MODELS MP100, MP140 & MP200
MULTI-PORT IN-LINE FANS
READ AND SAVE THESE INSTRUCTIONS
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK,
OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
1. Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer at the address or telephone number listed below
the warranty.
2. Before servicing or cleaning unit, switch power off at
service panel and lock the service disconnecting means
to prevent power from being switched on accidentally.
When the service disconnecting means cannot be locked,
securely fasten a prominent warning device, such as a
tag, to the service panel.
3. Installation work and electrical wiring must be done by
qualified person(s) in accordance with all applicable
codes and standards, including fire-rated construction
codes and standards.
4. Sufficient air is needed for proper combustion and
exhausting of gases through the flue (chimney) of fueling
equipment to prevent backdrafting. Follow the heating
equipment manufacturer’s guideline and safety standards such as those published by the National Fire
WARNING
Protection Association (NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
5. When cutting or drilling into wall or ceiling, do not
damage electrical wiring and other hidden utilities.
6. Ducted fans must always be vented to the outdoors.
7. This unit must be grounded.
CAUTION
1. For general ventilating use only. Do not use to exhaust
hazardous or explosive materials and vapors.
2. To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray, construction dust,
etc. off power unit.
3. If ventilator is installed in an unconditioned space
(such as an attic): Surround the ventilator with thermal
insulation - to minimize possible condensation.
4. Please read specification label on product for further
information and requirements.
PLAN THE INSTALLATION
Adequate ventilation requires that both intermittent and
continuous contamination be controlled.
Intermittent ventilation must be provided in the bathroom
and kitchen. The bathroom requires 8 air changes per hour.
(Multiply bathroom sq. footage by 1.1 for proper fan sizing).
The kitchen requires a minimum of 150 CFM capacity (71
l/s) when a ducted range hood is used. If a kitchen fan is
used, determine fan capacity by multiplying the room's sq.
footage by 2. All are run intermittently to control pollution at
the source.
Continuous ventilation, while the house is occupied, provides the flow of fresh air for good indoor air quality.
This ventilator is intended for continuous operation, supplying fresh air to the entire house.
RECOMMENDED VENTILATOR SIZING
DWELLING SIZE RANGE (Sq. Ftg.)
(include finished basement area)
MODEL
MP100
MP140
MP200
*AC/HR = Air Changes per Hour. Based on 8' ceilings.
Square Feet x .093 = Square Meters
.50 AC/HR* .35 AC/HR* .30 AC/HR*
1500 2140 2500
2100 3000 3500
3000 4285 5000
PLAN THE INSTALLATION
STALE
AIR
VENTILATOR
DIFFUSER
FRESH AIR
INLET
LOCATION OF DIFFUSERS & INLETS
SINGLE-STORY HOME
FRESH AIR INLETS
AIR FLOW IN TYPICAL INSTALLATION
VENTILATOR
The ventilator exhausts stale air. There are normally sufficient natural intake openings into a dwelling to admit fresh
outside air to be drawn in to replace the stale air. For better
control, fresh air inlets may be used.
The ventilator should be centrally located to keep ductwork
as short as possible. Locations for the ventilator include:
joists in an attic space or the basement, or a wall away from
the living areas.
EXHAUST
DIFFUSERS
(Available separately)
Exhaust diffusers regulate
the flow of fresh air drawn
through the house.
Exhaust diffusers should
be mounted in the ceilings or high on the wall.
For best performance, exhaust diffusers should be
mounted in a central location. An exhaust diffuser
should not be installed
near a cooking area. (see
figure)
COOKING AREA
Do not install
above or inside
this area
o
45
Cooking
Equipment
o
45
Floor
FRESH
AIR
DUCTED
KITCHEN
RANGE HOOD
DIFFUSER
DIFFUSER
DIFFUSER
DUCTED
BATH FAN
FRESH AIR INLETS
TWO-STORY HOME
FRESH AIR INLETS
DIFFUSER
SECOND
FLOOR
DUCTED
BATH FAN
FRESH AIR INLETS
DUCTED KITCHEN
RANGE HOOD
FRESH AIR INLETS (Available separately)
For best control of fresh air in a room, install a fresh air inlet.
The number of inlet vents depends on the floor plan.
Consider the rooms/areas through which fresh air should
flow toward the exhaust diffuser(s).
Vents should be located in outside walls, preferably near
the ceiling and approximately the same distance from a
diffuser. Vents should be separated from diffusers far
enough to allow fresh air to mix with room air before being
exhausted.
DIFFUSER
DUCTED
BATH FAN
FRESH AIR INLETS
DIFFUSER
FIRST FLOOR
INSTALL FRESH AIR INLETS
CONNECT DUCTWORK
1. Mount all fresh air inlets in chosen locations during
rough-in construction. Follow directions packed with
inlets.
MOUNT THE VENTILATOR
CEILING
JOISTS
FRAMING
OR
FROM
DIFFUSERS
4" ROUND
INSULATED
FLEXIBLE
DUCT
FROM
DIFFUSERS
DUCT
TAPE OR CLAMP
6" ROUND
INSULATED
FLEXIBLE
DUCT
(OUTLET)
TO ROOF OR
WALL CAP
1. Run 4" insulated, flexible ductwork from ventilator inlet
to diffuser location(s) and 6" insulated flexible ductwork
from ventilator outlet to roof or wall cap.Outlet side is
marked with a label.
2. To minimize condensation inside of ductwork in the attic, cover ductwork with additional insulation. Also, avoid
forming condensation traps in the ductwork runs.
3. Seal ductwork to ventilator and roof or wall cap with duct
tape or clamp (available separately).
4.
If some ventilator inlets will not be used:
Place the inlet
cover(s) (provided) over the unused inlet(s) and tape
them in place.
CEILING
JOISTS
FRAMING
1. Add framing to ceiling joists as shown.
2. Set ventilator in place and screw to framing with screws
provided. Ventilator may also be hung from joists or
rafters with hanging straps (available separately).
WIRE THE VENTILATOR
WARNING: DISCONNECT POWER AT SERVICE
ENTRANCE AND LOCK OUT SERVICE PANEL TO
PREVENT POWER FROM BEING SWITCHED ON
ACCIDENTALLY.
GROUND
WIRE
BLACK
WHITE
GROUND
(Green or
Bare Wires)
120 VAC
LINE IN
BLACK
BLACK
Use an ON/OFF switch to control the in-line ventilator.
Accessory timers and humidity controls are also available.
1. Remove the wiring adapter plate.
2. Attach power cable to wiring adapter plate using U.L./
CSA approved connector.
3. Connect black to black, white to white, and green or bare
wire to green ground screw.
4. Replace wiring adapter plate. Make sure tab on housing
slides through slot in plate.
WIRING ADAPTER
PLATE
ON/OFF
SWITCH