Broan RMDD3004, RMDD4804EX, RMDD4804, RMDD3004EX Installation Manual

Downdraft Ventilators
!
MODEL WIDTH BLOWER RMDD3004 30" 500 cfm Internal RMDD3604 36" 500 cfm Internal RMDD4804 48" 500 cfm Internal RMDD3004EX 30" Models 331H, 332H, 335, 336 HLB3, HLB6, HLB9, and HLB11 External (purchase separately) RMDD3604EX 36" Models 331H, 332H, 335, 336 HLB3, HLB6, HLB9, and HLB11 External (purchase separately) RMDD4804EX 48" Models 331H, 332H, 335, 336 HLB3, HLB6, HLB9, and HLB11 External (purchase separately)
WARNING - To reduce the risk of burns or ignition of clothing by reaching across burners, the downdraft remote control MUST
be mounted in the countertop - at least 4" from the burners. See "INSTALL COOKTOP" section on page 8.
READ AND SAVE THESE INSTRUCTIONS
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
1. Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer at the address or telephone number in the warranty.
2. Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power from be­ing switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
3. Installation work and electrical wiring must be done by a qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction codes and standards.
4. Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent backdrafting. Follow the heating equipment manufacturer’s guideline and safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
5. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
6. Ducted fans must always be vented to the outdoors.
7. To reduce the risk of fire, use only metal ductwork.
8. Do not install this product with the activating switch directly behind a burner or element. Minimum distance between the switch and the edge of the burner should be 4 inches.
9. Loose-fitting or hanging clothing should never be worn when operating this appliance. They may be ignited by burners/elements on cooktop.
10. Children should not be left alone or unattended in the area where this appliance is in use.
11. This unit must be grounded.
TO REDUCE THE RISK OF A RANGE TOP GREASE FIRE:
a) Never leave surface units unattended at high settings. Boilovers cause smoking and greasy spillovers that may ignite. Heat oils slowly on low or medium settings.
b) Always turn hood ON when cooking at high heat or when cooking flaming foods.
c) Clean ventilating fans frequently. Grease should not be allowed to accumulate on fan or filter.
d) Use proper pan size. Always use cookware appropriate for the size of the surface element.
NOTE: Model RMDDRBK Remote Up/Down
Control sold separately.
INSTALLER:
Save this manual for Electrical
Inspector and Homeowner to use.
WARNING
TO REDUCE THE RISK OF INJURY TO PERSONS IN THE EVENT OF A RANGE TOP GREASE FIRE, OBSERVE THE FOLLOWING
1. SMOTHER FLAMES with a close-fitting lid, cookie sheet, or metal tray, then turn off the burner. BE CAREFUL TO PREVENT BURNS. If the flames do not go out immedi ately, EVACUATE AND CALL THE FIRE DEPARTMENT.
2. NEVER PICK UP A FLAMING PAN - You may be burned.
3. DO NOT USE WATER, including wet dishcloths or towels
- a violent steam explosion will result.
4. Use an extinguisher ONLY if: A. You know you have a Class ABC extinguisher, and you
already know how to operate it.
B. The fire is small and contained in the area where it
started. C. The fire department is being called. D. You can fight the fire with your back to an exit.
a
Based on “Kitchen Firesafety Tips” published by NFPA.
CAUTION
1. For indoor use only.
2. For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.
3. To avoid motor bearing damage and noisy and/or unbalanced impel­lers, keep drywall spray, construction dust, etc. off power unit.
4. Clean filters and grease-laden surfaces frequently.
5. Do not repair or replace any part of this appliance unless specifically recommended in this manual. All other servicing should be done by a qualified technician.
6. Please read specification label on product for further information and requirements.
7. To reduce the risk of fire and electric shock, install this downdraft only with Rangemaster blower models shown below. Other blowers cannot be substituted. (blowers sold separately).
Register your product online at: www.broan.com/register
MODEL WIDTH BLOWER RMDD3004 30" 500 cfm Internal RMDD3604 36" 500 cfm Internal RMDD4804 48" 500 cfm Internal RMDD3004EX 30" External, Model 331H, 332H, 335, 336,
RMDD3604EX 36" External, Model 331H, 332H, 335, 336,
RMDD4804EX 48" External, Model 331H, 332H, 335, 336,
HLB3, HLB6, HLB9, y HLB11 (purchase separately)
HLB3, HLB6, HLB9, y HLB11 (purchase separately)
HLB3, HLB6, HLB9, y HLB11 (purchase separately)
Page 1
a
:
PLANNING
Downdraft Ventilators
Page 2
Internal Blower Installation
This downdraft blower system is designed to be used to exhaust airborne contaminants when cooking with a variety of gas or electric cooktops. It can be mounted in island, peninsula, or conventional wall locations.
This unit can be easily installed following these basic steps:
Cut out the countertop opening.
Mount the unit in the cabi­net.
Connect the ductwork and electrical.
Install the cooktop.
Note: the high level of air flow of this appliance may effect the gas flame on some types of gas cooktops. This is NORMAL and will cause no harm, but can be corrected by lowering the speed of the blower.
TYPICAL INSTALLATION
COUNTER TOP
BLOWER
COOK TOP
GEAR MOTOR COVER
BOX
CHIMNEY TOP
3-1/4" X 10" DUCT CONNECTOR
ELECTRICAL
SPECIFICATIONS
120 VAC • 60 Hz • 4.0 A
AIR VENT
120 VAC GROUNDED OUTLET
External Blower Installation
This downdraft blower system is designed to be used to ex­haust airborne contaminants when cooking with a variety of gas or electric cooktops. It can be mounted in island, peninsula, or conventional wall locations.
This unit can be easily installed following these basic steps:
Cut out the countertop opening.
Mount the unit in the cabinet.
Install Model 331H, 332H, 335, 336, HLB3, HLB6, HLB9, HLB11 External Blower
Connect the ductwork and electrical.
Install the cooktop.
Note: the high level of air flow of this appliance may effect the gas flame on some types of gas cooktops. This is NORMAL and will cause no harm, but can be corrected by lowering the speed of the blower.
TYPICAL INSTALLATION
COUNTER TOP
BLOWER
COOK TOP
GEAR MOTOR COVER
BOX
CHIMNEY TOP
AIR VENT
120 VAC GROUNDED OUTLET
3-1/4" X 14" DUCT CONNECTOR
ELECTRICAL
SPECIFICATIONS
120 VAC • 60 Hz • 6.0 A (max.)
TAKE MEASUREMENTS
All Units
1. Refer to the cooktop installation instructions for dimensions of cooktop, countertop cut-out, and cabinet requirements. Models RMDD3004 & RMDD3004EX will fit in most 30" wide cabinets. Models RMDD3604 & RMDD3604EX will fit in most 36" wide cabinets. Models RMDD4804 & RMDD4804EX will fit in most 48" wide cabinets. However, it is recommended that oversized cabinets be used for easier installation.
2. Cooktop depth can vary greatly from one to another. This may cause the fit of these two appliances to be rather tight.
Pay special attention to the areas of potential interference high­lighted above. A countertop with (A) a raised lip and/or (B) a backsplash may not allow enough flat countertop for a proper installation. Note that 2-3/8" of flat countertop is required behind cooktop and that 1-3/4" is necessary between the back edge of the cooktop and the inside of cabinet back.
1-3/4"
2
2-3/8"
Downdraft Ventilators
TAKE MEASUREMENTS (CONTINUED)
Internal Blower Installation External Blower Installation
Page 3
SIDE VIEW
OF DOWNDRAFT
SIDE VIEW
OF DOWNDRAFT
PLAN THE DUCTWORK
Internal Blower Installation External Blower Installation
1. The interior down­draft blower system is designed for use with 3-1/4" x 10" ductwork (can be transitioned to 6" round). Three different discharge directions are avail­able with side-to­side adjustment for accurate alignment of ductwork.
2. For best performance: Choose the ducting option which allows the shortest length of ductwork and a minimum number of elbows and transi­tions. Check location of floor joists, wall studs, electrical wiring or plumbing for possible interference.
LEFT
DISCHARGE
DISCHARGE
DOWN DISCHARGE
RIGHT
1. The exterior down­draft blower system is designed for use with 3-1/4" x 14"rectan­gular ductwork (can be transitioned to 8" or 10" round). Three different discharge directions are avail­able with side-to­side adjustment for accurate alignment of ductwork.
2. For best performance: Choose the ducting option which allows the shortest length of ductwork and a minimum number of elbows and transitions. Check location of floor joists, wall studs, electrical wiring or plumbing for possible interference.
LEFT
DISCHARGE
RIGHT
DISCHARGE
DOWN DISCHARGE
6" ROUND
ELBOW
EQUALS 8 FT. OF STRAIGHT DUCT
3. The system will operate most efficiently when the ductwork does not exceed 40 feet of equivalent duct. The chart, above, shows equivalent feet of elbows and transitions. The number of feet of straight duct plus the equivalent feet of transitions and/or elbows to be used should equal 40 feet or less.
NOTE: The equivalent feet of various roof and wall caps has been taken into consideration. Do not include them in this calculation.
3-1/4" X 10" TO 6" RD. TRANSITION
EQUALS 2 FT. OF STRAIGHT DUCT
3-1/4" X 10"
90O ELBOW
EQUALS 14 FT. OF
STRAIGHT DUCT
8" ROUND ELBOW
EQUALS 11 FT. OF
STRAIGHT DUCT
3. The system will operate most efficiently when the ductwork does not exceed 40 feet of equivalent duct. The chart, above, shows equivalent feet of elbows and transitions. The number of feet of straight duct plus the equivalent feet of transitions and/or elbows to be used should equal 40 feet or less.
NOTE: The equivalent feet of various roof and wall caps has been taken into consideration. Do not include them in this calculation.
3-1/4" X 14" TO 8" RD. TRANSITION
EQUALS 5 FT. OF STRAIGHT DUCT
3-1/4" X 14" 90O ELBOW
EQUALS 19 FT. OF
STRAIGHT DUCT
CENTER LINE
FOR EXTERNAL BLOWER)
DUCT
PLAN THE CABINET CUTOUTS
"
!
Downdraft Ventilators
Page 4
Blower Installation
BEFORE CUTTING HOLE IN CABINET FOR DUCTWORK,
check for interference with floor
joists, wall studs, electrical wir-
BOTTOM
DISCHARGE
CAUTION:
ing, or plumbing.
CENTER
LINES OF
CUTOUT
10¼" x 3½"
CUTOUT
(14¼" x 3½"
FOR
EXTERNAL
BLOWER)
22
1
/
(19"
8
FOR
EXTERNAL
BLOWER)
5½"
(4¼" FOR
EXTERNAL
BLOWER)
LEFT SIDE
DISCHARGE
"
CENTER LINE OF COUNTER
CUTOUT
OF DUCT
CUTOUT
CENTER LINE OF COUNTER
CUTOUT
(5" MAX.
FOR EXTERNA
BLOWER)
10¼" x 3½"
CUTOUT
(14¼" x 3½"
¼" to 7¾"
(2½" MAX.
FOR
L
EXTERNAL
BLOWER)
RIGHT SIDE
DISCHARGE
5½"
(4¼" FOR
EXTERNAL
BLOWER)
CENTER LINE OF COUNTER
CUTOUT
"
3
8
/
16 (21½" FOR EXTERNAL BLOWER)
5½"
(4¼" FOR
EXTERNAL
BLOWER)
CENTER
LINES OF
DUCT
CUTOUT
10¼" x 3½"
CUTOUT
(14¼" X 3½
FOR
EXTERNAL
BLOWER)
Downdraft Ventilators
PLAN THE WIRING
Internal Blower Installation External Blower Installation
Page 5
1. The Internal Downdraft Blower system draws 4 AMPS and requires a 120 VAC, 60 Hz circuit.
2. The unit has a 18 in. long power cord with a 3-pronged plug. Plan to provide a grounded outlet in a location which will allow the unit’s power cord to reach.
IMPORTANT - LOCATION OF ELECTRICAL OUTLET:
If Model RMDD3004 is being installed in a 30" wide cabi­net...
or Model RMDD3604 is being installed in a 36" wide cabinet...
or Model RMDD4804 is being installed in a 48" wide cabinet...
...the outlet cannot be located on the back wall
of cabinet.
In these cases, the width of the downdraft covers nearly the entire width of the back wall of the cabinet. So you must either:
mount the electrical box to a side wall or cabinet floor - at least 12 inches from the back wall.
mount the electrical box to a wall stud behind the cabinet - where it will not be covered by the downdraft. Then provide a clearance hole in the back wall of the cabinet.
PREPARE THE DOWNDRAFT
1. The External Downdraft Blower system draws 6 AMPS and requires a 120 VAC, 60 Hz circuit.
2. The unit has a 18 in. long power cord with a 3-pronged plug. Plan to provide a grounded outlet in a location which will allow the unit’s power cord to reach.
IMPORTANT - LOCATION OF ELECTRICAL OUTLET:
If Model RMDD3004EX is being installed in a 30" wide cabinet...
or Model RMDD3604EX is being installed in a 36" wide cabinet...
or Model RMDD4804EX is being installed in a 48" wide cabinet...
...the outlet cannot be located on the back wall
of cabinet.
In these cases, the width of the downdraft covers nearly the entire width of the back wall of the cabinet. So you must either:
mount the electrical box to a side wall or cabinet floor - at least 12 inches from the back wall.
mount the electrical box to a wall stud behind the cabinet - where it will not be covered by the downdraft. Then provide a clearance hole in the back wall of the cabinet.
Blower Duct Connection Installation (all blowers)
The downdraft is shipped with duct connector pointing toward the bottom of the unit. If you wish to change this orientation, follow the steps below:
1. Place the downdraft on its back on a table of flat work surface.
2. Remove the 4 nuts and 2 clamp channels.
3. Remove 2 screws and the gear motor cover.
4. Carefully position the blower under the bottom flange of the downdraft with the 3¼" x 10" discharge (3¼" x 14" for exterior or in-line blower) pointed in the desired direction.
5. Connect motor plug.
6. Replace the gear motor cover and 2 sheet metal screws.
7. Replace the 2 clamp channels and start the 4 nuts, do not tighten.
8. Slide blower left of right to desired position. Use cover plate (supplied) to close up any open space.
9. Tighten 4 nuts to secure top of blower. Use additional screws (supplied) through bottom flange to secure bottom in blower.
CLAMP
CHANNELS
SCREWS
GEARMOTOR
COVER
3¼" X 10" DISCHARGE
(3¼" X 14" FOR EXTERNAL BLOWER)
NUTS
BLOWER
MOTOR
PLUG
ADDITIONAL
SCREWS
BOTTOM
FLANGE
COVER
PLATE
CUT COUNTERTOP OPENING
All Units
1. Lay out and cut the cooktop cut-out far enough FORWARD so
downdraft will fit behind it.
2. Set cooktop in place and slide it as far forward as possible.
Center and square it with edges of countertop.
Downdraft Ventilators
Page 6
3. Place the plastic template against the back flange of the cook-
top and center it. Trace around template to mark the downdraft opening.
4. Remove cooktop from countertop.
5. Cut downdraft opening. Be careful not to chip edges of coun-
tertop.
MOUNT THE UNIT
!
All Units
1. Set downdraft into opening. Extend leveling brackets to floor
of cabinet so downdraft sits straight. (Note: Leveling brackets can be removed and re-attached in other positions. Bottom flange may have to face inward in tight cabinet installations.)
2. Secure the downdraft to the countertop as follows: Hold the downdraft against the back of countertop cut-out and tighten­ing the two mounting screws (one on each end of unit) on underside of countertop. Use a wood shim between screw and underside of granite countertops.
3. Screw leveling brackets to bottom of cabinet. Tighten screws holding leveling bracket to unit on each side.
INSTALL DUCTWORK
Downdraft Ventilators
Page 7
MOUNTING SCREWS
LEVELING BRACKET -
FLANGE FACING OUT
LEVELING BRACKET -
FLANGE FACING IN
Blower Installation
CAUTION: BEFORE CUTTING HOLE IN CABINET FOR DUCTWORK,
check for interference with floor
joists, wall studs, electrical wir-
ing, or plumbing.
1. Cut hole in cabinet as well as holes in wall or floor as neces­sary.
2. Mount the roof or wall cap and work back towards the cabinet, attaching all ductwork, elbows and transitions as previously planned. Tape all ductwork connections to make them secure and air tight.
3. Connect ductwork (and transition, if required) to downdraft. If necessary, LOOSEN nuts and screws that hold the blower in place, and slide blower left or right to meet ductwork. Re­tighten screws and nuts.
Note: A 3¼" x 10" collar (3¼" x 14" collar for external blower) is provided for installers who prefer to rivet the ductwork to the unit. This will allow blower to be removed and replaced easily in service situations without disturbing ductwork.
BLOWER
SCREWS
COLLAR
3¼" X 10" TO 6" RD.
TRANSITION
(3¼" X 14" TO 8"
RD. TRANSITION
FOR EXTERNAL
BLOWER
8" RD. ELBOW
& DUCTWORK
INSTALL ELECTRICAL WIRING
!
!
Downdraft Ventilators
Page 8
Internal Blower Installation
CAUTION: All electrical wiring should be done
by a qualified person(s) in accordance with all
applicable codes and standards.
1. Mount a standard wiring box, with 3-pronged receptacle, inside the cabinet. Make sure the downdraft's power cord can easily reach it.
2. Run appropriate power cable into cabinet and connect it to receptacle.
3. Plug the downdraft's power cord into the outlet. Make sure that the power cord is routed away from the heat generated by the cooktop.
INSTALL COOKTOP
All Units
External Blower Installation
CAUTION: All electrical wiring should be done
by a qualified person(s) in accordance with all
applicable codes and standards.
1. Mount a standard wiring box, with 3-pronged grounded recep­tacle, inside the kitchen cabinet. Make sure the unit's power cord can easily reach it.
2. Run appropriate power cable into cabinet and connect it to electrical box and receptacle.
3. External blower may not exceed 6.0 Amp rating.
4. Run 2-wire plus ground power cable from the external blower to wiring box on adaptor plate. Remove wiring box cover.
5. Connect wiring harness to power cable from external blower. Wire black to black, white to white, and green to green or bare wire.
6. Replace wiring box cover.
7. Plug the downdraft's power cord into outlet. Make sure that the power cord is routed away from the heat generated by the cooktop.
1. Align the cooktop with the downdraft and fasten cooktop in place.
Note: Accurate alignment of cooktop and downdraft is necessary to ensure that there is no interference when air vent is raised and lowered. There should be a gap of 1/32" - 1/16" between the back of the cooktop and the front of the downdraft cover.
COOKTOP
UP / DOWN
CONTROL
COUNTERTOP
Note: The downdraft up/down control must be mounted into the coun-
tertop, at least 4" from the cooktop.
Downdraft Ventilators
ON DOTTED LINE
2.000
.750
.750
REMOTE UP/DOWN CONTROL INSTALLATION (OPTIONAL)
All Units
When to use the Remote UP/DOWN Control
The Remote UP/DOWN Control should be used when your cooktop has a burner that is within 4 inches of the UP/DOWN Button on the downdraft chimney.
The Remote UP/DOWN Control can be used for convenient UP/ DOWN operation of the downdraft chimney (even when a burner is more than 4 inches from the UP/DOWN Button of the downdraft chimney).
How to use the Remote UP/DOWN Control
Do not place the remote control where it will interfere with cook­ing, where hot pans could be set, or where hot liquids could be spilled on the control.
The Remote UP/DOWN Control disables the UP/DOWN function of the UP/DOWN Button on the downdraft chimney.
Installation
1. Using the template at right, lay out the 3-hole pattern on the counter top. Mark the centers of the three holes to be drilled.
2. Carefully drill the three holes through the counter top. Be careful not to damage or chip the counter top surface when drilling the holes.
3. Remove the control from the plastic bag. Line the control up with the three holes and position the control so it is parallel with the front of the counter top.
4. Remove the two nylon thumbnuts from the plastic bag and thread onto the two studs on the control from below the counter top. Hand tighten only.
WARNING: To reduce the risk of burns or ignition of clothing by reaching across burners, the remote control must be mounted at least 4" away from any cook top burner.
5. Remove the blower, clamp channels, and gearmotor cover from downdraft (see"Prepare the Downdraft" on page 5). Remove the large panel to expose the downdraft's wiring.
.625
.438 DIA. HOLE
1.000
CUT OUT ON DOTTED LINE
WIRING
BOX
2.000
.625
.250 DIA.
HOLES
CUT OUT
Page 9
WIRING
BOX
LOWER
RIGHT
SIDE
OF
DOWNDRAFT
CABINET
FLOOR
6. At the lower right hand corner of downdraft, unplug the cable from the left side of the wiring box.
REMOTE
CABLE
7. Remove remote cable from the plastic bag and plug into back of control from below counter top. Route cable through cabinet to lower right hand corner of downdraft and through the clear­ance holes in the side of downdraft and wiring box. Plug cable into circuit board plug, as shown.
8. Stuff excess cable out of the way, secure the cable so it is not damaged by items stored in the cabinet, and reassemble downdraft.
USE AND CARE
All Units
WARNING: Always disconnect electric power supply before cleaning and/or servicing unit.
Downdraft Ventilators
Page 10
Cleaning
Use a mild detergent suitable for painted surfaces. DO NOT USE ABRASIVE CLOTH, STEEL WOOL PADS, OR SCOURING POW­DERS. Vacuum blower to clean. Do not immerse blower in water.
Wash the 2 aluminum/stainless steel grease filters in a mild de­tergent solution or a dishwasher. Remove them from the air vent by grasping the tab at the top of each filter.
Always turn the downdraft blower on before you begin cooking to establish an air flow in the kitchen. Let the blower run for a few minutes to clean the air after you turn the cooktop off. This will keep the whole kitchen cleaner and brighter. The activating switch is pressed and the air vent rises.
BACKSIDE OF
REMOTE SWITCH
TEMPLATE
Servicing
It may be necessary to remove the downdraft blower system from the cabinet in order to service components such as the blower motor or air vent mechanism.
Disconnect power to the cooktop and remove it first. Reverse the steps under “MOUNT THE UNIT” to remove the downdraft from the cabinet.
OPERATION
All Units
Downdraft Ventilators
Page 11
Turn the downdraft blower ON by pressing down on the activating switch. The air vent will rise.
KNOB
The blower can be turned ON or OFF and its speed can be adjusted with the recessed knob on the right side of the air vent.
WIRING DIAGRAM
Turn the downdraft blower OFF by pressing the activating switch again. The air vent will go down and the blower will shut OFF.
Note: For most convenient operation, set the blower to your favo­rite speed. The blower will come on to this speed whenever the activating switch is pressed and the air vent rises.
Heat Sentry
When chimney is UP and blower is ON (at any speed) or OFF: If the exhaust temperature becomes higher than expected, the Heat
Sentry mode will activate and increase the blower speed to HIGH. Lowering the chimney will turn blower OFF - even if Heat Sentry
is active.
Downdraft Ventilators
Page 12
SERVICE PARTSWARRANTY
BROAN ONE YEAR LIMITED WARRANTY
Broan warrants to the original consumer purchaser of its products that such products will be free from defects in materials or workmanship for a period of one year from the date of original purchase. THERE ARE NO OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, IMPLIED WARRANTIES OR MERCHANT ABILITY OR FITNESS FOR A PARTICU­LAR PURPOSE.
During this one-year period, Broan will, at its option, repair or replace, without charge, any product or part which is found to be defective under normal use and service.
THIS WARRANTY DOES NOT EXTEND TO FLUO­RESCENT LAMP STARTERS, TUBES, HALOGEN AND INCANDESCENDT BULBS. This warranty does not cover (a) normal maintenance and service or (b) any products or parts which have been subject to misuse, negligence, accident, improper maintenance or repair (other than by Broan), faulty installation or installation contrary to recommended installation instructions.
The duration of any implied warranty is limited to the one-year period as specified for the express warranty. Some states do not allow limitation on how long an implied warranty lasts, so the above limitation may not apply to you.
BROAN’S OBLIGATION TO REPAIR OR REPLACE, AT BROAN’S OPTION, SHALL BE THE PURCHASER’S SOLE AND EXCLUSIVE REMEDY UNDER THIS WARRANTY. BROAN SHALL NOT BE LIABLE FOR INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAM­AGES ARISING OUT OF OR IN CONNECTION WITH PRODUCT USE OR PERFORMANCE.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you.
This warranty gives you specific legal rights, and you may also have other rights, which vary from state to state. This warranty supersedes all prior warranties.
To qualify for warranty service, you must (a) notify Broan at the address or telephone number below, (b) give the model number and part identification and (c) describe the nature of any defect in the product or part. At the time of requesting warranty service, you must present evidence of the original purchase date.
Broan-NuTone LLC Hartford, Wisconsin www.broan.com 800-558-1711
Replacement parts can now be
ordered on our website.
Please visit us at www.Broan.com
KEY 30N 36N 48N NO. WIDTH WIDTH WIDTH DESCRIPTION
1 97018397 97018398 97018399 TOP COVER 2 99140195 99140195 99140195 FILTER SPRING 3 99230345 99230345 99230345 POP RIVET 4 97018526 97018527 97018528 CHIMNEY ASSEMBLY 5 97015874 97015874 97015874 END CAP RH 6 98009358 98009358 98009358 END CAP LR 7 97015973 97015973 97015973 MACHINED CHIMNEY SLIDE 8 98010013 98010013 98010013 MACHINED AIRBOX SLIDE 9 99160421 99160421 99160421 SCREW RHM 8-32 x .375 10 99160419 99160419 99160419 SCREW 8-32 x ..500 PHL 11 99271218 99271218 99271218 GROUND WIRE 12 99150471 99150471 99150471 SCREW 10-32 x .500 TYP CA PH 13 97015841 97015842 97015843 FILTER 14 99710032 99710032 99710032 SPACER 15 99111184 99111184 99111184 SLIDE STRIPS 16 97015974 97015975 97015976 AIRBOX WELDMENT 17 99271210 99271210 99271210 CORD SET 18 99400060 99400060 99400060 STRAIN RELIEF BUSHING 19 99271295 99271295 99271295 WIRE HARNESS 20 99271292 99271292 99271292 SWITCH ASSEMBLY 21 99271291 99271291 99271291 CONTROL BOARD 22 97018525 97018525 97018525 CRANK ASSEMBLY 23 97017023 97017023 97017023 GEAR MOTOR BRACKET 24 97017039 97017035 97017036 GEAR MOTOR KIT INTERNAL BLOWER MODELS (INCLUDES ITEM 23 & 27 ON 36N & 48N MODELS) 97017059 97017037 97017038 GEAR MOTOR KIT EXTERNAL BLOWER MODELS (INCLUDES ITEM 23 & 27 ON 36N & 48N MODELS) 26 98010798 98010799 98010801 FRONT AIRBOX BOTTOM 27 97017045 97017041 97017042 GEAR MOTOR COVER INTERNAL BLOWER MODELS 97017046 97017043 97017044 GEAR MOTOR COVER EXTERNAL BLOWER MODELS 28 98010802 98010803 98010803 AIRBOX OPENING COVER 29 98010804 98010804 98010824 AIRBOX CLAMP 30 99260488 99260488 99260488 WHIZ NUT 10-24 31 97018476 97018476 97018476 SCROLL BOX ASSEMBLY 32 98010809 33 98008157 98008157 98008157 CAPACITOR CLAMP 34 98010810 98010810 98010810 EXT - SCROLL BOX WELDMENT 35 99080362 99080362 99080362 MOTOR W/CAPACITOR 36 99020247 99020247 99020247 BLOWER WHEEL 37 99100484 99100484 99100484 MOTOR MOUNT ISOLATOR 38 99260477 99260477 99260477 WHIZ NUT 1/4-20 39 99030323 99030323 99030323 THERMOSTAT 40 97016974 97016974 97016974 ADAPTOR PLATE 41 98010005 98010005 98010005 OUTLET PLATE 42 99271304 99271304 99271304 WIRE HARNESS 43 99400042 99400042 99400042 STRAIN RELIEF BUSHING 44 99271296 99271296 99271296 UP/DOWN BUTTON HARNESS 45 99271306 99271306 99271306 THERMOSTAT WIRE HARNESS 46 98010010 98010010 98010010 THERMOSTAT MOUNTING BRACKET
98010809 98010809 SCROLL BOX COVER
Loading...
+ 28 hidden pages