Bryan Boilers RV500, RV550, RV600, RV800, RV700 User Manual

4 (1)
Bryan Boilers RV500, RV550, RV600, RV800, RV700 User Manual

RV-KD SERIES FORCED DRAFT 15# & 150# STEAM BOILERS (RV450-RV800)

EFFECTIVE DATE:

8/11/03

REPLACES:

 

 

D

 

11 1/4" TYP

A

 

H

(28.57)

B

 

 

 

 

V

 

 

18"

 

C

 

(45.72)

 

 

BURNER

55"

 

 

SERVICE AREA

 

 

 

(139.7)

 

 

48"

11

 

 

(121.9)

14"

 

 

 

(35.6)

 

 

 

 

 

32"

MINIMUM TUBE

 

 

(81.3)

REMOVAL CLEARANCE

NOTES:

1.ALL DIMENSIONS ARE IN INCHES. THOSE IN PARENTHESES ARE CENTIMETERS.

2.LOCATION DIMENSIONS

ARE ALL ±1/2".

3.GAS TRAIN, CONTROL AND BURNER CONFIGURATION WILL VARY DEPENDING ON JOB SPECIFICATIONS & CONDITIONS.

4.DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE. CONSULT FACTORY FOR CERTIFIED DIMENSIONS.

5.ALL FLANGES ARE 150# UNLESS OTHERWISE NOTED.

 

PLAN VIEW

 

 

4

2

 

 

 

G

17

7

 

 

6

16

 

 

 

5

10

79 1/2"

 

 

 

7

(201.9)

 

 

13

 

 

X

7 1/2"

33 1/2"

(19.1)

(85.1)

 

 

12

 

 

 

18

 

REAR VIEW

LEFT SIDE VIEW

 

 

19

 

3

1

9

 

 

14

 

104 3/4"

 

(266.1)

8

100 1/4"

(254.6)

 

85 1/8"

15

(216.2)

 

7

 

FRONT VIEW

1. L.W.C.O./PUMP CONTROL - 157

6. SURFACE BLOWOFF 1" NPT

11. WIDTH OVER BASE

16. FEEDWATER CONN. 2" NPT

2. PROBE TYPE AUX. L.W.C.O.

7. CLNOUT./INSP. OPNG.-1 1/2"NPT

12. COMB. CHAMBER DRAIN 1" NPT

17. LIFTING LUGS

3. PRESSURE CONTROLS

8. NORMAL BOILER WATER LEVEL

13. OIL CONNECTION

18. JACKET ACCESS PANELS

4. RELIEF VALVE(S)

9. ELEC. ENCLOSURE-

14. HEIGHT OVER FLOW NOZZLE

19. PRESSURE GAUGE

 

5. FORCED DRAFT BURNER

10. FLAME OBSERVATION PORT

15. HEIGHT OVER JACKET

 

 

 

 

 

BOILER MODEL

 

RV450

RV500

RV550

RV600

RV700

RV800

 

 

 

 

 

 

 

 

 

A-LENGTH OVER JACKET

 

120 1/2"

130 1/4"

143 1/4"

152 3/4"

175 1/4"

197 3/4"

 

 

(306.1)

(330.8)

(363.9)

(388.0)

(445.1)

(502.3)

 

 

 

 

 

 

 

 

 

 

 

 

 

B-FLUE LOCATION

 

18 3/4"

18 3/4"

18 3/4"

18 3/4"

20 3/4"

20 3/4"

 

 

(47.6)

(47.6)

(47.6)

(47.6)

(52.7)

(52.7)

 

 

 

 

 

 

 

 

 

 

C-FLUE DIAMETER

 

16"

16"

16"

16"

20"

20"

 

 

(40.6)

(40.6)

(40.6)

(40.6)

(50.8)

(50.8)

 

 

 

 

 

 

 

 

 

 

D-LENGTH OVER BASE

 

164 7/16"

174 1/8"

187"

196 5/8"

225 7/8"

248 3/8"

 

 

(417.6)

(442.2)

(474.9)

(499.4)

(573.7)

(630.8)

 

 

 

 

 

 

 

 

 

 

 

15 PSI

8" FLG

8" FLG

10" FLG

10" FLG

10" FLG

10" FLG

 

(20.3)

(20.3)

(25.4)

(25.4)

(25.4)

(25.4)

 

G-SUPPLY NOZZLE SIZE

 

 

 

 

 

 

 

 

 

 

150 PSI

6" FLG

6" FLG

6" FLG

6" FLG

6" FLG

6" FLG

 

 

(15.2)

(15.2)

(15.2)

(15.2)

(15.2)

(15.2)

 

 

 

 

 

 

 

 

 

 

 

 

 

H-BURNER EXTENSION

CONSULT FACTORY FOR BURNER EXTENSION APPLICATIONS

 

 

 

 

 

 

 

 

 

 

V-SUPPLY NOZZLE LOC.

 

59 13/16"

64 3/8"

71 1/16"

75 7/8"

87 1/8"

98 3/8"

 

(151.9)

(164.1)

(180.4)

(192.7)

(221.2)

(249.8)

 

 

 

 

 

 

 

 

 

15 PSI

1 1/2"

1 1/2"

2"

2"

2"

2"

X-BLOWDOWN CONNECTION

 

(3.8)

(3.8)

(5.1)

(5.1)

(5.1)

(5.1)

150 PSI

1"

1"

1"

1"

1"

1"

 

 

 

(2.54)

(2.54)

(2.54)

(2.54)

(2.54)

(2.54)

 

 

 

 

 

 

 

 

BRYAN BOILERS

783 NORTH CHILI AVE

PERU, INDIANA 46970

ORDER NO.:

 

 

 

ORDER REV. NO.:

 

 

 

FORM NO.:

2169