Installation
S59-2045
Thermostatic Mixing Valve with
Optional Cabinet
S59-2045RE (with Recess-Mounted
Enamel Cabinet)
S59-2045RS (with Recess-Mounted
Stainless Steel Cabinet)
S59-2045SE (with Surface-Mounted
Enamel Cabinet)
S59-2045SS (with Surface-Mounted
Stainless Steel Cabinet)
ASSE 1017 & UPC Certified
Table of Contents
Supplies Required ............................ 2
Optional Equipment Installation.................. 2
Dimensions ................................. 3
Installation Instructions ........................ 4
Troubleshooting .............................. 6
Inlet Connections: 3/4" NPT
Outlet Connection: 1" NPT
Temperature Range: 85 – 135°F
Maximum Pressure: 125 PSIG
Inlet Temperature Hot: 120 – 200° F
Inlet Temperature Cold: 33 – 80° F
Minimum Temperature Differential
(from valve set point): 20° F
215-1292 Rev. L; ECN 12-09-007
© 2012 Bradley
Page 1 of 8 11/26/2012
P.O. Box 309, Menomonee Falls, WI USA 53052-0309
PHONE 800.BRADLEY (800.272.3539) FAX 262.251.5817
bradleycorp.com

S59-2045 Installation
THIS
SIDE
UP
Packing List
•
•
•
•
IMPORTANT!
Read this entire installation manual to ensure proper installation.
When finished with the installation, file this manual with the owner or
maintenance department. Compliance and conformity to local codes and
ordinances is the responsibility of the installer.
Separate parts from packaging and make sure all parts are accounted
for before discarding packaging material. If any parts are missing, do not
begin installation until you obtain the missing parts.
Make sure that all water supply lines have been flushed and then
completely turned off before beginning installation. Debris in supply lines
can cause valves to malfunction.
Product warranties may be found under “Products” on our web site at
bradleycorp.com.
Supplies recommended for installation
• Lockable shut-off on the outlet if tempered water is supplied to one or more remote fixtures
• Lockable shut-off on the inlets/supplies
• (6) 3/8" wall anchors and fasteners for surface-mounted cabinet
• (4) 1/4" and (2) 3/8” fasteners (and wall anchors, if necessary) for recess-mounted cabinet
• Unions on all connections to facilitate removal of valve
Tools required for temperature adjustment
• 5/32" Allen wrench
• Blade screwdriver
1
Recessed Cabinet:
1. Rough-in wall opening 24-1/2" W x 24-1/2" H.
2. Insert the cabinet and secure to wall with four 1/4" fasteners
3. Install two 3/8” anchors and screws through the valve bracket
4. Install the valve nipples and one-half of the union ball valve
5. Insert the valve into the bracket in the cabinet (right side goes
6. Position the wall flange tight to the wall and caulk in place.
Install Optional Cabinet (If not installing cabinet, skip to Step 2)
Surface-Mounted Cabinet:
1. Measure and mark the cabinet mounting hole
locations at the dimensions shown on next page.
properly anchored (supplied by installer.)
in back of the cabinet into a secure brace (supplied by
installer) or into wall. This will support the valve.
using pipe sealant or teflon tape. Install the other half of the
union ball valve onto inlet and outlet pipe.
in first). Continue with the valve installation procedure.
Install six 3/8" wall anchors (supplied by installer).
2. Position the cabinet onto the wall and secure into
place with six 3/8" wall fasteners (supplied by
installer).
3. Install the valve nipples and one-half of the union ball
valve using pipe sealant or teflon tape. Then install
the other half of the union ball valve onto the inlet and
outlet piping.
4. Insert the valve into the bracket in the cabinet (right
side of the valve goes in first). Continue with the valve
installation procedure.
2 11/26/2012 Bradley • 215-1292 Rev. L; ECN 12-09-007

Installation S59-2045
Side View
Optional Recessed / Surface Mounted Cabinet Dimensions
Front View
22-
3/4"
(578)
Door
26"
(660)
10-1/2"
(267)
Nipple
8-1/2"
(216)
26"
(660)
22-3/4" (578)
Door
Union Ball
Valve
7"
(178)
Wall Flange
5"
(127)
14"
(356)
0.28" Dia. Holes
(4) each side,
(8) Total for
Recess Mount
2"
(51)
2"
(51)
2"
(51)
6-1/2"
(165)
(mm)
1-" NPT Outlet
2" (51)
24"
(610)
2"
(51)
3/4" NPT
Inlets
Bottom View
Mounting Hole Locations
for Surface Mount
20"
(508)
24"
(610)
8-7/16"
(214)
2"
(51)
(51)
6-1/4"
(159)
2"
7-1/2"
(191)
20"
(508)
Wall Opening:
24-1/2" W x 24-1/2" H
0.47 Dia. Holes
(6) Places
Bradley • 215-1292 Rev. L; ECN 12-09-007 11/26/2012 3