Bryant 394B User Manual

Page 1
Bryant
Airconditioning Company
installation instructions
GAS-FIRED FORCED-
AIR FURNACE
39 4B &D
Series A
thru 200

INTRODUCTION

Before installing the furnace, refer to “Procedure for Gas Furnace Installation” (packaged with the equip ment) for information concerning combustion, vent ing, piping, and other standard installation practices.
Further reference is made to the current edition of the American National Standard “Installation of Gas Appliances and Gas Piping,” Z21.30.
Model 394 Gas Furnaces are shipped from the factory
completely assembled and wired ready for indoor heating installation. They are manufactured with two types of blowers: belt and direct drive. The four
smaller sizes, 50, 80, 100, and 125, are direct drive
only. All sizes incorporate a low-voltage terminal
strip for convenience of field wiring (except 50,000-
Btuh unit with complete shut-off gas controls.)
This publication covers installation, startup and maintenance. For accessory installation details, refer to applicable installation literature.
CAL’TTON: Do Tiot insrall hirnace in a coitosívp or coiiTaminated almosphcre. Makp sure tliaV all local ordinance's for coinbusTioii and circiilaTing air supply are obser\ed.
Cancels: 39394D82

Figure 1—Modei 394D

39394DP85
11/1/74
A72548
The design of the 394B&D Upflow Gas-Fired Fur naces is A.G.A. certified for installation on com bustible flooring in alcoves, basements, closets, or utility rooms.
CLEARANCE REQUIREMENTS
(in inches)
Sides............................................................................1
Back.............................................................................0
Top of Plenum.............................................................1
Vent Connector (single wall)
Type B (double wall)...............................................1
Front........................................................................ ..6
Provide service clearance of 30 in. at front of unit.

Bryant Automatic Gas Controi Vaive

NOTE: On units equipped with an A-643 Bryant automatic gas control valve, there are three positions for the manual valve knob (OFF-PILOT-ON). There is a position stop at the PILOT position. To move the manual valve knob from the PILOT position to either ON or OFF position, the manual valve knob must be depressed.
......................................
6
If not already checked when lighting the main burn
er, check the proper operation of this valve by moving the room thermostat pointer above and below room temperature and observing that the main burn ers light on call for heat and go off when the pointer
is moved below the room temperature setting. All
Bryant automatic gas control valves have a delay when opening or closing.

Fan/Limit Control Operation

At the moment the thermostat calls for heat, the time
delay mechanism of the control is energized. If, due to pilot outage, the control bimetal element does not
sense a temperature change, the control will turn on the blower strictly by means of the time delay feature.
If for any reason the time delay is not energized as the thermostat calls for heat, the control bimetal element will bring on the blower when it senses a temperature rise of 50 degrees Fahrenheit (standard differential)
above the turn-off setting. During the blow-down period and after the thermostat is satisfied, the con trol will turn the blower off at the indicated setting sensed by the control bimetal element.
Page 2

TABLE I—DIMENSIONS IN INCHES

MODEL & SIZE A
394D-000050
3940-024050
394D-000080
14-3/16 46-3/16
12 12
C
46-3/16 46-3/16 10-3/8 9-1/2 14-1/2 27-1/8
394D-024080 14-3/16 46-3/16
3940-036080 14-3/16 46-3/16 12-9/16 394D-000100 394D-036100 3940-048100 394D-000125 394D-036125 394D-048125 394D-060125 394D-000150 3940-048150
394D-060150 394B-060150 394D-060175 394B-060175 394B-060200
17-1/2 46-3/16 17-1/2
46-3/16 15-7/8 15 14-1/2 27-1/8 21 46-3/16 21 21
46-3/16
46-3/16 21 46-3/16 21
46-3/16 19-5/16 18-1/2 14-1/2 27-1/8
24-1/2 46-3/16 24-1/2 46-3/16 24-1/2 24-1/2 31-1/2 31-1/2
31-1/2
49 22-7/8 21 18 29-15/16 49 22-7/8 21 18 29-15/16 49 29-7/8 29 18 29-15/16 49 29-7/8 29 18 29-15/16 49 29-7/8 ' 29 18 29-15/16
D E F
10-3/8 9-1/2
14-1/2 27-1/8
12-9/16 11-11/16 14-1/2 12-9/16 11-11/16
11-11/16
15-7/8 15
19-5/16 18-1/2 19-5/16 19-5/16 19-5/16
18-1/2 14-1/2 27-1/8 18-1/2 14-1/2 27-1/8 18-1/2 14-1/2 27-1/8
14-1/2 27-1/8 14-1/2 27-1/8 14-1/2 27-1/8
14-1/2 27-1/8
G
27-1/8
22-7/8 21 14-1/2 27-1/8 22-7/8
21 14-1/2
27-1/8
H
32-9/16 32-9/16 32-9/16 32-9/16 32-9/16 32-9/16 5 32-9/16 32-9/16 32-9/16 5 32-9/16 32-9/16 5
32-9/16 5 32-9/16 32-9/16 35-3/8 6 35-3/8 6 35-3/8 35-3/8 7 35-3/8

TABLE II—RATINGS AND PERFORMANCE*

NATURAL and LP Temp
Rise
MODEL
394D-000050
3940-024050 394D-000080 394D-024080
3940-036080 394D-000100 394D-036100
Input Btuh
50,000
80,000
100,000
Output Btuh
40,000
64,000
80,000
Range
70-100 45-100 70-100 70-100 45-100 70-100 45-100
3940-048100 45-75
394D-000125 394D-036125 394D-048125
125,000 '
100,000 394D-060125 394D-000150 394D-048150 394D-060150
150,000
120,000 394B-060150 394D-060175 394B-060175
175,000
140,000 394B-060200 200,000 160,000
"The above ratings are certified for altitudes to 2000 ft. For elevations above 2000 ft. reduce ratings 4% for each 1000 ft. above sea
level.
70-100
70-100 45-100 45-75 70-100 45-100 45-75 45-100 45-100
45-100 70-100
Heating
Ext Static
Pressure
0.12
0.12
0.15
0.2
0.2
0.5
0.5 1634
Cooling
Ext Static
CFM
408
Pressure
—
482 0.5 654 — 772 0.5 772 818
—
965 0.5 1200 1157 1540 1020
—
1069 1206
0.5 1447 1225
— —
1454 1736
0.5 1447
1688 1688 2290
0.5
0.5 2460
A72591
Vent
Dia
4 4 4 4 4
5 5
5
6
6
7
7
CFM
—
780
—
790
1190
—
—
1210 1560 2000
1500
2080 2310 2010
—2-
Page 3
TO HEATING AND COOLING CONNECTIONS OF THERMOSTAT
_A
TO CONDENSER CONTACTOR COIL
CONNECTIONS
TO HEATING AND
COOLING CONNECTIONS OF THERMOSTAT
TO CONDENSER LOW-VOLTAGE LEAD OR TERMINAL STRIP
NOTE:
WIRE WITH * IN FIGURE 3 IS REMOVED AND DISCARDED WHEN CONDENSER HAS TRANSFORMER.
A73118
Figure 3—Control Box, Cover Removed,
No Internal Wiring Changes
The 175,000-Btuh belt-drive, and 200,000-Btuh units are equipped with a Honeywell fan limit control. It provides control of fan operation and high-limit tem perature protection. The fan switch makes contact to start the blower motor on temperature rise to set point. The limit switch breaks the circuit to the burn ers when the temperature rise reaches the set point.

Thermostat Location

The room thermostat should be located where it will be in the natural circulating path of room air. Avoid locations where the thermostat would be exposed to cold air infiltration, drafts from windows, doors, or other openings leading to the outside, or exposure to
air currents from warm or cold air registers; or to ex posure where the natural circulation of the air is cut off—such as behind doors, above or below mantels, shelves, etc.
The thermostat should not be exposed to heat from nearby fireplaces, radios, televisions, lamps, or rays from the sun. Nor should the thermostat be mounted
on a wall containing pipes or warm air ducts, or a flue or vent that could affect its operation and prevent it from properly controlling the room temperature. Any hole in the plaster or panel through which the wires pass from the thermostat should be adequately sealed with suitable material to prevent drafts from affecting the thermostat.
Figure 4—Control Box, Cover Removed,
Showing Internal Wiring Changes
Set the thermostat heat anticipator at 0.5. If additional controls are connected in the thermostat
circuit, the amp draw must be added to these settings. Failure to make the settings will result in improper operation of the thermostat.
ELECTRICAL CONNECTIONS
Low-Voltage Wiring
Field low-voltage connections are made at the low-
voltage terminal strip. See Figure 3. For Model 394
Furnaces used in conjunction with electric or gas air
conditioning units that do not have an integral trans former, see Figure 3. If the 394 Furnace is used in con junction with an electric or gas air conditioning unit having an integral transformer, see Figure 4.
Figure 4 shows a field-installed wire running from
one side of the air conditioning transformer, through
the hole marked “F” in the terminal strip, to the
blower relay in the control box for the Model 394 Fur
nace. The wire marked * in Figure 3 is removed from the control box and discarded.
NOTE: For heating-only connections, See Figure 8. For heating and cooling connections, see Installation In structions packaged with condensing unit.
—3—
Page 4

Line-Voltage Wiring

All electrical connections are to made in accor dance with the local electrical codes. The unit must be grounded electrically in accordance with National Electric Code and local codes governing such in stallations. A permanent and uninterrupted or un
broken ground is essential to minimizing personal in jury if an electrical fault should occur. A permanent, separately fused electric power supply, complete with manual switch, should be provided for the furnace.
Field wiring connections should be made in accor dance with the unit wiring diagrams.
When making aluminum conductor connections to copper conductors or terminals, use only connectors
that are UL approved (marked Al/Cu with the UL
symbol) for the application and wire size. Do not
reduce wire size to fit connector by cutting off strands.
Use proper size connector. After insulation has been stripped from the aluminum
conductor, coat the conductor end with corrosion inhibitor (Burndy “Penetrox A” or equivalent), and wire-brush the aluminum surface thru the inhibitor.
CAUTION: Do nor wire-brii.sh connectors atul lug.s. The plating will be broken.
After cleaning, recoat the aluminum conductor with inhibitor, and make connection, then coat entire con nection. If applicable, wrap the connection for moisture and/or electrical protection.
CAUTION: Re sure ihe filiej- relainiM- spring is behind rile flange of the casing side.
When the side inlet is used, the bottom opening should be properly and permanently sealed.
NOTE: Side inlet application of sizes 048100, 060125,
060150, 060175, and 060200 requires use of the ap propriate optional external filter rack. See in structions packed with filter rack for installation.
Figure 6—Filter installed For Side Inlet
NOTE: Some units with direct-drive blowers have a
shipping bracket. See Figure 5. This bracket should be removed and discarded. Belt-drive units have wood
shipping blocks that are to be removed and discarded.
A73115
Figure 5—Filter Installed For Bottom Inlet
Filters
The filters are factory-installed in the bottom of the furnace. This is for bottom inlet application. See Figure 5.
For side inlet application, see Figure 2 and Table I for the opening size. Remove the filter and the retainer spring from the bottom opening. Install the retainer spring in the holes provided, one in the blower deck and the other in the retainer spring bracket. See Figure 6.

STARTUP AND ADJUSTMENT

In addition to the following information, refer to “Procedures for Gas Furnace Installation” packaged
with the unit.

Adjustment of Blower Speed

Four-Speed Direct Drive To change motor speed taps, remove the motor tap
lead (see Figure 5) and relocate it on the desired ter minal on the plug-in terminal block/speed selector located on the blower.

TABLE III

SPEED SELECTOR

Speed
Common Hi Med-Hi Med-Lo Lo
Tap No.
C
1 2 3 4
Belt Drive
The blower speed may be changed by opening or closing the motor pulley. When adjusting blower speed, be certain that the pulleys are properly aligned.
CAUTION: When adjusting the blower speed, make certain that the temperature rise across the bear ex changer does not exceed that specified on ilie rating plate.
Page 5

CARE AND MAINTENANCE

WARNING: Fiecaiise personal injury or damage to
the furnaee may result, maintuname should be per­Ibrmed by qualified persons only.

Care of Blower and Motor

For long life, economy, and high efficiency; clean ac cumulated dirt and grease from blower wheel and motor annually. Also clean around bearings and
shaft(s) of blower and motor. See label on blower for oiling instructions.

Belt Tension

Adjust tension on a V-belt so that the helt deflects ap proximately 3/4 to 1 inch when the pressure from one finger is applied midway between the blower and motor pulleys.

Filters

Each furnace is shipped with a washable permanent filter. Check every 30 to 60 days. See label on blower for cleaning method. It is not necessary to spray filter with oil.
Cleaning Heat Exchanger
If it becomes necessary to clean heat exchanger—
because of carbon deposits, soot, etc.—shut off gas
and electricity. Remove burners and manifold assem bly. Remove vent connector and draft diverter. Remove flue baffles from upper heating element flue outlets by removing two screws that secure Raffles in place. Clean flueways with brush and/or vacuum. Replace flue baffles and tighten screws carefully. Replace draft diverter and vent connector. Replace
manifold and burners. Connect gas and electricity.
Test for gas leaks.
WARNING: Never use a maieh or otbor open Hanie
to eiiei’k for gas leaks. Use a sotip-aml-waier solution.
A73119
Figure 7—Removing Baffles

PILOT

Pilot should be checked and cleaned if necessary at
the beginning of each heating season. Pilot flame should be high enough for proper impingement of the safety element and to light the burners. Remove ac
cumulation of soot and carbon from thermocouple safety element, if used.
It is recommended the pilot be turned off during the summer season.

HEATING-ONLY THERMOSTAT CONNECTIONS

Figure 8—Field Wiring Connection
—5—
Page 6
LINE-TO-LINE WIRING DIAGRAMS
Figure 9 - Units with 1/10-, 1/6-, or 1/5-KP Direct-
Drive Motor (no cooling fan relay)
lA
H5V
____
jWM
Figure 12 - 50,000-Btuh Unit with B or D controls
(no cooling fan relay)
R
Figure 10 - Units with 1/6-, 1/3-, 1/2-, or 3/4-HP
________________________
A73053
Figure 13 - 50,000-Btuh Unit with B or D Controls

SEQUENCE OF OPERATION—HEATING

The pilot (6A) must be lit, closing its contacts, before the gas valve (5A) will open. If, for some reason, the gas valve does not open when thermostat calls for heat, heat assist coil (2G) causes heating relay (7J) to close its contacts, energizing blower motor (3A, 3B, or 3D).
When the thermostat calls for heat, the control circuit is closed between terminals (4 and W). Power from transformer (lA) energizes automatic gas valve coil (5A) and heat assist coil (2G) simultaneously. After a short time delay, automatic gas valve (5A) opens, per mitting gas to flow to the burners where it is ignited by the gas pilot. After another delay, the heating relay switches its contacts (7J), energizing blower motor (3A, 3B, or 3D) on heating speed.
When the thermostat is satisfied, the circuit between
terminals (4 and W) is broken, deenergizing
automatic gas valve coil (5A) and heat assist coil (2G). After a few seconds, automatic gas valve (5A)
closes, stopping’the flow of gas to the burners. After a
Direct-Drive Motor (cooling fan relay). No Capacitor on 1/6- and 1/3-HP Motors.
—Mna4-
---------------------
íMüWu
■fciti-
24V
___
_________
fepi—©■
(cooling fan relay)
longer delay, heating relay (7J) opens its contacts to stop blower motor (3A, 3B, or 3D).
If the furnace overheats for any reason, limit control
(7H) will switch, breaking the circuit to automatic gas valve coil (5A). After a short delay, the gas valve closes, shutting off the flow of gas to the burners. The furnace will continue to cycle until the fault is corrected.

SEQUENCE OF OPERATION—COOLING

When the thermostat calls for cooling, power from transformer (lA) energizes cooling relay coil (2C), closing its contacts, and energizing blower motor (3A, 3B, or 3D) on its cooling speed. It continues to operate until the thermostat is satisfied.
When the thermostat is satisfied, the circuit to ter minal (G) is broken, deenergizing cooling relay coil (2C) which, in turn, opens its contacts, stopping blower motor (3A, 3B, or 3D).
Figure 11 - Units with 3/4-HP Belt-Drive Motor
JE. JiL
a
(cooling fan relay)
LEGEND
1 A-Transformer
2A-Cooling Fan Relay 2C-Cooling Fan Relay 2G-Fleatlng Fan Relay 3A-Fan Motor SP PH 3B-Fan Motor SP 3D-Fan Motor PSC 4A-Capacitor (None on 1/6-
& 1/3-HP Motors) 5A-Gas Valve 6A-Pllot (None on LP)
7J-Fan Control SPST N.O.
If any of the original wire, as supplied, must be replaced, use same type or equivalent wire.
/
—6—
Loading...