Bryant 376B User Manual

i nstallation, operatron, and maintenance instructions
HIGH-EFFICIENCY
DOWNFLOW/HORIZONTAL INDUCED-COMBUSTION FURNACE
376B
Series A
Sizes 040
thrullS
NOTE: Remove the Energy Guide tag from the furpace
when the installation is complete.
NOTE; This is a highly specialized piece of equipment.
Before beginning the installation, READ THESE
INSTRUCTIONS CAREFULLY AND COMPLETELY.

INTRODUCTION

Before installing the furnace, refer to “Procedure for Induced-Combustion Gas-Fired Furnaces” (packaged with
the equipment) for information concerning combustion, venting, piping, and other standard installation practices. Further reference is made to the current edition of the National Fuel Gas Code NFPA No. 54-1984/ANSI Z223.1-
1984. The induced-combustion vent system of this furnace is
designed to operate at zero or negative pressure at the vent connector outlet. This furnace, therefore, complies with the National Fuel Gas Code (NFPA No. 54-1984/ANSI Z223.1-
1984), Part 7.14.3.b. This furnace is also hsted by A.G.A. for use with the type B1 gas vent, as described in the National
Fuel Gas Code, Part 7.3.2. Each furnace is shipped from the factory completely assem
bled with multispeed direct-drive blower and wired ready for indoor heating installation. All sizes feature a blower con trol center with easy-to-read low-voltage terminal strip to ensure proper connections.
The output capacity and any representations of efficiency for this product are based on standard Department of Energy test procedures. The insteJled operation may vary, depending on installation, weather, or other factors.
Cancels; 39376DP5-A
40376DP5-B
9/1/85
TABLE I—CLEARANCES (In Inches)
Sizes DOWNFLOW (In Alcove or Closet)
Sides—Single-Wall Vent
Type-B1 Double-Wail Vent 0
Back 0 Top Front*—Single-Wall Vent 6
Type-B1 Double-Wall Vent
Vent—Single-Wail
Type-BI Double Wall 1
HORIZONTAL (In Alcove)
SidesT 0 Back Top—Single-Wall Vent
Type-B1 Double-Wall Vent 0 Front* Vent—Single-Wall
Type-BI Double-Wail 1 1
HORIZONTAL (In Closet)
Sides! 1 1 . Back 3 3
Top—Single-Wall Vent 2
Type-BI Double-Wall Vent 2 2
Front*—Single-Wall Vent 6 6
Type-BI Double-Wall Vent
Vent—Single-Wall 6 6
Type-BI Double-Wall 1 1
♦Provide a 30-in. service clearance in front of the furnace, t Indicates supply or return sides when furnace is in the horizontal
position.
040 and 055
3 “ 3 6 6
0 0
18 18
6 6
3 3
075 thrullS
A83215
Figure 2—Horizontal
0 0 0 1 6
1 0
2
The design of the downflow/horizontal gas-fired furnace is A.G.A. certified for natural and LP(propane) gas and for installation on combustible fiooring (with optional fioor
base), in alcoves, attics, crawl spaces, basements, closets, or utility rooms. The design of this furnace line is not A.G.A. certified for installation in mobile homes, recreation vehi cles, or outdoors.
BDP Company
TABLE III—RATINGS AND PERFORMANCE*
SIZE Input
Buth*
024040 024055 67,000 036055 036075 90,000 048075 90,000 048095 114,000 95,000 55—85 060095 114,000 060115 137,000
*The-above gas inputs are certified for altitudes to 2000 ft. For elevations above 2000 ft, tDetermined by U.S. Government tests. tTentative rating.
48,000 39,000 50—80 0.10 610 67,000 56,000 35—65
Capacity
Buthtt
56,000 75,000 45—75 0.15
75,000 95,000
115,000 45—75 0.20
Temperature
Rise
Range
40—70
40—70 55—85
External Static
Installation comprises the following:
*1. Inspection
*11. Location, Ventilation, and Air for Combustion
*III. Gas Piping
*IV. Venting

V. Supply-Air Plenum Installation (Downflow)

VI. Attic Installation
VII. Crawl Space Installation
VIII. Filter Arrangement
IX. Sequence of Operation
Heating Cooling
Ft=/Min External Static
Pressure
0.12
0.12
0.15 1240
0.20
0.20
*To perform these sections (or installation steps), refer to the appropriate sections of “Procedures for Induced-Com bustion Gas-Fired Furnaces” booklet packaged with this unit.
For accessory installation details, refer to applicable instal lation literature.
V. SUPPLY-AIR PLENUM INSTALLATION (DOWNFLOW) A. installation on a concrete slab
1. See Figure 3 for dimensions and location of supply-air
2. Construct hole in floor per dimensions in Figure 4 and
X. Electrical Connections
XI. Startup and Adjustment
XII. Care and Maintenance
3. Place plenum and furnace as shown in Figure 5.

B. Installation on a combustible floor

1. Read Installation Instructions packaged with combus
TABLE II—DIMENSIONS (In Inches)
Size 024040 024055 036055 14-3/1 6 036075 17-1/2 048075 17-1/2 1 5-7/8 048095 17-1/2 1 5-7/8 060095 21 19-3/8 060115 24-1/2 22-13/16
835t
1080
960t
1248 1350 1037 0.5 2010 1/2 P$C 208
reduce.input 4% for each 1000 ft above sea level.
A D
1 4-3/1 6
14-3/1 6 12-9/16
FCTMin
Pressure
0.5 Ш
0.5
0.5
0.5
0.5
0.5 ■ 1590
0.5 1929
12-9/16 12-9/16
1 5-7/8
890t
1157
1230t
1553
E Vent Conn 12-11/16 4 12-11/16 12-11/16
16 16 16
19-1/2
23
Motor
HP & Type
1/5 Páó 1/5 PSC 140 1/3 PSC 142 1/3 PSC 160 1/2 PSC 163 1/2 PSC 1/2 PSC 188
Shipping
Weight
<Lbs)
130
178
opening in furnace bottom.
Table IV.
tible floor base.
4 4 4 4
4 4
5
HOLE IN
FLOOR
Ì
Figure 4—Floor Opening for Concrete Slab
TABLE IV—OPENING DIMENSIONS
Furnace Casing
Width
14-3/16
17-1/2 16-7/16
21 1 9-7/8
24-1/2
*These dimensions apply when a Model 518A Evaporator Coil casing
is to be installed.
A
13-1/8
23-7/16
Heat-Oniy
19-5/8 19-5/8 19-5/8 19-5/8
В
Heat/Cooi*
20-15/16 20-15/16 20-15/16 20-15/16
—2-
Figure 7—Furnace, Plenum, and
Base Installed on a Combustible Floor
2. Cut and frame hole in floor per dimensions in Table I of Installation Instructions packaged with combustible
floor base. If this requires cutting of a floor joist, tie ends of cut joist into adjacent joists so that proper floor support will be maintained.
3. Assemble and install combustible floor base per
instructions packaged with base.
4. When completed, combustible floor base, plenum, and furnace (or coil casing when used) should be installed as shown in Figure 7.
VI. HORIZONTAL ATTIC INSTALLATION
The 376B Furnace can be installed horizontally on either the LH or RH side. A typical attic installation is shown in Fig ure 8.
NOTE: The National Fuel Gas Code requires the use of a
type B1 vent in an attic or concealed space.
A. Construct a working platform.
1. Place working platform in location where all required
furnace clearances are obteunable. See Table I.
2. Use materials in platform that will support installer
and service persons.
3. Secure platform to building j oists.
LINE CONTACT ONLY PERMISSIBLE BETWEEN LINES FORMED BY INTERSECTIONS OF THE TOP AND TWO SIDES OF THE FURNACE JACKET AND BUILDING JOISTS, STUDS OR FRAMING.'

B. Install furnace

1. Position furnace in desired location.
2. Connect gas supply pipe. See Figure 8 for typical pip ing entry. It is important to install a sediment trap in the gas pipe riser.
3. Cormect supply- and return-air ducts.
a. Install field-supplied duct flanges as shown in Fig
ure 9.
b. Using appropriate fasteners for type of supply-air
duct being used, connect duct to furnace.
c. Install field-supplied filter retainers as indicated in
Figure 10 and Table V before connecting retum-air duct to furnace.
NOTE: For ease of servicing, a return-air filter can be
installed in a common retum-air grille. The air velocity rat ing must not exceed 300 ft/min for disposable filters. The air velocity through permanent-type filters shall not exceed the manufacturer’s recommendation.
d. Using appropriate fasteners for type of duct being
used, connect retum-air duct to furnace.
4. Install 24-x24-in. sheet metal shield on platform in front of louvered control panel, as shown in Figure 8.

VII. CRAWL SPACE INSTALLATION

The 376B Furnace can be installed horizontally with either the LH or RH side up. In a crawl space, the furnace can
either be hung from the floor joist or installed on suitable blocks or pad. The furnace can be suspended from each cor ner by hanger bolts (Four each 3/8-in. all-thread rod) cut to desired length, 1 x 3/8 flat washer, 3/8 lockwasher, and 3/8 nut. Dimples are provided for hole locations. See Figure 3.
NOTE: Use Type B1 vent in a concealed space.
The crawl space installation is very similar to the attic; therefore, refer to Division VI, Section B, steps 1, 2, and 3. The installation of a sheet metal shield in front of the lou vered control panel is covered in step 4. For a crawl space installation, this same sheet metal shield must be installed
SEDIMENT TRAP'
A82178
Figure 8—Typical Attic Installation
—3-
Loading...
+ 5 hidden pages