Bryant 394B User Manual

Bryant
Airconditioning Company
installation instructions
GAS-FIRED FORCED-
AIR FURNACE
39 4B &D
Series A
thru 200

INTRODUCTION

Before installing the furnace, refer to “Procedure for Gas Furnace Installation” (packaged with the equip ment) for information concerning combustion, vent ing, piping, and other standard installation practices.
Further reference is made to the current edition of the American National Standard “Installation of Gas Appliances and Gas Piping,” Z21.30.
Model 394 Gas Furnaces are shipped from the factory
completely assembled and wired ready for indoor heating installation. They are manufactured with two types of blowers: belt and direct drive. The four
smaller sizes, 50, 80, 100, and 125, are direct drive
only. All sizes incorporate a low-voltage terminal
strip for convenience of field wiring (except 50,000-
Btuh unit with complete shut-off gas controls.)
This publication covers installation, startup and maintenance. For accessory installation details, refer to applicable installation literature.
CAL’TTON: Do Tiot insrall hirnace in a coitosívp or coiiTaminated almosphcre. Makp sure tliaV all local ordinance's for coinbusTioii and circiilaTing air supply are obser\ed.
Cancels: 39394D82

Figure 1—Modei 394D

39394DP85
11/1/74
A72548
The design of the 394B&D Upflow Gas-Fired Fur naces is A.G.A. certified for installation on com bustible flooring in alcoves, basements, closets, or utility rooms.
CLEARANCE REQUIREMENTS
(in inches)
Sides............................................................................1
Back.............................................................................0
Top of Plenum.............................................................1
Vent Connector (single wall)
Type B (double wall)...............................................1
Front........................................................................ ..6
Provide service clearance of 30 in. at front of unit.

Bryant Automatic Gas Controi Vaive

NOTE: On units equipped with an A-643 Bryant automatic gas control valve, there are three positions for the manual valve knob (OFF-PILOT-ON). There is a position stop at the PILOT position. To move the manual valve knob from the PILOT position to either ON or OFF position, the manual valve knob must be depressed.
......................................
6
If not already checked when lighting the main burn
er, check the proper operation of this valve by moving the room thermostat pointer above and below room temperature and observing that the main burn ers light on call for heat and go off when the pointer
is moved below the room temperature setting. All
Bryant automatic gas control valves have a delay when opening or closing.

Fan/Limit Control Operation

At the moment the thermostat calls for heat, the time
delay mechanism of the control is energized. If, due to pilot outage, the control bimetal element does not
sense a temperature change, the control will turn on the blower strictly by means of the time delay feature.
If for any reason the time delay is not energized as the thermostat calls for heat, the control bimetal element will bring on the blower when it senses a temperature rise of 50 degrees Fahrenheit (standard differential)
above the turn-off setting. During the blow-down period and after the thermostat is satisfied, the con trol will turn the blower off at the indicated setting sensed by the control bimetal element.

TABLE I—DIMENSIONS IN INCHES

MODEL & SIZE A
394D-000050
3940-024050
394D-000080
14-3/16 46-3/16
12 12
C
46-3/16 46-3/16 10-3/8 9-1/2 14-1/2 27-1/8
394D-024080 14-3/16 46-3/16
3940-036080 14-3/16 46-3/16 12-9/16 394D-000100 394D-036100 3940-048100 394D-000125 394D-036125 394D-048125 394D-060125 394D-000150 3940-048150
394D-060150 394B-060150 394D-060175 394B-060175 394B-060200
17-1/2 46-3/16 17-1/2
46-3/16 15-7/8 15 14-1/2 27-1/8 21 46-3/16 21 21
46-3/16
46-3/16 21 46-3/16 21
46-3/16 19-5/16 18-1/2 14-1/2 27-1/8
24-1/2 46-3/16 24-1/2 46-3/16 24-1/2 24-1/2 31-1/2 31-1/2
31-1/2
49 22-7/8 21 18 29-15/16 49 22-7/8 21 18 29-15/16 49 29-7/8 29 18 29-15/16 49 29-7/8 29 18 29-15/16 49 29-7/8 ' 29 18 29-15/16
D E F
10-3/8 9-1/2
14-1/2 27-1/8
12-9/16 11-11/16 14-1/2 12-9/16 11-11/16
11-11/16
15-7/8 15
19-5/16 18-1/2 19-5/16 19-5/16 19-5/16
18-1/2 14-1/2 27-1/8 18-1/2 14-1/2 27-1/8 18-1/2 14-1/2 27-1/8
14-1/2 27-1/8 14-1/2 27-1/8 14-1/2 27-1/8
14-1/2 27-1/8
G
27-1/8
22-7/8 21 14-1/2 27-1/8 22-7/8
21 14-1/2
27-1/8
H
32-9/16 32-9/16 32-9/16 32-9/16 32-9/16 32-9/16 5 32-9/16 32-9/16 32-9/16 5 32-9/16 32-9/16 5
32-9/16 5 32-9/16 32-9/16 35-3/8 6 35-3/8 6 35-3/8 35-3/8 7 35-3/8

TABLE II—RATINGS AND PERFORMANCE*

NATURAL and LP Temp
Rise
MODEL
394D-000050
3940-024050 394D-000080 394D-024080
3940-036080 394D-000100 394D-036100
Input Btuh
50,000
80,000
100,000
Output Btuh
40,000
64,000
80,000
Range
70-100 45-100 70-100 70-100 45-100 70-100 45-100
3940-048100 45-75
394D-000125 394D-036125 394D-048125
125,000 '
100,000 394D-060125 394D-000150 394D-048150 394D-060150
150,000
120,000 394B-060150 394D-060175 394B-060175
175,000
140,000 394B-060200 200,000 160,000
"The above ratings are certified for altitudes to 2000 ft. For elevations above 2000 ft. reduce ratings 4% for each 1000 ft. above sea
level.
70-100
70-100 45-100 45-75 70-100 45-100 45-75 45-100 45-100
45-100 70-100
Heating
Ext Static
Pressure
0.12
0.12
0.15
0.2
0.2
0.5
0.5 1634
Cooling
Ext Static
CFM
408
Pressure
482 0.5 654 772 0.5 772 818
965 0.5 1200 1157 1540 1020
1069 1206
0.5 1447 1225
1454 1736
0.5 1447
1688 1688 2290
0.5
0.5 2460
A72591
Vent
Dia
4 4 4 4 4
5 5
5
6
6
7
7
CFM
780
790
1190
1210 1560 2000
1500
2080 2310 2010
—2-
Loading...
+ 4 hidden pages