Bryant 376B User Manual

i nstallation, operatron, and maintenance instructions
HIGH-EFFICIENCY
DOWNFLOW/HORIZONTAL INDUCED-COMBUSTION FURNACE
376B
Series A
Sizes 040
thrullS
NOTE: Remove the Energy Guide tag from the furpace
when the installation is complete.
NOTE; This is a highly specialized piece of equipment.
Before beginning the installation, READ THESE
INSTRUCTIONS CAREFULLY AND COMPLETELY.

INTRODUCTION

Before installing the furnace, refer to “Procedure for Induced-Combustion Gas-Fired Furnaces” (packaged with
the equipment) for information concerning combustion, venting, piping, and other standard installation practices. Further reference is made to the current edition of the National Fuel Gas Code NFPA No. 54-1984/ANSI Z223.1-
1984. The induced-combustion vent system of this furnace is
designed to operate at zero or negative pressure at the vent connector outlet. This furnace, therefore, complies with the National Fuel Gas Code (NFPA No. 54-1984/ANSI Z223.1-
1984), Part 7.14.3.b. This furnace is also hsted by A.G.A. for use with the type B1 gas vent, as described in the National
Fuel Gas Code, Part 7.3.2. Each furnace is shipped from the factory completely assem
bled with multispeed direct-drive blower and wired ready for indoor heating installation. All sizes feature a blower con trol center with easy-to-read low-voltage terminal strip to ensure proper connections.
The output capacity and any representations of efficiency for this product are based on standard Department of Energy test procedures. The insteJled operation may vary, depending on installation, weather, or other factors.
Cancels; 39376DP5-A
40376DP5-B
9/1/85
TABLE I—CLEARANCES (In Inches)
Sizes DOWNFLOW (In Alcove or Closet)
Sides—Single-Wall Vent
Type-B1 Double-Wail Vent 0
Back 0 Top Front*—Single-Wall Vent 6
Type-B1 Double-Wall Vent
Vent—Single-Wail
Type-BI Double Wall 1
HORIZONTAL (In Alcove)
SidesT 0 Back Top—Single-Wall Vent
Type-B1 Double-Wall Vent 0 Front* Vent—Single-Wall
Type-BI Double-Wail 1 1
HORIZONTAL (In Closet)
Sides! 1 1 . Back 3 3
Top—Single-Wall Vent 2
Type-BI Double-Wall Vent 2 2
Front*—Single-Wall Vent 6 6
Type-BI Double-Wall Vent
Vent—Single-Wall 6 6
Type-BI Double-Wall 1 1
♦Provide a 30-in. service clearance in front of the furnace, t Indicates supply or return sides when furnace is in the horizontal
position.
040 and 055
3 “ 3 6 6
0 0
18 18
6 6
3 3
075 thrullS
A83215
Figure 2—Horizontal
0 0 0 1 6
1 0
2
The design of the downflow/horizontal gas-fired furnace is A.G.A. certified for natural and LP(propane) gas and for installation on combustible fiooring (with optional fioor
base), in alcoves, attics, crawl spaces, basements, closets, or utility rooms. The design of this furnace line is not A.G.A. certified for installation in mobile homes, recreation vehi cles, or outdoors.
BDP Company
TABLE III—RATINGS AND PERFORMANCE*
SIZE Input
Buth*
024040 024055 67,000 036055 036075 90,000 048075 90,000 048095 114,000 95,000 55—85 060095 114,000 060115 137,000
*The-above gas inputs are certified for altitudes to 2000 ft. For elevations above 2000 ft, tDetermined by U.S. Government tests. tTentative rating.
48,000 39,000 50—80 0.10 610 67,000 56,000 35—65
Capacity
Buthtt
56,000 75,000 45—75 0.15
75,000 95,000
115,000 45—75 0.20
Temperature
Rise
Range
40—70
40—70 55—85
External Static
Installation comprises the following:
*1. Inspection
*11. Location, Ventilation, and Air for Combustion
*III. Gas Piping
*IV. Venting

V. Supply-Air Plenum Installation (Downflow)

VI. Attic Installation
VII. Crawl Space Installation
VIII. Filter Arrangement
IX. Sequence of Operation
Heating Cooling
Ft=/Min External Static
Pressure
0.12
0.12
0.15 1240
0.20
0.20
*To perform these sections (or installation steps), refer to the appropriate sections of “Procedures for Induced-Com bustion Gas-Fired Furnaces” booklet packaged with this unit.
For accessory installation details, refer to applicable instal lation literature.
V. SUPPLY-AIR PLENUM INSTALLATION (DOWNFLOW) A. installation on a concrete slab
1. See Figure 3 for dimensions and location of supply-air
2. Construct hole in floor per dimensions in Figure 4 and
X. Electrical Connections
XI. Startup and Adjustment
XII. Care and Maintenance
3. Place plenum and furnace as shown in Figure 5.

B. Installation on a combustible floor

1. Read Installation Instructions packaged with combus
TABLE II—DIMENSIONS (In Inches)
Size 024040 024055 036055 14-3/1 6 036075 17-1/2 048075 17-1/2 1 5-7/8 048095 17-1/2 1 5-7/8 060095 21 19-3/8 060115 24-1/2 22-13/16
835t
1080
960t
1248 1350 1037 0.5 2010 1/2 P$C 208
reduce.input 4% for each 1000 ft above sea level.
A D
1 4-3/1 6
14-3/1 6 12-9/16
FCTMin
Pressure
0.5 Ш
0.5
0.5
0.5
0.5
0.5 ■ 1590
0.5 1929
12-9/16 12-9/16
1 5-7/8
890t
1157
1230t
1553
E Vent Conn 12-11/16 4 12-11/16 12-11/16
16 16 16
19-1/2
23
Motor
HP & Type
1/5 Páó 1/5 PSC 140 1/3 PSC 142 1/3 PSC 160 1/2 PSC 163 1/2 PSC 1/2 PSC 188
Shipping
Weight
<Lbs)
130
178
opening in furnace bottom.
Table IV.
tible floor base.
4 4 4 4
4 4
5
HOLE IN
FLOOR
Ì
Figure 4—Floor Opening for Concrete Slab
TABLE IV—OPENING DIMENSIONS
Furnace Casing
Width
14-3/16
17-1/2 16-7/16
21 1 9-7/8
24-1/2
*These dimensions apply when a Model 518A Evaporator Coil casing
is to be installed.
A
13-1/8
23-7/16
Heat-Oniy
19-5/8 19-5/8 19-5/8 19-5/8
В
Heat/Cooi*
20-15/16 20-15/16 20-15/16 20-15/16
—2-
Figure 7—Furnace, Plenum, and
Base Installed on a Combustible Floor
2. Cut and frame hole in floor per dimensions in Table I of Installation Instructions packaged with combustible
floor base. If this requires cutting of a floor joist, tie ends of cut joist into adjacent joists so that proper floor support will be maintained.
3. Assemble and install combustible floor base per
instructions packaged with base.
4. When completed, combustible floor base, plenum, and furnace (or coil casing when used) should be installed as shown in Figure 7.
VI. HORIZONTAL ATTIC INSTALLATION
The 376B Furnace can be installed horizontally on either the LH or RH side. A typical attic installation is shown in Fig ure 8.
NOTE: The National Fuel Gas Code requires the use of a
type B1 vent in an attic or concealed space.
A. Construct a working platform.
1. Place working platform in location where all required
furnace clearances are obteunable. See Table I.
2. Use materials in platform that will support installer
and service persons.
3. Secure platform to building j oists.
LINE CONTACT ONLY PERMISSIBLE BETWEEN LINES FORMED BY INTERSECTIONS OF THE TOP AND TWO SIDES OF THE FURNACE JACKET AND BUILDING JOISTS, STUDS OR FRAMING.'

B. Install furnace

1. Position furnace in desired location.
2. Connect gas supply pipe. See Figure 8 for typical pip ing entry. It is important to install a sediment trap in the gas pipe riser.
3. Cormect supply- and return-air ducts.
a. Install field-supplied duct flanges as shown in Fig
ure 9.
b. Using appropriate fasteners for type of supply-air
duct being used, connect duct to furnace.
c. Install field-supplied filter retainers as indicated in
Figure 10 and Table V before connecting retum-air duct to furnace.
NOTE: For ease of servicing, a return-air filter can be
installed in a common retum-air grille. The air velocity rat ing must not exceed 300 ft/min for disposable filters. The air velocity through permanent-type filters shall not exceed the manufacturer’s recommendation.
d. Using appropriate fasteners for type of duct being
used, connect retum-air duct to furnace.
4. Install 24-x24-in. sheet metal shield on platform in front of louvered control panel, as shown in Figure 8.

VII. CRAWL SPACE INSTALLATION

The 376B Furnace can be installed horizontally with either the LH or RH side up. In a crawl space, the furnace can
either be hung from the floor joist or installed on suitable blocks or pad. The furnace can be suspended from each cor ner by hanger bolts (Four each 3/8-in. all-thread rod) cut to desired length, 1 x 3/8 flat washer, 3/8 lockwasher, and 3/8 nut. Dimples are provided for hole locations. See Figure 3.
NOTE: Use Type B1 vent in a concealed space.
The crawl space installation is very similar to the attic; therefore, refer to Division VI, Section B, steps 1, 2, and 3. The installation of a sheet metal shield in front of the lou vered control panel is covered in step 4. For a crawl space installation, this same sheet metal shield must be installed
SEDIMENT TRAP'
A82178
Figure 8—Typical Attic Installation
—3-
above the louvered control panel. Extend the sheet metal shield over the furnace top far enough to cover the gas pipe entry hole.

VIII. FILTER ARRANGEMENT

The two factory-supplied filters are shipped in the blower
compartment. After the return-air duct has been connected to the furnace, install the filters in a V-formation inside the return-air plenum. See Figure 10 and Table V for horizontal applications. See Figure 11 for downflow applications.
TABLE V—FILTER RETAINER
Furnace Casing Width
1 4-3/1 6
17-1/2
21
24-1/2
0
15-3/16
14-1/2
13-9/16
12-1/4
Figure 11—Position of Filters
IX. SEQUENCE OF OPERATION
Using the schematic wiring diagram, Figure 12, trace the sequence of operation for the heating cycle is as follows;
1. When the blower door is in place, 120 volts is supplied through blower door interlock switch 9G. Transformer lA is energized, supplying 24 volts to heating-blower relay coil 2E, which opens normally closed blower relay contacts 2E in the low-speed circuit of blower motor 3D.
lA-Transformer, 120-VAC/24-VAC 2D-Relay, Inducer Motor DPST-N. O. 2E-Relay, Heating Blower (HFR) SPST-N. C. 2F-Relay, Cooling Blower (CFR) DPDT
3A-Motor, Inducer 3D-Motor, Blower 4A-Capacitor, Run 5F-Valve, Gas (Redundant) 6C3-Lockout Module (When Used) 6F-Generator, Spark (Solid-State) 6H-Switch, Pilot-Flame Sensing SPOT 7H1-Switch, Limit SPST-N. C.
7H2-Switch, Draft Safeguard (SPST-N. C.) Manual-Reset 7H3-Switch, Auxiliary Limit (SPST-N. C.) Manual-Reset (When
Used)
7P-Pressure Switch-N.O. 7V-Switch, Flow Sensing SPOT
9G-Switch, Blower Door Interlock SPST-N. O.
10B1-Connector, Edge (Furnace Control Board) 10B2-Connector, Edge (Inducer Control Board-7 CKT) 10B3-Connector, Edge (Inducer Control Board-2 CKT)
10B4-Connector, Pilot 10B5-Factory Test Points 10B6-Connector, Blower Motor 11B-Fuse, In Line 2 Amp (When Used) 11C-Link, Fusible (Overtemperature)3 Required 11E-Ground, Equipment TP-1-Test Point
Factory Wiring, 120-VAC Factory Wiring, 24-VAC Conductors on 6C1 (Furnace Control Board) Conductors on 6C2 (Inducer Control Board) Screw Terminal for Field Wiring
0
1/4-inch Quick-Connect Terminals
LEGEND
-4—
2. The wall thermostat “calls for heat,” closing the R and W circuit. This closed circuit supplies power to the 24­volt safety circuit containing Hmit switch 7H1, fusible link lie, manual-reset draft-safeguard switch 7H2, and manual reset auxiliary switch 7H3.
3. Simultaneously, the pick coil of gas valve 5F, spark generator 6F, and inducer-motor relay coil 2D are ener gized. Inducer-motor relay contacts 2D in the 120-volt circuit close, starting inducer blower motor 3A. Also, another set of contacts in inducer-motor relay 2D close in the 24-volt circuit, and lock in inducer-motor relay coil 2D. The coil is locked in until the R and W circuit or safety circuit opens.
4. When the pick coil of gas valve 5F is .energized, gas flows to the pilot. The pilot gas is ignited by a spark produced by spark generator 6F. Simultaneously, inducer motor 3A comes up to speed, actuating flow
sensing switch 7V, energizing the hold coil of gas valve
5F. The pick coil of gas valve 5F and spark generator 6F are deenergized when the contacts of pilot-flame sensing switch 6H move from the normally closed posi tion, breaking the circuit to the pick coil and spark gen erator. In approximately 50 to 60 seconds, the nor mally open pilot-flame sensing contacts close, making the circuit to the MGV (Main Operator) of gas valve 5F. Gas valve 5F opens in approximately 10 seconds, allowing gas flow to the main burners, which are
ignited by pilot 6H. Simultaneously, time-delay circuit
IIL in the blower control center is energized. Approxi
mately 50 seconds after gas valve 5F opens, heating relay coil 2E is deenergized, which closes the 120-volt contacts of heating relay 2E, starting blower motor 3D on its heating speed.
5. When the thermostat is satisfied, the circuit between R and W is broken, deenergizing gas valve 5F, inducer
motor relay 2D, and the solid-state time-delay circuit
on the printed-circuit board. The gas flow stops imme
diately to the pilot and main burners. After approxi mately 105 seconds, heat relay 2E is energized and blower motor 3D stops.
NOTE: After a brief interruption of either electric or gas sup
ply, the furnace will not resume operation until the contacts of pilot-flame sensing switch 6H move from the normally open to the normally closed position.
Cooling Cycle
1. The wall thermostat “calls for cooling.”
2. The R, G, and Y circuits are energized. Simultaneously, the R-and-Y circuit starts the outdoor condensing unit, and the R-and-G circuit energizes cooling relay coil 2F, which closes normally open contacts 2F, energizing the cooling speed winding of motor 3D and opening the
normally closed contacts of cooling relay 2F.
X. ELECTRICAL CONNECTIONS A. Line-Voltage Wiring
IMPORTANT: Before proceeding with the electrical con nections, make certain that voltage, frequency, and phase correspond to that specified on the unit rating plate. Also, check to be sure that the service provided by the utility is sufficient to handle the additional load imposed by this equipment. Refer to the unit rating plate for equipment elec trical requirements.
in accordance with the National Electrical Code and any local codes or ordinances that might apply.
Use a separate fused branch electrical circuit containing a properly sized fuse or HACR-type circuit breaker for this furnace. A disconnecting means must be located within sight of, and readily accessible to, the furnace. The blower door switch may be acceptable in some areas as a discon
necting means.
If fine-voltage wiring to the unit is encased in a nonmetalfic
sheath, connect the incoming ground wire to the grounding wire inside the furnace J-box. If metallic conduit is used, it will serve as the ground.
B. Low-Voltage Wiring
Make field low-voltage connections at the low-voltage termi nal strip. See Figure 15.
NOTE: When the furnace is instedled in the horizontal posi
tion with RH discharge air, low-voltage wire connections can be made easier by removing the two control box mount ing screws and letting the control box turn so that the low­voltage screw terminals are visible. Be sure to reinstall the control box after the connections are made.
NOTE: Use AWG No. 18 “color-coded” copper thermostat
wire for lengths up to 100 ft. Above 100 ft, use AWG No. 16 wire.
IMPORTANT: The thermostat heat anticipation must be set
to match the amp draw of the gas valve and electrical com ponents in the R-W circuit. Accurate amp draw readings can be obtained at thermostat subbase terminals R & W. Figure 13 illustrates an easy method of obtaining the actual amp draw. The amp reading should be taken after the blower motor has started.
The room thermostat should be located where it wfll be in
the natureJ circulation path of room air. Avoid locations where the thermostat would be exposed to cold-air infiltra tion, drafts from windows, doors, or other openings leading to the outside, or exposed to air currents from warm- or cold-air registers; or to exposure where the natural circula tion of the air is cut off—such as behind doors, above or below mantels, shelves, etc.
The thermostat should not be exposed to heat from nearby fireplaces, radios, televisions, lamps, or rays from the sun. Nor should the thermostat be mounted on a wall containing pipes or warm-air ducts, or a flue or vent that could affect its operation and prevent it from properly controlling the
See Figure 15 for wiring diagram showing the proper field
high- and low-voltage wiring. Make all electrical connections
Figure 13—Amp Draw Check With Ammeter
—5—
room temperature. Any hole in the plaster or panel through which the wires pass from the thermostat should be ade quately sealed with suitable material to prevent drafts from affecting the thermostat.

C. Blower Control Center

Each furnace features a blower control center. This will aid the installer and serviceperson when installing and servic ing the unit. A low-voltage terminal board is marked for easy connection of field wiring. See Figure 14.

XI. STARTUP AND ADJUSTMENT

In addition to the following information, refer to “Proce dures for Induced-Combustion Gas-Fired Furnaces” pack
aged with the unit.
NOTE: The furnace blower door must be in place to complete
the 115-volt circuit to the furnace.
A. Adjustment of Blower Speed
To change motor speed taps, remove the motor tap lead. See Table VI. and relocate it on the desired terminal on the plug-in terminal block/speed selector located on the blower.
TABLE VI—SPEED SELECTOR
Speed
Common Hi Med-Hi Med-Low Low
Tap No.
C
1
2
3
4
The gas service pressure must not exceed 14 in. wc (8.1 ounces) for natural gas.
NOTE; The gas valve regulator has been factory-set at 3.5
in. wc for natural gas. Refer to “Procedure for Induced­Combustion Gas-Fired Furnaces” for readjusting when checking input.
yii
- Ì-
Figure 14—Blower Control Center

B. Automatic Gas Control Valve

These units are equipped with an automatic gas control valve. If not already checked when lighting the main burner, check the proper operation of this valve by moving the room thermostat pointer above and below room temper ature and observing that the main burners light on “call for heat” (there will be a time delay) and go off when the pointer is moving below room temperature setting.
NOTE: For ease of adjusting the pilot flame, disconnect and
tape one power lead at the main gas valve. Disconnect ter minal No. 1. This will pervent main burner ignition and allow time to adjust the pilot. Reconnect the power lead after adjustment.
XII. CARE AND MAINTENANCE
- FIELD LOW-VOLTAGE WIRING
Figure 15—Heating and Cooling Application Wiring Diagram a7S46i
—6—
PILOT TUBE REGULATOR
CONN
PILOT J.
ADJUSTMENT
X- .- t.
Figure 16—Redundant Automatic Gas
Control Valve
ADJUSTMENT

-, \:

PRESSURE
TAP
/
For continuing high performance, and to minimize possible equipment failure, it is essential that periodic maintenance be performed on this equipment. Consult your local Dealer as to the proper frequency of maintenance and the availabil
ity of a maintenance contract. The abihty to properly perform maintenance on this equip
ment requires certain mechanical skills and tools. If you do not possess these, contact your Dealer for maintenance.
The niinimum maintenance that should be performed on this equipment is as follows:
1. Check and clean or replace air filter each month or as required.
2. Check blower motor and wheel for cleanliness and lubri cation each heating and cooling season. Clean and lubricate as necessary.
3. Check electrical connections for tightness and controls for proper operation each heating season. Service as
necessary.
c. Reinstall filters with cross-hatch binding facing
blower.

B. Blower Motor and Wheel

1. Remove blower access panel.
2. Remove vent pipe enclosure.
3. Disconnect vent pipe and remove short piece of pipe from furnace.
4. Disconnect wires from auxiliary limit on blower housing.
NOTE: For ease of blower removal, it may be necessary to
remove the control box on some sizes.
5. Remove blower assembly from furnace.
6. Remove motor from blower housing.
7. Lubricate motor using good grade of SAE 20 nondeter gent motor oil. Put one teaspoon, 5cc, 3/16 oz., or 16 to 25 drops in each oil port.
8. Remove blower wheel from housing and clean by using vacuum with soft brush attachment. Care must be exercised not to disturb balance weights (clips) on blower wheel vanes.
9. Reassemble furnace by reversing above procedures.
When a more detailed servicing procedure is required, see the furnace Service Manual available from yom Dealer or Distributor.
C. Cleaning Heat Exchanger
If it becomes necessary to clean the heat exchanger because of carbon deposits, soot, etc., proceed as follows:
NOTE: Deposits of soot and carbon indicate a problem exists
and needs correcting. Corrective action must be taken to
correct the problem.
1. Turn off gas and power to furnace.
2. Remove control and blower access doors.
3. Remove vent pipe enclosure and disconnect vent pipe from relief box.
4. Remove four screws that secure relief box to blower shelf.
5. Disconnect two wires from safeguard switch.
6. Disconnect wire harness edge connector from side of inducer control box.

A. Air Filter

Each furnace accommodates two filters which are installed in the return-air duct. See Figures 10 and 11.
To clean or replace the filters, proceed as follows:
1. Disconnect electriceil power before removing access panel.
2. Remove upper access panel.
3. Reach up behind top plate, tilt filters toward center of retum-air plenum, remove filters, and replace or clean as needed.
4. Furnaces are equipped with permanent, washable fil ters. Clean those filters as follows:
a. Clean with tap water.
b. Rinse and let dry. No oiling or coating of filters is
required.
-I’i
A77007
Figure 17—Dual Blower With Left-Hand
Housing and Wheel Removed.
—7—
7. Remove eight screws that secure flue collector box to center panel. Use care not to damage sealant.
8. Remove complete inducer assembly from furnace, exposing flue openings.
9. Remove flue choke.
10. Using field-provided small wire brush, steel spring cable, reversible electric drill, and vacuum cleaner; clean cells.
a. Assemble wire brush and steel spring cable.
(1.) Use 4 feet of 1/4-in. diameter high-grade steel
spring cable (commonly known as drain cleanout or Roto-Rooter cable).
(2.) Use 1/4-in. diameter wire brush (commonly
known as 25-caliber rifle cleaning brush).
NOTE: The items called for in steps 1 and 2 can be pur
chased at a local hardware store.
(3.) Insert twisted wire end of brush into end of
spring cable, and crimp tight with crimping tool or strike with baU-peen hammer. Tightness is
very important.
(4.) Remove metal screw fitting from wire brush to
allow insertion into cable.
b. Clean each heat exchanger cell.
(1.) Attach variable-speed reversible drill to end of
spring cable (end opposite brush).
(2.) Insert brush end of cable into upper opening of
cell and slowly rotate with drill. Do not force cable. Gradually insert at least 3 feet of cable into two upper passes of cell. See Figure 18.
(3.) Work cable in and out of cell three of four times
to obtain sufficient cleaning. Do not pull cable with great force. Reverse drill and gradually work cable out.
(4.) Remove burner assembly and flame radiators.
(Identify gas valve leads.)
(5.) Insert brush end of cable in lower opening of
cell, and proceed to clean two lower passes of cell in same manner as two upper passes.
(6.) Repeat the foregoing procedures until each cell
in furnace has been cleaned.
(7.) Using vacuum cleaner, remove residue from
each cell.
(8.) Using vacuum cleaner with soft brush attach
ment, clean burner assembly.
(9.) Reinstall flame radiators and burner assembly.
Care must be exercised to center the flame radi ators in the cell openings. Refer to furnace wir ing diagram when reconnecting gas valve leads.
11. After cleaning flue openings, check sealant on flue col lector to ensure that it has not been damaged. If new sealant is needed, contact your Distributor.
12. Reinstall flue choke. Be sure all screws are in place and tight.
13. Clean and replace flue collector assembly, making sure all eight screws are secure.
14. Replace four screws that secure the rehef box to blower shelf.
15. Reconnect two wires to safeguard switch.
16. Reconnect wire harness edge connector to side of
inducer control box.
17. Reconnect vent pipe to relief box, reinstall pipe
enclosure.
18. Replace blower door only.
19. Turn on power and gas.
20. Set thermostat and check furnace for proper operation.
21. Check for gas leaks.
22. Replace control door.

D. Pilot

Check the pilot and clean if necessary at the beginning of
each heating season. The pilot flame should be high enough for proper impingement of the safety element and to light the burners. Remove the accumulation of soot and carbon from the safety element or sensing probe. See Figure 19 and check electrode position.
E. Electrica! Controls and Wiring
NOTE: There may be more than one electrical supply to unit.
With power disconnected to unit, check all electrical connec tions for tightness. Tighten aU screws on electrical connec tions. If any smoky or burned connections are noticed, dis
assemble the connection, clean all parts and strip wire, and reassemble properly and securely. Electrical controls are dif ficult to check without proper instrumentation; therefore, reconnect electrical power to unit and observe unit through one complete operating cycle. If there are any discrepancies in the operating cycle, contact your Dealer and request service.
Figure 18—Cleaning Heat Exchanger Cell
A82181
—8—
^_T
16
Figure 19—Position of Electrode to Pilot
Loading...