Bryant 376CAV Installation Instruction

Installation, Start-Up, and
376CAV
Operating Instructions
DOWNFLOW/HORIZONTAL GAS-FIRED INDUCED-COMBUSTION FURNACES
NOTE: Read the entire instruction manual before starting the installation.
This symbol indicates a change since the last issue.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS.....................................................1
INTRODUCTION..........................................................................1
CODES AND STANDARDS........................................................3
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS........3
General......................................................................................4
Location Relative to Cooling Equipment ................................4
Hazardous Locations.................................................................4
Unconfined Space.....................................................................4
Confined Space.........................................................................5
AIR DUCTS...................................................................................5
General Requirements...............................................................5
Ductwork Acoustical Treatment...............................................5
Supply Air Connections............................................................5
Return Air Connections............................................................6
Downflow Installation ..............................................................6
Horizontal Attic Installation.....................................................6
Horizontal Crawlspace Installation ..........................................7
Filter Arrangement....................................................................8
Gas Piping.................................................................................9
Electrical Connections............................................................11
Venting....................................................................................11
START-UP PROCEDURES, ADJUSTEMENT, AND SAFETY
CHECK.........................................................................................11
General....................................................................................11
Sequence of Operation............................................................12
Start-Up Procedures................................................................15
Adjustments.............................................................................15
Check Safety Controls............................................................19
Checklist..................................................................................20
SAFETY CONSIDERATIONS
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified person­nel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in literature, on tags, and on labels attached to or shipped with unit and other safety precautions that may apply.
In the United States, follow all safety codes including the National Fuel Gas Code (NFGC) NFPA 54-1999/ANSI Z223.1-1999 and the Installation Standards, Warm Air Heating and Air Condition­ing Systems (NFPA 90B) ANSI/NFPA 90B.
In Canada, refer to the current edition of the CAN/CGA-B149.1­and .2-M99 National Standard of Canada, Natural Gas and Propane Installation Codes (NSCNGPIC).
Series H&J
Cancels: II 376C-50–3 II 376C–50–5
10–00
EFFICIENCY RATING CERTIFIED
r
o
p
C
o
r
r
e
i
r
r
a
C
R
E
G
I
S
I
S
O
9
REGISTERED QUALITY SYSTEM
Wear safety glasses and work gloves. Have a fire extinguisher available during start-up and adjustment procedures and service calls. Recognize safety information. This is the safety-alert symbol When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words; DANGER, WARNING, and CAUTION and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept pace with changing residential construction practices. We require these instructions as a minimum for a safe installation.
INTRODUCTION
The Model 376CAV, Series H and J Furnace is available in sizes 46,000 through 135,000 Btuh input capacities. The design of the downflow/horizontal gas-fired furnace is (A.G.A. & C.S.A.) certified for natural and propane gases and for installation on noncombustible flooring. The furnace is factory­shipped for use with natural gas. A factory accessory gas conver­sion kit, as listed on the furnace rating plate is required to convert furnace for use with propane gas. These furnaces SHALL NOT be installed directly on carpeting, tile, or any combustible material other than wood flooring. In downflow installations, a factory accessory floor base, as listed on the furnace rating plate, MUST be used when installed on combustible materials and wood flooring. A factory base is not required when this furnace is installed on manufacturer’s Coil Assembly Part No. CD5 or CK5, or when Coil Box Part No. KCAKC is used. This furnace is for installation in alcoves, attics, crawlspaces, basements, closets, or utility rooms. The design of this furnace line is not (A.G.A./C.S.A.) certified for installation in mobile homes, recreation vehicles, or outdoors.
a
t
i
o
n
CERTIFIED
®
T
E
0
0
M
R
I
F
D
R
E
3
8
8
2
A
1
#
.
—1—
1
28
⁄2†
20
13
⁄16†
39
7
⁄8†
INLET
7
⁄8† DIA
ACCESSORY
3
⁄4† DIA HOLE
1
GAS ENTRY
11
⁄16†
OUTLET
19
NOTE:
ADDITIONAL LOCA TED IN THE TOP PLA TE
7
⁄8† DIA K.O.’s ARE
AND BOTTOM PLATE
VENT CONNECTION
13
⁄16†
1
9
⁄8†
1
10
⁄4†
1
1
⁄16†
1
2
⁄8†
1
8
⁄4†
11
⁄16†
AIRFLOW
D
E
A
16
11
1
13
⁄16†
4
2
⁄16†
3
5
⁄16†
15
⁄16†
10
⁄16†
1
⁄4†
DIMPLES TO DRILL HOLES FOR HANGER BOLTS (4 PLACES) IN HORIZONTAL POSITION
1
⁄2† DIA
2
THERMOSTAT WIRE ENTRY
7
⁄8† DIA
ACCESSORY
7
⁄8† DIA HOLE
POWER ENTRY
1
1
⁄2† DIA
R.H. GAS ENTRY
7
⁄8† DIA
ACCESSORY
1
1
⁄16†
1
2
⁄8†
TYP
1
5
⁄8† TYP
NOTE:
Minimum return-air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer's recommendations for equivalent diameters. a. For 800 CFM–16-in. round or 14 b. For 1200 CFM–20-in. round or 14 c. For 1600 CFM–22-in. round or 14 d. For airflow requirements above 1800 CFM, must use entire return air opening.
1
2 x 12-in. rectangle.
1
2 x 191⁄2-in. rectangle.
1
2 x 231⁄4-in. rectangle.
TABLE 1—DIMENSIONS (IN.)
UNIT SIZE A D E VENT CONN SHIP. WT (LB)
024050 14-3/16 12-9/16 12-11/16 4 123 036050 14-3/16 12-9/16 12-11/16 4 128 024070 14-3/16 12-9/16 12-11/16 4 130 036070 14-3/16 12-9/16 12-11/16 4 139 036096 17-1/2 15-7/8 16 4 151 048096 17-1/2 15-7/8 16 4 153 048115 17-1/2 15-7/8 16 4 161 060115 21 19-3/8 19-1/2 4 177 066115 21 19-3/8 19-1/2 4 176 060135 24-1/2 22-7/8 23 5 193
Fig. 1—Dimensional Drawing
These instructions cover minimum requirements for a safe instal­lation and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept pace with changing residential construction practices. We require these instructions as a minimum for a safe installation.
A99288
CAUTION: Application of this furnace should be in­doors with special attention given to vent sizing and material, gas input rate, air temperature rise, and unit sizing. Improper installation or misapplication of the furnace can require excessive servicing or cause prema­ture component failure.
NOTE: These furnaces are designed for a minimum continuous return-air temperature of 60°F or intermittent operation down to 55°F such as when used with a night setback thermostat. Return-air temperature must not exceed a maximum of 85°F. Failure to follow these return-air temperature limits may affect reliability of heat exchangers, motors, and controls.
A93042
2
MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION
This fo rced air furnace is equipped for use with natural
gas at altitudes 0-10,000 ft (0-3,050m).
An accessory kit, supplied by the manufacturer,shall be used to convert to propane gas use or may be require d for somenatura l gas applications.
This furnace is for indoor installatio n in a building constructed on site.
This furnace may be installed on combustible flooring in alcove or closet at minimum clearance from combustible material.
This furnace may be used with a Type B-1 Vent and may be vented in com m on with other gas-fired appliances.
For installation on non-combustible floors only.
For installation on combustible flooring onlywhen installedon specia l base, Part No. KGA SB02 01ALL, Coil Assembly, Part No.CD5 or CK5, or Coil Casing, Part No. KCAKC.
For furnaces wider than 14.25 inches (362mm) may
#
be 0 inches.
18 inches fro nt clearance re quired for alcove.
Ø
Indicates supply or return sides whenfurnaceisin
*
the horizonta l position. Line contact only permissible betweenlines formed by intersectionsof the Top and two Sides of thefurnace jacke t, and building joists, studs or fram ing.
For single wall vent typ e 6 inches.
##
ForTypeB-1venttype3inches.
Clearance to Back 0 inches in downflow and horizontal (attic/alcove & craw lspace) positionsand 3 inches in horizontal closet positions.
Fig. 2Clearances to Combustibles
ThisfurnaceisapprovedforDOWNFLOWandHORIZONTAL installatio ns .
Clearance arrow s do not change with furnace orientatio n.
0"
B
A
C
K
E
D
I
S
1" #
*
Clearance in inch es
1"
TOP / PLENUM
E
C
A
N
R
U
F
1
T
N
O
R
F
F
R
BOTTOM
#
"
S
O
N
T
##
Ø
1"
#
E
*
D
I
S
E
R
V
I
C
E
30"
MIN
Vent Clearance to combustibles:
For Sin gle Wall vents 6 inches. For Type B-1 vent type1 inch .
322286-101REV. F (LIT)
A99262
WARNING: Improper installation, adjustment, alter­ation, service, maintenance, or use can cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified installer or agency must use only factory-authorized and listed kits or accessories when modifying this product. Failure to follow this warning could result in electrical shock, fire, personal injury, or death.
For accessory installation details, refer to the applicable installa­tion literature.
NOTE: Remove all shipping brackets and materials before oper­ating the furnace.
CODES AND STANDARDS
Before installing the furnace in the United States, refer to the current edition of the NFGC and the NFPA 90B. For further information the NFGC and NFPA 90B are available from National Fire Protection Association Inc., Batterymarch Park, Quincy, MA 02269; or for only the NFGC contact the American Gas Associa­tion, 400 N. Capitol St., N.W., Washington DC 20001.
Before installing the furnace in Canada, refer to the current edition of the NSCNGPIC. For a copy of the NSCNGPIC, contact Standard Sales, CSA International, 178 Rexdale Boulevard, Eto­bicoke (Toronto), Ontario, M9W 1R3, Canada.
Installation must comply with regulations of serving gas supplier and local building, heating, plumbing or other codes in effect in the area in which installation is made. In absence of local building codes, installation must comply with NFGC in the United States and the NSCNGPIC and all authorities having jurisdiction in Canada.
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
CAUTION: Electrostatic discharge can affect electronic
components. Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electro­static potential.
1. Disconnect all power to the furnace. DO NOT TOUCH
THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODYS ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch a clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a persons hand during grounding will be satisfactorily discharged.
3. After touching the chassis you may proceed to service the control or connecting wires as long as you do nothing that
3
recharges your body with static electricity (for example; DO NOT move or shuffle your feet, DO NOT touch un­grounded objects, etc.).
4. If you touch ungrounded objects (and recharge your body with static electricity), firmly touch furnace again before touching control or wires.
5. Use this procedure for installed and uninstalled (un­grounded) furnaces.
6. Before removing a new control from its container, dis­charge your bodys electrostatic charge to ground to protect the control from damage. If the control is to be installed in a furnace, follow items 1 through 5 before bringing the control or yourself into contact with the furnace. Put all used AND new controls into containers before touching ungrounded objects.
7. An ESD service kit (available from commercial sources) may also be used to prevent ESD damage.
LOCATION
I. GENERAL
CAUTION: Do not install furnace in a corrosive or
contaminated atmosphere. Make sure all combustion and circulating air requirements are met, in addition to all local codes and ordinances. Do not use this furnace during construction when adhe­sives, sealers, and/or new carpets are being installed. If the furnace is required during construction, use clean outside air for combustion and ventilation. Compounds of chlorine and fluorine when burned with combustion air form acids which cause corrosion of the heat exchangers and metal vent system. Some of these compounds are found in paneling and dry wall adhesives, paints, thin­ners, masonry cleaning materials, and many other sol­vents commonly used in the construction process. Excessive exposure to contaminated combustion air will result in safety and performance related problems.
III. HAZARDOUS LOCATIONS
18-IN. MINIMUM
TO BURNERS
A93044
WARNING: When furnace is installed in a residential garage, it must be installed so that burners and ignition sources are located a minimum of 18 in. above floor. The furnace must be located or protected to avoid physical damage by vehicles. When furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmosphere, unit must be installed in accor­dance with requirements of National Fire Protection Association, Inc.
Air For Combustion And Ventilation
Provisions for adequate combustion and ventilation air must be provided in accordance with Section 5.3 of the NFGC, Air for Combustion and Ventilation, or applicable provisions of the local building codes.
Canadian installations must be installed in accordance with NSC­NGPIC and all authorities having jurisdiction.
WARNING: DO NOT install the furnace on its back or sides. Safety control operation will be adversely affected. A failure to follow this warning can cause a fire, personal injury, or death.
This furnace must be installed so the electrical components are protected from water.
Locate furnace as close to the chimney/vent and as near the center of the air distribution system as possible. The furnace should be installed as level as possible.
Provide ample space for servicing and cleaning. Always comply with the minimum fire protection clearances shown on the unit rating plate. This furnace shall not be installed directly on carpeting, tile, or any combustible material other than wood flooring. The furnace may be installed on combustible flooring when installed with the accessory downflow subbase, which is available from your distributor or branch when required.
II. LOCATION RELATIVE TO COOLING EQUIPMENT
The cooling coil must be installed parallel with or on the downstream side of the unit to avoid condensation in the heat exchangers. When installed parallel with a furnace, dampers or other means used to control the flow of air must prevent chilled air from entering the unit. If the dampers are manually operated, they must be equipped with means to prevent operation of either unit unless the damper is in the full-heat or full-cool position.
CAUTION: Air for combustion must not be contami­nated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products.
CAUTION: The operation of exhaust fans, kitchen ven­tilation fans, clothes dryers, or fireplaces could create a NEGATIVE PRESSURE CONDITION at the furnace. Make-up air MUST be provided for the ventilation devices, in addition to that required by the furnace.
All fuel-burning equipment must be supplied with air for combus­tion of the fuel. Sufficient air MUST be provided to ensure there will not be a negative pressure in the equipment room or space. In addition, a positive seal MUST be made between the furnace cabinet and the return-air duct to avoid pulling air from the burner area and blocked vent safeguard opening.
The requirements for combustion and ventilation air depend upon whether the furnace is located in an unconfined or confined space.
IV. UNCONFINED SPACE
An unconfined space has volume of at least 50 cu ft for each 1000 Btuh of total input for all appliances (such as furnaces, clothes dryers, water heaters, etc.) in the space.
4
For Example:
376CAV FURNACE
INPUT BTUH
46,000 307 69,000 460
92,000 613 115,000 767 135,000 920
MINIMUM SQ FT WITH
7–1/2 FT CEILING
If the unconfined space is of unusually tight construction, air for combustion and ventilation MUST come from either the outdoors or spaces freely communicating with the outdoors. Combustion and ventilation openings must be sized the same as for a confined space as defined below. Return air must not be taken from the room unless an equal or greater amount of air is supplied to the room.
V. CONFINED SPACE
A confined space is defined as a space whose volume is less than 50 cu ft per 1000 Btuh of total input ratings of all appliances installed in that space. A confined space MUST have provisions for supplying air for combustion, ventilation, and dilution of flue gases using 1 of the following methods. (See Figs. 3, 4, and Table
2.) NOTE: In determining free area of an opening, the blocking
effect of louvers, grilles, and screens must be considered. If free area of louver or grille design is unknown, assume that wood louvers have a 20 percent free area and metal louvers or grilles have a 60 percent free area. Screens, when used, must not be smaller than 1/4-in. mesh. Louvers and grilles must be constructed so they cannot be closed.
The size of the openings depends upon whether air comes from outside of the structure or an unconfined space inside the structure.
1. All air from inside the structure requires 2 openings (for structures not usually tight):
a. Each opening MUST have at least 1 sq in. of free area
per 1000 Btuh of total input for all equipment within the confined space, but not less than 100 sq in. per opening. (See Fig. 3 and Table 2.) The minimum dimension of air openings shall not be less than 3 in.
b. If building is constructed unusually tight, a permanent
opening directly communicating with the outdoors shall be provided. See item 2 below.
c. If furnace is installed on a raised platform to provide a
return-air plenum, and return air is taken directly from hallway or space adjacent to furnace, all air for combus­tion must come from outdoors.
2. Air from outside the structure requires 1 of the following methods:
a. If combustion air is taken from outdoors through 2
vertical ducts, the openings and ducts MUST have at least 1 sq in. of free area per 4000 Btuh of total input for all equipment within the confined space. (See Figs. 3, 4, and Table 2.)
b. If combustion air is taken from outdoors through 2
horizontal ducts, the openings and ducts MUST have at least 1 sq in. of free area per 2000 Btuh of total input for all equipment within the confined space. (See Fig. 4 and Table 2.)
c. If combustion air is taken from outdoors through a single
opening or duct (horizontal or vertical) commencing within 12 in. of the top of the confined space, opening and duct MUST have at least 1 sq in. of free area per
3000 Btuh of the total input for all equipment within the confined space and not less than the sum of the areas of all vent connectors in the confined space. (See Fig. 4 and Table 2.) Equipment clearances to the structure shall be at least 1 in. from the sides and back and 6 in. from the front of the appliances.
When ducts are used, they must be of the same cross-sectional area as the free area of the openings to which they connect. The minimum dimension of ducts must not be less than 3 in. (See Fig.
4.)
AIR DUCTS
This section covers installation of the 376CAV Series H and J furnace.
I. GENERAL REQUIREMENTS
The duct system should be designed and sized according to accepted national standards such as those published by: Air Conditioning Contractors Association (ACCA), Sheet Metal and Air Conditioning Contractors National Association (SMACNA) or American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE). Or consult factory The Air Systems Design Guidelinesreference tables available from your local distributor. The duct system should be sized to handle the required system design airflow CFM at the design external static pressure.
When a furnace is installed so that the supply ducts carry air to areas outside the space containing the furnace, the return air must also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
Secure ductwork with proper fasteners for type of ductwork used. Seal supply- and return-duct connections to furnace with code approved tape or duct sealer.
Flexible connections should be used between ductwork and furnace to prevent transmission of vibration. Ductwork passing through unconditioned space should be insulated to enhance system performance. When air conditioning is used, a vapor barrier is recommended.
Maintain a 1-in. clearance from combustible materials to supply air ductwork for a distance of 36 in. horizontally from the furnace. See NFPA 90B or local code for further requirements.
II. DUCTWORK ACOUSTICAL TREATMENT
Metal duct systems that do not have a 90 degree elbow and 10 ft of main duct to the first branch take-off may require internal acoustical lining. As an alternative, fibrous ductwork may be used if constructed and installed in accordance with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous ductwork shall comply with NFPA 90B as tested by UL Standard 181 for Class 1 Rigid air ducts.
III. SUPPLY AIR CONNECTIONS A. Downflow Furnaces
Connect supply-air duct to supply-air opening on furnace. The supply-air ducts attachment must ONLY be connected to furnace supply/outlet or air conditioning coil casing (when used), when installed on non-combustible material. When installed on combus­tible material, supply-air duct attachment must ONLY be con­nected to an accessory subbase or factory approved air condition­ing coil casing. DO NOT cut main furnace casing to attach supply side air duct, humidifier, or other accessories. All accessories MUST be connected external to the furnace main casing.
B. Horizontal Furnaces
Connect supply-air duct to supply-air opening on furnace. The supply-air ducts attachment must ONLY be connected to furnace supply/outlet or air conditioning coil casing (when used). DO NOT cut main furnace casing to attach supply side air duct, humidifier, or other accessories. All accessories MUST be connected external to the furnace main casing.
5
VENT THROUGH ROOF (CATEGORY I)
DUCTS TO
OUTDOORS
1 SQ IN. PER 4000 BTUH
*
RETURN
AIR
INTERIOR
HEATED
SPACE
SUPPLY AIR
* Minimum opening size is 100 sq in. with minimum dimensions of 3 in.
Minimum of 3 in. when type B-1 vent is used.
Fig. 3Confined Space: Air for Combustion and Ventilation
12″ MAX
1 SQ IN. PER 1000 BTUH* IN DOOR OR WALL
UNCONFINED SPACE
6 MIN (FRONT)
1 SQ IN. PER 1000 BTUH* IN DOOR OR WALL
12″ MAX
A93387
from an Unconfined Indoor Space
12 MAX
1 SQ IN. PER 2000 BTUH
*
DUCTS
TO
OUTSIDE
1 SQ IN. PER 2000 BTUH
*
12 MAX
SUPPLY AIR
Minimum dimensions of 3 in.
*
NOTE:
Use any of the following combinations of openings: A & B C & D D & E F & G
RETURN
A
B
AIR
Fig. 4Confined Space: Air for Combustion and Ventilation
D
VENT THROUGH ROOF (CATEGORY I)
CONFINED
C
DUCT
TO
OUTDOORS
F
SPACE
G
E
12 MAX
12
MAX
1 SQ IN. PER 4000 BTUH
OUTDOORS 1 SQ IN.
PER 4000 BTUH
12
MAX
1 SQ IN. PER 4000 BTUH
*
*
A93388
from Outdoors
TABLE 2MINIMUM FREE AREA OF COMBUSTION AIR OPENING*
376CAV
FURNACE
INPUT
(BTUH)
46,000 100 11.50 4 23.0 6 15.33 5 69,000 100 17.25 5 34.5 7 23.00 6
92,000 100 23.00 6 46.0 8 30.67 7 115,000 115 28.75 7 57.5 9 38.33 7 135,000 135 33.75 7 67.5 10 45.00 8
* Free area shall be equal to or greater than the sum of the areas of all vent connectors in the confined space. Opening area must be increased if other gas appliances in the space require combustion air.
AIR FROM INDOOR
UNCONFINED SPACE
Free Area
of Opening
(Sq. In.)
IV. RETURN AIR CONNECTIONS
The return-air duct must be connected to return air opening as shown in Fig. 1. DO NOT cut into casing sides or back to attach any portion of return-air duct. Bypass humidifier connections should be made at ductwork or coil casing sides exterior to furnace.
WARNING: Do not install furnace on its back. Safety control operation will be adversely affected. Never con­nect return-air ducts to back of furnace. Failure to follow this warning could result in fire, personal injury, or death.
OUTDOOR AIR THROUGH
VERTICAL DUCTS
Free Area of
Opening and Duct
(Sq. In.)
Round
Pipe
(In. Dia.)
OUTDOOR AIR THROUGH
HORIZONTAL DUCTS
Free Area
of Opening and Duct
(Sq. In.)
Round
Pipe
(In. Dia)
OUTDOOR AIR THROUGH
SINGLE DUCT
Free Area
of Opening and Duct
(Sq. In.)
Round
(In. Dia)
rating plate, MUST be used. A factory accessory floor base is not required when this furnace is installed on manufacturers Coil Assembly Part No. CD5 or CK5, or when Coil Box Part No. KCAKC is used.
1. Determine application being installed from Table 3.
2. Construct hold in floor per dimensions specified in Table 3 and Fig. 5.
3. Construct plenum to dimensions specified in Table 3.
4. If downflow subbase (KGASB) is used, install as shown in Fig. 6.
Pipe
If coil assembly CD5, CK5 or Coil Box KCAKC is used, install as shown in Fig. 7.
V. DOWNFLOW INSTALLATION
This furnace is approved for use on combustible materials or wood flooring. A factory accessory floor base, as listed on the furnace
VI. HORIZONTAL ATTIC INSTALLATION
The furnace can be installed on either the left-hand (LH) or right-hand (RH) side. A typical attic installation is shown in Fig. 8.
6
FRONT
BACK
FRONT
A. Construct a Working Platform
Constructs a working platform, on location, where all required furnace clearances are met. (See Fig. 2 and 8.)
B. Install Furnace
1. Position furnace in desired location.
B A C K
2. Connect gas supply pipe. See Fig. 8 for typical piping entry.
3. Install field-supplied filter retainers as indicated in Fig. 11 and Table 4 before connecting return-air duct to furnace.
4. Connect supply- and return-air ducts.
5. Install 24- X 24–in. sheet metal shield on platform in front of louvered control panel as shown in Fig. 8.
VII. HORIZONTAL CRAWLSPACE INSTALLATION
A93043
The furnace can be installed horizontally with either LH or RH side up. In a crawlspace, furnace can either be hung from floor joist (see Fig. 10) or installed on suitable blocks or pad. (See Fig.
A
PLENUM
OPENING
B
D
FURNACE
CASING
WIDTH
14–3/16
17–1/2
21
24–1/2
FLOOR
OPENING
C
Fig. 5Floor and Plenum Opening Dimensions
TABLE 3OPENING DIMENSIONS (IN.)
APPLICATION
Non-Combustible Flooring 12–11/16 19 13–3/8 19–5/8
Combustible Flooring Using KGASB Subbase 11–13/16 19 13–7/16 20–3/8
Combustible Flooring with CD5 or CK5 Coil Assembly or
KCAKC Coil Box
Non-Combustible Flooring 16 19 16–5/8 19–5/8
Combustible Flooring Using KGASB Subbase 15–1/8 19 16–3/4 20–3/8
Combustible Flooring with CD5 or CK5 Coil Assembly or
KCAKC Coil Box
Non-Combustible Flooring 19–1/2 19 20–1/8 19–5/8
Combustible Flooring Using KGASB Subbase 18–5/8 19 20–1/4 20–3/8
Combustible Flooring with CD5 or CK5 Coil Assembly or
KCAKC Coil Box
Non-Combustible Flooring 23 19 23–5/8 19–5/8
Combustible Flooring Using KGASB Subbase 22–1/8 19 23–3/4 20–3/8
Combustible Flooring with CD5 or CK5 Coil Assembly or
KCAKC Coil Box
PLENUM OPENING FLOOR OPENING
ABCD
12–5/16 19 13–5/16 20
15–1/2 19 16–1/2 20
19 19 20 20
22–1/2 19 23–1/2 20
A96283
7
FURNACE
(OR COIL CASING
WHEN USED)
COMBUSTIBLE
FLOORING
FURNACE
CD5 OR CK5
COIL ASSEMBLY
OR KCAKC
COIL BOX
COMBUSTIBLE
FLOORING
DOWNFLOW
SUBBASE
SHEET METAL
PLENUM
FLOOR
OPENING
Fig. 6Furnace, Plenum, and Subbase Installed on a Com-
A96285
bustible Floor
9.) The furnace can be suspended from each corner by hanger bolts (4 each 3/8-in. all-thread rod) cut to desired length, 1- X 3/8–in. flat washer, 3/8–in. lockwasher, and 3/8–in. nut. Dimples are provided for hole locations. (See Fig. 1.)
Since horizontal crawlspace installation is very similar to attic installation, refer to Section VI, Horizontal Attic Installation. The installation of a sheet metal shield in front of louvered control panel is covered in Section VI.
For crawlspace installation, this same sheet metal shield must be installed above louvered control panel. Extend sheet metal shield over furnace top far enough to cover gas pipe entry hole.
SHEET METAL
PLENUM
FLOOR
OPENING
Fig. 7Furnace, Plenum, and Coil Assembly or Coil Box
A96284
Installed on a Combustible Floor
VIII. FILTER ARRANGEMENT
WARNING: Never operate unit without filter access
door removed. Failure to follow this warning could result in fire, personal injury, or death.
LINE CONTACT ONLY PERMISSIBLE BETWEEN LINES FORMED BY INTERSECTIONS OF THE TOP AND TWO SIDES OF THE FURNACE JACKET AND BUILDING JOISTS, STUDS, OR FRAMING.
MANUAL SHUTOFF
GAS VALVE
SEDIMENT
TRAP
GAS ENTRY
6
24
24
SHEET METAL
Fig. 8Typical Attic Installation
8
MIN
TYPE-B VENT
30-IN. MIN WORK AREA
A97516
The 2 factory-supplied filters are shipped in the blower compart­ment. After return-air duct has been connected to furnace, install filters in a V-formation inside return-air plenum. See Fig. 11 and Table 4 for horizontal applications. Horizontal filter retainers must be field supplied. See Fig. 12 for downflow applications.
IX. GAS PIPING
Gas piping must be installed in accordance with national and local codes. Refer to the current edition of the NFGC.
Canadian installations must be installed in accordance with NSC­NGPIC and all authorities having jurisdiction.
Refer to Table 5 for recommended gas pipe sizing. Risers should be used to connect to the furnace and the meter.
Fig. 9Horizontal Installation on Blocks
CAUTION: If a flexible connector is required or al-
lowed by the authority having jurisdiction, black iron pipe shall be installed at the gas valve and extend a minimum of 2 in. outside the furnace casing.
WARNING: Use the proper length of pipes to avoid stress on the gas control manifold. Failure to follow this warning can result in a gas leak, causing fire, explosion, personal injury, or death.
A95235
ANGLE IRON OR EQUIVALENT
(B)
(A)
ROD LOCATION USING DIMPLE LOCATORS (SEE DIMENSIONAL DWG FOR LOCATIONS)
(A) PREFERRED ROD LOCATION (B) ALTERNATE ROD LOCATION
Fig. 10Horizontal Crawlspace Installation on Hanger Rods
3
/8-IN. HEX NUT
& WASHER (4)
REQD PER ROD
(B)
(A)
(A)
(B)
NOTES:
3
8-IN. ROD
(A)
(B)
1. A 1 In. clearance minimum between top of furnace and combustible material.
2. The entire length of furnace must be supported when furnace is used in horizontal position.
A96633
9
;
;;;
;
;;
;;
;;;;;;
AIRFLOW
12
TABLE 5MAXIMUM CAPACITY OF PIPE*
NOMINAL IRON
PIPE SIZE
(IN.)
1/2 0.622 175 120 97 82 73 3/4 0.824 360 250 200 170 151
1 1.049 680 465 375 320 285 1–1/4 1.380 1400 950 770 660 580 1–1/2 1.610 2100 1460 1180 990 900
* Cubic ft of gas per hr for gas pressures of 0.5 psig (14-in. wc) or less, and a pressure drop of 0.5-in. wc (based on a 0.60 specific gravity gas). Ref: Table
4
D
10-2 NFPA 54/ANSI Z223.1-1996.
INTERNAL DIAMETER
(IN.)
LENGTH OF PIPE (FT)
10 20 30 40 50
FIELD-SUPPLIED FILTER RETAINERS
Fig. 11Horizontal Filter Arrangement
TABLE 4FILTER INFORMATION (IN.)
FURNACE CASING
WIDTH 14-3/16 (2)16X20X1 15–3/8
17-1/2 (2)16X20X1 14–3/4
21 (2)16X20X1 13–3/4
24-1/2 (2)16X20X1 12–1/2
INSTALLATION
POSITION
OF FILTERS
RETURN-AIR
PLENUM
FILTER SIZE AND QUANTITY D
AIRFLOW
A82173
WARNING: Never purge a line into a combustion chamber. Never use matches, candles, flame, or other sources of ignition for to check for gas leakage. Use a soap-and-water solution to check for gas leaks. Failure to follow this warning could result in fire, explosion, per­sonal injury, or death.
Joint compounds (pipe dope) should be applied sparingly and only to the male threads of the joints. This pipe dope must be resistant to the action of propane gas.
An accessible manual shutoff valve MUST be installed upstream of the furnace gas controls and within 72 in. of the furnace. A 1/8-in. NPT plugged tapping, accessible for test gage connection, MUST be installed immediately upstream of the gas supply connection to the furnace and downstream of the manual shutoff valve. Place a ground joint union between the gas control manifold and the manual shutoff.
Install a sediment trap in the riser leading to the furnace. The trap can be installed by connecting a tee to the riser leading from the furnace. Connect a capped nipple into the lower end of the tee. The capped nipple should extend below the level of the gas controls. (See Fig. 13.)
ACCESS DOOR
Fig. 12Downflow Filter Arrangement
CAUTION: Connect the gas pipe to the furnace using a
backup wrench to avoid damaging gas controls.
A88486
GAS
SUPPLY
MANUAL SHUTOFF VALVE (REQUIRED)
SEDIMENT TRAP
UNION
A89414
Fig. 13Typical Gas Pipe Arrangement
Piping should be pressure tested in accordance with local and national plumbing and gas codes before the furnace has been attached. If the pressure exceeds 0.5 psig (14-in. wc), the gas supply pipe must be disconnected from the furnace and capped
10
TABLE 6ELECTRICAL DATA
UNIT
SIZE
024050 115–60–1 127 104 6.6 14 42 15 036050 115–60–1 127 104 8.1 14 34 15 024070 115–60–1 127 104 6.7 14 42 15 036070 115–60–1 127 104 8.4 14 33 15 036096 115–60–1 127 104 9.2 14 30 15 048096 115–60–1 127 104 10.2 14 28 15 048115 115–60–1 127 104 10.1 14 28 15 060115 115–60–1 127 104 13.3 12 33 20 066115 115–60–1 127 104 15.2 12 29 20 060135 115–60–1 127 104 14.3 12 31 20
* Permissible limits of voltage range at which unit will operate satisfactorily.
Time-delay type is recommended.Length shown is a measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
VOLTS HERTZ
PHASE
OPERATING
VOLTAGE RANGE
Maximum* Minimum*
MAXIMUM
UNIT
AMPS
MIN
WIRE
GAGE
MAXIMUM
WIRE LENGTH (FT)
FUSE OR CKT BKR
MAXIMUM
AMPS
before the pressure test. If the test pressure is equal to or less than
0.5 psig (14-in. wc), turn off electric shutoff switch located on the gas valve before the test. It is recommended that the ground joint union be loosened before pressure testing.
After all connections have been made, purge the lines and check for gas leakage with regulated gas supply pressure.
X. ELECTRICAL CONNECTIONS
This section covers the electrical connections necessary to install the 376C503 furnace.
A. 115–V Wiring
Refer to the unit rating plate or Table 6 for equipment electrical requirements. The control system requires an earth ground for proper operation.
CAUTION: Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire.
Make all electrical connections in accordance with the current edition of the National Electrical Code (NEC) ANSI/NFPA 70-1999 and any local codes or ordinances that might apply. For Canadian installations, all electrical connections must be made in accordance with Canadian Electrical Code CSA C22.1, or authori­ties having jurisdiction.
NOTE: Proper polarity must be maintained for 115-v wiring. If polarity is incorrect, control board status code indicator light will flash rapidly and the furnace will not operate.
WARNING: The cabinet MUST have an uninterrupted or unbroken ground according to NEC, ANSI/NFPA 70-1999 and Canadian Electrical Code, CSA C22.1 or local codes to minimize personal injury if an electrical fault should occur. This may consist of electrical wire or conduit approved for electrical ground when installed in accordance with existing electrical codes. Do not use gas piping as an electrical ground. Failure to follow this warning could result in electrical shock, fire, or death.
B. 24–V Wiring
Make field 24-v connections at the 24-v terminal strip. (See Fig.
14.) Connect terminal Y as shown in Fig. 15 or proper cooling operation in cooling mode. Use only AWG No. 18, color-coded, copper thermostat wire.
The 24-v circuit contains an automotive-type, 3-amp fuse located on the main control board. Any direct shorts during installation, service, or maintenance could cause this fuse to blow. If fuse replacement is required, use ONLY a 3-amp fuse of identical size.
C. Accessories
1. Electronic Air Cleaner (EAC) Two quick-connect terminals marked EAC-1 and EAC-2 are provided for EAC connection. (See Fig. 14.) These terminals are energized with 115-v, (1.5-amp maximum) during blower motor operation.
2. Humidifier (HUM) A quick-connect terminal (HUM) and screw terminal (C
OM)
are provided for 24-v humidifier connection. (See Fig. 16.) HUM terminal is energized with 24-v (0.5-amp maximum) after inducer pressure switch closes.
WARNING: DO NOT connect furnace control HUM terminal to HUM (humidifier) terminal on Thermidis­tat, Zone Controller or similar device. See Thermidis­tat, Zone Controller, thermostat, or controller manufac­turers instructions for proper connection. A failure to follow this warning could result in fire.
NOTE: A field-supplied, 115-v controlled relay connected to EAC terminals may be added if humidifier operation is desired during blower operation.
XI. VENTING
Refer to the national or local installation code such as NFGC in the United States, or the NSCNGPIC in Canada for proper vent sizing and installation requirements. Use the enclosed Installation In­structions (Single-Stage Vent Tables for Category I Fan-Assisted Furnaces) for a quick, easy reference. After fully assembling the vent connector to the furnace flue collar, securely fasten the vent connector to the collar with two field­supplied, corrosion-resistant, sheet metal screws located 180° apart and midway up the collar. The horizontal portion of the venting system shall maintain a minimum of 1/4-in. upward slope per linear ft and it shall be rigidly supported every 5 ft or less with hangers or straps to ensure that there will be no movement after installation.
START-UP PROCEDURES, ADJUSTEMENT, AND
SAFETY CHECK
I. GENERAL NOTE: Proper polarity must be maintained for 115-v wiring. If
polarity is incorrect, control status indicator light will flash rapidly and furnace will not operate. The furnace must have a 115-v power supply properly connected and grounded. Proper polarity must be maintained for correct operation. Thermostat wire connections at R, W, C, and Y must be made at the 24-v terminal block on the furnace control. The gas service pressure must not exceed 0.5 psig (14-in. wc), but must be no less than 0.16 psig (4.5-in. wc).
11
BLOWER OFF DELAY ADJUSTMENT SWITCH
TEST/TWIN
SEC-1
3-AMP FUSE
COOL
HEAT
115-VAC (L1)
POWER SUPPLY
HOT SURFACE
IGNITOR CONNECTOR
Before operating the furnace, check each manual reset switch for continuity. If necessary, press the button to reset the switch.
The blower compartment door must be in place to complete the 115-v circuit to the furnace.
CAUTION: This furnace is equipped with 2 manual reset limit switches in the gas control area. The switches will open and shut off power to the gas valve if a flame rollout or an overheating condition occurs in the gas control area. DO NOT bypass the switches. Correct inadequate combustion air supply problem and reset the switches.
II. SEQUENCE OF OPERATION
CAUTION: Furnace control must be grounded for
proper operation, or control will lockout. Control is grounded through green wire routed to gas valve and burner bracket screw.
Using the schematic diagram shown in Fig. 16, follow the sequence of operation through the different modes. Read and follow the wiring diagram very carefully.
NOTE: If there is a power interruption and any thermostat call, the control will initiate a 90-sec blower only on period before starting another cycle.
G R Y
W
Com
24V HUM
115-VAC (L2) NEUTRAL CONNECTION
INDUCER MOTOR CONNECTOR
24-V THERMOST AT TERMINALS
HUMIDIFIER TERMINAL (24-VAC 0.5 AMP MAX)
LED OPERATION & DIAGNOSTIC LIGHT
HARNESS CONNECTOR
24-V TRANSFORMER SEC-2 SPARE-1 BLOWER SPEED
SELECTION TERMINALS SPARE-2
EAC-1 (BLACK) EAC-ELECTRONIC AIR CLEANER
TERMINALS (115-VAC 1 AMP MAX) EAC-2 (WHITE)
Fig. 14Furnace Control
1. Heating mode
NOTE: Ignition sequence will repeat 3 additional time before a lockout occurs. Lockout automatically resets after 3 hr, or can be manually reset by turning 115–v off (not at thermostat) for 3 sec minimum, then on again.
A00292
When the thermostat calls for heat,the R-W circuit closes. The furnace control performs a self-check, verifies the pressure switch contacts are open, and starts inducer motor.
a. Prepurge periodAs the inducer motor comes up to
speed, the pressure switch contacts close to begin a 15-sec prepurge period.
b. Igniter warm-upAt the end of the prepurge period, the
igniter is energized for a 17-sec igniter warm-up period.
c. Ignition sequenceWhen the igniter warm-up period is
completed, the gas valve opens, permitting gas flow to the burners where it is ignited. After 5 sec, the igniter is de-energized and a 2-sec flame-sensing period begins.
d. HUM terminal is energized with the gas valve. See
Accessories in the Electrical Connections section.
e. Flame-sensingWhen burner flame is sensed, the con-
trol begins the blower on delay period and continues holding the gas valve open. If burner flame is not sensed, the control closes the gas valve and repeats ignition cycle.
12
f. Blower on delayForty-five sec after burner flame is
proven, the blower motor is energized on heating speed. Simultaneously, terminals HUM and C
OM-24V for hu-
midifier, and EAC-1 and EAC-2 for EAC are energized. If jumper is on pin 6 and pin 9, blower on delay period is 66 sec.
g. Blower off delayWhen the thermostat is satisfied, the
circuit between R-W is broken, de-energizing the gas valve stopping gas flow to the burners. The blower motor and EAC remain energized 90, 135, 180, or 225 sec (depending on the blower off-time selection). The furnace is factory set for a 135-sec blower off delay period.
h. Post-purgeThe inducer motor remains energized 5 sec
after the burners are extinguished. If jumper is on pin 6 and pin 9, the post-purge period is 15 sec.
2. Cooling mode When the thermostat calls for cooling,R-G and R-Y circuits close. The R-Y circuit starts the outdoor condensing unit and the combined R-Y and R-G circuits start the furnace blower motor on cooling speed. The EAC-1 termi­nal is energized with 115–v when the blower is operating on cooling speed. When the thermostat is satisfied, R-G and R-Y circuits are broken. The furnace blower and EAC continue operating on cooling speed for an additional 90 sec.
NOTE: EAC-1 terminal in energized with 115-v whenever blower is operating.
3. Continuous blower mode When the R-G circuit is made, the blower motor operates on heating speed. During a call for heat, the blower stops, allowing the furnace heat exchangers to heat up more quickly, then restarts at the end of the 45-sec blower on delay period. If jumper is on pin 6 and pin 9, the blower on delay is 66 sec. The blower reverts to continuous operation after the heating cycle is completed.
When the thermostat calls for cooling,the blower oper­ates on cooling speed. When the thermostat is satisfied, the blower operates an additional 90 sec before reverting back to continuous operation on heating speed.
4. Heat pump mode When installed with a heat pump, the furnace control automatically changes the timing sequence to avoid long blower off time during demand defrost cycles. When the W-Y or W-Y-G thermostat inputs are received at the same time, the control changes the blower to heating speed or starts the blower if it was off, and begins a heating cycle. The blower remains on until the end of the prepurge period, then shuts off until the end of the ignition warm-up and trial for ignition periods (a total of 24 sec). The blower then comes back on at heating speed. When the W input signal disappears, the control begins the normal inducer post-purge period and the blower changes to cooling speed after a 1-sec delay. If the W-Y-G signals disappear at the same time, the blower remains on for the selected heating blower off delay period and the inducer goes through its normal post-purge period. If the W-Y inputs should disappear, leaving the G signal input, the control goes into continuous blower and the inducer re­mains on for the normal post-purge period. Anytime the control senses false flame, the control locks out of the heating mode. This occurs because the control cannot sense the W input due to the false flame signal, and as a result, sees only the Y input and goes into cooling mode blower off delay. All other control functions remain in standard format.
NOTE: EAC-1 terminal is energized whenever blower operates. HUM terminal is only energized when gas valve is energized.
FIVE WIRE
THREE-WIRE
HEATING-ONLY
BLOWER DOOR SWITCH
BLK
WHT
115-V FIELD-
SUPPLIED
DISCONNECT
BLK
WHT
GND
AUXILIARY J-BOX
FIELD 24-V WIRING FIELD 115-, 208/230-, 460-V WIRING FACTORY 24-V WIRING FACTORY 115-V WIRING
GND
FURNACE
NOTE 2
W
C
R
O N T
G
R O
C
L
Y
24-V
TERMINAL
BLOCK
WCR GY
NOTE 1
NOTES: Connect Y-terminal in furnace as shown for proper blower operation.
1. Some thermostats require a "C" terminal connection as shown.
2. If any of the original wire, as supplied, must be replaced, use
3. same type or equivalent wire.
THERMOSTAT TERMINALS
CONDENSING UNIT
TWO WIRE
Fig. 15Heating and Cooling Application Wiring Diagram
FIELD-SUPPLIED DISCONNECT
208/230- OR 460-V THREE PHASE
208/230-V SINGLE PHASE
GND
A99521
13
Fig. 16Furnace Wiring Diagram
A00304
PCB
BLOWER OFF DELAY
SELECTION CHART
90 SEC 135 SEC 180 SEC 225 SEC
GVR
HI/LO
RELAY
SEC-1
SEC-2
PL1
321 6
5
4
9
87
LED
TEST/TWIN
BLOWER
OFF
DELAY
G R Y W C
HUM
HSIR IDR BLW R
BLOWER SPEED SELECT
FU1
COOL
HEAT
L2
PL3
PL2
VAC
120
L1
PR1
1 2
1 2 3
PR2
24 VAC-3A
FUSE
SPARE-2
SPARE-1
EAC-1
EAC-2
C
1.5 AMP
12
PL5
WHT
BLK
WHT
WHT
BLK
BLK
HSI
BLK
WHT
WHT (COM)
RED (LO)
BLU (MED LO)
NOTE #7
OL
START
BLWM
YEL (MED HI)
BLK (HI)
BRN
BRN
TRAN
BLU
RED
BLK
WHT
WHT (COM)
CAP
RED
RED
ORN
FUSED DISCONNECT
SWITCH (WHEN REQ’D)
NOTE #4
FU2
BLK
WHT
JB
LEGEND
ALS AUXILIARY LIMIT SWITCH, OVERTEMP. -MANUAL RESET, SPST-(N.C.) BLWR BLOWER MOTOR RELA Y, SPST-(N.O.) BLWM BLOWER MOTOR BVSS BLOCKED VENT SHUTOFF SWITCH, SPST - (N.C.) CAP CAP ACITOR CPU MICROPROCESSOR AND CIRCUITRY DSS DRAFT SAFEGUARD SWITCH EAC-1 ELECTRONIC AIR CLEANER CONNECTION (115 VAC 1.5 AMP MAX.) EAC-2 ELECTRONIC AIR CLEANER CONNECTION (COMMON) FL FUSIBLE LINK FRS FLAME ROLLOUT SW . -MANU AL R ESET, SPST-(N.C.) FSE FLAME PROVING ELECTRODE FU1 FUSE, 3 AMP, A UT OM OTIVE BLADE TYPE, FACTORY INST ALLED FU2 FUSE OR CIRCUIT BREAKER CURRENT INTERRUPT DEVICE
(FIELD INSTALLED & SUPPLIED) GV GAS VALVE-REDUNDANT OPERATORS GVR GAS VALVE RELAY , DPST -(N.O.) HI/LO BLOWER MOTOR SPEED CHANGE RELAY, SPDT HSI HOT SURFAC E IGN ITOR (115 VAC ) HSIR HOT SURFACE IGNITOR RELAY, SPST-(N.O.) HUM 24VAC HUMIDIFIER CONNECTION (.5 AMP. MAX.) IDM INDUCED DRAFT MOTOR IDR INDUCED DRAFT RELAY, SPST-(N.O.) ILK BLOWER ACCESS PANEL INTERLOCK SWITCH, SPST -(N.O.) JB JUNCTION BOX LED LIGHT-EMITTING DIODE FOR STATUS CODES LGPS LOW GAS PRESSURE SWITCH, SPST-(N.O.) LS LIMIT SWITCH, A UT O RESET, SPST(N.C.) OL AUTO-RESET INTERNAL MOTOR OVERLOAD TEMP. SW.
PCB PRINTED CIRCUIT BOARD PL1 9-CIRCUIT CONNECTOR PL2 2-CIRCUIT PCB CONNECTOR PL3 3-CIRCUIT ID M CONNECT O R PL5 2-CIRCUIT HSI/PCB CONNECTOR PRS PRESSURE SWITCH, SPST-(N.O.) TEST/TWIN COMPONENT TEST & TWIN TERMINAL TRAN TRANSFO RM ER -115VAC/24VAC
JUNCTION UNMARKED TERMI NAL PCB TERMINAL FACTORY WIRING (115VAC) FACTORY WIRING (24VAC) FIELD WIRING (115VAC) FIELD WIRING (24VAC) CONDUCTOR ON PCB FIELD WIRING TERMINAL FIELD GROUND EQUIPMENT GROUND FIELD SPLICE PLUG RECEPTACLE
L1
L2
L1
BLWR
HI/LO
TO 115VAC FIELD DISCONNECT
NOTE #4
EQUIPMENT GROUND
SPARE-2
HEAT
SPARE-1
COOL
NOTE #7
COM
HSIR
EAC-1
START
OL
COM
HI
MED HI
MED LO
LO
BLWM
SCHEMATIC DIAGRAM
(NATURAL GAS & PRO PANE)
EAC-2
1
1
HSI
2
PL52
PL2
3
PL3
PR2
115VA C
PR1
TRAN
24VAC
1
2
IDR
TEST/TWIN
FU1
NOTE #6
CAP
L2
PL1
8
FSE
9
6
5
CPU
HSIR
IDR
BLWR
Y
G
C
R
W
GVR-2
SEC-1
HI/LO
GVR
SEC-2
NOTES:
322869-101 REV. H
1. If any of the original equipment wire is replaced use wire rated for 105°C.
2. Inducer (IDM) and blower (BLWM) motors contain internal auto-reset thermal overload s witches (OL).
3. Blower motor speed selections are for a verage conditions, see installation instructions for details on optimum speed selection.
4. Use only copper wire between the disconnect sw itch and the furnace junction bo x (JB ).
5. This wire must be connected to furnace sheetmetal for control to detect flame.
6. Replace only with a 3 amp fuse.
7. Yellow lead not on all motors.
8. Blower-on delay, gas heating 45 seco nds , cooling or heat pu m p 2 se co nds .
9. Blower-off delay, gas heating 90, 135, 180 or 225 sec on ds , co oling or heat pu m p 90 seco nds . (135 seconds only on some models)
10. Ignition-lock o u t will occur a f te r f o u r c o n s ecutive u nsucce s s f u l t ria ls -f o r -ignition. C ontrol will auto-reset after thre e hours.
11. When us e d , a uxiliary lim it s witch (ALS) is on s ome do wnflow models only. W h en used, FL is o n upflow models only.
12. Some models may have spad e quic k co nn e ct terminals.
13. Factory connected when LGPS is not used.
14. Factory connected when BVSS is not used. BVSS used when Chimney Adapter Accessory Kit is installed .
15. Gas valve leads are interchangeable on single stage valves .
BLK
OM
SW2
SW1
OM
3
4
7 1
OM
HUM
IDM
ILK
DSS
BVSS
PRS
ILK
L1
NEUTRAL
IDM
(WHEN USED)
NOTE #14
NOT USED NOT USED
NOT USED
FSE
BLU
PRS
DSS
BVSS
(WHEN USED)
NOTE #14
WHT
LS
FL
(NOT ON ALL MODELS)
NOTE #9
FRS1
FRS2
LS
FL
NOTE #12
ORN
ORN
ORN
ALS
(WHEN USED)
ORN
NOTE #11
LGPS
(WHEN USED)
NOTE #13
NOTE #14
NOTE #11
2
GVR-1
NOTE #14
ALS
(WHEN USED)
(WHEN USED)
NOTE #13
LGPS (WHEN USED)
NOTE #13
YEL
FRS1
FRS2
(WHEN USED) NOTE #11
GRN/YEL
GRN/YEL
GND
NOTE #5
GRN/YEL
NOTE #5
GRN/YEL
NOTE #15
NOTE #15
GV
GV
14
III. START-UP PROCEDURES
1. Purge gas linesAfter all connections have been made, purge the lines and check for leaks.
WARNING: Never purge a line into a combustion chamber. Never use matches, candles, flame, or other sources of ignition to check for gas leakage. Use a soap-and-water solution to check for gas leaks. Failure to follow this warning could result in fire, explosion, per­sonal injury, or death.
2. Component testThe furnace control allows all compo­nents, except gas valve, to be run for a short period of time. This feature helps diagnose a system problem in case of a component failure. To initiate component test procedure, short (jumper) the TEST 3/16-in. quick connect terminal on control (adjacent to diagnostic light) and the C
OM-24V
terminal on furnace thermostat connection block for ap­proximately 2 sec. (See Fig. 14.)
NOTE: Component test feature will not operate if any thermostat signal is present at control.
Component test sequence is as follows.
a. Momentarily jumper TEST and C
OM-24V terminals until
LED goes off. b. LED will display previous status code 4 times. c. Inducer motor starts and continues to run for entire
component test. d. Hot surface igniter is energized for 15 sec, then de-
energized.
e. Blower motor operates on cooling speed for 10 sec, then
stops. f. Blower motor operates on heating speed for 10 sec, then
stops. g. Inducer motor stops.
3. To operate furnace, follow procedures on operating instruc­tion label attached to furnace.
4. With furnace operating, set thermostat below room tem­perature and observe that furnace goes off. Set thermostat above room temperature and observe that furnace restarts.
IV. ADJUSTMENTS
1. Set gas input rate Furnace gas input rate on rating plate is for installations at altitudes up to 2000 ft. Furnace input rate must be within ±2 percent of input on furnace rating plate.
a. Determine natural gas orifice size and manifold pressure
for correct input. (1.) Obtain average yearly gas heat value (at installed
altitude) from local gas supplier.
(2.) Obtain average yearly gas specific gravity from
local gas supplier.
(3.) Verify furnace model. Table 7 can only be used for
model 376CAV Furnaces.
(4.) Find installation altitude in Table 7.
NOTE: For Canada altitudes of 2000 to 4500 ft, use U.S.A. altitudes of 2001 to 3000 ft in Table 7.
(5.) Find closest natural gas heat value and specific
gravity in Table 7.
(6.) Follow heat value and specific gravity lines to point
of intersection to find orifice size and manifold pressure settings for proper operation.
EXAMPLE: (0–2000 ft altitude) Heating value = 1025 Btu/cu ft Specific gravity = 0.62 Therefore: Orifice No. 43*
Manifold pressure 3.6-in. wc * Furnace is shipped with No. 43 orifices. In this example all main burner orifices are the correct size and do not need to be changed to obtain proper input rate.
(7.) Check and verify burner orifice size in furnace.
NEVER ASSUME ORIFICE SIZE. ALWAYS CHECK AND VERIFY.
NOTE: If orifice hole appears damaged or it is suspected to have been redrilled, check orifice hole with a numbered drill bit of correct size. Never redrill an orifice. A burr-free and squarely aligned orifice hole is essential for proper flame characteristics.
BURNER
ORIFICE
A93059
CAUTION: DO NOT redrill orifices. Improper drilling (burrs, out-of-round holes, etc.) can cause excessive burner noise and misdirection of burner flames. This can result in flame impingement of burners and heat exchang­ers causing failures.
b. Adjust manifold pressure to obtain input rate.
(1.) Remove regulator adjustment seal cap. (See Fig.
17.)
(2.) Turn adjusting screw, counterclockwise (out) to
decrease manifold pressure or clockwise (in) to increase manifold pressure.
NOTE: This furnace has been approved for a manifold pressure of 3.2-in. wc to 3.8-in. wc when installed at altitudes up to 2000 ft. For altitudes above 2000 ft, the manifold pressure can be adjusted from 2.0-in. wc to 3.8-in. wc.
CAUTION: DO NOT bottom out gas valve regulator adjusting screw. This can result in unregulated manifold pressure and result in excess overfire and heat exchanger failures.
(3.) After correct manifold pressure is obtained, replace
gas valve regulator adjustment screw cap and verify adjusted gas input rate using method outlined in item c.
15
TABLE 7MODEL 376CAV ORIFICE SIZEAND MANIFOLD PRESSURE FOR CORRECT INPUT
(TABULATED DATA BASED ON 23,000 BTUH PER BURNER, DERATED 4 PERCENT FOR EACH 1000 FT ABOVE SEA LEVEL)*
ALTITUDE
RANGE
(FT)
0
to
2000
U.S.A. and Canada
ALTITUDE
RANGE
(FT)
U.S.A.
Altitudes
2001
to
3000
or
Canada
Altitudes
2000
U.S.A. and Canada
to
4500
ALTITUDE
RANGE
(FT)
3001
to
4000
U.S.A. Only
ALTITUDE
RANGE
(FT)
4001
to
5000
U.S.A. Only
* For size 060135 only, input is 22,500 Btuh per burner. Deduct 0.1-in. wc from manifold pressure shown in table. Change orifice size if manifold pressure falls below 3.2-in. wc on altitudes up to 2000 ft, otherwise change orifice size if manifold pressure falls below 2.0-in. wc. Orifice sizes shown in SHADING are factory installed.
AVG GAS
HEAT VALUE
(BTU/CU FT)
850 41 3.6 41 3.7 41 3.8 40 3.6 40 3.8 875 42 3.8 41 3.5 41 3.6 41 3.7 41 3.8 900 42 3.5 42 3.7 42 3.8 41 3.5 41 3.6 925 42 3.4 42 3.5 42 3.6 42 3.7 42 3.8 950 42 3.2 42 3.3 42 3.4 42 3.5 42 3.6
975 43 3.7 43 3.8 42 3.2 42 3.3 42 3.4 1000 43 3.5 43 3.6 43 3.7 42 3.2 42 3.3 1025 43 3.3 43 3.4 43 3.6 43 3.7 43 3.8 1050 43 3.2 43 3.3 43 3.4 43 3.5 43 3.6 1075 44 3.5 44 3.6 43 3.2 43 3.3 43 3.4 1100 44 3.3 44 3.4 44 3.5 43 3.2 43 3.3
AVG GAS
HEAT VALUE
(BTU/CU FT)
775 42 3.7 42 3.8 41 3.5 41 3.6 41 3.8
800 42 3.4 42 3.6 42 3.7 42 3.8 41 3.5
825 42 3.2 42 3.3 42 3.5 42 3.6 42 3.7
850 43 3.7 43 3.8 42 3.3 42 3.4 42 3.5
875 43 3.5 43 3.6 43 3.7 42 3.2 42 3.3
900 43 3.3 43 3.4 43 3.5 43 3.7 43 3.8
925 43 3.1 43 3.2 43 3.4 43 3.5 43 3.6
950 43 3.0 43 3.1 43 3.2 43 3.3 43 3.4
975 43 2.8 43 2.9 43 3.0 43 3.1 43 3.2 1000 43 2.7 43 2.8 43 2.9 43 3.0 43 3.1 1025 43 2.6 43 2.6 43 2.7 43 2.8 43 2.9
AVG GAS
HEAT VALUE
(BTU/CU FT)
750 42 3.4 42 3.6 42 3.7 42 3.8 41 3.5
775 42 3.2 42 3.3 42 3.5 42 3.6 42 3.7
800 43 3.7 43 3.8 42 3.2 42 3.3 42 3.4
825 43 3.5 43 3.6 43 3.7 43 3.8 42 3.2
850 43 3.3 43 3.4 43 3.5 43 3.6 43 3.7
875 43 3.1 43 3.2 43 3.3 43 3.4 43 3.5
900 43 2.9 43 3.0 43 3.1 43 3.2 43 3.3
925 43 2.8 43 2.9 43 3.0 43 3.0 43 3.1
950 43 2.6 43 2.7 43 2.8 43 2.9 43 3.0
975 43 2.5 43 2.6 43 2.7 43 2.7 43 2.8 1000 43 2.4 43 2.4 43 2.5 43 2.6 43 2.7
AVG GAS
HEAT VALUE
(BTU/CU FT)
725 42 3.2 42 3.3 42 3.5 42 3.6 42 3.7
750 43 3.7 43 3.8 42 3.2 42 3.3 42 3.4
775 43 3.4 43 3.6 43 3.7 43 3.8 42 3.2
800 43 3.2 43 3.3 43 3.5 43 3.6 43 3.7
825 43 3.0 43 3.1 43 3.2 43 3.4 43 3.5
850 43 2.9 43 3.0 43 3.1 43 3.2 43 3.3
875 43 2.7 43 2.8 43 2.9 43 3.0 43 3.1
900 43 2.6 43 2.6 43 2.7 43 2.8 43 2.9
925 43 2.4 43 2.5 43 2.6 43 2.7 43 2.8
950 43 2.3 43 2.4 43 2.5 43 2.5 43 2.6
0.58 0.60 0.62 0.64 0.66
Orifice
no.
Orifice
no.
Orifice
no.
Orifice
no.
Manifold
Pressure
0.58 0.60 0.62 0.64 0.66 Manifold
Pressure
0.58 0.60 0.62 0.64 0.66 Manifold
Pressure
0.58 0.60 0.62 0.64 0.66 Manifold
Pressure
Orifice
no.
Orifice
no.
Orifice
no.
Orifice
no.
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
Orifice
no.
Orifice
no.
Orifice
no.
Orifice
no.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
no.
Orifice
no.
Orifice
no.
Orifice
no.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
no.
Orifice
no.
Orifice
no.
Orifice
no.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
16
TABLE 7MODEL 376CAV ORIFICE SIZEAND MANIFOLD PRESSURE FOR CORRECT INPUT (CONTINUED)
(TABULATED DATA BASED ON 23,000 BTUH PER BURNER, DERATED 4 PERCENT FOR EACH 1000 FT ABOVE SEA LEVEL)*
ALTITUDE
RANGE
(FT)
5001
to
6000
U.S.A. Only
ALTITUDE
RANGE
(FT)
6001
to
7000
U.S.A. Only
ALTITUDE
RANGE
(FT)
7001
to
8000
U.S.A. Only
ALTITUDE
RANGE
(FT)
8001
to
9000
U.S.A. Only
* For size 060135 only, input is 22,500 Btuh per burner. Deduct 0.1-in. wc from manifold pressure shown in table. Change orifice size if manifold pressure falls below 3.2-in. wc on altitudes up to 2000 ft, otherwise change orifice size if manifold pressure falls below 2.0-in. wc. Orifice sizes shown in SHADING are factory installed.
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
700 43 3.7 43 3.8 42 3.2 42 3.3 42 3.4 725 43 3.4 43 3.6 43 3.7 43 3.8 42 3.2 750 43 3.2 43 3.3 43 3.4 43 3.5 43 3.6 775 43 3.0 43 3.1 43 3.2 43 3.3 43 3.4 800 43 2.8 43 2.9 43 3.0 43 3.1 43 3.2 825 43 2.7 43 2.7 43 2.8 43 2.9 43 3.0 850 43 2.5 43 2.6 43 2.7 43 2.8 43 2.8 875 43 2.4 43 2.4 43 2.5 43 2.6 43 2.7 900 43 2.2 43 2.3 43 2.4 43 2.5 43 2.5 925 43 2.1 43 2.2 43 2.3 43 2.3 43 2.4 950 48 3.8 43 2.1 43 2.1 43 2.2 43 2.3 975 48 3.6 48 3.7 43 2.0 43 2.1 43 2.2
1000 48 3.4 48 3.5 48 3.6 48 3.7 43 2.1
AVG GAS HEAT VALUE AT ALTITUDE
(BTU/CU FT)
650 43 3.7 43 3.8 42 3.2 42 3.3 42 3.5 675 43 3.4 43 3.5 43 3.7 43 3.8 42 3.2 700 43 3.2 43 3.3 43 3.4 43 3.5 43 3.6 725 43 3.0 43 3.1 43 3.2 43 3.3 43 3.4 750 43 2.8 43 2.9 43 3.0 43 3.1 43 3.2 775 43 2.6 43 2.7 43 2.8 43 2.9 43 3.0 800 43 2.4 43 2.5 43 2.6 43 2.7 43 2.8 825 43 2.3 43 2.4 43 2.5 43 2.5 43 2.6 850 43 2.2 43 2.2 43 2.3 43 2.4 43 2.5 875 43 2.0 43 2.1 43 2.2 43 2.3 43 2.3
AVG GAS HEAT VALUE AT ALTITUDE
(BTU/CU FT)
625 43 3.4 43 3.6 43 3.7 43 3.8 42 3.2 650 43 3.2 43 3.3 43 3.4 43 3.5 43 3.6 675 43 3.0 43 3.1 43 3.2 43 3.3 43 3.4 700 43 2.7 43 2.8 43 2.9 43 3.0 43 3.1 725 43 2.6 43 2.6 43 2.7 43 2.8 43 2.9 750 43 2.4 43 2.5 43 2.6 43 2.6 43 2.7 775 43 2.2 43 2.3 43 2.4 43 2.5 43 2.5 800 43 2.1 43 2.2 43 2.2 43 2.3 43 2.4 825 48 3.7 43 2.0 43 2.1 43 2.2 43 2.2 850 48 3.5 48 3.6 48 3.7 43 2.1 43 2.1
AVG GAS HEAT VALUE AT ALTITUDE
(BTU/CU FT)
600 43 3.2 43 3.3 43 3.4 43 3.5 43 3.6 625 43 3.0 43 3.1 43 3.2 43 3.3 43 3.4 650 43 2.7 43 2.8 43 2.9 43 3.0 43 3.1 675 43 2.5 43 2.6 43 2.7 43 2.8 43 2.9 700 43 2.4 43 2.4 43 2.5 43 2.6 43 2.7 725 43 2.2 43 2.3 43 2.3 43 2.4 43 2.5 750 43 2.0 43 2.1 43 2.2 43 2.3 43 2.3 775 48 3.6 48 3.7 43 2.1 43 2.1 43 2.2 800 48 3.4 48 3.5 48 3.6 48 3.7 43 2.0
0.58 0.60 0.62 0.64 0.66
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
0.58 0.60 0.62 0.64 0.66 Manifold
Pressure
0.58 0.60 0.62 0.64 0.66 Manifold
Pressure
0.58 0.60 0.62 0.64 0.66 Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
17
TABLE 7MODEL 376CAV ORIFICE SIZEAND MANIFOLD PRESSURE FOR CORRECT INPUT (CONTINUED)
(TABULATED DATA BASED ON 23,000 BTUH PER BURNER, DERATED 4 PERCENT FOR EACH 1000 FT ABOVE SEA
ALTITUDE
RANGE
(FT)
9001
to
10,000
U.S.A. Only
* For size 060135 only, input is 22,500 Btuh per burner. Deduct 0.1-in. wc from manifold pressure shown in table. Change orifice size if manifold pressure falls below 3.2-in. wc on altitudes up to 2000 ft, otherwise change orifice size if manifold pressure falls below 2.0-in. wc. Orifice sizes shown in SHADING are factory installed.
AVG GAS HEAT VALUE AT ALTITUDE
(BTU/CU FT)
575 43 3.0 43 3.1 43 3.2 43 3.3 43 3.4 600 43 2.7 43 2.8 43 2.9 43 3.0 43 3.1 625 43 2.5 43 2.6 43 2.7 43 2.8 43 2.8 650 43 2.3 43 2.4 43 2.5 43 2.6 43 2.6 675 43 2.1 43 2.2 43 2.3 43 2.4 43 2.4 700 48 3.8 43 2.1 43 2.1 43 2.2 43 2.3 725 48 3.5 48 3.6 48 3.7 43 2.1 43 2.1 750 49 3.8 48 3.4 48 3.5 48 3.6 48 3.7 775 49 3.6 49 3.7 49 3.8 48 3.4 48 3.5
0.58 0.60 0.62 0.64 0.66
Orifice
No.
Manifold Pressure
Orifice
No.
SPECIFIC GRAVITY OF NATURAL GAS
Manifold Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
(4.) Burner flame should be clear blue, almost transpar-
ent. (See Fig. 18.)
c. Verify natural gas input rate by clocking gas meter.
NOTE: High -Altitude Adjustment UNITED STATES
At installation altitudes above 2000 ft, this furnace has been approved for a 4 percent derate for each 1000 ft above sea level. See Table 8 for derate multiplier factor.
Fig. 17Redundant Automatic Gas Control Valve
BURNER FLAME
MANIFOLD
Fig. 18Burner Flame
BURNER
A00238
A89020
18
TABLE 8ALTITUDE DERATE MULTIPLIER FOR U.S.A.
ALTITUDE
(FT)
02000 0 1.00 20013000 812 0.90 30014000 1216 0.86 40015000 1620 0.82 50016000 2024 0.78 60017000 2428 0.74 70018000 2832 0.70 80019000 3236 0.66
900110,000 3640 0.62
* Derate multiplier factor is based on midpoint altitude for altitude range.
EXAMPLE:
92,000 BTUH INPUT FURNACE INSTALLED AT 4300 FT.
Furnace Input
Rate at
Sea Level
92,000 0.82 75,440
PERCENT OF
DERATE
Derate
Multiplier
X=
Factor
DERATE MULTIPLIER FACTOR FOR U.S.A.*
Furnace Input Rate
at Installation
Altitude
CANADA At installation altitudes from 2000 to 4500 ft, this furnace must be
derated 10 percent by an authorized Gas Conversion Station. To determine correct input rate for altitude, see example above and use 0.90 as derate multiplier factor.
a. Turn off all other gas appliances and pilots. b. Start furnace and let operate for 3 minutes. c. Measure time (in sec) for gas meter test dial to complete
1 revolution. d. Refer to Table 9 for cu ft of gas per hr. e. Multiply gas rate (cu ft/hr) X heating value (Btu/cu ft)
using natural gas heating value from local gas
utility/supplier.
EXAMPLE: (0–2000 ft altitude) Btu heating input = Btu/cu ft X cu ft/hr Heating value of gas = 1050 Btu/cu ft Time for 1 revolution of 2-cu ft dial = 82 sec Gas rate = 88 cu ft/hr (from Table 9) Btu heating input = 88 X 1050 = 92,400 Btuh In this example, the orifice size and manifold pressure adjustment is within ±2 percent of the furnace input rate.
d. To change blower motor speed selections for heating
mode, remove blower motor lead from control board HEAT terminal. (See Fig. 14.) Select desired blower motor speed lead from 1 of the other terminals and relocate it to HEAT terminal. See Table 10 for lead color identification. Reconnect original lead on SPARE termi­nal.
Follow this same procedure for proper selection of COOL speed selection.
TABLE 9GAS RATE (CU FT/HR)
SECONDS
FOR 1
REVOLUTION
SIZE OF TEST DIAL
I
10 360 720 1800 50 72 144 360 11 327 655 1636 51 71 141 355 12 300 600 1500 52 69 138 346 13 277 555 1385 53 68 136 340 14 257 514 1286 54 67 133 333 15 240 480 1200 55 65 131 327 16 225 450 1125 56 64 129 321 17 212 424 1059 57 63 126 316 18 200 400 1000 58 62 124 310 19 189 379 947 59 61 122 305 20 180 360 900 60 60 120 300 21 171 343 857 62 58 116 290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 95 237 29 124 248 621 78 46 92 231 30 120 240 600 80 45 90 225 31 116 232 581 82 44 88 220 32 113 225 563 84 43 86 214 33 109 218 545 86 42 84 209 34 106 212 529 88 41 82 205 35 103 206 514 90 40 80 200 36 100 200 500 92 39 78 196 37 97 195 486 94 38 76 192 38 95 189 474 96 38 75 188 39 92 185 462 98 37 74 184 40 90 180 450 100 36 72 180 41 88 176 439 102 35 71 178 42 86 172 429 104 35 69 173 43 84 167 419 106 34 68 170 44 82 164 409 108 33 67 167 45 80 160 400 110 33 65 164 46 78 157 391 112 32 64 161 47 76 153 383 116 31 62 155 48 75 150 375 120 30 60 150 49 73 147 367
Cu Ft2Cu Ft5Cu Ft
SECONDS
FOR 1
REVOLUTION
SIZE OF TEST DIAL
1
Cu Ft2Cu Ft5Cu Ft
2. Set temperature rise. Furnace must operate within range of temperature rise specified on the unit rating plate. Determine the air tem­perature rise as follows.
a. Place duct thermometers in return and supply ducts as
near furnace as possible. Be sure thermometers do not seeheat exchangers so that radiant heat will not affect thermometer readings. This is particularly important with straight-run ducts.
b. When thermometer readings stabilize, subtract return-air
temperature from supply-air temperature to determine temperature rise.
c. Adjust air temperature rise by adjusting blower speed.
Increase blower speed to reduce temperature rise. De­crease blower speed to increase temperature rise.
WARNING: Disconnect the electrical power before changing the speed tap. A failure to follow this warning could result in personal injury.
CAUTION: If Model 376CAV066115 is installed in
0.50-in. wc or lower static pressure ductwork, evaporator coil condensate blow off can occur during cooling opera­tion. When installed in this manner, do not use high blower speed tap for cooling.
TABLE 10SPEED SELECTOR
COLOR SPEED
Black High COOL
Yellow (When Present) Medium-High SPARE
Blue Medium-Low HEAT
Red Low SPARE
White Common L2/COM
FACTORY-
ATTACHED TO
CAUTION: Recheck temperature rise. It must be within
limits specified on unit rating plate. Recommended op­eration is at midpoint of rise or above.
3. Set thermostat heat anticipator. The thermostat heat anticipator must be set to match the amp draw of the electrical components in the R-W circuit. Accurate amp draw readings can be obtained at thermostat subbase terminals R and W. Fig. 19 illustrates an easy method of obtaining the actual amp draw. The amp reading should be taken after the blower motor has started. See the thermostat manufacturers instructions for adjusting the heat anticipator and for varying the heating cycle length.
NOTE: When using an electronic thermostat, set cycle rate for 3 cycles per hr.
V. CHECK SAFETY CONTROLS
The flame sensor, gas valve, and pressure switch were all checked in the Start-Up Procedures section as part of normal operation.
1. Check primary limit control. This control shuts off the combustion control system and energizes the circulating-air blower motor if the furnace overheats. The preferred method of checking the limit control is to gradually block off the return air after the furnace has been operating for a period of at least 5 minutes. As soon as the limit has shut off the burners, the return-air opening should be unblocked. By using this method to check the limit control, it can be established that the limit is functioning properly and operates if there is a motor failure.
2. Check blocked vent safeguard switch. The purpose of this control is to permit the safe shutdown of the furnace during certain blocked vent conditions.
a. Disconnect power to furnace and remove vent connector
from furnace outlet collar. Be sure to allow time for vent pipe to cool down before removing.
19
THERMOSTAT SUBBASE TERMINALS WITH THERMOSTAT REMOVED (ANITICIPATOR, CLOCK, ETC., MUST BE OUT OF CIRCUIT.)
HOOK-AROUND AMMETER
R Y W G
10 TURNS
FROM UNIT 24-V CONTROL TERMINALS
EXAMPLE:
5.0 AMPS ON AMMETER 10 TURNS AROUND JAWS
0.5 AMPS FOR THERMOSTAT
=
ANTICIPATOR SETTING
Fig. 19Amp Draw Check With Ammeter
b. Restore power to furnace and set room thermostat above
room temperature.
c. After normal start-up, allow furnace to operate for 2
minutes, then block flue outlet 100 percent. Furnace should cycle off within 2 minutes.
d. Remove blockage and reconnect vent pipe to furnace
outlet collar.
e. Wait 5 minutes and then reset blocked vent safeguard
switch.
3. Check pressure switch. This control proves operation of draft inducer blower.
a. Turn off 115-v power to furnace. b. Remove control door and disconnect inducer motor lead
wires from wire harness.
c. Turn on 115-v power to furnace.
A96316
d. Set thermostat to call for heatand wait 1 minute.
When pressure switch is functioning properly, hot sur­face igniter should NOT glow and control diagnostic light flashes a status code 31. If hot surface igniter glows when inducer motor is disconnected, shut down furnace immediately. Determine reason pressure switch did not
function properly and correct condition. e. Turn off 115-v power to furnace. f. Reconnect inducer motor wires, replace control door, and
turn on 115-v power.
4. Check auxiliary limits (when used). a. Turn off 115-v power to furnace. b. Remove blower access door. c. Disconnect red motor lead at blower speed selector.
Mark terminal for proper re-connection. d. Replace blower access door. e. Turn on 115-v power to furnace. Be sure room thermo-
stat is calling for heat. f. Allow furnace to operate until auxiliary limit activates,
but DO NOT operate furnace longer than 4 minutes.
g. If furnace operates for 4 minutes, check/replace limit
switch(es). h. Turn off 115-v power to furnace. i. Remove blower access door. j. Reconnect red motor lead, reset switch, and replace door. k. Turn on 115-v power to furnace
VI. CHECKLIST
1. Put away tools and instruments and clean up debris.
2. Verify manual reset switches has continuity.
3. Ensure blower and control access doors are properly in­stalled.
4. Cycle test furnace with room thermostat.
5. Check operation of accessories per manufacturers instruc­tions.
6. Review Users Guide with owner.
7. Leave literature packet near furnace.
20
CHECKLISTINSTALLATION
LOAD CALCULATION
_________________ Heating Load (Btuh) _________________ Cooling Load (Btuh) _________________ Furnace Model Selection
AIR FOR COMBUSTION AND VENTILATION
_________________ Unconfined Space _________________ Confined Space
VENTING
_________________ NFGC (United States) _________________ NSCNGPIC (Canada) _________________ Local Codes _________________ 1/4-in. Upward Slope _________________ Joints Secure _________________ See Vent Table Instructions
CHECKLISTSTART-UP
_________________ _________________ Temperature Rise Adjusted
_________________ Thermostat Anticipator Setting or _________________ Thermostat Cycle Rate (3 cycles per Hr)
_________________ Primary Limit _________________ Pressure Switches _________________ Draft Safeguard Switch _________________ Auxiliary Limit Switch(es)
_________________ Manufacturer _________________ Model number
(Set Within 2 percent of Rating Plate)
CHECK SAFETY CONTROLS OPERATION
Gas Input Rate
Thermostat
21
22
23
SERVICE TRAINING
Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including:
Unit Familiarization Maintenance
Installation Overview • Operating Sequence
A large selection of product, theory, and skills programs is available, using popular video-based formats and materials. All include video and/or slides, plus companion book.
Classroom Service Training plus "hands-on" the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting, fewer callbacks. Course descriptions and schedules are in our catalog.
CALL FOR FREE CATALOG 1-800-962-9212
[ ] Packaged Service Training [ ] Classroom Service Training
© 2000 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231
24
Printed in U.S.A. 376c503 Catalog No. 5337–605
Loading...