Bryant 376CAV Installation Instruction

Installation, Start-Up, and
376CAV
Operating Instructions
DOWNFLOW/HORIZONTAL GAS-FIRED INDUCED-COMBUSTION FURNACES
NOTE: Read the entire instruction manual before starting the installation.
This symbol indicates a change since the last issue.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS.....................................................1
INTRODUCTION..........................................................................1
CODES AND STANDARDS........................................................3
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS........3
General......................................................................................4
Location Relative to Cooling Equipment ................................4
Hazardous Locations.................................................................4
Unconfined Space.....................................................................4
Confined Space.........................................................................5
AIR DUCTS...................................................................................5
General Requirements...............................................................5
Ductwork Acoustical Treatment...............................................5
Supply Air Connections............................................................5
Return Air Connections............................................................6
Downflow Installation ..............................................................6
Horizontal Attic Installation.....................................................6
Horizontal Crawlspace Installation ..........................................7
Filter Arrangement....................................................................8
Gas Piping.................................................................................9
Electrical Connections............................................................11
Venting....................................................................................11
START-UP PROCEDURES, ADJUSTEMENT, AND SAFETY
CHECK.........................................................................................11
General....................................................................................11
Sequence of Operation............................................................12
Start-Up Procedures................................................................15
Adjustments.............................................................................15
Check Safety Controls............................................................19
Checklist..................................................................................20
SAFETY CONSIDERATIONS
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified person­nel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in literature, on tags, and on labels attached to or shipped with unit and other safety precautions that may apply.
In the United States, follow all safety codes including the National Fuel Gas Code (NFGC) NFPA 54-1999/ANSI Z223.1-1999 and the Installation Standards, Warm Air Heating and Air Condition­ing Systems (NFPA 90B) ANSI/NFPA 90B.
In Canada, refer to the current edition of the CAN/CGA-B149.1­and .2-M99 National Standard of Canada, Natural Gas and Propane Installation Codes (NSCNGPIC).
Series H&J
Cancels: II 376C-50–3 II 376C–50–5
10–00
EFFICIENCY RATING CERTIFIED
r
o
p
C
o
r
r
e
i
r
r
a
C
R
E
G
I
S
I
S
O
9
REGISTERED QUALITY SYSTEM
Wear safety glasses and work gloves. Have a fire extinguisher available during start-up and adjustment procedures and service calls. Recognize safety information. This is the safety-alert symbol When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words; DANGER, WARNING, and CAUTION and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept pace with changing residential construction practices. We require these instructions as a minimum for a safe installation.
INTRODUCTION
The Model 376CAV, Series H and J Furnace is available in sizes 46,000 through 135,000 Btuh input capacities. The design of the downflow/horizontal gas-fired furnace is (A.G.A. & C.S.A.) certified for natural and propane gases and for installation on noncombustible flooring. The furnace is factory­shipped for use with natural gas. A factory accessory gas conver­sion kit, as listed on the furnace rating plate is required to convert furnace for use with propane gas. These furnaces SHALL NOT be installed directly on carpeting, tile, or any combustible material other than wood flooring. In downflow installations, a factory accessory floor base, as listed on the furnace rating plate, MUST be used when installed on combustible materials and wood flooring. A factory base is not required when this furnace is installed on manufacturer’s Coil Assembly Part No. CD5 or CK5, or when Coil Box Part No. KCAKC is used. This furnace is for installation in alcoves, attics, crawlspaces, basements, closets, or utility rooms. The design of this furnace line is not (A.G.A./C.S.A.) certified for installation in mobile homes, recreation vehicles, or outdoors.
a
t
i
o
n
CERTIFIED
®
T
E
0
0
M
R
I
F
D
R
E
3
8
8
2
A
1
#
.
—1—
1
28
⁄2†
20
13
⁄16†
39
7
⁄8†
INLET
7
⁄8† DIA
ACCESSORY
3
⁄4† DIA HOLE
1
GAS ENTRY
11
⁄16†
OUTLET
19
NOTE:
ADDITIONAL LOCA TED IN THE TOP PLA TE
7
⁄8† DIA K.O.’s ARE
AND BOTTOM PLATE
VENT CONNECTION
13
⁄16†
1
9
⁄8†
1
10
⁄4†
1
1
⁄16†
1
2
⁄8†
1
8
⁄4†
11
⁄16†
AIRFLOW
D
E
A
16
11
1
13
⁄16†
4
2
⁄16†
3
5
⁄16†
15
⁄16†
10
⁄16†
1
⁄4†
DIMPLES TO DRILL HOLES FOR HANGER BOLTS (4 PLACES) IN HORIZONTAL POSITION
1
⁄2† DIA
2
THERMOSTAT WIRE ENTRY
7
⁄8† DIA
ACCESSORY
7
⁄8† DIA HOLE
POWER ENTRY
1
1
⁄2† DIA
R.H. GAS ENTRY
7
⁄8† DIA
ACCESSORY
1
1
⁄16†
1
2
⁄8†
TYP
1
5
⁄8† TYP
NOTE:
Minimum return-air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer's recommendations for equivalent diameters. a. For 800 CFM–16-in. round or 14 b. For 1200 CFM–20-in. round or 14 c. For 1600 CFM–22-in. round or 14 d. For airflow requirements above 1800 CFM, must use entire return air opening.
1
2 x 12-in. rectangle.
1
2 x 191⁄2-in. rectangle.
1
2 x 231⁄4-in. rectangle.
TABLE 1—DIMENSIONS (IN.)
UNIT SIZE A D E VENT CONN SHIP. WT (LB)
024050 14-3/16 12-9/16 12-11/16 4 123 036050 14-3/16 12-9/16 12-11/16 4 128 024070 14-3/16 12-9/16 12-11/16 4 130 036070 14-3/16 12-9/16 12-11/16 4 139 036096 17-1/2 15-7/8 16 4 151 048096 17-1/2 15-7/8 16 4 153 048115 17-1/2 15-7/8 16 4 161 060115 21 19-3/8 19-1/2 4 177 066115 21 19-3/8 19-1/2 4 176 060135 24-1/2 22-7/8 23 5 193
Fig. 1—Dimensional Drawing
These instructions cover minimum requirements for a safe instal­lation and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept pace with changing residential construction practices. We require these instructions as a minimum for a safe installation.
A99288
CAUTION: Application of this furnace should be in­doors with special attention given to vent sizing and material, gas input rate, air temperature rise, and unit sizing. Improper installation or misapplication of the furnace can require excessive servicing or cause prema­ture component failure.
NOTE: These furnaces are designed for a minimum continuous return-air temperature of 60°F or intermittent operation down to 55°F such as when used with a night setback thermostat. Return-air temperature must not exceed a maximum of 85°F. Failure to follow these return-air temperature limits may affect reliability of heat exchangers, motors, and controls.
A93042
2
MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION
This fo rced air furnace is equipped for use with natural
gas at altitudes 0-10,000 ft (0-3,050m).
An accessory kit, supplied by the manufacturer,shall be used to convert to propane gas use or may be require d for somenatura l gas applications.
This furnace is for indoor installatio n in a building constructed on site.
This furnace may be installed on combustible flooring in alcove or closet at minimum clearance from combustible material.
This furnace may be used with a Type B-1 Vent and may be vented in com m on with other gas-fired appliances.
For installation on non-combustible floors only.
For installation on combustible flooring onlywhen installedon specia l base, Part No. KGA SB02 01ALL, Coil Assembly, Part No.CD5 or CK5, or Coil Casing, Part No. KCAKC.
For furnaces wider than 14.25 inches (362mm) may
#
be 0 inches.
18 inches fro nt clearance re quired for alcove.
Ø
Indicates supply or return sides whenfurnaceisin
*
the horizonta l position. Line contact only permissible betweenlines formed by intersectionsof the Top and two Sides of thefurnace jacke t, and building joists, studs or fram ing.
For single wall vent typ e 6 inches.
##
ForTypeB-1venttype3inches.
Clearance to Back 0 inches in downflow and horizontal (attic/alcove & craw lspace) positionsand 3 inches in horizontal closet positions.
Fig. 2Clearances to Combustibles
ThisfurnaceisapprovedforDOWNFLOWandHORIZONTAL installatio ns .
Clearance arrow s do not change with furnace orientatio n.
0"
B
A
C
K
E
D
I
S
1" #
*
Clearance in inch es
1"
TOP / PLENUM
E
C
A
N
R
U
F
1
T
N
O
R
F
F
R
BOTTOM
#
"
S
O
N
T
##
Ø
1"
#
E
*
D
I
S
E
R
V
I
C
E
30"
MIN
Vent Clearance to combustibles:
For Sin gle Wall vents 6 inches. For Type B-1 vent type1 inch .
322286-101REV. F (LIT)
A99262
WARNING: Improper installation, adjustment, alter­ation, service, maintenance, or use can cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified installer or agency must use only factory-authorized and listed kits or accessories when modifying this product. Failure to follow this warning could result in electrical shock, fire, personal injury, or death.
For accessory installation details, refer to the applicable installa­tion literature.
NOTE: Remove all shipping brackets and materials before oper­ating the furnace.
CODES AND STANDARDS
Before installing the furnace in the United States, refer to the current edition of the NFGC and the NFPA 90B. For further information the NFGC and NFPA 90B are available from National Fire Protection Association Inc., Batterymarch Park, Quincy, MA 02269; or for only the NFGC contact the American Gas Associa­tion, 400 N. Capitol St., N.W., Washington DC 20001.
Before installing the furnace in Canada, refer to the current edition of the NSCNGPIC. For a copy of the NSCNGPIC, contact Standard Sales, CSA International, 178 Rexdale Boulevard, Eto­bicoke (Toronto), Ontario, M9W 1R3, Canada.
Installation must comply with regulations of serving gas supplier and local building, heating, plumbing or other codes in effect in the area in which installation is made. In absence of local building codes, installation must comply with NFGC in the United States and the NSCNGPIC and all authorities having jurisdiction in Canada.
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
CAUTION: Electrostatic discharge can affect electronic
components. Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electro­static potential.
1. Disconnect all power to the furnace. DO NOT TOUCH
THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODYS ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch a clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a persons hand during grounding will be satisfactorily discharged.
3. After touching the chassis you may proceed to service the control or connecting wires as long as you do nothing that
3
recharges your body with static electricity (for example; DO NOT move or shuffle your feet, DO NOT touch un­grounded objects, etc.).
4. If you touch ungrounded objects (and recharge your body with static electricity), firmly touch furnace again before touching control or wires.
5. Use this procedure for installed and uninstalled (un­grounded) furnaces.
6. Before removing a new control from its container, dis­charge your bodys electrostatic charge to ground to protect the control from damage. If the control is to be installed in a furnace, follow items 1 through 5 before bringing the control or yourself into contact with the furnace. Put all used AND new controls into containers before touching ungrounded objects.
7. An ESD service kit (available from commercial sources) may also be used to prevent ESD damage.
LOCATION
I. GENERAL
CAUTION: Do not install furnace in a corrosive or
contaminated atmosphere. Make sure all combustion and circulating air requirements are met, in addition to all local codes and ordinances. Do not use this furnace during construction when adhe­sives, sealers, and/or new carpets are being installed. If the furnace is required during construction, use clean outside air for combustion and ventilation. Compounds of chlorine and fluorine when burned with combustion air form acids which cause corrosion of the heat exchangers and metal vent system. Some of these compounds are found in paneling and dry wall adhesives, paints, thin­ners, masonry cleaning materials, and many other sol­vents commonly used in the construction process. Excessive exposure to contaminated combustion air will result in safety and performance related problems.
III. HAZARDOUS LOCATIONS
18-IN. MINIMUM
TO BURNERS
A93044
WARNING: When furnace is installed in a residential garage, it must be installed so that burners and ignition sources are located a minimum of 18 in. above floor. The furnace must be located or protected to avoid physical damage by vehicles. When furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmosphere, unit must be installed in accor­dance with requirements of National Fire Protection Association, Inc.
Air For Combustion And Ventilation
Provisions for adequate combustion and ventilation air must be provided in accordance with Section 5.3 of the NFGC, Air for Combustion and Ventilation, or applicable provisions of the local building codes.
Canadian installations must be installed in accordance with NSC­NGPIC and all authorities having jurisdiction.
WARNING: DO NOT install the furnace on its back or sides. Safety control operation will be adversely affected. A failure to follow this warning can cause a fire, personal injury, or death.
This furnace must be installed so the electrical components are protected from water.
Locate furnace as close to the chimney/vent and as near the center of the air distribution system as possible. The furnace should be installed as level as possible.
Provide ample space for servicing and cleaning. Always comply with the minimum fire protection clearances shown on the unit rating plate. This furnace shall not be installed directly on carpeting, tile, or any combustible material other than wood flooring. The furnace may be installed on combustible flooring when installed with the accessory downflow subbase, which is available from your distributor or branch when required.
II. LOCATION RELATIVE TO COOLING EQUIPMENT
The cooling coil must be installed parallel with or on the downstream side of the unit to avoid condensation in the heat exchangers. When installed parallel with a furnace, dampers or other means used to control the flow of air must prevent chilled air from entering the unit. If the dampers are manually operated, they must be equipped with means to prevent operation of either unit unless the damper is in the full-heat or full-cool position.
CAUTION: Air for combustion must not be contami­nated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products.
CAUTION: The operation of exhaust fans, kitchen ven­tilation fans, clothes dryers, or fireplaces could create a NEGATIVE PRESSURE CONDITION at the furnace. Make-up air MUST be provided for the ventilation devices, in addition to that required by the furnace.
All fuel-burning equipment must be supplied with air for combus­tion of the fuel. Sufficient air MUST be provided to ensure there will not be a negative pressure in the equipment room or space. In addition, a positive seal MUST be made between the furnace cabinet and the return-air duct to avoid pulling air from the burner area and blocked vent safeguard opening.
The requirements for combustion and ventilation air depend upon whether the furnace is located in an unconfined or confined space.
IV. UNCONFINED SPACE
An unconfined space has volume of at least 50 cu ft for each 1000 Btuh of total input for all appliances (such as furnaces, clothes dryers, water heaters, etc.) in the space.
4
For Example:
376CAV FURNACE
INPUT BTUH
46,000 307 69,000 460
92,000 613 115,000 767 135,000 920
MINIMUM SQ FT WITH
7–1/2 FT CEILING
If the unconfined space is of unusually tight construction, air for combustion and ventilation MUST come from either the outdoors or spaces freely communicating with the outdoors. Combustion and ventilation openings must be sized the same as for a confined space as defined below. Return air must not be taken from the room unless an equal or greater amount of air is supplied to the room.
V. CONFINED SPACE
A confined space is defined as a space whose volume is less than 50 cu ft per 1000 Btuh of total input ratings of all appliances installed in that space. A confined space MUST have provisions for supplying air for combustion, ventilation, and dilution of flue gases using 1 of the following methods. (See Figs. 3, 4, and Table
2.) NOTE: In determining free area of an opening, the blocking
effect of louvers, grilles, and screens must be considered. If free area of louver or grille design is unknown, assume that wood louvers have a 20 percent free area and metal louvers or grilles have a 60 percent free area. Screens, when used, must not be smaller than 1/4-in. mesh. Louvers and grilles must be constructed so they cannot be closed.
The size of the openings depends upon whether air comes from outside of the structure or an unconfined space inside the structure.
1. All air from inside the structure requires 2 openings (for structures not usually tight):
a. Each opening MUST have at least 1 sq in. of free area
per 1000 Btuh of total input for all equipment within the confined space, but not less than 100 sq in. per opening. (See Fig. 3 and Table 2.) The minimum dimension of air openings shall not be less than 3 in.
b. If building is constructed unusually tight, a permanent
opening directly communicating with the outdoors shall be provided. See item 2 below.
c. If furnace is installed on a raised platform to provide a
return-air plenum, and return air is taken directly from hallway or space adjacent to furnace, all air for combus­tion must come from outdoors.
2. Air from outside the structure requires 1 of the following methods:
a. If combustion air is taken from outdoors through 2
vertical ducts, the openings and ducts MUST have at least 1 sq in. of free area per 4000 Btuh of total input for all equipment within the confined space. (See Figs. 3, 4, and Table 2.)
b. If combustion air is taken from outdoors through 2
horizontal ducts, the openings and ducts MUST have at least 1 sq in. of free area per 2000 Btuh of total input for all equipment within the confined space. (See Fig. 4 and Table 2.)
c. If combustion air is taken from outdoors through a single
opening or duct (horizontal or vertical) commencing within 12 in. of the top of the confined space, opening and duct MUST have at least 1 sq in. of free area per
3000 Btuh of the total input for all equipment within the confined space and not less than the sum of the areas of all vent connectors in the confined space. (See Fig. 4 and Table 2.) Equipment clearances to the structure shall be at least 1 in. from the sides and back and 6 in. from the front of the appliances.
When ducts are used, they must be of the same cross-sectional area as the free area of the openings to which they connect. The minimum dimension of ducts must not be less than 3 in. (See Fig.
4.)
AIR DUCTS
This section covers installation of the 376CAV Series H and J furnace.
I. GENERAL REQUIREMENTS
The duct system should be designed and sized according to accepted national standards such as those published by: Air Conditioning Contractors Association (ACCA), Sheet Metal and Air Conditioning Contractors National Association (SMACNA) or American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE). Or consult factory The Air Systems Design Guidelinesreference tables available from your local distributor. The duct system should be sized to handle the required system design airflow CFM at the design external static pressure.
When a furnace is installed so that the supply ducts carry air to areas outside the space containing the furnace, the return air must also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
Secure ductwork with proper fasteners for type of ductwork used. Seal supply- and return-duct connections to furnace with code approved tape or duct sealer.
Flexible connections should be used between ductwork and furnace to prevent transmission of vibration. Ductwork passing through unconditioned space should be insulated to enhance system performance. When air conditioning is used, a vapor barrier is recommended.
Maintain a 1-in. clearance from combustible materials to supply air ductwork for a distance of 36 in. horizontally from the furnace. See NFPA 90B or local code for further requirements.
II. DUCTWORK ACOUSTICAL TREATMENT
Metal duct systems that do not have a 90 degree elbow and 10 ft of main duct to the first branch take-off may require internal acoustical lining. As an alternative, fibrous ductwork may be used if constructed and installed in accordance with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous ductwork shall comply with NFPA 90B as tested by UL Standard 181 for Class 1 Rigid air ducts.
III. SUPPLY AIR CONNECTIONS A. Downflow Furnaces
Connect supply-air duct to supply-air opening on furnace. The supply-air ducts attachment must ONLY be connected to furnace supply/outlet or air conditioning coil casing (when used), when installed on non-combustible material. When installed on combus­tible material, supply-air duct attachment must ONLY be con­nected to an accessory subbase or factory approved air condition­ing coil casing. DO NOT cut main furnace casing to attach supply side air duct, humidifier, or other accessories. All accessories MUST be connected external to the furnace main casing.
B. Horizontal Furnaces
Connect supply-air duct to supply-air opening on furnace. The supply-air ducts attachment must ONLY be connected to furnace supply/outlet or air conditioning coil casing (when used). DO NOT cut main furnace casing to attach supply side air duct, humidifier, or other accessories. All accessories MUST be connected external to the furnace main casing.
5
VENT THROUGH ROOF (CATEGORY I)
DUCTS TO
OUTDOORS
1 SQ IN. PER 4000 BTUH
*
RETURN
AIR
INTERIOR
HEATED
SPACE
SUPPLY AIR
* Minimum opening size is 100 sq in. with minimum dimensions of 3 in.
Minimum of 3 in. when type B-1 vent is used.
Fig. 3Confined Space: Air for Combustion and Ventilation
12″ MAX
1 SQ IN. PER 1000 BTUH* IN DOOR OR WALL
UNCONFINED SPACE
6 MIN (FRONT)
1 SQ IN. PER 1000 BTUH* IN DOOR OR WALL
12″ MAX
A93387
from an Unconfined Indoor Space
12 MAX
1 SQ IN. PER 2000 BTUH
*
DUCTS
TO
OUTSIDE
1 SQ IN. PER 2000 BTUH
*
12 MAX
SUPPLY AIR
Minimum dimensions of 3 in.
*
NOTE:
Use any of the following combinations of openings: A & B C & D D & E F & G
RETURN
A
B
AIR
Fig. 4Confined Space: Air for Combustion and Ventilation
D
VENT THROUGH ROOF (CATEGORY I)
CONFINED
C
DUCT
TO
OUTDOORS
F
SPACE
G
E
12 MAX
12
MAX
1 SQ IN. PER 4000 BTUH
OUTDOORS 1 SQ IN.
PER 4000 BTUH
12
MAX
1 SQ IN. PER 4000 BTUH
*
*
A93388
from Outdoors
TABLE 2MINIMUM FREE AREA OF COMBUSTION AIR OPENING*
376CAV
FURNACE
INPUT
(BTUH)
46,000 100 11.50 4 23.0 6 15.33 5 69,000 100 17.25 5 34.5 7 23.00 6
92,000 100 23.00 6 46.0 8 30.67 7 115,000 115 28.75 7 57.5 9 38.33 7 135,000 135 33.75 7 67.5 10 45.00 8
* Free area shall be equal to or greater than the sum of the areas of all vent connectors in the confined space. Opening area must be increased if other gas appliances in the space require combustion air.
AIR FROM INDOOR
UNCONFINED SPACE
Free Area
of Opening
(Sq. In.)
IV. RETURN AIR CONNECTIONS
The return-air duct must be connected to return air opening as shown in Fig. 1. DO NOT cut into casing sides or back to attach any portion of return-air duct. Bypass humidifier connections should be made at ductwork or coil casing sides exterior to furnace.
WARNING: Do not install furnace on its back. Safety control operation will be adversely affected. Never con­nect return-air ducts to back of furnace. Failure to follow this warning could result in fire, personal injury, or death.
OUTDOOR AIR THROUGH
VERTICAL DUCTS
Free Area of
Opening and Duct
(Sq. In.)
Round
Pipe
(In. Dia.)
OUTDOOR AIR THROUGH
HORIZONTAL DUCTS
Free Area
of Opening and Duct
(Sq. In.)
Round
Pipe
(In. Dia)
OUTDOOR AIR THROUGH
SINGLE DUCT
Free Area
of Opening and Duct
(Sq. In.)
Round
(In. Dia)
rating plate, MUST be used. A factory accessory floor base is not required when this furnace is installed on manufacturers Coil Assembly Part No. CD5 or CK5, or when Coil Box Part No. KCAKC is used.
1. Determine application being installed from Table 3.
2. Construct hold in floor per dimensions specified in Table 3 and Fig. 5.
3. Construct plenum to dimensions specified in Table 3.
4. If downflow subbase (KGASB) is used, install as shown in Fig. 6.
Pipe
If coil assembly CD5, CK5 or Coil Box KCAKC is used, install as shown in Fig. 7.
V. DOWNFLOW INSTALLATION
This furnace is approved for use on combustible materials or wood flooring. A factory accessory floor base, as listed on the furnace
VI. HORIZONTAL ATTIC INSTALLATION
The furnace can be installed on either the left-hand (LH) or right-hand (RH) side. A typical attic installation is shown in Fig. 8.
6
FRONT
BACK
FRONT
A. Construct a Working Platform
Constructs a working platform, on location, where all required furnace clearances are met. (See Fig. 2 and 8.)
B. Install Furnace
1. Position furnace in desired location.
B A C K
2. Connect gas supply pipe. See Fig. 8 for typical piping entry.
3. Install field-supplied filter retainers as indicated in Fig. 11 and Table 4 before connecting return-air duct to furnace.
4. Connect supply- and return-air ducts.
5. Install 24- X 24–in. sheet metal shield on platform in front of louvered control panel as shown in Fig. 8.
VII. HORIZONTAL CRAWLSPACE INSTALLATION
A93043
The furnace can be installed horizontally with either LH or RH side up. In a crawlspace, furnace can either be hung from floor joist (see Fig. 10) or installed on suitable blocks or pad. (See Fig.
A
PLENUM
OPENING
B
D
FURNACE
CASING
WIDTH
14–3/16
17–1/2
21
24–1/2
FLOOR
OPENING
C
Fig. 5Floor and Plenum Opening Dimensions
TABLE 3OPENING DIMENSIONS (IN.)
APPLICATION
Non-Combustible Flooring 12–11/16 19 13–3/8 19–5/8
Combustible Flooring Using KGASB Subbase 11–13/16 19 13–7/16 20–3/8
Combustible Flooring with CD5 or CK5 Coil Assembly or
KCAKC Coil Box
Non-Combustible Flooring 16 19 16–5/8 19–5/8
Combustible Flooring Using KGASB Subbase 15–1/8 19 16–3/4 20–3/8
Combustible Flooring with CD5 or CK5 Coil Assembly or
KCAKC Coil Box
Non-Combustible Flooring 19–1/2 19 20–1/8 19–5/8
Combustible Flooring Using KGASB Subbase 18–5/8 19 20–1/4 20–3/8
Combustible Flooring with CD5 or CK5 Coil Assembly or
KCAKC Coil Box
Non-Combustible Flooring 23 19 23–5/8 19–5/8
Combustible Flooring Using KGASB Subbase 22–1/8 19 23–3/4 20–3/8
Combustible Flooring with CD5 or CK5 Coil Assembly or
KCAKC Coil Box
PLENUM OPENING FLOOR OPENING
ABCD
12–5/16 19 13–5/16 20
15–1/2 19 16–1/2 20
19 19 20 20
22–1/2 19 23–1/2 20
A96283
7
FURNACE
(OR COIL CASING
WHEN USED)
COMBUSTIBLE
FLOORING
FURNACE
CD5 OR CK5
COIL ASSEMBLY
OR KCAKC
COIL BOX
COMBUSTIBLE
FLOORING
DOWNFLOW
SUBBASE
SHEET METAL
PLENUM
FLOOR
OPENING
Fig. 6Furnace, Plenum, and Subbase Installed on a Com-
A96285
bustible Floor
9.) The furnace can be suspended from each corner by hanger bolts (4 each 3/8-in. all-thread rod) cut to desired length, 1- X 3/8–in. flat washer, 3/8–in. lockwasher, and 3/8–in. nut. Dimples are provided for hole locations. (See Fig. 1.)
Since horizontal crawlspace installation is very similar to attic installation, refer to Section VI, Horizontal Attic Installation. The installation of a sheet metal shield in front of louvered control panel is covered in Section VI.
For crawlspace installation, this same sheet metal shield must be installed above louvered control panel. Extend sheet metal shield over furnace top far enough to cover gas pipe entry hole.
SHEET METAL
PLENUM
FLOOR
OPENING
Fig. 7Furnace, Plenum, and Coil Assembly or Coil Box
A96284
Installed on a Combustible Floor
VIII. FILTER ARRANGEMENT
WARNING: Never operate unit without filter access
door removed. Failure to follow this warning could result in fire, personal injury, or death.
LINE CONTACT ONLY PERMISSIBLE BETWEEN LINES FORMED BY INTERSECTIONS OF THE TOP AND TWO SIDES OF THE FURNACE JACKET AND BUILDING JOISTS, STUDS, OR FRAMING.
MANUAL SHUTOFF
GAS VALVE
SEDIMENT
TRAP
GAS ENTRY
6
24
24
SHEET METAL
Fig. 8Typical Attic Installation
8
MIN
TYPE-B VENT
30-IN. MIN WORK AREA
A97516
Loading...
+ 16 hidden pages