature control, which includes a field-selectable time period between checks for frost (30, 50, a nd 90 minutes). Electron ic timer and defrost cycle start only when contactor is energized and defrost ther­mostat (DFT) is cl osed (below 28 F).
Defrost mode is identical to Cooling mode, except outdoor-fan motor (OFM) stops and a bank of supplemental electric heat turns on to warm air supplying the conditioned space. Defrost mode is terminated when the DFT reaches 65 F.
D. Air Circulation
When the fan switch is at FAN ON, the indoor-air fans oper­ate continuously to provide ventilation. The thermostat operates the other components as described above.
E. Emergency Heat Cycle
If the compressor is inoperative due to a tripped safety device, the second stage of the thermostat automatically energizes the ind oor-air fan and t he el ectri c resis tance heat­ers (if equipped).
II. 575C090,120 UNITS
When power is supplied to unit, the transformer (TRAN) is energized. The crankcase heater is also energized.
A. Cooling
With the thermostat subbase in the cooling position, and when the space temperature comes within 2° F of the cooling set point, the thermostat makes circu it R-O. This energizes the reversing valve solenoid (RVS) and places the unit in standby condition for cooling.
As the space temperature continues to rise, the second stage of the thermostat m ak es, closing ci rcuit R-Y. When compres­sor time delay (5 ± 2 minutes) is completed, a circuit is made to contactor (C), starting the compressor (COMP) and outdoor-fan motor (OFM). Circuit R-G is made at the same time, energizing the ind oor-fan contactor (IFC) and starting the indoor-fan motor (IFM) after one-second delay.
18
When the thermost at is satisfied, contacts open, deenergiz­ing C. The COMP, IFM, and OFM stop.
B. Heating
On a call for heat, thermostat make s circuits R-Y and R-G. When compressor time delay (5 ± 2 minutes) is completed, a circuit is made to C, starting COMP and OFM. Circuit R-G also energizes IFC and starts IFM after a 1-second delay.
III. 541A180 UNITS
A. Heating
Place thermostat selector at HEAT and set temperature selector above room ambient.
B. Cooling
Place thermostat selector at COOL and set temperature selector below room ambient.
When thermosta t calls for unit ope ration (eithe r heating or cooling), the indoor-fan motor starts immediately. The outdoor-fan motors and compressor start within 3 seconds to 5 minutes depending on when unit was last shut off by ther­mostat, because u nit contains a compressor ti me delay cir­cuit. When fir st-stage cooling is re quired, thermost at (TC1) closes, causing the heat pump to start with an unloaded com­pressor. When TC2 closes, demanding addition a l c ooli ng, the compressor loads to full load operation.
During heating, compressor is always fully loaded. When TH1 demands first-stage heating, the heat pump starts within 3 seconds to 5 minutes depending on when unit was last shut off by thermostat, because unit c onta ins a compr e s­sor time delay circuit. (The defrost board has speed termi­nals to shorten this cycle.) When TH2 of the thermostat closes, auxiliary heat supply (electric strip heat) is ener gize d in 1 or 2 stages dependin g on number of stages availab le and whether outdoor ther mostats are closed.
Defrost is achieved by reversal fro m heating to cooling cycle and deenergization of outdoor-fan motors, allowing hot refrigerant gas to defrost outdoor coil. Defrost is achieved with a timer set to initiate defrost every 30, 50, or 90 minutes (factory set at 30 minutes).
Defrost is initiated when refrigerant temperature leaving the outdoor coil is me asured below 2 7 F, (typical ly when the outdoor ambi en t tem perature is be lo w 4 5 F a s sen s ed b y t he defrost thermostat [DFT]).
Defrost is terminated when: The refrigerant temperature rises to 80 F at the DFT location on the liq uid line; or the refrigerant pressure rises to 280 psig at the HPS2 l ocation on the liquid line; or the defrost timer completes the 10-minute cycle.
IV. DUPLEX UNITS
A. Duplex 575C120 Units with 524A-H240 (See Fig. 12)
Cooling When the thermostat is set for cooling, and the space tem-
perature comes within 2° F of the coolin g set point, the the r­mostat completes the circuit from R to O a nd the reversing valves in both un its are energiz ed. If the space temperature continues to rise, the circuit from R to Y1 is completed. If the time delays and safeties are satisfied, the compressor contac­tor closes, starting the compressor and outdoor-fan motors of Heat Pump A. A t t h e sa me t i me th e c ir cuit is c o mpl ete d fro m R to G, starting the indoor-fan mot or. If the space temp era­ture continues to rise, the circuit is completed from R to Y2 and the Cooling mode is initiated in Heat Pump B in a similar ma nner.
When the thermostat is satisfied, the contacts open, deene r­gizing first the Heat Pump B and then Heat Pump A.
Heating When the thermostat calls for heating, the circuit from R to
Y1 is completed. If the time delays and safeties are satisfied, the compressor contactor closes, starting the compressor and outdoor-fan motors of Heat Pump A and Heat Pump B. At the same time the circuit is completed from R to G, starting the indoor-fan motor. If the second stage of heating is required, the circuit from R to W2 will be compl eted and the electric resistance heaters will be energized.
When the thermostat is satisfied, the contacts open, deene r­gizing Heat Pump A an d Heat Pump B.
B. Duplex 575C120 and 541A180 Units With 524A-H300 (See Fig. 13)
Cooling When the thermostat c alls for cooling, the circui t from R to
Y1 is completed. If the time delays and safeties are satisfied, the compressor contactor closes, starting the compressor and outdoor-fan motors of Heat Pump A (541A180). At the same time the circuit is completed from R to G, starting the indoor­fan motor. If the space temperature continues to rise, the circuit is completed from R to Y2 and the Cooling mode is initiated in Heat Pump B (575C120).
When the thermostat is satisfied, the contacts open, deene r­gizing first the Heat Pump B and then Heat Pump A.
Heating When the thermostat calls for heating, the circuit from R to
W1 is completed. If the time delays and safeties are satisfied, the compressor contactor closes, starting the compressor and outdoor-fan motors of Heat Pump A and Heat Pump B. At the same time the circuit is completed from R to G, starting the indoor-fan motor. If the second stage of heating is required, the circuit from R to W2 will be compl eted and the electric resistance heaters will be energized.
When the thermostat is satisfied, the contacts open, deene r­gizing Heat Pump A an d Heat Pump B.
C. Safeties
The high-pressure switch, loss-of-charge switch, oil pressure safety switch, and compressor overtemperature safety are located in a CLO circuit that prev ents heat pump operation if these safety devices are activated. A light at the thermo­stat energizes when CLO c irc ui t i s af fe cte d. Th e lo ckout s ys ­tem can be reset by adjusting the thermostat to open the contacts (down for Heating mode, up for Cooling mode), deenergizing the CLO circuitry. Compressor overcurrent pro­tection is achieved with a circuit breaker which requires manual resetting at the outdoor unit control box.
The unit is equipped with an oil pressure safety switch that protects the compr essor if oil pressure does not devel op on start-up or is lost during operation. The oil pressure switch is of the manual reset type and therefore must be reset at the outdoor unit. DO NOT RESET MORE THAN ONCE.
If oil pressure switch trips, determine cau se and correct. DO NOT JUMPER OIL PRESSURE SAFETY SWITCH.
To reset the oil pressu re switch:
1. Disconnect power to the unit.
2. Press the RESET button on the oil pressure switch.
3. Reconnect power to the unit.
19
Unit is equipped with a no-dump reversing valve circuit. When unit is in Cooling mode, reversing valve remains in cooling positi on unti l a cal l for he ating is reque sted by ther­mostat. When unit is in Heating mode, reversing valve remains in heating position until there is a call for cooling.
The crankcase heater is in a lockout circuit. If crankcase heater is defective, compressor is locked off. Heat pump remains off until cor rective action i s taken. The locko ut cir­cuit cannot be reactivated by adjusting the thermostat. To reset the crankcase heater lockout, disconnect and then reconnect power to unit.
D. Check Operation
Ensure operation of all safety controls. Replace all service panels. Be sure that control panel cover is closed tightly.
V. RESTART
Manual reset of the 24-v control circu it is necessary if unit shutdown is caused by automatic reset devices (including IP [internal compressor overcurrent protection], HPS [high­pressure switch], and LCS [loss-of-charge switch]) or if shutdown is caused by manual reset devices (including OPS [oil pressure switch] and compressor circuit breaker protection). To restart the unit when IP, HPS, or LCS has tripped (after device has reset automatically), open an d then close the thermostat contacts. Opening and then closing thermostat contacts interrupts and restores 24-v power to the compressor lockout (CLO), which resets the circuit.
It is necessary to manually reset the compressor circuit breaker and OPS at the unit if either of these safeties should shut down the unit.
IMPORTANT: If OPS trips, it must be reset first before mak- ing and breaking the thermostat contacts to reset CLO. If this procedure is not followed, the CLO cannot reset.
VI. CAUSES OF COMPLETE UNIT SHUTDOWN:
• interruption of supplied power
• open compressor overtemperature prote c tion (IP)
• compressor electrical overload prote c tion (CB)
• open high-pressure or loss-of-charge safety switches
• open oil pressure switch
• open crankcase heater lockout (C LO2)
• open control circuit fuse (FU1 or FU2)
• open discharge gas thermostat (575C only)
SERVICE
I. COMPRESSOR REMOVAL
See Table 1 for compressor informatio n. Follow safety codes and wear safety glasses and work gloves.
1. Shut off power to unit. Remove unit access panel.
2. Recover refrigerant from system using refrigerant recovery methods, and in accor dance with local and national standards.
3. Disconnect compressor wiring at compressor termi­nal box.
4. Disc onnect refrigerant lines from compressor.
5. Remove screws from compressor mounting plate.
CAUTION: Exce ssive movement of copper lines at compressor may cause higher l evels of vibration when unit is restored to service.
6. Remove or disconnect crankcase heater from com­pressor base.
7. Remove compressor from unit.
8. On 541A180 un it remove co mpressor ho lddown bolts and lift compressor off mounting plate.
9. Clean system. Add new liquid line filter drier.
10. Install new compressor on compressor mounting plate and position in unit. Connect suction and dis­charge lines to compressor. Secure mounting plate with compressor to unit. Ensure that compressor holddown bolts are in place. Connect wiring. Install crankcase heater.
11. Evacuate and recharge unit.
12. Restore unit power.
II. 575C090,120 COOLING MODE OPERATION (See Fig. 20)
1. High pressure, high temperature refrigerant vapor from the compressor flows through the reversing valve and is directed to the vapor headers of both outdoor coils.
2. At the o utdoor coil vapor header, the high pressure, high temperature refrigerant vapor flows up to check valve “A” that blocks the flow. All the refrigerant is then directed to flow into the coil circuits.
3. Subcooled refrigerant liquid leaves the coil circuits through the side outlet on the liquid headers. The liquid refrigerant from each coi l flows through check valves “B” which are op en, enters the l iquid line an d goes to the indoor c oil.
4. The liquid refrigerant is expanded and evaporated in the indoor coil result ing in low pressure vapor. This low pressure vapor returns to the outdoor unit through the system vapor line, reversing valve, and accumulator, reentering the compressor at the suc­tion connection.
III. 575C090,120 HEATING MODE OPERATION (See Fig. 21)
1. High pressure, high temperature refrigerant vapor from the compressor flows through the reversing valve and is directed through the system vapor line to the indoor coil. Refrigerant is condensed and sub­cooled in the indoor co il and returns to the outdoor unit through the system liquid line.
2. Check valve “B” blocks the flow of liquid and the liquid refrigerant must flow through the filter driers, through check valve “C”, and into the liquid header assembly.
3. The liquid refrigerant is expanded as it passes through the fixed orifice metering devices into outdoor coil circui ts. The refrigera nt evaporat es as it passes through the coil circuits resulting in low pressure vapor.
4. The low pressure vapor leaves the coil circuits and enters the vapor headers, check valves “A” are open, and return s to th e com pre ss or th ro ug h th e vap or li ne , reversing valve, and accumulator, reentering the compressor at the suction connection.
20
IV. 541A180 COOLING MODE OPERATION (See Fig. 22)
1. High pressure, high temperature refrigerant vapor from the compressor flows through the reversing valve and is directed to the outdoor coil vapor header.
2. At the outdoor coil vapor header, the high pressure, high temperature refrigerant vapor flows up to check valve “A” that blocks the flow. All the refrigerant is then directed to flow into the coil circuits.
3. Subcooled refrigerant liquid leaves the coil circuits entering the portion of the vapor header which is above check valve “A”. Check valve “C” is closed, therefore, the liquid refrigerant passes through check valve “B,” which is open, and enters the liquid line and goes to the indoor coil.
4. The liquid refrigerant is expanded and evaporated in the indoor coil resulting in low pressure vapor. This low pressure vapor returns to the outdoor unit through the system vapor line, reversing valve, and accumulator, reentering the compressor at the suc­tion connection.
V. 541A180 HEATING MODE OPERATION (See Fig. 23)
1. High pressure, high temperature refrigerant vapor from the compressor flows through the reversing valve and is directed through the system vapor line to the indoor coil. Refrigerant is condensed and subcooled in the indoor coil and returns to the outdoor unit through the system liquid line.
2. Check valve “B” blocks the flow of liquid and the refrigerant is then directed to flow through check valve “C” (which is open), through the filter drier, and into the liquid header assembly.
3. The liquid refrigerant is expanded as it passes through the capillary tubes into outdoor coil circuits. The refrigerant eva porates as it passes throug h the coil circuits resulting in low pressure vapor.
4. The low pressure vapor leaves the coil circuits and enters the vapor header, check valve “A” is open, and returns to the compressor through the vapor line, reversing valve, and accumulator, reentering the compressor at the suction connection.
VI. CRANKCASE HEATER
The crankcase heater prevents refrigerant migration and compressor oil diluti on during shutdown when compressor is not operating.
Close both compress o r se rvice val ves when cr ankc as e h eate r is deenergized for more than 6 hours.
VII. OUTDOOR UNIT FANS
Each fan is suppor ted by a formed -wire mount bolted to the fan deck and covered wit h a wi re guard. O n the 54 1A18 0, the exposed end of the mo tor shaft is covered wi th a rubber boot. In case a fan motor must be repaired or replaced, be sure the rubber boot i s put back on when the fan is reinst alled and be sure the fan guard is in place before starting the unit.
VIII. LUBRICATION
Fan motors have permanently sealed bearings. No further lubrication is required.
COMPRESSOR
REVERSING VALVE
ACCUMULATOR
CK VALVE B
CK VALVE A
CK VALVE C
FILTER DRIER
FIXED ORIFICE METERING DEVICE
FILTER DRIER
LIQUID LINE
Fig. 20 — 575C090,120 Cooling Mode (Size 090 Shown)
VAPOR LINE
BALL VALV E
BALL VALV E
FROM INDOOR UNIT
TO INDOOR UNIT
21
COMPRESSOR
REVERSING VALVE
ACCUMULATOR
CK VALVE B
CK VALVE A
CK VALVE C
FILTER DRIER
FIXED ORIFICE METERING DEVICE
FILTER DRIER
LIQUID LINE
Fig. 21 — 575C090,120 Heating Mode (Size 090 Shown)
VAPOR LINE
BALL VALV E
BALL VALV E
TO INDOOR UNIT
FROM INDOOR UNIT
CK VALVE B
CK VALVE A
FILTER DRIER
COMPR
GAS AND OIL
MUFFLER
ACCUMULATOR
HOT GAS
REVERSING
VALV E
REFRIGERANT MIXTURE
FROM INDOOR COIL
LIQUID
LLSV
TO INDOOR COIL
ANGLE VALV E WITH SCHRADER PORT
COIL RETURN
BEND END
CK VALVE C
Fig. 22 — 541A180 Cooling Mode
22
CK VALVE B
COMPR
GAS AND OIL
MUFFLER
ACCUMULATOR
REVERSING
VALV E
REFRIGERANT MIXTURE
TO INDOOR COIL
LIQUID
LLSV
FROM INDOOR COIL
ANGLE VALV E WITH SCHRADER PORT
CK VALVE A
FILTER
DRIER
CK VALVE C
COIL RETURN
BEND END
Fig. 23 — 541A180 Heating Mode
IX. COIL CLEANING AND MAINTENANCE
This section discusses the cleaning and the maintenance of standard coils and E-Coated coils. Routine cleaning of coil surfaces is essenti al to mi ni mize c o ntam ina tion b uil d-up and remove harmful residue. Ins pect coils monthly and cl ean as required.
A. Cleaning Standard Coils
Standard coils can be cleaned with a vacuum cleaner, washed out with low velocity water, blown out with com­pressed air, or brushed (do not use wire brush). Fan motors are dripproof but not waterproof. Do not use acid cleaners.
Clean coil annually or as required by location or outdoor air conditions. Inspect coil monthly and clean as required. Fins are not continuous through coil sections. Dirt and debris may pass through first section and become trapped, restricting airflow. Use a flashlight to determine if dirt or debris has col­lected between coil section s.
Clean coils as follows:
1. Turn off unit power.
2. Remove screws holding rear corner posts and top cover in place. Pivot top cover up 12 to 18 in. and support with a board or other adequate rigid support. See Fig. 24.
3. Remove clips securing tube sheets together at the return bend end of the coil. Carefully sp read the ends of the coil rows apart by moving the outer sections. See Fig. 25.
4. Using a water hose or other suitabl e equipment, flu sh down between the sections of coil to remove dirt and debris.
HOT GAS
5. Clean the remaining surfaces in the norma l manner.
6. Reposition outer coil sections. Reinstall clips which secure tube sheets, and replace top cover and rear corner posts.
7. Restore unit power.
B. Cleaning and Maintaining E-Coated Coils
Routine cleaning of coil surfaces is essential to maintain proper operation of the unit. Elimination of contamination and removal of harmf ul res idue wil l greatl y increa se the l ife of the coil and extend the life of the unit. The following maintenance and cleaning procedures are recommended as part of the routine maintenance activities to extend the life of the coil.
Remove Surface Loaded Fibers Debris such as dirt and fibers on the surface of the coil
should be removed with a vacuum cleaner. If a vacuum cleaner is not available, a soft brush may be used. The clean­ing tool should be applied in the direction of the fins. Coil surfaces can be easily damaged (fin edges bent over) if the tool is applied across the fins.
NOTE: Use of a water stream, such as a garden hose, against a surface loaded coil will drive the fibers and dirt into the coil. This will make cleaning efforts more difficult. Surface debris must be completely removed prior to using low veloc­ity clean water rinse.
Periodic Clean Water Rinse A periodic clean water rinse is very beneficial for coils that
are applied in coastal or industrial environments. However, it is very important that the water rinse is made with very low velocity water stream to avoid damaging the fin edges. Monthly cleaning is recommended.
23
Fig. 24 — Pivot and Support Top Cover
Fig. 25 — Coil Cleaning (Typical)
The following field supplied equipment is required for coil cleaning:
1
•2
/2 gallon garde n sp rayer
• water rinse with low velocity spray nozzle Environmentally Sound Coil
Cleaner Application Instructions Perform the following procedure to clean the coil. NOTE: Wear proper eye protection such as safety glasses
during mixing and application.
1. Remove all surface debris and dirt from the coil with a vacuum cleaner.
2. Th oro ughl y we t fin ned s u rfac es with cl ea n water and a low velocity garden hose, being careful not to bend fins.
3. Mix Environmentally Sound Coil Cleaner in a 21/2 gallon garden sprayer according to the instruc­tions included with the cleaner. The optimum solution temperature is 100 F.
CAUTION: DO NOT USE water in excess of 130 F. Enzymes in coil cleaner will be destroyed and coil cleaner will not be effective.
4. Thoroughly apply Environmentally Sound Coil Cleaner solution to all coil surfaces including finned area, tube sheets, and coil headers. Hold garden sprayer nozz le clos e to f inned ar eas and appl y cl eaner with a vertical, up-and-down motion. Avoid spraying in horizontal pattern to minimize potential for fin damage. Ensure cleaner thoroughly pen etrates deep into finned ar eas. Interior and exterior f inned areas must be thorough ly cleaned.
5. Allow finned surfaces to remain wet with cleaning solution for 10 minutes. Ensure surfaces are not allowed to dry before rinsing. Reapply cleaner as needed to ensure 10-minute saturation is achieved.
6. Thoroughly rinse all surfaces with low velocity clean water us in g do wn wa rd r in si ng m ot io n of wa te r sp r ay nozzle. Protect fins from damage from the spray nozzle.
Routine Cleaning of E-Coated Coil Surfaces Monthly cleaning with Environmentally Sound Coil Cleaner
is essential to extend the life of coils. It is recommended that all coils including standard aluminum, pre-coated, copper/copper, or E-coated coils be cleaned with the Envir on­mentally Sound Coil Cleaner as described below. Coil clean­ing should be part of th e regularly scheduled maintenance procedures of the un it to ensure long life of the coil. Failure to clean the coils may result in reduced durability in the environment.
Environmentally Sound Coil Cleaner is non-bacterial, biodegradable and will not harm the coil or surrounding components such as electrical wiring, painted metal surfaces or insulation. Use of non-recommended coil cleaners is strongly discouraged since coil and unit durability could be affected.
CAUTION: Do not use bleach, harsh chemicals, or acid cleaners on outdoor or indoor coils of any kind. These types of cleaner s are difficult to rinse, and they promote rapid corrosion of the fi n coll ar — coppe r tube connection. Only use the Environmentally Sound Coil Cleaner.
Never use high pressure air or liquids to clean coils. High pressures damage coils and increase the airside pressure drop. To promote unit integrity, follow clean­ing and maintenance procedures in this do cument.
X. REPLACEMENT PARTS
A complete list of replacement parts is available from your Bryant dealer.
24
LEGEND
CCH — Crankcase Heater
N.C. — Normally Closed
TROUBLESHOOTING CHART — HEATING CYCLE
25
LEGEND
CCH — Crankcase Heater
TXV — Thermostatic Expansion Valve
TROUBLESHOOTING CHART — COOLING CYCLE
Copyright 2004 Bryant Heating & Cooling Systems Printed in U.S.A. CATALOG NO. 5357-506
START-UP CHECKLIST
I. PRELIMINARY INFORMATION
OUTDOOR UNIT: MODEL NO. _______________________________ SERIAL NO.: ____________________________ ______ INDOOR UNIT: MODEL NO. _________________________________ SERIAL NO.: __________________________________ ADDITIONAL ACCESSORIES __________________________________________________________________________________
II. PRE-START-UP
OUTDOOR UNIT
IS THERE ANY SHIPPING DAMAGE? (Y/N)____________ IF SO, WHERE:________ ________________________________________________________________________________________
_______________________________________________________________________________________________________________ WILL THIS DAMAGE PREVENT UNIT START-UP? (Y/N) _____________ CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT? (Y/N) _____________ HAS THE GROUND WIRE BEEN CONNECTED? (Y/N) ____________ HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY? (Y/N) ___________ ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? (Y/N) ___________ HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED (Washers are snug, but not tight)?
(Y/N) _______________
CONTROLS
ARE THERMOSTAT AND INDOOR FAN CONTROL WIRING CONNECTIONS MADE AND CHECKED? (Y/N)_______________
ARE ALL WIRING TERMINALS (including main power supply) TIGHT? (Y/N) ______________ HAS CRANKCASE HEATER BEEN ENERGIZED FOR 24 HOURS? (Y/N) ______________
INDOOR UNIT
HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE? (Y/N) ____________ ARE PROPER AIR FILTERS IN PLACE? (Y/N)_________ _____ HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT? (Y/N)____________ DO THE FAN BELTS HAVE PROPER TENSION? (Y/N) ________________ HAS CORRECT FAN ROTATION BEEN CONFIRMED? (Y/N)________________
PIPING
HAVE LEAK CHECKS BEEN MADE AT COMPRESSOR, OUTDOOR UNIT, INDOOR UNIT, TXVs (Thermostatic Expansion Valves), SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS WITH A LEAK DETECTOR? (Y/N)_______ _________
LOCATE, REPAIR, AND REPORT ANY LEAKS. ___________________________________________________________ ______ HAVE ALL COMPRESSOR SERVICE VALVES BEEN FULLY OPENED (BACKSEATED)? (Y/N)___________ HAS LIQUID LINE SERVICE VALVE BEEN OPENED? (Y/N)___________ IS THE OIL LEVEL IN COMPRESSOR CRANKCASE VISIBLE IN THE COMPRESSOR SIGHT GLASS?
(Y/N) _______________
CHECK VOLTAGE IMBALANCE
LINE-TO-LINE VOLTS: AB_ __________ V AC___________ V BC ___________V (AB + AC + BC)/3 = AVERAGE VOLTAGE =________________V MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =_______________V VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) = _______________ % IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!
CALL LOCAL POWER COMPANY FOR ASSISTANCE.
CL-1
III. START-UP
CHECK INDOOR FAN SPEED AND RECORD._______________ CHECK OUTDOOR FAN SPEED AND RECORD.________________ AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:
COOLING HEATING
OIL PRESSURE ______________ ____ __________________ SUCTION PRESSURE _______ ___________ _____ _____________ SUCTION LINE TEMP ______________ ____ __________________ DISCHARGE PRESSURE __________________ __________________ DISCHARGE LINE TEMP __________________ __________________ ENTERING OUTDOOR AIR __________________ __________________ LEAVING OUTDOOR AIR TEMP __________________ ____________ ______ INDOOR ENTERING-AIR DB (d ry bulb) TEMP __________________ __________________ INDOOR ENTERING-AIR WB (wet bulb) TEMP __________________ __________________ INDOOR LEAVING-AIR DB TEMP __________________ __________________ INDOOR LEAVING-AIR WB TEMP ______________ ____ __________________
COMPRESSOR AMPS (L1/L2/L3) _______ / _______ / _______ _______ / ____ ___ / _______ CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES; ARE THE SIGHT GLASSES SHOWING
OIL LEVEL IN VIEW? (Y/N)
NOTES:
______________________________________________________________________________________________________________ ______________________________________________________________________________________________________________ ______________________________________________________________________________________________________________ ______________________________________________________________________________________________________________ ______________________________________________________________________________________________________________ ______________________________________________________________________________________________________________ ______________________________________________________________________________________________________________ ______________________________________________________________________________________________________________ ______________________________________________________________________________________________________________ ______________________________________________________________________________________________________________ ______________________________________________________________________________________________________________ ______________________________________________________________________________________________________________
CUT ALONG DOTTED LINE
Copyright 2004 Bryant Heating & Cooling Systems Printed in U.S.A. 10-05A CL-2 CATALOG NO. 5357-506
CUT ALONG DOTTED LINE
Loading...