Bryan Boilers CLM-300-W-GI, CLM-150-S150-GI User Manual

0 (0)
Bryan “Flexible Water Tube”
CLM Series
Steam & Water Boilers
900,000 to 3,000,000 BTUH
Atmospheric gas fi red
Form No. 1920
(Rev. 02/08)
Water Boiler
CLM-300-W-GI
BRYAN® BOILERS
Originators of the “Flexible Water Tube” design
Steam Boiler
High effi ciency hot water and steam boilers for commercial and industrial applications
Bryan fl exible tube boilers are ideally suited for both hot water and steam space heating systems as well as either high or low pressure process steam. In a range of sizes from 900,000 to 3,000,000 BTUH in­put, Bryan CLM series fl exible tube boilers are ideal for many commercial, institutional and industrial applications. These include healthcare facilities; schools; apartments; churches; offi ce buildings; correctional facilities; airports; sewage treatment plants; golf, tennis and fi tness clubs. Hospitals, dairies, restaurants, laundries, dry cleaners, food processing, tire recapping and metal plating are just a few of the many applications. All Bryan boilers are built in accor­dance with the requirements of the ASME Boiler and Pressure Vessel Code.
Effi cient “Flexible Water Tube” design
The Bryan bent water tube provides rapid internal circulation — for maximum heat transfer and operating effi ciency.
Easily replaceable tubes
Tubes are easily removable and replaceable without welding or rolling. Little service space is required.
No “Thermal Shock”
The fl exibility of the bent water tube design elimi­nates all possible damage from "Thermal Shock" and from stresses caused by poor or unequal internal circulation. This is particularly important with forced hot water heating systems designed for higher tem­peratures and greater temperature drops.
Steam Boilers: Section IV or I
Steam release area
Large, full-size steam drum provides for dry steam and stable water level.
High or low pressure construction
Boiler is constructed as standard for 15 psi or 150 psi maximum working pressure. Also available for higher pressures to 300 psi.
Water Boilers: Section IV
High or low pressure construction
Boiler is constructed as standard for 160 psi maximum working pressure at 230°F operating temperature and 250°F design temperature. Also available for higher pressures to 250 psi, at 285°F operating temperature and 300°F design temperature.
Natural internal circulation
The water tube design and the large downcomer legs provide adequate internal circula­tion without concern over exterior pumping condi­tions. Low pressure drop through boiler.
Compact — minimum fl oor space
Requires less floor space than most boilers, minimum boiler room size. Since the tubes can be removed from one side, the boilers are available with right or left hand construction for common tube removal, further minimizing space needs. Shipped completely assembled and wired. Units can also be shipped "Knocked Down" for on-site assembly.
Bryan CLM Series Boiler Specifi cations
NOMINAL OUTPUT STEAM HEATING APPROX.
BOILER INPUT MODEL MBH (KW)
CLM-90 900 (264) 720 (211) 21 (206) 742 (337) 110 (10.2) 1,450 (658) CLM-120 1,200 (352) 960 (281) 29 (284) 990 (449) 145 (13.5) 1,750 (794) CLM-150 1,500 (440) 1,200 (352) 36 (353) 1,237 (561) 180 (16.7) 2,050 (930) CLM-180 1,800 (527) 1,440 (422) 43 (421) 1,485 (674) 215 (20.0) 2,350 (1,066) CLM-210 2,100 (615) 1,680 (492) 50 (490) 1,732 (786) 251 (23.3) 2,650 (1,202) CLM-240 2,400 (703) 1,920 (563) 57 (559) 1,979 (898) 287 (26.7) 2,950 (1,338) CLM-270 2,700 (791) 2,160 (633) 64 (627) 2,227 (1,010) 322 (29.9) 3,500 (1,588) CLM-300 3,000 (879) 2,400 (703) 72 (706) 2,474 (1,122) 360 (33.5) 3,950 (1,792)
NOTES: * Lbs. steam per hour from and at 212°F.
MBH (KW) BHP LBS/HR* SQ. FT. (M²) LBS. (KG)
OUTPUT SURFACE SHIP WT.
Loading...