P.O. Box 309, Menomonee Falls, WI USA 53052-0309
PHONE 800.BRADLEY (800.272.3539) FAX 262.251.5817
bradleycorp.com
S19-320EXP120, S19-320EXP220 Installation
DISCONTINUED
IMPORTANT
Installation
R
WI 53051
alls,
HENTLICH ZU
WEEK
WÖC
P.O. Box 309, Menomonee F
DAIRE
e(s) each week and sign
UNIT EACH
y malfunctions immediatel
hentlich im
TEST THIS
hrift. Jeglic
DIESES GERÄT 1ST
ESSAI HEBDOMA
Test-operate valv
Report an
Ventil(e) wöc
t immédiatement.
durch Untersc
Test le fonctionnement des v
signe en bas. S'il y à quelqu
un rappor
Date
Datum
Date
114-051
PRÜFEN.
Testbetrieb prüfen,
he Störung sofor
Signed
Unterschrift
below.
bestätigt
t melden.
y.
alves chaque semaine et
e chose qui ne v
Date Signed
Signe
THIS
SIDE
UP
a pas fait
Signed
Signed
Date
Date
P.O. BOX 309, MENOMONEE FALLS, WI 53052-0309 USA
TEL: 1-800-BRADLEY FAX: (262-251-5817)
http://www.bradleycorp.com
Read this installation manual completely to ensure proper installation, then file it
with the owner or maintenance department. Compliance and conformity to drain
requirements and other local codes and ordinances is the responsibility of the installer.
Separate parts from packaging and make sure all parts are accounted for before
Packing List
•
•
•
discarding any packaging material. If any parts are missing, do not begin installation
•
until you obtain the missing parts.
Flush the water supply lines before beginning installation and after installation is
complete. Test the unit for leaks and adequate water flow. Main water supply to the
eyewash should be “ON” at all times. Provisions shall be made to prevent unauthorized
shutoff.
The ANSI Z358.1 standard requires an uninterruptible supply of flushing fluid at a
minimum 30 PSI (0.21 MPa) flowing pressure. Flushing fluid should be tepid per ANSI
Z358.1.
The inspection and testing results of this equipment should be recorded weekly to verify
proper operation. This equipment should be inspected annually to ensure compliance
with ANSI Z358.1.
Workers who may come in contact with potentially hazardous materials should be
trained regarding the placement and proper operation of emergency equipment per ANSI
Z358.1.
For questions regarding the operation or installation of this product, visit www.
bradleycorp.com or call 1-800-BRADLEY.
Product warranties and parts information may also be found under ”Products” on our
web site at www.bradleycorp.com.
NOTE: If the alarm system is ordered with the model S19-300T or S19-300B Heat Trace Shower and Eye
Wash, the mounting bracket will be attached to the unit.
STROBE LIGHT
269-1305 (120V)
269-1305A (220/240V)
JUNCTION
BOX
269-1314
CONDUIT
CONNECTOR
269-1308
TO POWER
SUPPLY
PIPE PLUG
269-1294
NIPPLE
269-1316
HORN
269-1306
NIPPLE
269-1342
MOUNTING BRACKET
ASSEMBLY
S70-156
U-BOLT (qty. 2)
269-587
NUT (qty. 4)
161-065
FLEXIBLE
CONDUIT
269-1588
TO FLOW
SWITCH
CUT-OUT
SWITCH BOX
269-1928
Parts not shown:
Supplies required for installation:
CONDUIT
CONNECTOR
269-1308
JUNCTION
BOX
269-1312
FLOW
SWITCH
269-1421
Bradley Corporation •
215-1083 Rev. H; ECM 10-05-011B 4/12/11
3
S19-320EXP120, S19-320EXP220 Installation
DISCONTINUED
Installation
IMPORTANT: Power should be supplied
to the alarm by no larger than a 15 amp
branch circuit with a dedicated circuit
breaker or fuse and should not supply
power to any other device. Compliance
and conformity to local codes and
ordinances is the responsibility of the
installer.
Step 1: Install the flow switch in the water
supply line
NOTE: Because the flow switch will attach to the
mounted alarm via a 7-foot waterproof cable, the
installer must keep the location for mounting the
alarm in mind when choosing the flow switch location (see Figure 1).
1. Choose a location for mounting the flow
switch in a horizontal run of the water supply
line. The inlet and outlet ports of the flow
switch must be a minimum of 6 inches from
any tees or elbows in the water supply line
(see Figure 1).
NOTE: If the water supply line will be exposed to
temperatures at or below freezing, the inlet supply
must be freeze-protected 6 inches above the flow
switch tee (freeze protection by others).
TOP SUPPLY
JUNCTION
BOX
120 VAC
POWER
SUPPLY
INLET
ALARM
SYSTEM
WATERPROOF
CABLE
2. Mount the flow switch assembly in the water
supply line.
position with the water pipe in the
horizontal position.
marked by the arrow on the flow switch
body.
(supplied by installer) on all water pipe
connections.
NOTE: The alarm system is designed to work properly even if both the eyewash and drench shower are
used simultaneously. The alarm will continue to
operate as long as either the eye wash or drench
shower is still in use.
1. Choose a location for mounting the alarm assembly. The alarm should be mounted at least 7 feet
above ground level for best visibility.
hardware (see Figure 1 on page 4).
installation is NOT supplied).
Step 3: Make electrical connections—alarm to flow switch
1. Connect the flow switch to the alarm by installing a conduit connector to the end of the 7-foot
waterproof cable and into the flow switch junction box (see Figure 1 on page 4 and Figure 2
below).
NOTE: The cable may be cut to any length required.
NOTE: To prevent water condensation from dripping onto the flow switch, make sure the cable is not
taut.
NOTE: Refer to the instruction manual supplied with the conduit connector for assembly information.
Step 4: Complete electrical supply connections
1. Connect the alarm system to the power source using the shorter length of waterproof cable.
2. Follow the same procedure as in Step
3 for completing the electrical supply connection.
Figure 2
WHITE
BLACK
BLACKBLACK
WHITE
GREEN
PUSH BUTTON
ALARM LIGHT
GREEN
BLACK
RED (NOT USED)
BLUE
GREEN (GROUND)
BLACK
RED
GREEN
(GROUND)
BLACK
BLUE (NOT USED)
BLACK
POWER IN
RED
BLUE
BLUE
RED
BLACK
REMOTE
LOCATION
SENSING
FLOW
SWITCH
Bradley Corporation •
215-1083 Rev. H; ECM 10-05-011B 4/12/11
5
S19-320EXP120, S19-320EXP220 Installation
DISCONTINUED
Installation
Step 5: Test the alarm system
NOTE: Testing the alarm for the first time using the drench shower may expose the flow switch to an
unnecessary water hammer since the downstream piping may be empty of water. The flow switch is designed to
withstand such a water hammer, but using the smaller eye wash flow is recommended. Refer to Figure 3 when
testing the alarm system.
1. Apply power to the alarm branch circuit. The alarm should remain off.
2. Make sure the alarm horn cut-out switch is in the “ON” position (pull the button out).
3. Open the eye wash valve. The alarm should sound and the strobelight flash shortly after water flows
from the system.
4. Use the alarm horn cut-off switch to silence the horn. Pushing the button should shut off the horn but
allow the strobelight to keep flashing.
5. Shut off the eye wash flow valve. The strobelight should stop flashing.
6. Reset the alarm horn cut-out switch by pulling the button out.
7. Repeat the tests in procedures 1-6 above, this time using the drench shower only.