Broan MP280 Instructions Manual

MODEL MP280 MULTI-PORT IN-LINE VENTILATOR
READ AND SAVE THESE INSTRUCTIONS
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOW­ING:
1. Use this unit only in the manner intended by the manu­facturer. If you have questions, contact the manufac­turer at the address or telephone number listed below the warranty.
2. Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
3. Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction codes and standards.
4. Sufficient air is needed for proper combustion and exhausing of gases through the flue (chimney) of fuel burning equipment to prevent backdrafting. Follow the heating equipment manufacturer’s guideline and safety standards such as those published by the National Fire
WARNING
Protection Association (NFPA), and the American Soci­ety for Heating, Refrigeration and Air Conditioning Engi­neers (ASHRAE), and the local code authorities.
5. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
6. Ducted fans must always be vented to the outdoors.
7. This unit must be grounded.
CAUTION
1. For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.
2. To avoid motor bearing damage and noisy and/or un­balanced impellers, keep drywall spray, construction dust, etc. off power unit.
3. If ventilator is installed in an unconditioned space (such as an attic): Surround the ventilator with thermal insulation - to minimize possible condensation.
4. Please read specification label on product for further information and requirements.
PLAN THE INSTALLATION
Adequate ventilation requires that both intermittent and continuous contamination be controlled.
Intermittent ventilation must be provided in the bathroom and kitchen. The bathroom requires 8 air changes per hour. (Multiply bathroom sq. footage by 1.1 for proper fan sizing) The kitchen requires a minimum of 150 CFM capacity (71 l/s) when a ducted range hood is used. If a kitchen fan is used, determine fan capacity by multiplying the room's sq. footage by 2. All are run intermittently to control pollution at the source.
Continuous ventilation, while the house is occupied, pro­vides the flow of fresh air for good indoor air quality.
This ventilator is intended to for continuous operation, supplying fresh air to the entire house.
RECOMMENDED VENTILATOR SIZING
DWELLING SIZE RANGE (Sq. Ftg.)
(include finished basement area)
MODEL MP280
*AC/HR = Air Changes per Hour. Based on 8' ceilings. SQ. FT. x 10.764 = M
.50 AC/HR* .35 AC/HR* .30 AC/HR*
4200 6000 7000
2
PLAN THE INSTALLATION
LOCATION OF DIFFUSERS & INLETS
FRESH AIR
STALE AIR
VENTILATOR
DIFFUSER
INLET
FRESH AIR
AIR FLOW IN TYPICAL INSTALLATION
VENTILATOR
The ventilator exhausts stale air. There are normally suffi­cient natural intake openings into a dwelling to admit fresh outside air to be drawn in to replace the stale air. For better control, fresh air inlets may be used.
The ventilator should be centrally located to keep ductwork as short as possible. Locations for the ventilator include: joists in an attic space or the basement, or a wall away from the living areas.
EXHAUST DIFFUSERS
(Available separately) Exhaust diffusers regulate
the flow of fresh air drawn through the house.
Exhaust diffusers should be mounted in the ceil­ings or high on the wall.
For best performance, ex­haust diffusers should be mounted in a central loca­tion. An exhaust diffuser should not be installed near a cooking area. (see figure)
COOKING AREA
Do not install
above or inside
this area
o
45
Cooking
Equipment
o
45
Floor
SINGLE-STORY HOME
DUCTED KITCHEN RANGE HOOD
DIFFUSER
DIFFUSER
FRESH AIR INLETS
DIFFUSER
DUCTED
BATH FAN
FRESH AIR INLETS
TWO-STORY HOME
FRESH AIR INLETS
DIFFUSER
SECOND FLOOR
DUCTED
BATH FAN
FRESH AIR INLETS
DUCTED
KITCHEN RANGE HOOD
FRESH AIR INLETS (Available separately)
For best control of fresh air in a room, install a fresh air inlet. The number of inlet vents depends on the floor plan.
Consider the rooms/areas through which fresh air should flow toward the exhaust diffuser(s).
Vents should be located in outside walls, preferably near the ceiling and approximately the same distance from a diffuser. Vents should be separated from diffusers far enough to allow fresh air to mix with room air before being exhausted.
DIFFUSER
DUCTED
BATH FAN
FRESH AIR INLETS
DIFFUSER
FIRST FLOOR
Loading...
+ 2 hidden pages