Braeburn 5000 User Manual

0 (0)

1 Specifications cont.

Premier Series

Programmable Thermostats

MODEL

Single Stage Heat / Cool

5000

7 Day or 5 - 2 Day Programmable

Before Installing, Programming or Operating,

PLEASE READ ALL INSTRUCTIONS

1

Specifications

6

Temperature Adjustment

2

Installation

7

Additional Operation

3

Testing Your New Thermostat

 

Features

8

Battery Replacement

4

Programming User Settings

5

Setting Your Energy

9

Troubleshooting

 

Saving Program

10

Wiring Diagrams

WARNING

Important Safety Information

Always turn off power to the air conditioning or heating system prior to installing, removing, cleaning or servicing thermostat.

This thermostat requires either 24 Volts AC Power or two (2) properly installed “AA” alkaline batteries for normal operation and control of the heating or cooling system.

This thermostat requires two (2) properly installed “AA” alkaline batteries to retain clock setting in the event of loss of AC Power due to a power outage or rolling blackouts when used as a hardwired thermostat.

This thermostat should only be used as described in this manual.Any other use is not recommended and will void the warranty.

1 Specifications

Electrical Rating: 24 Volt AC (18-30 Volt AC) 1 amp maximum load per terminal

3 amp total maximum load (all terminals)

Control Range: 45˚ - 90˚ F (7˚ - 32˚ C)

Accuracy: +/- 1˚ F (+/- .5˚ C)

AC Power: 18-30 Volt AC

DC Power: 3.0 Volt DC (2 AA Alkaline batteries included)

Compatibility: Compatible with low voltage single stage gas, oil or electric heating or cooling systems, including single stage heat pumps. This thermostat can also be used on 250mv to 750mv millivolt heating only systems.

Terminations: Rc, Rh, B, O,Y,W, G, C

2 Installation

Replacing Existing Thermostat

Most thermostats have three parts:

The cover, which may snap or hinge over the existing thermostat.

The electronics or body, which controls the existing system.

The sub-base, where the wires attach through the wall to the existing system.

1.Always turn off power to the air conditioning and heating system prior to removing existing thermostat.

2.Carefully remove the cover and electronics body from the old thermostat sub-base. Depending on the brand, these parts may pull off or need to be unscrewed.The old sub-base should remain wired and on the wall until steps 4 and 5.

3.Label every old wire with the letter of the connection to which the wire is attached. Example letters are R, M, and Y etc. Depending on the brand of the old thermostat, your letters may be different.

4.After labeling the old wires, loosen each connection and remove them from old sub-base. Secure the wires to prevent them from slipping into the hole in the wall.

5.Remove the old sub-base from the wall, again being careful that the wires do not slip into the hole in the wall.

6.Use the chart below to determine the new thermostat connections.As an example, if the old thermostat had a G or F connection, it goes to G on the new thermostat. Using a pencil and the chart below, circle the letter of each wire removed from the old thermostat.

Old Terminal from

New Terminal for

Terminal

Existing Thermostat

New Thermostat

Description

 

 

 

V or RC

Rc

Cooling Transformer

M, 4, Rh or R

Rh

Heating Transformer

B

B

Reversing Valve (Heating)

O

O

Reversing Valve (Cooling)

 

 

 

Y

Y

Cooling Control

H,W or 4

W

Heating Control

 

 

 

G or F

G

Fan Control

C

C

24 Volt AC,Transformer

 

 

Common

 

 

 

NOTE: This thermostat is designed for use with 24 Volt AC low voltage single stage gas, oil or electric heating or cooling systems, including single stage heat pumps. This thermostat can also be used on 250mv to 750mv millivolt heating only systems. Do not use this thermostat on applications with voltages above 30 Volts AC.

1

2 Installation cont.

Installing Your New Thermostat

NOTE: When installing this thermostat in a new location, following a few simple guidelines and the applicable building codes will give the best results. Install the thermostat in a location that provides good airflow by avoiding areas behind doors, near corners, air vents, direct sunlight or heat generating devices. The wiring must conform to all building codes and ordinances as required by local and national code authorities having jurisdiction for this installation.

1.Always turn off the power to the air conditioning and heating system prior to installing this thermostat.

2.Locate the release latch on the bottom (not the back) of the thermostat. Press the release latch in and separate the body from the sub-base of the thermostat.

3.Set the thermostat electronics and cover down on a clean surface. Place the sub-base on the wall in the desired location.

4.Using the slotted mounting holes in the sub-base, mark the placement of the mounting holes through the slots and onto the wall. Insure the wires come out of the wall into the center hole of the sub-base.

5.After verifying the drill will not damage items in the wall, use a 3/16 drill to create the mounting holes. Gently tap the supplied plastic anchors into the holes in the wall.

6.Place the thermostat sub-base against the wall in the desired location. Ensure the thermostat is level, the wires are inserted in the opening, and the mounting holes are aligned with the slots on the sub-base.

7.Fasten sub-base to wall using the supplied screws into the plastic wall anchors.

8.Connect wires to the quick wiring terminal blocks. Use the wiring diagram chart to insure the old and new connections are correct.

9.To prevent electrical shorts and potential damage to the thermostat, make sure all wire connections are secure and not touching each other.

10.Turn the thermostat body over, exposing the rear view of the circuit board.

11.Locate the internal ˚F / ˚C switch on the circuit board. Using your fingers, flip the switch toward the preferred temperature ˚F / ˚C scale.

12.Locate the internal fan option switch, HG (Gas) / HE (Elec) on the circuit board. This switch controls the heating system fan delay. Select gas for gas or oil fired systems. This will allow the furnace to run for a few seconds before starting the fan. Select electric for systems with electric furnace elements that require the fan to come on immediately. Using your finger, flip the switch toward the HG (Gas) or HE (Elec).

13.Locate the internal NORM HP switch on the circuit board. This switch configures the thermostat for normal (NORM) heating and cooling systems or heat pump (HP) systems. Using your fingers, flip the switch toward the NORM or HP.

14.Locate the internal programming switch on the circuit board. This switch configures the programming mode for either 5-2 DAY (weekday-weekend), or full 7 DAY programming. Using your finger, gently flip the switch toward the programming option that best suits your schedule.

15.Ensure the cover is still installed on the thermostat body, and install the unit onto the sub-base. To do so, use the mounting tabs on the top of the sub-base as a guide hinge, and close up the thermostat case by pivoting the body and cover closed. The latch on the bottom of the thermostat will click when the case is properly closed.

16.Flip the front thermostat cover open and open the battery compartment door.

(continued on page 3)

2 Installation cont.

(continued from page 2)

17.Locate the positive [+] ends of the batteries and match them with the positive [+] terminals located in the battery compartment. Install the two new “AA” alkaline batteries (supplied). Close battery compartment door.

18.Restore system power and proceed to Testing Your New Thermostat.

NOTE: If batteries were installed prior to accomplishing steps 10 through 15, you will need to reset the thermostat to register thermostat switch configurations prior to programming any user settings. Gently press the RESET button on the front of the thermostat using a paper clip or a small pencil tip.

3 Testing Your New Thermostat

WARNING! Read BEFORE Testing

Do not short (or jumper) across terminals on the gas valve or at the heating or cooling system control board to test the thermostat installation. This could damage the thermostat and void the warranty.

Do not select COOL mode of operation if the outside temperature is below 50˚ F (10˚ C).This could possibly damage the controlled cooling system and may cause personal injury.

This thermostat includes an automatic compressor protection feature to avoid potential damage to the cooling system from short cycling. This thermostat automatically provides a 5-minute delay after turning off the cooling system output to protect the compressor. This protection is also present in the heat mode of operation on single stage heat pump systems.

NOTE: Test your thermostat prior to programming any user settings. Pressing the RESET button will erase any user entries previously programmed and return them to their default values.

1.Place the system switch in the HEAT position.

2.Press thebutton on the keypad until the set point temperature setting is a minimum of 3 degrees higher than the current room temperature. The heating system should start within several seconds. The fan may not turn on immediately due to the heating system built-in fan delay.

3.Place the system switch in the OFF position. The heating system should stop within several seconds on normal single stage heating or cooling systems. On single stage heat pump systems you must wait 5 minutes for the automatic compressor short cycle protection period to expire, or press the RESET button to bypass this feature for initial testing purposes. Pressing the RESET button will erase any user entries for time of day, day of week, option settings and programming if previously programmed.

4.Place the system switch in the COOL position.

5.Press thebutton on the keypad until the set point temperature is a minimum of 3 degrees lower than the current room temperature.

6.The cooling system should start within several seconds. Place the system switch in the OFF position. The cooling system should stop within a few seconds.

7.Place the fan switch in the ON position. The system blower should start.

8.Place the fan switch in the AUTO position. The system blower should stop.

2

3

Braeburn 5000 User Manual

4 Programming User Settings

Default Thermostat Settings

Function

Status After Reset

 

 

Operation Mode

Normal Operating Mode

Temperature Hold

Extended and Temporary Hold Cleared

 

 

Clock

12:00 p.m., Monday

Room Temperature

70˚ F (21.0˚ C), to be renewed within

 

5 seconds

 

 

Set Point Temperature

According to System Switch

 

62˚ F (17.0˚ C) for Heat and Off

 

83˚ F (28.0˚ C) for Cool

Temperature Scale

˚F or ˚C dependent on switch setting

 

 

Operating Program

DAY program, Monday

Low Battery Warning

Off, to be renewed within 5 seconds

 

 

Temperature Differential

0.5˚ F (0.25˚ C)

Short Cycle Protection Timer

Reset

 

 

Output Relays

Off

Extended Hold

Indefinite

Keypad Lock

Unlocked

Adaptive Recovery Mode

Off

Residual Cooling Fan Delay

60 seconds

Filter Check Monitor

0 days-off

 

 

Setting Current Time of Day and Day of Week

NOTE: It is important for you to set the current time of day (note AM/PM indicator in display), and the current day of week correctly to avoid problems with program execution.

1.When in normal operating mode, press the DAY/TIME keypad button. The LCD display

will be cleared except for the time, am/pm indicator and the day of the week. The hour portion of the time will flash.

2. Press theorbutton to set current hour.

3.Press the DAY/TIME button again, the minute portion of the time will flash.

4.Press theorbutton to set the current minute.

5.Press the DAY/TIME button again. The day of the week indicator will flash.

6.Press theorbutton to set the current day of the week.

7.Press the DAY/TIME button again and the thermostat will return to normal operating mode.

NOTE: The thermostat will return to normal operating mode automatically after 30 seconds if no key is pressed. It will also return to normal operating mode immediately if the RETURN button is pressed.

4 Programming User Settings cont.

Setting Thermostat User Options

The default user options are compatible with most systems and applications. They are normally set at the time of installation and usually do not require modification under normal operating conditions. If you wish to change these settings, simply follow the instructions below.

NOTE: The temperature differential settings are the same for both the heating and cooling systems.

Setting the Temperature Differential

The default setting is 0.5˚ F (0.25˚ C). The

room temperature must change 0.5˚ F (0.25˚ C) from the set point temperature

before the thermostat will call for heating or cooling.

1. In normal operating mode, press and hold the RETURN button for 4 seconds.

The LCD display will show "d1 X", where "X" equals the ˚F / ˚C differential setting. This is the current temperature differential setting.

2.Press theorbutton to set the temperature differential to your desired setting of 0.5˚, 1˚, or 2˚ F (0.3˚, 0.5˚, or 1˚ C).

NOTE: Once you have finished setting the temperature differential you can wait 30 seconds and the thermostat will automatically return to the normal operation mode. Otherwise, you can press the RETURN button again to set the Residual Cooling Fan Delay. When you go directly to the next programming step, it is not necessary to press and hold RETURN for 4 seconds.

Setting Residual Cooling Fan Delay

The default setting is 60 seconds. During the COOL mode of operation, the fan will stay on for 60 seconds after the set point temperature has been satisfied, and the compressor has shut off.

1.In normal operating mode, press and

hold the RETURN button for 4 seconds. Press RETURN again until "FAN XX" is displayed where "XX" is the fan delay time in seconds.

2.Press theorbutton to change the Residual Cooling Fan Delay to the desired setting of 0 (disabled), 30, 60, or 90 seconds.

3.Press the RETURN button again to set the Extended Hold Time or wait 30 seconds for the thermostat to return to the normal mode.

Setting the Extended Hold Time (see section 7)

The default setting is Long (indefinite) Hold. If the HOLD feature is activated, the current set point will be held until HOLD is released.

1.In normal operating mode, press and hold the RETURN button for 4 seconds. Press RETURN repeatedly until "HOLD LG" is displayed where "LG" is indefinite hold. (continued on page 6)

4

5

Loading...
+ 6 hidden pages