Bryant 575B User Manual

wiring diagrams
SPLIT-SYSTEM HEAT PUMP UNITS
Cancels: WD 575C.90.1 WD 575B.72.1
DIAGRAM INDEX
575C/575B
Sizes 072 to 120
with
524A-H
6/15/03
UNIT SIZE
575B
575C
524A-H
*Units produced after 3/31/03.
C— CAP — CB — CCH, CH — CDT — CLO — COMP — CTD — DFC — DFT — DGT — EQUIP — FM — GND — HP, HPS — IFC — IFM
072
090-120
090-120 Applies to all Unit Wiring Diagram Not Available 9
Contactor, Compressor Capacitor Circuit Breaker Crankcase Heater Contactor Dummy Terminal Compressor Lockout Compressor Compressor Time Delay Defrost Control Defrost Thermostat Discharge Gas Thermostat Equipment Fan Motor Ground High-Pressure Switch Indoor-Fan Contactor Indoor-Fan Motor
CHARACTERISTICS
ELECTRICAL
(V-Ph-Hz)
208/230-3-60
460-3-60 2 575-3-60 2
208/230-3-60
460-3-60 38AK540180 5 or 6* 575-3-60 38AK540211 7 or 8*
Control Schematic and Component Arrangement Not available
Control Schematic and Component Arrangement
TYPE
LABEL DIAGRAM
NUMBER
38AK540179 3 or 4*
FIGURE NO.
LEGEND (Fig. 1-9)
LAR — LAS — LCS — LLSV — LP, LPS — MMR — NEC — OF, OFM — OFR — PL — PS — RV — RVS — TB — TRAN(S) — T’STAT
Low Ambient Relay Low Ambient Switch Loss-of-Charge Switch Liquid Line Solenoid Valve Low-Pressure Switch Motormaster® Relay National Electrical Code Outdoor-Fan Motor Outdoor-Fan Relay Plug Pressure Switch Reversing Valve Reversing Valve Solenoid Terminal Block Transformer Thermostat
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked) Terminal Block
Splice Factory Power W ir in g Factory Control Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring To indicate common potential only, not to represent wiring.
1
NOTES (Fig. 1 and 2)
1. F actory wiring is in accordance with N at i on al E l ec tr i­cal Code (NEC). Field modifications or additions must be in compliance with all applicable codes.
2. Use copper conductors onl y.
3. CAUTION: Not suitable for use on systems exceedin g 150 volts to ground.
4. Manual reset circuit breaker is integral to the transformer.
NOTES (Fig. 3-8)
1. If any of the original wire furnished must be replaced, it must be replaced with type 90° C wire or its equivalent.
2. For thermostat and subbase part no. see price pages.
3. Set heat anticipator at .6.
4. Use copper conductors only.
5. Three-phase motors are protected under primary single phasing conditions.
6. 39 VA available for field-installed acces sories. Control power requirement for heat pump condensing unit is 36 VA (sealed). Supplied control transformer is 75 VA.
NOTES (Fig. 9)
1. Factory wiring is in accordance with National Electri­cal Code (NEC). Field modifications or additions must be in compliance with all applicable codes.
2. Use copper conductors only.
SEQUENCE OF OPERATION —
575B OUTDOOR UNIT WITH
524A-H INDOOR UNIT
When power is supplied to unit, the transformer (TRAN) and crankcase heater (CCH) are energized.
Cooling
On a call for cooling, the thermostat c ompletes the following circuits: R-G, R-Y, and R-O. If the compressor recycle delay of 3 minutes is complete, the compre ssor and outd oo r fan sta rt. The reversing valve is en ergized for cooling and the indo or­fan motor starts.
When the thermostat is satisfied, the circuits are opened, and the compressor, outdoor-fan motor, and indoor-fan motor stop. The reversing valve is dee nergized.
Heating
On a call for heating, the thermostat completes the following circuits: R-G and R-Y. If the compressor recycle delay of 3 minutes is complete, the compre ssor and outd oo r fan sta rt. The indoor-fan motor will also start.
If room temperature continues to fall, the thermostat com­pletes circuit R-W. If the optional electric heat package is used, the hea t r elay is energized, and the elect ri c hea t ers are energized.
When the thermostat is satisfied, the circuits are opened, and the compr essor, outdoor-fan motor, heaters, and indoor­fan motor stop.
Defrost
The Defrost board (DB) is a time and temperature control, which includes a fiel d-sele ctab le time per iod between checks for frost (30, 50, and 90 minutes). Electronic timer and defrost cycle start only when contactor is energized and defrost thermostat (DFT) is closed (below 36 F [2.2 C]).
Defrost mode is identical to Cooling mode, except outdoor-fan motor (OFM) stops and a ban k of supp lemen tal ele ctric h eat (if equipped) turns on to warm air supplying the conditioned space. Defrost mode is terminated when the DFT reaches 51 F (10.6 C).
Low Ambient
Cooling head pressure control at low ambient conditions is accomplish ed through a low ambien t relay and switch. The switch is factor y se t to close at 250 psig and open at 100 psig . In Heating mode, the low ambient switch is bypassed by nor­mally closed contacts on the low ambient relay.
Air Circulation
When the fan switch is at FAN ON, the indoor-air fans oper­ate continuously to provide ventilation. The thermostat oper­ates the other components as described above.
Emergency Heat Cycle
If the compressor is inoperative due to a tripped safety device, the second stage of the thermostat automatically energizes the ind oor-air fan and th e el ectric resis tance h eat­ers (if equipped).
SEQUENCE OF OPERATION —
575C OUTDOOR UNIT WITH
524A-H INDOOR UNIT
When power is supplied to unit, the transformer (TRAN) is energized. The crankcase heater is also energized.
Cooling
With the thermostat in the cooling position, and when the space temperature comes within 2° F of the cooling set point, the thermostat makes circuit R-O. This energizes the revers­ing valve solenoid (RVS) and places the unit in standby con­dition for cooling.
As the space temperature continues to rise, the second stage of the thermostat mak es, closing circu it R-Y. When compres­sor time delay (5 ± 2 minutes) is completed, a circuit is made to contactor (C), starting the compressor (COMP) and outdoor-fan motor (OFM). Circuit R-G is made at the same time, energizing the ind oor-fan contactor (IFC) and sta rting the indoor-fan motor (IFM) after one-second delay.
When the thermostat is satisfied, contacts open, deenergiz­ing C. The COMP, IFM, and OFM stop.
Heating
On a call for heat, thermostat makes circuits R-Y and R-G. When compressor time delay (5 ± 2 minutes) is completed, a circuit is made to C, starting COMP and OFM. Circuit R-G also energizes IFC and starts IFM after a 1-second delay.
Should room temperature continue to fall, circuit R-W is made through second -s tage thermostat bulb. If optional elec­tric heat package is used, a relay is energized, bringing on supplemental electric heat. When thermostat is satisfied, contacts open, deenergizing contac tor and relay; motors and heaters deenergize.
Defrost
Defrost board (DB) is a time and temperature control, which includes a field-selectable time period between checks for frost (30, 50, a nd 90 minutes). Electron ic timer and defrost cycle start only when contactor is energized and defrost ther­mostat (DFT) is closed (below 28 F [–2.2 C]).
Defrost mode is identical to Cooling mode, except outdoor-fan motor (OFM) stops and a bank of supplemental electric heat turns on to warm air supplying the conditioned space. Defrost mode is terminated when the DFT reaches 65 F (18.3 C).
—2—
CONNECTION DIAGRAM
LOW AMBIENT
SWITCH
BL
LOW AMBIENT RELAY
COIL
R
3
1
2
PRI
BL
TRANS
G
SEC
BK
BL
PL
BK
(WHEN
BL
USED)
CAP
BR
BR
FM
T3
COMP
T1
R
R
DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT POWER BEFORE SERVICING
BL
R
R
T2
BL
BK
L3
T3
L2
T2
T1
L1
COIL
BK
BK
CCH
POWER SUPPLY PER N.E.C. AND LOCAL CODES 208/230 VAC, 60 HZ, 3 PH.
L3
GROUND EQUIPMENT PER N.E.C. AND
L2
LOCAL CODES.
BK
L1
ATTACH GROUND
208/230 VAC, 60 HZ, 3 PH POWER SUPPLY
L3
T3
R
DEFROST CONTROL
FAN
R
BL
R-RV
BL
O
Y-R V
RV
BK
COIL
RV
CC
PS2
PS1
DF
O
C
BL
R
BK
BL BL
Y
Y
BK
SEN
BK
Y
WR
TWO SWITCH WIRING
W
Y
O
DEFROST HEAT
COMPRESSOR
HEAT/COOL
PS2
PS1
LP/HP
LP/HP
COMMON
24 VAC
LADDER DIAGRAM
CCH
+t°
CONTACTOR
CONTACTOR
T2
T3
T1
CAP
FM
208/230V
TRANSFORMER NOTE 4
24V
Y-R V
FAN
RV
RESET
DEFROST CONTROL
R­RV
CC
PS2
PS1
DF
CRYWO
LAR
L2
T2
COMPRESSOR
LAS
LOW AMBIENT
21
RELAY
L1
T1
CONT.
DFC
FAN
(WHEN USED)
RV
COIL
C
COIL
LP/HP
SEN
DEFROST HEAT COMPRESSOR HEAT/COOL COMMON 24 VAC
Fig. 1 — Control Schematic and Component Arrangement — 575B072 (208/230 V)
—3—
CONNECTION DIAGRAM
BL
R
LOW AMBIENT
SWITCH
BL
LOW AMBIENT RELAY
COIL
3
1
BL
2
PL
BL
BK
G
CAP
BR
BR
FM
PRI
TRANS
SEC
R
R
BL
BL
BK
DEFROST
RELAY
R
R
BL
COIL
FAN
DANGER: ELECTRICAL SHOCK HAZARD
DISCONNECT POWER BEFORE SERVICING
R
R
T2
T3
COMP
T1
3
1
2
BL
BK
BK
L3
T3
L2
T2
L1
T1
BK
COIL
Y
Y
DEFROST CONTROL
R-RV
Y-R V
BK
RV
COIL
RV
CC
PS2
PS1
DF
C
O
BK
BL BL
Y
Y
BK
SEN
BK
Y
WR
W
BL
Y
O
O
R
575/460 VAC
60 HZ 3PH
L3
L2
BK
L1
ATTA CH
GROUND
CCH
LP/HP
PS2
PS1
LP/HP
TWO SWITCH WIRING
DEFROST HEAT
COMPRESSOR HEAT/COOL
COMMON 24 VAC
L3
CONTACTOR
T3
T3
CAP
FM
575/460V
24V
RESET
LADDER DIAGRAM
575/460 VAC 60 HZ 3PH
CCH
+t°
L2
CONTACTOR
T2
T1
TRANSFORMER NOTE 4
DFR
FAN
DEFROST CONTROL
R-
RV
T2
COMPRESSOR
LOW AMBIENT
RELAY
Y-R V RV
CC
PS2
PS1
DF
CRYWO
LAR
LAS
L1
T1
CONT.
DEFROST
RELAY
RV
COIL
C
COIL
LP/HP
1
213
SEN
DEFROST HEAT COMPRESSOR HEAT/COOL COMMON 24 VAC
Fig. 2 — Control Schematic and Component Arrangement — 575B072 (460 and 575 V)
—4—
Loading...
+ 8 hidden pages