Bryant 355MAV User Manual

service and
355MAV
maintenance procedures
DELUXE 4-WAY MULTIPOISE VARIABLE-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE
A93040
NOTE: Read the entire instruction manual before starting the installation.
This symbol indicates a change since the last issue.
WARNING: ELECTRICAL SHOCK, FIRE, OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death, or property damage. Improper servicing could result in dangerous operation, serious injury, death, or property damage.
- Before servicing, disconnect all electrical power to furnace.
- When servicing controls, label all wires prior to disconnecting. Reconnect wires correctly.
- Verify proper operation after servicing.
Series I
Cancels: SP05-57 SP05-64
9-04
WARNING: FIRE OR EXPLOSION HAZARD
Failure to follow this warning could cause corrosion of heat exchanger, fire, personal injury, or death. Never store anything on, near, or in contact with the furnace, such as:
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum cleaners, or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning compounds, plastic or plastic containers, gasoline, kerosene, cigarette lighter fluid, dry cleaning fluids, or other volatile fluids.
3. Paint thinners and other painting compounds, paper bags, or other paper products.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS.....................................................1
GENERAL......................................................................................2
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS........2
CARE AND MAINTENANCE.....................................................3
Cleaning and/or Replacing Air Filter.......................................3
Blower Motor and Wheel Maintenance...................................3
Cleaning Burners ......................................................................5
Cleaning Heat Exchangers........................................................5
Flushing Collector Box and Drainage
System.......................................................................................6
Servicing Hot Surface Igniter...................................................8
Electrical Controls and Wiring.................................................8
Checking Heat Tape Operation
(If Applicable)...........................................................................9
Winterizing................................................................................9
WIRING DIAGRAM...................................................................10
TROUBLESHOOTING ...............................................................10
WARNING: ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in possible damage to this equipment, serious personal injury, or death. The ability to properly perform maintenance on this equipment requires certain expertise, mechanical skills, tools, and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment other than those procedures recommended in the User’s Manual.
—1—
SAFETY CONSIDERATIONS
Recognize safety information. This is the safety-alert symbol When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified service agency personnel should install, repair, or service heating equip­ment.
.
These instructions are written as if the furnace is installed in an
GENERAL
upflow application. An upflow furnace application is where the blower is located below the combustion and controls section of the furnace, and conditioned air is discharged upward. Since this furnace can be installed in any of the 4 positions shown in Fig. 2, you must revise your orientation to component location accord­ingly.
AIRFLOW
UPFLOW
A98308
Fig. 1—Multipoise Furnace in Upflow Orientation
EFFICIENCY RATING CERTIFIED
ISO 9001:2000
CERTIFIED
REGISTERED
Untrained personnel can perform basic maintenance functions described in User’s Information Manual such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the unit and other safety precautions that may apply.
CAUTION: CUT HAZARD
Failure to follow this caution may result in personal injury. Be careful of sharp metal edges, etc. Use care and wear protective clothing, gloves, and safety glasses when removing parts.
Follow all safety codes including the National Fuel Gas Code (NFGC) NFPA 54-2002/ANSI Z223.1-2002 in the USA, CSA B149.1-00 National Standard of Canada, Natural Gas and Propane Installation Codes (NSCNGPIC) in Canada, and the Installation Standards, Warm Air Heating and Air Conditioning Systems (NFPA 90B) ANSI/NFPA 90B. Wear safety glasses and work gloves. Have a fire extinguisher available during start-up and adjustment procedures and service calls.
HORIZONTAL
RIGHT
AIRFLOW
HORIZONTAL
LEFT
DOWNFLOW
AIRFLOW
Fig. 2—Multipoise Orientation
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
CAUTION: UNIT DAMAGE HAZARD
Failure to follow this caution may damage furnace
components.
Electrostatic discharge can affect electronic components.
Take precautions during furnace installation and servic-
ing to protect the furnace electronic control. Precautions
will prevent electrostatic discharges from personnel and
hand tools which are held during the procedure. These
precautions will help to avoid exposing the control to
electrostatic discharge by putting the furnace, the control,
and the person at the same electrostatic potential.
1. Disconnect all power to the furnace. DO NOT TOUCH
THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch a clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a person’s hand during grounding will be satisfactorily discharged.
3. After touching the chassis, you may proceed to service the control or connecting wires as long as you do nothing that recharges your body with static electricity (for example; DO NOT move or shuffle your feet, DO NOT touch un­grounded objects, etc.).
4. If you touch ungrounded objects (recharge your body with static electricity), firmly touch furnace again before touch­ing control or wires.
5. Use this procedure for installed and uninstalled (un­grounded) furnaces.
6. Before removing a new control from its container, dis­charge your body’s electrostatic charge to ground to protect the control from damage. If the control is to be installed in a furnace, follow items 1 through 5 before bringing the control or yourself into contact with the furnace. Put all used AND new controls into containers before touching ungrounded objects.
AIRFLOW
A93041
—2—
WASHABLE FILTER
FILTER SUPPORT
FILTER RETAINER
WASHABLE FILTER OR DISPOSABLE MEDIA FILTER IN FILTER CABINET
Fig. 3—Bottom Filter Arrangement
A00232
WASHABLE
FILTER
IN FURNACE
WASHABLE FILTER OR DISPOSABLE MEDIA FILTER IN FILTER CABINET
Fig. 4—Filter Installed for Side Inlet
FILTER RETAINER
A00233
7. An ESD service kit (available from commercial sources) may also be used to prevent ESD damage.
CARE AND MAINTENANCE
For continuing high performance and to minimize possible furnace failure, it is essential that maintenance be performed annually. Consult your local dealer for maintenance and maintenance contract availability.
WARNING: ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death. Turn off the gas and electrical supplies to the unit before performing any maintenance or service. Follow the oper­ating instructions on the label attached to the furnace.
The minimum maintenance that should be performed on this equipment is as follows:
1. Check and clean or replace air filter each month as needed.
2. Check blower motor and wheel for cleanliness annually.
3. Check electrical connections for tightness and controls for proper operation each heating season. Service as necessary.
4. Check for proper condensate drainage. Clean as necessary.
5. Check for blockages in combustion-air and vent pipes annually.
6. Check burners for cleanliness annually.
I. CLEANING AND/OR REPLACING AIR FILTER
The air filter arrangement may vary depending on the application or orientation.
WARNING: FIRE, CARBON MONOXIDE AND POISONING HAZARD
Failure to follow this warning could result in fire, personal injury, or death. Never operate unit without a filter or with the blower access panel removed. Dust and lint on internal parts in furnace can cause a loss of efficiency.
NOTE: If the filter has an airflow direction arrow, the arrow must point toward the blower.
To clean or replace filters, proceed as follows: If filter is installed in filter cabinet adjacent to furnace:
1. Turn off electrical supply to furnace.
2. Remove filter cabinet door.
3. Slide filter out of cabinet.
4. If equipped with permanent, washable filter, clean filter by spraying cold tap water through filter in opposite direction of airflow. Rinse filter and let dry. Oiling or coating of the filter is not recommended.
5. If equipped with factory specified disposable media filter, replace only with a factory specified media filter of the same size.
6. Slide filter into cabinet.
7. Replace filter cabinet door.
8. Turn on electrical supply to furnace.
If filter is installed in furnace blower compartment:
1. Turn off electrical supply to furnace.
2. Remove main furnace door and blower access panel.
3. Release filter retainer wire. (See Fig. 3 or 4.)
NOTE: Filters shown in Fig. 3 and 4 can be in furnace blower compartment or in filter cabinet, but not in both.
4. Slide filter out of furnace.
5. Furnaces are equipped with permanent, washable filter(s). Clean filter by spraying cold tap water through filter in opposite direction of airflow.
6. Rinse filter and let dry. Oiling or coating filter is not recommended.
7. Slide filter into furnace.
8. Recapture filter retaining wire.
9. Replace blower access panel and main furnace door.
II. BLOWER MOTOR AND WHEEL MAINTENANCE
To ensure long life, economy, and high efficiency, clean accumu­lated dirt and grease from blower wheel and motor annually.
The inducer and blower motors are pre-lubricated and require no additional lubrication. These motors can be identified by the absence of oil ports on each end of the motor.
—3—
PLUG
CAP
COLLECTOR BOX
DRAIN TUBE (BLUE
& WHITE STRIPED)
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
TUBE (GREEN)
INDUCER HOUSING
(MOLDED) DRAIN
TUBE (BEHIND
COLLECTOR BOX
DRAIN TUBE)
COLLECTOR BOX
DRAIN TUBE (BLUE)
FIELD-INSTALLED
FACTORY-SUPPLIED
DRAIN TUBE
COUPLING (LEFT
DRAIN OPTION)
FIELD-INSTALLED
FACTORY-SUPPLIED
DRAIN TUBE
FIELD-INSTALLED
FACTORY-SUPPLIED
1
2-IN. CPVC STREET
ELBOWS (2) FOR
LEFT DRAIN OPTION
FIELD-INSTALLED
FACTORY-SUPPLIED
COUPLING (RIGHT
CONDENSATE TRAP
DRAIN TUBE
DRAIN OPTION)
A01030
Fig. 5—Factory-Shipped Upflow Tube
Configuration
(Shown with Blower Access Panel Removed)
The following items should be performed by a qualified service technician.
Clean blower motor and wheel as follows:
1. Turn off electrical supply to furnace.
2. Remove main furnace door and blower access panel.
3. Disconnect wires. All factory wires can be left connected, but field thermostat
connections may need to be disconnected depending on their length and routing.
4. Position control box, transformer, and door switch assembly to right side of furnace casing.
5. If condensate trap is located in left- or right-hand side of furnace casing, proceed to item 6. Otherwise remove trap and tubing as described below (See Fig. 5.):
a. Disconnect field drain connection from condensate trap. b. Disconnect drain and relief port tubes from condensate
trap.
c. Remove condensate trap from blower shelf.
6. Remove screws securing blower assembly to blower shelf and slide blower assembly out of furnace. Detach ground wire and disconnect blower motor harness plugs from blower motor.
NOTE: Blower wheel is fragile. Use care.
7. Clean blower wheel and motor by using a vacuum with soft brush attachment. Be careful not to disturb balance weights (clips) on blower wheel vanes. Do not bend wheel or blades as balance will be affected.
8. If greasy residue is present on blower wheel, remove wheel from the blower housing and wash it with an appropriate degreaser. To remove wheel:
a. Mark blower wheel location on shaft before disassembly
to ensure proper reassembly.
b. Loosen setscrew holding blower wheel on motor shaft.
NOTE: Mark blower mounting arms and blower housing so each arm is positioned at the same hole location during reassembly.
c. Mark blower wheel orientation and cutoff plate location
to ensure proper reassembly.
d. Remove screws securing cutoff plate and remove cutoff
plate from housing.
e. Remove bolts holding motor mounts to blower housing
and slide motor and mounts out of housing. f. Remove blower wheel from housing. g. Clean wheel per instructions on degreaser cleaner. Do
not get degreaser in motor.
9. Reassemble motor and blower wheel by reversing items 8b through 8f. Ensure wheel is positioned for proper rotation. Be sure to attach ground wire and reconnect blower harness plugs to blower motor.
10. Reinstall blower assembly in furnace.
11. Reinstall condensate trap and tubing if previously removed. a. Reinstall condensate trap in hole in blower shelf.
b. Connect condensate trap drain tubes. See Fig. 5 or tubing
diagram on main furnace door for proper tube location. (1.) Connect 1 tube (blue or blue and white striped)
from collector box.
(2.) Connect 1 tube (violet or unmarked) from inducer
housing.
(3.) Connect 1 tube (relief port, green or pink) from
collector box.
c. Connect field drain to condensate trap.
NOTE: Ensure tubes are not kinked or pinched, as this will affect operation.
12. Reinstall control box, transformer, and door switch assem­bly on blower shelf.
13. Reconnect wires. a. Refer to furnace wiring diagram and connect thermosta
leads if previously disconnected. (See Fig. 17.)
WARNING: ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death. Blower access panel door switch opens 115-v power to furnace control. No component operation can occur. Caution must be taken when manually closing this switch for service purposes.
14. Turn on electrical supply. Manually close blower access panel door switch. Use a piece of tape to hold switch closed. Check for proper rotation and speed changes between heating and cooling by jumpering R to G and R to Y/Y2 on furnace control thermostat terminals. (See Fig. 12.)
15. If furnace is operating properly, release blower access panel door switch, replace blower access panel, and replace main furnace door.
—4—
III. CLEANING BURNERS
The following items should be performed by a qualified service technician. If the burners develop an accumulation of light dirt or dust, they may be cleaned by using the following procedure:
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
3. Remove burner box cover.
4. Using backup wrench, disconnect gas supply pipe from furnace gas valve.
CAUTION: ELECTRICAL SHOCK AND UNIT DAMAGE HAZARD
Failure to follow this caution may result in minor personal injury or furnace component damage. Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
5. Remove wires from gas valve. Note location for reassem­bly.
6. Remove burner box pressure tube from gas valve regulator fitting.
7. Remove screws that secure manifold to burner box. (See Fig. 6.)
NOTE: Do not remove burner box from cell panel.
8. Remove manifold, orifices, and gas valve as 1 assembly.
9. Remove screws attaching burner assembly in burner box.
10. Remove burner assembly from burner box.
NOTE: All burners are attached to burner bracket and can be removed as 1 assembly.
11. Clean burners with soft brush and vacuum.
12. Reinstall manifold, orifice, and gas valve assembly in burner box. Ensure manifold seal grommet is installed properly and burners fit over orifices.
13. Reconnect wires to gas valve. Refer to furnace wiring diagram for proper wire location.
CELL
PANEL
MANIFOLD MOUNTING SCREWS
14. Reinstall burner box pressure tube to gas valve regulator fitting.
15. Reinstall gas supply pipe to furnace gas control valve using backup wrench on gas valve to prevent rotation and improper orientation.
NOTE: Use propane gas resistant pipe dope to prevent gas leaks. DO NOT use Teflon tape.
WARNING: FIRE, EXPLOSION, UNIT DAMAGE HAZARD
Failure to follow this warning could result in property damage, personal injury, or death. Gas valve switch MUST be facing forward or tilted slightly.
16. Replace burner box cover.
17. Turn on gas and electrical supplies to furnace.
18. Check for gas leaks.
WARNING: FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in serious injury, death or property damage. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, per­sonal injury or loss of life.
19. Replace main furnace door.
IV. CLEANING HEAT EXCHANGERS
The following items should be performed by a qualified service technician.
A. Primary Heat Exchangers
If the heat exchangers get an accumulation of light dirt or dust on the inside, they may be cleaned by the following procedure:
NOTE: If the heat exchangers get a heavy accumulation of soot and carbon, both the primary and secondary heat exchangers should be replaced rather than trying to clean them thoroughly due to their intricate design. A build-up of soot and carbon indicates that a problem exists which needs to be corrected, such as improper adjustment of manifold pressure, insufficient or poor quality combustion air, improper vent termination, incorrect size or damaged manifold orifice(s), improper gas, or a restricted heat exchanger (primary or secondary). Action must be taken to correct the problem.
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
MANIFOLD
GAS VALVE REGULATOR FITTING
GAS CONTROL VALVE
Fig. 6—Burner Box Assembly
GASKET
A02312
—5—
CAUTION: ELECTRICAL SHOCK AND UNIT DAMAGE HAZARD
Failure to follow this caution may result in minor personal injury or furnace component damage. Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and hazardous operation.
3. Disconnect wires or connectors to flame rollout switch, gas valve, igniter, and flame sensor.
4. Disconnect combustion-air intake pipe from intake housing.
5. Remove the pressure switch tube from intake housing.
6. Remove screws attaching intake housing to burner box, and rotate intake housing away from burner box for removal.
7. Using backup wrench, disconnect gas supply pipe from furnace gas control valve.
8. Disconnect pressure tubing from gas valve.
9. Remove 2 screws attaching top filler panel and rotate upwards to gain access to screws attaching burner box to cell panel.
10. Remove screws attaching burner box to cell panel. (See Fig.
6.)
NOTE: Burner box cover, manifold, gas valve, and burner assembly should be removed as 1 assembly.
11. Clean heat exchanger openings with a vacuum and a soft brush. (See Fig. 7.)
NOTE: After cleaning, inspect the heat exchangers to ensure they are free of all foreign objects that may restrict flow of combustion products.
PRIMARY HX INLET OPENINGS
RTV
PAM
A93087
Fig. 8—Combustion-Air Intake Housing Gasket Repair
15. Turn on gas and electrical supplies to furnace.
16. Check furnace operation through 2 complete heat operating cycles. Look through sight glass in burner enclosure to check burners. Burner flames should be clear blue, almost transparent. (See Fig. 10.)
17. Check for gas leaks.
WARNING: FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in serious injury, death or property damage. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, per­sonal injury or loss of life.
Fig. 7—Cleaning Inlet Openings of Primary Heat
Exchangers
12. Reverse items 4 through 10 for reassembly.
CAUTION: UNIT MAY NOT OPERATE
Failure to attach this ground wire to an adequate casing ground may cause the furnace control to lock out. The ground wire from the gas valve MUST be attached to the burner box attachment screw.
NOTE: Be sure burner box gasket is installed between burner box and cell panel. (See Fig. 6.) If gasket is damaged, replace it.
NOTE: Inspect combustion-air intake housing. If foamed gasket was removed, check for any damage. If gasket is damaged in any way, it must be repaired. To repair, remove damaged gasket section, apply sealant releasing agent such as PAM cooking spray or equivalent (must not contain corn or canola oil, aromatic or halogenated hydrocarbons or inadequate seal may occur) to burner box and apply a small bead of G.E. RTV 162, G.E. RTV 6702, or Dow-Corning RTV 738 sealant to edge of combustion-air intake housing. (See Fig. 8.)
13. Refer to furnace wiring diagram and reconnect wires to flame rollout switch, gas valve, igniter, and flame sensor.
14. Reconnect pressure switch tubes to gas valve and intake housing. Refer to tube routing label on main furnace door for proper tube location. (See Fig. 9.) Be sure tubes are not kinked.
A96305
18. Replace main furnace door.
B. Secondary Heat Exchangers NOTE: The condensing side (inside) of the secondary heat
exchangers CANNOT be serviced or inspected. A small number of bottom outlet openings can be inspected by removing the inducer assembly. See Flushing Collector Box and Drainage System section for details on removing inducer assembly.
V. FLUSHING COLLECTOR BOX AND DRAINAGE SYSTEM
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
3. Disconnect inducer motor and pressure switch wires or connectors.
4. Disconnect pressure switch tubes.
5. Disconnect vent pipe from inducer housing outlet by loosening coupling clamp on inducer outlet.
6. Disconnect drain tube from inducer housing. (See Fig. 8.)
7. Remove inducer housing assembly by removing 4 bolts attaching assembly to cell panel.
8. Flush inside of collector box with water until discharge from condensate trap is clean and runs freely.
NOTE: Ensure the drain tube disconnected from the inducer housing is higher than the collector box opening or water will flow out tube.
9. Inspect inside area of collector box for any pieces of foreign materials and remove if present.
—6—
CAUTION: UNIT DAMAGE HAZARD
DO NOT use wire brush or other sharp object to inspect or dislodge materials in secondary heat exchangers as failure of the secondary heat exchanger may occur. Flush with water only.
10. Reassemble inducer assembly by reversing items 5-7. Tighten vent coupling clamp screw(s) to 15 in.-lb of torque.
NOTE: If seal between the inducer housing and the collector box is damaged in any way, it must be repaired. To repair, apply sealant releasing agent such as PAM cooking spray or equivalent (must not contain corn or canola oil, aromatic or halogenated hydrocarbons which can cause an inadequate seal to occur) to inducer housing. (See Fig. 11.) Apply a small bead of G.E. RTV 162, G.E. RTV 6702, or Dow-Corning RTV 738 sealant to groove in collector box.
11. Refer to furnace wiring diagram and reconnect wires to inducer motor and pressure switches or connectors.
12. Reconnect pressure tubes to pressure switches. See diagram on main furnace door for proper location of tubes. Be sure tubes are not kinked. (See Fig. 9.)
13. Turn on gas and electrical supplies to furnace.
14. Check furnace operation through 2 complete heat operating cycles. Check area below inducer housing, vent pipe, and condensate trap to ensure no condensate leaks occur. If leaks are found, correct the problem.
15. Check for gas leaks.
Furnace is shipped from factory in upflow configuration. Pressure tube and drain tube routing MUST match the diagrams below.
Condensate Trap; Factory Installed
in Blower Shelf
(Blower access panel removed)
COLLECTOR BOX TUBE
COLLECTOR BO X TUBE (GREE N)
INDUCER HOUSING (MOLDED) DRAIN TUBE
(BEHIND COLLECTOR BOX DRAIN TUBE)
COLLECTOR BOX DRAIN TUBE
FACTORY-SUPPLIED DR AIN TUBE
COUPLING (LEFT DRAIN OPTION)
Condensate Trap on
COLLECTOR BO X TUBE (GREEN)
BURNER EN C LO SURE PRESSU R E
REFERENCE TUBE ASSEMBLY
INDUCER HOUSING DRAIN TUBE (VIOLET)
(PINK )
(BLUE)
FIELD-INSTALLED
FIELD-INSTALLED FACTORY-
SUPPLIED DRAIN TUBE
LEFT Side
CAP
COLLECTOR BOX DRAIN TUBE
(BLUE & WHITE STRIPED)
COLLECTOR BOX
EXTENSION TUBE
CONDENSATE TRAP
Tube location when used in UPFLOW application
BURNER EN C L OSURE PRESSU R E
Tube location when used in DOWN FLOW application
PLUG
TUBE ROUTING
REFERENCE TUBE ASSEMBLY
CAP
PLUG
COLLECTOR BOX
DRAIN TUBE
(BLUE & W HITE STRIPED)
CONDENSATE TRAP
FIELD-INSTALLED
FACTORY-SUPPLIED DRAIN
TUBE COUPLING (RIGHT
DRAIN OPTION)
FIELD-INSTALLED FACTORY-SUPPLIED 1/2-IN. CPVC STREET
ELBOWS (2) FOR LEFT
DRAIN OPTION
COLLECTOR BOX DRAIN TUBE
(BLUE )
COLLECTOR BO X EXTENSION TUBE
COLLECTOR BOX TU BE
(PINK)
COLLECTOR BO X TUBE
(PINK)
COLLECTOR BOX TU BE
(GREEN)
COLLECTOR BOX DRAIN TUBE
(BLUE )
CONDENSA TE TR AP
INDUCER HOUSING
DRAIN TUBE
(VIOLET)
COLLECTOR BOX TUBE
(GREEN)
BURNER EN CLOSURE
PRESSURE REFERENCE
TUBE ASSEMBLY
COLLECTOR BOX DRAIN TUBE
(BLUE & WHITE STRIPED)
INDUCER HOUSING
DRAIN TUBE
(VIOLET)
DRAIN TUBE
COUPLING
DRAIN TUBES ROUTED IN
FRONT OF GAS VALVE
Tube location when used on
HORIZONT AL - LEFT ap plication
COLLECTOR BO X DR AIN TUBE
PLUG
CAP
BURNER
ENCLOSURE
PRESSURE
REFERENCE TUBE
ASSEMBLY
COLLECTOR BOX
EXTENSION TUBE
CONDENSATE TRAP
COLLECTOR BOX EXTENSION DRAIN TUBE
COLLECTOR BO X TUBE (PINK) RELOCATE T UBE BE TW EE N BLOWER SHELF AND
INDUCER HOUSING FOR 0 40,06 0 , AND 080 HEATING INP UT FURNACES
NOTE:
1. All tubing must be connected securely and routed to avoid kinks and traps.
2. Pressure tubing must always slope away from pressure switch to collector box connection as shown.
3. HORIZONTAL-LEFT installations require the collector box pressure tube to be relocated between the inducer housing and the blower shelf to prevent a trap.Refer to the Installation Instructions for further details.
DRAIN TUBE
COUPLING
(BLUE & WHITE STRIPED)
COLLECTOR
BOX TUBE
(GREEN)
INDUCER HOUSING
DRAIN TUBE
(VIOLET)
COLLECTOR BOX
DRAIN TUBE (BLUE)
COLLECTOR BOX DRAIN TUBE (BLUE)
PLUG
CAP
COLLECTOR BO X TUBE (GREE N)
COLLECTOR BOX DRAIN TUBE
(BLUE AND W HITE STRIPED)
Condensate Trap on LEFT
Side Optional
BURNER ENCLOSURE PRESSURE
REFERENCE TUBE ASSEMBLY CAP
PLUG
COLLECTOR BOX
DRAIN TUBE
(BLUE & WHITE STRIPED)
Condensate Trap on
CAP
COLLECTOR BOX DRAIN TUBE
(BLUE )
COLLECTOR BOX TUBE
PLUG
COLLECTOR BOX EXTENSION TUBE
CONDENSATE TRAP
COLLECTOR BOX EXTENSION
GAS VALVE
Tube location when used on
HORIZONTAL - RIGHT application
COLLECTOR BOX TUBE (PIN K)
INDUCER HOUSING DRAIN TUBE (VIOLET)
AUXILIARY "J" BOX RELOCATED HERE
COLLECTOR BO X EXTENSION TUBE
CONDENSATE TRAP
325400-201 REV. C (LIT - BOTTOM)
RIGHT Side
(PINK)
DRAIN TUBE
TUBE ASSEMBLY
BURNER
ENCLOSURE
PRESSURE
REFERENCE
Fig. 9—Furnace Pressure and Drain Tubing Diagram
—7—
A00351
BURNER FLAME
MANIFOLD
Fig. 10—Burner Flame
BURNER
PAM
RTV
A89020
WARNING: FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in serious injury, death or property damage. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, per­sonal injury or loss of life.
16. Replace main furnace door.
VI. SERVICING HOT SURFACE IGNITER
The igniter does NOT require annual inspection. Check igniter resistance before removal.
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
3. Disconnect igniter wire connection.
4. Check igniter resistance. a. Using an ohm meter, check resistance across both igniter
leads in connector. b. Cold reading should be between 45 ohms and 90 ohms. c. If ohm reading is higher than 110 ohms, igniter is
cracked and must be replaced.
5. Remove igniter assembly.
Fig. 11—Gasket on Collector Box
CAUTION: UNIT DAMAGE HAZARD
Failure to follow this caution may result in premature failure of the igniter. The igniter is fragile. DO NOT allow it to hit the side of the burner box opening while removing or replacing it.
b. Inspect igniter for a white area indicating a crack may be
present. If found, replace igniter.
NOTE: A small crack cannot be seen on a new igniter. After a period of operation, a white area will be visible around the crack.
c. If replacement is required, replace igniter on igniter
bracket external to furnace to avoid damage as the silicon portion is very brittle and will easily crack or shatter.
d. To remove igniter from igniter bracket, remove screw
holding igniter ceramic block to bracket and pull ce­ramic block out of bracket.
6. To replace igniter/igniter assembly, reverse items 5a through 5d.
7. Reconnect igniter wire connection.
8. Turn on gas and electrical supplies to furnace.
9. Verify igniter operation by initiating control board self-test feature or by cycling thermostat.
10. Replace main furnace door.
VII. ELECTRICAL CONTROLS AND WIRING
A93081
CAUTION: BURN HAZARD
Failure to follow this caution may result in minor personal injury. Allow igniter to cool before removal. Normal operating temperatures exceed 2000°F.
a. Do not remove igniter from bracket while assembly is in
furnace. Using a 1/4 in. nutdriver, remove screw secur­ing bracket and ignitor assembly to bottom of burner box. The screw in the bracket is always located toward outside of burner box. The screw may be hidden by inlet box or inlet pipe, but can be removed without removing either. After removing screw, slide igniter and bracket toward outside of burner box and pull straight out.
—8—
WARNING: ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death. There may be more than 1 electrical supply to the unit. Check accessories and cooling unit for additional electri­cal supplies.
The electrical ground and polarity for 115-v wiring must be maintained properly. Refer to Fig. 12 for field wiring information and to Fig. 16 for unit wiring information. NOTE: If the polarity is not correct, the STATUS LED on the furnace control will flash rapidly and prevent the furnace from operating. The control system also requires an earth ground for proper operation of the furnace control and flame sensor.
BLK
WHT
GND
115-VOLT FIELD-
SUPPLIED
FUSED
DISCONNECT
BLK
WHT
JUNCTION BOX
FIVE
WIRE
THREE-WIRE
HEATING-
ONLY
CONTROL
BOX
FURNACE
W2
COM
W/W1
Y/Y2
R G
24-VOLT
TERMINAL
BLOCK
NOTE 2
WCY RG
NOTE 1
NOTES: 1.
Connect Y/Y2-terminal as shown for proper operation. Some thermostats require a "C" terminal connection as shown.
2. If any of the original wire, as supplied, must be replaced, use
3. same type or equivalent wire.
Fig. 12—Field Wiring
FIELD 24-VOLT WIRING FIELD 115-, 208/230-, 460-VOLT WIRING FACTORY 24-VOLT WIRING FACTORY 115-VOLT WIRING
1-STAGE THERMOSTAT TERMINALS
CONDENSING
UNIT
FIELD-SUPPLIED
FUSED DISCONNECT
GND
208/230- OR 460-VOLT THREE PHASE
208/230­VOLT SINGLE PHASE
A95236
The 24-v circuit contains an automotive-type, 3-amp fuse located on the furnace control. (See Fig. 13.) Any direct shorts of the 24-v wiring during installation, service, or maintenance will cause this fuse to blow. If fuse replacement is required, use ONLY a fuse of identical size. The furnace control LED will flash status code 24 when fuse needs to be replaced.
With power to the unit disconnected, check all electrical connec­tions for tightness. Tighten all screws on electrical connections. If any smoky or burned connections are found, disassemble the connection, clean all parts, strip wire, and reassemble properly and securely.
Reconnect electrical supply to unit and observe unit through 1 complete operating cycle and check for proper operation.
VIII. CHECKING HEAT TAPE OPERATION (IF APPLICABLE)
In applications where the ambient temperature around the furnace is 32°F or lower, freeze protection measures are required. If this application is where heat tape has been applied, check to ensure it will operate when low temperatures are present.
NOTE: Heat tape, when used, should be wrapped around the condensate drain trap and drain line. There is no need to use heat tape within the furnace casing. Most heat tapes are temperature activated, and it is not practical to verify the actual heating of the tape. Check the following:
1. Check for signs of physical damage to heat tape such as nicks, cuts, abrasions, gnawing by animals, etc.
2. Check for discolored heat tape insulation. If any damage or discolored insulation is evident, replace heat tape.
3. Check that heat tape power supply circuit is on.
CAUTION: UNIT AND PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in furnace component failures or water property damage. If this furnace is to be operated in an unconditioned space where the ambient temperatures may be 32°F or lower, freeze protection measures must be taken. See CONDEN­SATE DRAIN PROTECTION section of Installation, Start-up, and Operating Instructions. (See Fig. 14.)
IX. WINTERIZING
CAUTION: UNIT DAMAGE HAZARD
Failure to follow this caution may result in furnace component damage. Freezing condensate left in the furnace will damage the furnace.
If the furnace will be off for an extended period of time in a structure where the temperature will drop to 32°F or below, winterize as follows:
1. Turn off electrical supply to furnace.
2. Remove main furnace door.
3. Disconnect upper inducer housing drain connection cap from inducer housing. (See Fig. 15.)
4. Connect field-supplied 1/2-in. I.D. inducer housing tube to upper inducer housing drain connection.
5. Insert funnel in tube and pour one quart of antifreeze, propylene glycol (RV, swimming pool antifreeze, or equivalent) into funnel/tube until it is visible at point where condensate enters open drain. (See Fig. 16.)
—9—
MODEL PLUG
(
CONNECTOR
SW1 SETUP
SWITCHES AND
BLOWER OFF-
DELAY
AIR CONDITIONING
(A/C) AIRFLOW
SETUP SWITCHES
24-V THERMOSTAT
TERMINALS
STATUS AND COMM
LED LIGHTS
COMMUNICATION
CONNECTOR
CONTINUOUS FAN
(CF) AIRFLOW
SETUP SWITCHES
FUTURE
APPLICATIONS
HUMIDIFIER
TERMINAL (24-VAC
0.5 AMP MAX.
ACRDJ – AIR
CONDITIONING
RELAY DISABLE
JUMPER
FLASH
UPGRADE
CONNECTOR
(FACTORY
ONLY)
3-AMP FUSE
TRANSFORMER 24-VAC
CONNECTIONS
115-VAC (L2) NEUTRAL
CONNECTIONS
PL1 – LOW VOLTAGE MAIN
HARNESS CONNECTOR
Fig. 13—Variable Capacity Furnace Control
CAUTION: UNIT DAMAGE HAZARD
Failure of plastic components may occur. Do not use ethylene glycol (Prestone II antifreeze/coolant or equivalent automotive type).
6. Replace drain connection cap and clamp to inducer housing.
7. Replace main furnace door.
8. Propylene glycol need not be removed before restarting furnace.
WIRING DIAGRAM
See Fig. 12, 13, and 18 for Wiring Diagram
EAC-1 TERMINAL
115-VAC 1.0 AMP MAX.)
115-VAC (L1) LINE
VOLTAGE CONNECTIONS
32°F MINIMUM INSTALLED AMBIENT OR FREEZE PROTECTION REQUIRED
PL3 – ECM BLOWER
HARNESS
CONNECTOR
PL2 – HOT SURFACE IGNITER & INDUCER
MOTOR CONNECTOR
A02278
TROUBLESHOOTING
Use the troubleshooting guide, the status code LED on the furnace control and the component test to isolate furnace operation problems.
A more detailed troubleshooting guide is available from your distributor.
For an explanation of status codes, refer to service label located on
Fig. 14—Freeze Protection
A93058
back of main furnace door. (See Fig. 17.)
—10—
The furnace control stores all status codes for a period of 72 hours, regardless of 115-v or 24-v power interruption.
NOTE: Removing blower access panel opens blower access panel door switch and terminates 115-v power to furnace control. Before removing blower access panel or turning off 115-v power, look into blower access panel sight glass for current LED status.
1. To retrieve status code, proceed with the following:
NOTE: NO thermostat signal may be present at furnace control and all blower time delay periods must be completed.
a. Leave 115-v power to furnace turned on. b. Remove main furnace door. c. Look into blower access panel sight glass for current
LED status code. d. Remove blower access panel. e. Turn setup switch SW1-1 to ON position. (See Fig. 13 or
18 for location.) f. Manually close blower access panel door switch. Use a
piece of tape to hold switch closed.
WARNING: UNIT MAY NOT OPERATE
Failure to follow this warning could result in electrical shock, personal injury, or death. Blower access panel door switch opens 115-v power to furnace control. No component operation can occur unless switch is closed. Caution must be taken when manually closing this switch for service purposes.
A99118
Fig. 15—Inducer Housing Drain Tube
A99119
Fig. 16—Funnel in Drain and Antifreeze Running
Through Trap
g. The AMBER LED will flash the status codes in the order
of occurence. Record status codes until status code 11 flashes (1 short and 1 long).
h. After status code # flashes, the status codes will repeat
until setup switch SW1-1 is turned off.
i. Remove tape to release blower access panel door switch
and replace blower access panel.
j. Operate furnace through 1 heat cycle to test for proper
operation and check LED status.
k. If furnace is operating properly and LEDs indicate
proper operation, replace main furnace door.
2. Status codes are erased after 72 hours or they can be manually erased by performing the following procedure:
a. Leave 115-v power to furnace turned on. b. Remove main furnace door. c. Look into blower access panel sight glass for current
LED status code. d. Remove blower access panel. e. Turn setup switch SW1-1 to ON position. (See Fig. 13 or
18 for location.) f. Jumper thermostat terminals R, W/W1, and Y/Y2 on
furnace control.
g. Manually close blower access panel door switch. Use a
piece of tape to hold switch closed.
h. After status code 11 flashes for at least 2 times, remove
R, W/W1, and Y/Y2 jumpers. i. Turn setup switch SW1-1 to OFF position. j. Remove tape to release blower access panel door switch
and replace blower access panel.
k. Operate furnace through 1 heat cycle to check for proper
operation and check LED status. l. If furnace is operating properly and LEDs indicate proper
operation, replace main furnace door.
—11—
3. The control can also assist in troubleshooting by performing a Component Test. The Component Test will functionally operate all furnace components, except the gas valve.
NOTE: The component test feature will not operate if the furnace control is receiving any thermostat signals or until all time delays have expired.
a. To initiate Component Test proceed with the following:
(1.) Leave 115-v power to furnace turned on. (2.) Remove main furnace door. (3.) Remove blower access panel. (4.) Turn setup switch SW1-6 to ON position. (5.) Manually close blower access panel door switch.
Use a piece of tape to hold switch closed.
WARNING: UNIT MAY NOT OPERATE
Failure to follow this warning could result in electrical shock, personal injury, or death. Blower access panel door switch opens 115-v power to control center. No component operation can occur unless switch is closed. Caution must be taken when manually closing this switch for service purposes.
b. When items (1) through (5) above have been completed,
the following will occur:
(1.) Inducer motor operates at medium speed through
step (3), then turns off.
(2.) After waiting for 15 seconds, hot surface igniter is
energized for 15 sec, then de-energized.
(3.) Main blower motor operates at midrange airflow for
15 seconds, then turns off.
(4.) After component operation test is completed, 1 or
more fault codes (11, 25, 41, or 42) will flash. See service label on back of main furnace door or Fig. 15 for explanation of codes.
NOTE: To repeat component test, turn setup switch SW1-6 to OFF and then back to ON.
c. After component test, perform the following:
(1.) Remove tape to release blower access panel door
switch and turn setup switch SW1-6 to OFF posi-
tion. (2.) Replace blower access panel. (3.) Operate furnace through 1 heat cycle to check for
proper operation and check LED status. (4.) If furnace is operating properly and LEDs indicate
proper operation, replace main furnace door.
—12—
SERVICE
If status code recall is needed disconnect the "R" thermostat lead, reset power, and put setup switch "SW1-1" in the ON position. To clear the status code history put setup switch "SW1-1" in the ON position and jumper thermostat terminals "R", "W/W1", and "Y/Y2" simultaneously until status code #11 is flashed.
LED CODE
CONTINUOUS OFF ­CONTINUOUS ON ­RAPID FLASHING -
EACH OF THE FOLLOWING STA TUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY THE NUM BER OF LONG FLASHES.
11 NO PREVIO U S CODE - Stored status codes are erased automatically after 72 hours or as
specified abov e.
12 BLO WER ON AFTER POWER UP- (115 VAC or 24 VAC) - Blower runs for 90 seconds, if unit is
powered up during a call for he at (R-W/W1 closed ) or (R-W/W1 opens) during the blower on-delay period.
13 LIMIT CIRCUIT LOCKOUT - Loc kout occ u rs if the limit, o r flame rollout s witch is ope n lo n g er than
3 minutes or 10 successive limit trips occurred during high-heat. Control will auto reset after
3 hours. Refer to status code #33. 14 IGNITION LOCKOUT - Control will a u t o- reset after 3 hours . Ref e r to status co de #34. 15 BLOWER MOTOR LOCKOUT- Indicates the blower failed to reach 250 RPM or the blower failed
to communicate within 30 seconds after being turned ON in two successive h eating cycles .
Control will auto reset after 3 hours. Refer to status code #41. 21 GAS HEATING LOCKOUT- Control will NOT auto reset. Check for:
- Mis-wired gas valve. - Defectiv e control (va lve rela y )
22 ABNORMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is de-en e rgiz ed .
Inducer will run until fault is cleared. Check for:
- Leaky gas valve. - Stuck-open gas valve.
23 PRESSURE SWITCH DID NOT OPEN- Check for:
- Obstructed pressure tubing. - Pressure switch stuck closed.
24 SECONDARY VOLTAGE FUSE IS OPEN - Check for:
- Short circuit in secondary voltage (24 VAC) wiring.
25 MODEL SELECTION OR SETUP ERROR- Either indicates the model plug (PL4) is missing or incorrect
or setup switch "SW1-1" or "SW1-6" is positioned improperly. If code flashes only 4 times on
power-up control is defaulting to model selec tion stored in memory. Check the following:
- Thermo st at ca l l wit h "SW1-1" ON. - Thermo st at ca l l wit h "SW1-6" ON.
- "SW1-1 " and "SW1-6" both ON together. - Two differe nt furnace models twinned.
- Wiring diagram for m o d el plug nu mb e r an d resistanc e va lues if code flas he s co ntin u ou sly.
31 HIGH-HEAT PRESSU RE SW ITCH O R RELA Y D ID N OT CLOSE OR REOPENED - Indicates the high-heat
pressure switch input failed to clos e on a call for high-heat, or opened during high-heat.
Control relay may be de fec tive or gas valve is mis-wired. Refer to status code #32. 32 LOW-HEAT PRESSURE SWITCH DID NOT CLOSE OR REOPENED - Indicates the low-heat pressure
switch input failed to close on a call for low-heat, or opened during low-heat. If opens during
blower on-delay period, blower will come on for the selected blower off-delay. If opens within
5 minutes after ignition the next heating cycle will be restricted to high-heat. Check for:
- Proper v ent sizing. -Plugged condensate drain.
- Low inlet gas pressure (i f LG P S u sed). - Excessive wind .
- Restricted combustion air su pply. - Improper pre ssure switch wiring .
- Water in vent piping, possible sagging pipe. - Disconnected or obstructed pressure tubing.
- Failed or "Out-of-Calibration" pressure switch es.
33 LIMIT CIRCUIT FAULT - Indicates the limit, or flame rollout is open or the furnace is operating in
high-heat only mode du e to 2 succ e ssive low heat limit trips. Blower will run for 4 minutes or
until open switch remakes whic hever is longer. If open longer than 3 minutes, code changes
to lockout #13. If open less than 3 minutes status code #33 c ontinues to flash until blower shuts
off. Flame rollout s w itch require s man u al reset. Check for:
- Improper or misaligned limit and/or limit shield. - Defective switch or connections.
- Improper low-heat gas input adjustment. - Loose blower wheel.
- Stuck high-heat solenoid in gas valve - Proper rear air baffle.
34 IGNITION PROVING FAULT - Control will try three more times before a lockout #14 occurs. If
flame signal is lost during blower on-delay period, blower will come on for the selected blowe r
off-delay. Check for: - Gas valve de f e c t iv e o r t urned "OFF".
- Defe ctive Hot Surface Igniter - Manual valve shut-off.
- Low inlet gas pressure - Flam e sensor must not be grounded.
- Inadequate flame carryover or rough ignition. - Control ground continuity
- Green/Yellow wire MUST be connected to furnace sheet metal.
- Proper flame sense micro amps (.5 micro amps DC min., 4.0 - 6.0 nominal).
- Oxide buildup on flame sensor (clean with fin e steel wo ol.)
41 BLOWER MOTOR F AUL T - Indicates the blower failed to reach 250 RPM or the blower failed to
commun i c a te within the prescribed time limits. Thi rty se c onds after be ing turned ON or te n
seconds during steady-state operation. 42 INDUCER MOTOR F AUL T - Indicates the inducer has not started within 20 seconds after a call for
heat, the inducer motor RPM is outside its valid range of operation, or the inducer RPM signal
was lost for 5 seconds during operation. Check for:
- Proper v ent sizing. - Restricted combustion air supply.
- Failed induc er motor. - Improper motor wiring.
43 LOW-HEAT PRESSURE SWITCH OP EN W HILE HIGH-HEAT PRESSURE SWITCH IS CLOSED- Check for:
- Plugged condensate drain. - Low inlet gas pressure (if LGPS used).
- Water in vent piping, possibly sagging pipe. - Improper pressure switch wiring.
- Stuck open low-heat pressure switch. - Disconnected or obstructed pressure tubing.
45 CONTROL CIRCUITRY LOCKOUT - Auto-reset after 1 hour lockout due to:
- Flame sense circuit falure. - Gas valve relay stuck op en .
- Software chec k error.
Reset power to clear loc kout. Replace control if status cod e re p ea ts .
Check for 115 VAC at L1 and L2, and 24 VAC at SEC-1 and SEC-2. Control has 24 VAC power. Line voltage (115 VAC) polarity is reversed.
STATUS
COMPONENT TEST
To initiate the component test sequence, shut "OFF" the room thermostat or disconnect th e "R" thermostat lead. Reset power and then put setup switch "SW 1-6" in the ON position to start the com ponent test sequence. Once initiated the furnace control will turn th e inducer ON. The inducer motor will r u n for th e entire test. The hot surface igniter and blower motor will be turned ON f o r 15 se conds each. When the blower is turned OFF the inducer will be turned OFF. When the component test is completed one or more of the following codes will flash.
CODE DESCRIPTION
Indicates the inducer and blower motor tested OK. Visual check of hot surface igniter required.
11 25 SETUP ERROR 41 BLOWER MOTOR FAULT ­42 INDUCER MOTOR FAULT -
control. To repeat component test tu rn setup switch "SW1-6" OFF and then back ON . After component test is completed put setup sw itch "SW1-6" in the O FF position and reconnect the "R" thermostat lead.
- Same as code 25 above. Indicates blower motor failed test. Check blower, wiring, and furnace control. Indicates inducer motor failed test. Check inducer, wiring and furnace
328072-101 REV. A
Fig. 17—Service Label
—13—
A02279
SCHEMATIC DIAGRAM
TO 115V A C FIELD-DISCONNECT SWITCH
FRS
LS
CONNECTION DIAGRAM
EQUIPMENT
L2
ILK
BLU
M
SW1-7,8
BLOWER OFF DELAY
HSI
PL10
2
PL2
GROUND
L2
FUSED OR CIRCUIT
RED RED
NOTE #8
RED
LPS
RED
HPS
BRN
GV
90
SEC
120
78
78 78
SELECTION
OFF OFF OFF
HSIR
ORN
HI
C
327971-101 REV. A
PL12
ILK
1
RED GRN YEL BLU
180
5.1
012
100
BLWM
4
5
3
PL12
IND
NOTE #7
L1
PL10
2
WHT
VS
PL2
220
5.1
120 013
L2
L2
115VAC
L1
1
2
EAC-2
PL14
EAC-1
EAC
BLWM
BLK
4
BLK
1
1 2 3
OFF
1 2 3
OFF 1 2 3
OFF
PL1
1 2 3
OFF
1 2 3
4
OFF
1 2 3
OFF
1 2 3
PL8
OFF
1 2 3
OFF
SIZE
A/C OR CF AIRFLOW SELECTION CHART BASED ON 350 CFM/TON
MODEL
SW4
OAT
PRINTED CIRCIUT BOARD
040,060,
TRAN
SEC1
PL14
PL13
L1
122512251225
1
1050
875
700
2
525
DEF.
3.5T080
PL9
SEC2
24VAC
PL1-8
HUMR
R
HUM
GRN/YEL
PL12
WHT
NEUTRAL - L2
COMM
ACRDJ
HUM
1
1
AB CD
LPS
PL1-2
PL1-12
HPSR
ACR
COMMR
PRINTED CIRCIUT BOARD
TRAN
BLU
WHT
NOTE #11
EAC-2
SEC-1
LEDS
CF
1
SW1
PL4
FU1
NOTE #6
PL1-6
FRS LS
YEL
1 2 3 4 5
RED
17
GRN
16
YEL BLU
10
IND
BLK
NOTE #7 PL12
BLK
EAC-1
210017501400
1750
1
1
1750
1225
1050
2
875
875 1050 1225 1400
2
700
700
DEF.
DEF.
1. Default A/C airflow when A/C switches are in OFF position
2. Default cont. fan airflow when CF switches are in OFF position
120
5T080,100
PL7
SEC-2
FUSE 3-AMP
NOTE #8
ACRDJ
W/W1
W/W1DHUM G om
C
W2 Y/Y2 RY1
RED
STAT US
LGPS
PL1-4
DHUM
WHT
CODE
24V
AC
1
HPS
M
PL1-3
PL1-10
(WHEN USED)
CPU
W2
Y/Y2
JUNCTION
IND Inductor (Note #7)
LED Light Emitting Diode for Status Codes
LGPS Low Gas Pressure Switch, SPST (N.O.)
A/C Air Conditioning (Adjust abl e Airflow -CFM)
ACR Air Conditioning Relay, SPST (N.O.)
ACRDJ Air Conditioning Relay Defeat Jumper
LEGEN
G
HI
TERMINAL
LPS Low-Heat Pressure Switch, SPST (N.O.)
BLWM Blower Motor (ECM)
FSE
PL1-5
A02291
GV
C
PL1-1
NOTE #3
GVR
PCB
NOTE #5
Y1
COM
CONTROL TERMINAL
FACTORY POWER
WIRING (115VAC)
2. Use only copper wire between the d isconnect switch and the furnace junction box (JB).
3. This wire must be connected to furnac e shee t m e tal for control to prove flam e .
4. Symbols are electrical representation only.
1. If any of the original equipment wire is replaced use wire rated for 105°C.
NOTES:
FACTORY CONTROL
WIRING (24VAC)
FIELD CONTROL
WIRING (24VAC)
CONDUCTOR ON
90 seconds or 5 seconds when dehumidify call is active.
auto-reset after three hours.
5. Solid lines inside PCB are printed circuit board conductors and are not included in legend.
6. Replace only with a 3 am p fuse.
7. Inductor is used with 3/4 hp and 1 hp ECM Blower motors.
8. Factory connected when (LGPS) not used.
9. Blower off-delay, gas heating selections are (90, 120, 150, 180) seconds, cooling or heat pump
CONTROL
FIELD WIRING
SCREW TERMINAL
electronic control circuits.
10. Ignition lockout will o c c u r after four cons ecutive u nsucce s sful trials for ignit io n . C ontrol w ill
11. Any of the 5 wires shown within the NEUTRAL L2 box can be connected to any terminal within the box.
12. Blower motor (BLWM) and Inducer m otor (IDM) are locked-rotor overload protected by redundant
EQUIPMENT
GROUND
PLUG RECEPTACLE
Fig. 18−Wiring Diagram
SPST (N.O.)
LS Limit Switch, Auto-Reset, SPST (N.C.)
PCB Printed Circuit Board
PL1 12-Circuit Connector
PL2 4-Circuit HSI & IDM Co n nec tor
PL3 4-Circuit ECM BLWM Conne c t o r
PL4 4-Circuit Model Plu g Connector
PL7 4-Circuit Communication Connector
PL9 2-Circuit OAT Connector
PL10 2-Circuit HSI Connector
PL11 IDM Connector (12-Ci rcuit)
PL12 1-Circuit Inductor Splice Connector
PL13 16-Circuit ECM Blower Ctrl. Connector
PL14 5-Circuit ECM Blower Powe r Connector
SW1-1 Manual Switch, Status Code Recall, SPST (N.O.)
SW1-2 Manual Switch, Low-Heat Only, SPST (N.O.)
SW1-3 Manual Switch, Low-Heat Rise Adj. SPST (N.O.)
SW1-4 Manual Switch, Comfort/Efficiency Adjustment,
SW1-5 Manual Switch, Cooling CFM/Ton, SPST (N.O. )
SW1-6 Manual Switch, Component Test, SPST (N.O.)
SW1-7,8 Manual Switches, Blower Off-Delay, SPST(N.O.)
SW4-1 Manual Switch, Twinning Main (OFF) / Sec. (ON)
SW4-2&3 FOR FUTURE USE
TRAN Transformer, 115VAC / 24VAC
(115VAC 1.0 Amp Max.)
Factory Installed
CF Continuous Fan (Adjustable Airflow -CFM)
COMMR Communication Relay, SPDT
CPU Microprocessor / Circuitry
DHUM DHUM Connection (24VAC )
EAC-1 Elec tronic Air Cleaner Connection
EAC-2 Electronic Air Cleaner Connection (Common)
FRS Flame Rollout Switch, Man. Reset, SPST(N.C.)
FSE Flame-Proving Sensor Electrode
FUSE F use, 3 Amp, Autom otive Blade T ype,
GV Gas Valve
GVR Gas Val v e Rel ay, DPST (N.O.)
HPS High-Heat Pressure Switch, SPST (N.O.)
HPSR High-Heat Pressure Switch Relay, SPST (N.C.)
HSI Hot Surface Igniter (115VAC)
HSIR Hot Surface Igniter Relay, SPST (N.O.)
HUM 24VAC Humidifier Connection (0.5 Amp Max.)
HUMR Humidifier Relay , SPST (N.O.)
IDM Inducer Draft Motor, 2-Speed, Shaded Pole
IDR Induce r Motor Relay, SPST (N.O.)
IHI/LOR Inducer Motor Speed Change Relay, SPDT
ILK Blower Door Interlock Switch, SPST (N.O.)
D
L2
IDM
PL11
6
12
1
4
2
1
3
IHI/LOR
PL13
1
4
2
10
PL1-11
PL1-7
PCB
1
7
10
16
PL1-9
CPU
IDR
NOTE #5
GND
NEUTRAL
NOTE #2
L1
SWITCH (WH E N RE Q’D)
BREAKER DISCONNECT
(WHEN USED)LGPS
GRY
GRN/YEL
SEC
150
FU2
IDM
2
4
1
10
YEL
ORN
GRN/YEL
FSE
WHT
YEL
GRN/YEL
BRN
NOTE #3
SEC
180
SEC
7 8
OFF
123 4
PL3
WHT BLK
JB
HSI
6
12
BRN
WHT
MODEL
PL4 - MODEL PLUG CHART
MODEL
BLK
BLK
BLK
HSI
WHT
1
PL3
75
91
120
150
2 - 3
5.1
5.1
5.1
5.1
1 - 4
PIN RESISTANCE K
008
009
010
011
PLUG
HK70EZ
040
060
SIZE
5T-080
3.5T080
—14—
A02350a
Close door switch.
Is door switch closed?
YES
NO NO
NO
YES YES
Is there 115V going to switch? Is circuit breaker closed?
Check for continuity in wire from circuit
Replace door switch.
NO
breaker to furnace.
Close circuit breaker and go back to
START.
Check room thermostat or
interconnecting cable.
Is 24V present at W/W1, W2, Y1, Y/Y2 or
G thermostat terminals on the furnace
control?
YES
Disconnect all the thermostat wires from
the furnace control.
NO
Does the problem repeat when using a
YES
jumper wire?
NO
The thermostat is not compatible with the
furnace control. Either install a ballast
resistor, connect the Com24V thermostat
terminal to the thermostat, or replace the
thermostat.
YES
Replace transformer.
Does the control respond to W/W1, W2,
Y1, Y/Y2, and G (24V) thermostat
signals?
Run system through a low-heat, high-
heat, or cooling cycle to check operation.
Status codes are erased after 72 hours
or can be manually erased by putting
setup switch SW1-1 in the ON position
and jumpering R, W/W1, and Y/Y2
simultaneously until status code #11 is
flashed.
Replace furnace control.
NOYES
Troubleshooting Guide – Variable Speed
START
Is there 115V at L1 and L2?
NO NO NO
Is AMBER LED status light on?
YES
YES
YES
Is there 24V at SEC-1 and SEC-2?
Replace furnace control.
Check for correct line voltage polarity. If
units are twinned, check for proper low-
voltage (24V) transformer phasing.
YES
Is AMBER LED status light blinking
rapidly without a pause?
NO
To recall previous status codes disconnect the R
thermostat connection, reset power, and put setup
switch SW1-1 in the ON position. The AMBER LED
NO
Is AMBER LED status light blinking
ON/OFF slowly with a combination of
short and long flashes?
will flash the status codes in the order of occurrence.
Record status codes until status code #11 flashes (1
short and 1 long flash). After status code #11
flashes the status codes will repeat. Status codes
are erased after 72 hours or can be manually erased
by putting setup switch SW1-1 in the ON position
and jumpering R, W/W1, and Y/Y2 simultaneously
until status code #11 is flashed. When done put
setup switch SW1-1 in the OFF position.
Was there a previous status code other
than #11?
YES
Determine status code. The status code
is a 2 digit number with the first digit
determined by the number of short
flashes and the second digit by the
number of long flashes?
Go to section below for the status code
that was flashed.
—15—
A02350b
LOCKOUT Auto-reset
after 1 hour lockout due
to:
45 CONTROL CIRCUITRY
WHILE HIGH-HEAT PRESSURE
SWITCH IS CLOSED - Check for:
- Low-heat pressure switch stuck open.
43 LOW-HEAT PRESSURE SWITCH OPEN
- Flame circuit failure.
- Disconnected or obstructed pressure
open.
- Gas valve relay stuck
tubing.
- Improper pressure switch wiring.
- Software check error.
Reset power to clear
- Low inlet gas pressure (if LGPS used).
- Plugged condensate drain.
lockout. Replace control
if code repeats.
pipe.
- Water in vent piping, possible sagging
NO
Replace furnace control.
Unplug igniter harness from control and
repeat component test by turning setup
Check for continuity in the
harness and igniter. Replace
defective component.
YES
switch SW1-6 OFF and then back ON.
Check for 115V between pin 3 and
NEUTRAL-L2 on the control. Was 115V
present for the 15 second period?
NO
Reconnect the R thermostat lead and set
Check connections. If OK,
thermostat to call for heat. Connect
replace control.
voltmeter across gas valve connections.
Does gas valve receive 24V?
Check that all gas valves are
turned on. Replace valve.
YES
or rough ignition.
bracket.
Check for:
- Inadequateflame carryover
- Low inlet gas pressure.
- Proper firing rate.
NO
NO
YES
Does gas valve open and allow gas to
flow?
Do the main burners ignite?
- Air leakage around igniter
YES
Allow blower tocome on and
YES
repeat test to check for
Do the main burners stay on?
intermittent operation.
NO
Check connections and retry.
Repeat call for heat and check flame
If current is near typical value
NO
sensor current during trial for ignition
NO
(4.0-6.0 nominal) and burners
will not stay on, repeat check
period. Is the DC microamps below 0.5?
in high-heat. If burners will
still not stay on replace
control. If burners operate in
high-heat then switch to low-
heat, check manifold
Clean flame sensor with fine steel wool
and recheck current. Nominal current is
pressure. If OK, check
burner carryover and flame
sensor location.
4.0 to 6.0 microamps.
YES
NO
NO
YES
Is current near typical value? Replace electrode.
Will main burners ignite and stay on? Replace furnace control.
YES
Fixed.
NOT CLOSE OR REOPENED – If opens
during blower on-delay period, blower will
32 LOW-HEAT PRESSURE SWITCH DID
erased after 72 hours or can be manually
erased by putting setup switch SW1-1 in
11 NO PREVIOUS CODE – Status codes are
- Low inlet gas pressure (if LGPS used).
- Restricted combustion air supply.
12 BLOWER ON AFTER POWER UP –
- Disconnected or obstructed pressure
(115V OR 24V) – Normal operation.
tubing.
Blower runs for 90 seconds, if unit is
- Proper vent sizing.
come on for the selected blower off-delay.
If opens within 5 minutes after ignition the
next heating cycle will be restricted to
high-heat. Check for:
the ON position and jumpering R, W/W1,
and Y/Y2 simultaneously until status code
#11 is flashed. Run system through a low-
heat, high-heat, or cooling cycle to check
system.
- Defective or miswired pressure switches
- Excessive wind.
powered up during a call for heat (R-
W/W1 closed) or when (R-W/W1 opens)
- Pluggedcondensatedrain.
- Water in vent piping, possible sagging
during the blower on-delay period.
pipe.
occurs if the limit or flame rollout switch is
13 LIMIT CIRCUIT LOCKOUT – Lockout
limit or flame rollout switch is open or the
furnace is operating in high-heat only
33 LIMIT CIRCUIT FAULT – Indicates the
open longer than 3 minutes or 10
successive limit trips occurred during high-
heat. Control will auto-reset after 3 hours.
mode due to 2 successive low-heat limit
trips. Blower will run for 4 min. or until
open switch remakes whichever is longer.
See code 33.
If open longer than 3 min., code changes
to lockout #13. If open less than 3 min.
status code #33 continues to flash until
ignite gas and prove flame in 4 attempts.
14 IGNITION LOCKOUT – System failed to
blower shuts off. Flame rollout switch
Control will auto-reset after 3 hours. See
- Loose blower wheel.
- Defective switch or connections.
15 BLOWER MOTOR LOCKOUT – Indicates
shield.
- Improper low-heat gas input adjustment.
- Improper or misaligned limit and/or limit
- Stuck high-heat solenoid in gas valve.
the blower failed to reach 250 RPM or the
blower failed to communicate within 30
seconds after being turned ON in two
successive heating cycles. Control will
auto-reset after 3 hours. See code 41.
21 GAS HEATING LOCKOUT – Turn off
not sensed during the trial for ignition
34 IGNITION PROVING FAILURE – If flame is
power and wait 5 minutes to retry. Check
for:
period, the control will repeat the ignition
- Stuck closed gas valve relay on control.
sequence 3 more times before lockout #14
- Miswire or short to gas valve wire.
occurs. If flame signal is lost during the
blower on-delay period, blower will come on
for the selected blower off-delay. Check
the following items first before proceeding
Flame is proved while gas valve is de-
energized. Inducer will run until fault is
22 ABNORMAL FLAME-PROVING SIGNAL
- Proper rear air baffle.
requires manual reset. Check for:
status code 34.
to furnace sheet metal.
- Manual shut-off valve.
- Gas valve turned off.
to the next step.
- Green/Yellow wire MUST be connected
- Flame sensor must not be grounded.
To determine whetherthe problem is in the
gas valve, igniter, or flame sensor the
system can be operated in component test
mode. To check the igniter remove the R
thermostat connection from the control,
reset power, and put setup switch SW1-6 in
the ON position to start the component test.
Does the igniter glow orange/white by the
end of the 15 second warm-up period?
wiring including thermostat leads.
Disconnect thermostat leads to isolate
short circuit.
cleared. Check for:
- Stuck open or leakygas valve.
Check for:
- Obstructed pressure tube.
23 PRESSURE SWITCH DID NOT OPEN –
- Pressure switch stuck closed.
Check for:
24 SECONDARY VOLTAGE FUSE IS OPEN
- Short circuit in secondary voltage (24V)
—16—
A02350c
You have an open wire or bad
terminal on either the BLACK or
NO
Turn power back on. Is there 115VAC at
PL14-5 and PL14-4?
YES
WHITE power leads between
the furnace control and the
blower motor. If you have a
power choke disconnect it and
check continuity.
YES
Is there 12-VDC at PL13-7 RED (+) and
PL13-1 GREEN (-)?
YES
wer
You have an open wire or bad
terminal on either the RED or
GREEN wire between the
furnace control and the blower
motor.
YES
NO
Is there 12-VDC at PL3-1 RED (+) and
PL3-2 GREEN (-)?
NO
NO
Is there 5-VDC at PL3-3
NO
Replace the furnace control.
Is there 5-VDC at PL13-16 YELLOW (+)
YES
YELLOW (+) and PL3-2
GREEN (-)?
YES
The voltage just measured should be
and PL13-1 GREEN (-)?
You have an open wire or bad
terminal on the YELLOW wire
between the furnace control and
very stable and should not fluctuate more
than .02-VDC. If the voltage fluctuates
more than this get a different voltmeter
the blower motor.
NO
before proceeding.
Turn power off, reconnect PL13 and
PL14 to the blower motor, then turn
power back on. Connect a DC voltmeter
across PL3-3 YELLOW (+) and PL3-2
GREEN (-). Does the voltage fluctuate
more than it did in the previous step?
Turn power off, disconnect PL13 and
PL14 from the blower motor, then turn
power back on. Connect a DC voltmeter
across PL13-16 BLUE (+) and PL13-1
GREEN (-). The voltage should be near
0-VDC but it will fluctuate briefly several
times a second. If you have an analog
voltmeter the needle will briefly go high
several times a second. If you have a
digital voltmeter with a bar graph it will
show a large change in magnitude on the
bar graph several times a second. If you
have a standard digital voltmeter it will
show a brief fluctuation in voltage and the
magnitude may vary depending on the
voltmeter used.
YES
after being turned ON or ten seconds
during steady-state operation. Turn po
off and check the following items first
defaulting to the model selection stored in
memory. If status code 25 flashes
continuously it could indicate any of the
before proceeding to the next step.
following:
- Rubbing blower wheel.
- Model plug PL4 is missing and there is
blower failed to reach 250 RPM or the
blower failed to communicate within the
prescribed time limits. Thirty seconds
41 BLOWER MOTOR FAULT – Indicates the
SETUP ERROR – If status code 25 only
flashes 4 times on power-up the control is
missing its model plug PL4 and is
25 INVALID MODEL SELECTION OR
- Loose blower wheel.
- Wiring from furnace control to blower
no valid model stored in permanent
memory. This will happen if you forget
motor.
Remove the R thermostat connection from
to install the model plug PL4 on a
service replacement control.
NO
the furnace control, disconnect both
connectors from the blower motor PL13
and PL14. Does the blower wheel turn
freely?
Replace the blower control module attached to
- Thermostat call with SW1-1 ON.
- Thermostat call with SW1-6 ON.
- SW1-1 and SW1-6both ON.
- Two different furnace models twinned.
RELAY DID NOT CLOSE OR
31 HIGH-HEAT PRESSURE SWITCH OR
the blower motor. Follow the instructions with
the blower control module to make sure the
entire blower motor does not need to be
replaced.
You have an open wire or bad terminal on the
BLUE wire between the furnace control and the
- Control relay may be defective.
- Gas valve is miswired.
- See status code 32.
REOPENED - Check for:
inducer motor has not started within 20
seconds after a call for heat, the inducer
42 INDUCER MOTOR FAULT – Indicates the
NO
blower motor.
Replace the furnace control.
- Proper vent sizing.
- Failed inducer motor.
- Restricted combustion air supply.
motor RPM is outside its valid range of
operation, or the inducer RPM signal was
lost for 5 seconds during operation.
- Improper motor wiring.
Check for:
Connect a DC voltmeter across PL3-4 BLUE
(+) and PL3-2 GREEN (-). Does the voltage
fluctuate as described two steps back?
YES
NO
Does the voltage fluctuate as described in the
previous step?
YES
Replace the blower control module attached to
the blower motor. Follow the instructions with
the blower control module to make sure the
entire blower motor does not need to be
replaced.
—17—
SER VICE TRAINING
Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including:
• Unit Familiarization • Maintenance
• Installation Overview • Operating Sequence A large selection of product, theory, and skills programs is available, using popular video-based formats and materials. All include video and/or slides, plus companion book.
Classroom Service Training plus "hands-on" the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting, fewer callbacks. Course descriptions and schedules are in our catalog.
CALL FOR FREE CATALOG 1-800-644-5544
[ ] Packaged Service Training [ ] Classroom Service Training
A94328
—18—
—19—
© 2004 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231
—20—
Printed in U.S.A. SP0564 Catalog No. 5335-523
Loading...