Bradley Corporation S59-2045 Installation Manual

Installation
S59-2045
S59-2045RE (with Recess-Mounted Enamel Cabinet)
S59-2045RS (with Recess-Mounted Stainless Steel Cabinet)
S59-2045SE (with Surface-Mounted Enamel Cabinet)
S59-2045SS (with Surface-Mounted Stainless Steel Cabinet)
ASSE 1017 & UPC Certified
Table of Contents
Supplies Required ............................ 2
Optional Equipment Installation.................. 2
Dimensions ................................. 3
Installation Instructions ........................ 4
Troubleshooting .............................. 6
Inlet Connections: 3/4" NPT
Outlet Connection: 1" NPT
Temperature Range: 85 – 135°F
Maximum Pressure: 125 PSIG
Inlet Temperature Hot: 120 – 200° F
Inlet Temperature Cold: 33 – 80° F
Minimum Temperature Differential (from valve set point): 20° F
215-1292 Rev. L; ECN 12-09-007 © 2012 Bradley Page 1 of 8 11/26/2012
P.O. Box 309, Menomonee Falls, WI USA 53052-0309 PHONE 800.BRADLEY (800.272.3539) FAX 262.251.5817
bradleycorp.com
S59-2045 Installation
Installation
THIS SIDE UP
Packing List
IMPORTANT!
Read this entire installation manual to ensure proper installation. When finished with the installation, file this manual with the owner or maintenance department. Compliance and conformity to local codes and ordinances is the responsibility of the installer.
Separate parts from packaging and make sure all parts are accounted for before discarding packaging material. If any parts are missing, do not begin installation until you obtain the missing parts.
Make sure that all water supply lines have been flushed and then completely turned off before beginning installation. Debris in supply lines can cause valves to malfunction.
Product warranties may be found under “Products” on our web site at bradleycorp.com.
Supplies recommended for installation
• Lockable shut-off on the outlet if tempered water is supplied to one or more remote fixtures
• Lockable shut-off on the inlets/supplies
• (6) 3/8" wall anchors and fasteners for surface-mounted cabinet
• (4) 1/4" and (2) 3/8” fasteners (and wall anchors, if necessary) for recess-mounted cabinet
• Unions on all connections to facilitate removal of valve
Tools required for temperature adjustment
• 5/32" Allen wrench
• Blade screwdriver
1
Recessed Cabinet:
1. Rough-in wall opening 24-1/2" W x 24-1/2" H.
2. Insert the cabinet and secure to wall with four 1/4" fasteners
3. Install two 3/8” anchors and screws through the valve bracket
4. Install the valve nipples and one-half of the union ball valve
5. Insert the valve into the bracket in the cabinet (right side goes
6. Position the wall flange tight to the wall and caulk in place.
Install Optional Cabinet (If not installing cabinet, skip to Step 2)
Surface-Mounted Cabinet:
1. Measure and mark the cabinet mounting hole locations at the dimensions shown on next page.
properly anchored (supplied by installer.)
in back of the cabinet into a secure brace (supplied by installer) or into wall. This will support the valve.
using pipe sealant or teflon tape. Install the other half of the union ball valve onto inlet and outlet pipe.
in first). Continue with the valve installation procedure.
Install six 3/8" wall anchors (supplied by installer).
2. Position the cabinet onto the wall and secure into place with six 3/8" wall fasteners (supplied by installer).
3. Install the valve nipples and one-half of the union ball valve using pipe sealant or teflon tape. Then install the other half of the union ball valve onto the inlet and outlet piping.
4. Insert the valve into the bracket in the cabinet (right side of the valve goes in first). Continue with the valve installation procedure.
2 11/26/2012 Bradley • 215-1292 Rev. L; ECN 12-09-007
Installation S59-2045
Side View
Optional Recessed / Surface Mounted Cabinet Dimensions
Front View
22-
3/4"
(578)
Door
26"
(660)
10-1/2"
(267)
Nipple
8-1/2"
(216)
26"
(660)
22-3/4" (578)
Door
Union Ball
Valve
7"
(178)
Wall Flange
5"
(127)
14"
(356)
0.28" Dia. Holes (4) each side,
(8) Total for
Recess Mount
2"
(51)
2"
(51)
2"
(51)
6-1/2"
(165)
(mm)
1-" NPT Outlet
2" (51)
24"
(610)
2"
(51)
3/4" NPT
Inlets
Bottom View
Mounting Hole Locations
for Surface Mount
20"
(508)
24"
(610)
8-7/16"
(214)
2"
(51)
(51)
6-1/4"
(159)
2"
7-1/2"
(191)
20"
(508)
Wall Opening:
24-1/2" W x 24-1/2" H
0.47 Dia. Holes (6) Places
Bradley • 215-1292 Rev. L; ECN 12-09-007 11/26/2012 3